Preliminary remarks

Notes on planning:

The energy consumption quantities do not take into account light


scenes and their dimming levels.
Project 0

Content

Cover page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Preliminary remarks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Content . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Images . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Product data sheets


CLIPSAL BY SCHNEIDER ELECTRIC - 9 WATT LED DOWNLIGHT ON 3000K ............................ 9
SETTING (1x 9 WATT LED 3000K)

Site 1 - Building 2

Storey 1
Calculation objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Site 1 - Building 2 - Storey 1

Room 2
Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Calculation objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Workplane (Room 2) / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

Site 1 - Building 2 - Storey 1

Room 3
Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Calculation objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Workplane (Room 3) / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

Site 1

Building 3
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

Site 1 - Building 3

Storey 1
Room List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Project 0

Content

Calculation objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

Site 1 - Building 3 - Storey 1

Room 4
Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Calculation objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Workplane (Room 4) / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

Site 1 - Building 3 - Storey 1

Room 5
Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Calculation objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Workplane (Room 5) / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45

Site 1 - Building 3 - Storey 1

Room 6
Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Calculation objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Workplane (Room 6) / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53

Site 1 - Building 3 - Storey 1

Space 1
Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Calculation objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Workplane (Space 1) / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61

Site 1 - Building 3 - Storey 1

Room 7
Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Project 0

Content

Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64


Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Calculation objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Workplane (Room 7) / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69

Site 1 - Building 3 - Storey 1

Room 8
Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Calculation objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Workplane (Room 8) / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77

Site 1 - Building 3 - Storey 1

Space 2
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80

Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Project 0

Description

6
Project 0

Images

7
Project 0

Luminaire list

Φtotal Ptotal Luminous efficacy


10465 lm 117.0 W 89.4 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

13 CLIPSAL BY TPDL1C2 9 WATT LED DOWNLIGHT ON 3000K SETTING 9.0 W 805 lm 89.4 lm/W
SCHNEIDER
ELECTRIC

8
Project 0

Product data sheet

CLIPSAL BY SCHNEIDER ELECTRIC 9 WATT LED DOWNLIGHT ON 3000K SETTING

Article No. TPDL1C2

P 9.0 W

ΦLamp 805 lm

ΦLuminaire 805 lm

η 100.00 %

Luminous efficacy 89.4 lm/W


Polar LDC
CCT 3000 K

CRI 100

9
Project 0

Building 2 · Storey 1
Calculation objects

10
Project 0

Building 2 · Storey 1
Calculation objects

Work planes

Properties Ē Emin Emax g1 g2 Index


(Target)

Workplane (Room 2) 61.1 lx 0.64 lx 132 lx 0.010 0.005 S2


Perpendicular illuminance (adaptive) (≥ 500 lx)
Height: 0.800 m, Wall zone: 0.000 m

Workplane (Room 3) 114 lx 0.69 lx 171 lx 0.006 0.004 S4


Perpendicular illuminance (adaptive) (≥ 500 lx)
Height: 0.800 m, Wall zone: 0.000 m

11
Project 0

Building 2 · Storey 1 · Room 2


Summary

Ground area: 16.65 m² | Reflection factors: Ceiling: 70.0 %, Walls: 50.0 %, Floor: 20.0 % | Light loss factor: 0.80 (fixed) | Clearance
height: 2.800 m | 12
Project 0

Building 2 · Storey 1 · Room 2


Summary

Results

Symbol Calculated Target Check

Workplane Ē 61.1 lx ≥ 500 lx

g1 0.010 - -

Consumption values Consumption 0 kWh/a max. 50 kWh/a

Lighting power density Room 0.00 W/m² - -

0.00 W/m²/100 lx - -

Utilisation profile: DIALux presetting, Standard (office)

13
Project 0

Building 2 · Storey 1 · Room 2


Calculation objects

14
Project 0

Building 2 · Storey 1 · Room 2


Calculation objects

Work planes

Properties Ē Emin Emax g1 g2 Index


(Target)

Workplane (Room 2) 61.1 lx 0.64 lx 132 lx 0.010 0.005 S2


Perpendicular illuminance (adaptive) (≥ 500 lx)
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: DIALux presetting, Standard (office)

15
Project 0

Building 2 · Storey 1 · Room 2


Workplane (Room 2)

Properties Ē Emin Emax g1 g2 Index


(Target)

Workplane (Room 2) 61.1 lx 0.64 lx 132 lx 0.010 0.005 S2


Perpendicular illuminance (adaptive) (≥ 500 lx)
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: DIALux presetting, Standard (office)

16
Project 0

Building 2 · Storey 1 · Room 3


Summary

Ground area: 12.60 m² | Reflection factors: Ceiling: 70.0 %, Walls: 50.0 %, Floor: 20.0 % | Light loss factor: 0.80 (fixed) | Clearance
height: 2.800 m | 17
Project 0

Building 2 · Storey 1 · Room 3


Summary

Results

Symbol Calculated Target Check

Workplane Ē 114 lx ≥ 500 lx

g1 0.006 - -

Consumption values Consumption 0 kWh/a max. 50 kWh/a

Lighting power density Room 0.00 W/m² - -

0.00 W/m²/100 lx - -

Utilisation profile: DIALux presetting, Standard (office)

18
Project 0

Building 2 · Storey 1 · Room 3


Calculation objects

19
Project 0

Building 2 · Storey 1 · Room 3


Calculation objects

Work planes

Properties Ē Emin Emax g1 g2 Index


(Target)

Workplane (Room 3) 114 lx 0.69 lx 171 lx 0.006 0.004 S4


Perpendicular illuminance (adaptive) (≥ 500 lx)
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: DIALux presetting, Standard (office)

20
Project 0

Building 2 · Storey 1 · Room 3


Workplane (Room 3)

Properties Ē Emin Emax g1 g2 Index


(Target)

Workplane (Room 3) 114 lx 0.69 lx 171 lx 0.006 0.004 S4


Perpendicular illuminance (adaptive) (≥ 500 lx)
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: DIALux presetting, Standard (office)

21
Project 0

Building 3
Luminaire list

Φtotal Ptotal Luminous efficacy


10465 lm 117.0 W 89.4 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

13 CLIPSAL BY TPDL1C2 9 WATT LED DOWNLIGHT ON 3000K SETTING 9.0 W 805 lm 89.4 lm/W
SCHNEIDER
ELECTRIC

22
Project 0

Building 3 · Storey 1
Room List

23
Project 0

Building 3 · Storey 1
Room List

Room 4

Ptotal ARoom Lighting power density Ēhorizontal (Workplane)


9.0 W 16.50 m² 0.55 W/m² = 0.92 W/m²/100 lx (Room) 59.2 lx

pcs. Manufacturer Article No. Article name P ΦLuminaire

1 CLIPSAL BY TPDL1C2 9 WATT LED DOWNLIGHT ON 3000K SETTING 9.0 W 805 lm


SCHNEIDER
ELECTRIC

Room 5

Ptotal ARoom Lighting power density Ēhorizontal (Workplane)


36.0 W 12.75 m² 2.82 W/m² = 2.50 W/m²/100 lx (Room) 113 lx

pcs. Manufacturer Article No. Article name P ΦLuminaire

4 CLIPSAL BY TPDL1C2 9 WATT LED DOWNLIGHT ON 3000K SETTING 9.0 W 805 lm


SCHNEIDER
ELECTRIC

Room 6

Ptotal ARoom Lighting power density Ēhorizontal (Workplane)


18.0 W 11.54 m² 1.56 W/m² = 2.05 W/m²/100 lx (Room) 76.2 lx

pcs. Manufacturer Article No. Article name P ΦLuminaire

2 CLIPSAL BY TPDL1C2 9 WATT LED DOWNLIGHT ON 3000K SETTING 9.0 W 805 lm


SCHNEIDER
ELECTRIC

24
Project 0

Building 3 · Storey 1
Room List

Room 7

Ptotal ARoom Lighting power density Ēhorizontal (Workplane)


9.0 W 3.15 m² 2.86 W/m² = 2.20 W/m²/100 lx (Room) 130 lx

pcs. Manufacturer Article No. Article name P ΦLuminaire

1 CLIPSAL BY TPDL1C2 9 WATT LED DOWNLIGHT ON 3000K SETTING 9.0 W 805 lm


SCHNEIDER
ELECTRIC

Room 8

Ptotal ARoom Lighting power density Ēhorizontal (Workplane)


9.0 W 1.45 m² 6.21 W/m² = 4.15 W/m²/100 lx (Room) 150 lx

pcs. Manufacturer Article No. Article name P ΦLuminaire

1 CLIPSAL BY TPDL1C2 9 WATT LED DOWNLIGHT ON 3000K SETTING 9.0 W 805 lm


SCHNEIDER
ELECTRIC

Space 1

Ptotal ARoom Lighting power density Ēhorizontal (Workplane)


18.0 W 13.65 m² 1.32 W/m² = 1.24 W/m²/100 lx (Room) 106 lx

pcs. Manufacturer Article No. Article name P ΦLuminaire

2 CLIPSAL BY TPDL1C2 9 WATT LED DOWNLIGHT ON 3000K SETTING 9.0 W 805 lm


SCHNEIDER
ELECTRIC

25
Project 0

Building 3 · Storey 1
Room List

Space 2

Ptotal ARoom Lighting power density


18.0 W 6.98 m² 2.58 W/m² (Room)

pcs. Manufacturer Article No. Article name P ΦLuminaire

2 CLIPSAL BY TPDL1C2 9 WATT LED DOWNLIGHT ON 3000K SETTING 9.0 W 805 lm


SCHNEIDER
ELECTRIC

26
Project 0

Building 3 · Storey 1
Luminaire list

Φtotal Ptotal Luminous efficacy


10465 lm 117.0 W 89.4 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

13 CLIPSAL BY TPDL1C2 9 WATT LED DOWNLIGHT ON 3000K SETTING 9.0 W 805 lm 89.4 lm/W
SCHNEIDER
ELECTRIC

27
Project 0

Building 3 · Storey 1
Calculation objects

28
Project 0

Building 3 · Storey 1
Calculation objects

Work planes

Properties Ē Emin Emax g1 g2 Index


(Target)

Workplane (Room 4) 59.2 lx 1.03 lx 132 lx 0.017 0.008 S6


Perpendicular illuminance (adaptive) (≥ 500 lx)
Height: 0.800 m, Wall zone: 0.000 m

Workplane (Room 5) 113 lx 1.32 lx 170 lx 0.012 0.008 S8


Perpendicular illuminance (adaptive) (≥ 500 lx)
Height: 0.800 m, Wall zone: 0.000 m

Workplane (Room 6) 76.2 lx 15.0 lx 159 lx 0.20 0.094 S10


Perpendicular illuminance (adaptive) (≥ 500 lx)
Height: 0.800 m, Wall zone: 0.000 m

Workplane (Space 1) 106 lx 30.4 lx 163 lx 0.29 0.19 S11


Perpendicular illuminance (adaptive) (≥ 500 lx)
Height: 0.800 m, Wall zone: 0.000 m

Workplane (Room 7) 130 lx 73.4 lx 166 lx 0.56 0.44 S13


Perpendicular illuminance (adaptive) (≥ 500 lx)
Height: 0.800 m, Wall zone: 0.000 m

Workplane (Room 8) 150 lx 113 lx 176 lx 0.75 0.64 S15


Perpendicular illuminance (adaptive) (≥ 500 lx)
Height: 0.800 m, Wall zone: 0.000 m

29
Project 0

Building 3 · Storey 1 · Room 4


Summary

Ground area: 16.50 m² | Reflection factors: Ceiling: 70.0 %, Walls: 50.0 %, Floor: 20.0 % | Light loss factor: 0.80 (fixed) | Clearance
height: 2.470 m | Mounting height: 2.470 m 30
Project 0

Building 3 · Storey 1 · Room 4


Summary

Results

Symbol Calculated Target Check

Workplane Ē 59.2 lx ≥ 500 lx

g1 0.017 - -

Consumption values Consumption 25 kWh/a max. 600 kWh/a

Lighting power density Room 0.55 W/m² - -

0.92 W/m²/100 lx - -

Utilisation profile: DIALux presetting, Standard (office)

Luminaire list

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

1 CLIPSAL BY TPDL1C2 9 WATT LED DOWNLIGHT ON 3000K SETTING 9.0 W 805 lm 89.4 lm/W
SCHNEIDER
ELECTRIC

31
Project 0

Building 3 · Storey 1 · Room 4


Luminaire layout plan

32
Project 0

Building 3 · Storey 1 · Room 4


Luminaire layout plan

Manufacturer CLIPSAL BY
SCHNEIDER ELECTRIC

Article No. TPDL1C2

Article name 9 WATT LED


DOWNLIGHT ON
3000K SETTING

Individual luminaires
X Y Mounting Luminaire
height

2.777 m 1.751 m 2.470 m 1

33
Project 0

Building 3 · Storey 1 · Room 4


Luminaire list

Φtotal Ptotal Luminous efficacy


805 lm 9.0 W 89.4 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

1 CLIPSAL BY TPDL1C2 9 WATT LED DOWNLIGHT ON 3000K SETTING 9.0 W 805 lm 89.4 lm/W
SCHNEIDER
ELECTRIC

34
Project 0

Building 3 · Storey 1 · Room 4


Calculation objects

35
Project 0

Building 3 · Storey 1 · Room 4


Calculation objects

Work planes

Properties Ē Emin Emax g1 g2 Index


(Target)

Workplane (Room 4) 59.2 lx 1.03 lx 132 lx 0.017 0.008 S6


Perpendicular illuminance (adaptive) (≥ 500 lx)
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: DIALux presetting, Standard (office)

36
Project 0

Building 3 · Storey 1 · Room 4


Workplane (Room 4)

Properties Ē Emin Emax g1 g2 Index


(Target)

Workplane (Room 4) 59.2 lx 1.03 lx 132 lx 0.017 0.008 S6


Perpendicular illuminance (adaptive) (≥ 500 lx)
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: DIALux presetting, Standard (office)

37
Project 0

Building 3 · Storey 1 · Room 5


Summary

Ground area: 12.75 m² | Reflection factors: Ceiling: 70.0 %, Walls: 50.0 %, Floor: 20.0 % | Light loss factor: 0.80 (fixed) | Clearance
height: 2.470 m - 2.800 m | Mounting height: 2.470 m 38
Project 0

Building 3 · Storey 1 · Room 5


Summary

Results

Symbol Calculated Target Check

Workplane Ē 113 lx ≥ 500 lx

g1 0.012 - -

Consumption values Consumption 99 kWh/a max. 450 kWh/a

Lighting power density Room 2.82 W/m² - -

2.50 W/m²/100 lx - -

Utilisation profile: DIALux presetting, Standard (office)

Luminaire list

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

4 CLIPSAL BY TPDL1C2 9 WATT LED DOWNLIGHT ON 3000K SETTING 9.0 W 805 lm 89.4 lm/W
SCHNEIDER
ELECTRIC

39
Project 0

Building 3 · Storey 1 · Room 5


Luminaire layout plan

40
Project 0

Building 3 · Storey 1 · Room 5


Luminaire layout plan

Manufacturer CLIPSAL BY
SCHNEIDER ELECTRIC

Article No. TPDL1C2

Article name 9 WATT LED


DOWNLIGHT ON
3000K SETTING

1 x CLIPSAL BY SCHNEIDER ELECTRIC 9 WATT LED DOWNLIGHT ON 3000K SETTING


Type Line arrangement X Y Mounting Luminaire
height
1st luminaire (X/Y/Z) 3.482 m, 2.500 m,
2.470 m 3.482 m 2.500 m 2.470 m 2

X-direction 1 pcs., Center - center,


3.450 m

Arrangement A1

Individual luminaires
X Y Mounting Luminaire
height

0.520 m 0.267 m 2.470 m 1

0.525 m 2.500 m 2.470 m 3

3.525 m 0.300 m 2.470 m 4

41
Project 0

Building 3 · Storey 1 · Room 5


Luminaire list

Φtotal Ptotal Luminous efficacy


3220 lm 36.0 W 89.4 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

4 CLIPSAL BY TPDL1C2 9 WATT LED DOWNLIGHT ON 3000K SETTING 9.0 W 805 lm 89.4 lm/W
SCHNEIDER
ELECTRIC

42
Project 0

Building 3 · Storey 1 · Room 5


Calculation objects

43
Project 0

Building 3 · Storey 1 · Room 5


Calculation objects

Work planes

Properties Ē Emin Emax g1 g2 Index


(Target)

Workplane (Room 5) 113 lx 1.32 lx 170 lx 0.012 0.008 S8


Perpendicular illuminance (adaptive) (≥ 500 lx)
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: DIALux presetting, Standard (office)

44
Project 0

Building 3 · Storey 1 · Room 5


Workplane (Room 5)

Properties Ē Emin Emax g1 g2 Index


(Target)

Workplane (Room 5) 113 lx 1.32 lx 170 lx 0.012 0.008 S8


Perpendicular illuminance (adaptive) (≥ 500 lx)
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: DIALux presetting, Standard (office)

45
Project 0

Building 3 · Storey 1 · Room 6


Summary

Ground area: 11.54 m² | Reflection factors: Ceiling: 70.0 %, Walls: 50.0 %, Floor: 20.0 % | Light loss factor: 0.80 (fixed) | Clearance
height: 2.470 m - 2.800 m | Mounting height: 2.470 m 46
Project 0

Building 3 · Storey 1 · Room 6


Summary

Results

Symbol Calculated Target Check

Workplane Ē 76.2 lx ≥ 500 lx

g1 0.20 - -

Consumption values Consumption 50 kWh/a max. 450 kWh/a

Lighting power density Room 1.56 W/m² - -

2.05 W/m²/100 lx - -

Utilisation profile: DIALux presetting, Standard (office)

Luminaire list

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

2 CLIPSAL BY TPDL1C2 9 WATT LED DOWNLIGHT ON 3000K SETTING 9.0 W 805 lm 89.4 lm/W
SCHNEIDER
ELECTRIC

47
Project 0

Building 3 · Storey 1 · Room 6


Luminaire layout plan

48
Project 0

Building 3 · Storey 1 · Room 6


Luminaire layout plan

Manufacturer CLIPSAL BY
SCHNEIDER ELECTRIC

Article No. TPDL1C2

Article name 9 WATT LED


DOWNLIGHT ON
3000K SETTING

Individual luminaires
X Y Mounting Luminaire
height

0.675 m 1.125 m 2.470 m 1

2.875 m 1.125 m 2.470 m 2

49
Project 0

Building 3 · Storey 1 · Room 6


Luminaire list

Φtotal Ptotal Luminous efficacy


1610 lm 18.0 W 89.4 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

2 CLIPSAL BY TPDL1C2 9 WATT LED DOWNLIGHT ON 3000K SETTING 9.0 W 805 lm 89.4 lm/W
SCHNEIDER
ELECTRIC

50
Project 0

Building 3 · Storey 1 · Room 6


Calculation objects

51
Project 0

Building 3 · Storey 1 · Room 6


Calculation objects

Work planes

Properties Ē Emin Emax g1 g2 Index


(Target)

Workplane (Room 6) 76.2 lx 15.0 lx 159 lx 0.20 0.094 S10


Perpendicular illuminance (adaptive) (≥ 500 lx)
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: DIALux presetting, Standard (office)

52
Project 0

Building 3 · Storey 1 · Room 6


Workplane (Room 6)

Properties Ē Emin Emax g1 g2 Index


(Target)

Workplane (Room 6) 76.2 lx 15.0 lx 159 lx 0.20 0.094 S10


Perpendicular illuminance (adaptive) (≥ 500 lx)
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: DIALux presetting, Standard (office)

53
Project 0

Building 3 · Storey 1 · Space 1


Summary

Ground area: 13.65 m² | Reflection factors: Ceiling: 70.0 %, Walls: 50.0 %, Floor: 20.0 % | Light loss factor: 0.80 (fixed) | Mounting
height: 2.470 m 54
Project 0

Building 3 · Storey 1 · Space 1


Summary

Results

Symbol Calculated Target Check

Workplane Ē 106 lx ≥ 500 lx

g1 0.29 - -

Consumption values Consumption 50 kWh/a max. 500 kWh/a

Lighting power density Room 1.32 W/m² - -

1.24 W/m²/100 lx - -

Utilisation profile: DIALux presetting, Standard (office)

Luminaire list

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

2 CLIPSAL BY TPDL1C2 9 WATT LED DOWNLIGHT ON 3000K SETTING 9.0 W 805 lm 89.4 lm/W
SCHNEIDER
ELECTRIC

55
Project 0

Building 3 · Storey 1 · Space 1


Luminaire layout plan

56
Project 0

Building 3 · Storey 1 · Space 1


Luminaire layout plan

Manufacturer CLIPSAL BY
SCHNEIDER ELECTRIC

Article No. TPDL1C2

Article name 9 WATT LED


DOWNLIGHT ON
3000K SETTING

Individual luminaires
X Y Mounting Luminaire
height

0.504 m 0.572 m 2.470 m 1

3.535 m 0.512 m 2.470 m 2

57
Project 0

Building 3 · Storey 1 · Space 1


Luminaire list

Φtotal Ptotal Luminous efficacy


1610 lm 18.0 W 89.4 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

2 CLIPSAL BY TPDL1C2 9 WATT LED DOWNLIGHT ON 3000K SETTING 9.0 W 805 lm 89.4 lm/W
SCHNEIDER
ELECTRIC

58
Project 0

Building 3 · Storey 1 · Space 1


Calculation objects

59
Project 0

Building 3 · Storey 1 · Space 1


Calculation objects

Work planes

Properties Ē Emin Emax g1 g2 Index


(Target)

Workplane (Space 1) 106 lx 30.4 lx 163 lx 0.29 0.19 S11


Perpendicular illuminance (adaptive) (≥ 500 lx)
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: DIALux presetting, Standard (office)

60
Project 0

Building 3 · Storey 1 · Space 1


Workplane (Space 1)

Properties Ē Emin Emax g1 g2 Index


(Target)

Workplane (Space 1) 106 lx 30.4 lx 163 lx 0.29 0.19 S11


Perpendicular illuminance (adaptive) (≥ 500 lx)
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: DIALux presetting, Standard (office)

61
Project 0

Building 3 · Storey 1 · Room 7


Summary

Ground area: 3.15 m² | Reflection factors: Ceiling: 70.0 %, Walls: 50.0 %, Floor: 20.0 % | Light loss factor: 0.80 (fixed) | Clearance
height: 2.470 m | Mounting height: 2.470 m 62
Project 0

Building 3 · Storey 1 · Room 7


Summary

Results

Symbol Calculated Target Check

Workplane Ē 130 lx ≥ 500 lx

g1 0.56 - -

Consumption values Consumption 25 kWh/a max. 150 kWh/a

Lighting power density Room 2.86 W/m² - -

2.20 W/m²/100 lx - -

Utilisation profile: DIALux presetting, Standard (office)

Luminaire list

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

1 CLIPSAL BY TPDL1C2 9 WATT LED DOWNLIGHT ON 3000K SETTING 9.0 W 805 lm 89.4 lm/W
SCHNEIDER
ELECTRIC

63
Project 0

Building 3 · Storey 1 · Room 7


Luminaire layout plan

64
Project 0

Building 3 · Storey 1 · Room 7


Luminaire layout plan

Manufacturer CLIPSAL BY
SCHNEIDER ELECTRIC

Article No. TPDL1C2

Article name 9 WATT LED


DOWNLIGHT ON
3000K SETTING

Individual luminaires
X Y Mounting Luminaire
height

0.900 m 0.875 m 2.470 m 1

65
Project 0

Building 3 · Storey 1 · Room 7


Luminaire list

Φtotal Ptotal Luminous efficacy


805 lm 9.0 W 89.4 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

1 CLIPSAL BY TPDL1C2 9 WATT LED DOWNLIGHT ON 3000K SETTING 9.0 W 805 lm 89.4 lm/W
SCHNEIDER
ELECTRIC

66
Project 0

Building 3 · Storey 1 · Room 7


Calculation objects

67
Project 0

Building 3 · Storey 1 · Room 7


Calculation objects

Work planes

Properties Ē Emin Emax g1 g2 Index


(Target)

Workplane (Room 7) 130 lx 73.4 lx 166 lx 0.56 0.44 S13


Perpendicular illuminance (adaptive) (≥ 500 lx)
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: DIALux presetting, Standard (office)

68
Project 0

Building 3 · Storey 1 · Room 7


Workplane (Room 7)

Properties Ē Emin Emax g1 g2 Index


(Target)

Workplane (Room 7) 130 lx 73.4 lx 166 lx 0.56 0.44 S13


Perpendicular illuminance (adaptive) (≥ 500 lx)
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: DIALux presetting, Standard (office)

69
Project 0

Building 3 · Storey 1 · Room 8


Summary

Ground area: 1.45 m² | Reflection factors: Ceiling: 70.0 %, Walls: 50.0 %, Floor: 20.0 % | Light loss factor: 0.80 (fixed) | Clearance
height: 2.470 m | Mounting height: 2.470 m 70
Project 0

Building 3 · Storey 1 · Room 8


Summary

Results

Symbol Calculated Target Check

Workplane Ē 150 lx ≥ 500 lx

g1 0.75 - -

Consumption values Consumption 25 kWh/a max. 100 kWh/a

Lighting power density Room 6.21 W/m² - -

4.15 W/m²/100 lx - -

Utilisation profile: DIALux presetting, Standard (office)

Luminaire list

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

1 CLIPSAL BY TPDL1C2 9 WATT LED DOWNLIGHT ON 3000K SETTING 9.0 W 805 lm 89.4 lm/W
SCHNEIDER
ELECTRIC

71
Project 0

Building 3 · Storey 1 · Room 8


Luminaire layout plan

72
Project 0

Building 3 · Storey 1 · Room 8


Luminaire layout plan

Manufacturer CLIPSAL BY
SCHNEIDER ELECTRIC

Article No. TPDL1C2

Article name 9 WATT LED


DOWNLIGHT ON
3000K SETTING

Individual luminaires
X Y Mounting Luminaire
height

0.725 m 0.500 m 2.470 m 1

73
Project 0

Building 3 · Storey 1 · Room 8


Luminaire list

Φtotal Ptotal Luminous efficacy


805 lm 9.0 W 89.4 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

1 CLIPSAL BY TPDL1C2 9 WATT LED DOWNLIGHT ON 3000K SETTING 9.0 W 805 lm 89.4 lm/W
SCHNEIDER
ELECTRIC

74
Project 0

Building 3 · Storey 1 · Room 8


Calculation objects

75
Project 0

Building 3 · Storey 1 · Room 8


Calculation objects

Work planes

Properties Ē Emin Emax g1 g2 Index


(Target)

Workplane (Room 8) 150 lx 113 lx 176 lx 0.75 0.64 S15


Perpendicular illuminance (adaptive) (≥ 500 lx)
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: DIALux presetting, Standard (office)

76
Project 0

Building 3 · Storey 1 · Room 8


Workplane (Room 8)

Properties Ē Emin Emax g1 g2 Index


(Target)

Workplane (Room 8) 150 lx 113 lx 176 lx 0.75 0.64 S15


Perpendicular illuminance (adaptive) (≥ 500 lx)
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: DIALux presetting, Standard (office)

77
Project 0

Building 3 · Storey 1 · Space 2


Luminaire layout plan

78
Project 0

Building 3 · Storey 1 · Space 2


Luminaire layout plan

Manufacturer CLIPSAL BY
SCHNEIDER ELECTRIC

Article No. TPDL1C2

Article name 9 WATT LED


DOWNLIGHT ON
3000K SETTING

Individual luminaires
X Y Mounting Luminaire
height

1.336 m 0.920 m 2.470 m 1

4.366 m 0.860 m 2.470 m 2

79
Project 0

Building 3 · Storey 1 · Space 2


Luminaire list

Φtotal Ptotal Luminous efficacy


1610 lm 18.0 W 89.4 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

2 CLIPSAL BY TPDL1C2 9 WATT LED DOWNLIGHT ON 3000K SETTING 9.0 W 805 lm 89.4 lm/W
SCHNEIDER
ELECTRIC

80
Project 0

Glossary

A Formula symbol for a surface in the geometry

Background area The background area borders the direct ambient area according to DIN EN 12464-1 and
reaches up to the borders of the room. In larger rooms, the background area is at least 3
m wide. It is located horizontally at floor level.

CCT (Engl. correlated color temperature)


Body temperature of a thermal radiator that serves to describe its light color. Unit: Kelvin
[K]. The lesser the numerical value the redder; the greater the numerical value the bluer
the light color. The color temperature of gas-discharge lamps and semi-conductors are
termed "correlated color temperature" in contrast to the color temperature of thermal
radiators.

Allocation of the light colors to the color temperature ranges acc. to EN 12464-1:

Light color - color temperature [K]


warm white (ww) < 3,300 K
neutral white (nw) ≥ 3,300 – 5,300 K
daylight white (dw) > 5.300 K

Clearance height The designation for the distance between upper edge of the floor and bottom edge of
the ceiling (in the completely furnished status of room).

CRI (Engl. color rendering index)


Designation for the color rendering index of a luminaire or a lamp acc. to DIN 6169: 1976
or CIE 13.3: 1995.

The general color rendering index Ra (or CRI) is a dimensionless figure that describes the
quality of a white light source in regards to its similarity with the remission spectra of
defined 8 test colors (see DIN 6169 or CIE 1974) to a reference light source.

Daylight factor Ratio of the illuminance achieved solely by daylight incidence at a point in the inside to
the horizontal illuminance in the outer area under an unobstructed sky.

Formula symbol: D (Engl. daylight factor)


Unit: %

81
Project 0

Glossary

Daylight quotient effective area A calculation surface within which the daylight quotient is calculated.

Eta (η) (light output ratio)


The light output ratio describes what percentage of the luminous flux of a free radiating
lamp (or LED module) is emitted by the luminaire when installed.

Unit: %

g1 Often also Uo (Engl. overall uniformity)


Designates the overall uniformity of the illuminance on a surface. It is the quotient from
Emin to Ē and is required, for instance, in standards for illumination of workstations.

g2 Actually it designates the "non-uniformity" of the illuminance on a surface. It is the


quotient of Emin to Emax and is generally only relevant for certifying the emergency
lighting acc. to EN 1838.

Illuminance Describes the ratio of the luminous flux that strikes a certain surface to the size of this
surface (lm/m² = lx). The illuminance is not tied to an object surface. It can be determined
anywhere in space (inside or outside). The illuminance is not a product feature because it
is a recipient value. Luxometers are used for measuring.

Unit: Lux
Abbreviation: lx
Formula symbol: E

Illuminance, adaptive For the determining of the middle adaptive illuminance on a surface, this is rastered
"adaptively". In the area of large illuminance differences within the surface, the raster is
subdivided finer; within lesser differences, a rougher classification is made.

Illuminance, horizontal Illuminance that is calculated or measured on a horizontal (level) surface (this can be for
example a table top or the floor). The horizontal illuminance is usually identified by the
formula letter Eh.

Illuminance, perpendicular Illuminance that is calculated or measured plumb-vertical to a surface. This needs to be
taken into account for tilted surfaces. If the surface is horizontal or vertical, then there is
no difference between the perpendicular and the horizontal or vertical illuminance.

82
Project 0

Glossary

Illuminance, vertical Illuminance that is calculated or measured on a vertical surface (this can be for example
the front of some shelves). The vertical illuminance is usually identified by the formula
letter Ev.

LENI (Engl. lighting energy numeric indicator)


Lighting energy numeric indicator acc. to EN 15193

Unit: kWh/m² year

Light loss factor See MF

LLMF (Engl. lamp lumen maintenance factor)/acc. to CIE 97: 2005


Lamp flux maintenance factor that takes the luminous flux reduction into account of a
luminaire or an LED module in the course of the operating time. The lamp flux
maintenance factor is specified as a decimal digit and can have a maximum value of 1
(no luminous flux reduction existing).

LMF (Engl. luminaire maintenance factor)/acc. to CIE 97: 2005


Luminaire maintenance factor that takes the soiling into account of the luminaire in the
course of the operating time. The luminaire maintenance factor is specified as a decimal
digit and can have a maximum value of 1 (no soiling existing).

LSF (Engl. lamp survival factor)/acc. to CIE 97: 2005


Lamp survival factor that takes the total failure into account of a luminaire in the course
of the operating time. The lamp survival factor is specified as a decimal digit and can
have a maximum value of 1 (no failures existing within the time concerned or prompt
replacement after the failure).

Luminance Dimension for the "brightness impression" that the human eye has of a surface. The
surface itself can emit light thereby or light striking it can be reflected (emitter value). It is
the only photometric value that the human eye can perceive.

Unit: Candela per square meter


Abbreviation: cd/m²
Formula symbol: L

Luminous efficacy Ratio of the emitted luminous flux Φ [lm] to the absorbed electrical power P [W] Unit: lm/
W.

This ratio can be formed for the lamp or LED module (lamp or module light output), the
lamp or module with control gear (system light output) and the complete luminaire
(luminaire light output).

83
Project 0

Glossary

Luminous flux Dimension for the total light output that is emitted from one light source in all directions.
It is thus an "emitter value" that specifies the entire emitting output. The luminous flux of
a light source can only be determined in a laboratory. A difference is made between the
lamp or LED module luminous flux and the luminaire luminous flux.

Unit: Lumen
Abbreviation: lm
Formula symbol: Φ

Luminous intensity Describes the intensity of the light in a certain direction (emitter value). The luminous
intensity is a matter of the luminous flux Φ that is emitted in a certain spherical angle Ω.
The radiation characteristics of a light source are presented graphically in a light
distribution curve (LDC). The luminous intensity is an SI base unit.

Unit: Candela
Abbreviation: cd
Formula symbol: I

MF (Engl. maintenance factor)/acc. to CIE 97: 2005


Maintenance factor as decimal number between 0 and 1 that describes the ratio of the
new value of a photometric planning parameter (e.g. of the illuminance) to a
maintenance value after a certain time. The maintenance factor takes into account the
soiling of luminaires and rooms as well as the luminous flux reduction and the failure of
light sources.
The maintenance factor is taken into account either overall or determined in detail acc. to
CIE 97: 2005 by the formula RMF x LMF x LLMF x LSF.

P (Engl. power)
Electric power consumption

Unit: watt
Abbreviation: W

Reflection factor The reflection degree of a surface describes how much of the striking light is reflected
back. The reflection degree is defined by the color of the surface.

84
Project 0

Glossary

RMF (Engl. room surface maintenance factor)/acc. to CIE 97: 2005


Room surface maintenance factor that takes the soiling into account of the space
encompassing surfaces in the course of the operating time. The room surface
maintenance factor is specified as a decimal digit and can have a maximum value of 1
(no soiling existing).

Surrounding area The ambient area directly borders the area of the visual task and should be planned with
a width of at least 0.5 m according to DIN EN 12464-1. It is at the same height as the
area of the visual task.

UGR (max) (unified glare rating)


Measure for the psychological glare effect in interiors.
In addition to luminaire luminance, the UGR value also depends on the position of the
observer, the viewing direction and the ambient luminance. Among other things, EN
12464-1 specifies maximum permissible UGR values for various indoor workplaces.

UGR observer Calculation point in the room, for the DIALux the UGR value is determined. The location
and height of the calculation point should correspond to the typical observer position
(position and eye level of the user).

Visual task area The area that is needed for carrying out the visual task in accordance with DIN EN
12464-1. The height corresponds with the height at which the visual task is executed.

Wall zone Circumferential area between working plane and walls that is not taken into account for
the calculation.

Workplane Virtual measuring or calculation surface at the height of the visual task that generally
follows the room geometry. The working plane may also feature a wall zone.