L15-01-RECEPTION/COLLAB.
1. General Details:
Floor Area ......................................................... 178.0 m²
Avg. Ceiling Height ............................................... 3.0 m
Building Weight ................................................. 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ....................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s/person
OA Requirement 2 .............................................. 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type .......................... Recessed (Unvented) Occupancy ........................................................... 17.0 People
Wattage ............................................................. 12.00 W/m² Activity Level .......................................... Office Work
Ballast Multiplier .................................................. 1.00 Sensible ............................................................... 71.8 W/person
Schedule ...................................................... Lighting Latent ................................................................... 60.1 W/person
Schedule ......................................................... People
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
S 49.7 26 0 0
ESE 10.0 5 0 0
SSW 10.0 4 0 0
ESE 28.0 13 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling .................................................... 0.20 ACH
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
1. General Details:
Floor Area ........................................................... 71.5 m²
Avg. Ceiling Height ............................................... 3.0 m
Building Weight ................................................. 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ....................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s/person
OA Requirement 2 .............................................. 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type .......................... Recessed (Unvented) Occupancy ............................................................. 7.0 People
Wattage ............................................................. 12.00 W/m² Activity Level .......................................... Office Work
Ballast Multiplier .................................................. 1.00 Sensible ............................................................... 71.8 W/person
Schedule ...................................................... Lighting Latent ................................................................... 60.1 W/person
Schedule ......................................................... People
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling .................................................... 0.00 ACH
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
1. General Details:
Floor Area ......................................................... 121.0 m²
Avg. Ceiling Height ............................................... 3.0 m
Building Weight ................................................. 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ....................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s/person
OA Requirement 2 .............................................. 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type .......................... Recessed (Unvented) Occupancy ........................................................... 15.0 People
Wattage ............................................................. 12.00 W/m² Activity Level .......................................... Office Work
Ballast Multiplier .................................................. 1.00 Sensible ............................................................... 71.8 W/person
Schedule ...................................................... Lighting Latent ................................................................... 60.1 W/person
Schedule ......................................................... People
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 47.0 22 0 0
NNE 22.2 12 0 0
NNE 5.6 4 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling .................................................... 0.20 ACH
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
1. General Details:
Floor Area ......................................................... 220.0 m²
Avg. Ceiling Height ............................................... 3.0 m
Building Weight ................................................. 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ....................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s/person
OA Requirement 2 .............................................. 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type .......................... Recessed (Unvented) Occupancy ........................................................... 44.0 People
Wattage ............................................................. 12.00 W/m² Activity Level .......................................... Office Work
Ballast Multiplier .................................................. 1.00 Sensible ............................................................... 71.8 W/person
Schedule ...................................................... Lighting Latent ................................................................... 60.1 W/person
Schedule ......................................................... People
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WNW 22.5 18 0 0
WNW 78.7 36 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling .................................................... 0.20 ACH
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
1. General Details:
Floor Area ......................................................... 115.5 m²
Avg. Ceiling Height ............................................... 3.0 m
Building Weight ................................................. 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ....................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s/person
OA Requirement 2 .............................................. 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type .......................... Recessed (Unvented) Occupancy ........................................................... 18.0 People
Wattage ............................................................. 12.00 W/m² Activity Level .......................................... Office Work
Ballast Multiplier .................................................. 1.00 Sensible ............................................................... 71.8 W/person
Schedule ...................................................... Lighting Latent ................................................................... 60.1 W/person
Schedule ......................................................... People
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WNW 45.0 36 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling .................................................... 0.20 ACH
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
1. General Details:
Floor Area ......................................................... 102.5 m²
Avg. Ceiling Height ............................................... 3.0 m
Building Weight ................................................. 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ....................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s/person
OA Requirement 2 .............................................. 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type .......................... Recessed (Unvented) Occupancy ........................................................... 18.0 People
Wattage ............................................................. 12.00 W/m² Activity Level .......................................... Office Work
Ballast Multiplier .................................................. 1.00 Sensible ............................................................... 71.8 W/person
Schedule ...................................................... Lighting Latent ................................................................... 60.1 W/person
Schedule ........... MEETING ROOM PEOPLE & EQP
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WNW 50.0 40 0 0
S 33.8 27 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling .................................................... 0.20 ACH
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
L15-09 OFFICE
1. General Details:
Floor Area ........................................................... 34.0 m²
Avg. Ceiling Height ............................................... 3.0 m
Building Weight ................................................. 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ....................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s/person
OA Requirement 2 .............................................. 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type .......................... Recessed (Unvented) Occupancy ............................................................. 9.0 People
Wattage ............................................................. 12.00 W/m² Activity Level .......................................... Office Work
Ballast Multiplier .................................................. 1.00 Sensible ............................................................... 71.8 W/person
Schedule ...................................................... Lighting Latent ................................................................... 60.1 W/person
Schedule ......................................................... People
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WNW 33.8 16 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling .................................................... 0.20 ACH
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
1. General Details:
Floor Area ........................................................... 13.5 m²
Avg. Ceiling Height ............................................... 3.0 m
Building Weight ................................................. 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ....................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s/person
OA Requirement 2 .............................................. 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type .......................... Recessed (Unvented) Occupancy ............................................................. 2.0 People
Wattage ............................................................. 12.00 W/m² Activity Level .......................................... Office Work
Ballast Multiplier .................................................. 1.00 Sensible ............................................................... 71.8 W/person
Schedule ...................................................... Lighting Latent ................................................................... 60.1 W/person
Schedule ......................................................... People
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling .................................................... 0.00 ACH
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
1. General Details:
Floor Area ........................................................... 86.0 m²
Avg. Ceiling Height ............................................... 3.0 m
Building Weight ................................................. 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ....................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s/person
OA Requirement 2 .............................................. 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type .......................... Recessed (Unvented) Occupancy ........................................................... 13.0 People
Wattage ............................................................. 12.00 W/m² Activity Level .......................................... Office Work
Ballast Multiplier .................................................. 1.00 Sensible ............................................................... 71.8 W/person
Schedule ...................................................... Lighting Latent ................................................................... 60.1 W/person
Schedule ......................................................... People
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNE 34.3 28 0 0
WNW 37.0 26 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling .................................................... 0.20 ACH
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
1. General Details:
Floor Area ............................................................. 9.0 m²
Avg. Ceiling Height ............................................... 4.2 m
Building Weight ................................................. 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ....................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s/person
OA Requirement 2 .............................................. 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type .......................... Recessed (Unvented) Occupancy ............................................................. 1.0 Person
Wattage ............................................................. 12.00 W/m² Activity Level .......................................... Office Work
Ballast Multiplier .................................................. 1.00 Sensible ............................................................... 71.8 W/person
Schedule ...................................................... Lighting Latent ................................................................... 60.1 W/person
Schedule .......................................... EXERCISE RM.
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNE 11.3 9 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling .................................................... 0.20 ACH
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
1. General Details:
Floor Area ........................................................... 31.0 m²
Avg. Ceiling Height ............................................... 3.0 m
Building Weight ................................................. 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ....................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s/person
OA Requirement 2 .............................................. 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type .......................... Recessed (Unvented) Occupancy ............................................................. 9.0 People
Wattage ............................................................. 12.00 W/m² Activity Level .......................................... Office Work
Ballast Multiplier .................................................. 1.00 Sensible ............................................................... 71.8 W/person
Schedule ...................................................... Lighting Latent ................................................................... 60.1 W/person
Schedule ...................................................... Lighting
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 32.0 15 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling .................................................... 0.20 ACH
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
1. General Details:
Floor Area ........................................................... 47.5 m²
Avg. Ceiling Height ............................................... 3.0 m
Building Weight ................................................. 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ....................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s/person
OA Requirement 2 .............................................. 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type .......................... Recessed (Unvented) Occupancy ........................................................... 16.0 People
Wattage ............................................................. 12.00 W/m² Activity Level .......................................... Office Work
Ballast Multiplier .................................................. 1.00 Sensible ............................................................... 71.8 W/person
Schedule ...................................................... Lighting Latent ................................................................... 60.1 W/person
Schedule ...................................................... Lighting
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ESE 36.6 17 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling .................................................... 0.20 ACH
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
1. General Details:
Floor Area ........................................................... 47.5 m²
Avg. Ceiling Height ............................................... 3.0 m
Building Weight ................................................. 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ....................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s/person
OA Requirement 2 .............................................. 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type .......................... Recessed (Unvented) Occupancy ........................................................... 16.0 People
Wattage ............................................................. 12.00 W/m² Activity Level .......................................... Office Work
Ballast Multiplier .................................................. 1.00 Sensible ............................................................... 71.8 W/person
Schedule ...................................................... Lighting Latent ................................................................... 60.1 W/person
Schedule ........... MEETING ROOM PEOPLE & EQP
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ESE 22.4 10 0 0
ESE 11.3 9 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling .................................................... 0.20 ACH
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
1. General Details:
Floor Area ........................................................... 24.4 m²
Avg. Ceiling Height ............................................... 3.0 m
Building Weight ................................................. 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ....................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s/person
OA Requirement 2 .............................................. 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type .......................... Recessed (Unvented) Occupancy ............................................................. 8.0 People
Wattage ............................................................. 12.00 W/m² Activity Level .......................................... Office Work
Ballast Multiplier .................................................. 1.00 Sensible ............................................................... 71.8 W/person
Schedule ...................................................... Lighting Latent ................................................................... 60.1 W/person
Schedule ........... MEETING ROOM PEOPLE & EQP
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ESE 16.7 13 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling .................................................... 0.20 ACH
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
1. General Details:
Floor Area ........................................................... 24.0 m²
Avg. Ceiling Height ............................................... 3.0 m
Building Weight ................................................. 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ....................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s/person
OA Requirement 2 .............................................. 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type .......................... Recessed (Unvented) Occupancy ............................................................. 8.0 People
Wattage ............................................................. 12.00 W/m² Activity Level .......................................... Office Work
Ballast Multiplier .................................................. 1.00 Sensible ............................................................... 71.8 W/person
Schedule ...................................................... Lighting Latent ................................................................... 60.1 W/person
Schedule ........... MEETING ROOM PEOPLE & EQP
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ESE 16.8 13 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling .................................................... 0.20 ACH
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
1. General Details:
Floor Area ........................................................... 47.0 m²
Avg. Ceiling Height ............................................... 3.0 m
Building Weight ................................................. 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ....................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s/person
OA Requirement 2 .............................................. 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type .......................... Recessed (Unvented) Occupancy ........................................................... 16.0 People
Wattage ............................................................. 12.00 W/m² Activity Level .......................................... Office Work
Ballast Multiplier .................................................. 1.00 Sensible ............................................................... 71.8 W/person
Schedule ...................................................... Lighting Latent ................................................................... 60.1 W/person
Schedule ........... MEETING ROOM PEOPLE & EQP
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ESE 16.9 13 0 0
ESE 17.0 8 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling .................................................... 0.20 ACH
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
1. General Details:
Floor Area ............................................................. 7.5 m²
Avg. Ceiling Height ............................................... 3.0 m
Building Weight ................................................. 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ....................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s/person
OA Requirement 2 .............................................. 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type .......................... Recessed (Unvented) Occupancy ............................................................. 1.0 Person
Wattage ............................................................. 12.00 W/m² Activity Level .......................................... Office Work
Ballast Multiplier .................................................. 1.00 Sensible ............................................................... 71.8 W/person
Schedule ...................................................... Lighting Latent ................................................................... 60.1 W/person
Schedule ...................................... Store RM. People
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling .................................................... 0.00 ACH
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
L15-24 1P ROOM
1. General Details:
Floor Area ............................................................. 7.0 m²
Avg. Ceiling Height ............................................... 3.0 m
Building Weight ................................................. 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ....................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s/person
OA Requirement 2 .............................................. 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type .......................... Recessed (Unvented) Occupancy ............................................................. 1.0 Person
Wattage ............................................................. 12.00 W/m² Activity Level .......................................... Office Work
Ballast Multiplier .................................................. 1.00 Sensible ............................................................... 71.8 W/person
Schedule ...................................................... Lighting Latent ................................................................... 60.1 W/person
Schedule ......................................................... People
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling .................................................... 0.00 ACH
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
1. General Details:
Floor Area ........................................................... 22.0 m²
Avg. Ceiling Height ............................................... 3.0 m
Building Weight ................................................. 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ....................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s/person
OA Requirement 2 .............................................. 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type .......................... Recessed (Unvented) Occupancy ............................................................. 6.0 People
Wattage ............................................................. 12.00 W/m² Activity Level .......................................... Office Work
Ballast Multiplier .................................................. 1.00 Sensible ............................................................... 71.8 W/person
Schedule ...................................................... Lighting Latent ................................................................... 60.1 W/person
Schedule ........... MEETING ROOM PEOPLE & EQP
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling .................................................... 0.00 ACH
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
1. General Details:
Floor Area ............................................................. 8.5 m²
Avg. Ceiling Height ............................................... 3.0 m
Building Weight ................................................. 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ....................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s/person
OA Requirement 2 .............................................. 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type .......................... Recessed (Unvented) Occupancy ............................................................. 4.0 People
Wattage ............................................................. 12.00 W/m² Activity Level .......................................... Office Work
Ballast Multiplier .................................................. 1.00 Sensible ............................................................... 71.8 W/person
Schedule ...................................................... Lighting Latent ................................................................... 60.1 W/person
Schedule ........... MEETING ROOM PEOPLE & EQP
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling .................................................... 0.00 ACH
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
1. General Details:
Floor Area ........................................................... 18.0 m²
Avg. Ceiling Height ............................................... 3.0 m
Building Weight ................................................. 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ....................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s/person
OA Requirement 2 .............................................. 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type .......................... Recessed (Unvented) Occupancy ............................................................. 3.0 People
Wattage ............................................................. 12.00 W/m² Activity Level .......................................... Office Work
Ballast Multiplier .................................................. 1.00 Sensible ............................................................... 71.8 W/person
Schedule ...................................................... Lighting Latent ................................................................... 60.1 W/person
Schedule ......................................................... People
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling .................................................... 0.00 ACH
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
1. General Details:
Floor Area ........................................................... 12.0 m²
Avg. Ceiling Height ............................................... 3.0 m
Building Weight ................................................. 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ....................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s/person
OA Requirement 2 .............................................. 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type .......................... Recessed (Unvented) Occupancy ............................................................. 3.0 People
Wattage ............................................................. 12.00 W/m² Activity Level .......................................... Office Work
Ballast Multiplier .................................................. 1.00 Sensible ............................................................... 71.8 W/person
Schedule ...................................................... Lighting Latent ................................................................... 60.1 W/person
Schedule ......................................................... People
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling .................................................... 0.00 ACH
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
1. General Details:
Floor Area ........................................................... 19.0 m²
Avg. Ceiling Height ............................................... 3.0 m
Building Weight ................................................. 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ....................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s/person
OA Requirement 2 .............................................. 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type .......................... Recessed (Unvented) Occupancy ............................................................. 6.0 People
Wattage ............................................................. 12.00 W/m² Activity Level .......................................... Office Work
Ballast Multiplier .................................................. 1.00 Sensible ............................................................... 71.8 W/person
Schedule ...................................................... Lighting Latent ................................................................... 60.1 W/person
Schedule ........... MEETING ROOM PEOPLE & EQP
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling .................................................... 0.00 ACH
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
1. General Details:
Floor Area ........................................................... 22.3 m²
Avg. Ceiling Height ............................................... 3.0 m
Building Weight ................................................. 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ....................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s/person
OA Requirement 2 .............................................. 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type .......................... Recessed (Unvented) Occupancy ............................................................. 9.0 People
Wattage ............................................................. 12.00 W/m² Activity Level .......................................... Office Work
Ballast Multiplier .................................................. 1.00 Sensible ............................................................... 71.8 W/person
Schedule ...................................................... Lighting Latent ................................................................... 60.1 W/person
Schedule ........... MEETING ROOM PEOPLE & EQP
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling .................................................... 0.00 ACH
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
1. General Details:
Floor Area ........................................................... 13.0 m²
Avg. Ceiling Height ............................................... 3.0 m
Building Weight ................................................. 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ....................................... User-Defined
OA Requirement 1 ................................................ 0.0 L/s/person
OA Requirement 2 .............................................. 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type .......................... Recessed (Unvented) Occupancy ............................................................. 2.0 People
Wattage ............................................................. 12.00 W/m² Activity Level .......................................... Office Work
Ballast Multiplier .................................................. 1.00 Sensible ............................................................... 71.8 W/person
Schedule ...................................................... Lighting Latent ................................................................... 60.1 W/person
Schedule ................................ Tea Point Equipment
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling .................................................... 0.00 ACH
Design Heating ................................................... 0.00 L/s
Energy Analysis .................................................. 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).