You are on page 1of 62

Date:

9/23/2019

0388 SFN 5640 J 003 A - Control Building Illumination System Calculation


0388 SFN 5640 J 003 A - Control Building 9/23/2019
Illumination System Calculation
0388 SFN 5640 J 003 A - Control Building Illumination System Calculation / Table of contents

Table of contents
0388 SFN 5640 J 003 A - Control Building Illumination System Calculation
San Francisco Control Building
Building 1
Ground Floor
Cable Gallery
Views............................................................................................................................................................................. 5
Cable Gallery / Perpendicular illuminance (adaptive).................................................................................................... 6
Staircase (1st floor)
Views............................................................................................................................................................................. 7
Workplane (Staircase (1st floor)) / Perpendicular illuminance (adaptive)...................................................................... 8
Staircase (1st to 2nd floor)
Views........................................................................................................................................................................... 10
Workplane (Staircase (1st to 2nd floor)) / Perpendicular illuminance (adaptive)......................................................... 11
Second Floor
Auxillary Room
Views........................................................................................................................................................................... 12
Auxillary Room / Perpendicular illuminance (adaptive)................................................................................................13
Battery Room
Views........................................................................................................................................................................... 15
Battery Room / Perpendicular illuminance (adaptive)..................................................................................................16
Computer Room
Views........................................................................................................................................................................... 18
Computer Room / Perpendicular illuminance (adaptive)............................................................................................. 19
Conference Area
Views........................................................................................................................................................................... 21
Conference Area / Perpendicular illuminance (adaptive).............................................................................................22
Control Room
Views........................................................................................................................................................................... 24
Control Room / Perpendicular illuminance (adaptive)..................................................................................................25
Guard Area
Views........................................................................................................................................................................... 27
Workplane (Guard Area) / Perpendicular illuminance (adaptive).................................................................................28
Hall
Views........................................................................................................................................................................... 30
Workplane (Hall) / Perpendicular illuminance (adaptive)............................................................................................. 31
He
Views........................................................................................................................................................................... 33
He / Perpendicular illuminance (adaptive)................................................................................................................... 34
Operator's Quarter (Female)
Views........................................................................................................................................................................... 36
Operator's Quarter / Perpendicular illuminance (adaptive)..........................................................................................37
Operator's Quarter (Male)
Views........................................................................................................................................................................... 39
Workplane (Operator's Quarter (Male)) / Perpendicular illuminance (adaptive).......................................................... 40
Pantry
Views........................................................................................................................................................................... 41
Pantry / Perpendicular illuminance (adaptive)............................................................................................................. 42
Records Room
Views........................................................................................................................................................................... 44
Records Room / Perpendicular illuminance (adaptive)................................................................................................45
Relay and Communication Room
Views........................................................................................................................................................................... 46
Relay and Communication Room / Perpendicular illuminance (adaptive)................................................................... 47
She
Views........................................................................................................................................................................... 49
She / Perpendicular illuminance (adaptive)................................................................................................................. 50

Page 3
0388 SFN 5640 J 003 A - Control Building 9/23/2019
Illumination System Calculation
0388 SFN 5640 J 003 A - Control Building Illumination System Calculation / Table of contents

Shower
Views........................................................................................................................................................................... 52
Workplane (Shower) / Perpendicular illuminance (adaptive)....................................................................................... 53
Staircase (2nd to Roof Deck)
Views........................................................................................................................................................................... 55
Workplane (Staircase (2nd to Roof Deck)) / Perpendicular illuminance (adaptive)..................................................... 56
Roof Deck
Mechanical Room
Views........................................................................................................................................................................... 57
Mechanical Room / Perpendicular illuminance (adaptive)........................................................................................... 58
Staircase (Roof Deck)
Views........................................................................................................................................................................... 60
Workplane (Staircase (Roof Deck)) / Perpendicular illuminance (adaptive)................................................................ 61

Page 4
0388 SFN 5640 J 003 A - Control Building 9/23/2019
Illumination System Calculation
San Francisco Control Building / Building 1 / Ground Floor / Cable Gallery / Views

Cable Gallery

Cable Gallery

Page 5
0388 SFN 5640 J 003 A - Control Building 9/23/2019
Illumination System Calculation
San Francisco Control Building / Building 1 / Ground Floor / Cable Gallery / Cable Gallery / Perpendicular illuminance
(adaptive)

Cable Gallery / Perpendicular illuminance (adaptive)

Cable Gallery: Perpendicular illuminance (adaptive) (Surface)


Light scene: Light scene 1
Average: 185 lx (Target: ≥ 100 lx), Min: 37.4 lx, Max: 304 lx, Min/average: 0.20, Min/max: 0.12
Height: 0.800 m, Wall zone: 0.000 m

Isolines [lx]

Scale: 1 : 300

False colours [lx]

Scale: 1 : 300

Value grid [lx]

Scale: 1 : 300

Page 6
0388 SFN 5640 J 003 A - Control Building 9/23/2019
Illumination System Calculation
San Francisco Control Building / Building 1 / Ground Floor / Staircase (1st floor) / Views

Staircase (1st floor)

Staircase (1st Floor)

Page 7
0388 SFN 5640 J 003 A - Control Building 9/23/2019
Illumination System Calculation
San Francisco Control Building / Building 1 / Ground Floor / Staircase (1st floor) / Workplane (Staircase (1st floor)) /
Perpendicular illuminance (adaptive)

Workplane (Staircase (1st floor)) / Perpendicular illuminance


(adaptive)

Workplane (Staircase (1st floor)): Perpendicular illuminance (adaptive) (Surface)


Light scene: Light scene 1
Average: 143 lx (Target: ≥ 100 lx), Min: 77.1 lx, Max: 192 lx, Min/average: 0.54, Min/max: 0.40
Height: 0.800 m, Wall zone: 0.000 m

Isolines [lx]

Scale: 1 : 50

Page 8
0388 SFN 5640 J 003 A - Control Building 9/23/2019
Illumination System Calculation
San Francisco Control Building / Building 1 / Ground Floor / Staircase (1st floor) / Workplane (Staircase (1st floor)) /
Perpendicular illuminance (adaptive)

False colours [lx]

Scale: 1 : 50

Value grid [lx]

Scale: 1 : 50

Page 9
0388 SFN 5640 J 003 A - Control Building 9/23/2019
Illumination System Calculation
San Francisco Control Building / Building 1 / Ground Floor / Staircase (1st to 2nd floor) / Views

Staircase (1st to 2nd floor)

Staircase (1st to 2nd Floor Platform)

Page 10
0388 SFN 5640 J 003 A - Control Building 9/23/2019
Illumination System Calculation
San Francisco Control Building / Building 1 / Ground Floor / Staircase (1st to 2nd floor) / Workplane (Staircase (1st to
2nd floor)) / Perpendicular illuminance (adaptive)

Workplane (Staircase (1st to 2nd floor)) / Perpendicular illuminance


(adaptive)

Workplane (Staircase (1st to 2nd floor)): Perpendicular illuminance (adaptive) (Surface)


Light scene: Light scene 1
Average: 107 lx (Target: ≥ 100 lx), Min: 77.2 lx, Max: 120 lx, Min/average: 0.72, Min/max: 0.64
Height: 0.800 m, Wall zone: 0.000 m

Isolines [lx]

Scale: 1 : 40

False colours [lx]

Scale: 1 : 40

Value grid [lx]

Scale: 1 : 40

Page 11
0388 SFN 5640 J 003 A - Control Building 9/23/2019
Illumination System Calculation
San Francisco Control Building / Building 1 / Second Floor / Auxillary Room / Views

Auxillary Room

Auxillary Room

Page 12
0388 SFN 5640 J 003 A - Control Building 9/23/2019
Illumination System Calculation
San Francisco Control Building / Building 1 / Second Floor / Auxillary Room / Auxillary Room / Perpendicular
illuminance (adaptive)

Auxillary Room / Perpendicular illuminance (adaptive)

Auxillary Room: Perpendicular illuminance (adaptive) (Surface)


Light scene: Light scene 1
Average: 217 lx (Target: ≥ 200 lx), Min: 0.000 lx, Max: 365 lx, Min/average: 0.00, Min/max: 0.00
Height: 0.800 m, Wall zone: 0.000 m

Isolines [lx]

Scale: 1 : 75

Page 13
0388 SFN 5640 J 003 A - Control Building 9/23/2019
Illumination System Calculation
San Francisco Control Building / Building 1 / Second Floor / Auxillary Room / Auxillary Room / Perpendicular
illuminance (adaptive)

False colours [lx]

Scale: 1 : 75

Value grid [lx]

Scale: 1 : 75

Page 14
0388 SFN 5640 J 003 A - Control Building 9/23/2019
Illumination System Calculation
San Francisco Control Building / Building 1 / Second Floor / Battery Room / Views

Battery Room

Battery Room

Page 15
0388 SFN 5640 J 003 A - Control Building 9/23/2019
Illumination System Calculation
San Francisco Control Building / Building 1 / Second Floor / Battery Room / Battery Room / Perpendicular illuminance
(adaptive)

Battery Room / Perpendicular illuminance (adaptive)

Battery Room: Perpendicular illuminance (adaptive) (Surface)


Light scene: Light scene 1
Average: 293 lx (Target: ≥ 200 lx), Min: 195 lx, Max: 344 lx, Min/average: 0.67, Min/max: 0.57
Height: 0.800 m, Wall zone: 0.000 m

Isolines [lx]

Scale: 1 : 75

Page 16
0388 SFN 5640 J 003 A - Control Building 9/23/2019
Illumination System Calculation
San Francisco Control Building / Building 1 / Second Floor / Battery Room / Battery Room / Perpendicular illuminance
(adaptive)

False colours [lx]

Scale: 1 : 75

Value grid [lx]

Scale: 1 : 75

Page 17
0388 SFN 5640 J 003 A - Control Building 9/23/2019
Illumination System Calculation
San Francisco Control Building / Building 1 / Second Floor / Computer Room / Views

Computer Room

Computer Room

Page 18
0388 SFN 5640 J 003 A - Control Building 9/23/2019
Illumination System Calculation
San Francisco Control Building / Building 1 / Second Floor / Computer Room / Computer Room / Perpendicular
illuminance (adaptive)

Computer Room / Perpendicular illuminance (adaptive)

Computer Room: Perpendicular illuminance (adaptive) (Surface)


Light scene: Light scene 1
Average: 440 lx (Target: ≥ 400 lx), Min: 327 lx, Max: 494 lx, Min/average: 0.74, Min/max: 0.66
Height: 0.800 m, Wall zone: 0.000 m

Isolines [lx]

Scale: 1 : 50

Page 19
0388 SFN 5640 J 003 A - Control Building 9/23/2019
Illumination System Calculation
San Francisco Control Building / Building 1 / Second Floor / Computer Room / Computer Room / Perpendicular
illuminance (adaptive)

False colours [lx]

Scale: 1 : 50

Value grid [lx]

Scale: 1 : 50

Page 20
0388 SFN 5640 J 003 A - Control Building 9/23/2019
Illumination System Calculation
San Francisco Control Building / Building 1 / Second Floor / Conference Area / Views

Conference Area

Conference Area

Page 21
0388 SFN 5640 J 003 A - Control Building 9/23/2019
Illumination System Calculation
San Francisco Control Building / Building 1 / Second Floor / Conference Area / Conference Area / Perpendicular
illuminance (adaptive)

Conference Area / Perpendicular illuminance (adaptive)

Conference Area: Perpendicular illuminance (adaptive) (Surface)


Light scene: Light scene 1
Average: 336 lx (Target: ≥ 300 lx), Min: 174 lx, Max: 428 lx, Min/average: 0.52, Min/max: 0.41
Height: 0.800 m, Wall zone: 0.000 m

Isolines [lx]

Scale: 1 : 50

Page 22
0388 SFN 5640 J 003 A - Control Building 9/23/2019
Illumination System Calculation
San Francisco Control Building / Building 1 / Second Floor / Conference Area / Conference Area / Perpendicular
illuminance (adaptive)

False colours [lx]

Scale: 1 : 50

Value grid [lx]

Scale: 1 : 50

Page 23
0388 SFN 5640 J 003 A - Control Building 9/23/2019
Illumination System Calculation
San Francisco Control Building / Building 1 / Second Floor / Control Room / Views

Control Room

Control Room

Page 24
0388 SFN 5640 J 003 A - Control Building 9/23/2019
Illumination System Calculation
San Francisco Control Building / Building 1 / Second Floor / Control Room / Control Room / Perpendicular illuminance
(adaptive)

Control Room / Perpendicular illuminance (adaptive)

Control Room: Perpendicular illuminance (adaptive) (Surface)


Light scene: Light scene 1
Average: 407 lx (Target: ≥ 400 lx), Min: 4.09 lx, Max: 558 lx, Min/average: 0.010, Min/max: 0.007
Height: 0.800 m, Wall zone: 0.000 m

Isolines [lx]

Scale: 1 : 100

Page 25
0388 SFN 5640 J 003 A - Control Building 9/23/2019
Illumination System Calculation
San Francisco Control Building / Building 1 / Second Floor / Control Room / Control Room / Perpendicular illuminance
(adaptive)

False colours [lx]

Scale: 1 : 100

Value grid [lx]

Scale: 1 : 100

Page 26
0388 SFN 5640 J 003 A - Control Building 9/23/2019
Illumination System Calculation
San Francisco Control Building / Building 1 / Second Floor / Guard Area / Views

Guard Area

Guard's Area

Page 27
0388 SFN 5640 J 003 A - Control Building 9/23/2019
Illumination System Calculation
San Francisco Control Building / Building 1 / Second Floor / Guard Area / Workplane (Guard Area) / Perpendicular
illuminance (adaptive)

Workplane (Guard Area) / Perpendicular illuminance (adaptive)

Workplane (Guard Area): Perpendicular illuminance (adaptive) (Surface)


Light scene: Light scene 1
Average: 129 lx (Target: ≥ 100 lx), Min: 44.4 lx, Max: 183 lx, Min/average: 0.34, Min/max: 0.24
Height: 0.800 m, Wall zone: 0.000 m

Isolines [lx]

Scale: 1 : 60

Page 28
0388 SFN 5640 J 003 A - Control Building 9/23/2019
Illumination System Calculation
San Francisco Control Building / Building 1 / Second Floor / Guard Area / Workplane (Guard Area) / Perpendicular
illuminance (adaptive)

False colours [lx]

Scale: 1 : 60

Value grid [lx]

Scale: 1 : 60

Page 29
0388 SFN 5640 J 003 A - Control Building 9/23/2019
Illumination System Calculation
San Francisco Control Building / Building 1 / Second Floor / Hall / Views

Hall

Hall

Page 30
0388 SFN 5640 J 003 A - Control Building 9/23/2019
Illumination System Calculation
San Francisco Control Building / Building 1 / Second Floor / Hall / Workplane (Hall) / Perpendicular illuminance
(adaptive)

Workplane (Hall) / Perpendicular illuminance (adaptive)

Workplane (Hall): Perpendicular illuminance (adaptive) (Surface)


Light scene: Light scene 1
Average: 154 lx (Target: ≥ 50.0 lx), Min: 76.8 lx, Max: 208 lx, Min/average: 0.50, Min/max: 0.37
Height: 0.800 m, Wall zone: 0.000 m

Isolines [lx]

Scale: 1 : 105

Page 31
0388 SFN 5640 J 003 A - Control Building 9/23/2019
Illumination System Calculation
San Francisco Control Building / Building 1 / Second Floor / Hall / Workplane (Hall) / Perpendicular illuminance
(adaptive)

False colours [lx]

Scale: 1 : 105

Value grid [lx]

Scale: 1 : 105

Page 32
0388 SFN 5640 J 003 A - Control Building 9/23/2019
Illumination System Calculation
San Francisco Control Building / Building 1 / Second Floor / He / Views

He

He

Page 33
0388 SFN 5640 J 003 A - Control Building 9/23/2019
Illumination System Calculation
San Francisco Control Building / Building 1 / Second Floor / He / He / Perpendicular illuminance (adaptive)

He / Perpendicular illuminance (adaptive)

He: Perpendicular illuminance (adaptive) (Surface)


Light scene: Light scene 1
Average: 110 lx (Target: ≥ 100 lx), Min: 0.31 lx, Max: 171 lx, Min/average: 0.003, Min/max: 0.002
Height: 0.800 m, Wall zone: 0.000 m

Isolines [lx]

Scale: 1 : 25

Page 34
0388 SFN 5640 J 003 A - Control Building 9/23/2019
Illumination System Calculation
San Francisco Control Building / Building 1 / Second Floor / He / He / Perpendicular illuminance (adaptive)

False colours [lx]

Scale: 1 : 25

Value grid [lx]

Scale: 1 : 25

Page 35
0388 SFN 5640 J 003 A - Control Building 9/23/2019
Illumination System Calculation
San Francisco Control Building / Building 1 / Second Floor / Operator's Quarter (Female) / Views

Operator's Quarter (Female)

Operator's Quarter (Female)

Page 36
0388 SFN 5640 J 003 A - Control Building 9/23/2019
Illumination System Calculation
San Francisco Control Building / Building 1 / Second Floor / Operator's Quarter (Female) / Operator's Quarter /
Perpendicular illuminance (adaptive)

Operator's Quarter / Perpendicular illuminance (adaptive)

Operator's Quarter: Perpendicular illuminance (adaptive) (Surface)


Light scene: Light scene 1
Average: 157 lx (Target: ≥ 100 lx), Min: 102 lx, Max: 197 lx, Min/average: 0.65, Min/max: 0.52
Height: 0.800 m, Wall zone: 0.000 m

Isolines [lx]

Scale: 1 : 25

Page 37
0388 SFN 5640 J 003 A - Control Building 9/23/2019
Illumination System Calculation
San Francisco Control Building / Building 1 / Second Floor / Operator's Quarter (Female) / Operator's Quarter /
Perpendicular illuminance (adaptive)

False colours [lx]

Scale: 1 : 25

Value grid [lx]

Scale: 1 : 25

Page 38
0388 SFN 5640 J 003 A - Control Building 9/23/2019
Illumination System Calculation
San Francisco Control Building / Building 1 / Second Floor / Operator's Quarter (Male) / Views

Operator's Quarter (Male)

Operator's Quarter (Male)

Page 39
0388 SFN 5640 J 003 A - Control Building 9/23/2019
Illumination System Calculation
San Francisco Control Building / Building 1 / Second Floor / Operator's Quarter (Male) / Workplane (Operator's Quarter
(Male)) / Perpendicular illuminance (adaptive)

Workplane (Operator's Quarter (Male)) / Perpendicular illuminance


(adaptive)

Workplane (Operator's Quarter (Male)): Perpendicular illuminance (adaptive) (Surface)


Light scene: Light scene 1
Average: 155 lx (Target: ≥ 100 lx), Min: 58.2 lx, Max: 243 lx, Min/average: 0.38, Min/max: 0.24
Height: 0.800 m, Wall zone: 0.000 m

Isolines [lx]

Scale: 1 : 60

False colours [lx]

Scale: 1 : 60

Value grid [lx]

Scale: 1 : 60

Page 40
0388 SFN 5640 J 003 A - Control Building 9/23/2019
Illumination System Calculation
San Francisco Control Building / Building 1 / Second Floor / Pantry / Views

Pantry

Pantry

Page 41
0388 SFN 5640 J 003 A - Control Building 9/23/2019
Illumination System Calculation
San Francisco Control Building / Building 1 / Second Floor / Pantry / Pantry / Perpendicular illuminance (adaptive)

Pantry / Perpendicular illuminance (adaptive)

Pantry: Perpendicular illuminance (adaptive) (Surface)


Light scene: Light scene 1
Average: 106 lx (Target: ≥ 100 lx), Min: 4.44 lx, Max: 174 lx, Min/average: 0.042, Min/max: 0.026
Height: 0.800 m, Wall zone: 0.000 m

Isolines [lx]

Scale: 1 : 50

Page 42
0388 SFN 5640 J 003 A - Control Building 9/23/2019
Illumination System Calculation
San Francisco Control Building / Building 1 / Second Floor / Pantry / Pantry / Perpendicular illuminance (adaptive)

False colours [lx]

Scale: 1 : 50

Value grid [lx]

Scale: 1 : 50

Page 43
0388 SFN 5640 J 003 A - Control Building 9/23/2019
Illumination System Calculation
San Francisco Control Building / Building 1 / Second Floor / Records Room / Views

Records Room

Records Room

Page 44
0388 SFN 5640 J 003 A - Control Building 9/23/2019
Illumination System Calculation
San Francisco Control Building / Building 1 / Second Floor / Records Room / Records Room / Perpendicular
illuminance (adaptive)

Records Room / Perpendicular illuminance (adaptive)

Records Room: Perpendicular illuminance (adaptive) (Surface)


Light scene: Light scene 1
Average: 213 lx (Target: ≥ 200 lx), Min: 107 lx, Max: 291 lx, Min/average: 0.50, Min/max: 0.37
Height: 0.800 m, Wall zone: 0.000 m

Isolines [lx]

Scale: 1 : 70

False colours [lx]

Scale: 1 : 70

Value grid [lx]

Scale: 1 : 70

Page 45
0388 SFN 5640 J 003 A - Control Building 9/23/2019
Illumination System Calculation
San Francisco Control Building / Building 1 / Second Floor / Relay and Communication Room / Views

Relay and Communication Room

Relay and Communication Room

Page 46
0388 SFN 5640 J 003 A - Control Building 9/23/2019
Illumination System Calculation
San Francisco Control Building / Building 1 / Second Floor / Relay and Communication Room / Relay and
Communication Room / Perpendicular illuminance (adaptive)

Relay and Communication Room / Perpendicular illuminance


(adaptive)

Relay and Communication Room: Perpendicular illuminance (adaptive) (Surface)


Light scene: Light scene 1
Average: 345 lx (Target: ≥ 300 lx), Min: 0.75 lx, Max: 552 lx, Min/average: 0.002, Min/max: 0.001
Height: 0.800 m, Wall zone: 0.000 m

Isolines [lx]

Scale: 1 : 115

Page 47
0388 SFN 5640 J 003 A - Control Building 9/23/2019
Illumination System Calculation
San Francisco Control Building / Building 1 / Second Floor / Relay and Communication Room / Relay and
Communication Room / Perpendicular illuminance (adaptive)

False colours [lx]

Scale: 1 : 115

Value grid [lx]

Scale: 1 : 115

Page 48
0388 SFN 5640 J 003 A - Control Building 9/23/2019
Illumination System Calculation
San Francisco Control Building / Building 1 / Second Floor / She / Views

She

She

Page 49
0388 SFN 5640 J 003 A - Control Building 9/23/2019
Illumination System Calculation
San Francisco Control Building / Building 1 / Second Floor / She / She / Perpendicular illuminance (adaptive)

She / Perpendicular illuminance (adaptive)

She: Perpendicular illuminance (adaptive) (Surface)


Light scene: Light scene 1
Average: 188 lx (Target: ≥ 100 lx), Min: 0.99 lx, Max: 250 lx, Min/average: 0.005, Min/max: 0.004
Height: 0.800 m, Wall zone: 0.000 m

Isolines [lx]

Scale: 1 : 20

Page 50
0388 SFN 5640 J 003 A - Control Building 9/23/2019
Illumination System Calculation
San Francisco Control Building / Building 1 / Second Floor / She / She / Perpendicular illuminance (adaptive)

False colours [lx]

Scale: 1 : 20

Value grid [lx]

Scale: 1 : 20

Page 51
0388 SFN 5640 J 003 A - Control Building 9/23/2019
Illumination System Calculation
San Francisco Control Building / Building 1 / Second Floor / Shower / Views

Shower

Shower

Page 52
0388 SFN 5640 J 003 A - Control Building 9/23/2019
Illumination System Calculation
San Francisco Control Building / Building 1 / Second Floor / Shower / Workplane (Shower) / Perpendicular illuminance
(adaptive)

Workplane (Shower) / Perpendicular illuminance (adaptive)

Workplane (Shower): Perpendicular illuminance (adaptive) (Surface)


Light scene: Light scene 1
Average: 162 lx (Target: ≥ 100 lx), Min: 136 lx, Max: 184 lx, Min/average: 0.84, Min/max: 0.74
Height: 0.800 m, Wall zone: 0.000 m

Isolines [lx]

Scale: 1 : 20

Page 53
0388 SFN 5640 J 003 A - Control Building 9/23/2019
Illumination System Calculation
San Francisco Control Building / Building 1 / Second Floor / Shower / Workplane (Shower) / Perpendicular illuminance
(adaptive)

False colours [lx]

Scale: 1 : 20

Value grid [lx]

Scale: 1 : 20

Page 54
0388 SFN 5640 J 003 A - Control Building 9/23/2019
Illumination System Calculation
San Francisco Control Building / Building 1 / Second Floor / Staircase (2nd to Roof Deck) / Views

Staircase (2nd to Roof Deck)

Staircase (2nd to 3rd Floor Platform)

Page 55
0388 SFN 5640 J 003 A - Control Building 9/23/2019
Illumination System Calculation
San Francisco Control Building / Building 1 / Second Floor / Staircase (2nd to Roof Deck) / Workplane (Staircase (2nd
to Roof Deck)) / Perpendicular illuminance (adaptive)

Workplane (Staircase (2nd to Roof Deck)) / Perpendicular illuminance


(adaptive)

Workplane (Staircase (2nd to Roof Deck)): Perpendicular illuminance (adaptive) (Surface)


Light scene: Light scene 1
Average: 168 lx (Target: ≥ 100 lx), Min: 111 lx, Max: 219 lx, Min/average: 0.66, Min/max: 0.51
Height: 0.800 m, Wall zone: 0.000 m

Isolines [lx]

Scale: 1 : 50

False colours [lx]

Scale: 1 : 50

Value grid [lx]

Scale: 1 : 50

Page 56
0388 SFN 5640 J 003 A - Control Building 9/23/2019
Illumination System Calculation
San Francisco Control Building / Building 1 / Roof Deck / Mechanical Room / Views

Mechanical Room

Mechanical Room

Page 57
0388 SFN 5640 J 003 A - Control Building 9/23/2019
Illumination System Calculation
San Francisco Control Building / Building 1 / Roof Deck / Mechanical Room / Mechanical Room / Perpendicular
illuminance (adaptive)

Mechanical Room / Perpendicular illuminance (adaptive)

Mechanical Room: Perpendicular illuminance (adaptive) (Surface)


Light scene: Light scene 1
Average: 124 lx (Target: ≥ 100 lx), Min: 31.6 lx, Max: 185 lx, Min/average: 0.25, Min/max: 0.17
Height: 0.800 m, Wall zone: 0.000 m

Isolines [lx]

Scale: 1 : 70

Page 58
0388 SFN 5640 J 003 A - Control Building 9/23/2019
Illumination System Calculation
San Francisco Control Building / Building 1 / Roof Deck / Mechanical Room / Mechanical Room / Perpendicular
illuminance (adaptive)

False colours [lx]

Scale: 1 : 70

Value grid [lx]

Scale: 1 : 70

Page 59
0388 SFN 5640 J 003 A - Control Building 9/23/2019
Illumination System Calculation
San Francisco Control Building / Building 1 / Roof Deck / Staircase (Roof Deck) / Views

Staircase (Roof Deck)

Staircase (3rd Floor)

Page 60
0388 SFN 5640 J 003 A - Control Building 9/23/2019
Illumination System Calculation
San Francisco Control Building / Building 1 / Roof Deck / Staircase (Roof Deck) / Workplane (Staircase (Roof Deck)) /
Perpendicular illuminance (adaptive)

Workplane (Staircase (Roof Deck)) / Perpendicular illuminance


(adaptive)

Workplane (Staircase (Roof Deck)): Perpendicular illuminance (adaptive) (Surface)


Light scene: Light scene 1
Average: 129 lx (Target: ≥ 100 lx), Min: 67.1 lx, Max: 191 lx, Min/average: 0.52, Min/max: 0.35
Height: 0.800 m, Wall zone: 0.000 m

Isolines [lx]

Scale: 1 : 110

Page 61
0388 SFN 5640 J 003 A - Control Building 9/23/2019
Illumination System Calculation
San Francisco Control Building / Building 1 / Roof Deck / Staircase (Roof Deck) / Workplane (Staircase (Roof Deck)) /
Perpendicular illuminance (adaptive)

False colours [lx]

Scale: 1 : 110

Value grid [lx]

Scale: 1 : 110

Page 62