You are on page 1of 446

Sèmè City-Lot A6

MAITRISE D'OUVRAGE
Sèmè City

ARCHITECTE MANDATAIRE MOE


Hardel Le Bihan architectes

40 rue de Paradis 75010 Paris


Tél: +33 1 44 64 83 30
Email: acceuil.secretariat@hardel-lebihan.com

ARCHITECTE
Ricardo Bofill Taller de Arquitectura

Av. de la Indùstria, 14, 08960 Sant Just Desvern,


Barcelona, Espagne
Tél: +34 934 99 99 00
Email: xxx.xxx@xxx.xxx

ARCHITECTE
Cobloc architecture

27 rue 5-108, Zongo Nima-Zone Résidentielle, Cotonou


Tél: +229 91 71 39 39
Email: bonjour@cobloc.archi

BET TCE Urbaniste


Atomas & Paysagiste
Atelier LD
1 Rue Georges Clemenceau,
Av. Commandant Driss El Harthi, Rabat, Maroc 76230 Bois-Guillaume
Tél: +212 5376-54268 Tél: +212 5376-54268
Email: www@atomas.ma Email: contact.paris@atelierld.com

Acousticien BET Conseil Qualité BET Conseil Structure Paysagiste


PEUTZ Environnementale En Vertu des Possibles Philippe NIEZ
Elioth by egis (evp)

10 Rue des Messageries, 75010 Paris 4 Rue Dolorès Ibarruri, 93188 Montreuil 80 Rue du Faubourg Saint-Denis, 75010 Paris 77 Rue des Archives, 75003 Paris
Tél: +33 1 45 23 05 00 Tél: +33 1 49 20 13 10 Tél: +33 1 40 26 15 97 Tél: +33 1 43 66 58 81
Email: s.mercier@peutz.fr Email: xxx.xxx@xxx.xxx Email: evp@evp-ingenierie.com Email: contact@philippeniez.com

ECHELLE INTITULÉ DATE

BILAN THERMIQUE 29/02/2024

LOT EMETTEUR PHASE DISCIPLINE SOUS-DISCIPLINE TYPE DE DOCUMENT ZONE NIVEAU NUMERO INDICE

A6 ATM APD FLD-TN CVC NDC - - 12,01 0


Air System Sizing Summary for A06-RDC-Commerce 1
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:12

Air System Information


Air System Name ................... A06-RDC-Commerce 1 Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area ................................................................ 70,0 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ....................................................... 16,3 kW Load occurs at ................................................. Jun 1600
Sensible coil load .................................................. 16,0 kW OA DB / WB ................................................... 32,0 / 27,0 °C
Coil L/s at Jun 1600 ............................................. 1328 L/s Entering DB / WB ........................................... 22,8 / 16,1 °C
Max block L/s at Jun 1600 ................................... 1456 L/s Leaving DB / WB ........................................... 12,8 / 12,1 °C
Sum of peak zone L/s .......................................... 1456 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,978 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 4,3 Resulting RH .............................................................. 50 %
W/m² .................................................................. 233,4 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K

Preheat Coil Sizing Data


No heating coil loads occurred during this calculation.

Supply Fan Sizing Data

Actual max L/s at Jun 1600 .................................. 1456 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ........................................................ 1455 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 20,80 L/(s-m²) Fan static ...................................................................... 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s ..................................................... 0 L/s L/s/person ................................................................ 0,00 L/s/person
L/(s-m²) ................................................................. 0,00 L/(s-m²)

Hourly Analysis Program v4.90 Page 1 of 11


Zone Sizing Summary for A06-RDC-Commerce 1
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:12

Air System Information


Air System Name ................... A06-RDC-Commerce 1 Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area ................................................................ 70,0 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 16,2 1456 15 Jun 1600 0,0 70,0 20,80

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
A06-RDC-Commerce 1 1 16,2 Jun 1600 1456 0,0 70,0 20,80

Hourly Analysis Program v4.90 Page 2 of 11


Ventilation Sizing Summary for A06-RDC-Commerce 1
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:12

1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 L/s

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (m²) Occupants (L/s) (L/s/person) (L/(s-m²)) (L/s) (% of supply) (L/s)
Zone 1
A06-RDC-Commerce 1 1 70,0 10,0 1455,9 0,00 0,00 0,0 0,0 0,0
Totals (incl. Space Multipliers) 1455,9 0,0

Hourly Analysis Program v4.90 Page 3 of 11


Air System Design Load Summary for A06-RDC-Commerce 1
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:12

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 32,0 °C / 27,0 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 49 m² 9440 - 49 m² - -
Wall Transmission 23 m² 409 - 23 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 49 m² 675 - 49 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 70 m² 0 - 70 m² 0 -
Partitions 23 m² 99 - 23 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1400 W 1400 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 3500 W 3500 - 0 0 -
People 10 674 352 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 16197 352 - 0 0
Zone Conditioning - 15976 352 - -131 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 1328 L/s 0 - 15 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 1328 L/s 0 - 15 L/s 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 15976 352 - -131 0
Central Cooling Coil - 15976 365 - -131 0
Preheat Coil - 0 - - 0 -
Terminal Reheat Coils - 0 - - 0 -
>> Total Conditioning - 15976 365 - -131 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 4 of 11


Zone Design Load Summary for A06-RDC-Commerce 1
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:12

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 32,0 °C / 27,0 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 49 m² 9440 - 49 m² - -
Wall Transmission 23 m² 409 - 23 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 49 m² 675 - 49 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 70 m² 0 - 70 m² 0 -
Partitions 23 m² 99 - 23 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1400 W 1400 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 3500 W 3500 - 0 0 -
People 10 674 352 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 16197 352 - 0 0

Hourly Analysis Program v4.90 Page 5 of 11


Space Design Load Summary for A06-RDC-Commerce 1
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:12

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A06-RDC-Commerce 1 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 32,0 °C / 27,0 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 49 m² 9440 - 49 m² - -
Wall Transmission 23 m² 409 - 23 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 49 m² 675 - 49 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 70 m² 0 - 70 m² 0 -
Partitions 23 m² 99 - 23 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1400 W 1400 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 3500 W 3500 - 0 0 -
People 10 674 352 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 16197 352 - 0 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A06-RDC-Commerce 1 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NW EXPOSURE
WALL 16 1,471 - 242 - 0
WINDOW 1 32 1,700 0,811 450 7299 0
NE EXPOSURE
WALL 8 1,471 - 168 - 0
WINDOW 1 16 1,700 0,811 225 2141 0

Hourly Analysis Program v4.90 Page 6 of 11


Hourly Air System Design Day Loads for A06-RDC-Commerce 1
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:12

DESIGN MONTH: JULY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 23,4 900 10,6 10,9 0,0 0,0 0,0 0,0 0,0 0,0
0100 22,8 873 10,2 10,6 0,0 0,0 0,0 0,0 0,0 0,0
0200 22,2 847 9,9 10,2 0,0 0,0 0,0 0,0 0,0 0,0
0300 21,8 823 9,6 9,9 0,0 0,0 0,0 0,0 0,0 0,0
0400 21,4 801 9,3 9,7 0,0 0,0 0,0 0,0 0,0 0,0
0500 21,3 781 9,1 9,4 0,0 0,0 0,0 0,0 0,0 0,0
0600 21,5 793 9,2 9,6 0,0 0,0 0,0 0,0 0,0 0,0
0700 22,1 891 10,4 10,8 0,0 0,0 0,0 0,0 0,0 0,0
0800 23,2 944 11,1 11,4 0,0 0,0 0,0 0,0 0,0 0,0
0900 24,7 977 11,5 11,9 0,0 0,0 0,0 0,0 0,0 0,0
1000 26,4 995 11,7 12,1 0,0 0,0 0,0 0,0 0,0 0,0
1100 28,4 1001 11,8 12,2 0,0 0,0 0,0 0,0 0,0 0,0
1200 30,2 1037 12,3 12,6 0,0 0,0 0,0 0,0 0,0 0,0
1300 31,6 1112 13,2 13,6 0,0 0,0 0,0 0,0 0,0 0,0
1400 32,6 1198 14,3 14,7 0,0 0,0 0,0 0,0 0,0 0,0
1500 32,9 1269 15,2 15,6 0,0 0,0 0,0 0,0 0,0 0,0
1600 32,6 1304 15,7 16,0 0,0 0,0 0,0 0,0 0,0 0,0
1700 31,7 1255 15,0 15,4 0,0 0,0 0,0 0,0 0,0 0,0
1800 30,5 1096 13,0 13,3 0,0 0,0 0,0 0,0 0,0 0,0
1900 29,0 1059 12,5 12,9 0,0 0,0 0,0 0,0 0,0 0,0
2000 27,4 1024 12,1 12,4 0,0 0,0 0,0 0,0 0,0 0,0
2100 26,2 991 11,7 12,0 0,0 0,0 0,0 0,0 0,0 0,0
2200 25,0 959 11,3 11,6 0,0 0,0 0,0 0,0 0,0 0,0
2300 24,1 928 10,9 11,2 0,0 0,0 0,0 0,0 0,0 0,0

Hourly Analysis Program v4.90 Page 7 of 11


Hourly Zone Loads for A06-RDC-Commerce 1
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:12

ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 23,4 22,5 51 900,0 10563,8 10550,4 0,0 0,0 0,0
0100 22,8 22,5 51 873,3 10227,9 10220,1 0,0 0,0 0,0
0200 22,2 22,5 51 847,5 9905,5 9902,4 0,0 0,0 0,0
0300 21,8 22,4 52 823,4 9606,9 9607,2 0,0 0,0 0,0
0400 21,4 22,4 52 801,0 9330,7 9333,4 0,0 0,0 0,0
0500 21,3 22,4 52 780,6 9081,1 9085,1 0,0 0,0 0,0
0600 21,5 22,4 52 792,8 9243,6 9232,8 0,0 0,0 0,0
0700 22,1 22,5 51 890,7 10501,2 10434,7 0,0 0,0 0,0
0800 23,2 22,5 51 944,0 11187,5 11095,2 0,0 0,0 0,0
0900 24,7 22,5 51 976,8 11609,9 11504,3 0,0 0,0 0,0
1000 26,4 22,6 51 994,7 11838,4 11727,9 0,0 0,0 0,0
1100 28,4 22,6 51 1000,7 11911,2 11802,1 0,0 0,0 0,0
1200 30,2 22,6 51 1036,7 12377,6 12254,0 0,0 0,0 0,0
1300 31,6 22,6 51 1112,2 13364,0 13207,4 0,0 0,0 0,0
1400 32,6 22,7 50 1198,0 14493,2 14301,9 0,0 0,0 0,0
1500 32,9 22,7 50 1268,8 15427,0 15212,4 0,0 0,0 0,0
1600 32,6 22,7 50 1304,1 15887,9 15670,5 0,0 0,0 0,0
1700 31,7 22,7 50 1254,6 15205,7 15029,9 0,0 0,0 0,0
1800 30,5 22,6 51 1095,5 13079,3 12995,7 0,0 0,0 0,0
1900 29,0 22,6 51 1059,1 12604,6 12536,3 0,0 0,0 0,0
2000 27,4 22,6 51 1024,0 12147,7 12094,8 0,0 0,0 0,0
2100 26,2 22,5 51 990,7 11717,7 11677,6 0,0 0,0 0,0
2200 25,0 22,5 51 958,6 11306,0 11276,8 0,0 0,0 0,0
2300 24,1 22,5 51 928,3 10921,2 10900,8 0,0 0,0 0,0

Hourly Analysis Program v4.90 Page 8 of 11


System Psychrometrics for A06-RDC-Commerce 1
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:12

June DESIGN COOLING DAY, 1600

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 32,0 0,02059 0 400 0 0
Vent - Return Mixing Outlet 22,8 0,00864 1328 1464 - -
Preheat Coil Outlet 22,8 0,00864 1328 1464 0 -
Central Cooling Coil Outlet 12,8 0,00855 1328 1464 15976 365
Supply Fan Outlet 12,8 0,00855 1328 1464 0 -
Cold Supply Duct Outlet 12,8 0,00855 1328 1464 - -
Zone Air - 22,8 0,00864 1328 1464 15976 352
Return Plenum Outlet 22,8 0,00864 1328 1464 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 16197 Cooling 15976 22,8 1328 1464 0 0

Hourly Analysis Program v4.90 Page 9 of 11


System Psychrometrics for A06-RDC-Commerce 1
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:12

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 22,0 0,01667 0 400 0 0
Vent - Return Mixing Outlet 20,2 0,00866 15 800 - -
Preheat Coil Outlet 20,2 0,00866 15 800 0 -
Central Cooling Coil Outlet 12,8 0,00866 15 800 131 0
Supply Fan Outlet 12,8 0,00866 15 800 0 -
Cold Supply Duct Outlet 12,8 0,00866 15 800 - -
Zone Air - 20,2 0,00866 15 800 131 0
Return Plenum Outlet 20,2 0,00866 15 800 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 0 Heating 131 20,2 15 800 0 0

Hourly Analysis Program v4.90 Page 10 of 11


Psychrometric Analysis for A06-RDC-Commerce 1
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:12

Location: OUIDAH, BENIN


Altitude: 5,8 m.
Data for: June DESIGN COOLING DAY, 1600

1. Central Cooling Coil Outlet


2. Supply Fan Outlet
3. Room Air 0,024
0,022
0,020

Specific Humidity ( kg/kg )


0,018
0,016
0,014
0,012

12 3
0,010
0,008
0,006
0,004
0,002
0,000
0 5 10 15 20 25 30 35
Temperature ( °C )

Hourly Analysis Program v4.90 Page 11 of 11


Air System Sizing Summary for A06-RDC-Hall d'acceuil 1
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:16

Air System Information


Air System Name ............... A06-RDC-Hall d'acceuil 1 Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area .............................................................. 106,0 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ....................................................... 26,0 kW Load occurs at ................................................. Dec 1600
Sensible coil load .................................................. 25,6 kW OA DB / WB ................................................... 27,6 / 24,2 °C
Coil L/s at Dec 1600 ............................................ 2130 L/s Entering DB / WB ........................................... 22,8 / 16,0 °C
Max block L/s at Dec 1600 ................................... 2337 L/s Leaving DB / WB ........................................... 12,8 / 12,1 °C
Sum of peak zone L/s .......................................... 2337 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,986 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 4,1 Resulting RH .............................................................. 50 %
W/m² .................................................................. 245,2 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K

Preheat Coil Sizing Data


No heating coil loads occurred during this calculation.

Supply Fan Sizing Data

Actual max L/s at Dec 1600 ................................. 2337 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ........................................................ 2335 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 22,04 L/(s-m²) Fan static ...................................................................... 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s ..................................................... 0 L/s L/s/person ................................................................ 0,00 L/s/person
L/(s-m²) ................................................................. 0,00 L/(s-m²)

Hourly Analysis Program v4.90 Page 1 of 11


Zone Sizing Summary for A06-RDC-Hall d'acceuil 1
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:16

Air System Information


Air System Name ............... A06-RDC-Hall d'acceuil 1 Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area .............................................................. 106,0 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 26,0 2337 23 Dec 1600 0,0 106,0 22,04

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
A06-RDC-Hall d'acceuil 1 1 26,0 Dec 1600 2337 0,0 106,0 22,04

Hourly Analysis Program v4.90 Page 2 of 11


Ventilation Sizing Summary for A06-RDC-Hall d'acceuil 1
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:16

1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 L/s

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (m²) Occupants (L/s) (L/s/person) (L/(s-m²)) (L/s) (% of supply) (L/s)
Zone 1
A06-RDC-Hall d'acceuil 1 1 106,0 10,0 2336,7 0,00 0,00 0,0 0,0 0,0
Totals (incl. Space Multipliers) 2336,7 0,0

Hourly Analysis Program v4.90 Page 3 of 11


Air System Design Load Summary for A06-RDC-Hall d'acceuil 1
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:16

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Dec 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 27,6 °C / 24,2 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 81 m² 16933 - 81 m² - -
Wall Transmission 39 m² 418 - 39 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 81 m² 512 - 81 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 106 m² 0 - 106 m² 0 -
Partitions 23 m² 40 - 23 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 2120 W 2120 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 5300 W 5300 - 0 0 -
People 10 674 352 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 25997 352 - 0 0
Zone Conditioning - 25627 352 - -209 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 2130 L/s 0 - 23 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 2130 L/s 0 - 23 L/s 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 25627 352 - -209 0
Central Cooling Coil - 25627 368 - -209 0
Preheat Coil - 0 - - 0 -
Terminal Reheat Coils - 0 - - 0 -
>> Total Conditioning - 25627 368 - -209 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 4 of 11


Zone Design Load Summary for A06-RDC-Hall d'acceuil 1
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:16

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Dec 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 27,6 °C / 24,2 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 81 m² 16933 - 81 m² - -
Wall Transmission 39 m² 418 - 39 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 81 m² 512 - 81 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 106 m² 0 - 106 m² 0 -
Partitions 23 m² 40 - 23 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 2120 W 2120 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 5300 W 5300 - 0 0 -
People 10 674 352 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 25997 352 - 0 0

Hourly Analysis Program v4.90 Page 5 of 11


Space Design Load Summary for A06-RDC-Hall d'acceuil 1
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:16

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A06-RDC-Hall d'acceuil 1 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 27,6 °C / 24,2 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 81 m² 16933 - 81 m² - -
Wall Transmission 39 m² 418 - 39 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 81 m² 512 - 81 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 106 m² 0 - 106 m² 0 -
Partitions 23 m² 40 - 23 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 2120 W 2120 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 5300 W 5300 - 0 0 -
People 10 674 352 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 25997 352 - 0 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A06-RDC-Hall d'acceuil 1 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NW EXPOSURE
WALL 8 1,471 - 17 - 0
WINDOW 1 16 1,700 0,811 102 1129 0
SW EXPOSURE
WALL 23 1,471 - 261 - 0
WINDOW 1 49 1,700 0,811 307 13335 0
SE EXPOSURE
WALL 8 1,471 - 140 - 0
WINDOW 1 16 1,700 0,811 102 2468 0

Hourly Analysis Program v4.90 Page 6 of 11


Hourly Air System Design Day Loads for A06-RDC-Hall d'acceuil 1
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:16

DESIGN MONTH: JULY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 23,4 1164 13,5 13,9 0,0 0,0 0,0 0,0 0,0 0,0
0100 22,8 1134 13,1 13,5 0,0 0,0 0,0 0,0 0,0 0,0
0200 22,2 1105 12,8 13,1 0,0 0,0 0,0 0,0 0,0 0,0
0300 21,8 1077 12,5 12,8 0,0 0,0 0,0 0,0 0,0 0,0
0400 21,4 1052 12,2 12,5 0,0 0,0 0,0 0,0 0,0 0,0
0500 21,3 1030 11,9 12,2 0,0 0,0 0,0 0,0 0,0 0,0
0600 21,5 1030 11,9 12,2 0,0 0,0 0,0 0,0 0,0 0,0
0700 22,1 1100 12,7 13,1 0,0 0,0 0,0 0,0 0,0 0,0
0800 23,2 1146 13,3 13,7 0,0 0,0 0,0 0,0 0,0 0,0
0900 24,7 1181 13,7 14,1 0,0 0,0 0,0 0,0 0,0 0,0
1000 26,4 1207 14,0 14,4 0,0 0,0 0,0 0,0 0,0 0,0
1100 28,4 1242 14,4 14,8 0,0 0,0 0,0 0,0 0,0 0,0
1200 30,2 1298 15,1 15,5 0,0 0,0 0,0 0,0 0,0 0,0
1300 31,6 1367 16,0 16,4 0,0 0,0 0,0 0,0 0,0 0,0
1400 32,6 1473 17,3 17,6 0,0 0,0 0,0 0,0 0,0 0,0
1500 32,9 1579 18,6 19,0 0,0 0,0 0,0 0,0 0,0 0,0
1600 32,6 1638 19,3 19,7 0,0 0,0 0,0 0,0 0,0 0,0
1700 31,7 1580 18,6 19,0 0,0 0,0 0,0 0,0 0,0 0,0
1800 30,5 1388 16,2 16,6 0,0 0,0 0,0 0,0 0,0 0,0
1900 29,0 1346 15,7 16,1 0,0 0,0 0,0 0,0 0,0 0,0
2000 27,4 1306 15,2 15,6 0,0 0,0 0,0 0,0 0,0 0,0
2100 26,2 1268 14,8 15,1 0,0 0,0 0,0 0,0 0,0 0,0
2200 25,0 1231 14,3 14,7 0,0 0,0 0,0 0,0 0,0 0,0
2300 24,1 1196 13,9 14,2 0,0 0,0 0,0 0,0 0,0 0,0

Hourly Analysis Program v4.90 Page 7 of 11


Hourly Zone Loads for A06-RDC-Hall d'acceuil 1
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:16

ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 23,4 22,4 51 1164,4 13536,1 13506,6 0,0 0,0 0,0
0100 22,8 22,4 52 1134,2 13164,3 13141,0 0,0 0,0 0,0
0200 22,2 22,4 52 1104,8 12804,5 12786,5 0,0 0,0 0,0
0300 21,8 22,4 52 1077,4 12471,3 12457,3 0,0 0,0 0,0
0400 21,4 22,4 52 1052,1 12164,0 12152,9 0,0 0,0 0,0
0500 21,3 22,3 52 1029,5 11891,5 11881,8 0,0 0,0 0,0
0600 21,5 22,3 52 1030,3 11910,4 11891,3 0,0 0,0 0,0
0700 22,1 22,4 52 1099,9 12786,2 12727,3 0,0 0,0 0,0
0800 23,2 22,4 51 1146,4 13370,8 13288,4 0,0 0,0 0,0
0900 24,7 22,4 51 1180,5 13799,6 13701,5 0,0 0,0 0,0
1000 26,4 22,4 51 1207,5 14137,3 14028,4 0,0 0,0 0,0
1100 28,4 22,4 51 1241,8 14567,8 14445,7 0,0 0,0 0,0
1200 30,2 22,4 51 1298,3 15279,9 15135,4 0,0 0,0 0,0
1300 31,6 22,5 51 1367,4 16152,4 15982,1 0,0 0,0 0,0
1400 32,6 22,5 51 1472,5 17490,3 17279,6 0,0 0,0 0,0
1500 32,9 22,5 51 1579,2 18853,3 18605,8 0,0 0,0 0,0
1600 32,6 22,6 51 1637,9 19598,2 19340,7 0,0 0,0 0,0
1700 31,7 22,5 51 1580,5 18833,5 18622,2 0,0 0,0 0,0
1800 30,5 22,5 51 1388,0 16343,7 16236,0 0,0 0,0 0,0
1900 29,0 22,5 51 1346,4 15814,7 15723,9 0,0 0,0 0,0
2000 27,4 22,4 51 1305,9 15302,1 15228,5 0,0 0,0 0,0
2100 26,2 22,4 51 1267,8 14821,8 14762,5 0,0 0,0 0,0
2200 25,0 22,4 51 1230,9 14360,6 14313,5 0,0 0,0 0,0
2300 24,1 22,4 51 1196,4 13931,7 13894,3 0,0 0,0 0,0

Hourly Analysis Program v4.90 Page 8 of 11


System Psychrometrics for A06-RDC-Hall d'acceuil 1
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:16

December DESIGN COOLING DAY, 1600

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 27,6 0,01774 0 400 0 0
Vent - Return Mixing Outlet 22,8 0,00861 2130 1214 - -
Preheat Coil Outlet 22,8 0,00861 2130 1214 0 -
Central Cooling Coil Outlet 12,8 0,00855 2130 1214 25627 368
Supply Fan Outlet 12,8 0,00855 2130 1214 0 -
Cold Supply Duct Outlet 12,8 0,00855 2130 1214 - -
Zone Air - 22,8 0,00860 2130 1214 25627 352
Return Plenum Outlet 22,8 0,00860 2130 1214 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 25997 Cooling 25627 22,8 2130 1214 0 0

Hourly Analysis Program v4.90 Page 9 of 11


System Psychrometrics for A06-RDC-Hall d'acceuil 1
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:16

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 22,0 0,01667 0 400 0 0
Vent - Return Mixing Outlet 20,2 0,00865 23 800 - -
Preheat Coil Outlet 20,2 0,00865 23 800 0 -
Central Cooling Coil Outlet 12,8 0,00865 23 800 209 0
Supply Fan Outlet 12,8 0,00865 23 800 0 -
Cold Supply Duct Outlet 12,8 0,00865 23 800 - -
Zone Air - 20,2 0,00865 23 800 209 0
Return Plenum Outlet 20,2 0,00865 23 800 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 0 Heating 209 20,2 23 800 0 0

Hourly Analysis Program v4.90 Page 10 of 11


Psychrometric Analysis for A06-RDC-Hall d'acceuil 1
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:16

Location: OUIDAH, BENIN


Altitude: 5,8 m.
Data for: December DESIGN COOLING DAY, 1600
0,020
1. Central Cooling Coil Outlet
2. Supply Fan Outlet
3. Room Air
0,018

0,016

Specific Humidity ( kg/kg )


0,014

0,012

0,010
12 3
0,008

0,006

0,004

0,002

0,000
0 5 10 15 20 25 30 35
Temperature ( °C )

Hourly Analysis Program v4.90 Page 11 of 11


Air System Sizing Summary for A06-RDC-Commerce 3
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:14

Air System Information


Air System Name ................... A06-RDC-Commerce 3 Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area ................................................................ 67,8 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ....................................................... 14,0 kW Load occurs at ................................................. Nov 0900
Sensible coil load .................................................. 13,6 kW OA DB / WB ................................................... 20,8 / 20,5 °C
Coil L/s at Nov 0900 ............................................ 1132 L/s Entering DB / WB ........................................... 22,8 / 16,1 °C
Max block L/s at Nov 0900 ................................... 1246 L/s Leaving DB / WB ........................................... 12,8 / 12,1 °C
Sum of peak zone L/s .......................................... 1246 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,975 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 4,9 Resulting RH .............................................................. 50 %
W/m² .................................................................. 206,1 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K

Preheat Coil Sizing Data


No heating coil loads occurred during this calculation.

Supply Fan Sizing Data

Actual max L/s at Nov 0900 ................................. 1246 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ........................................................ 1245 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 18,37 L/(s-m²) Fan static ...................................................................... 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s ..................................................... 0 L/s L/s/person ................................................................ 0,00 L/s/person
L/(s-m²) ................................................................. 0,00 L/(s-m²)

Hourly Analysis Program v4.90 Page 1 of 11


Zone Sizing Summary for A06-RDC-Commerce 3
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:14

Air System Information


Air System Name ................... A06-RDC-Commerce 3 Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area ................................................................ 67,8 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 13,9 1246 12 Nov 0900 0,0 67,8 18,37

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
A06-RDC-Commerce 3 1 13,9 Nov 0900 1246 0,0 67,8 18,37

Hourly Analysis Program v4.90 Page 2 of 11


Ventilation Sizing Summary for A06-RDC-Commerce 3
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:14

1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 L/s

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (m²) Occupants (L/s) (L/s/person) (L/(s-m²)) (L/s) (% of supply) (L/s)
Zone 1
A06-RDC-Commerce 3 1 67,8 10,0 1245,5 0,00 0,00 0,0 0,0 0,0
Totals (incl. Space Multipliers) 1245,5 0,0

Hourly Analysis Program v4.90 Page 3 of 11


Air System Design Load Summary for A06-RDC-Commerce 3
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:14

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Nov 0900 HEATING DATA AT DES HTG
COOLING OA DB / WB 20,8 °C / 20,5 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 44 m² 8372 - 44 m² - -
Wall Transmission 20 m² 170 - 20 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 44 m² -86 - 44 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 68 m² 0 - 68 m² 0 -
Partitions 23 m² -19 - 23 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1356 W 1356 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 3390 W 3390 - 0 0 -
People 10 674 352 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 13857 352 - 0 0
Zone Conditioning - 13618 352 - -113 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 1132 L/s 0 - 12 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 1132 L/s 0 - 12 L/s 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 13618 352 - -113 0
Central Cooling Coil - 13618 354 - -113 0
Preheat Coil - 0 - - 0 -
Terminal Reheat Coils - 0 - - 0 -
>> Total Conditioning - 13618 354 - -113 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 4 of 11


Zone Design Load Summary for A06-RDC-Commerce 3
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:14

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Nov 0900 HEATING DATA AT DES HTG
COOLING OA DB / WB 20,8 °C / 20,5 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 44 m² 8372 - 44 m² - -
Wall Transmission 20 m² 170 - 20 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 44 m² -86 - 44 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 68 m² 0 - 68 m² 0 -
Partitions 23 m² -19 - 23 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1356 W 1356 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 3390 W 3390 - 0 0 -
People 10 674 352 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 13857 352 - 0 0

Hourly Analysis Program v4.90 Page 5 of 11


Space Design Load Summary for A06-RDC-Commerce 3
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:14

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A06-RDC-Commerce 3 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Nov 0900 HEATING DATA AT DES HTG
COOLING OA DB / WB 20,8 °C / 20,5 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 44 m² 8372 - 44 m² - -
Wall Transmission 20 m² 170 - 20 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 44 m² -86 - 44 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 68 m² 0 - 68 m² 0 -
Partitions 23 m² -19 - 23 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1356 W 1356 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 3390 W 3390 - 0 0 -
People 10 674 352 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 13857 352 - 0 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A06-RDC-Commerce 3 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NE EXPOSURE
WALL 4 1,471 - 15 - 0
WINDOW 1 8 1,700 0,811 -16 459 0
E EXPOSURE
WALL 6 1,471 - 47 - 0
WINDOW 1 12 1,700 0,811 -23 2329 0
SE EXPOSURE
WALL 11 1,471 - 108 - 0
WINDOW 1 24 1,700 0,811 -47 5584 0

Hourly Analysis Program v4.90 Page 6 of 11


Hourly Air System Design Day Loads for A06-RDC-Commerce 3
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:14

DESIGN MONTH: JULY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 23,4 707 8,2 8,6 0,0 0,0 0,0 0,0 0,0 0,0
0100 22,8 691 8,0 8,4 0,0 0,0 0,0 0,0 0,0 0,0
0200 22,2 675 7,9 8,2 0,0 0,0 0,0 0,0 0,0 0,0
0300 21,8 660 7,7 8,0 0,0 0,0 0,0 0,0 0,0 0,0
0400 21,4 647 7,5 7,9 0,0 0,0 0,0 0,0 0,0 0,0
0500 21,3 635 7,4 7,7 0,0 0,0 0,0 0,0 0,0 0,0
0600 21,5 676 7,9 8,2 0,0 0,0 0,0 0,0 0,0 0,0
0700 22,1 853 10,1 10,4 0,0 0,0 0,0 0,0 0,0 0,0
0800 23,2 936 11,1 11,5 0,0 0,0 0,0 0,0 0,0 0,0
0900 24,7 966 11,5 11,9 0,0 0,0 0,0 0,0 0,0 0,0
1000 26,4 958 11,4 11,7 0,0 0,0 0,0 0,0 0,0 0,0
1100 28,4 937 11,1 11,5 0,0 0,0 0,0 0,0 0,0 0,0
1200 30,2 926 11,0 11,3 0,0 0,0 0,0 0,0 0,0 0,0
1300 31,6 926 11,0 11,3 0,0 0,0 0,0 0,0 0,0 0,0
1400 32,6 925 11,0 11,3 0,0 0,0 0,0 0,0 0,0 0,0
1500 32,9 916 10,8 11,2 0,0 0,0 0,0 0,0 0,0 0,0
1600 32,6 897 10,6 11,0 0,0 0,0 0,0 0,0 0,0 0,0
1700 31,7 868 10,2 10,6 0,0 0,0 0,0 0,0 0,0 0,0
1800 30,5 831 9,8 10,1 0,0 0,0 0,0 0,0 0,0 0,0
1900 29,0 808 9,5 9,8 0,0 0,0 0,0 0,0 0,0 0,0
2000 27,4 785 9,2 9,5 0,0 0,0 0,0 0,0 0,0 0,0
2100 26,2 763 8,9 9,3 0,0 0,0 0,0 0,0 0,0 0,0
2200 25,0 743 8,7 9,0 0,0 0,0 0,0 0,0 0,0 0,0
2300 24,1 724 8,5 8,8 0,0 0,0 0,0 0,0 0,0 0,0

Hourly Analysis Program v4.90 Page 7 of 11


Hourly Zone Loads for A06-RDC-Commerce 3
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:14

ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 23,4 22,5 52 706,8 8258,3 8248,2 0,0 0,0 0,0
0100 22,8 22,4 52 690,5 8056,9 8049,3 0,0 0,0 0,0
0200 22,2 22,4 52 674,8 7862,7 7857,1 0,0 0,0 0,0
0300 21,8 22,4 52 660,3 7685,1 7680,7 0,0 0,0 0,0
0400 21,4 22,4 52 647,0 7522,9 7519,1 0,0 0,0 0,0
0500 21,3 22,4 52 635,2 7379,8 7375,9 0,0 0,0 0,0
0600 21,5 22,4 52 675,9 7904,3 7871,0 0,0 0,0 0,0
0700 22,1 22,6 51 852,5 10187,7 10051,9 0,0 0,0 0,0
0800 23,2 22,6 51 935,8 11272,3 11100,3 0,0 0,0 0,0
0900 24,7 22,6 51 966,4 11664,0 11488,0 0,0 0,0 0,0
1000 26,4 22,6 51 957,7 11535,0 11377,0 0,0 0,0 0,0
1100 28,4 22,6 51 936,8 11249,1 11113,0 0,0 0,0 0,0
1200 30,2 22,6 51 926,1 11099,9 10976,9 0,0 0,0 0,0
1300 31,6 22,6 51 926,4 11098,3 10980,7 0,0 0,0 0,0
1400 32,6 22,6 51 924,7 11071,3 10959,7 0,0 0,0 0,0
1500 32,9 22,6 51 915,6 10946,6 10844,6 0,0 0,0 0,0
1600 32,6 22,6 51 897,4 10704,2 10615,7 0,0 0,0 0,0
1700 31,7 22,6 51 868,0 10316,8 10246,6 0,0 0,0 0,0
1800 30,5 22,5 51 831,2 9836,4 9786,3 0,0 0,0 0,0
1900 29,0 22,5 51 807,8 9534,9 9494,9 0,0 0,0 0,0
2000 27,4 22,5 51 784,9 9241,6 9210,5 0,0 0,0 0,0
2100 26,2 22,5 51 763,5 8969,5 8945,6 0,0 0,0 0,0
2200 25,0 22,5 52 743,0 8711,4 8693,5 0,0 0,0 0,0
2300 24,1 22,5 52 724,1 8474,4 8461,0 0,0 0,0 0,0

Hourly Analysis Program v4.90 Page 8 of 11


System Psychrometrics for A06-RDC-Commerce 3
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:14

November DESIGN COOLING DAY, 0900

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 20,8 0,01505 0 400 0 0
Vent - Return Mixing Outlet 22,8 0,00866 1132 1578 - -
Preheat Coil Outlet 22,8 0,00866 1132 1578 0 -
Central Cooling Coil Outlet 12,8 0,00855 1132 1578 13618 354
Supply Fan Outlet 12,8 0,00855 1132 1578 0 -
Cold Supply Duct Outlet 12,8 0,00855 1132 1578 - -
Zone Air - 22,8 0,00866 1132 1578 13618 352
Return Plenum Outlet 22,8 0,00866 1132 1578 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 13857 Cooling 13618 22,8 1132 1578 0 0

Hourly Analysis Program v4.90 Page 9 of 11


System Psychrometrics for A06-RDC-Commerce 3
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:14

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 22,0 0,01667 0 400 0 0
Vent - Return Mixing Outlet 20,3 0,00866 12 800 - -
Preheat Coil Outlet 20,3 0,00866 12 800 0 -
Central Cooling Coil Outlet 12,8 0,00866 12 800 113 0
Supply Fan Outlet 12,8 0,00866 12 800 0 -
Cold Supply Duct Outlet 12,8 0,00866 12 800 - -
Zone Air - 20,3 0,00866 12 800 113 0
Return Plenum Outlet 20,3 0,00866 12 800 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 0 Heating 113 20,3 12 800 0 0

Hourly Analysis Program v4.90 Page 10 of 11


Psychrometric Analysis for A06-RDC-Commerce 3
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:14

Location: OUIDAH, BENIN


Altitude: 5,8 m.
Data for: November DESIGN COOLING DAY, 0900
0,020
1. Central Cooling Coil Outlet
2. Supply Fan Outlet
3. Room Air
0,018

0,016

Specific Humidity ( kg/kg )


0,014

0,012

0,010
12 3
0,008

0,006

0,004

0,002

0,000
0 5 10 15 20 25 30 35
Temperature ( °C )

Hourly Analysis Program v4.90 Page 11 of 11


Air System Sizing Summary for A06-RDC-Commerce 4
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:14

Air System Information


Air System Name ................... A06-RDC-Commerce 4 Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area .............................................................. 105,4 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ....................................................... 22,8 kW Load occurs at ................................................. Jun 1600
Sensible coil load .................................................. 22,5 kW OA DB / WB ................................................... 32,0 / 27,0 °C
Coil L/s at Jun 1600 ............................................. 1867 L/s Entering DB / WB ........................................... 22,8 / 16,0 °C
Max block L/s at Jun 1600 ................................... 2049 L/s Leaving DB / WB ........................................... 12,8 / 12,1 °C
Sum of peak zone L/s .......................................... 2049 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,984 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 4,6 Resulting RH .............................................................. 50 %
W/m² .................................................................. 216,7 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K

Preheat Coil Sizing Data


No heating coil loads occurred during this calculation.

Supply Fan Sizing Data

Actual max L/s at Jun 1600 .................................. 2049 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ........................................................ 2048 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 19,44 L/(s-m²) Fan static ...................................................................... 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s ..................................................... 0 L/s L/s/person ................................................................ 0,00 L/s/person
L/(s-m²) ................................................................. 0,00 L/(s-m²)

Hourly Analysis Program v4.90 Page 1 of 11


Zone Sizing Summary for A06-RDC-Commerce 4
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:14

Air System Information


Air System Name ................... A06-RDC-Commerce 4 Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area .............................................................. 105,4 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 22,8 2049 20 Jun 1600 0,0 105,4 19,44

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
A06-RDC-Commerce 4 1 22,8 Jun 1600 2049 0,0 105,4 19,44

Hourly Analysis Program v4.90 Page 2 of 11


Ventilation Sizing Summary for A06-RDC-Commerce 4
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:14

1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 L/s

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (m²) Occupants (L/s) (L/s/person) (L/(s-m²)) (L/s) (% of supply) (L/s)
Zone 1
A06-RDC-Commerce 4 1 105,4 10,0 2049,3 0,00 0,00 0,0 0,0 0,0
Totals (incl. Space Multipliers) 2049,3 0,0

Hourly Analysis Program v4.90 Page 3 of 11


Air System Design Load Summary for A06-RDC-Commerce 4
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:14

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 32,0 °C / 27,0 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 73 m² 12966 - 73 m² - -
Wall Transmission 47 m² 770 - 47 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 73 m² 1012 - 73 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 105 m² 0 - 105 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 2108 W 2108 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 5270 W 5270 - 0 0 -
People 10 674 352 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 22799 352 - 0 0
Zone Conditioning - 22467 352 - -184 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 1867 L/s 0 - 20 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 1867 L/s 0 - 20 L/s 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 22467 352 - -184 0
Central Cooling Coil - 22467 370 - -184 0
Preheat Coil - 0 - - 0 -
Terminal Reheat Coils - 0 - - 0 -
>> Total Conditioning - 22467 370 - -184 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 4 of 11


Zone Design Load Summary for A06-RDC-Commerce 4
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:14

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 32,0 °C / 27,0 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 73 m² 12966 - 73 m² - -
Wall Transmission 47 m² 770 - 47 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 73 m² 1012 - 73 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 105 m² 0 - 105 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 2108 W 2108 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 5270 W 5270 - 0 0 -
People 10 674 352 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 22799 352 - 0 0

Hourly Analysis Program v4.90 Page 5 of 11


Space Design Load Summary for A06-RDC-Commerce 4
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:14

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A06-RDC-Commerce 4 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 32,0 °C / 27,0 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 73 m² 12966 - 73 m² - -
Wall Transmission 47 m² 770 - 47 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 73 m² 1012 - 73 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 105 m² 0 - 105 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 2108 W 2108 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 5270 W 5270 - 0 0 -
People 10 674 352 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 22799 352 - 0 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A06-RDC-Commerce 4 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NW EXPOSURE
WALL 23 1,471 - 363 - 0
WINDOW 1 49 1,700 0,811 675 10948 0
E EXPOSURE
WALL 16 1,471 - 311 - 0
WINDOW 1 8 1,700 0,811 112 951 0
SE EXPOSURE
WALL 8 1,471 - 96 - 0
WINDOW 1 16 1,700 0,811 225 1066 0

Hourly Analysis Program v4.90 Page 6 of 11


Hourly Air System Design Day Loads for A06-RDC-Commerce 4
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:14

DESIGN MONTH: JULY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 23,4 1289 15,1 15,5 0,0 0,0 0,0 0,0 0,0 0,0
0100 22,8 1252 14,7 15,0 0,0 0,0 0,0 0,0 0,0 0,0
0200 22,2 1217 14,2 14,6 0,0 0,0 0,0 0,0 0,0 0,0
0300 21,8 1184 13,8 14,2 0,0 0,0 0,0 0,0 0,0 0,0
0400 21,4 1152 13,4 13,8 0,0 0,0 0,0 0,0 0,0 0,0
0500 21,3 1124 13,1 13,4 0,0 0,0 0,0 0,0 0,0 0,0
0600 21,5 1129 13,2 13,5 0,0 0,0 0,0 0,0 0,0 0,0
0700 22,1 1230 14,4 14,8 0,0 0,0 0,0 0,0 0,0 0,0
0800 23,2 1284 15,1 15,4 0,0 0,0 0,0 0,0 0,0 0,0
0900 24,7 1311 15,4 15,8 0,0 0,0 0,0 0,0 0,0 0,0
1000 26,4 1322 15,5 15,9 0,0 0,0 0,0 0,0 0,0 0,0
1100 28,4 1336 15,7 16,1 0,0 0,0 0,0 0,0 0,0 0,0
1200 30,2 1415 16,7 17,0 0,0 0,0 0,0 0,0 0,0 0,0
1300 31,6 1544 18,3 18,7 0,0 0,0 0,0 0,0 0,0 0,0
1400 32,6 1679 20,0 20,4 0,0 0,0 0,0 0,0 0,0 0,0
1500 32,9 1791 21,5 21,8 0,0 0,0 0,0 0,0 0,0 0,0
1600 32,6 1849 22,2 22,6 0,0 0,0 0,0 0,0 0,0 0,0
1700 31,7 1781 21,4 21,7 0,0 0,0 0,0 0,0 0,0 0,0
1800 30,5 1550 18,4 18,7 0,0 0,0 0,0 0,0 0,0 0,0
1900 29,0 1502 17,8 18,1 0,0 0,0 0,0 0,0 0,0 0,0
2000 27,4 1455 17,2 17,5 0,0 0,0 0,0 0,0 0,0 0,0
2100 26,2 1411 16,6 17,0 0,0 0,0 0,0 0,0 0,0 0,0
2200 25,0 1368 16,1 16,4 0,0 0,0 0,0 0,0 0,0 0,0
2300 24,1 1327 15,6 15,9 0,0 0,0 0,0 0,0 0,0 0,0

Hourly Analysis Program v4.90 Page 7 of 11


Hourly Zone Loads for A06-RDC-Commerce 4
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:14

ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 23,4 22,5 51 1289,0 15143,1 15124,0 0,0 0,0 0,0
0100 22,8 22,5 51 1252,4 14682,5 14672,0 0,0 0,0 0,0
0200 22,2 22,5 51 1217,0 14238,9 14235,7 0,0 0,0 0,0
0300 21,8 22,5 51 1183,6 13822,4 13824,7 0,0 0,0 0,0
0400 21,4 22,4 51 1152,2 13433,2 13439,6 0,0 0,0 0,0
0500 21,3 22,4 51 1123,6 13081,2 13090,0 0,0 0,0 0,0
0600 21,5 22,4 51 1129,5 13168,7 13161,8 0,0 0,0 0,0
0700 22,1 22,5 51 1230,2 14468,4 14398,1 0,0 0,0 0,0
0800 23,2 22,5 51 1283,7 15158,2 15058,5 0,0 0,0 0,0
0900 24,7 22,5 51 1311,2 15511,9 15398,9 0,0 0,0 0,0
1000 26,4 22,5 51 1322,3 15654,1 15537,5 0,0 0,0 0,0
1100 28,4 22,5 51 1335,7 15824,7 15703,3 0,0 0,0 0,0
1200 30,2 22,6 51 1414,8 16851,6 16690,4 0,0 0,0 0,0
1300 31,6 22,6 51 1543,7 18536,3 18313,6 0,0 0,0 0,0
1400 32,6 22,7 50 1678,6 20312,2 20031,5 0,0 0,0 0,0
1500 32,9 22,7 50 1790,5 21793,4 21473,0 0,0 0,0 0,0
1600 32,6 22,7 50 1849,3 22562,4 22234,9 0,0 0,0 0,0
1700 31,7 22,7 50 1781,4 21619,6 21355,2 0,0 0,0 0,0
1800 30,5 22,6 51 1549,9 18513,6 18392,1 0,0 0,0 0,0
1900 29,0 22,6 51 1501,9 17884,8 17785,1 0,0 0,0 0,0
2000 27,4 22,6 51 1455,5 17278,3 17200,9 0,0 0,0 0,0
2100 26,2 22,6 51 1411,2 16704,0 16645,3 0,0 0,0 0,0
2200 25,0 22,5 51 1368,2 16150,8 16108,1 0,0 0,0 0,0
2300 24,1 22,5 51 1327,4 15630,1 15600,5 0,0 0,0 0,0

Hourly Analysis Program v4.90 Page 8 of 11


System Psychrometrics for A06-RDC-Commerce 4
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:14

June DESIGN COOLING DAY, 1600

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 32,0 0,02059 0 400 0 0
Vent - Return Mixing Outlet 22,8 0,00861 1867 1272 - -
Preheat Coil Outlet 22,8 0,00861 1867 1272 0 -
Central Cooling Coil Outlet 12,8 0,00855 1867 1272 22467 370
Supply Fan Outlet 12,8 0,00855 1867 1272 0 -
Cold Supply Duct Outlet 12,8 0,00855 1867 1272 - -
Zone Air - 22,8 0,00861 1867 1272 22467 352
Return Plenum Outlet 22,8 0,00861 1867 1272 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 22799 Cooling 22467 22,8 1867 1272 0 0

Hourly Analysis Program v4.90 Page 9 of 11


System Psychrometrics for A06-RDC-Commerce 4
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:14

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 22,0 0,01667 0 400 0 0
Vent - Return Mixing Outlet 20,2 0,00866 20 800 - -
Preheat Coil Outlet 20,2 0,00866 20 800 0 -
Central Cooling Coil Outlet 12,8 0,00866 20 800 184 0
Supply Fan Outlet 12,8 0,00866 20 800 0 -
Cold Supply Duct Outlet 12,8 0,00866 20 800 - -
Zone Air - 20,2 0,00866 20 800 184 0
Return Plenum Outlet 20,2 0,00866 20 800 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 0 Heating 184 20,2 20 800 0 0

Hourly Analysis Program v4.90 Page 10 of 11


Psychrometric Analysis for A06-RDC-Commerce 4
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:14

Location: OUIDAH, BENIN


Altitude: 5,8 m.
Data for: June DESIGN COOLING DAY, 1600

1. Central Cooling Coil Outlet


2. Supply Fan Outlet
3. Room Air 0,024
0,022
0,020

Specific Humidity ( kg/kg )


0,018
0,016
0,014
0,012

12 3
0,010
0,008
0,006
0,004
0,002
0,000
0 5 10 15 20 25 30 35
Temperature ( °C )

Hourly Analysis Program v4.90 Page 11 of 11


Air System Sizing Summary for A06-RDC-Commerce 5
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:14

Air System Information


Air System Name ................... A06-RDC-Commerce 5 Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area ................................................................ 67,9 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ....................................................... 13,6 kW Load occurs at ................................................. Jun 0900
Sensible coil load .................................................. 13,2 kW OA DB / WB ................................................... 24,1 / 23,8 °C
Coil L/s at Jun 0900 ............................................. 1098 L/s Entering DB / WB ........................................... 22,8 / 16,1 °C
Max block L/s at Jun 0900 ................................... 1206 L/s Leaving DB / WB ........................................... 12,8 / 12,1 °C
Sum of peak zone L/s .......................................... 1206 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,974 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 5,0 Resulting RH .............................................................. 50 %
W/m² .................................................................. 199,7 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K

Preheat Coil Sizing Data


No heating coil loads occurred during this calculation.

Supply Fan Sizing Data

Actual max L/s at Jun 0900 .................................. 1206 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ........................................................ 1205 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 17,76 L/(s-m²) Fan static ...................................................................... 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s ..................................................... 0 L/s L/s/person ................................................................ 0,00 L/s/person
L/(s-m²) ................................................................. 0,00 L/(s-m²)

Hourly Analysis Program v4.90 Page 1 of 11


Zone Sizing Summary for A06-RDC-Commerce 5
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:14

Air System Information


Air System Name ................... A06-RDC-Commerce 5 Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area ................................................................ 67,9 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 13,4 1206 12 Jun 0900 0,0 67,9 17,76

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
A06-RDC-Commerce 5 1 13,4 Jun 0900 1206 0,0 67,9 17,76

Hourly Analysis Program v4.90 Page 2 of 11


Ventilation Sizing Summary for A06-RDC-Commerce 5
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:14

1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 L/s

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (m²) Occupants (L/s) (L/s/person) (L/(s-m²)) (L/s) (% of supply) (L/s)
Zone 1
A06-RDC-Commerce 5 1 67,9 10,0 1205,8 0,00 0,00 0,0 0,0 0,0
Totals (incl. Space Multipliers) 1205,8 0,0

Hourly Analysis Program v4.90 Page 3 of 11


Air System Design Load Summary for A06-RDC-Commerce 5
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:14

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 0900 HEATING DATA AT DES HTG
COOLING OA DB / WB 24,1 °C / 23,8 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 44 m² 7560 - 44 m² - -
Wall Transmission 20 m² 263 - 20 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 44 m² 165 - 44 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 68 m² 0 - 68 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1358 W 1358 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 3395 W 3395 - 0 0 -
People 10 674 352 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 13415 352 - 0 0
Zone Conditioning - 13206 352 - -108 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 1098 L/s 0 - 12 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 1098 L/s 0 - 12 L/s 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 13206 352 - -108 0
Central Cooling Coil - 13206 354 - -108 0
Preheat Coil - 0 - - 0 -
Terminal Reheat Coils - 0 - - 0 -
>> Total Conditioning - 13206 354 - -108 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 4 of 11


Zone Design Load Summary for A06-RDC-Commerce 5
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:14

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 0900 HEATING DATA AT DES HTG
COOLING OA DB / WB 24,1 °C / 23,8 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 44 m² 7560 - 44 m² - -
Wall Transmission 20 m² 263 - 20 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 44 m² 165 - 44 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 68 m² 0 - 68 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1358 W 1358 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 3395 W 3395 - 0 0 -
People 10 674 352 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 13415 352 - 0 0

Hourly Analysis Program v4.90 Page 5 of 11


Space Design Load Summary for A06-RDC-Commerce 5
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:14

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A06-RDC-Commerce 5 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 0900 HEATING DATA AT DES HTG
COOLING OA DB / WB 24,1 °C / 23,8 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 44 m² 7560 - 44 m² - -
Wall Transmission 20 m² 263 - 20 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 44 m² 165 - 44 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 68 m² 0 - 68 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1358 W 1358 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 3395 W 3395 - 0 0 -
People 10 674 352 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 13415 352 - 0 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A06-RDC-Commerce 5 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NE EXPOSURE
WALL 11 1,471 - 148 - 0
WINDOW 1 24 1,700 0,811 90 4766 0
E EXPOSURE
WALL 6 1,471 - 78 - 0
WINDOW 1 12 1,700 0,811 45 2200 0
SE EXPOSURE
WALL 4 1,471 - 37 - 0
WINDOW 1 8 1,700 0,811 30 594 0

Hourly Analysis Program v4.90 Page 6 of 11


Hourly Air System Design Day Loads for A06-RDC-Commerce 5
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:14

DESIGN MONTH: JULY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 23,4 753 8,8 9,2 0,0 0,0 0,0 0,0 0,0 0,0
0100 22,8 735 8,6 8,9 0,0 0,0 0,0 0,0 0,0 0,0
0200 22,2 717 8,4 8,7 0,0 0,0 0,0 0,0 0,0 0,0
0300 21,8 700 8,2 8,5 0,0 0,0 0,0 0,0 0,0 0,0
0400 21,4 685 8,0 8,3 0,0 0,0 0,0 0,0 0,0 0,0
0500 21,3 671 7,8 8,2 0,0 0,0 0,0 0,0 0,0 0,0
0600 21,5 723 8,5 8,8 0,0 0,0 0,0 0,0 0,0 0,0
0700 22,1 943 11,2 11,6 0,0 0,0 0,0 0,0 0,0 0,0
0800 23,2 1048 12,6 12,9 0,0 0,0 0,0 0,0 0,0 0,0
0900 24,7 1094 13,2 13,5 0,0 0,0 0,0 0,0 0,0 0,0
1000 26,4 1092 13,1 13,5 0,0 0,0 0,0 0,0 0,0 0,0
1100 28,4 1059 12,7 13,0 0,0 0,0 0,0 0,0 0,0 0,0
1200 30,2 1024 12,3 12,6 0,0 0,0 0,0 0,0 0,0 0,0
1300 31,6 1011 12,1 12,4 0,0 0,0 0,0 0,0 0,0 0,0
1400 32,6 1003 12,0 12,3 0,0 0,0 0,0 0,0 0,0 0,0
1500 32,9 988 11,8 12,1 0,0 0,0 0,0 0,0 0,0 0,0
1600 32,6 966 11,5 11,8 0,0 0,0 0,0 0,0 0,0 0,0
1700 31,7 933 11,1 11,4 0,0 0,0 0,0 0,0 0,0 0,0
1800 30,5 893 10,6 10,9 0,0 0,0 0,0 0,0 0,0 0,0
1900 29,0 867 10,2 10,6 0,0 0,0 0,0 0,0 0,0 0,0
2000 27,4 841 9,9 10,3 0,0 0,0 0,0 0,0 0,0 0,0
2100 26,2 817 9,6 10,0 0,0 0,0 0,0 0,0 0,0 0,0
2200 25,0 794 9,3 9,7 0,0 0,0 0,0 0,0 0,0 0,0
2300 24,1 773 9,1 9,4 0,0 0,0 0,0 0,0 0,0 0,0

Hourly Analysis Program v4.90 Page 7 of 11


Hourly Zone Loads for A06-RDC-Commerce 5
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:14

ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 23,4 22,5 51 753,3 8828,5 8835,8 0,0 0,0 0,0
0100 22,8 22,5 52 734,8 8596,8 8606,4 0,0 0,0 0,0
0200 22,2 22,5 52 716,9 8374,7 8386,1 0,0 0,0 0,0
0300 21,8 22,5 52 700,2 8168,0 8180,5 0,0 0,0 0,0
0400 21,4 22,5 52 684,6 7976,4 7989,4 0,0 0,0 0,0
0500 21,3 22,4 52 670,6 7805,8 7818,5 0,0 0,0 0,0
0600 21,5 22,5 52 723,0 8486,4 8461,4 0,0 0,0 0,0
0700 22,1 22,6 51 943,2 11373,2 11218,7 0,0 0,0 0,0
0800 23,2 22,7 50 1048,3 12766,9 12566,3 0,0 0,0 0,0
0900 24,7 22,7 50 1093,9 13367,9 13158,7 0,0 0,0 0,0
1000 26,4 22,7 50 1092,5 13330,0 13139,6 0,0 0,0 0,0
1100 28,4 22,7 50 1058,6 12855,3 12699,7 0,0 0,0 0,0
1200 30,2 22,7 50 1024,3 12383,0 12257,4 0,0 0,0 0,0
1300 31,6 22,7 51 1011,0 12197,8 12086,1 0,0 0,0 0,0
1400 32,6 22,7 51 1002,8 12083,0 11981,0 0,0 0,0 0,0
1500 32,9 22,7 51 988,2 11882,2 11792,6 0,0 0,0 0,0
1600 32,6 22,7 51 965,7 11579,3 11505,1 0,0 0,0 0,0
1700 31,7 22,6 51 932,6 11139,1 11084,4 0,0 0,0 0,0
1800 30,5 22,6 51 892,8 10613,6 10580,0 0,0 0,0 0,0
1900 29,0 22,6 51 866,6 10272,8 10249,7 0,0 0,0 0,0
2000 27,4 22,6 51 841,2 9943,6 9929,7 0,0 0,0 0,0
2100 26,2 22,5 51 817,2 9636,6 9630,1 0,0 0,0 0,0
2200 25,0 22,5 51 794,4 9345,6 9345,1 0,0 0,0 0,0
2300 24,1 22,5 51 773,1 9076,4 9080,4 0,0 0,0 0,0

Hourly Analysis Program v4.90 Page 8 of 11


System Psychrometrics for A06-RDC-Commerce 5
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:14

June DESIGN COOLING DAY, 0900

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 24,1 0,01857 0 400 0 0
Vent - Return Mixing Outlet 22,8 0,00866 1098 1603 - -
Preheat Coil Outlet 22,8 0,00866 1098 1603 0 -
Central Cooling Coil Outlet 12,8 0,00855 1098 1603 13206 354
Supply Fan Outlet 12,8 0,00855 1098 1603 0 -
Cold Supply Duct Outlet 12,8 0,00855 1098 1603 - -
Zone Air - 22,8 0,00866 1098 1603 13206 352
Return Plenum Outlet 22,8 0,00866 1098 1603 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 13415 Cooling 13206 22,8 1098 1603 0 0

Hourly Analysis Program v4.90 Page 9 of 11


System Psychrometrics for A06-RDC-Commerce 5
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:14

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 22,0 0,01667 0 400 0 0
Vent - Return Mixing Outlet 20,2 0,00866 12 800 - -
Preheat Coil Outlet 20,2 0,00866 12 800 0 -
Central Cooling Coil Outlet 12,8 0,00866 12 800 108 0
Supply Fan Outlet 12,8 0,00866 12 800 0 -
Cold Supply Duct Outlet 12,8 0,00866 12 800 - -
Zone Air - 20,2 0,00866 12 800 108 0
Return Plenum Outlet 20,2 0,00866 12 800 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 0 Heating 108 20,2 12 800 0 0

Hourly Analysis Program v4.90 Page 10 of 11


Psychrometric Analysis for A06-RDC-Commerce 5
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:14

Location: OUIDAH, BENIN


Altitude: 5,8 m.
Data for: June DESIGN COOLING DAY, 0900
0,020
1. Central Cooling Coil Outlet
2. Supply Fan Outlet
3. Room Air
0,018

0,016

Specific Humidity ( kg/kg )


0,014

0,012

0,010
12 3
0,008

0,006

0,004

0,002

0,000
0 5 10 15 20 25 30 35
Temperature ( °C )

Hourly Analysis Program v4.90 Page 11 of 11


Air System Sizing Summary for A06-RDC-Commerce 6
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:15

Air System Information


Air System Name ................... A06-RDC-Commerce 6 Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area .............................................................. 133,9 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ....................................................... 24,2 kW Load occurs at ................................................. Dec 1500
Sensible coil load .................................................. 23,8 kW OA DB / WB ................................................... 27,9 / 24,3 °C
Coil L/s at Dec 1500 ............................................ 1978 L/s Entering DB / WB ........................................... 22,8 / 16,0 °C
Max block L/s at Dec 1500 ................................... 2165 L/s Leaving DB / WB ........................................... 12,8 / 12,1 °C
Sum of peak zone L/s .......................................... 2165 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,985 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 5,5 Resulting RH .............................................................. 50 %
W/m² .................................................................. 180,5 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K

Preheat Coil Sizing Data


No heating coil loads occurred during this calculation.

Supply Fan Sizing Data

Actual max L/s at Dec 1500 ................................. 2165 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ........................................................ 2163 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 16,17 L/(s-m²) Fan static ...................................................................... 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s ..................................................... 0 L/s L/s/person ................................................................ 0,00 L/s/person
L/(s-m²) ................................................................. 0,00 L/(s-m²)

Hourly Analysis Program v4.90 Page 1 of 11


Zone Sizing Summary for A06-RDC-Commerce 6
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:15

Air System Information


Air System Name ................... A06-RDC-Commerce 6 Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area .............................................................. 133,9 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 24,1 2165 22 Dec 1500 0,0 133,9 16,17

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
A06-RDC-Commerce 6 1 24,1 Dec 1500 2165 0,0 133,9 16,17

Hourly Analysis Program v4.90 Page 2 of 11


Ventilation Sizing Summary for A06-RDC-Commerce 6
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:15

1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 L/s

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (m²) Occupants (L/s) (L/s/person) (L/(s-m²)) (L/s) (% of supply) (L/s)
Zone 1
A06-RDC-Commerce 6 1 133,9 10,0 2165,0 0,00 0,00 0,0 0,0 0,0
Totals (incl. Space Multipliers) 2165,0 0,0

Hourly Analysis Program v4.90 Page 3 of 11


Air System Design Load Summary for A06-RDC-Commerce 6
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:15

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Dec 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 27,9 °C / 24,3 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 61 m² 13246 - 61 m² - -
Wall Transmission 29 m² 400 - 29 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 61 m² 394 - 61 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 134 m² 0 - 134 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 2678 W 2678 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 6695 W 6695 - 0 0 -
People 10 674 352 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 24086 352 - 0 0
Zone Conditioning - 23803 352 - -192 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 1978 L/s 0 - 22 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 1978 L/s 0 - 22 L/s 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 23803 352 - -192 0
Central Cooling Coil - 23803 369 - -192 0
Preheat Coil - 0 - - 0 -
Terminal Reheat Coils - 0 - - 0 -
>> Total Conditioning - 23803 369 - -192 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 4 of 11


Zone Design Load Summary for A06-RDC-Commerce 6
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:15

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Dec 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 27,9 °C / 24,3 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 61 m² 13246 - 61 m² - -
Wall Transmission 29 m² 400 - 29 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 61 m² 394 - 61 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 134 m² 0 - 134 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 2678 W 2678 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 6695 W 6695 - 0 0 -
People 10 674 352 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 24086 352 - 0 0

Hourly Analysis Program v4.90 Page 5 of 11


Space Design Load Summary for A06-RDC-Commerce 6
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:15

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A06-RDC-Commerce 6 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 27,9 °C / 24,3 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 61 m² 13246 - 61 m² - -
Wall Transmission 29 m² 400 - 29 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 61 m² 394 - 61 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 134 m² 0 - 134 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 2678 W 2678 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 6695 W 6695 - 0 0 -
People 10 674 352 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 24086 352 - 0 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A06-RDC-Commerce 6 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 10 1,471 - 97 - 0
WINDOW 1 24 1,700 0,811 158 6353 0
S EXPOSURE
WALL 6 1,471 - 95 - 0
WINDOW 1 12 1,700 0,811 78 2917 0
SE EXPOSURE
WALL 13 1,471 - 208 - 0
WINDOW 1 24 1,700 0,811 158 3976 0

Hourly Analysis Program v4.90 Page 6 of 11


Hourly Air System Design Day Loads for A06-RDC-Commerce 6
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:15

DESIGN MONTH: JULY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 23,4 1124 13,1 13,4 0,0 0,0 0,0 0,0 0,0 0,0
0100 22,8 1107 12,9 13,2 0,0 0,0 0,0 0,0 0,0 0,0
0200 22,2 1091 12,7 13,0 0,0 0,0 0,0 0,0 0,0 0,0
0300 21,8 1075 12,5 12,8 0,0 0,0 0,0 0,0 0,0 0,0
0400 21,4 1061 12,3 12,6 0,0 0,0 0,0 0,0 0,0 0,0
0500 21,3 1048 12,1 12,5 0,0 0,0 0,0 0,0 0,0 0,0
0600 21,5 1060 12,3 12,6 0,0 0,0 0,0 0,0 0,0 0,0
0700 22,1 1141 13,3 13,6 0,0 0,0 0,0 0,0 0,0 0,0
0800 23,2 1187 13,8 14,2 0,0 0,0 0,0 0,0 0,0 0,0
0900 24,7 1212 14,1 14,5 0,0 0,0 0,0 0,0 0,0 0,0
1000 26,4 1223 14,3 14,6 0,0 0,0 0,0 0,0 0,0 0,0
1100 28,4 1242 14,5 14,9 0,0 0,0 0,0 0,0 0,0 0,0
1200 30,2 1266 14,8 15,2 0,0 0,0 0,0 0,0 0,0 0,0
1300 31,6 1286 15,0 15,4 0,0 0,0 0,0 0,0 0,0 0,0
1400 32,6 1319 15,4 15,8 0,0 0,0 0,0 0,0 0,0 0,0
1500 32,9 1351 15,8 16,2 0,0 0,0 0,0 0,0 0,0 0,0
1600 32,6 1362 16,0 16,3 0,0 0,0 0,0 0,0 0,0 0,0
1700 31,7 1329 15,6 15,9 0,0 0,0 0,0 0,0 0,0 0,0
1800 30,5 1252 14,6 15,0 0,0 0,0 0,0 0,0 0,0 0,0
1900 29,0 1228 14,3 14,7 0,0 0,0 0,0 0,0 0,0 0,0
2000 27,4 1205 14,0 14,4 0,0 0,0 0,0 0,0 0,0 0,0
2100 26,2 1183 13,8 14,1 0,0 0,0 0,0 0,0 0,0 0,0
2200 25,0 1162 13,5 13,9 0,0 0,0 0,0 0,0 0,0 0,0
2300 24,1 1142 13,3 13,6 0,0 0,0 0,0 0,0 0,0 0,0

Hourly Analysis Program v4.90 Page 7 of 11


Hourly Zone Loads for A06-RDC-Commerce 6
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:15

ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 23,4 22,4 51 1124,1 13073,9 13062,4 0,0 0,0 0,0
0100 22,8 22,4 51 1107,1 12864,4 12856,3 0,0 0,0 0,0
0200 22,2 22,4 51 1090,5 12661,0 12655,7 0,0 0,0 0,0
0300 21,8 22,4 52 1075,1 12471,8 12468,4 0,0 0,0 0,0
0400 21,4 22,4 52 1060,7 12297,1 12294,9 0,0 0,0 0,0
0500 21,3 22,4 52 1048,2 12145,3 12143,1 0,0 0,0 0,0
0600 21,5 22,4 52 1060,0 12302,4 12286,1 0,0 0,0 0,0
0700 22,1 22,4 51 1141,1 13338,5 13269,5 0,0 0,0 0,0
0800 23,2 22,4 51 1187,1 13923,4 13830,0 0,0 0,0 0,0
0900 24,7 22,4 51 1211,6 14233,1 14130,1 0,0 0,0 0,0
1000 26,4 22,4 51 1222,8 14370,1 14266,1 0,0 0,0 0,0
1100 28,4 22,5 51 1242,3 14616,1 14505,8 0,0 0,0 0,0
1200 30,2 22,5 51 1266,0 14914,4 14796,1 0,0 0,0 0,0
1300 31,6 22,5 51 1286,1 15167,4 15044,2 0,0 0,0 0,0
1400 32,6 22,5 51 1318,8 15582,6 15447,3 0,0 0,0 0,0
1500 32,9 22,5 51 1351,1 15991,1 15845,6 0,0 0,0 0,0
1600 32,6 22,5 51 1362,3 16127,2 15985,1 0,0 0,0 0,0
1700 31,7 22,5 51 1329,4 15691,0 15578,1 0,0 0,0 0,0
1800 30,5 22,5 51 1252,1 14687,9 14626,0 0,0 0,0 0,0
1900 29,0 22,5 51 1228,1 14382,2 14332,1 0,0 0,0 0,0
2000 27,4 22,4 51 1204,7 14084,1 14045,4 0,0 0,0 0,0
2100 26,2 22,4 51 1182,8 13806,9 13777,4 0,0 0,0 0,0
2200 25,0 22,4 51 1161,7 13541,8 13520,0 0,0 0,0 0,0
2300 24,1 22,4 51 1142,1 13297,4 13281,5 0,0 0,0 0,0

Hourly Analysis Program v4.90 Page 8 of 11


System Psychrometrics for A06-RDC-Commerce 6
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:15

December DESIGN COOLING DAY, 1500

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 27,9 0,01775 0 400 0 0
Vent - Return Mixing Outlet 22,8 0,00861 1978 1245 - -
Preheat Coil Outlet 22,8 0,00861 1978 1245 0 -
Central Cooling Coil Outlet 12,8 0,00855 1978 1245 23803 369
Supply Fan Outlet 12,8 0,00855 1978 1245 0 -
Cold Supply Duct Outlet 12,8 0,00855 1978 1245 - -
Zone Air - 22,8 0,00861 1978 1245 23803 352
Return Plenum Outlet 22,8 0,00861 1978 1245 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 24086 Cooling 23803 22,8 1978 1245 0 0

Hourly Analysis Program v4.90 Page 9 of 11


System Psychrometrics for A06-RDC-Commerce 6
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:15

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 22,0 0,01667 0 400 0 0
Vent - Return Mixing Outlet 20,1 0,00864 22 800 - -
Preheat Coil Outlet 20,1 0,00864 22 800 0 -
Central Cooling Coil Outlet 12,8 0,00864 22 800 192 0
Supply Fan Outlet 12,8 0,00864 22 800 0 -
Cold Supply Duct Outlet 12,8 0,00864 22 800 - -
Zone Air - 20,1 0,00864 22 800 192 0
Return Plenum Outlet 20,1 0,00864 22 800 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 0 Heating 192 20,1 22 800 0 0

Hourly Analysis Program v4.90 Page 10 of 11


Psychrometric Analysis for A06-RDC-Commerce 6
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:15

Location: OUIDAH, BENIN


Altitude: 5,8 m.
Data for: December DESIGN COOLING DAY, 1500
0,020
1. Central Cooling Coil Outlet
2. Supply Fan Outlet
3. Room Air
0,018

0,016

Specific Humidity ( kg/kg )


0,014

0,012

0,010
12 3
0,008

0,006

0,004

0,002

0,000
0 5 10 15 20 25 30 35
Temperature ( °C )

Hourly Analysis Program v4.90 Page 11 of 11


Air System Sizing Summary for A06-RDC-Commerce 8
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:15

Air System Information


Air System Name ................... A06-RDC-Commerce 8 Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area ................................................................ 67,9 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ....................................................... 15,0 kW Load occurs at ................................................. Jun 1600
Sensible coil load .................................................. 14,6 kW OA DB / WB ................................................... 32,0 / 27,0 °C
Coil L/s at Jun 1600 ............................................. 1217 L/s Entering DB / WB ........................................... 22,8 / 16,1 °C
Max block L/s at Jun 1600 ................................... 1333 L/s Leaving DB / WB ........................................... 12,8 / 12,1 °C
Sum of peak zone L/s .......................................... 1333 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,976 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 4,5 Resulting RH .............................................................. 50 %
W/m² .................................................................. 221,1 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K

Preheat Coil Sizing Data


No heating coil loads occurred during this calculation.

Supply Fan Sizing Data

Actual max L/s at Jun 1600 .................................. 1333 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ........................................................ 1332 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 19,63 L/(s-m²) Fan static ...................................................................... 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s ..................................................... 0 L/s L/s/person ................................................................ 0,00 L/s/person
L/(s-m²) ................................................................. 0,00 L/(s-m²)

Hourly Analysis Program v4.90 Page 1 of 11


Zone Sizing Summary for A06-RDC-Commerce 8
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:15

Air System Information


Air System Name ................... A06-RDC-Commerce 8 Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area ................................................................ 67,9 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 14,8 1333 13 Jun 1600 0,0 67,9 19,63

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
A06-RDC-Commerce 8 1 14,8 Jun 1600 1333 0,0 67,9 19,63

Hourly Analysis Program v4.90 Page 2 of 11


Ventilation Sizing Summary for A06-RDC-Commerce 8
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:15

1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 L/s

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (m²) Occupants (L/s) (L/s/person) (L/(s-m²)) (L/s) (% of supply) (L/s)
Zone 1
A06-RDC-Commerce 8 1 67,9 10,0 1333,2 0,00 0,00 0,0 0,0 0,0
Totals (incl. Space Multipliers) 1333,2 0,0

Hourly Analysis Program v4.90 Page 3 of 11


Air System Design Load Summary for A06-RDC-Commerce 8
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:15

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 32,0 °C / 27,0 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 44 m² 8429 - 44 m² - -
Wall Transmission 20 m² 360 - 20 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 44 m² 616 - 44 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 68 m² 0 - 68 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1358 W 1358 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 3395 W 3395 - 0 0 -
People 10 674 352 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 14832 352 - 0 0
Zone Conditioning - 14646 352 - -118 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 1217 L/s 0 - 13 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 1217 L/s 0 - 13 L/s 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 14646 352 - -118 0
Central Cooling Coil - 14646 363 - -118 0
Preheat Coil - 0 - - 0 -
Terminal Reheat Coils - 0 - - 0 -
>> Total Conditioning - 14646 363 - -118 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 4 of 11


Zone Design Load Summary for A06-RDC-Commerce 8
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:15

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 32,0 °C / 27,0 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 44 m² 8429 - 44 m² - -
Wall Transmission 20 m² 360 - 20 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 44 m² 616 - 44 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 68 m² 0 - 68 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1358 W 1358 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 3395 W 3395 - 0 0 -
People 10 674 352 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 14832 352 - 0 0

Hourly Analysis Program v4.90 Page 5 of 11


Space Design Load Summary for A06-RDC-Commerce 8
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:15

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A06-RDC-Commerce 8 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 32,0 °C / 27,0 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 44 m² 8429 - 44 m² - -
Wall Transmission 20 m² 360 - 20 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 44 m² 616 - 44 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 68 m² 0 - 68 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1358 W 1358 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 3395 W 3395 - 0 0 -
People 10 674 352 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 14832 352 - 0 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A06-RDC-Commerce 8 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NW EXPOSURE
WALL 11 1,471 - 163 - 0
WINDOW 1 24 1,700 0,811 337 5474 0
N EXPOSURE
WALL 6 1,471 - 113 - 0
WINDOW 1 12 1,700 0,811 167 1884 0
NE EXPOSURE
WALL 4 1,471 - 84 - 0
WINDOW 1 8 1,700 0,811 112 1071 0

Hourly Analysis Program v4.90 Page 6 of 11


Hourly Air System Design Day Loads for A06-RDC-Commerce 8
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:15

DESIGN MONTH: JULY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 23,4 833 9,8 10,1 0,0 0,0 0,0 0,0 0,0 0,0
0100 22,8 810 9,5 9,8 0,0 0,0 0,0 0,0 0,0 0,0
0200 22,2 788 9,2 9,6 0,0 0,0 0,0 0,0 0,0 0,0
0300 21,8 767 9,0 9,3 0,0 0,0 0,0 0,0 0,0 0,0
0400 21,4 748 8,7 9,1 0,0 0,0 0,0 0,0 0,0 0,0
0500 21,3 730 8,5 8,8 0,0 0,0 0,0 0,0 0,0 0,0
0600 21,5 737 8,6 8,9 0,0 0,0 0,0 0,0 0,0 0,0
0700 22,1 811 9,5 9,8 0,0 0,0 0,0 0,0 0,0 0,0
0800 23,2 852 10,0 10,4 0,0 0,0 0,0 0,0 0,0 0,0
0900 24,7 881 10,4 10,7 0,0 0,0 0,0 0,0 0,0 0,0
1000 26,4 902 10,6 11,0 0,0 0,0 0,0 0,0 0,0 0,0
1100 28,4 917 10,8 11,2 0,0 0,0 0,0 0,0 0,0 0,0
1200 30,2 956 11,3 11,7 0,0 0,0 0,0 0,0 0,0 0,0
1300 31,6 1022 12,1 12,5 0,0 0,0 0,0 0,0 0,0 0,0
1400 32,6 1093 13,0 13,4 0,0 0,0 0,0 0,0 0,0 0,0
1500 32,9 1151 13,8 14,1 0,0 0,0 0,0 0,0 0,0 0,0
1600 32,6 1181 14,2 14,5 0,0 0,0 0,0 0,0 0,0 0,0
1700 31,7 1138 13,6 14,0 0,0 0,0 0,0 0,0 0,0 0,0
1800 30,5 1000 11,9 12,2 0,0 0,0 0,0 0,0 0,0 0,0
1900 29,0 969 11,5 11,8 0,0 0,0 0,0 0,0 0,0 0,0
2000 27,4 939 11,1 11,4 0,0 0,0 0,0 0,0 0,0 0,0
2100 26,2 911 10,7 11,1 0,0 0,0 0,0 0,0 0,0 0,0
2200 25,0 883 10,4 10,7 0,0 0,0 0,0 0,0 0,0 0,0
2300 24,1 857 10,1 10,4 0,0 0,0 0,0 0,0 0,0 0,0

Hourly Analysis Program v4.90 Page 7 of 11


Hourly Zone Loads for A06-RDC-Commerce 8
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:15

ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 23,4 22,5 51 833,0 9771,5 9770,3 0,0 0,0 0,0
0100 22,8 22,5 51 810,0 9483,1 9486,6 0,0 0,0 0,0
0200 22,2 22,5 52 787,9 9206,8 9214,1 0,0 0,0 0,0
0300 21,8 22,5 52 767,1 8948,3 8958,4 0,0 0,0 0,0
0400 21,4 22,4 52 747,6 8707,7 8719,8 0,0 0,0 0,0
0500 21,3 22,4 52 730,0 8490,7 8503,7 0,0 0,0 0,0
0600 21,5 22,4 52 737,4 8593,3 8594,6 0,0 0,0 0,0
0700 22,1 22,5 51 810,8 9538,4 9496,0 0,0 0,0 0,0
0800 23,2 22,5 51 852,1 10070,1 10006,7 0,0 0,0 0,0
0900 24,7 22,5 51 880,9 10441,4 10365,0 0,0 0,0 0,0
1000 26,4 22,5 51 901,9 10711,5 10627,4 0,0 0,0 0,0
1100 28,4 22,6 51 917,3 10907,7 10819,4 0,0 0,0 0,0
1200 30,2 22,6 51 956,4 11414,4 11309,8 0,0 0,0 0,0
1300 31,6 22,6 51 1021,8 12269,3 12136,5 0,0 0,0 0,0
1400 32,6 22,7 51 1092,8 13202,3 13041,8 0,0 0,0 0,0
1500 32,9 22,7 50 1151,3 13973,6 13794,8 0,0 0,0 0,0
1600 32,6 22,7 50 1180,5 14352,6 14172,7 0,0 0,0 0,0
1700 31,7 22,7 50 1137,7 13761,6 13618,8 0,0 0,0 0,0
1800 30,5 22,6 51 999,9 11920,2 11859,1 0,0 0,0 0,0
1900 29,0 22,6 51 968,9 11515,0 11467,0 0,0 0,0 0,0
2000 27,4 22,6 51 939,0 11125,5 11090,7 0,0 0,0 0,0
2100 26,2 22,6 51 910,5 10758,4 10734,6 0,0 0,0 0,0
2200 25,0 22,5 51 883,1 10407,0 10392,5 0,0 0,0 0,0
2300 24,1 22,5 51 857,3 10077,9 10070,8 0,0 0,0 0,0

Hourly Analysis Program v4.90 Page 8 of 11


System Psychrometrics for A06-RDC-Commerce 8
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:15

June DESIGN COOLING DAY, 1600

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 32,0 0,02059 0 400 0 0
Vent - Return Mixing Outlet 22,8 0,00865 1217 1524 - -
Preheat Coil Outlet 22,8 0,00865 1217 1524 0 -
Central Cooling Coil Outlet 12,8 0,00855 1217 1524 14646 363
Supply Fan Outlet 12,8 0,00855 1217 1524 0 -
Cold Supply Duct Outlet 12,8 0,00855 1217 1524 - -
Zone Air - 22,8 0,00865 1217 1524 14646 352
Return Plenum Outlet 22,8 0,00865 1217 1524 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 14832 Cooling 14646 22,8 1217 1524 0 0

Hourly Analysis Program v4.90 Page 9 of 11


System Psychrometrics for A06-RDC-Commerce 8
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:15

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 22,0 0,01667 0 400 0 0
Vent - Return Mixing Outlet 20,1 0,00866 13 800 - -
Preheat Coil Outlet 20,1 0,00866 13 800 0 -
Central Cooling Coil Outlet 12,8 0,00866 13 800 118 0
Supply Fan Outlet 12,8 0,00866 13 800 0 -
Cold Supply Duct Outlet 12,8 0,00866 13 800 - -
Zone Air - 20,1 0,00866 13 800 118 0
Return Plenum Outlet 20,1 0,00866 13 800 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 0 Heating 118 20,1 13 800 0 0

Hourly Analysis Program v4.90 Page 10 of 11


Psychrometric Analysis for A06-RDC-Commerce 8
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:15

Location: OUIDAH, BENIN


Altitude: 5,8 m.
Data for: June DESIGN COOLING DAY, 1600

1. Central Cooling Coil Outlet


2. Supply Fan Outlet
3. Room Air 0,024
0,022
0,020

Specific Humidity ( kg/kg )


0,018
0,016
0,014
0,012

12 3
0,010
0,008
0,006
0,004
0,002
0,000
0 5 10 15 20 25 30 35
Temperature ( °C )

Hourly Analysis Program v4.90 Page 11 of 11


Air System Sizing Summary for A06-RDC-Commerce 9
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:16

Air System Information


Air System Name ................... A06-RDC-Commerce 9 Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area ................................................................ 63,1 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ........................................................ 8,7 kW Load occurs at ................................................. Jun 1000
Sensible coil load ................................................... 8,4 kW OA DB / WB ................................................... 25,8 / 25,5 °C
Coil L/s at Jun 1000 .............................................. 697 L/s Entering DB / WB ........................................... 22,8 / 16,1 °C
Max block L/s at Jun 1000 .................................... 763 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s ........................................... 763 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,959 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 7,2 Resulting RH .............................................................. 51 %
W/m² .................................................................. 138,5 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K

Preheat Coil Sizing Data


No heating coil loads occurred during this calculation.

Supply Fan Sizing Data

Actual max L/s at Jun 1000 ................................... 763 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ......................................................... 762 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 12,09 L/(s-m²) Fan static ...................................................................... 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s ..................................................... 0 L/s L/s/person ................................................................ 0,00 L/s/person
L/(s-m²) ................................................................. 0,00 L/(s-m²)

Hourly Analysis Program v4.90 Page 1 of 11


Zone Sizing Summary for A06-RDC-Commerce 9
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:16

Air System Information


Air System Name ................... A06-RDC-Commerce 9 Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area ................................................................ 63,1 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 8,5 763 8 Jun 1000 0,0 63,1 12,09

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
A06-RDC-Commerce 9 1 8,5 Jun 1000 763 0,0 63,1 12,09

Hourly Analysis Program v4.90 Page 2 of 11


Ventilation Sizing Summary for A06-RDC-Commerce 9
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:16

1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 L/s

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (m²) Occupants (L/s) (L/s/person) (L/(s-m²)) (L/s) (% of supply) (L/s)
Zone 1
A06-RDC-Commerce 9 1 63,1 10,0 762,8 0,00 0,00 0,0 0,0 0,0
Totals (incl. Space Multipliers) 762,8 0,0

Hourly Analysis Program v4.90 Page 3 of 11


Air System Design Load Summary for A06-RDC-Commerce 9
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:16

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1000 HEATING DATA AT DES HTG
COOLING OA DB / WB 25,8 °C / 25,5 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 16 m² 3191 - 16 m² - -
Wall Transmission 8 m² 111 - 8 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 16 m² 93 - 16 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 63 m² 0 - 63 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1262 W 1262 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 3155 W 3155 - 0 0 -
People 10 674 352 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 8486 352 - 0 0
Zone Conditioning - 8385 352 - -68 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 697 L/s 0 - 8 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 697 L/s 0 - 8 L/s 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 8385 352 - -68 0
Central Cooling Coil - 8385 356 - -68 0
Preheat Coil - 0 - - 0 -
Terminal Reheat Coils - 0 - - 0 -
>> Total Conditioning - 8385 356 - -68 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 4 of 11


Zone Design Load Summary for A06-RDC-Commerce 9
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:16

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1000 HEATING DATA AT DES HTG
COOLING OA DB / WB 25,8 °C / 25,5 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 16 m² 3191 - 16 m² - -
Wall Transmission 8 m² 111 - 8 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 16 m² 93 - 16 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 63 m² 0 - 63 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1262 W 1262 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 3155 W 3155 - 0 0 -
People 10 674 352 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 8486 352 - 0 0

Hourly Analysis Program v4.90 Page 5 of 11


Space Design Load Summary for A06-RDC-Commerce 9
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:16

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A06-RDC-Commerce 9 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1000 HEATING DATA AT DES HTG
COOLING OA DB / WB 25,8 °C / 25,5 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 16 m² 3191 - 16 m² - -
Wall Transmission 8 m² 111 - 8 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 16 m² 93 - 16 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 63 m² 0 - 63 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1262 W 1262 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 3155 W 3155 - 0 0 -
People 10 674 352 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 8486 352 - 0 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A06-RDC-Commerce 9 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NE EXPOSURE
WALL 8 1,471 - 111 - 0
WINDOW 1 16 1,700 0,811 93 3191 0

Hourly Analysis Program v4.90 Page 6 of 11


Hourly Air System Design Day Loads for A06-RDC-Commerce 9
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:16

DESIGN MONTH: JULY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 23,4 548 6,5 6,8 0,0 0,0 0,0 0,0 0,0 0,0
0100 22,8 541 6,4 6,7 0,0 0,0 0,0 0,0 0,0 0,0
0200 22,2 534 6,3 6,6 0,0 0,0 0,0 0,0 0,0 0,0
0300 21,8 527 6,2 6,6 0,0 0,0 0,0 0,0 0,0 0,0
0400 21,4 521 6,1 6,5 0,0 0,0 0,0 0,0 0,0 0,0
0500 21,3 515 6,1 6,4 0,0 0,0 0,0 0,0 0,0 0,0
0600 21,5 535 6,3 6,7 0,0 0,0 0,0 0,0 0,0 0,0
0700 22,1 621 7,4 7,8 0,0 0,0 0,0 0,0 0,0 0,0
0800 23,2 663 7,9 8,3 0,0 0,0 0,0 0,0 0,0 0,0
0900 24,7 683 8,2 8,6 0,0 0,0 0,0 0,0 0,0 0,0
1000 26,4 687 8,3 8,6 0,0 0,0 0,0 0,0 0,0 0,0
1100 28,4 676 8,1 8,5 0,0 0,0 0,0 0,0 0,0 0,0
1200 30,2 659 7,9 8,2 0,0 0,0 0,0 0,0 0,0 0,0
1300 31,6 650 7,8 8,1 0,0 0,0 0,0 0,0 0,0 0,0
1400 32,6 646 7,7 8,1 0,0 0,0 0,0 0,0 0,0 0,0
1500 32,9 640 7,6 8,0 0,0 0,0 0,0 0,0 0,0 0,0
1600 32,6 631 7,5 7,9 0,0 0,0 0,0 0,0 0,0 0,0
1700 31,7 618 7,4 7,7 0,0 0,0 0,0 0,0 0,0 0,0
1800 30,5 603 7,2 7,5 0,0 0,0 0,0 0,0 0,0 0,0
1900 29,0 592 7,0 7,4 0,0 0,0 0,0 0,0 0,0 0,0
2000 27,4 583 6,9 7,3 0,0 0,0 0,0 0,0 0,0 0,0
2100 26,2 573 6,8 7,1 0,0 0,0 0,0 0,0 0,0 0,0
2200 25,0 564 6,7 7,0 0,0 0,0 0,0 0,0 0,0 0,0
2300 24,1 556 6,6 6,9 0,0 0,0 0,0 0,0 0,0 0,0

Hourly Analysis Program v4.90 Page 7 of 11


Hourly Zone Loads for A06-RDC-Commerce 9
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:16

ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 23,4 22,6 52 548,0 6468,1 6480,8 0,0 0,0 0,0
0100 22,8 22,6 52 540,6 6375,0 6388,6 0,0 0,0 0,0
0200 22,2 22,6 52 533,6 6285,9 6300,1 0,0 0,0 0,0
0300 21,8 22,6 52 527,0 6202,9 6217,3 0,0 0,0 0,0
0400 21,4 22,6 52 520,8 6125,8 6140,1 0,0 0,0 0,0
0500 21,3 22,5 52 515,3 6056,9 6070,7 0,0 0,0 0,0
0600 21,5 22,6 52 535,4 6329,0 6322,4 0,0 0,0 0,0
0700 22,1 22,7 51 620,6 7477,3 7401,8 0,0 0,0 0,0
0800 23,2 22,7 51 662,6 8041,9 7941,9 0,0 0,0 0,0
0900 24,7 22,7 51 683,3 8317,3 8211,3 0,0 0,0 0,0
1000 26,4 22,7 51 687,2 8359,8 8261,4 0,0 0,0 0,0
1100 28,4 22,7 51 676,4 8202,4 8121,9 0,0 0,0 0,0
1200 30,2 22,7 51 658,8 7953,7 7893,8 0,0 0,0 0,0
1300 31,6 22,7 51 650,2 7831,5 7782,2 0,0 0,0 0,0
1400 32,6 22,7 51 646,0 7771,7 7728,3 0,0 0,0 0,0
1500 32,9 22,7 51 639,6 7682,3 7646,0 0,0 0,0 0,0
1600 32,6 22,7 51 630,6 7558,8 7530,7 0,0 0,0 0,0
1700 31,7 22,7 51 617,9 7385,6 7367,6 0,0 0,0 0,0
1800 30,5 22,6 51 602,8 7181,7 7174,4 0,0 0,0 0,0
1900 29,0 22,6 51 592,5 7045,7 7043,7 0,0 0,0 0,0
2000 27,4 22,6 51 582,5 6914,4 6917,1 0,0 0,0 0,0
2100 26,2 22,6 51 573,1 6791,8 6798,1 0,0 0,0 0,0
2200 25,0 22,6 51 564,2 6675,5 6684,7 0,0 0,0 0,0
2300 24,1 22,6 51 555,8 6567,7 6578,9 0,0 0,0 0,0

Hourly Analysis Program v4.90 Page 8 of 11


System Psychrometrics for A06-RDC-Commerce 9
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:16

June DESIGN COOLING DAY, 1000

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 25,8 0,02060 0 400 0 0
Vent - Return Mixing Outlet 22,8 0,00873 697 2065 - -
Preheat Coil Outlet 22,8 0,00873 697 2065 0 -
Central Cooling Coil Outlet 12,8 0,00856 697 2065 8385 356
Supply Fan Outlet 12,8 0,00856 697 2065 0 -
Cold Supply Duct Outlet 12,8 0,00856 697 2065 - -
Zone Air - 22,8 0,00873 697 2065 8385 352
Return Plenum Outlet 22,8 0,00873 697 2065 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 8486 Cooling 8385 22,8 697 2065 0 0

Hourly Analysis Program v4.90 Page 9 of 11


System Psychrometrics for A06-RDC-Commerce 9
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:16

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 22,0 0,01667 0 400 0 0
Vent - Return Mixing Outlet 20,2 0,00866 8 800 - -
Preheat Coil Outlet 20,2 0,00866 8 800 0 -
Central Cooling Coil Outlet 12,8 0,00866 8 800 68 0
Supply Fan Outlet 12,8 0,00866 8 800 0 -
Cold Supply Duct Outlet 12,8 0,00866 8 800 - -
Zone Air - 20,2 0,00866 8 800 68 0
Return Plenum Outlet 20,2 0,00866 8 800 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 0 Heating 68 20,2 8 800 0 0

Hourly Analysis Program v4.90 Page 10 of 11


Psychrometric Analysis for A06-RDC-Commerce 9
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:16

Location: OUIDAH, BENIN


Altitude: 5,8 m.
Data for: June DESIGN COOLING DAY, 1000

1. Central Cooling Coil Outlet


2. Supply Fan Outlet
3. Room Air 0,024
0,022
0,020

Specific Humidity ( kg/kg )


0,018
0,016
0,014
0,012

12 3 0,010
0,008
0,006
0,004
0,002
0,000
0 5 10 15 20 25 30 35
Temperature ( °C )

Hourly Analysis Program v4.90 Page 11 of 11


Air System Sizing Summary for A06-RDC:Commerce 10
Project Name: A06 01/10/2024
Prepared by: nina 03:10

Air System Information


Air System Name ................. A06-RDC:Commerce 10 Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area ................................................................ 34,0 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ........................................................ 8,4 kW Load occurs at ................................................. Sep 0900
Sensible coil load ................................................... 8,0 kW OA DB / WB ................................................... 23,6 / 23,3 °C
Coil L/s at Sep 0900 ............................................. 668 L/s Entering DB / WB ........................................... 22,8 / 16,2 °C
Max block L/s at Sep 0900 .................................... 735 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s ........................................... 735 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,957 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 4,0 Resulting RH .............................................................. 51 %
W/m² .................................................................. 247,0 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K

Preheat Coil Sizing Data


No heating coil loads occurred during this calculation.

Supply Fan Sizing Data

Actual max L/s at Sep 0900 .................................. 735 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ......................................................... 734 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 21,61 L/(s-m²) Fan static ...................................................................... 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s ..................................................... 0 L/s L/s/person ................................................................ 0,00 L/s/person
L/(s-m²) ................................................................. 0,00 L/(s-m²)

Hourly Analysis Program v4.90 Page 1 of 13


Zone Sizing Summary for A06-RDC:Commerce 10
Project Name: A06 01/10/2024
Prepared by: nina 03:10

Air System Information


Air System Name ................. A06-RDC:Commerce 10 Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area ................................................................ 34,0 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 8,2 735 7 Sep 0900 0,0 34,0 21,61

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
A06-RDC-Commerce 10 1 8,2 Sep 0900 735 0,0 34,0 21,61

Hourly Analysis Program v4.90 Page 2 of 13


Ventilation Sizing Summary for A06-RDC:Commerce 10
Project Name: A06 01/10/2024
Prepared by: nina 03:10

1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 L/s

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (m²) Occupants (L/s) (L/s/person) (L/(s-m²)) (L/s) (% of supply) (L/s)
Zone 1
A06-RDC-Commerce 10 1 34,0 10,0 734,8 0,00 0,00 0,0 0,0 0,0
Totals (incl. Space Multipliers) 734,8 0,0

Hourly Analysis Program v4.90 Page 3 of 13


Air System Design Load Summary for A06-RDC:Commerce 10
Project Name: A06 01/10/2024
Prepared by: nina 03:10

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Sep 0900 HEATING DATA AT DES HTG
COOLING OA DB / WB 23,6 °C / 23,3 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 28 m² 4881 - 28 m² - -
Wall Transmission 13 m² 159 - 13 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 28 m² 78 - 28 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 34 m² 0 - 34 m² 0 -
Partitions 24 m² 2 - 24 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 680 W 680 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1700 W 1700 - 0 0 -
People 10 674 352 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 8175 352 - 0 0
Zone Conditioning - 8034 352 - -67 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 668 L/s 0 - 7 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 668 L/s 0 - 7 L/s 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 8034 352 - -67 0
Central Cooling Coil - 8034 364 - -67 0
Preheat Coil - 0 - - 0 -
Terminal Reheat Coils - 0 - - 0 -
>> Total Conditioning - 8034 364 - -67 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 4 of 13


Zone Design Load Summary for A06-RDC:Commerce 10
Project Name: A06 01/10/2024
Prepared by: nina 03:10

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Sep 0900 HEATING DATA AT DES HTG
COOLING OA DB / WB 23,6 °C / 23,3 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 28 m² 4881 - 28 m² - -
Wall Transmission 13 m² 159 - 13 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 28 m² 78 - 28 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 34 m² 0 - 34 m² 0 -
Partitions 24 m² 2 - 24 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 680 W 680 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1700 W 1700 - 0 0 -
People 10 674 352 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 8175 352 - 0 0

Hourly Analysis Program v4.90 Page 5 of 13


Space Design Load Summary for A06-RDC:Commerce 10
Project Name: A06 01/10/2024
Prepared by: nina 03:10

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A06-RDC-Commerce 10 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Sep 0900 HEATING DATA AT DES HTG
COOLING OA DB / WB 23,6 °C / 23,3 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 28 m² 4881 - 28 m² - -
Wall Transmission 13 m² 159 - 13 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 28 m² 78 - 28 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 34 m² 0 - 34 m² 0 -
Partitions 24 m² 2 - 24 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 680 W 680 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1700 W 1700 - 0 0 -
People 10 674 352 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 8175 352 - 0 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A06-RDC-Commerce 10 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NE EXPOSURE
WALL 4 1,471 - 41 - 0
WINDOW 1 8 1,700 0,811 23 1072 0
E EXPOSURE
WALL 6 1,471 - 77 - 0
WINDOW 1 12 1,700 0,811 33 2477 0
SE EXPOSURE
WALL 4 1,471 - 41 - 0
WINDOW 1 8 1,700 0,811 23 1333 0

Hourly Analysis Program v4.90 Page 6 of 13


Hourly Air System Design Day Loads for A06-RDC:Commerce 10
Project Name: A06 01/10/2024
Prepared by: nina 03:10

DESIGN MONTH: JULY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 23,4 436 5,1 5,4 0,0 0,0 0,0 0,0 0,0 0,0
0100 22,8 424 5,0 5,3 0,0 0,0 0,0 0,0 0,0 0,0
0200 22,2 413 4,8 5,2 0,0 0,0 0,0 0,0 0,0 0,0
0300 21,8 402 4,7 5,0 0,0 0,0 0,0 0,0 0,0 0,0
0400 21,4 393 4,6 4,9 0,0 0,0 0,0 0,0 0,0 0,0
0500 21,3 384 4,5 4,8 0,0 0,0 0,0 0,0 0,0 0,0
0600 21,5 416 4,9 5,2 0,0 0,0 0,0 0,0 0,0 0,0
0700 22,1 550 6,5 6,9 0,0 0,0 0,0 0,0 0,0 0,0
0800 23,2 614 7,3 7,7 0,0 0,0 0,0 0,0 0,0 0,0
0900 24,7 640 7,7 8,0 0,0 0,0 0,0 0,0 0,0 0,0
1000 26,4 636 7,6 8,0 0,0 0,0 0,0 0,0 0,0 0,0
1100 28,4 614 7,3 7,7 0,0 0,0 0,0 0,0 0,0 0,0
1200 30,2 599 7,2 7,5 0,0 0,0 0,0 0,0 0,0 0,0
1300 31,6 596 7,1 7,5 0,0 0,0 0,0 0,0 0,0 0,0
1400 32,6 593 7,1 7,4 0,0 0,0 0,0 0,0 0,0 0,0
1500 32,9 586 7,0 7,3 0,0 0,0 0,0 0,0 0,0 0,0
1600 32,6 572 6,8 7,1 0,0 0,0 0,0 0,0 0,0 0,0
1700 31,7 552 6,5 6,9 0,0 0,0 0,0 0,0 0,0 0,0
1800 30,5 526 6,2 6,6 0,0 0,0 0,0 0,0 0,0 0,0
1900 29,0 509 6,0 6,3 0,0 0,0 0,0 0,0 0,0 0,0
2000 27,4 493 5,8 6,2 0,0 0,0 0,0 0,0 0,0 0,0
2100 26,2 477 5,6 6,0 0,0 0,0 0,0 0,0 0,0 0,0
2200 25,0 462 5,4 5,8 0,0 0,0 0,0 0,0 0,0 0,0
2300 24,1 449 5,3 5,6 0,0 0,0 0,0 0,0 0,0 0,0

Hourly Analysis Program v4.90 Page 7 of 13


Hourly Zone Loads for A06-RDC:Commerce 10
Project Name: A06 01/10/2024
Prepared by: nina 03:10

ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 23,4 22,5 52 436,0 5112,9 5099,1 0,0 0,0 0,0
0100 22,8 22,5 52 424,2 4966,1 4954,2 0,0 0,0 0,0
0200 22,2 22,4 52 412,8 4824,8 4814,5 0,0 0,0 0,0
0300 21,8 22,4 53 402,3 4696,4 4687,1 0,0 0,0 0,0
0400 21,4 22,4 53 392,8 4579,6 4570,8 0,0 0,0 0,0
0500 21,3 22,4 53 384,3 4475,8 4467,1 0,0 0,0 0,0
0600 21,5 22,5 52 415,9 4882,0 4853,1 0,0 0,0 0,0
0700 22,1 22,6 51 549,8 6619,7 6519,9 0,0 0,0 0,0
0800 23,2 22,7 51 613,5 7458,0 7332,2 0,0 0,0 0,0
0900 24,7 22,7 51 639,6 7798,6 7667,9 0,0 0,0 0,0
1000 26,4 22,7 51 635,6 7736,8 7616,9 0,0 0,0 0,0
1100 28,4 22,7 51 614,2 7441,7 7340,3 0,0 0,0 0,0
1200 30,2 22,7 51 599,4 7240,2 7151,0 0,0 0,0 0,0
1300 31,6 22,7 51 596,3 7195,0 7110,7 0,0 0,0 0,0
1400 32,6 22,7 51 593,3 7153,3 7073,4 0,0 0,0 0,0
1500 32,9 22,7 51 585,7 7048,9 6975,3 0,0 0,0 0,0
1600 32,6 22,6 51 572,2 6868,8 6803,9 0,0 0,0 0,0
1700 31,7 22,6 51 551,6 6595,6 6542,1 0,0 0,0 0,0
1800 30,5 22,6 52 526,2 6262,4 6221,4 0,0 0,0 0,0
1900 29,0 22,6 52 509,2 6042,7 6008,4 0,0 0,0 0,0
2000 27,4 22,5 52 492,6 5829,1 5800,8 0,0 0,0 0,0
2100 26,2 22,5 52 477,1 5630,9 5607,5 0,0 0,0 0,0
2200 25,0 22,5 52 462,2 5443,0 5423,7 0,0 0,0 0,0
2300 24,1 22,5 52 448,5 5270,3 5254,2 0,0 0,0 0,0

Hourly Analysis Program v4.90 Page 8 of 13


System Psychrometrics for A06-RDC:Commerce 10
Project Name: A06 01/10/2024
Prepared by: nina 03:10

September DESIGN COOLING DAY, 0900

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 23,6 0,01793 0 400 0 0
Vent - Return Mixing Outlet 22,8 0,00875 668 2119 - -
Preheat Coil Outlet 22,8 0,00875 668 2119 0 -
Central Cooling Coil Outlet 12,8 0,00856 668 2119 8034 364
Supply Fan Outlet 12,8 0,00856 668 2119 0 -
Cold Supply Duct Outlet 12,8 0,00856 668 2119 - -
Zone Air - 22,8 0,00874 668 2119 8034 352
Return Plenum Outlet 22,8 0,00874 668 2119 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 8175 Cooling 8034 22,8 668 2119 0 0

Hourly Analysis Program v4.90 Page 9 of 13


System Psychrometrics for A06-RDC:Commerce 10
Project Name: A06 01/10/2024
Prepared by: nina 03:10

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 22,0 0,01667 0 400 0 0
Vent - Return Mixing Outlet 20,4 0,00866 7 800 - -
Preheat Coil Outlet 20,4 0,00866 7 800 0 -
Central Cooling Coil Outlet 12,8 0,00866 7 800 67 0
Supply Fan Outlet 12,8 0,00866 7 800 0 -
Cold Supply Duct Outlet 12,8 0,00866 7 800 - -
Zone Air - 20,4 0,00866 7 800 67 0
Return Plenum Outlet 20,4 0,00866 7 800 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 0 Heating 67 20,4 7 800 0 0

Hourly Analysis Program v4.90 Page 10 of 13


Hourly Air System Design Day Loads for A06-RDC:Commerce 10
Project Name: A06 01/10/2024
Prepared by: nina 03:10

Data for July

Total Cooling Total Heating


8

6
Load ( kW )

0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Hourly Analysis Program v4.90 Page 11 of 13


Hourly Zone Design Day Loads for A06-RDC:Commerce 10
Project Name: A06 01/10/2024
Prepared by: nina 03:10

Zone: Zone 1
Data for July

Zone Sensible Zone Conditioning


8000

7000

6000

5000
W

4000

3000

2000

1000

0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Hourly Analysis Program v4.90 Page 12 of 13


Psychrometric Analysis for A06-RDC:Commerce 10
Project Name: A06 01/10/2024
Prepared by: nina 03:10

Location: OUIDAH, BENIN


Altitude: 5,8 m.
Data for: September DESIGN COOLING DAY, 0900
0,020
1. Central Cooling Coil Outlet
2. Supply Fan Outlet
3. Room Air
0,018

0,016

Specific Humidity ( kg/kg )


0,014

0,012

0,010
12 3

0,008

0,006

0,004

0,002

0,000
0 5 10 15 20 25 30 35
Temperature ( °C )

Hourly Analysis Program v4.90 Page 13 of 13


Air System Sizing Summary for A06-RDC-Bureau chef cuisine
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:11

Air System Information


Air System Name ....... A06-RDC-Bureau chef cuisine Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area ................................................................ 11,5 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ........................................................ 2,1 kW Load occurs at ................................................. Dec 1600
Sensible coil load ................................................... 1,9 kW OA DB / WB ................................................... 27,6 / 24,2 °C
Coil L/s at Dec 1600 ............................................. 161 L/s Entering DB / WB ........................................... 22,7 / 16,3 °C
Max block L/s at Dec 1600 .................................... 179 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s ........................................... 179 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,915 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 5,4 Resulting RH .............................................................. 52 %
W/m² .................................................................. 184,2 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K

Preheat Coil Sizing Data


No heating coil loads occurred during this calculation.

Supply Fan Sizing Data

Actual max L/s at Dec 1600 .................................. 179 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ......................................................... 179 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 15,56 L/(s-m²) Fan static ...................................................................... 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s ..................................................... 0 L/s L/s/person ................................................................ 0,00 L/s/person
L/(s-m²) ................................................................. 0,00 L/(s-m²)

Hourly Analysis Program v4.90 Page 1 of 11


Zone Sizing Summary for A06-RDC-Bureau chef cuisine
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:11

Air System Information


Air System Name ....... A06-RDC-Bureau chef cuisine Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area ................................................................ 11,5 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 2,0 179 2 Dec 1600 0,0 11,5 15,56

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
A06-RDC-B.chef cuisine 1 2,0 Dec 1600 179 0,0 11,5 15,56

Hourly Analysis Program v4.90 Page 2 of 11


Ventilation Sizing Summary for A06-RDC-Bureau chef cuisine
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:11

1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 L/s

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (m²) Occupants (L/s) (L/s/person) (L/(s-m²)) (L/s) (% of supply) (L/s)
Zone 1
A06-RDC-B.chef cuisine 1 11,5 3,0 178,9 0,00 0,00 0,0 0,0 0,0
Totals (incl. Space Multipliers) 178,9 0,0

Hourly Analysis Program v4.90 Page 3 of 11


Air System Design Load Summary for A06-RDC-Bureau chef cuisine
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:11

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Dec 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 27,6 °C / 24,2 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 823 - 3 m² - -
Wall Transmission 7 m² 78 - 7 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 19 - 3 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 12 m² 0 - 12 m² 0 -
Partitions 17 m² 30 - 17 m² 0 -
Ceiling 12 m² 20 - 12 m² 0 -
Overhead Lighting 230 W 230 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 575 W 575 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 1990 180 - 0 0
Zone Conditioning - 1938 180 - -17 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 161 L/s 0 - 2 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 161 L/s 0 - 2 L/s 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 1938 180 - -17 0
Central Cooling Coil - 1938 181 - -17 0
Preheat Coil - 0 - - 0 -
Terminal Reheat Coils - 0 - - 0 -
>> Total Conditioning - 1938 181 - -17 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 4 of 11


Zone Design Load Summary for A06-RDC-Bureau chef cuisine
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:11

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Dec 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 27,6 °C / 24,2 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 823 - 3 m² - -
Wall Transmission 7 m² 78 - 7 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 19 - 3 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 12 m² 0 - 12 m² 0 -
Partitions 17 m² 30 - 17 m² 0 -
Ceiling 12 m² 20 - 12 m² 0 -
Overhead Lighting 230 W 230 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 575 W 575 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 1990 180 - 0 0

Hourly Analysis Program v4.90 Page 5 of 11


Space Design Load Summary for A06-RDC-Bureau chef cuisine
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:11

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A06-RDC-B.chef cuisine '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 27,6 °C / 24,2 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 823 - 3 m² - -
Wall Transmission 7 m² 78 - 7 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 19 - 3 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 12 m² 0 - 12 m² 0 -
Partitions 17 m² 30 - 17 m² 0 -
Ceiling 12 m² 20 - 12 m² 0 -
Overhead Lighting 230 W 230 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 575 W 575 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 1990 180 - 0 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A06-RDC-B.chef cuisine '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 7 1,471 - 78 - 0
WINDOW 1 3 1,700 0,811 19 823 0

Hourly Analysis Program v4.90 Page 6 of 11


Hourly Air System Design Day Loads for A06-RDC-Bureau chef cuisine
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:11

DESIGN MONTH: JULY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 23,4 110 1,3 1,5 0,0 0,0 0,0 0,0 0,0 0,0
0100 22,8 108 1,3 1,4 0,0 0,0 0,0 0,0 0,0 0,0
0200 22,2 106 1,2 1,4 0,0 0,0 0,0 0,0 0,0 0,0
0300 21,8 105 1,2 1,4 0,0 0,0 0,0 0,0 0,0 0,0
0400 21,4 104 1,2 1,4 0,0 0,0 0,0 0,0 0,0 0,0
0500 21,3 103 1,2 1,4 0,0 0,0 0,0 0,0 0,0 0,0
0600 21,5 102 1,2 1,4 0,0 0,0 0,0 0,0 0,0 0,0
0700 22,1 103 1,2 1,4 0,0 0,0 0,0 0,0 0,0 0,0
0800 23,2 105 1,2 1,4 0,0 0,0 0,0 0,0 0,0 0,0
0900 24,7 107 1,3 1,4 0,0 0,0 0,0 0,0 0,0 0,0
1000 26,4 110 1,3 1,5 0,0 0,0 0,0 0,0 0,0 0,0
1100 28,4 113 1,3 1,5 0,0 0,0 0,0 0,0 0,0 0,0
1200 30,2 116 1,4 1,5 0,0 0,0 0,0 0,0 0,0 0,0
1300 31,6 119 1,4 1,6 0,0 0,0 0,0 0,0 0,0 0,0
1400 32,6 124 1,5 1,6 0,0 0,0 0,0 0,0 0,0 0,0
1500 32,9 128 1,5 1,7 0,0 0,0 0,0 0,0 0,0 0,0
1600 32,6 131 1,6 1,7 0,0 0,0 0,0 0,0 0,0 0,0
1700 31,7 129 1,5 1,7 0,0 0,0 0,0 0,0 0,0 0,0
1800 30,5 122 1,4 1,6 0,0 0,0 0,0 0,0 0,0 0,0
1900 29,0 120 1,4 1,6 0,0 0,0 0,0 0,0 0,0 0,0
2000 27,4 118 1,4 1,6 0,0 0,0 0,0 0,0 0,0 0,0
2100 26,2 116 1,4 1,5 0,0 0,0 0,0 0,0 0,0 0,0
2200 25,0 114 1,3 1,5 0,0 0,0 0,0 0,0 0,0 0,0
2300 24,1 112 1,3 1,5 0,0 0,0 0,0 0,0 0,0 0,0

Hourly Analysis Program v4.90 Page 7 of 11


Hourly Zone Loads for A06-RDC-Bureau chef cuisine
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:11

ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 23,4 22,5 54 109,9 1306,6 1287,6 0,0 0,0 0,0
0100 22,8 22,5 54 108,2 1284,5 1266,2 0,0 0,0 0,0
0200 22,2 22,5 54 106,4 1261,7 1244,3 0,0 0,0 0,0
0300 21,8 22,5 54 104,9 1243,5 1226,5 0,0 0,0 0,0
0400 21,4 22,5 54 103,7 1228,4 1211,7 0,0 0,0 0,0
0500 21,3 22,5 54 102,6 1214,3 1197,8 0,0 0,0 0,0
0600 21,5 22,5 54 101,9 1206,2 1189,6 0,0 0,0 0,0
0700 22,1 22,5 54 102,9 1219,1 1201,2 0,0 0,0 0,0
0800 23,2 22,5 54 104,7 1243,8 1223,9 0,0 0,0 0,0
0900 24,7 22,5 54 107,2 1276,5 1254,5 0,0 0,0 0,0
1000 26,4 22,5 54 110,0 1313,8 1289,5 0,0 0,0 0,0
1100 28,4 22,5 54 113,2 1355,0 1328,5 0,0 0,0 0,0
1200 30,2 22,5 54 116,4 1396,3 1367,8 0,0 0,0 0,0
1300 31,6 22,5 54 119,1 1431,9 1401,8 0,0 0,0 0,0
1400 32,6 22,6 53 123,6 1491,4 1458,4 0,0 0,0 0,0
1500 32,9 22,6 53 128,4 1553,8 1518,0 0,0 0,0 0,0
1600 32,6 22,6 53 130,9 1587,0 1550,4 0,0 0,0 0,0
1700 31,7 22,6 53 129,0 1559,5 1525,7 0,0 0,0 0,0
1800 30,5 22,6 53 122,1 1466,4 1439,0 0,0 0,0 0,0
1900 29,0 22,5 54 120,0 1438,6 1412,9 0,0 0,0 0,0
2000 27,4 22,5 54 117,8 1409,9 1385,9 0,0 0,0 0,0
2100 26,2 22,5 54 115,7 1382,7 1360,2 0,0 0,0 0,0
2200 25,0 22,5 54 113,6 1355,3 1334,1 0,0 0,0 0,0
2300 24,1 22,5 54 111,7 1329,8 1309,8 0,0 0,0 0,0

Hourly Analysis Program v4.90 Page 8 of 11


System Psychrometrics for A06-RDC-Bureau chef cuisine
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:11

December DESIGN COOLING DAY, 1600

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 27,6 0,01774 0 400 0 0
Vent - Return Mixing Outlet 22,7 0,00896 161 2908 - -
Preheat Coil Outlet 22,7 0,00896 161 2908 0 -
Central Cooling Coil Outlet 12,8 0,00858 161 2908 1938 181
Supply Fan Outlet 12,8 0,00858 161 2908 0 -
Cold Supply Duct Outlet 12,8 0,00858 161 2908 - -
Zone Air - 22,7 0,00896 161 2908 1938 180
Return Plenum Outlet 22,7 0,00896 161 2908 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 1990 Cooling 1938 22,7 161 2908 0 0

Hourly Analysis Program v4.90 Page 9 of 11


System Psychrometrics for A06-RDC-Bureau chef cuisine
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:11

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 22,0 0,01667 0 400 0 0
Vent - Return Mixing Outlet 20,7 0,00866 2 800 - -
Preheat Coil Outlet 20,7 0,00866 2 800 0 -
Central Cooling Coil Outlet 12,8 0,00866 2 800 17 0
Supply Fan Outlet 12,8 0,00866 2 800 0 -
Cold Supply Duct Outlet 12,8 0,00866 2 800 - -
Zone Air - 20,7 0,00866 2 800 17 0
Return Plenum Outlet 20,7 0,00866 2 800 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 0 Heating 17 20,7 2 800 0 0

Hourly Analysis Program v4.90 Page 10 of 11


Psychrometric Analysis for A06-RDC-Bureau chef cuisine
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:11

Location: OUIDAH, BENIN


Altitude: 5,8 m.
Data for: December DESIGN COOLING DAY, 1600
0,020
1. Central Cooling Coil Outlet
2. Supply Fan Outlet
3. Room Air
0,018

0,016

Specific Humidity ( kg/kg )


0,014

0,012

3 0,010
12
0,008

0,006

0,004

0,002

0,000
0 5 10 15 20 25 30 35
Temperature ( °C )

Hourly Analysis Program v4.90 Page 11 of 11


Air System Sizing Summary for A06-R1-Bureau cantine
Project Name: A06 01/05/2024
Prepared by: ATOMAS 04:51

Air System Information


Air System Name .................. A06-R1-Bureau cantine Number of zones .......................................................... 1
Equipment Class ............................................ UNDEF Floor Area ................................................................ 13,0 m²
Air System Type ............................................ CAV/RH Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ................... Sum of space airflow rates
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ........................................................ 2,2 kW Load occurs at ................................................ Aug 1800
Sensible coil load ................................................... 2,1 kW OA DB / WB ................................................... 30,5 / 26,5 °C
Coil L/s at Aug 1800 ............................................. 195 L/s Entering DB / WB ........................................... 21,7 / 15,8 °C
Max block L/s ....................................................... 195 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s ........................................... 195 L/s Coil ADP .................................................................. 11,8 °C
Sensible heat ratio .............................................. 0,972 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 6,0 Resulting RH .............................................................. 54 %
W/m² .................................................................. 166,8 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... 0,09 L/s Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K

Supply Fan Sizing Data

Actual max L/s ...................................................... 195 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ......................................................... 195 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 15,01 L/(s-m²) Fan static ...................................................................... 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s ..................................................... 0 L/s L/s/person ................................................................ 0,00 L/s/person
L/(s-m²) ................................................................. 0,00 L/(s-m²)

Hourly Analysis Program v4.90 Page 1 of 13


Zone Sizing Summary for A06-R1-Bureau cantine
Project Name: A06 01/05/2024
Prepared by: ATOMAS 04:51

Air System Information


Air System Name .................. A06-R1-Bureau cantine Number of zones .......................................................... 1
Equipment Class ............................................ UNDEF Floor Area ................................................................ 13,0 m²
Air System Type ............................................ CAV/RH Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ................... Sum of space airflow rates
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 2,2 195 195 Aug 1800 0,0 13,0 15,01

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
A06-R1-Bureau cantine 1 2,2 Aug 1800 195 0,0 13,0 15,01

Hourly Analysis Program v4.90 Page 2 of 13


Ventilation Sizing Summary for A06-R1-Bureau cantine
Project Name: A06 01/05/2024
Prepared by: ATOMAS 04:51

1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 L/s

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (m²) Occupants (L/s) (L/s/person) (L/(s-m²)) (L/s) (% of supply) (L/s)
Zone 1
A06-R1-Bureau cantine 1 13,0 1,0 195,1 0,00 0,00 0,0 0,0 0,0
Totals (incl. Space Multipliers) 195,1 0,0

Hourly Analysis Program v4.90 Page 3 of 13


Air System Design Load Summary for A06-R1-Bureau cantine
Project Name: A06 01/05/2024
Prepared by: ATOMAS 04:51

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1800 HEATING DATA AT DES HTG
COOLING OA DB / WB 30,5 °C / 26,5 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 34 m² 604 - 34 m² 0 -
Roof Transmission 13 m² 481 - 13 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 3 m² 54 - 3 m² 0 -
Floor Transmission 13 m² 49 - 13 m² 1 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 260 W 260 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 650 W 650 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 2171 60 - 1 0
Zone Conditioning - 2109 60 - -527 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 195 L/s 0 - 195 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 195 L/s 0 - 195 L/s 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 2109 60 - -527 0
Central Cooling Coil - 2109 60 - -527 0
>> Total Conditioning - 2109 60 - -527 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 4 of 13


Zone Design Load Summary for A06-R1-Bureau cantine
Project Name: A06 01/05/2024
Prepared by: ATOMAS 04:51

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1800 HEATING DATA AT DES HTG
COOLING OA DB / WB 30,5 °C / 26,5 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 34 m² 604 - 34 m² 0 -
Roof Transmission 13 m² 481 - 13 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 3 m² 54 - 3 m² 0 -
Floor Transmission 13 m² 49 - 13 m² 1 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 260 W 260 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 650 W 650 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 2171 60 - 1 0

Hourly Analysis Program v4.90 Page 5 of 13


Space Design Load Summary for A06-R1-Bureau cantine
Project Name: A06 01/05/2024
Prepared by: ATOMAS 04:51

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A06-R1-Bureau cantine '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1800 HEATING DATA AT DES HTG
COOLING OA DB / WB 30,5 °C / 26,5 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 34 m² 604 - 34 m² 0 -
Roof Transmission 13 m² 481 - 13 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 3 m² 54 - 3 m² 0 -
Floor Transmission 13 m² 49 - 13 m² 1 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 260 W 260 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 650 W 650 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 2171 60 - 1 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A06-R1-Bureau cantine '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 7 1,471 - 108 - 0
NW EXPOSURE
WALL 11 1,471 - 200 - 0
NE EXPOSURE
WALL 7 1,471 - 152 - 0
SE EXPOSURE
WALL 8 1,471 - 143 - 0
DOOR 3 2,500 - 54 - 0
H EXPOSURE
ROOF 13 1,137 - 481 - 0

Hourly Analysis Program v4.90 Page 6 of 13


Hourly Air System Design Day Loads for A06-R1-Bureau cantine
Project Name: A06 01/05/2024
Prepared by: ATOMAS 04:51

DESIGN MONTH: JULY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 23,4 195 2,0 2,1 0,0 0,0 0,0 0,0 0,0 0,0
0100 22,8 195 2,0 2,0 0,0 0,0 0,0 0,0 0,0 0,0
0200 22,2 195 1,9 2,0 0,0 0,0 0,0 0,0 0,0 0,0
0300 21,8 195 1,9 2,0 0,0 0,0 0,0 0,0 0,0 0,0
0400 21,4 195 1,9 1,9 0,0 0,0 0,0 0,0 0,0 0,0
0500 21,3 195 1,8 1,9 0,0 0,0 0,0 0,0 0,0 0,0
0600 21,5 195 1,8 1,9 0,0 0,0 0,0 0,0 0,0 0,0
0700 22,1 195 1,8 1,8 0,0 0,0 0,0 0,0 0,0 0,0
0800 23,2 195 1,8 1,8 0,0 0,0 0,0 0,0 0,0 0,0
0900 24,7 195 1,8 1,8 0,0 0,0 0,0 0,0 0,0 0,0
1000 26,4 195 1,8 1,8 0,0 0,0 0,0 0,0 0,0 0,0
1100 28,4 195 1,8 1,9 0,0 0,0 0,0 0,0 0,0 0,0
1200 30,2 195 1,9 1,9 0,0 0,0 0,0 0,0 0,0 0,0
1300 31,6 195 1,9 2,0 0,0 0,0 0,0 0,0 0,0 0,0
1400 32,6 195 2,0 2,0 0,0 0,0 0,0 0,0 0,0 0,0
1500 32,9 195 2,0 2,1 0,0 0,0 0,0 0,0 0,0 0,0
1600 32,6 195 2,1 2,1 0,0 0,0 0,0 0,0 0,0 0,0
1700 31,7 195 2,1 2,1 0,0 0,0 0,0 0,0 0,0 0,0
1800 30,5 195 2,1 2,2 0,0 0,0 0,0 0,0 0,0 0,0
1900 29,0 195 2,1 2,2 0,0 0,0 0,0 0,0 0,0 0,0
2000 27,4 195 2,1 2,1 0,0 0,0 0,0 0,0 0,0 0,0
2100 26,2 195 2,1 2,1 0,0 0,0 0,0 0,0 0,0 0,0
2200 25,0 195 2,0 2,1 0,0 0,0 0,0 0,0 0,0 0,0
2300 24,1 195 2,0 2,1 0,0 0,0 0,0 0,0 0,0 0,0

Hourly Analysis Program v4.90 Page 7 of 13


Hourly Zone Loads for A06-R1-Bureau cantine
Project Name: A06 01/05/2024
Prepared by: ATOMAS 04:51

ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 23,4 21,2 56 195,1 1911,6 1990,2 0,0 0,0 0,0
0100 22,8 21,1 56 195,1 1857,3 1961,0 0,0 0,0 0,0
0200 22,2 21,0 57 195,1 1802,0 1930,3 0,0 0,0 0,0
0300 21,8 20,8 57 195,1 1749,0 1899,9 0,0 0,0 0,0
0400 21,4 20,7 58 195,1 1698,1 1869,8 0,0 0,0 0,0
0500 21,3 20,6 58 195,1 1648,9 1839,9 0,0 0,0 0,0
0600 21,5 20,5 59 195,1 1602,7 1811,0 0,0 0,0 0,0
0700 22,1 20,4 59 195,1 1561,6 1784,3 0,0 0,0 0,0
0800 23,2 20,3 59 195,1 1539,5 1767,2 0,0 0,0 0,0
0900 24,7 20,3 59 195,1 1549,3 1766,7 0,0 0,0 0,0
1000 26,4 20,4 59 195,1 1595,0 1785,8 0,0 0,0 0,0
1100 28,4 20,5 59 195,1 1672,6 1822,8 0,0 0,0 0,0
1200 30,2 20,7 58 195,1 1768,9 1871,5 0,0 0,0 0,0
1300 31,6 21,0 57 195,1 1869,7 1924,7 0,0 0,0 0,0
1400 32,6 21,2 56 195,1 1965,5 1977,3 0,0 0,0 0,0
1500 32,9 21,4 55 195,1 2047,5 2024,3 0,0 0,0 0,0
1600 32,6 21,5 55 195,1 2108,9 2061,8 0,0 0,0 0,0
1700 31,7 21,6 54 195,1 2147,7 2088,2 0,0 0,0 0,0
1800 30,5 21,7 54 195,1 2159,9 2100,9 0,0 0,0 0,0
1900 29,0 21,7 54 195,1 2145,8 2099,5 0,0 0,0 0,0
2000 27,4 21,6 54 195,1 2111,9 2086,8 0,0 0,0 0,0
2100 26,2 21,6 54 195,1 2068,0 2067,7 0,0 0,0 0,0
2200 25,0 21,5 55 195,1 2017,8 2044,1 0,0 0,0 0,0
2300 24,1 21,4 55 195,1 1965,1 2018,0 0,0 0,0 0,0

Hourly Analysis Program v4.90 Page 8 of 13


System Psychrometrics for A06-R1-Bureau cantine
Project Name: A06 01/05/2024
Prepared by: ATOMAS 04:51

August DESIGN COOLING DAY, 1800

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 30,5 0,02035 0 400 0 0
Vent - Return Mixing Outlet 21,7 0,00872 195 1380 - -
Central Cooling Coil Outlet 12,8 0,00862 195 1380 2109 60
Supply Fan Outlet 12,8 0,00862 195 1380 0 -
Cold Supply Duct Outlet 12,8 0,00862 195 1380 - -
Zone Air - 21,7 0,00872 195 1380 2109 60
Return Plenum Outlet 21,7 0,00872 195 1380 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 2171 Deadband 2109 21,7 195 1380 0 0

Hourly Analysis Program v4.90 Page 9 of 13


System Psychrometrics for A06-R1-Bureau cantine
Project Name: A06 01/05/2024
Prepared by: ATOMAS 04:51

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 22,0 0,01667 0 400 0 0
Vent - Return Mixing Outlet 15,0 0,00883 195 800 - -
Central Cooling Coil Outlet 12,8 0,00883 195 800 527 0
Supply Fan Outlet 12,8 0,00883 195 800 0 -
Cold Supply Duct Outlet 12,8 0,00883 195 800 - -
Zone Air - 15,0 0,00883 195 800 527 0
Return Plenum Outlet 15,0 0,00883 195 800 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 -1 Deadband 527 15,0 195 800 0 0

Hourly Analysis Program v4.90 Page 10 of 13


Hourly Air System Design Day Loads for A06-R1-Bureau cantine
Project Name: A06 01/05/2024
Prepared by: ATOMAS 04:51

Data for July

Total Cooling Total Heating


2,2
2,0
1,8
1,6
1,4
Load ( kW )

1,2
1,0
0,8
0,6
0,4
0,2
0,0
00 02 04 06 08 10 12 14 16 18 20 22
01 03 05 07 09 11 13 15 17 19 21 23
Hour of Day

Hourly Analysis Program v4.90 Page 11 of 13


Hourly Zone Design Day Loads for A06-R1-Bureau cantine
Project Name: A06 01/05/2024
Prepared by: ATOMAS 04:51

Zone: Zone 1
Data for July

Zone Sensible Zone Conditioning


2200
2000
1800
1600
1400
1200
W

1000
800
600
400
200
0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Hourly Analysis Program v4.90 Page 12 of 13


Psychrometric Analysis for A06-R1-Bureau cantine
Project Name: A06 01/05/2024
Prepared by: ATOMAS 04:51

Location: OUIDAH, BENIN


Altitude: 5,8 m.
Data for: August DESIGN COOLING DAY, 1800

1. Central Cooling Coil Outlet


2. Supply Fan Outlet
3. Room Air 0,024
0,022
0,020

Specific Humidity ( kg/kg )


0,018
0,016
0,014
0,012

12 3 0,010
0,008
0,006
0,004
0,002
0,000
0 5 10 15 20 25 30 35
Temperature ( °C )

Hourly Analysis Program v4.90 Page 13 of 13


Air System Sizing Summary for A06-R1-Espace de travail D
Project Name: A06 01/05/2024
Prepared by: ATOMAS 04:50

Air System Information


Air System Name ........... A06-R1-Espace de travail D Number of zones .......................................................... 1
Equipment Class ............................................ UNDEF Floor Area .............................................................. 229,0 m²
Air System Type ............................................ CAV/RH Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ................... Sum of space airflow rates
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ....................................................... 32,0 kW Load occurs at ................................................. Jun 1600
Sensible coil load .................................................. 30,4 kW OA DB / WB ................................................... 32,0 / 27,0 °C
Coil L/s at Jun 1600 ............................................. 2848 L/s Entering DB / WB ........................................... 21,6 / 15,8 °C
Max block L/s ...................................................... 2848 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s .......................................... 2848 L/s Coil ADP .................................................................. 11,8 °C
Sensible heat ratio .............................................. 0,951 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 7,2 Resulting RH .............................................................. 55 %
W/m² .................................................................. 139,6 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... 1,38 L/s Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K

Supply Fan Sizing Data

Actual max L/s ..................................................... 2848 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ........................................................ 2846 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 12,44 L/(s-m²) Fan static ...................................................................... 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s ..................................................... 0 L/s L/s/person ................................................................ 0,00 L/s/person
L/(s-m²) ................................................................. 0,00 L/(s-m²)

Hourly Analysis Program v4.90 Page 1 of 13


Zone Sizing Summary for A06-R1-Espace de travail D
Project Name: A06 01/05/2024
Prepared by: ATOMAS 04:50

Air System Information


Air System Name ........... A06-R1-Espace de travail D Number of zones .......................................................... 1
Equipment Class ............................................ UNDEF Floor Area .............................................................. 229,0 m²
Air System Type ............................................ CAV/RH Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ................... Sum of space airflow rates
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 31,7 2848 2848 Jun 1600 0,0 229,0 12,44

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
A06-R1-E.de travail D 1 31,7 Jun 1600 2848 0,0 229,0 12,44

Hourly Analysis Program v4.90 Page 2 of 13


Ventilation Sizing Summary for A06-R1-Espace de travail D
Project Name: A06 01/05/2024
Prepared by: ATOMAS 04:50

1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 L/s

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (m²) Occupants (L/s) (L/s/person) (L/(s-m²)) (L/s) (% of supply) (L/s)
Zone 1
A06-R1-E.de travail D 1 229,0 44,0 2848,4 0,00 0,00 0,0 0,0 0,0
Totals (incl. Space Multipliers) 2848,4 0,0

Hourly Analysis Program v4.90 Page 3 of 13


Air System Design Load Summary for A06-R1-Espace de travail D
Project Name: A06 01/05/2024
Prepared by: ATOMAS 04:50

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 32,0 °C / 27,0 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 75 m² 10501 - 75 m² - -
Wall Transmission 60 m² 817 - 60 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 75 m² 1039 - 75 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 80 m² 338 - 80 m² 9 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 4580 W 4580 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 11450 W 11449 - 0 0 -
People 44 2966 1549 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 31690 1549 - 9 0
Zone Conditioning - 30409 1549 - -2336 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 2848 L/s 0 - 2848 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 2848 L/s 0 - 2848 L/s 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 30409 1549 - -2336 0
Central Cooling Coil - 30409 1552 - -2336 0
>> Total Conditioning - 30409 1552 - -2336 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 4 of 13


Zone Design Load Summary for A06-R1-Espace de travail D
Project Name: A06 01/05/2024
Prepared by: ATOMAS 04:50

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 32,0 °C / 27,0 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 75 m² 10501 - 75 m² - -
Wall Transmission 60 m² 817 - 60 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 75 m² 1039 - 75 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 80 m² 338 - 80 m² 9 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 4580 W 4580 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 11450 W 11449 - 0 0 -
People 44 2966 1549 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 31690 1549 - 9 0

Hourly Analysis Program v4.90 Page 5 of 13


Space Design Load Summary for A06-R1-Espace de travail D
Project Name: A06 01/05/2024
Prepared by: ATOMAS 04:50

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A06-R1-E.de travail D '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 32,0 °C / 27,0 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 75 m² 10501 - 75 m² - -
Wall Transmission 60 m² 817 - 60 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 75 m² 1039 - 75 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 80 m² 338 - 80 m² 9 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 4580 W 4580 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 11450 W 11449 - 0 0 -
People 44 2966 1549 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 31690 1549 - 9 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A06-R1-E.de travail D '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 11 1,471 - 112 - 0
WINDOW 1 4 1,700 0,811 56 380 0
NW EXPOSURE
WALL 21 1,471 - 321 - 0
WINDOW 1 24 1,700 0,811 337 5474 0
NE EXPOSURE
WALL 2 1,471 - 48 - 0
WINDOW 1 20 1,700 0,811 281 2677 0
E EXPOSURE
WALL 5 1,471 - 104 - 0
WINDOW 1 6 1,700 0,811 83 705 0
SE EXPOSURE
WALL 14 1,471 - 169 - 0
WINDOW 1 16 1,700 0,811 225 1066 0
S EXPOSURE
WALL 7 1,471 - 62 - 0
WINDOW 1 4 1,700 0,811 56 199 0

Hourly Analysis Program v4.90 Page 6 of 13


Hourly Air System Design Day Loads for A06-R1-Espace de travail D
Project Name: A06 01/05/2024
Prepared by: ATOMAS 04:50

DESIGN MONTH: JULY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 23,4 2848 26,9 28,4 0,0 0,0 0,0 0,0 0,0 0,0
0100 22,8 2848 26,6 28,1 0,0 0,0 0,0 0,0 0,0 0,0
0200 22,2 2848 26,2 27,8 0,0 0,0 0,0 0,0 0,0 0,0
0300 21,8 2848 25,9 27,5 0,0 0,0 0,0 0,0 0,0 0,0
0400 21,4 2848 25,6 27,2 0,0 0,0 0,0 0,0 0,0 0,0
0500 21,3 2848 25,4 26,9 0,0 0,0 0,0 0,0 0,0 0,0
0600 21,5 2848 25,5 27,1 0,0 0,0 0,0 0,0 0,0 0,0
0700 22,1 2848 26,9 28,5 0,0 0,0 0,0 0,0 0,0 0,0
0800 23,2 2848 27,7 29,2 0,0 0,0 0,0 0,0 0,0 0,0
0900 24,7 2848 28,1 29,7 0,0 0,0 0,0 0,0 0,0 0,0
1000 26,4 2848 28,3 29,8 0,0 0,0 0,0 0,0 0,0 0,0
1100 28,4 2848 28,3 29,9 0,0 0,0 0,0 0,0 0,0 0,0
1200 30,2 2848 28,5 30,1 0,0 0,0 0,0 0,0 0,0 0,0
1300 31,6 2848 29,0 30,6 0,0 0,0 0,0 0,0 0,0 0,0
1400 32,6 2848 29,6 31,2 0,0 0,0 0,0 0,0 0,0 0,0
1500 32,9 2848 30,1 31,7 0,0 0,0 0,0 0,0 0,0 0,0
1600 32,6 2848 30,4 31,9 0,0 0,0 0,0 0,0 0,0 0,0
1700 31,7 2848 30,0 31,6 0,0 0,0 0,0 0,0 0,0 0,0
1800 30,5 2848 28,9 30,5 0,0 0,0 0,0 0,0 0,0 0,0
1900 29,0 2848 28,6 30,1 0,0 0,0 0,0 0,0 0,0 0,0
2000 27,4 2848 28,2 29,8 0,0 0,0 0,0 0,0 0,0 0,0
2100 26,2 2848 27,9 29,4 0,0 0,0 0,0 0,0 0,0 0,0
2200 25,0 2848 27,5 29,1 0,0 0,0 0,0 0,0 0,0 0,0
2300 24,1 2848 27,2 28,8 0,0 0,0 0,0 0,0 0,0 0,0

Hourly Analysis Program v4.90 Page 7 of 13


Hourly Zone Loads for A06-R1-Espace de travail D
Project Name: A06 01/05/2024
Prepared by: ATOMAS 04:50

ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 23,4 20,6 59 2848,4 25543,6 26880,4 0,0 0,0 0,0
0100 22,8 20,5 59 2848,4 25105,3 26560,7 0,0 0,0 0,0
0200 22,2 20,4 60 2848,4 24678,7 26241,2 0,0 0,0 0,0
0300 21,8 20,3 60 2848,4 24287,2 25935,7 0,0 0,0 0,0
0400 21,4 20,2 60 2848,4 23927,5 25644,0 0,0 0,0 0,0
0500 21,3 20,2 61 2848,4 23602,5 25369,0 0,0 0,0 0,0
0600 21,5 20,2 60 2848,4 24060,1 25533,8 0,0 0,0 0,0
0700 22,1 20,6 59 2848,4 26599,6 26900,6 0,0 0,0 0,0
0800 23,2 20,8 58 2848,4 27910,8 27672,2 0,0 0,0 0,0
0900 24,7 21,0 57 2848,4 28572,3 28102,0 0,0 0,0 0,0
1000 26,4 21,0 57 2848,4 28749,1 28266,7 0,0 0,0 0,0
1100 28,4 21,0 57 2848,4 28707,7 28303,7 0,0 0,0 0,0
1200 30,2 21,1 57 2848,4 29016,3 28529,9 0,0 0,0 0,0
1300 31,6 21,2 56 2848,4 29804,5 29034,4 0,0 0,0 0,0
1400 32,6 21,4 56 2848,4 30722,1 29634,1 0,0 0,0 0,0
1500 32,9 21,5 55 2848,4 31426,2 30134,5 0,0 0,0 0,0
1600 32,6 21,6 55 2848,4 31650,6 30374,3 0,0 0,0 0,0
1700 31,7 21,5 55 2848,4 30828,7 30017,0 0,0 0,0 0,0
1800 30,5 21,2 56 2848,4 28766,3 28918,1 0,0 0,0 0,0
1900 29,0 21,1 57 2848,4 28169,7 28569,8 0,0 0,0 0,0
2000 27,4 21,0 57 2848,4 27587,9 28226,6 0,0 0,0 0,0
2100 26,2 20,9 58 2848,4 27038,3 27886,4 0,0 0,0 0,0
2200 25,0 20,8 58 2848,4 26506,0 27542,8 0,0 0,0 0,0
2300 24,1 20,7 58 2848,4 26007,1 27206,4 0,0 0,0 0,0

Hourly Analysis Program v4.90 Page 8 of 13


System Psychrometrics for A06-R1-Espace de travail D
Project Name: A06 01/05/2024
Prepared by: ATOMAS 04:50

June DESIGN COOLING DAY, 1600

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 32,0 0,02059 0 400 0 0
Vent - Return Mixing Outlet 21,6 0,00882 2848 2161 - -
Central Cooling Coil Outlet 12,8 0,00863 2848 2161 30409 1552
Supply Fan Outlet 12,8 0,00863 2848 2161 0 -
Cold Supply Duct Outlet 12,8 0,00863 2848 2161 - -
Zone Air - 21,6 0,00882 2848 2161 30409 1549
Return Plenum Outlet 21,6 0,00882 2848 2161 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 31690 Deadband 30409 21,6 2848 2161 0 0

Hourly Analysis Program v4.90 Page 9 of 13


System Psychrometrics for A06-R1-Espace de travail D
Project Name: A06 01/05/2024
Prepared by: ATOMAS 04:50

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 22,0 0,01667 0 400 0 0
Vent - Return Mixing Outlet 13,5 0,00892 2848 800 - -
Central Cooling Coil Outlet 12,8 0,00892 2848 800 2336 0
Supply Fan Outlet 12,8 0,00892 2848 800 0 -
Cold Supply Duct Outlet 12,8 0,00892 2848 800 - -
Zone Air - 13,5 0,00892 2848 800 2336 0
Return Plenum Outlet 13,5 0,00892 2848 800 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 -9 Deadband 2336 13,5 2848 800 0 0

Hourly Analysis Program v4.90 Page 10 of 13


Hourly Air System Design Day Loads for A06-R1-Espace de travail D
Project Name: A06 01/05/2024
Prepared by: ATOMAS 04:50

Data for July

Total Cooling Total Heating

30

25
Load ( kW )

20

15

10

0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Hourly Analysis Program v4.90 Page 11 of 13


Hourly Zone Design Day Loads for A06-R1-Espace de travail D
Project Name: A06 01/05/2024
Prepared by: ATOMAS 04:50

Zone: Zone 1
Data for July

Zone Sensible Zone Conditioning

30000

25000

20000
W

15000

10000

5000

0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Hourly Analysis Program v4.90 Page 12 of 13


Psychrometric Analysis for A06-R1-Espace de travail D
Project Name: A06 01/05/2024
Prepared by: ATOMAS 04:50

Location: OUIDAH, BENIN


Altitude: 5,8 m.
Data for: June DESIGN COOLING DAY, 1600

1. Central Cooling Coil Outlet


2. Supply Fan Outlet
3. Room Air 0,024
0,022
0,020

Specific Humidity ( kg/kg )


0,018
0,016
0,014
0,012

12 3 0,010
0,008
0,006
0,004
0,002
0,000
0 5 10 15 20 25 30 35
Temperature ( °C )

Hourly Analysis Program v4.90 Page 13 of 13


Air System Sizing Summary for A06-R1-Espace de travail G
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:33

Air System Information


Air System Name ........... A06-R1-Espace de travail G Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area .............................................................. 229,4 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ....................................................... 33,3 kW Load occurs at ................................................. Nov 1500
Sensible coil load .................................................. 31,7 kW OA DB / WB ................................................... 29,0 / 25,4 °C
Coil L/s at Nov 1500 ............................................ 2634 L/s Entering DB / WB ........................................... 22,8 / 16,2 °C
Max block L/s at Nov 1500 ................................... 2890 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s .......................................... 2890 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,952 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 6,9 Resulting RH .............................................................. 51 %
W/m² .................................................................. 145,1 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K

Preheat Coil Sizing Data


No heating coil loads occurred during this calculation.

Supply Fan Sizing Data

Actual max L/s at Nov 1500 ................................. 2890 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ........................................................ 2888 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 12,60 L/(s-m²) Fan static ...................................................................... 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s ..................................................... 0 L/s L/s/person ................................................................ 0,00 L/s/person
L/(s-m²) ................................................................. 0,00 L/(s-m²)

Hourly Analysis Program v4.90 Page 1 of 13


Zone Sizing Summary for A06-R1-Espace de travail G
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:33

Air System Information


Air System Name ........... A06-R1-Espace de travail G Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area .............................................................. 229,4 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 32,2 2890 29 Nov 1500 0,0 229,4 12,60

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
A06-R1-E.de travail G 1 32,2 Nov 1500 2890 0,0 229,4 12,60

Hourly Analysis Program v4.90 Page 2 of 13


Ventilation Sizing Summary for A06-R1-Espace de travail G
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:33

1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 L/s

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (m²) Occupants (L/s) (L/s/person) (L/(s-m²)) (L/s) (% of supply) (L/s)
Zone 1
A06-R1-E.de travail G 1 229,4 44,0 2890,1 0,00 0,00 0,0 0,0 0,0
Totals (incl. Space Multipliers) 2890,1 0,0

Hourly Analysis Program v4.90 Page 3 of 13


Air System Design Load Summary for A06-R1-Espace de travail G
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:33

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Nov 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 29,0 °C / 25,4 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 77 m² 11503 - 77 m² - -
Wall Transmission 85 m² 790 - 85 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 77 m² 644 - 77 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 80 m² 193 - 80 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 4588 W 4588 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 11470 W 11469 - 0 0 -
People 44 2966 1549 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 32153 1549 - 0 0
Zone Conditioning - 31694 1549 - -266 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 2634 L/s 0 - 29 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 2634 L/s 0 - 29 L/s 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 31694 1549 - -266 0
Central Cooling Coil - 31694 1588 - -266 0
Preheat Coil - 0 - - 0 -
Terminal Reheat Coils - 0 - - 0 -
>> Total Conditioning - 31694 1588 - -266 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 4 of 13


Zone Design Load Summary for A06-R1-Espace de travail G
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:33

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Nov 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 29,0 °C / 25,4 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 77 m² 11503 - 77 m² - -
Wall Transmission 85 m² 790 - 85 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 77 m² 644 - 77 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 80 m² 193 - 80 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 4588 W 4588 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 11470 W 11469 - 0 0 -
People 44 2966 1549 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 32153 1549 - 0 0

Hourly Analysis Program v4.90 Page 5 of 13


Space Design Load Summary for A06-R1-Espace de travail G
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:33

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A06-R1-E.de travail G '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Nov 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 29,0 °C / 25,4 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 77 m² 11503 - 77 m² - -
Wall Transmission 85 m² 790 - 85 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 77 m² 644 - 77 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 80 m² 193 - 80 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 4588 W 4588 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 11470 W 11469 - 0 0 -
People 44 2966 1549 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 32153 1549 - 0 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A06-R1-E.de travail G '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 21 1,471 - 223 - 0
WINDOW 1 24 1,700 0,811 204 6149 0
NW EXPOSURE
WALL 22 1,471 - 85 - 0
WINDOW 1 4 1,700 0,811 34 296 0
N EXPOSURE
WALL 5 1,471 - 13 - 0
WINDOW 1 6 1,700 0,811 50 249 0
NE EXPOSURE
WALL 14 1,471 - 79 - 0
WINDOW 1 16 1,700 0,811 136 918 0
E EXPOSURE
WALL 5 1,471 - 77 - 0
WINDOW 1 6 1,700 0,811 50 729 0
SE EXPOSURE
WALL 17 1,471 - 313 - 0
WINDOW 1 20 1,700 0,811 170 3162 0

Hourly Analysis Program v4.90 Page 6 of 13


Hourly Air System Design Day Loads for A06-R1-Espace de travail G
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:33

DESIGN MONTH: JULY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 23,4 2127 25,2 26,7 0,0 0,0 0,0 0,0 0,0 0,0
0100 22,8 2096 24,8 26,3 0,0 0,0 0,0 0,0 0,0 0,0
0200 22,2 2066 24,4 25,9 0,0 0,0 0,0 0,0 0,0 0,0
0300 21,8 2037 24,1 25,6 0,0 0,0 0,0 0,0 0,0 0,0
0400 21,4 2011 23,7 25,3 0,0 0,0 0,0 0,0 0,0 0,0
0500 21,3 1986 23,4 25,0 0,0 0,0 0,0 0,0 0,0 0,0
0600 21,5 2020 23,8 25,4 0,0 0,0 0,0 0,0 0,0 0,0
0700 22,1 2207 26,2 27,8 0,0 0,0 0,0 0,0 0,0 0,0
0800 23,2 2305 27,5 29,0 0,0 0,0 0,0 0,0 0,0 0,0
0900 24,7 2355 28,1 29,7 0,0 0,0 0,0 0,0 0,0 0,0
1000 26,4 2371 28,3 29,9 0,0 0,0 0,0 0,0 0,0 0,0
1100 28,4 2374 28,3 29,9 0,0 0,0 0,0 0,0 0,0 0,0
1200 30,2 2383 28,5 30,0 0,0 0,0 0,0 0,0 0,0 0,0
1300 31,6 2407 28,8 30,3 0,0 0,0 0,0 0,0 0,0 0,0
1400 32,6 2448 29,3 30,9 0,0 0,0 0,0 0,0 0,0 0,0
1500 32,9 2486 29,8 31,4 0,0 0,0 0,0 0,0 0,0 0,0
1600 32,6 2496 29,9 31,5 0,0 0,0 0,0 0,0 0,0 0,0
1700 31,7 2448 29,3 30,8 0,0 0,0 0,0 0,0 0,0 0,0
1800 30,5 2338 27,9 29,4 0,0 0,0 0,0 0,0 0,0 0,0
1900 29,0 2301 27,4 28,9 0,0 0,0 0,0 0,0 0,0 0,0
2000 27,4 2264 26,9 28,5 0,0 0,0 0,0 0,0 0,0 0,0
2100 26,2 2229 26,5 28,0 0,0 0,0 0,0 0,0 0,0 0,0
2200 25,0 2193 26,0 27,6 0,0 0,0 0,0 0,0 0,0 0,0
2300 24,1 2160 25,6 27,1 0,0 0,0 0,0 0,0 0,0 0,0

Hourly Analysis Program v4.90 Page 7 of 13


Hourly Zone Loads for A06-R1-Espace de travail G
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:33

ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 23,4 22,6 52 2127,4 25294,7 25200,1 0,0 0,0 0,0
0100 22,8 22,6 52 2096,5 24894,7 24810,0 0,0 0,0 0,0
0200 22,2 22,6 52 2065,8 24499,7 24423,9 0,0 0,0 0,0
0300 21,8 22,6 52 2037,2 24134,3 24064,8 0,0 0,0 0,0
0400 21,4 22,6 52 2010,6 23796,2 23731,1 0,0 0,0 0,0
0500 21,3 22,6 52 1986,3 23489,3 23426,5 0,0 0,0 0,0
0600 21,5 22,6 52 2020,0 23955,3 23848,0 0,0 0,0 0,0
0700 22,1 22,6 52 2207,4 26482,0 26211,4 0,0 0,0 0,0
0800 23,2 22,7 51 2304,8 27788,9 27451,4 0,0 0,0 0,0
0900 24,7 22,7 51 2355,1 28455,7 28094,5 0,0 0,0 0,0
1000 26,4 22,7 51 2370,8 28651,1 28295,8 0,0 0,0 0,0
1100 28,4 22,7 51 2374,0 28677,9 28336,7 0,0 0,0 0,0
1200 30,2 22,7 51 2383,4 28791,5 28457,0 0,0 0,0 0,0
1300 31,6 22,7 51 2406,8 29097,1 28756,9 0,0 0,0 0,0
1400 32,6 22,7 51 2448,1 29648,8 29288,7 0,0 0,0 0,0
1500 32,9 22,7 51 2485,5 30144,6 29770,5 0,0 0,0 0,0
1600 32,6 22,7 51 2495,9 30269,0 29904,6 0,0 0,0 0,0
1700 31,7 22,7 51 2448,3 29600,0 29291,3 0,0 0,0 0,0
1800 30,5 22,7 51 2337,8 28081,9 27872,8 0,0 0,0 0,0
1900 29,0 22,6 51 2301,0 27586,6 27402,2 0,0 0,0 0,0
2000 27,4 22,6 51 2264,3 27095,2 26934,9 0,0 0,0 0,0
2100 26,2 22,6 51 2228,8 26623,3 26483,4 0,0 0,0 0,0
2200 25,0 22,6 52 2193,4 26156,3 26034,6 0,0 0,0 0,0
2300 24,1 22,6 52 2159,5 25712,3 25605,6 0,0 0,0 0,0

Hourly Analysis Program v4.90 Page 8 of 13


System Psychrometrics for A06-R1-Espace de travail G
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:33

November DESIGN COOLING DAY, 1500

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 29,0 0,01911 0 400 0 0
Vent - Return Mixing Outlet 22,8 0,00877 2634 2272 - -
Preheat Coil Outlet 22,8 0,00877 2634 2272 0 -
Central Cooling Coil Outlet 12,8 0,00856 2634 2272 31694 1588
Supply Fan Outlet 12,8 0,00856 2634 2272 0 -
Cold Supply Duct Outlet 12,8 0,00856 2634 2272 - -
Zone Air - 22,8 0,00876 2634 2272 31694 1549
Return Plenum Outlet 22,8 0,00876 2634 2272 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 32153 Cooling 31694 22,8 2634 2272 0 0

Hourly Analysis Program v4.90 Page 9 of 13


System Psychrometrics for A06-R1-Espace de travail G
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:33

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 22,0 0,01667 0 400 0 0
Vent - Return Mixing Outlet 20,4 0,00866 29 800 - -
Preheat Coil Outlet 20,4 0,00866 29 800 0 -
Central Cooling Coil Outlet 12,8 0,00866 29 800 266 0
Supply Fan Outlet 12,8 0,00866 29 800 0 -
Cold Supply Duct Outlet 12,8 0,00866 29 800 - -
Zone Air - 20,4 0,00866 29 800 266 0
Return Plenum Outlet 20,4 0,00866 29 800 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 0 Heating 266 20,4 29 800 0 0

Hourly Analysis Program v4.90 Page 10 of 13


Hourly Air System Design Day Loads for A06-R1-Espace de travail G
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:33

Data for July

Total Cooling Total Heating

30

25

20
Load ( kW )

15

10

0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Hourly Analysis Program v4.90 Page 11 of 13


Hourly Zone Design Day Loads for A06-R1-Espace de travail G
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:33

Zone: Zone 1
Data for July

Zone Sensible Zone Conditioning


30000

25000

20000
W

15000

10000

5000

0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Hourly Analysis Program v4.90 Page 12 of 13


Psychrometric Analysis for A06-R1-Espace de travail G
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:33

Location: OUIDAH, BENIN


Altitude: 5,8 m.
Data for: November DESIGN COOLING DAY, 1500
0,020
1. Central Cooling Coil Outlet
2. Supply Fan Outlet
3. Room Air
0,018

0,016

Specific Humidity ( kg/kg )


0,014

0,012

0,010
12 3

0,008

0,006

0,004

0,002

0,000
0 5 10 15 20 25 30 35
Temperature ( °C )

Hourly Analysis Program v4.90 Page 13 of 13


Air System Sizing Summary for A06-R1-Espace lounge
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:34

Air System Information


Air System Name .................. A06-R1-Espace lounge Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area ................................................................ 42,7 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ........................................................ 6,8 kW Load occurs at ................................................. Sep 0900
Sensible coil load ................................................... 6,4 kW OA DB / WB ................................................... 23,6 / 23,3 °C
Coil L/s at Sep 0900 ............................................. 529 L/s Entering DB / WB ........................................... 22,7 / 16,2 °C
Max block L/s at Sep 0900 .................................... 583 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s ........................................... 583 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,936 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 6,3 Resulting RH .............................................................. 51 %
W/m² .................................................................. 159,1 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K

Preheat Coil Sizing Data


No heating coil loads occurred during this calculation.

Supply Fan Sizing Data

Actual max L/s at Sep 0900 .................................. 583 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ......................................................... 582 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 13,64 L/(s-m²) Fan static ...................................................................... 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s ..................................................... 0 L/s L/s/person ................................................................ 0,00 L/s/person
L/(s-m²) ................................................................. 0,00 L/(s-m²)

Hourly Analysis Program v4.90 Page 1 of 13


Zone Sizing Summary for A06-R1-Espace lounge
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:34

Air System Information


Air System Name .................. A06-R1-Espace lounge Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area ................................................................ 42,7 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 6,5 583 6 Sep 0900 0,0 42,7 13,64

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
A06-R1-Espace lounge 1 6,5 Sep 0900 583 0,0 42,7 13,64

Hourly Analysis Program v4.90 Page 2 of 13


Ventilation Sizing Summary for A06-R1-Espace lounge
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:34

1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 L/s

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (m²) Occupants (L/s) (L/s/person) (L/(s-m²)) (L/s) (% of supply) (L/s)
Zone 1
A06-R1-Espace lounge 1 42,7 12,0 582,5 0,00 0,00 0,0 0,0 0,0
Totals (incl. Space Multipliers) 582,5 0,0

Hourly Analysis Program v4.90 Page 3 of 13


Air System Design Load Summary for A06-R1-Espace lounge
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:34

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Sep 0900 HEATING DATA AT DES HTG
COOLING OA DB / WB 23,6 °C / 23,3 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 14 m² 2441 - 14 m² - -
Wall Transmission 17 m² 200 - 17 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 14 m² 39 - 14 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 36 m² 3 - 36 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 854 W 854 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2135 W 2135 - 0 0 -
People 12 809 422 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 6481 422 - 0 0
Zone Conditioning - 6362 422 - -54 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 529 L/s 0 - 6 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 529 L/s 0 - 6 L/s 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 6362 422 - -54 0
Central Cooling Coil - 6362 431 - -54 0
Preheat Coil - 0 - - 0 -
Terminal Reheat Coils - 0 - - 0 -
>> Total Conditioning - 6362 431 - -54 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 4 of 13


Zone Design Load Summary for A06-R1-Espace lounge
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:34

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Sep 0900 HEATING DATA AT DES HTG
COOLING OA DB / WB 23,6 °C / 23,3 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 14 m² 2441 - 14 m² - -
Wall Transmission 17 m² 200 - 17 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 14 m² 39 - 14 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 36 m² 3 - 36 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 854 W 854 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2135 W 2135 - 0 0 -
People 12 809 422 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 6481 422 - 0 0

Hourly Analysis Program v4.90 Page 5 of 13


Space Design Load Summary for A06-R1-Espace lounge
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:34

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A06-R1-Espace lounge '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Sep 0900 HEATING DATA AT DES HTG
COOLING OA DB / WB 23,6 °C / 23,3 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 14 m² 2441 - 14 m² - -
Wall Transmission 17 m² 200 - 17 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 14 m² 39 - 14 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 36 m² 3 - 36 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 854 W 854 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2135 W 2135 - 0 0 -
People 12 809 422 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 6481 422 - 0 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A06-R1-Espace lounge '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SE EXPOSURE
WALL 6 1,471 - 70 - 0
WINDOW 1 4 1,700 0,811 11 666 0
E EXPOSURE
WALL 5 1,471 - 68 - 0
WINDOW 1 6 1,700 0,811 17 1238 0
NE EXPOSURE
WALL 6 1,471 - 63 - 0
WINDOW 1 4 1,700 0,811 11 536 0

Hourly Analysis Program v4.90 Page 6 of 13


Hourly Air System Design Day Loads for A06-R1-Espace lounge
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:34

DESIGN MONTH: JULY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 23,4 424 5,0 5,4 0,0 0,0 0,0 0,0 0,0 0,0
0100 22,8 417 4,9 5,3 0,0 0,0 0,0 0,0 0,0 0,0
0200 22,2 410 4,8 5,3 0,0 0,0 0,0 0,0 0,0 0,0
0300 21,8 404 4,8 5,2 0,0 0,0 0,0 0,0 0,0 0,0
0400 21,4 399 4,7 5,1 0,0 0,0 0,0 0,0 0,0 0,0
0500 21,3 394 4,6 5,1 0,0 0,0 0,0 0,0 0,0 0,0
0600 21,5 408 4,8 5,2 0,0 0,0 0,0 0,0 0,0 0,0
0700 22,1 472 5,6 6,1 0,0 0,0 0,0 0,0 0,0 0,0
0800 23,2 503 6,0 6,5 0,0 0,0 0,0 0,0 0,0 0,0
0900 24,7 517 6,2 6,6 0,0 0,0 0,0 0,0 0,0 0,0
1000 26,4 517 6,2 6,6 0,0 0,0 0,0 0,0 0,0 0,0
1100 28,4 508 6,1 6,5 0,0 0,0 0,0 0,0 0,0 0,0
1200 30,2 503 6,0 6,4 0,0 0,0 0,0 0,0 0,0 0,0
1300 31,6 504 6,0 6,5 0,0 0,0 0,0 0,0 0,0 0,0
1400 32,6 504 6,0 6,5 0,0 0,0 0,0 0,0 0,0 0,0
1500 32,9 502 6,0 6,4 0,0 0,0 0,0 0,0 0,0 0,0
1600 32,6 496 5,9 6,4 0,0 0,0 0,0 0,0 0,0 0,0
1700 31,7 486 5,8 6,2 0,0 0,0 0,0 0,0 0,0 0,0
1800 30,5 473 5,6 6,1 0,0 0,0 0,0 0,0 0,0 0,0
1900 29,0 464 5,5 5,9 0,0 0,0 0,0 0,0 0,0 0,0
2000 27,4 455 5,4 5,8 0,0 0,0 0,0 0,0 0,0 0,0
2100 26,2 447 5,3 5,7 0,0 0,0 0,0 0,0 0,0 0,0
2200 25,0 439 5,2 5,6 0,0 0,0 0,0 0,0 0,0 0,0
2300 24,1 431 5,1 5,5 0,0 0,0 0,0 0,0 0,0 0,0

Hourly Analysis Program v4.90 Page 7 of 13


Hourly Zone Loads for A06-R1-Espace lounge
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:34

ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 23,4 22,6 52 423,8 5043,1 5016,2 0,0 0,0 0,0
0100 22,8 22,6 52 417,1 4956,5 4931,4 0,0 0,0 0,0
0200 22,2 22,6 52 410,4 4871,5 4848,1 0,0 0,0 0,0
0300 21,8 22,6 52 404,5 4795,9 4773,5 0,0 0,0 0,0
0400 21,4 22,6 53 399,1 4728,0 4706,1 0,0 0,0 0,0
0500 21,3 22,5 53 394,2 4666,3 4644,6 0,0 0,0 0,0
0600 21,5 22,6 52 408,4 4859,5 4822,9 0,0 0,0 0,0
0700 22,1 22,7 52 472,2 5719,7 5631,0 0,0 0,0 0,0
0800 23,2 22,7 52 503,5 6140,9 6032,6 0,0 0,0 0,0
0900 24,7 22,7 51 517,1 6321,6 6209,1 0,0 0,0 0,0
1000 26,4 22,7 51 516,7 6309,5 6203,9 0,0 0,0 0,0
1100 28,4 22,7 51 508,3 6189,3 6095,7 0,0 0,0 0,0
1200 30,2 22,7 52 503,5 6118,8 6032,9 0,0 0,0 0,0
1300 31,6 22,7 52 504,0 6123,7 6040,1 0,0 0,0 0,0
1400 32,6 22,7 52 504,4 6125,6 6044,4 0,0 0,0 0,0
1500 32,9 22,7 52 501,9 6088,9 6012,1 0,0 0,0 0,0
1600 32,6 22,7 52 495,9 6005,6 5935,3 0,0 0,0 0,0
1700 31,7 22,7 52 486,0 5869,3 5807,9 0,0 0,0 0,0
1800 30,5 22,7 52 473,3 5696,3 5645,0 0,0 0,0 0,0
1900 29,0 22,7 52 464,3 5575,7 5530,2 0,0 0,0 0,0
2000 27,4 22,6 52 455,3 5455,7 5415,5 0,0 0,0 0,0
2100 26,2 22,6 52 446,8 5343,4 5307,6 0,0 0,0 0,0
2200 25,0 22,6 52 438,6 5235,1 5203,1 0,0 0,0 0,0
2300 24,1 22,6 52 430,9 5134,9 5105,9 0,0 0,0 0,0

Hourly Analysis Program v4.90 Page 8 of 13


System Psychrometrics for A06-R1-Espace lounge
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:34

September DESIGN COOLING DAY, 0900

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 23,6 0,01793 0 400 0 0
Vent - Return Mixing Outlet 22,7 0,00885 529 2799 - -
Preheat Coil Outlet 22,7 0,00885 529 2799 0 -
Central Cooling Coil Outlet 12,8 0,00857 529 2799 6362 431
Supply Fan Outlet 12,8 0,00857 529 2799 0 -
Cold Supply Duct Outlet 12,8 0,00857 529 2799 - -
Zone Air - 22,7 0,00884 529 2799 6362 422
Return Plenum Outlet 22,7 0,00884 529 2799 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 6481 Cooling 6362 22,7 529 2799 0 0

Hourly Analysis Program v4.90 Page 9 of 13


System Psychrometrics for A06-R1-Espace lounge
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:34

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 22,0 0,01667 0 400 0 0
Vent - Return Mixing Outlet 20,5 0,00866 6 800 - -
Preheat Coil Outlet 20,5 0,00866 6 800 0 -
Central Cooling Coil Outlet 12,8 0,00866 6 800 54 0
Supply Fan Outlet 12,8 0,00866 6 800 0 -
Cold Supply Duct Outlet 12,8 0,00866 6 800 - -
Zone Air - 20,5 0,00866 6 800 54 0
Return Plenum Outlet 20,5 0,00866 6 800 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 0 Heating 54 20,5 6 800 0 0

Hourly Analysis Program v4.90 Page 10 of 13


Hourly Air System Design Day Loads for A06-R1-Espace lounge
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:34

Data for July

Total Cooling Total Heating


6,5
6,0
5,5
5,0
4,5
Load ( kW )

4,0
3,5
3,0
2,5
2,0
1,5
1,0
0,5
0,0
00 02 04 06 08 10 12 14 16 18 20 22
01 03 05 07 09 11 13 15 17 19 21 23
Hour of Day

Hourly Analysis Program v4.90 Page 11 of 13


Hourly Zone Design Day Loads for A06-R1-Espace lounge
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:34

Zone: Zone 1
Data for July

Zone Sensible Zone Conditioning


6500
6000
5500
5000
4500
4000
3500
W

3000
2500
2000
1500
1000
500
0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Hourly Analysis Program v4.90 Page 12 of 13


Psychrometric Analysis for A06-R1-Espace lounge
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:34

Location: OUIDAH, BENIN


Altitude: 5,8 m.
Data for: September DESIGN COOLING DAY, 0900
0,020
1. Central Cooling Coil Outlet
2. Supply Fan Outlet
3. Room Air
0,018

0,016

Specific Humidity ( kg/kg )


0,014

0,012

3
0,010
12
0,008

0,006

0,004

0,002

0,000
0 5 10 15 20 25 30 35
Temperature ( °C )

Hourly Analysis Program v4.90 Page 13 of 13


Air System Sizing Summary for A06-R1-Salle de réunion 1
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:35

Air System Information


Air System Name ............. A06-R1-Salle de réunion 1 Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area ................................................................ 31,8 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ........................................................ 6,1 kW Load occurs at ................................................. Sep 1600
Sensible coil load ................................................... 5,8 kW OA DB / WB ................................................... 31,4 / 26,5 °C
Coil L/s at Sep 1600 ............................................. 480 L/s Entering DB / WB ........................................... 22,8 / 16,2 °C
Max block L/s at Sep 1600 .................................... 527 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s ........................................... 527 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,941 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 5,2 Resulting RH .............................................................. 51 %
W/m² .................................................................. 192,8 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K

Preheat Coil Sizing Data


No heating coil loads occurred during this calculation.

Supply Fan Sizing Data

Actual max L/s at Sep 1600 .................................. 527 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ......................................................... 527 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 16,59 L/(s-m²) Fan static ...................................................................... 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s ..................................................... 0 L/s L/s/person ................................................................ 0,00 L/s/person
L/(s-m²) ................................................................. 0,00 L/(s-m²)

Hourly Analysis Program v4.90 Page 1 of 13


Zone Sizing Summary for A06-R1-Salle de réunion 1
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:35

Air System Information


Air System Name ............. A06-R1-Salle de réunion 1 Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area ................................................................ 31,8 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 5,9 527 5 Sep 1600 0,0 31,8 16,59

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
A06-R1-S.de réunion 1 1 5,9 Sep 1600 527 0,0 31,8 16,59

Hourly Analysis Program v4.90 Page 2 of 13


Ventilation Sizing Summary for A06-R1-Salle de réunion 1
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:35

1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 L/s

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (m²) Occupants (L/s) (L/s/person) (L/(s-m²)) (L/s) (% of supply) (L/s)
Zone 1
A06-R1-S.de réunion 1 1 31,8 6,0 527,4 0,00 0,00 0,0 0,0 0,0
Totals (incl. Space Multipliers) 527,4 0,0

Hourly Analysis Program v4.90 Page 3 of 13


Air System Design Load Summary for A06-R1-Salle de réunion 1
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:35

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Sep 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 31,4 °C / 26,5 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 16 m² 2806 - 16 m² - -
Wall Transmission 14 m² 166 - 14 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 16 m² 210 - 16 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 8 m² 29 - 8 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 636 W 636 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1590 W 1590 - 0 0 -
People 6 431 361 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 5868 361 - 0 0
Zone Conditioning - 5769 361 - -48 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 480 L/s 0 - 5 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 480 L/s 0 - 5 L/s 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 5769 361 - -48 0
Central Cooling Coil - 5769 361 - -48 0
Preheat Coil - 0 - - 0 -
Terminal Reheat Coils - 0 - - 0 -
>> Total Conditioning - 5769 361 - -48 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 4 of 13


Zone Design Load Summary for A06-R1-Salle de réunion 1
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:35

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Sep 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 31,4 °C / 26,5 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 16 m² 2806 - 16 m² - -
Wall Transmission 14 m² 166 - 14 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 16 m² 210 - 16 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 8 m² 29 - 8 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 636 W 636 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1590 W 1590 - 0 0 -
People 6 431 361 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 5868 361 - 0 0

Hourly Analysis Program v4.90 Page 5 of 13


Space Design Load Summary for A06-R1-Salle de réunion 1
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:35

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A06-R1-S.de réunion 1 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Sep 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 31,4 °C / 26,5 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 16 m² 2806 - 16 m² - -
Wall Transmission 14 m² 166 - 14 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 16 m² 210 - 16 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 8 m² 29 - 8 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 636 W 636 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1590 W 1590 - 0 0 -
People 6 431 361 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 5868 361 - 0 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A06-R1-S.de réunion 1 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NW EXPOSURE
WALL 7 1,471 - 78 - 0
WINDOW 1 8 1,700 0,811 105 1285 0
SW EXPOSURE
WALL 7 1,471 - 88 - 0
WINDOW 1 8 1,700 0,811 105 1521 0

Hourly Analysis Program v4.90 Page 6 of 13


Hourly Air System Design Day Loads for A06-R1-Salle de réunion 1
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:35

DESIGN MONTH: JULY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 23,4 352 4,1 4,5 0,0 0,0 0,0 0,0 0,0 0,0
0100 22,8 345 4,1 4,4 0,0 0,0 0,0 0,0 0,0 0,0
0200 22,2 337 4,0 4,3 0,0 0,0 0,0 0,0 0,0 0,0
0300 21,8 330 3,9 4,2 0,0 0,0 0,0 0,0 0,0 0,0
0400 21,4 324 3,8 4,1 0,0 0,0 0,0 0,0 0,0 0,0
0500 21,3 318 3,7 4,1 0,0 0,0 0,0 0,0 0,0 0,0
0600 21,5 315 3,7 4,0 0,0 0,0 0,0 0,0 0,0 0,0
0700 22,1 320 3,7 4,1 0,0 0,0 0,0 0,0 0,0 0,0
0800 23,2 325 3,8 4,2 0,0 0,0 0,0 0,0 0,0 0,0
0900 24,7 331 3,9 4,3 0,0 0,0 0,0 0,0 0,0 0,0
1000 26,4 338 4,0 4,3 0,0 0,0 0,0 0,0 0,0 0,0
1100 28,4 346 4,1 4,4 0,0 0,0 0,0 0,0 0,0 0,0
1200 30,2 364 4,3 4,7 0,0 0,0 0,0 0,0 0,0 0,0
1300 31,6 388 4,6 5,0 0,0 0,0 0,0 0,0 0,0 0,0
1400 32,6 420 5,0 5,4 0,0 0,0 0,0 0,0 0,0 0,0
1500 32,9 450 5,4 5,8 0,0 0,0 0,0 0,0 0,0 0,0
1600 32,6 468 5,6 6,0 0,0 0,0 0,0 0,0 0,0 0,0
1700 31,7 455 5,5 5,8 0,0 0,0 0,0 0,0 0,0 0,0
1800 30,5 403 4,8 5,1 0,0 0,0 0,0 0,0 0,0 0,0
1900 29,0 394 4,7 5,0 0,0 0,0 0,0 0,0 0,0 0,0
2000 27,4 385 4,6 4,9 0,0 0,0 0,0 0,0 0,0 0,0
2100 26,2 377 4,5 4,8 0,0 0,0 0,0 0,0 0,0 0,0
2200 25,0 368 4,3 4,7 0,0 0,0 0,0 0,0 0,0 0,0
2300 24,1 360 4,2 4,6 0,0 0,0 0,0 0,0 0,0 0,0

Hourly Analysis Program v4.90 Page 7 of 13


Hourly Zone Loads for A06-R1-Salle de réunion 1
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:35

ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 23,4 22,5 53 352,0 4158,0 4144,6 0,0 0,0 0,0
0100 22,8 22,5 53 344,6 4062,5 4051,5 0,0 0,0 0,0
0200 22,2 22,5 53 337,2 3969,3 3960,3 0,0 0,0 0,0
0300 21,8 22,5 53 330,3 3882,1 3874,7 0,0 0,0 0,0
0400 21,4 22,5 53 323,8 3800,7 3794,5 0,0 0,0 0,0
0500 21,3 22,5 53 317,9 3726,8 3721,3 0,0 0,0 0,0
0600 21,5 22,5 53 314,6 3686,7 3680,4 0,0 0,0 0,0
0700 22,1 22,5 53 319,6 3754,7 3742,5 0,0 0,0 0,0
0800 23,2 22,5 53 325,0 3825,9 3808,5 0,0 0,0 0,0
0900 24,7 22,5 53 331,2 3908,1 3885,7 0,0 0,0 0,0
1000 26,4 22,5 53 338,4 4001,9 3974,4 0,0 0,0 0,0
1100 28,4 22,5 53 346,4 4106,7 4074,2 0,0 0,0 0,0
1200 30,2 22,6 52 363,7 4333,2 4290,3 0,0 0,0 0,0
1300 31,6 22,6 52 388,2 4654,8 4598,4 0,0 0,0 0,0
1400 32,6 22,6 52 419,9 5073,9 5000,8 0,0 0,0 0,0
1500 32,9 22,7 51 450,3 5477,3 5390,1 0,0 0,0 0,0
1600 32,6 22,7 51 468,2 5714,0 5622,1 0,0 0,0 0,0
1700 31,7 22,7 51 455,0 5527,9 5451,7 0,0 0,0 0,0
1800 30,5 22,6 52 403,2 4826,3 4787,8 0,0 0,0 0,0
1900 29,0 22,6 52 394,0 4705,3 4671,9 0,0 0,0 0,0
2000 27,4 22,6 52 385,1 4587,7 4559,6 0,0 0,0 0,0
2100 26,2 22,6 52 376,5 4474,8 4451,3 0,0 0,0 0,0
2200 25,0 22,6 52 368,0 4363,7 4344,3 0,0 0,0 0,0
2300 24,1 22,5 52 359,8 4257,9 4241,8 0,0 0,0 0,0

Hourly Analysis Program v4.90 Page 8 of 13


System Psychrometrics for A06-R1-Salle de réunion 1
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:35

September DESIGN COOLING DAY, 1600

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 31,4 0,01984 0 400 0 0
Vent - Return Mixing Outlet 22,8 0,00882 480 2217 - -
Preheat Coil Outlet 22,8 0,00882 480 2217 0 -
Central Cooling Coil Outlet 12,8 0,00857 480 2217 5769 361
Supply Fan Outlet 12,8 0,00857 480 2217 0 -
Cold Supply Duct Outlet 12,8 0,00857 480 2217 - -
Zone Air - 22,8 0,00882 480 2217 5769 361
Return Plenum Outlet 22,8 0,00882 480 2217 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 5868 Cooling 5769 22,8 480 2217 0 0

Hourly Analysis Program v4.90 Page 9 of 13


System Psychrometrics for A06-R1-Salle de réunion 1
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:35

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 22,0 0,01667 0 400 0 0
Vent - Return Mixing Outlet 20,3 0,00866 5 800 - -
Preheat Coil Outlet 20,3 0,00866 5 800 0 -
Central Cooling Coil Outlet 12,8 0,00866 5 800 48 0
Supply Fan Outlet 12,8 0,00866 5 800 0 -
Cold Supply Duct Outlet 12,8 0,00866 5 800 - -
Zone Air - 20,3 0,00866 5 800 48 0
Return Plenum Outlet 20,3 0,00866 5 800 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 0 Heating 48 20,3 5 800 0 0

Hourly Analysis Program v4.90 Page 10 of 13


Hourly Air System Design Day Loads for A06-R1-Salle de réunion 1
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:35

Data for July

Total Cooling Total Heating


6,0
5,5
5,0
4,5
4,0
Load ( kW )

3,5
3,0
2,5
2,0
1,5
1,0
0,5
0,0
00 02 04 06 08 10 12 14 16 18 20 22
01 03 05 07 09 11 13 15 17 19 21 23
Hour of Day

Hourly Analysis Program v4.90 Page 11 of 13


Hourly Zone Design Day Loads for A06-R1-Salle de réunion 1
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:35

Zone: Zone 1
Data for July

Zone Sensible Zone Conditioning

5500
5000
4500
4000
3500
3000
W

2500
2000
1500
1000
500
0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Hourly Analysis Program v4.90 Page 12 of 13


Psychrometric Analysis for A06-R1-Salle de réunion 1
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:35

Location: OUIDAH, BENIN


Altitude: 5,8 m.
Data for: September DESIGN COOLING DAY, 1600
0,020
1. Central Cooling Coil Outlet
2. Supply Fan Outlet
3. Room Air
0,018

0,016

Specific Humidity ( kg/kg )


0,014

0,012

0,010
12 3

0,008

0,006

0,004

0,002

0,000
0 5 10 15 20 25 30 35
Temperature ( °C )

Hourly Analysis Program v4.90 Page 13 of 13


Air System Sizing Summary for A06-R2-Salle de réunion 2
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:04

Air System Information


Air System Name ............. A06-R2-Salle de réunion 2 Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area ................................................................ 73,8 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ....................................................... 13,3 kW Load occurs at ................................................. Jun 1600
Sensible coil load .................................................. 12,4 kW OA DB / WB ................................................... 32,0 / 27,0 °C
Coil L/s at Jun 1600 ............................................. 1027 L/s Entering DB / WB ........................................... 22,8 / 16,3 °C
Max block L/s at Jun 1600 ................................... 1130 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s .......................................... 1130 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,932 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 5,6 Resulting RH .............................................................. 51 %
W/m² .................................................................. 179,6 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K

Preheat Coil Sizing Data


No heating coil loads occurred during this calculation.

Supply Fan Sizing Data

Actual max L/s at Jun 1600 .................................. 1130 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ........................................................ 1129 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 15,31 L/(s-m²) Fan static ...................................................................... 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s ..................................................... 0 L/s L/s/person ................................................................ 0,00 L/s/person
L/(s-m²) ................................................................. 0,00 L/(s-m²)

Hourly Analysis Program v4.90 Page 1 of 6


Zone Sizing Summary for A06-R1-Salle de réunion 2
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:04

Air System Information


Air System Name ............. A06-R1-Salle de réunion 2 Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area ................................................................ 73,8 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 12,6 1130 11 Jun 1600 0,0 73,8 15,31

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
A06-R1-S.de réunion 2 3 4,2 Jun 1600 377 0,0 24,6 15,31

Hourly Analysis Program v4.90 Page 2 of 6


Air System Design Load Summary for A06-R1-Salle de réunion 2
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:04

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 32,0 °C / 27,0 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 24 m² 5474 - 24 m² - -
Wall Transmission 21 m² 321 - 21 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 24 m² 337 - 24 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 45 m² 191 - 45 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1476 W 1476 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 3690 W 3690 - 0 0 -
People 15 1077 901 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 12567 901 - 0 0
Zone Conditioning - 12350 901 - -105 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 1027 L/s 0 - 11 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 1027 L/s 0 - 11 L/s 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 12350 901 - -105 0
Central Cooling Coil - 12350 905 - -105 0
Preheat Coil - 0 - - 0 -
Terminal Reheat Coils - 0 - - 0 -
>> Total Conditioning - 12350 905 - -105 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 3 of 6


System Psychrometrics for A06-R1-Salle de réunion 2
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:04

June DESIGN COOLING DAY, 1600

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 32,0 0,02059 0 400 0 0
Vent - Return Mixing Outlet 22,8 0,00887 1027 2455 - -
Preheat Coil Outlet 22,8 0,00887 1027 2455 0 -
Central Cooling Coil Outlet 12,8 0,00857 1027 2455 12350 905
Supply Fan Outlet 12,8 0,00857 1027 2455 0 -
Cold Supply Duct Outlet 12,8 0,00857 1027 2455 - -
Zone Air - 22,8 0,00887 1027 2455 12350 901
Return Plenum Outlet 22,8 0,00887 1027 2455 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 12567 Cooling 12350 22,8 1027 2455 0 0

Hourly Analysis Program v4.90 Page 4 of 6


System Psychrometrics for A06-R1-Salle de réunion 2
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:04

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 22,0 0,01667 0 400 0 0
Vent - Return Mixing Outlet 20,5 0,00866 11 800 - -
Preheat Coil Outlet 20,5 0,00866 11 800 0 -
Central Cooling Coil Outlet 12,8 0,00866 11 800 105 0
Supply Fan Outlet 12,8 0,00866 11 800 0 -
Cold Supply Duct Outlet 12,8 0,00866 11 800 - -
Zone Air - 20,5 0,00866 11 800 105 0
Return Plenum Outlet 20,5 0,00866 11 800 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 0 Heating 105 20,5 11 800 0 0

Hourly Analysis Program v4.90 Page 5 of 6


Psychrometric Analysis for A06-R1-Salle de réunion 2
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:04

Location: OUIDAH, BENIN


Altitude: 5,8 m.
Data for: June DESIGN COOLING DAY, 1600

1. Central Cooling Coil Outlet


2. Supply Fan Outlet
3. Room Air 0,024
0,022
0,020

Specific Humidity ( kg/kg )


0,018
0,016
0,014
0,012

12 3 0,010
0,008
0,006
0,004
0,002
0,000
0 5 10 15 20 25 30 35
Temperature ( °C )

Hourly Analysis Program v4.90 Page 6 of 6


Air System Sizing Summary for A06-R1-Salle de réunion 2
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:04

Air System Information


Air System Name ............. A06-R1-Salle de réunion 2 Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area ................................................................ 73,8 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ....................................................... 13,3 kW Load occurs at ................................................. Jun 1600
Sensible coil load .................................................. 12,4 kW OA DB / WB ................................................... 32,0 / 27,0 °C
Coil L/s at Jun 1600 ............................................. 1027 L/s Entering DB / WB ........................................... 22,8 / 16,3 °C
Max block L/s at Jun 1600 ................................... 1130 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s .......................................... 1130 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,932 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 5,6 Resulting RH .............................................................. 51 %
W/m² .................................................................. 179,6 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K

Preheat Coil Sizing Data


No heating coil loads occurred during this calculation.

Supply Fan Sizing Data

Actual max L/s at Jun 1600 .................................. 1130 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ........................................................ 1129 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 15,31 L/(s-m²) Fan static ...................................................................... 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s ..................................................... 0 L/s L/s/person ................................................................ 0,00 L/s/person
L/(s-m²) ................................................................. 0,00 L/(s-m²)

Hourly Analysis Program v4.90 Page 1 of 6


Zone Sizing Summary for A06-R1-Salle de réunion 2
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:04

Air System Information


Air System Name ............. A06-R1-Salle de réunion 2 Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area ................................................................ 73,8 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 12,6 1130 11 Jun 1600 0,0 73,8 15,31

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
A06-R1-S.de réunion 2 3 4,2 Jun 1600 377 0,0 24,6 15,31

Hourly Analysis Program v4.90 Page 2 of 6


Air System Design Load Summary for A06-R1-Salle de réunion 2
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:04

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 32,0 °C / 27,0 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 24 m² 5474 - 24 m² - -
Wall Transmission 21 m² 321 - 21 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 24 m² 337 - 24 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 45 m² 191 - 45 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1476 W 1476 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 3690 W 3690 - 0 0 -
People 15 1077 901 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 12567 901 - 0 0
Zone Conditioning - 12350 901 - -105 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 1027 L/s 0 - 11 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 1027 L/s 0 - 11 L/s 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 12350 901 - -105 0
Central Cooling Coil - 12350 905 - -105 0
Preheat Coil - 0 - - 0 -
Terminal Reheat Coils - 0 - - 0 -
>> Total Conditioning - 12350 905 - -105 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 3 of 6


System Psychrometrics for A06-R1-Salle de réunion 2
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:04

June DESIGN COOLING DAY, 1600

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 32,0 0,02059 0 400 0 0
Vent - Return Mixing Outlet 22,8 0,00887 1027 2455 - -
Preheat Coil Outlet 22,8 0,00887 1027 2455 0 -
Central Cooling Coil Outlet 12,8 0,00857 1027 2455 12350 905
Supply Fan Outlet 12,8 0,00857 1027 2455 0 -
Cold Supply Duct Outlet 12,8 0,00857 1027 2455 - -
Zone Air - 22,8 0,00887 1027 2455 12350 901
Return Plenum Outlet 22,8 0,00887 1027 2455 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 12567 Cooling 12350 22,8 1027 2455 0 0

Hourly Analysis Program v4.90 Page 4 of 6


System Psychrometrics for A06-R1-Salle de réunion 2
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:04

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 22,0 0,01667 0 400 0 0
Vent - Return Mixing Outlet 20,5 0,00866 11 800 - -
Preheat Coil Outlet 20,5 0,00866 11 800 0 -
Central Cooling Coil Outlet 12,8 0,00866 11 800 105 0
Supply Fan Outlet 12,8 0,00866 11 800 0 -
Cold Supply Duct Outlet 12,8 0,00866 11 800 - -
Zone Air - 20,5 0,00866 11 800 105 0
Return Plenum Outlet 20,5 0,00866 11 800 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 0 Heating 105 20,5 11 800 0 0

Hourly Analysis Program v4.90 Page 5 of 6


Psychrometric Analysis for A06-R1-Salle de réunion 2
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:04

Location: OUIDAH, BENIN


Altitude: 5,8 m.
Data for: June DESIGN COOLING DAY, 1600

1. Central Cooling Coil Outlet


2. Supply Fan Outlet
3. Room Air 0,024
0,022
0,020

Specific Humidity ( kg/kg )


0,018
0,016
0,014
0,012

12 3 0,010
0,008
0,006
0,004
0,002
0,000
0 5 10 15 20 25 30 35
Temperature ( °C )

Hourly Analysis Program v4.90 Page 6 of 6


Air System Sizing Summary for A06-R1-Salle de réunion 3
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:05

Air System Information


Air System Name ............. A06-R1-Salle de réunion 3 Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area ................................................................ 31,3 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ........................................................ 5,2 kW Load occurs at ................................................. Jun 1600
Sensible coil load ................................................... 4,8 kW OA DB / WB ................................................... 32,0 / 27,0 °C
Coil L/s at Jun 1600 .............................................. 401 L/s Entering DB / WB ........................................... 22,8 / 16,3 °C
Max block L/s at Jun 1600 .................................... 441 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s ........................................... 441 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,930 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 6,0 Resulting RH .............................................................. 52 %
W/m² .................................................................. 165,8 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K

Preheat Coil Sizing Data


No heating coil loads occurred during this calculation.

Supply Fan Sizing Data

Actual max L/s at Jun 1600 ................................... 441 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ......................................................... 441 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 14,10 L/(s-m²) Fan static ...................................................................... 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s ..................................................... 0 L/s L/s/person ................................................................ 0,00 L/s/person
L/(s-m²) ................................................................. 0,00 L/(s-m²)

Hourly Analysis Program v4.90 Page 1 of 6


Zone Sizing Summary for A06-R1-Salle de réunion 3
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:05

Air System Information


Air System Name ............. A06-R1-Salle de réunion 3 Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area ................................................................ 31,3 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 4,9 441 4 Jun 1600 0,0 31,3 14,10

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
A06-R1-S.de réunion 3 1 4,9 Jun 1600 441 0,0 31,3 14,10

Hourly Analysis Program v4.90 Page 2 of 6


Air System Design Load Summary for A06-R1-Salle de réunion 3
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:05

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 32,0 °C / 27,0 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 8 m² 1825 - 8 m² - -
Wall Transmission 15 m² 290 - 15 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 8 m² 112 - 8 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 15 m² 62 - 15 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 626 W 626 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1565 W 1565 - 0 0 -
People 6 431 361 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 4910 361 - 0 0
Zone Conditioning - 4827 361 - -41 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 401 L/s 0 - 4 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 401 L/s 0 - 4 L/s 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 4827 361 - -41 0
Central Cooling Coil - 4827 362 - -41 0
Preheat Coil - 0 - - 0 -
Terminal Reheat Coils - 0 - - 0 -
>> Total Conditioning - 4827 362 - -41 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 3 of 6


System Psychrometrics for A06-R1-Salle de réunion 3
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:05

June DESIGN COOLING DAY, 1600

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 32,0 0,02059 0 400 0 0
Vent - Return Mixing Outlet 22,8 0,00888 401 2494 - -
Preheat Coil Outlet 22,8 0,00888 401 2494 0 -
Central Cooling Coil Outlet 12,8 0,00857 401 2494 4827 362
Supply Fan Outlet 12,8 0,00857 401 2494 0 -
Cold Supply Duct Outlet 12,8 0,00857 401 2494 - -
Zone Air - 22,8 0,00888 401 2494 4827 361
Return Plenum Outlet 22,8 0,00888 401 2494 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 4910 Cooling 4827 22,8 401 2494 0 0

Hourly Analysis Program v4.90 Page 4 of 6


System Psychrometrics for A06-R1-Salle de réunion 3
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:05

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 22,0 0,01667 0 400 0 0
Vent - Return Mixing Outlet 20,4 0,00866 4 800 - -
Preheat Coil Outlet 20,4 0,00866 4 800 0 -
Central Cooling Coil Outlet 12,8 0,00866 4 800 41 0
Supply Fan Outlet 12,8 0,00866 4 800 0 -
Cold Supply Duct Outlet 12,8 0,00866 4 800 - -
Zone Air - 20,4 0,00866 4 800 41 0
Return Plenum Outlet 20,4 0,00866 4 800 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 0 Heating 41 20,4 4 800 0 0

Hourly Analysis Program v4.90 Page 5 of 6


Psychrometric Analysis for A06-R1-Salle de réunion 3
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:05

Location: OUIDAH, BENIN


Altitude: 5,8 m.
Data for: June DESIGN COOLING DAY, 1600

1. Central Cooling Coil Outlet


2. Supply Fan Outlet
3. Room Air 0,024
0,022
0,020

Specific Humidity ( kg/kg )


0,018
0,016
0,014
0,012

12 3 0,010
0,008
0,006
0,004
0,002
0,000
0 5 10 15 20 25 30 35
Temperature ( °C )

Hourly Analysis Program v4.90 Page 6 of 6


Air System Sizing Summary for A06-R1-Salle de réunion 4
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:05

Air System Information


Air System Name ............. A06-R1-Salle de réunion 4 Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area ................................................................ 24,6 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ........................................................ 4,7 kW Load occurs at ................................................. Dec 1600
Sensible coil load ................................................... 4,4 kW OA DB / WB ................................................... 27,6 / 24,2 °C
Coil L/s at Dec 1600 ............................................. 364 L/s Entering DB / WB ........................................... 22,8 / 16,3 °C
Max block L/s at Dec 1600 .................................... 401 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s ........................................... 401 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,934 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 5,2 Resulting RH .............................................................. 51 %
W/m² .................................................................. 190,8 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K

Preheat Coil Sizing Data


No heating coil loads occurred during this calculation.

Supply Fan Sizing Data

Actual max L/s at Dec 1600 .................................. 401 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ......................................................... 400 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 16,29 L/(s-m²) Fan static ...................................................................... 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s ..................................................... 0 L/s L/s/person ................................................................ 0,00 L/s/person
L/(s-m²) ................................................................. 0,00 L/(s-m²)

Hourly Analysis Program v4.90 Page 1 of 6


Zone Sizing Summary for A06-R1-Salle de réunion 4
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:05

Air System Information


Air System Name ............. A06-R1-Salle de réunion 4 Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area ................................................................ 24,6 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 4,5 401 4 Dec 1600 0,0 24,6 16,29

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
A06-R1-S.de reunion 4 1 4,5 Dec 1600 401 0,0 24,6 16,29

Hourly Analysis Program v4.90 Page 2 of 6


Air System Design Load Summary for A06-R1-Salle de réunion 4
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:05

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Dec 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 27,6 °C / 24,2 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 8 m² 2223 - 8 m² - -
Wall Transmission 7 m² 77 - 7 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 8 m² 51 - 8 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 15 m² 26 - 15 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 492 W 492 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1230 W 1230 - 0 0 -
People 5 359 301 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 4458 301 - 0 0
Zone Conditioning - 4385 301 - -36 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 364 L/s 0 - 4 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 364 L/s 0 - 4 L/s 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 4385 301 - -36 0
Central Cooling Coil - 4385 309 - -36 0
Preheat Coil - 0 - - 0 -
Terminal Reheat Coils - 0 - - 0 -
>> Total Conditioning - 4385 309 - -36 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 3 of 6


System Psychrometrics for A06-R1-Salle de réunion 4
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:05

December DESIGN COOLING DAY, 1600

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 27,6 0,01774 0 400 0 0
Vent - Return Mixing Outlet 22,8 0,00886 364 2354 - -
Preheat Coil Outlet 22,8 0,00886 364 2354 0 -
Central Cooling Coil Outlet 12,8 0,00857 364 2354 4385 309
Supply Fan Outlet 12,8 0,00857 364 2354 0 -
Cold Supply Duct Outlet 12,8 0,00857 364 2354 - -
Zone Air - 22,8 0,00885 364 2354 4385 301
Return Plenum Outlet 22,8 0,00885 364 2354 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 4458 Cooling 4385 22,8 364 2354 0 0

Hourly Analysis Program v4.90 Page 4 of 6


System Psychrometrics for A06-R1-Salle de réunion 4
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:05

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 22,0 0,01667 0 400 0 0
Vent - Return Mixing Outlet 20,3 0,00866 4 800 - -
Preheat Coil Outlet 20,3 0,00866 4 800 0 -
Central Cooling Coil Outlet 12,8 0,00866 4 800 36 0
Supply Fan Outlet 12,8 0,00866 4 800 0 -
Cold Supply Duct Outlet 12,8 0,00866 4 800 - -
Zone Air - 20,3 0,00866 4 800 36 0
Return Plenum Outlet 20,3 0,00866 4 800 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 0 Heating 36 20,3 4 800 0 0

Hourly Analysis Program v4.90 Page 5 of 6


Psychrometric Analysis for A06-R1-Salle de réunion 4
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:05

Location: OUIDAH, BENIN


Altitude: 5,8 m.
Data for: December DESIGN COOLING DAY, 1600
0,020
1. Central Cooling Coil Outlet
2. Supply Fan Outlet
3. Room Air
0,018

0,016

Specific Humidity ( kg/kg )


0,014

0,012

3
0,010
12
0,008

0,006

0,004

0,002

0,000
0 5 10 15 20 25 30 35
Temperature ( °C )

Hourly Analysis Program v4.90 Page 6 of 6


Air System Sizing Summary for A06-R1-Salle de réunion 5
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:05

Air System Information


Air System Name ............. A06-R1-Salle de réunion 5 Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area ................................................................ 45,0 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ........................................................ 6,3 kW Load occurs at ................................................. Dec 1600
Sensible coil load ................................................... 6,0 kW OA DB / WB ................................................... 27,6 / 24,2 °C
Coil L/s at Dec 1600 ............................................. 496 L/s Entering DB / WB ........................................... 22,7 / 16,2 °C
Max block L/s at Dec 1600 .................................... 547 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s ........................................... 547 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,951 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 7,2 Resulting RH .............................................................. 51 %
W/m² .................................................................. 139,4 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K

Preheat Coil Sizing Data


No heating coil loads occurred during this calculation.

Supply Fan Sizing Data

Actual max L/s at Dec 1600 .................................. 547 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ......................................................... 547 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 12,16 L/(s-m²) Fan static ...................................................................... 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s ..................................................... 0 L/s L/s/person ................................................................ 0,00 L/s/person
L/(s-m²) ................................................................. 0,00 L/(s-m²)

Hourly Analysis Program v4.90 Page 1 of 6


Zone Sizing Summary for A06-R1-Salle de réunion 5
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:05

Air System Information


Air System Name ............. A06-R1-Salle de réunion 5 Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area ................................................................ 45,0 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 6,1 547 5 Dec 1600 0,0 45,0 12,16

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
A06-R1-S.de réunion 5 1 6,1 Dec 1600 547 0,0 45,0 12,16

Hourly Analysis Program v4.90 Page 2 of 6


Air System Design Load Summary for A06-R1-Salle de réunion 5
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:05

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Dec 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 27,6 °C / 24,2 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 8 m² 2223 - 8 m² - -
Wall Transmission 16 m² 233 - 16 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 8 m² 51 - 8 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 40 m² 70 - 40 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 900 W 900 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2250 W 2250 - 0 0 -
People 5 359 301 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 6085 301 - 0 0
Zone Conditioning - 5964 301 - -51 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 496 L/s 0 - 5 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 496 L/s 0 - 5 L/s 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 5964 301 - -51 0
Central Cooling Coil - 5964 308 - -51 0
Preheat Coil - 0 - - 0 -
Terminal Reheat Coils - 0 - - 0 -
>> Total Conditioning - 5964 308 - -51 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 3 of 6


System Psychrometrics for A06-R1-Salle de réunion 5
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:05

December DESIGN COOLING DAY, 1600

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 27,6 0,01774 0 400 0 0
Vent - Return Mixing Outlet 22,7 0,00877 496 1942 - -
Preheat Coil Outlet 22,7 0,00877 496 1942 0 -
Central Cooling Coil Outlet 12,8 0,00856 496 1942 5964 308
Supply Fan Outlet 12,8 0,00856 496 1942 0 -
Cold Supply Duct Outlet 12,8 0,00856 496 1942 - -
Zone Air - 22,7 0,00877 496 1942 5964 301
Return Plenum Outlet 22,7 0,00877 496 1942 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 6085 Cooling 5964 22,7 496 1942 0 0

Hourly Analysis Program v4.90 Page 4 of 6


System Psychrometrics for A06-R1-Salle de réunion 5
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:05

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 22,0 0,01667 0 400 0 0
Vent - Return Mixing Outlet 20,5 0,00866 5 800 - -
Preheat Coil Outlet 20,5 0,00866 5 800 0 -
Central Cooling Coil Outlet 12,8 0,00866 5 800 51 0
Supply Fan Outlet 12,8 0,00866 5 800 0 -
Cold Supply Duct Outlet 12,8 0,00866 5 800 - -
Zone Air - 20,5 0,00866 5 800 51 0
Return Plenum Outlet 20,5 0,00866 5 800 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 0 Heating 51 20,5 5 800 0 0

Hourly Analysis Program v4.90 Page 5 of 6


Psychrometric Analysis for A06-R1-Salle de réunion 5
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:05

Location: OUIDAH, BENIN


Altitude: 5,8 m.
Data for: December DESIGN COOLING DAY, 1600
0,020
1. Central Cooling Coil Outlet
2. Supply Fan Outlet
3. Room Air
0,018

0,016

Specific Humidity ( kg/kg )


0,014

0,012

0,010
12 3

0,008

0,006

0,004

0,002

0,000
0 5 10 15 20 25 30 35
Temperature ( °C )

Hourly Analysis Program v4.90 Page 6 of 6


Air System Sizing Summary for A06-R2-Bureau cantine
Project Name: A06 01/05/2024
Prepared by: ATOMAS 04:51

Air System Information


Air System Name .................. A06-R2-Bureau cantine Number of zones .......................................................... 1
Equipment Class ............................................ UNDEF Floor Area ................................................................ 13,0 m²
Air System Type ............................................ CAV/RH Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ................... Sum of space airflow rates
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ........................................................ 2,2 kW Load occurs at ................................................ Aug 1800
Sensible coil load ................................................... 2,1 kW OA DB / WB ................................................... 30,5 / 26,5 °C
Coil L/s at Aug 1800 ............................................. 195 L/s Entering DB / WB ........................................... 21,7 / 15,8 °C
Max block L/s ....................................................... 195 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s ........................................... 195 L/s Coil ADP .................................................................. 11,8 °C
Sensible heat ratio .............................................. 0,972 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 6,0 Resulting RH .............................................................. 54 %
W/m² .................................................................. 166,8 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... 0,09 L/s Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K

Supply Fan Sizing Data

Actual max L/s ...................................................... 195 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ......................................................... 195 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 15,01 L/(s-m²) Fan static ...................................................................... 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s ..................................................... 0 L/s L/s/person ................................................................ 0,00 L/s/person
L/(s-m²) ................................................................. 0,00 L/(s-m²)

Hourly Analysis Program v4.90 Page 1 of 13


Zone Sizing Summary for A06-R1-Bureau cantine
Project Name: A06 01/05/2024
Prepared by: ATOMAS 04:51

Air System Information


Air System Name .................. A06-R1-Bureau cantine Number of zones .......................................................... 1
Equipment Class ............................................ UNDEF Floor Area ................................................................ 13,0 m²
Air System Type ............................................ CAV/RH Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ................... Sum of space airflow rates
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 2,2 195 195 Aug 1800 0,0 13,0 15,01

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
A06-R1-Bureau cantine 1 2,2 Aug 1800 195 0,0 13,0 15,01

Hourly Analysis Program v4.90 Page 2 of 13


Ventilation Sizing Summary for A06-R1-Bureau cantine
Project Name: A06 01/05/2024
Prepared by: ATOMAS 04:51

1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 L/s

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (m²) Occupants (L/s) (L/s/person) (L/(s-m²)) (L/s) (% of supply) (L/s)
Zone 1
A06-R1-Bureau cantine 1 13,0 1,0 195,1 0,00 0,00 0,0 0,0 0,0
Totals (incl. Space Multipliers) 195,1 0,0

Hourly Analysis Program v4.90 Page 3 of 13


Air System Design Load Summary for A06-R1-Bureau cantine
Project Name: A06 01/05/2024
Prepared by: ATOMAS 04:51

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1800 HEATING DATA AT DES HTG
COOLING OA DB / WB 30,5 °C / 26,5 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 34 m² 604 - 34 m² 0 -
Roof Transmission 13 m² 481 - 13 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 3 m² 54 - 3 m² 0 -
Floor Transmission 13 m² 49 - 13 m² 1 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 260 W 260 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 650 W 650 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 2171 60 - 1 0
Zone Conditioning - 2109 60 - -527 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 195 L/s 0 - 195 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 195 L/s 0 - 195 L/s 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 2109 60 - -527 0
Central Cooling Coil - 2109 60 - -527 0
>> Total Conditioning - 2109 60 - -527 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 4 of 13


Zone Design Load Summary for A06-R1-Bureau cantine
Project Name: A06 01/05/2024
Prepared by: ATOMAS 04:51

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1800 HEATING DATA AT DES HTG
COOLING OA DB / WB 30,5 °C / 26,5 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 34 m² 604 - 34 m² 0 -
Roof Transmission 13 m² 481 - 13 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 3 m² 54 - 3 m² 0 -
Floor Transmission 13 m² 49 - 13 m² 1 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 260 W 260 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 650 W 650 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 2171 60 - 1 0

Hourly Analysis Program v4.90 Page 5 of 13


Space Design Load Summary for A06-R1-Bureau cantine
Project Name: A06 01/05/2024
Prepared by: ATOMAS 04:51

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A06-R1-Bureau cantine '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1800 HEATING DATA AT DES HTG
COOLING OA DB / WB 30,5 °C / 26,5 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 34 m² 604 - 34 m² 0 -
Roof Transmission 13 m² 481 - 13 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 3 m² 54 - 3 m² 0 -
Floor Transmission 13 m² 49 - 13 m² 1 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 260 W 260 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 650 W 650 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 2171 60 - 1 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A06-R1-Bureau cantine '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 7 1,471 - 108 - 0
NW EXPOSURE
WALL 11 1,471 - 200 - 0
NE EXPOSURE
WALL 7 1,471 - 152 - 0
SE EXPOSURE
WALL 8 1,471 - 143 - 0
DOOR 3 2,500 - 54 - 0
H EXPOSURE
ROOF 13 1,137 - 481 - 0

Hourly Analysis Program v4.90 Page 6 of 13


Hourly Air System Design Day Loads for A06-R1-Bureau cantine
Project Name: A06 01/05/2024
Prepared by: ATOMAS 04:51

DESIGN MONTH: JULY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 23,4 195 2,0 2,1 0,0 0,0 0,0 0,0 0,0 0,0
0100 22,8 195 2,0 2,0 0,0 0,0 0,0 0,0 0,0 0,0
0200 22,2 195 1,9 2,0 0,0 0,0 0,0 0,0 0,0 0,0
0300 21,8 195 1,9 2,0 0,0 0,0 0,0 0,0 0,0 0,0
0400 21,4 195 1,9 1,9 0,0 0,0 0,0 0,0 0,0 0,0
0500 21,3 195 1,8 1,9 0,0 0,0 0,0 0,0 0,0 0,0
0600 21,5 195 1,8 1,9 0,0 0,0 0,0 0,0 0,0 0,0
0700 22,1 195 1,8 1,8 0,0 0,0 0,0 0,0 0,0 0,0
0800 23,2 195 1,8 1,8 0,0 0,0 0,0 0,0 0,0 0,0
0900 24,7 195 1,8 1,8 0,0 0,0 0,0 0,0 0,0 0,0
1000 26,4 195 1,8 1,8 0,0 0,0 0,0 0,0 0,0 0,0
1100 28,4 195 1,8 1,9 0,0 0,0 0,0 0,0 0,0 0,0
1200 30,2 195 1,9 1,9 0,0 0,0 0,0 0,0 0,0 0,0
1300 31,6 195 1,9 2,0 0,0 0,0 0,0 0,0 0,0 0,0
1400 32,6 195 2,0 2,0 0,0 0,0 0,0 0,0 0,0 0,0
1500 32,9 195 2,0 2,1 0,0 0,0 0,0 0,0 0,0 0,0
1600 32,6 195 2,1 2,1 0,0 0,0 0,0 0,0 0,0 0,0
1700 31,7 195 2,1 2,1 0,0 0,0 0,0 0,0 0,0 0,0
1800 30,5 195 2,1 2,2 0,0 0,0 0,0 0,0 0,0 0,0
1900 29,0 195 2,1 2,2 0,0 0,0 0,0 0,0 0,0 0,0
2000 27,4 195 2,1 2,1 0,0 0,0 0,0 0,0 0,0 0,0
2100 26,2 195 2,1 2,1 0,0 0,0 0,0 0,0 0,0 0,0
2200 25,0 195 2,0 2,1 0,0 0,0 0,0 0,0 0,0 0,0
2300 24,1 195 2,0 2,1 0,0 0,0 0,0 0,0 0,0 0,0

Hourly Analysis Program v4.90 Page 7 of 13


Hourly Zone Loads for A06-R1-Bureau cantine
Project Name: A06 01/05/2024
Prepared by: ATOMAS 04:51

ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 23,4 21,2 56 195,1 1911,6 1990,2 0,0 0,0 0,0
0100 22,8 21,1 56 195,1 1857,3 1961,0 0,0 0,0 0,0
0200 22,2 21,0 57 195,1 1802,0 1930,3 0,0 0,0 0,0
0300 21,8 20,8 57 195,1 1749,0 1899,9 0,0 0,0 0,0
0400 21,4 20,7 58 195,1 1698,1 1869,8 0,0 0,0 0,0
0500 21,3 20,6 58 195,1 1648,9 1839,9 0,0 0,0 0,0
0600 21,5 20,5 59 195,1 1602,7 1811,0 0,0 0,0 0,0
0700 22,1 20,4 59 195,1 1561,6 1784,3 0,0 0,0 0,0
0800 23,2 20,3 59 195,1 1539,5 1767,2 0,0 0,0 0,0
0900 24,7 20,3 59 195,1 1549,3 1766,7 0,0 0,0 0,0
1000 26,4 20,4 59 195,1 1595,0 1785,8 0,0 0,0 0,0
1100 28,4 20,5 59 195,1 1672,6 1822,8 0,0 0,0 0,0
1200 30,2 20,7 58 195,1 1768,9 1871,5 0,0 0,0 0,0
1300 31,6 21,0 57 195,1 1869,7 1924,7 0,0 0,0 0,0
1400 32,6 21,2 56 195,1 1965,5 1977,3 0,0 0,0 0,0
1500 32,9 21,4 55 195,1 2047,5 2024,3 0,0 0,0 0,0
1600 32,6 21,5 55 195,1 2108,9 2061,8 0,0 0,0 0,0
1700 31,7 21,6 54 195,1 2147,7 2088,2 0,0 0,0 0,0
1800 30,5 21,7 54 195,1 2159,9 2100,9 0,0 0,0 0,0
1900 29,0 21,7 54 195,1 2145,8 2099,5 0,0 0,0 0,0
2000 27,4 21,6 54 195,1 2111,9 2086,8 0,0 0,0 0,0
2100 26,2 21,6 54 195,1 2068,0 2067,7 0,0 0,0 0,0
2200 25,0 21,5 55 195,1 2017,8 2044,1 0,0 0,0 0,0
2300 24,1 21,4 55 195,1 1965,1 2018,0 0,0 0,0 0,0

Hourly Analysis Program v4.90 Page 8 of 13


System Psychrometrics for A06-R1-Bureau cantine
Project Name: A06 01/05/2024
Prepared by: ATOMAS 04:51

August DESIGN COOLING DAY, 1800

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 30,5 0,02035 0 400 0 0
Vent - Return Mixing Outlet 21,7 0,00872 195 1380 - -
Central Cooling Coil Outlet 12,8 0,00862 195 1380 2109 60
Supply Fan Outlet 12,8 0,00862 195 1380 0 -
Cold Supply Duct Outlet 12,8 0,00862 195 1380 - -
Zone Air - 21,7 0,00872 195 1380 2109 60
Return Plenum Outlet 21,7 0,00872 195 1380 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 2171 Deadband 2109 21,7 195 1380 0 0

Hourly Analysis Program v4.90 Page 9 of 13


System Psychrometrics for A06-R1-Bureau cantine
Project Name: A06 01/05/2024
Prepared by: ATOMAS 04:51

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 22,0 0,01667 0 400 0 0
Vent - Return Mixing Outlet 15,0 0,00883 195 800 - -
Central Cooling Coil Outlet 12,8 0,00883 195 800 527 0
Supply Fan Outlet 12,8 0,00883 195 800 0 -
Cold Supply Duct Outlet 12,8 0,00883 195 800 - -
Zone Air - 15,0 0,00883 195 800 527 0
Return Plenum Outlet 15,0 0,00883 195 800 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 -1 Deadband 527 15,0 195 800 0 0

Hourly Analysis Program v4.90 Page 10 of 13


Hourly Air System Design Day Loads for A06-R1-Bureau cantine
Project Name: A06 01/05/2024
Prepared by: ATOMAS 04:51

Data for July

Total Cooling Total Heating


2,2
2,0
1,8
1,6
1,4
Load ( kW )

1,2
1,0
0,8
0,6
0,4
0,2
0,0
00 02 04 06 08 10 12 14 16 18 20 22
01 03 05 07 09 11 13 15 17 19 21 23
Hour of Day

Hourly Analysis Program v4.90 Page 11 of 13


Hourly Zone Design Day Loads for A06-R1-Bureau cantine
Project Name: A06 01/05/2024
Prepared by: ATOMAS 04:51

Zone: Zone 1
Data for July

Zone Sensible Zone Conditioning


2200
2000
1800
1600
1400
1200
W

1000
800
600
400
200
0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Hourly Analysis Program v4.90 Page 12 of 13


Psychrometric Analysis for A06-R1-Bureau cantine
Project Name: A06 01/05/2024
Prepared by: ATOMAS 04:51

Location: OUIDAH, BENIN


Altitude: 5,8 m.
Data for: August DESIGN COOLING DAY, 1800

1. Central Cooling Coil Outlet


2. Supply Fan Outlet
3. Room Air 0,024
0,022
0,020

Specific Humidity ( kg/kg )


0,018
0,016
0,014
0,012

12 3 0,010
0,008
0,006
0,004
0,002
0,000
0 5 10 15 20 25 30 35
Temperature ( °C )

Hourly Analysis Program v4.90 Page 13 of 13


Air System Sizing Summary for A06-R2-Espace de travail D
Project Name: A06 01/05/2024
Prepared by: ATOMAS 04:50

Air System Information


Air System Name ........... A06-R2-Espace de travail D Number of zones .......................................................... 1
Equipment Class ............................................ UNDEF Floor Area .............................................................. 229,0 m²
Air System Type ............................................ CAV/RH Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ................... Sum of space airflow rates
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ....................................................... 32,0 kW Load occurs at ................................................. Jun 1600
Sensible coil load .................................................. 30,4 kW OA DB / WB ................................................... 32,0 / 27,0 °C
Coil L/s at Jun 1600 ............................................. 2848 L/s Entering DB / WB ........................................... 21,6 / 15,8 °C
Max block L/s ...................................................... 2848 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s .......................................... 2848 L/s Coil ADP .................................................................. 11,8 °C
Sensible heat ratio .............................................. 0,951 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 7,2 Resulting RH .............................................................. 55 %
W/m² .................................................................. 139,6 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... 1,38 L/s Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K

Supply Fan Sizing Data

Actual max L/s ..................................................... 2848 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ........................................................ 2846 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 12,44 L/(s-m²) Fan static ...................................................................... 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s ..................................................... 0 L/s L/s/person ................................................................ 0,00 L/s/person
L/(s-m²) ................................................................. 0,00 L/(s-m²)

Hourly Analysis Program v4.90 Page 1 of 13


Zone Sizing Summary for A06-R1-Espace de travail D
Project Name: A06 01/05/2024
Prepared by: ATOMAS 04:50

Air System Information


Air System Name ........... A06-R1-Espace de travail D Number of zones .......................................................... 1
Equipment Class ............................................ UNDEF Floor Area .............................................................. 229,0 m²
Air System Type ............................................ CAV/RH Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ................... Sum of space airflow rates
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 31,7 2848 2848 Jun 1600 0,0 229,0 12,44

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
A06-R1-E.de travail D 1 31,7 Jun 1600 2848 0,0 229,0 12,44

Hourly Analysis Program v4.90 Page 2 of 13


Ventilation Sizing Summary for A06-R1-Espace de travail D
Project Name: A06 01/05/2024
Prepared by: ATOMAS 04:50

1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 L/s

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (m²) Occupants (L/s) (L/s/person) (L/(s-m²)) (L/s) (% of supply) (L/s)
Zone 1
A06-R1-E.de travail D 1 229,0 44,0 2848,4 0,00 0,00 0,0 0,0 0,0
Totals (incl. Space Multipliers) 2848,4 0,0

Hourly Analysis Program v4.90 Page 3 of 13


Air System Design Load Summary for A06-R1-Espace de travail D
Project Name: A06 01/05/2024
Prepared by: ATOMAS 04:50

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 32,0 °C / 27,0 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 75 m² 10501 - 75 m² - -
Wall Transmission 60 m² 817 - 60 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 75 m² 1039 - 75 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 80 m² 338 - 80 m² 9 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 4580 W 4580 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 11450 W 11449 - 0 0 -
People 44 2966 1549 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 31690 1549 - 9 0
Zone Conditioning - 30409 1549 - -2336 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 2848 L/s 0 - 2848 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 2848 L/s 0 - 2848 L/s 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 30409 1549 - -2336 0
Central Cooling Coil - 30409 1552 - -2336 0
>> Total Conditioning - 30409 1552 - -2336 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 4 of 13


Zone Design Load Summary for A06-R1-Espace de travail D
Project Name: A06 01/05/2024
Prepared by: ATOMAS 04:50

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 32,0 °C / 27,0 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 75 m² 10501 - 75 m² - -
Wall Transmission 60 m² 817 - 60 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 75 m² 1039 - 75 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 80 m² 338 - 80 m² 9 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 4580 W 4580 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 11450 W 11449 - 0 0 -
People 44 2966 1549 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 31690 1549 - 9 0

Hourly Analysis Program v4.90 Page 5 of 13


Space Design Load Summary for A06-R1-Espace de travail D
Project Name: A06 01/05/2024
Prepared by: ATOMAS 04:50

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A06-R1-E.de travail D '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 32,0 °C / 27,0 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 75 m² 10501 - 75 m² - -
Wall Transmission 60 m² 817 - 60 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 75 m² 1039 - 75 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 80 m² 338 - 80 m² 9 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 4580 W 4580 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 11450 W 11449 - 0 0 -
People 44 2966 1549 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 31690 1549 - 9 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A06-R1-E.de travail D '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 11 1,471 - 112 - 0
WINDOW 1 4 1,700 0,811 56 380 0
NW EXPOSURE
WALL 21 1,471 - 321 - 0
WINDOW 1 24 1,700 0,811 337 5474 0
NE EXPOSURE
WALL 2 1,471 - 48 - 0
WINDOW 1 20 1,700 0,811 281 2677 0
E EXPOSURE
WALL 5 1,471 - 104 - 0
WINDOW 1 6 1,700 0,811 83 705 0
SE EXPOSURE
WALL 14 1,471 - 169 - 0
WINDOW 1 16 1,700 0,811 225 1066 0
S EXPOSURE
WALL 7 1,471 - 62 - 0
WINDOW 1 4 1,700 0,811 56 199 0

Hourly Analysis Program v4.90 Page 6 of 13


Hourly Air System Design Day Loads for A06-R1-Espace de travail D
Project Name: A06 01/05/2024
Prepared by: ATOMAS 04:50

DESIGN MONTH: JULY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 23,4 2848 26,9 28,4 0,0 0,0 0,0 0,0 0,0 0,0
0100 22,8 2848 26,6 28,1 0,0 0,0 0,0 0,0 0,0 0,0
0200 22,2 2848 26,2 27,8 0,0 0,0 0,0 0,0 0,0 0,0
0300 21,8 2848 25,9 27,5 0,0 0,0 0,0 0,0 0,0 0,0
0400 21,4 2848 25,6 27,2 0,0 0,0 0,0 0,0 0,0 0,0
0500 21,3 2848 25,4 26,9 0,0 0,0 0,0 0,0 0,0 0,0
0600 21,5 2848 25,5 27,1 0,0 0,0 0,0 0,0 0,0 0,0
0700 22,1 2848 26,9 28,5 0,0 0,0 0,0 0,0 0,0 0,0
0800 23,2 2848 27,7 29,2 0,0 0,0 0,0 0,0 0,0 0,0
0900 24,7 2848 28,1 29,7 0,0 0,0 0,0 0,0 0,0 0,0
1000 26,4 2848 28,3 29,8 0,0 0,0 0,0 0,0 0,0 0,0
1100 28,4 2848 28,3 29,9 0,0 0,0 0,0 0,0 0,0 0,0
1200 30,2 2848 28,5 30,1 0,0 0,0 0,0 0,0 0,0 0,0
1300 31,6 2848 29,0 30,6 0,0 0,0 0,0 0,0 0,0 0,0
1400 32,6 2848 29,6 31,2 0,0 0,0 0,0 0,0 0,0 0,0
1500 32,9 2848 30,1 31,7 0,0 0,0 0,0 0,0 0,0 0,0
1600 32,6 2848 30,4 31,9 0,0 0,0 0,0 0,0 0,0 0,0
1700 31,7 2848 30,0 31,6 0,0 0,0 0,0 0,0 0,0 0,0
1800 30,5 2848 28,9 30,5 0,0 0,0 0,0 0,0 0,0 0,0
1900 29,0 2848 28,6 30,1 0,0 0,0 0,0 0,0 0,0 0,0
2000 27,4 2848 28,2 29,8 0,0 0,0 0,0 0,0 0,0 0,0
2100 26,2 2848 27,9 29,4 0,0 0,0 0,0 0,0 0,0 0,0
2200 25,0 2848 27,5 29,1 0,0 0,0 0,0 0,0 0,0 0,0
2300 24,1 2848 27,2 28,8 0,0 0,0 0,0 0,0 0,0 0,0

Hourly Analysis Program v4.90 Page 7 of 13


Hourly Zone Loads for A06-R1-Espace de travail D
Project Name: A06 01/05/2024
Prepared by: ATOMAS 04:50

ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 23,4 20,6 59 2848,4 25543,6 26880,4 0,0 0,0 0,0
0100 22,8 20,5 59 2848,4 25105,3 26560,7 0,0 0,0 0,0
0200 22,2 20,4 60 2848,4 24678,7 26241,2 0,0 0,0 0,0
0300 21,8 20,3 60 2848,4 24287,2 25935,7 0,0 0,0 0,0
0400 21,4 20,2 60 2848,4 23927,5 25644,0 0,0 0,0 0,0
0500 21,3 20,2 61 2848,4 23602,5 25369,0 0,0 0,0 0,0
0600 21,5 20,2 60 2848,4 24060,1 25533,8 0,0 0,0 0,0
0700 22,1 20,6 59 2848,4 26599,6 26900,6 0,0 0,0 0,0
0800 23,2 20,8 58 2848,4 27910,8 27672,2 0,0 0,0 0,0
0900 24,7 21,0 57 2848,4 28572,3 28102,0 0,0 0,0 0,0
1000 26,4 21,0 57 2848,4 28749,1 28266,7 0,0 0,0 0,0
1100 28,4 21,0 57 2848,4 28707,7 28303,7 0,0 0,0 0,0
1200 30,2 21,1 57 2848,4 29016,3 28529,9 0,0 0,0 0,0
1300 31,6 21,2 56 2848,4 29804,5 29034,4 0,0 0,0 0,0
1400 32,6 21,4 56 2848,4 30722,1 29634,1 0,0 0,0 0,0
1500 32,9 21,5 55 2848,4 31426,2 30134,5 0,0 0,0 0,0
1600 32,6 21,6 55 2848,4 31650,6 30374,3 0,0 0,0 0,0
1700 31,7 21,5 55 2848,4 30828,7 30017,0 0,0 0,0 0,0
1800 30,5 21,2 56 2848,4 28766,3 28918,1 0,0 0,0 0,0
1900 29,0 21,1 57 2848,4 28169,7 28569,8 0,0 0,0 0,0
2000 27,4 21,0 57 2848,4 27587,9 28226,6 0,0 0,0 0,0
2100 26,2 20,9 58 2848,4 27038,3 27886,4 0,0 0,0 0,0
2200 25,0 20,8 58 2848,4 26506,0 27542,8 0,0 0,0 0,0
2300 24,1 20,7 58 2848,4 26007,1 27206,4 0,0 0,0 0,0

Hourly Analysis Program v4.90 Page 8 of 13


System Psychrometrics for A06-R1-Espace de travail D
Project Name: A06 01/05/2024
Prepared by: ATOMAS 04:50

June DESIGN COOLING DAY, 1600

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 32,0 0,02059 0 400 0 0
Vent - Return Mixing Outlet 21,6 0,00882 2848 2161 - -
Central Cooling Coil Outlet 12,8 0,00863 2848 2161 30409 1552
Supply Fan Outlet 12,8 0,00863 2848 2161 0 -
Cold Supply Duct Outlet 12,8 0,00863 2848 2161 - -
Zone Air - 21,6 0,00882 2848 2161 30409 1549
Return Plenum Outlet 21,6 0,00882 2848 2161 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 31690 Deadband 30409 21,6 2848 2161 0 0

Hourly Analysis Program v4.90 Page 9 of 13


System Psychrometrics for A06-R1-Espace de travail D
Project Name: A06 01/05/2024
Prepared by: ATOMAS 04:50

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 22,0 0,01667 0 400 0 0
Vent - Return Mixing Outlet 13,5 0,00892 2848 800 - -
Central Cooling Coil Outlet 12,8 0,00892 2848 800 2336 0
Supply Fan Outlet 12,8 0,00892 2848 800 0 -
Cold Supply Duct Outlet 12,8 0,00892 2848 800 - -
Zone Air - 13,5 0,00892 2848 800 2336 0
Return Plenum Outlet 13,5 0,00892 2848 800 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 -9 Deadband 2336 13,5 2848 800 0 0

Hourly Analysis Program v4.90 Page 10 of 13


Hourly Air System Design Day Loads for A06-R1-Espace de travail D
Project Name: A06 01/05/2024
Prepared by: ATOMAS 04:50

Data for July

Total Cooling Total Heating

30

25
Load ( kW )

20

15

10

0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Hourly Analysis Program v4.90 Page 11 of 13


Hourly Zone Design Day Loads for A06-R1-Espace de travail D
Project Name: A06 01/05/2024
Prepared by: ATOMAS 04:50

Zone: Zone 1
Data for July

Zone Sensible Zone Conditioning

30000

25000

20000
W

15000

10000

5000

0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Hourly Analysis Program v4.90 Page 12 of 13


Psychrometric Analysis for A06-R1-Espace de travail D
Project Name: A06 01/05/2024
Prepared by: ATOMAS 04:50

Location: OUIDAH, BENIN


Altitude: 5,8 m.
Data for: June DESIGN COOLING DAY, 1600

1. Central Cooling Coil Outlet


2. Supply Fan Outlet
3. Room Air 0,024
0,022
0,020

Specific Humidity ( kg/kg )


0,018
0,016
0,014
0,012

12 3 0,010
0,008
0,006
0,004
0,002
0,000
0 5 10 15 20 25 30 35
Temperature ( °C )

Hourly Analysis Program v4.90 Page 13 of 13


Air System Sizing Summary for A06-R2-Espace de travail G
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:33

Air System Information


Air System Name ........... A06-R2-Espace de travail G Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area .............................................................. 229,4 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ....................................................... 33,3 kW Load occurs at ................................................. Nov 1500
Sensible coil load .................................................. 31,7 kW OA DB / WB ................................................... 29,0 / 25,4 °C
Coil L/s at Nov 1500 ............................................ 2634 L/s Entering DB / WB ........................................... 22,8 / 16,2 °C
Max block L/s at Nov 1500 ................................... 2890 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s .......................................... 2890 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,952 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 6,9 Resulting RH .............................................................. 51 %
W/m² .................................................................. 145,1 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K

Preheat Coil Sizing Data


No heating coil loads occurred during this calculation.

Supply Fan Sizing Data

Actual max L/s at Nov 1500 ................................. 2890 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ........................................................ 2888 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 12,60 L/(s-m²) Fan static ...................................................................... 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s ..................................................... 0 L/s L/s/person ................................................................ 0,00 L/s/person
L/(s-m²) ................................................................. 0,00 L/(s-m²)

Hourly Analysis Program v4.90 Page 1 of 13


Zone Sizing Summary for A06-R1-Espace de travail G
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:33

Air System Information


Air System Name ........... A06-R1-Espace de travail G Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area .............................................................. 229,4 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 32,2 2890 29 Nov 1500 0,0 229,4 12,60

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
A06-R1-E.de travail G 1 32,2 Nov 1500 2890 0,0 229,4 12,60

Hourly Analysis Program v4.90 Page 2 of 13


Ventilation Sizing Summary for A06-R1-Espace de travail G
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:33

1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 L/s

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (m²) Occupants (L/s) (L/s/person) (L/(s-m²)) (L/s) (% of supply) (L/s)
Zone 1
A06-R1-E.de travail G 1 229,4 44,0 2890,1 0,00 0,00 0,0 0,0 0,0
Totals (incl. Space Multipliers) 2890,1 0,0

Hourly Analysis Program v4.90 Page 3 of 13


Air System Design Load Summary for A06-R1-Espace de travail G
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:33

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Nov 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 29,0 °C / 25,4 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 77 m² 11503 - 77 m² - -
Wall Transmission 85 m² 790 - 85 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 77 m² 644 - 77 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 80 m² 193 - 80 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 4588 W 4588 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 11470 W 11469 - 0 0 -
People 44 2966 1549 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 32153 1549 - 0 0
Zone Conditioning - 31694 1549 - -266 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 2634 L/s 0 - 29 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 2634 L/s 0 - 29 L/s 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 31694 1549 - -266 0
Central Cooling Coil - 31694 1588 - -266 0
Preheat Coil - 0 - - 0 -
Terminal Reheat Coils - 0 - - 0 -
>> Total Conditioning - 31694 1588 - -266 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 4 of 13


Zone Design Load Summary for A06-R1-Espace de travail G
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:33

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Nov 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 29,0 °C / 25,4 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 77 m² 11503 - 77 m² - -
Wall Transmission 85 m² 790 - 85 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 77 m² 644 - 77 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 80 m² 193 - 80 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 4588 W 4588 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 11470 W 11469 - 0 0 -
People 44 2966 1549 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 32153 1549 - 0 0

Hourly Analysis Program v4.90 Page 5 of 13


Space Design Load Summary for A06-R1-Espace de travail G
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:33

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A06-R1-E.de travail G '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Nov 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 29,0 °C / 25,4 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 77 m² 11503 - 77 m² - -
Wall Transmission 85 m² 790 - 85 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 77 m² 644 - 77 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 80 m² 193 - 80 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 4588 W 4588 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 11470 W 11469 - 0 0 -
People 44 2966 1549 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 32153 1549 - 0 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A06-R1-E.de travail G '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 21 1,471 - 223 - 0
WINDOW 1 24 1,700 0,811 204 6149 0
NW EXPOSURE
WALL 22 1,471 - 85 - 0
WINDOW 1 4 1,700 0,811 34 296 0
N EXPOSURE
WALL 5 1,471 - 13 - 0
WINDOW 1 6 1,700 0,811 50 249 0
NE EXPOSURE
WALL 14 1,471 - 79 - 0
WINDOW 1 16 1,700 0,811 136 918 0
E EXPOSURE
WALL 5 1,471 - 77 - 0
WINDOW 1 6 1,700 0,811 50 729 0
SE EXPOSURE
WALL 17 1,471 - 313 - 0
WINDOW 1 20 1,700 0,811 170 3162 0

Hourly Analysis Program v4.90 Page 6 of 13


Hourly Air System Design Day Loads for A06-R1-Espace de travail G
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:33

DESIGN MONTH: JULY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 23,4 2127 25,2 26,7 0,0 0,0 0,0 0,0 0,0 0,0
0100 22,8 2096 24,8 26,3 0,0 0,0 0,0 0,0 0,0 0,0
0200 22,2 2066 24,4 25,9 0,0 0,0 0,0 0,0 0,0 0,0
0300 21,8 2037 24,1 25,6 0,0 0,0 0,0 0,0 0,0 0,0
0400 21,4 2011 23,7 25,3 0,0 0,0 0,0 0,0 0,0 0,0
0500 21,3 1986 23,4 25,0 0,0 0,0 0,0 0,0 0,0 0,0
0600 21,5 2020 23,8 25,4 0,0 0,0 0,0 0,0 0,0 0,0
0700 22,1 2207 26,2 27,8 0,0 0,0 0,0 0,0 0,0 0,0
0800 23,2 2305 27,5 29,0 0,0 0,0 0,0 0,0 0,0 0,0
0900 24,7 2355 28,1 29,7 0,0 0,0 0,0 0,0 0,0 0,0
1000 26,4 2371 28,3 29,9 0,0 0,0 0,0 0,0 0,0 0,0
1100 28,4 2374 28,3 29,9 0,0 0,0 0,0 0,0 0,0 0,0
1200 30,2 2383 28,5 30,0 0,0 0,0 0,0 0,0 0,0 0,0
1300 31,6 2407 28,8 30,3 0,0 0,0 0,0 0,0 0,0 0,0
1400 32,6 2448 29,3 30,9 0,0 0,0 0,0 0,0 0,0 0,0
1500 32,9 2486 29,8 31,4 0,0 0,0 0,0 0,0 0,0 0,0
1600 32,6 2496 29,9 31,5 0,0 0,0 0,0 0,0 0,0 0,0
1700 31,7 2448 29,3 30,8 0,0 0,0 0,0 0,0 0,0 0,0
1800 30,5 2338 27,9 29,4 0,0 0,0 0,0 0,0 0,0 0,0
1900 29,0 2301 27,4 28,9 0,0 0,0 0,0 0,0 0,0 0,0
2000 27,4 2264 26,9 28,5 0,0 0,0 0,0 0,0 0,0 0,0
2100 26,2 2229 26,5 28,0 0,0 0,0 0,0 0,0 0,0 0,0
2200 25,0 2193 26,0 27,6 0,0 0,0 0,0 0,0 0,0 0,0
2300 24,1 2160 25,6 27,1 0,0 0,0 0,0 0,0 0,0 0,0

Hourly Analysis Program v4.90 Page 7 of 13


Hourly Zone Loads for A06-R1-Espace de travail G
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:33

ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 23,4 22,6 52 2127,4 25294,7 25200,1 0,0 0,0 0,0
0100 22,8 22,6 52 2096,5 24894,7 24810,0 0,0 0,0 0,0
0200 22,2 22,6 52 2065,8 24499,7 24423,9 0,0 0,0 0,0
0300 21,8 22,6 52 2037,2 24134,3 24064,8 0,0 0,0 0,0
0400 21,4 22,6 52 2010,6 23796,2 23731,1 0,0 0,0 0,0
0500 21,3 22,6 52 1986,3 23489,3 23426,5 0,0 0,0 0,0
0600 21,5 22,6 52 2020,0 23955,3 23848,0 0,0 0,0 0,0
0700 22,1 22,6 52 2207,4 26482,0 26211,4 0,0 0,0 0,0
0800 23,2 22,7 51 2304,8 27788,9 27451,4 0,0 0,0 0,0
0900 24,7 22,7 51 2355,1 28455,7 28094,5 0,0 0,0 0,0
1000 26,4 22,7 51 2370,8 28651,1 28295,8 0,0 0,0 0,0
1100 28,4 22,7 51 2374,0 28677,9 28336,7 0,0 0,0 0,0
1200 30,2 22,7 51 2383,4 28791,5 28457,0 0,0 0,0 0,0
1300 31,6 22,7 51 2406,8 29097,1 28756,9 0,0 0,0 0,0
1400 32,6 22,7 51 2448,1 29648,8 29288,7 0,0 0,0 0,0
1500 32,9 22,7 51 2485,5 30144,6 29770,5 0,0 0,0 0,0
1600 32,6 22,7 51 2495,9 30269,0 29904,6 0,0 0,0 0,0
1700 31,7 22,7 51 2448,3 29600,0 29291,3 0,0 0,0 0,0
1800 30,5 22,7 51 2337,8 28081,9 27872,8 0,0 0,0 0,0
1900 29,0 22,6 51 2301,0 27586,6 27402,2 0,0 0,0 0,0
2000 27,4 22,6 51 2264,3 27095,2 26934,9 0,0 0,0 0,0
2100 26,2 22,6 51 2228,8 26623,3 26483,4 0,0 0,0 0,0
2200 25,0 22,6 52 2193,4 26156,3 26034,6 0,0 0,0 0,0
2300 24,1 22,6 52 2159,5 25712,3 25605,6 0,0 0,0 0,0

Hourly Analysis Program v4.90 Page 8 of 13


System Psychrometrics for A06-R1-Espace de travail G
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:33

November DESIGN COOLING DAY, 1500

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 29,0 0,01911 0 400 0 0
Vent - Return Mixing Outlet 22,8 0,00877 2634 2272 - -
Preheat Coil Outlet 22,8 0,00877 2634 2272 0 -
Central Cooling Coil Outlet 12,8 0,00856 2634 2272 31694 1588
Supply Fan Outlet 12,8 0,00856 2634 2272 0 -
Cold Supply Duct Outlet 12,8 0,00856 2634 2272 - -
Zone Air - 22,8 0,00876 2634 2272 31694 1549
Return Plenum Outlet 22,8 0,00876 2634 2272 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 32153 Cooling 31694 22,8 2634 2272 0 0

Hourly Analysis Program v4.90 Page 9 of 13


System Psychrometrics for A06-R1-Espace de travail G
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:33

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 22,0 0,01667 0 400 0 0
Vent - Return Mixing Outlet 20,4 0,00866 29 800 - -
Preheat Coil Outlet 20,4 0,00866 29 800 0 -
Central Cooling Coil Outlet 12,8 0,00866 29 800 266 0
Supply Fan Outlet 12,8 0,00866 29 800 0 -
Cold Supply Duct Outlet 12,8 0,00866 29 800 - -
Zone Air - 20,4 0,00866 29 800 266 0
Return Plenum Outlet 20,4 0,00866 29 800 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 0 Heating 266 20,4 29 800 0 0

Hourly Analysis Program v4.90 Page 10 of 13


Hourly Air System Design Day Loads for A06-R1-Espace de travail G
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:33

Data for July

Total Cooling Total Heating

30

25

20
Load ( kW )

15

10

0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Hourly Analysis Program v4.90 Page 11 of 13


Hourly Zone Design Day Loads for A06-R1-Espace de travail G
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:33

Zone: Zone 1
Data for July

Zone Sensible Zone Conditioning


30000

25000

20000
W

15000

10000

5000

0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Hourly Analysis Program v4.90 Page 12 of 13


Psychrometric Analysis for A06-R1-Espace de travail G
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:33

Location: OUIDAH, BENIN


Altitude: 5,8 m.
Data for: November DESIGN COOLING DAY, 1500
0,020
1. Central Cooling Coil Outlet
2. Supply Fan Outlet
3. Room Air
0,018

0,016

Specific Humidity ( kg/kg )


0,014

0,012

0,010
12 3

0,008

0,006

0,004

0,002

0,000
0 5 10 15 20 25 30 35
Temperature ( °C )

Hourly Analysis Program v4.90 Page 13 of 13


Air System Sizing Summary for A06-R2-Espace de travail
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:06

Air System Information


Air System Name .............. A06-R2-Espace de travail Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area .............................................................. 229,0 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ....................................................... 42,1 kW Load occurs at .................................................. Jul 1600
Sensible coil load .................................................. 39,4 kW OA DB / WB ................................................... 32,6 / 27,0 °C
Coil L/s at Jul 1600 .............................................. 3278 L/s Entering DB / WB ........................................... 22,7 / 16,2 °C
Max block L/s at Jul 1600 .................................... 3609 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s .......................................... 3609 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,936 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 5,4 Resulting RH .............................................................. 51 %
W/m² .................................................................. 184,0 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K

Preheat Coil Sizing Data


No heating coil loads occurred during this calculation.

Supply Fan Sizing Data

Actual max L/s at Jul 1600 ................................... 3609 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ........................................................ 3607 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 15,76 L/(s-m²) Fan static ...................................................................... 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s ..................................................... 0 L/s L/s/person ................................................................ 0,00 L/s/person
L/(s-m²) ................................................................. 0,00 L/(s-m²)

Hourly Analysis Program v4.90 Page 1 of 11


Zone Sizing Summary for A06-R2-Espace de travail
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:06

Air System Information


Air System Name .............. A06-R2-Espace de travail Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area .............................................................. 229,0 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 40,2 3609 36 Jul 1600 0,0 229,0 15,76

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
A06-R2-E.de travail D 1 40,2 Jul 1600 3609 0,0 229,0 15,76

Hourly Analysis Program v4.90 Page 2 of 11


Ventilation Sizing Summary for A06-R2-Espace de travail
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:06

1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 L/s

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (m²) Occupants (L/s) (L/s/person) (L/(s-m²)) (L/s) (% of supply) (L/s)
Zone 1
A06-R2-E.de travail D 1 229,0 44,0 3609,5 0,00 0,00 0,0 0,0 0,0
Totals (incl. Space Multipliers) 3609,5 0,0

Hourly Analysis Program v4.90 Page 3 of 11


Air System Design Load Summary for A06-R2-Espace de travail
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:06

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 32,6 °C / 27,0 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 75 m² 10318 - 75 m² - -
Wall Transmission 60 m² 864 - 60 m² 0 -
Roof Transmission 229 m² 8312 - 229 m² 0 -
Window Transmission 75 m² 1110 - 75 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 80 m² 365 - 80 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 4580 W 4580 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 11450 W 11449 - 0 0 -
People 44 3159 2644 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 40156 2644 - 0 0
Zone Conditioning - 39429 2644 - -335 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 3278 L/s 0 - 36 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 3278 L/s 0 - 36 L/s 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 39429 2644 - -335 0
Central Cooling Coil - 39429 2706 - -335 0
Preheat Coil - 0 - - 0 -
Terminal Reheat Coils - 0 - - 0 -
>> Total Conditioning - 39429 2706 - -335 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 4 of 11


Zone Design Load Summary for A06-R2-Espace de travail
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:06

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 32,6 °C / 27,0 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 75 m² 10318 - 75 m² - -
Wall Transmission 60 m² 864 - 60 m² 0 -
Roof Transmission 229 m² 8312 - 229 m² 0 -
Window Transmission 75 m² 1110 - 75 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 80 m² 365 - 80 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 4580 W 4580 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 11450 W 11449 - 0 0 -
People 44 3159 2644 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 40156 2644 - 0 0

Hourly Analysis Program v4.90 Page 5 of 11


Space Design Load Summary for A06-R2-Espace de travail
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:06

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A06-R2-E.de travail D '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 32,6 °C / 27,0 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 75 m² 10318 - 75 m² - -
Wall Transmission 60 m² 864 - 60 m² 0 -
Roof Transmission 229 m² 8312 - 229 m² 0 -
Window Transmission 75 m² 1110 - 75 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 80 m² 365 - 80 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 4580 W 4580 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 11450 W 11449 - 0 0 -
People 44 3159 2644 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 40156 2644 - 0 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A06-R2-E.de travail D '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 11 1,471 - 124 - 0
WINDOW 1 4 1,700 0,811 60 421 0
NW EXPOSURE
WALL 21 1,471 - 326 - 0
WINDOW 1 24 1,700 0,811 360 5260 0
NE EXPOSURE
WALL 2 1,471 - 48 - 0
WINDOW 1 20 1,700 0,811 300 2575 0
E EXPOSURE
WALL 5 1,471 - 108 - 0
WINDOW 1 6 1,700 0,811 89 715 0
SE EXPOSURE
WALL 14 1,471 - 189 - 0
WINDOW 1 16 1,700 0,811 240 1143 0
S EXPOSURE
WALL 7 1,471 - 68 - 0
WINDOW 1 4 1,700 0,811 60 202 0
H EXPOSURE
ROOF 229 1,137 - 8312 - 0

Hourly Analysis Program v4.90 Page 6 of 11


Hourly Air System Design Day Loads for A06-R2-Espace de travail
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:06

DESIGN MONTH: JULY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 23,4 2482 29,3 31,9 0,0 0,0 0,0 0,0 0,0 0,0
0100 22,8 2405 28,3 30,9 0,0 0,0 0,0 0,0 0,0 0,0
0200 22,2 2334 27,4 30,1 0,0 0,0 0,0 0,0 0,0 0,0
0300 21,8 2270 26,6 29,3 0,0 0,0 0,0 0,0 0,0 0,0
0400 21,4 2212 25,9 28,6 0,0 0,0 0,0 0,0 0,0 0,0
0500 21,3 2160 25,3 27,9 0,0 0,0 0,0 0,0 0,0 0,0
0600 21,5 2170 25,4 28,1 0,0 0,0 0,0 0,0 0,0 0,0
0700 22,1 2345 27,6 30,2 0,0 0,0 0,0 0,0 0,0 0,0
0800 23,2 2440 28,8 31,4 0,0 0,0 0,0 0,0 0,0 0,0
0900 24,7 2515 29,7 32,3 0,0 0,0 0,0 0,0 0,0 0,0
1000 26,4 2584 30,5 33,2 0,0 0,0 0,0 0,0 0,0 0,0
1100 28,4 2660 31,5 34,2 0,0 0,0 0,0 0,0 0,0 0,0
1200 30,2 2777 33,0 35,6 0,0 0,0 0,0 0,0 0,0 0,0
1300 31,6 2932 35,0 37,6 0,0 0,0 0,0 0,0 0,0 0,0
1400 32,6 3089 37,0 39,6 0,0 0,0 0,0 0,0 0,0 0,0
1500 32,9 3213 38,6 41,2 0,0 0,0 0,0 0,0 0,0 0,0
1600 32,6 3278 39,4 42,1 0,0 0,0 0,0 0,0 0,0 0,0
1700 31,7 3235 38,9 41,5 0,0 0,0 0,0 0,0 0,0 0,0
1800 30,5 3068 36,7 39,4 0,0 0,0 0,0 0,0 0,0 0,0
1900 29,0 2975 35,5 38,2 0,0 0,0 0,0 0,0 0,0 0,0
2000 27,4 2867 34,1 36,8 0,0 0,0 0,0 0,0 0,0 0,0
2100 26,2 2759 32,8 35,4 0,0 0,0 0,0 0,0 0,0 0,0
2200 25,0 2658 31,5 34,1 0,0 0,0 0,0 0,0 0,0 0,0
2300 24,1 2566 30,3 33,0 0,0 0,0 0,0 0,0 0,0 0,0

Hourly Analysis Program v4.90 Page 7 of 11


Hourly Zone Loads for A06-R2-Espace de travail
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:06

ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 23,4 22,6 53 2481,8 29403,0 29271,1 0,0 0,0 0,0
0100 22,8 22,5 53 2405,1 28417,3 28313,4 0,0 0,0 0,0
0200 22,2 22,5 53 2334,2 27512,4 27430,4 0,0 0,0 0,0
0300 21,8 22,5 53 2270,1 26701,9 26635,3 0,0 0,0 0,0
0400 21,4 22,5 53 2212,0 25972,9 25916,7 0,0 0,0 0,0
0500 21,3 22,5 53 2159,6 25321,3 25271,2 0,0 0,0 0,0
0600 21,5 22,5 53 2170,5 25491,9 25404,6 0,0 0,0 0,0
0700 22,1 22,5 53 2345,2 27799,1 27567,0 0,0 0,0 0,0
0800 23,2 22,5 53 2440,3 29054,4 28752,2 0,0 0,0 0,0
0900 24,7 22,6 53 2514,8 30036,5 29683,8 0,0 0,0 0,0
1000 26,4 22,6 52 2583,7 30943,7 30549,1 0,0 0,0 0,0
1100 28,4 22,6 52 2660,3 31953,1 31515,0 0,0 0,0 0,0
1200 30,2 22,6 52 2777,0 33498,6 32992,7 0,0 0,0 0,0
1300 31,6 22,7 52 2932,3 35566,1 34972,1 0,0 0,0 0,0
1400 32,6 22,7 52 3089,3 37663,4 36989,0 0,0 0,0 0,0
1500 32,9 22,7 51 3213,4 39317,8 38593,6 0,0 0,0 0,0
1600 32,6 22,7 51 3277,6 40156,4 39429,0 0,0 0,0 0,0
1700 31,7 22,7 51 3235,4 39534,9 38879,5 0,0 0,0 0,0
1800 30,5 22,7 52 3067,9 37216,6 36712,7 0,0 0,0 0,0
1900 29,0 22,7 52 2975,5 35952,0 35524,7 0,0 0,0 0,0
2000 27,4 22,6 52 2866,9 34482,3 34136,6 0,0 0,0 0,0
2100 26,2 22,6 52 2759,4 33042,9 32768,5 0,0 0,0 0,0
2200 25,0 22,6 52 2658,2 31703,2 31487,9 0,0 0,0 0,0
2300 24,1 22,6 52 2565,7 30491,8 30323,5 0,0 0,0 0,0

Hourly Analysis Program v4.90 Page 8 of 11


System Psychrometrics for A06-R2-Espace de travail
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:06

July DESIGN COOLING DAY, 1600

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 32,6 0,02036 0 400 0 0
Vent - Return Mixing Outlet 22,7 0,00885 3278 2320 - -
Preheat Coil Outlet 22,7 0,00885 3278 2320 0 -
Central Cooling Coil Outlet 12,8 0,00857 3278 2320 39429 2706
Supply Fan Outlet 12,8 0,00857 3278 2320 0 -
Cold Supply Duct Outlet 12,8 0,00857 3278 2320 - -
Zone Air - 22,7 0,00885 3278 2320 39429 2644
Return Plenum Outlet 22,7 0,00885 3278 2320 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 40156 Cooling 39429 22,7 3278 2320 0 0

Hourly Analysis Program v4.90 Page 9 of 11


System Psychrometrics for A06-R2-Espace de travail
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:06

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 22,0 0,01667 0 400 0 0
Vent - Return Mixing Outlet 20,5 0,00866 36 800 - -
Preheat Coil Outlet 20,5 0,00866 36 800 0 -
Central Cooling Coil Outlet 12,8 0,00866 36 800 335 0
Supply Fan Outlet 12,8 0,00866 36 800 0 -
Cold Supply Duct Outlet 12,8 0,00866 36 800 - -
Zone Air - 20,5 0,00866 36 800 335 0
Return Plenum Outlet 20,5 0,00866 36 800 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 0 Heating 335 20,5 36 800 0 0

Hourly Analysis Program v4.90 Page 10 of 11


Psychrometric Analysis for A06-R2-Espace de travail
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:06

Location: OUIDAH, BENIN


Altitude: 5,8 m.
Data for: July DESIGN COOLING DAY, 1600

1. Central Cooling Coil Outlet


2. Supply Fan Outlet
3. Room Air 0,024
0,022
0,020

Specific Humidity ( kg/kg )


0,018
0,016
0,014
0,012

12 3 0,010
0,008
0,006
0,004
0,002
0,000
0 5 10 15 20 25 30 35
Temperature ( °C )

Hourly Analysis Program v4.90 Page 11 of 11


Air System Sizing Summary for A06-R2-Espace lounge
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:34

Air System Information


Air System Name .................. A06-R2-Espace lounge Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area ................................................................ 42,7 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ........................................................ 6,8 kW Load occurs at ................................................. Sep 0900
Sensible coil load ................................................... 6,4 kW OA DB / WB ................................................... 23,6 / 23,3 °C
Coil L/s at Sep 0900 ............................................. 529 L/s Entering DB / WB ........................................... 22,7 / 16,2 °C
Max block L/s at Sep 0900 .................................... 583 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s ........................................... 583 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,936 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 6,3 Resulting RH .............................................................. 51 %
W/m² .................................................................. 159,1 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K

Preheat Coil Sizing Data


No heating coil loads occurred during this calculation.

Supply Fan Sizing Data

Actual max L/s at Sep 0900 .................................. 583 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ......................................................... 582 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 13,64 L/(s-m²) Fan static ...................................................................... 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s ..................................................... 0 L/s L/s/person ................................................................ 0,00 L/s/person
L/(s-m²) ................................................................. 0,00 L/(s-m²)

Hourly Analysis Program v4.90 Page 1 of 13


Zone Sizing Summary for A06-R1-Espace lounge
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:34

Air System Information


Air System Name .................. A06-R1-Espace lounge Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area ................................................................ 42,7 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 6,5 583 6 Sep 0900 0,0 42,7 13,64

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
A06-R1-Espace lounge 1 6,5 Sep 0900 583 0,0 42,7 13,64

Hourly Analysis Program v4.90 Page 2 of 13


Ventilation Sizing Summary for A06-R1-Espace lounge
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:34

1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 L/s

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (m²) Occupants (L/s) (L/s/person) (L/(s-m²)) (L/s) (% of supply) (L/s)
Zone 1
A06-R1-Espace lounge 1 42,7 12,0 582,5 0,00 0,00 0,0 0,0 0,0
Totals (incl. Space Multipliers) 582,5 0,0

Hourly Analysis Program v4.90 Page 3 of 13


Air System Design Load Summary for A06-R1-Espace lounge
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:34

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Sep 0900 HEATING DATA AT DES HTG
COOLING OA DB / WB 23,6 °C / 23,3 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 14 m² 2441 - 14 m² - -
Wall Transmission 17 m² 200 - 17 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 14 m² 39 - 14 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 36 m² 3 - 36 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 854 W 854 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2135 W 2135 - 0 0 -
People 12 809 422 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 6481 422 - 0 0
Zone Conditioning - 6362 422 - -54 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 529 L/s 0 - 6 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 529 L/s 0 - 6 L/s 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 6362 422 - -54 0
Central Cooling Coil - 6362 431 - -54 0
Preheat Coil - 0 - - 0 -
Terminal Reheat Coils - 0 - - 0 -
>> Total Conditioning - 6362 431 - -54 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 4 of 13


Zone Design Load Summary for A06-R1-Espace lounge
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:34

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Sep 0900 HEATING DATA AT DES HTG
COOLING OA DB / WB 23,6 °C / 23,3 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 14 m² 2441 - 14 m² - -
Wall Transmission 17 m² 200 - 17 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 14 m² 39 - 14 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 36 m² 3 - 36 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 854 W 854 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2135 W 2135 - 0 0 -
People 12 809 422 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 6481 422 - 0 0

Hourly Analysis Program v4.90 Page 5 of 13


Space Design Load Summary for A06-R1-Espace lounge
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:34

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A06-R1-Espace lounge '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Sep 0900 HEATING DATA AT DES HTG
COOLING OA DB / WB 23,6 °C / 23,3 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 14 m² 2441 - 14 m² - -
Wall Transmission 17 m² 200 - 17 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 14 m² 39 - 14 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 36 m² 3 - 36 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 854 W 854 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2135 W 2135 - 0 0 -
People 12 809 422 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 6481 422 - 0 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A06-R1-Espace lounge '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SE EXPOSURE
WALL 6 1,471 - 70 - 0
WINDOW 1 4 1,700 0,811 11 666 0
E EXPOSURE
WALL 5 1,471 - 68 - 0
WINDOW 1 6 1,700 0,811 17 1238 0
NE EXPOSURE
WALL 6 1,471 - 63 - 0
WINDOW 1 4 1,700 0,811 11 536 0

Hourly Analysis Program v4.90 Page 6 of 13


Hourly Air System Design Day Loads for A06-R1-Espace lounge
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:34

DESIGN MONTH: JULY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 23,4 424 5,0 5,4 0,0 0,0 0,0 0,0 0,0 0,0
0100 22,8 417 4,9 5,3 0,0 0,0 0,0 0,0 0,0 0,0
0200 22,2 410 4,8 5,3 0,0 0,0 0,0 0,0 0,0 0,0
0300 21,8 404 4,8 5,2 0,0 0,0 0,0 0,0 0,0 0,0
0400 21,4 399 4,7 5,1 0,0 0,0 0,0 0,0 0,0 0,0
0500 21,3 394 4,6 5,1 0,0 0,0 0,0 0,0 0,0 0,0
0600 21,5 408 4,8 5,2 0,0 0,0 0,0 0,0 0,0 0,0
0700 22,1 472 5,6 6,1 0,0 0,0 0,0 0,0 0,0 0,0
0800 23,2 503 6,0 6,5 0,0 0,0 0,0 0,0 0,0 0,0
0900 24,7 517 6,2 6,6 0,0 0,0 0,0 0,0 0,0 0,0
1000 26,4 517 6,2 6,6 0,0 0,0 0,0 0,0 0,0 0,0
1100 28,4 508 6,1 6,5 0,0 0,0 0,0 0,0 0,0 0,0
1200 30,2 503 6,0 6,4 0,0 0,0 0,0 0,0 0,0 0,0
1300 31,6 504 6,0 6,5 0,0 0,0 0,0 0,0 0,0 0,0
1400 32,6 504 6,0 6,5 0,0 0,0 0,0 0,0 0,0 0,0
1500 32,9 502 6,0 6,4 0,0 0,0 0,0 0,0 0,0 0,0
1600 32,6 496 5,9 6,4 0,0 0,0 0,0 0,0 0,0 0,0
1700 31,7 486 5,8 6,2 0,0 0,0 0,0 0,0 0,0 0,0
1800 30,5 473 5,6 6,1 0,0 0,0 0,0 0,0 0,0 0,0
1900 29,0 464 5,5 5,9 0,0 0,0 0,0 0,0 0,0 0,0
2000 27,4 455 5,4 5,8 0,0 0,0 0,0 0,0 0,0 0,0
2100 26,2 447 5,3 5,7 0,0 0,0 0,0 0,0 0,0 0,0
2200 25,0 439 5,2 5,6 0,0 0,0 0,0 0,0 0,0 0,0
2300 24,1 431 5,1 5,5 0,0 0,0 0,0 0,0 0,0 0,0

Hourly Analysis Program v4.90 Page 7 of 13


Hourly Zone Loads for A06-R1-Espace lounge
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:34

ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 23,4 22,6 52 423,8 5043,1 5016,2 0,0 0,0 0,0
0100 22,8 22,6 52 417,1 4956,5 4931,4 0,0 0,0 0,0
0200 22,2 22,6 52 410,4 4871,5 4848,1 0,0 0,0 0,0
0300 21,8 22,6 52 404,5 4795,9 4773,5 0,0 0,0 0,0
0400 21,4 22,6 53 399,1 4728,0 4706,1 0,0 0,0 0,0
0500 21,3 22,5 53 394,2 4666,3 4644,6 0,0 0,0 0,0
0600 21,5 22,6 52 408,4 4859,5 4822,9 0,0 0,0 0,0
0700 22,1 22,7 52 472,2 5719,7 5631,0 0,0 0,0 0,0
0800 23,2 22,7 52 503,5 6140,9 6032,6 0,0 0,0 0,0
0900 24,7 22,7 51 517,1 6321,6 6209,1 0,0 0,0 0,0
1000 26,4 22,7 51 516,7 6309,5 6203,9 0,0 0,0 0,0
1100 28,4 22,7 51 508,3 6189,3 6095,7 0,0 0,0 0,0
1200 30,2 22,7 52 503,5 6118,8 6032,9 0,0 0,0 0,0
1300 31,6 22,7 52 504,0 6123,7 6040,1 0,0 0,0 0,0
1400 32,6 22,7 52 504,4 6125,6 6044,4 0,0 0,0 0,0
1500 32,9 22,7 52 501,9 6088,9 6012,1 0,0 0,0 0,0
1600 32,6 22,7 52 495,9 6005,6 5935,3 0,0 0,0 0,0
1700 31,7 22,7 52 486,0 5869,3 5807,9 0,0 0,0 0,0
1800 30,5 22,7 52 473,3 5696,3 5645,0 0,0 0,0 0,0
1900 29,0 22,7 52 464,3 5575,7 5530,2 0,0 0,0 0,0
2000 27,4 22,6 52 455,3 5455,7 5415,5 0,0 0,0 0,0
2100 26,2 22,6 52 446,8 5343,4 5307,6 0,0 0,0 0,0
2200 25,0 22,6 52 438,6 5235,1 5203,1 0,0 0,0 0,0
2300 24,1 22,6 52 430,9 5134,9 5105,9 0,0 0,0 0,0

Hourly Analysis Program v4.90 Page 8 of 13


System Psychrometrics for A06-R1-Espace lounge
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:34

September DESIGN COOLING DAY, 0900

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 23,6 0,01793 0 400 0 0
Vent - Return Mixing Outlet 22,7 0,00885 529 2799 - -
Preheat Coil Outlet 22,7 0,00885 529 2799 0 -
Central Cooling Coil Outlet 12,8 0,00857 529 2799 6362 431
Supply Fan Outlet 12,8 0,00857 529 2799 0 -
Cold Supply Duct Outlet 12,8 0,00857 529 2799 - -
Zone Air - 22,7 0,00884 529 2799 6362 422
Return Plenum Outlet 22,7 0,00884 529 2799 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 6481 Cooling 6362 22,7 529 2799 0 0

Hourly Analysis Program v4.90 Page 9 of 13


System Psychrometrics for A06-R1-Espace lounge
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:34

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 22,0 0,01667 0 400 0 0
Vent - Return Mixing Outlet 20,5 0,00866 6 800 - -
Preheat Coil Outlet 20,5 0,00866 6 800 0 -
Central Cooling Coil Outlet 12,8 0,00866 6 800 54 0
Supply Fan Outlet 12,8 0,00866 6 800 0 -
Cold Supply Duct Outlet 12,8 0,00866 6 800 - -
Zone Air - 20,5 0,00866 6 800 54 0
Return Plenum Outlet 20,5 0,00866 6 800 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 0 Heating 54 20,5 6 800 0 0

Hourly Analysis Program v4.90 Page 10 of 13


Hourly Air System Design Day Loads for A06-R1-Espace lounge
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:34

Data for July

Total Cooling Total Heating


6,5
6,0
5,5
5,0
4,5
Load ( kW )

4,0
3,5
3,0
2,5
2,0
1,5
1,0
0,5
0,0
00 02 04 06 08 10 12 14 16 18 20 22
01 03 05 07 09 11 13 15 17 19 21 23
Hour of Day

Hourly Analysis Program v4.90 Page 11 of 13


Hourly Zone Design Day Loads for A06-R1-Espace lounge
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:34

Zone: Zone 1
Data for July

Zone Sensible Zone Conditioning


6500
6000
5500
5000
4500
4000
3500
W

3000
2500
2000
1500
1000
500
0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Hourly Analysis Program v4.90 Page 12 of 13


Psychrometric Analysis for A06-R1-Espace lounge
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:34

Location: OUIDAH, BENIN


Altitude: 5,8 m.
Data for: September DESIGN COOLING DAY, 0900
0,020
1. Central Cooling Coil Outlet
2. Supply Fan Outlet
3. Room Air
0,018

0,016

Specific Humidity ( kg/kg )


0,014

0,012

3
0,010
12
0,008

0,006

0,004

0,002

0,000
0 5 10 15 20 25 30 35
Temperature ( °C )

Hourly Analysis Program v4.90 Page 13 of 13


Air System Sizing Summary for A06-R2-Salle de réunion 1
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:35

Air System Information


Air System Name ............. A06-R2-Salle de réunion 1 Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area ................................................................ 31,8 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ........................................................ 6,1 kW Load occurs at ................................................. Sep 1600
Sensible coil load ................................................... 5,8 kW OA DB / WB ................................................... 31,4 / 26,5 °C
Coil L/s at Sep 1600 ............................................. 480 L/s Entering DB / WB ........................................... 22,8 / 16,2 °C
Max block L/s at Sep 1600 .................................... 527 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s ........................................... 527 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,941 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 5,2 Resulting RH .............................................................. 51 %
W/m² .................................................................. 192,8 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K

Preheat Coil Sizing Data


No heating coil loads occurred during this calculation.

Supply Fan Sizing Data

Actual max L/s at Sep 1600 .................................. 527 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ......................................................... 527 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 16,59 L/(s-m²) Fan static ...................................................................... 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s ..................................................... 0 L/s L/s/person ................................................................ 0,00 L/s/person
L/(s-m²) ................................................................. 0,00 L/(s-m²)

Hourly Analysis Program v4.90 Page 1 of 13


Zone Sizing Summary for A06-R1-Salle de réunion 1
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:35

Air System Information


Air System Name ............. A06-R1-Salle de réunion 1 Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area ................................................................ 31,8 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 5,9 527 5 Sep 1600 0,0 31,8 16,59

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
A06-R1-S.de réunion 1 1 5,9 Sep 1600 527 0,0 31,8 16,59

Hourly Analysis Program v4.90 Page 2 of 13


Ventilation Sizing Summary for A06-R1-Salle de réunion 1
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:35

1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 L/s

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (m²) Occupants (L/s) (L/s/person) (L/(s-m²)) (L/s) (% of supply) (L/s)
Zone 1
A06-R1-S.de réunion 1 1 31,8 6,0 527,4 0,00 0,00 0,0 0,0 0,0
Totals (incl. Space Multipliers) 527,4 0,0

Hourly Analysis Program v4.90 Page 3 of 13


Air System Design Load Summary for A06-R1-Salle de réunion 1
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:35

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Sep 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 31,4 °C / 26,5 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 16 m² 2806 - 16 m² - -
Wall Transmission 14 m² 166 - 14 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 16 m² 210 - 16 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 8 m² 29 - 8 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 636 W 636 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1590 W 1590 - 0 0 -
People 6 431 361 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 5868 361 - 0 0
Zone Conditioning - 5769 361 - -48 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 480 L/s 0 - 5 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 480 L/s 0 - 5 L/s 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 5769 361 - -48 0
Central Cooling Coil - 5769 361 - -48 0
Preheat Coil - 0 - - 0 -
Terminal Reheat Coils - 0 - - 0 -
>> Total Conditioning - 5769 361 - -48 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 4 of 13


Zone Design Load Summary for A06-R1-Salle de réunion 1
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:35

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Sep 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 31,4 °C / 26,5 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 16 m² 2806 - 16 m² - -
Wall Transmission 14 m² 166 - 14 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 16 m² 210 - 16 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 8 m² 29 - 8 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 636 W 636 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1590 W 1590 - 0 0 -
People 6 431 361 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 5868 361 - 0 0

Hourly Analysis Program v4.90 Page 5 of 13


Space Design Load Summary for A06-R1-Salle de réunion 1
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:35

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A06-R1-S.de réunion 1 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Sep 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 31,4 °C / 26,5 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 16 m² 2806 - 16 m² - -
Wall Transmission 14 m² 166 - 14 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 16 m² 210 - 16 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 8 m² 29 - 8 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 636 W 636 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1590 W 1590 - 0 0 -
People 6 431 361 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 5868 361 - 0 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A06-R1-S.de réunion 1 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NW EXPOSURE
WALL 7 1,471 - 78 - 0
WINDOW 1 8 1,700 0,811 105 1285 0
SW EXPOSURE
WALL 7 1,471 - 88 - 0
WINDOW 1 8 1,700 0,811 105 1521 0

Hourly Analysis Program v4.90 Page 6 of 13


Hourly Air System Design Day Loads for A06-R1-Salle de réunion 1
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:35

DESIGN MONTH: JULY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 23,4 352 4,1 4,5 0,0 0,0 0,0 0,0 0,0 0,0
0100 22,8 345 4,1 4,4 0,0 0,0 0,0 0,0 0,0 0,0
0200 22,2 337 4,0 4,3 0,0 0,0 0,0 0,0 0,0 0,0
0300 21,8 330 3,9 4,2 0,0 0,0 0,0 0,0 0,0 0,0
0400 21,4 324 3,8 4,1 0,0 0,0 0,0 0,0 0,0 0,0
0500 21,3 318 3,7 4,1 0,0 0,0 0,0 0,0 0,0 0,0
0600 21,5 315 3,7 4,0 0,0 0,0 0,0 0,0 0,0 0,0
0700 22,1 320 3,7 4,1 0,0 0,0 0,0 0,0 0,0 0,0
0800 23,2 325 3,8 4,2 0,0 0,0 0,0 0,0 0,0 0,0
0900 24,7 331 3,9 4,3 0,0 0,0 0,0 0,0 0,0 0,0
1000 26,4 338 4,0 4,3 0,0 0,0 0,0 0,0 0,0 0,0
1100 28,4 346 4,1 4,4 0,0 0,0 0,0 0,0 0,0 0,0
1200 30,2 364 4,3 4,7 0,0 0,0 0,0 0,0 0,0 0,0
1300 31,6 388 4,6 5,0 0,0 0,0 0,0 0,0 0,0 0,0
1400 32,6 420 5,0 5,4 0,0 0,0 0,0 0,0 0,0 0,0
1500 32,9 450 5,4 5,8 0,0 0,0 0,0 0,0 0,0 0,0
1600 32,6 468 5,6 6,0 0,0 0,0 0,0 0,0 0,0 0,0
1700 31,7 455 5,5 5,8 0,0 0,0 0,0 0,0 0,0 0,0
1800 30,5 403 4,8 5,1 0,0 0,0 0,0 0,0 0,0 0,0
1900 29,0 394 4,7 5,0 0,0 0,0 0,0 0,0 0,0 0,0
2000 27,4 385 4,6 4,9 0,0 0,0 0,0 0,0 0,0 0,0
2100 26,2 377 4,5 4,8 0,0 0,0 0,0 0,0 0,0 0,0
2200 25,0 368 4,3 4,7 0,0 0,0 0,0 0,0 0,0 0,0
2300 24,1 360 4,2 4,6 0,0 0,0 0,0 0,0 0,0 0,0

Hourly Analysis Program v4.90 Page 7 of 13


Hourly Zone Loads for A06-R1-Salle de réunion 1
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:35

ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 23,4 22,5 53 352,0 4158,0 4144,6 0,0 0,0 0,0
0100 22,8 22,5 53 344,6 4062,5 4051,5 0,0 0,0 0,0
0200 22,2 22,5 53 337,2 3969,3 3960,3 0,0 0,0 0,0
0300 21,8 22,5 53 330,3 3882,1 3874,7 0,0 0,0 0,0
0400 21,4 22,5 53 323,8 3800,7 3794,5 0,0 0,0 0,0
0500 21,3 22,5 53 317,9 3726,8 3721,3 0,0 0,0 0,0
0600 21,5 22,5 53 314,6 3686,7 3680,4 0,0 0,0 0,0
0700 22,1 22,5 53 319,6 3754,7 3742,5 0,0 0,0 0,0
0800 23,2 22,5 53 325,0 3825,9 3808,5 0,0 0,0 0,0
0900 24,7 22,5 53 331,2 3908,1 3885,7 0,0 0,0 0,0
1000 26,4 22,5 53 338,4 4001,9 3974,4 0,0 0,0 0,0
1100 28,4 22,5 53 346,4 4106,7 4074,2 0,0 0,0 0,0
1200 30,2 22,6 52 363,7 4333,2 4290,3 0,0 0,0 0,0
1300 31,6 22,6 52 388,2 4654,8 4598,4 0,0 0,0 0,0
1400 32,6 22,6 52 419,9 5073,9 5000,8 0,0 0,0 0,0
1500 32,9 22,7 51 450,3 5477,3 5390,1 0,0 0,0 0,0
1600 32,6 22,7 51 468,2 5714,0 5622,1 0,0 0,0 0,0
1700 31,7 22,7 51 455,0 5527,9 5451,7 0,0 0,0 0,0
1800 30,5 22,6 52 403,2 4826,3 4787,8 0,0 0,0 0,0
1900 29,0 22,6 52 394,0 4705,3 4671,9 0,0 0,0 0,0
2000 27,4 22,6 52 385,1 4587,7 4559,6 0,0 0,0 0,0
2100 26,2 22,6 52 376,5 4474,8 4451,3 0,0 0,0 0,0
2200 25,0 22,6 52 368,0 4363,7 4344,3 0,0 0,0 0,0
2300 24,1 22,5 52 359,8 4257,9 4241,8 0,0 0,0 0,0

Hourly Analysis Program v4.90 Page 8 of 13


System Psychrometrics for A06-R1-Salle de réunion 1
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:35

September DESIGN COOLING DAY, 1600

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 31,4 0,01984 0 400 0 0
Vent - Return Mixing Outlet 22,8 0,00882 480 2217 - -
Preheat Coil Outlet 22,8 0,00882 480 2217 0 -
Central Cooling Coil Outlet 12,8 0,00857 480 2217 5769 361
Supply Fan Outlet 12,8 0,00857 480 2217 0 -
Cold Supply Duct Outlet 12,8 0,00857 480 2217 - -
Zone Air - 22,8 0,00882 480 2217 5769 361
Return Plenum Outlet 22,8 0,00882 480 2217 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 5868 Cooling 5769 22,8 480 2217 0 0

Hourly Analysis Program v4.90 Page 9 of 13


System Psychrometrics for A06-R1-Salle de réunion 1
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:35

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 22,0 0,01667 0 400 0 0
Vent - Return Mixing Outlet 20,3 0,00866 5 800 - -
Preheat Coil Outlet 20,3 0,00866 5 800 0 -
Central Cooling Coil Outlet 12,8 0,00866 5 800 48 0
Supply Fan Outlet 12,8 0,00866 5 800 0 -
Cold Supply Duct Outlet 12,8 0,00866 5 800 - -
Zone Air - 20,3 0,00866 5 800 48 0
Return Plenum Outlet 20,3 0,00866 5 800 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 0 Heating 48 20,3 5 800 0 0

Hourly Analysis Program v4.90 Page 10 of 13


Hourly Air System Design Day Loads for A06-R1-Salle de réunion 1
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:35

Data for July

Total Cooling Total Heating


6,0
5,5
5,0
4,5
4,0
Load ( kW )

3,5
3,0
2,5
2,0
1,5
1,0
0,5
0,0
00 02 04 06 08 10 12 14 16 18 20 22
01 03 05 07 09 11 13 15 17 19 21 23
Hour of Day

Hourly Analysis Program v4.90 Page 11 of 13


Hourly Zone Design Day Loads for A06-R1-Salle de réunion 1
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:35

Zone: Zone 1
Data for July

Zone Sensible Zone Conditioning

5500
5000
4500
4000
3500
3000
W

2500
2000
1500
1000
500
0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Hourly Analysis Program v4.90 Page 12 of 13


Psychrometric Analysis for A06-R1-Salle de réunion 1
Project Name: A06 01/05/2024
Prepared by: ATOMAS 05:35

Location: OUIDAH, BENIN


Altitude: 5,8 m.
Data for: September DESIGN COOLING DAY, 1600
0,020
1. Central Cooling Coil Outlet
2. Supply Fan Outlet
3. Room Air
0,018

0,016

Specific Humidity ( kg/kg )


0,014

0,012

0,010
12 3

0,008

0,006

0,004

0,002

0,000
0 5 10 15 20 25 30 35
Temperature ( °C )

Hourly Analysis Program v4.90 Page 13 of 13


Air System Sizing Summary for A06-R2-Salle de réunion 2
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:04

Air System Information


Air System Name ............. A06-R2-Salle de réunion 2 Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area ................................................................ 73,8 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ....................................................... 13,3 kW Load occurs at ................................................. Jun 1600
Sensible coil load .................................................. 12,4 kW OA DB / WB ................................................... 32,0 / 27,0 °C
Coil L/s at Jun 1600 ............................................. 1027 L/s Entering DB / WB ........................................... 22,8 / 16,3 °C
Max block L/s at Jun 1600 ................................... 1130 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s .......................................... 1130 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,932 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 5,6 Resulting RH .............................................................. 51 %
W/m² .................................................................. 179,6 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K

Preheat Coil Sizing Data


No heating coil loads occurred during this calculation.

Supply Fan Sizing Data

Actual max L/s at Jun 1600 .................................. 1130 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ........................................................ 1129 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 15,31 L/(s-m²) Fan static ...................................................................... 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s ..................................................... 0 L/s L/s/person ................................................................ 0,00 L/s/person
L/(s-m²) ................................................................. 0,00 L/(s-m²)

Hourly Analysis Program v4.90 Page 1 of 6


Zone Sizing Summary for A06-R1-Salle de réunion 2
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:04

Air System Information


Air System Name ............. A06-R1-Salle de réunion 2 Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area ................................................................ 73,8 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 12,6 1130 11 Jun 1600 0,0 73,8 15,31

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
A06-R1-S.de réunion 2 3 4,2 Jun 1600 377 0,0 24,6 15,31

Hourly Analysis Program v4.90 Page 2 of 6


Air System Design Load Summary for A06-R1-Salle de réunion 2
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:04

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 32,0 °C / 27,0 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 24 m² 5474 - 24 m² - -
Wall Transmission 21 m² 321 - 21 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 24 m² 337 - 24 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 45 m² 191 - 45 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1476 W 1476 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 3690 W 3690 - 0 0 -
People 15 1077 901 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 12567 901 - 0 0
Zone Conditioning - 12350 901 - -105 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 1027 L/s 0 - 11 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 1027 L/s 0 - 11 L/s 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 12350 901 - -105 0
Central Cooling Coil - 12350 905 - -105 0
Preheat Coil - 0 - - 0 -
Terminal Reheat Coils - 0 - - 0 -
>> Total Conditioning - 12350 905 - -105 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 3 of 6


System Psychrometrics for A06-R1-Salle de réunion 2
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:04

June DESIGN COOLING DAY, 1600

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 32,0 0,02059 0 400 0 0
Vent - Return Mixing Outlet 22,8 0,00887 1027 2455 - -
Preheat Coil Outlet 22,8 0,00887 1027 2455 0 -
Central Cooling Coil Outlet 12,8 0,00857 1027 2455 12350 905
Supply Fan Outlet 12,8 0,00857 1027 2455 0 -
Cold Supply Duct Outlet 12,8 0,00857 1027 2455 - -
Zone Air - 22,8 0,00887 1027 2455 12350 901
Return Plenum Outlet 22,8 0,00887 1027 2455 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 12567 Cooling 12350 22,8 1027 2455 0 0

Hourly Analysis Program v4.90 Page 4 of 6


System Psychrometrics for A06-R1-Salle de réunion 2
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:04

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 22,0 0,01667 0 400 0 0
Vent - Return Mixing Outlet 20,5 0,00866 11 800 - -
Preheat Coil Outlet 20,5 0,00866 11 800 0 -
Central Cooling Coil Outlet 12,8 0,00866 11 800 105 0
Supply Fan Outlet 12,8 0,00866 11 800 0 -
Cold Supply Duct Outlet 12,8 0,00866 11 800 - -
Zone Air - 20,5 0,00866 11 800 105 0
Return Plenum Outlet 20,5 0,00866 11 800 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 0 Heating 105 20,5 11 800 0 0

Hourly Analysis Program v4.90 Page 5 of 6


Psychrometric Analysis for A06-R1-Salle de réunion 2
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:04

Location: OUIDAH, BENIN


Altitude: 5,8 m.
Data for: June DESIGN COOLING DAY, 1600

1. Central Cooling Coil Outlet


2. Supply Fan Outlet
3. Room Air 0,024
0,022
0,020

Specific Humidity ( kg/kg )


0,018
0,016
0,014
0,012

12 3 0,010
0,008
0,006
0,004
0,002
0,000
0 5 10 15 20 25 30 35
Temperature ( °C )

Hourly Analysis Program v4.90 Page 6 of 6


Air System Sizing Summary for A06-R2-Salle de réunion 3
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:05

Air System Information


Air System Name ............. A06-R2-Salle de réunion 3 Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area ................................................................ 31,3 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ........................................................ 5,2 kW Load occurs at ................................................. Jun 1600
Sensible coil load ................................................... 4,8 kW OA DB / WB ................................................... 32,0 / 27,0 °C
Coil L/s at Jun 1600 .............................................. 401 L/s Entering DB / WB ........................................... 22,8 / 16,3 °C
Max block L/s at Jun 1600 .................................... 441 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s ........................................... 441 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,930 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 6,0 Resulting RH .............................................................. 52 %
W/m² .................................................................. 165,8 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K

Preheat Coil Sizing Data


No heating coil loads occurred during this calculation.

Supply Fan Sizing Data

Actual max L/s at Jun 1600 ................................... 441 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ......................................................... 441 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 14,10 L/(s-m²) Fan static ...................................................................... 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s ..................................................... 0 L/s L/s/person ................................................................ 0,00 L/s/person
L/(s-m²) ................................................................. 0,00 L/(s-m²)

Hourly Analysis Program v4.90 Page 1 of 6


Zone Sizing Summary for A06-R1-Salle de réunion 3
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:05

Air System Information


Air System Name ............. A06-R1-Salle de réunion 3 Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area ................................................................ 31,3 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 4,9 441 4 Jun 1600 0,0 31,3 14,10

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
A06-R1-S.de réunion 3 1 4,9 Jun 1600 441 0,0 31,3 14,10

Hourly Analysis Program v4.90 Page 2 of 6


Air System Design Load Summary for A06-R1-Salle de réunion 3
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:05

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 32,0 °C / 27,0 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 8 m² 1825 - 8 m² - -
Wall Transmission 15 m² 290 - 15 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 8 m² 112 - 8 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 15 m² 62 - 15 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 626 W 626 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1565 W 1565 - 0 0 -
People 6 431 361 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 4910 361 - 0 0
Zone Conditioning - 4827 361 - -41 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 401 L/s 0 - 4 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 401 L/s 0 - 4 L/s 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 4827 361 - -41 0
Central Cooling Coil - 4827 362 - -41 0
Preheat Coil - 0 - - 0 -
Terminal Reheat Coils - 0 - - 0 -
>> Total Conditioning - 4827 362 - -41 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 3 of 6


System Psychrometrics for A06-R1-Salle de réunion 3
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:05

June DESIGN COOLING DAY, 1600

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 32,0 0,02059 0 400 0 0
Vent - Return Mixing Outlet 22,8 0,00888 401 2494 - -
Preheat Coil Outlet 22,8 0,00888 401 2494 0 -
Central Cooling Coil Outlet 12,8 0,00857 401 2494 4827 362
Supply Fan Outlet 12,8 0,00857 401 2494 0 -
Cold Supply Duct Outlet 12,8 0,00857 401 2494 - -
Zone Air - 22,8 0,00888 401 2494 4827 361
Return Plenum Outlet 22,8 0,00888 401 2494 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 4910 Cooling 4827 22,8 401 2494 0 0

Hourly Analysis Program v4.90 Page 4 of 6


System Psychrometrics for A06-R1-Salle de réunion 3
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:05

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 22,0 0,01667 0 400 0 0
Vent - Return Mixing Outlet 20,4 0,00866 4 800 - -
Preheat Coil Outlet 20,4 0,00866 4 800 0 -
Central Cooling Coil Outlet 12,8 0,00866 4 800 41 0
Supply Fan Outlet 12,8 0,00866 4 800 0 -
Cold Supply Duct Outlet 12,8 0,00866 4 800 - -
Zone Air - 20,4 0,00866 4 800 41 0
Return Plenum Outlet 20,4 0,00866 4 800 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 0 Heating 41 20,4 4 800 0 0

Hourly Analysis Program v4.90 Page 5 of 6


Psychrometric Analysis for A06-R1-Salle de réunion 3
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:05

Location: OUIDAH, BENIN


Altitude: 5,8 m.
Data for: June DESIGN COOLING DAY, 1600

1. Central Cooling Coil Outlet


2. Supply Fan Outlet
3. Room Air 0,024
0,022
0,020

Specific Humidity ( kg/kg )


0,018
0,016
0,014
0,012

12 3 0,010
0,008
0,006
0,004
0,002
0,000
0 5 10 15 20 25 30 35
Temperature ( °C )

Hourly Analysis Program v4.90 Page 6 of 6


Air System Sizing Summary for A06-R2-Salle de réunion 4
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:05

Air System Information


Air System Name ............. A06-R2-Salle de réunion 4 Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area ................................................................ 24,6 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ........................................................ 4,7 kW Load occurs at ................................................. Dec 1600
Sensible coil load ................................................... 4,4 kW OA DB / WB ................................................... 27,6 / 24,2 °C
Coil L/s at Dec 1600 ............................................. 364 L/s Entering DB / WB ........................................... 22,8 / 16,3 °C
Max block L/s at Dec 1600 .................................... 401 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s ........................................... 401 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,934 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 5,2 Resulting RH .............................................................. 51 %
W/m² .................................................................. 190,8 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K

Preheat Coil Sizing Data


No heating coil loads occurred during this calculation.

Supply Fan Sizing Data

Actual max L/s at Dec 1600 .................................. 401 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ......................................................... 400 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 16,29 L/(s-m²) Fan static ...................................................................... 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s ..................................................... 0 L/s L/s/person ................................................................ 0,00 L/s/person
L/(s-m²) ................................................................. 0,00 L/(s-m²)

Hourly Analysis Program v4.90 Page 1 of 6


Zone Sizing Summary for A06-R1-Salle de réunion 4
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:05

Air System Information


Air System Name ............. A06-R1-Salle de réunion 4 Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area ................................................................ 24,6 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 4,5 401 4 Dec 1600 0,0 24,6 16,29

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
A06-R1-S.de reunion 4 1 4,5 Dec 1600 401 0,0 24,6 16,29

Hourly Analysis Program v4.90 Page 2 of 6


Air System Design Load Summary for A06-R1-Salle de réunion 4
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:05

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Dec 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 27,6 °C / 24,2 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 8 m² 2223 - 8 m² - -
Wall Transmission 7 m² 77 - 7 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 8 m² 51 - 8 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 15 m² 26 - 15 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 492 W 492 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1230 W 1230 - 0 0 -
People 5 359 301 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 4458 301 - 0 0
Zone Conditioning - 4385 301 - -36 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 364 L/s 0 - 4 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 364 L/s 0 - 4 L/s 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 4385 301 - -36 0
Central Cooling Coil - 4385 309 - -36 0
Preheat Coil - 0 - - 0 -
Terminal Reheat Coils - 0 - - 0 -
>> Total Conditioning - 4385 309 - -36 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 3 of 6


System Psychrometrics for A06-R1-Salle de réunion 4
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:05

December DESIGN COOLING DAY, 1600

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 27,6 0,01774 0 400 0 0
Vent - Return Mixing Outlet 22,8 0,00886 364 2354 - -
Preheat Coil Outlet 22,8 0,00886 364 2354 0 -
Central Cooling Coil Outlet 12,8 0,00857 364 2354 4385 309
Supply Fan Outlet 12,8 0,00857 364 2354 0 -
Cold Supply Duct Outlet 12,8 0,00857 364 2354 - -
Zone Air - 22,8 0,00885 364 2354 4385 301
Return Plenum Outlet 22,8 0,00885 364 2354 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 4458 Cooling 4385 22,8 364 2354 0 0

Hourly Analysis Program v4.90 Page 4 of 6


System Psychrometrics for A06-R1-Salle de réunion 4
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:05

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 22,0 0,01667 0 400 0 0
Vent - Return Mixing Outlet 20,3 0,00866 4 800 - -
Preheat Coil Outlet 20,3 0,00866 4 800 0 -
Central Cooling Coil Outlet 12,8 0,00866 4 800 36 0
Supply Fan Outlet 12,8 0,00866 4 800 0 -
Cold Supply Duct Outlet 12,8 0,00866 4 800 - -
Zone Air - 20,3 0,00866 4 800 36 0
Return Plenum Outlet 20,3 0,00866 4 800 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 0 Heating 36 20,3 4 800 0 0

Hourly Analysis Program v4.90 Page 5 of 6


Psychrometric Analysis for A06-R1-Salle de réunion 4
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:05

Location: OUIDAH, BENIN


Altitude: 5,8 m.
Data for: December DESIGN COOLING DAY, 1600
0,020
1. Central Cooling Coil Outlet
2. Supply Fan Outlet
3. Room Air
0,018

0,016

Specific Humidity ( kg/kg )


0,014

0,012

3
0,010
12
0,008

0,006

0,004

0,002

0,000
0 5 10 15 20 25 30 35
Temperature ( °C )

Hourly Analysis Program v4.90 Page 6 of 6


Air System Sizing Summary for A06-R2-Salle de réunion 5
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:05

Air System Information


Air System Name ............. A06-R2-Salle de réunion 5 Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area ................................................................ 45,0 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ........................................................ 6,3 kW Load occurs at ................................................. Dec 1600
Sensible coil load ................................................... 6,0 kW OA DB / WB ................................................... 27,6 / 24,2 °C
Coil L/s at Dec 1600 ............................................. 496 L/s Entering DB / WB ........................................... 22,7 / 16,2 °C
Max block L/s at Dec 1600 .................................... 547 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s ........................................... 547 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,951 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 7,2 Resulting RH .............................................................. 51 %
W/m² .................................................................. 139,4 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K

Preheat Coil Sizing Data


No heating coil loads occurred during this calculation.

Supply Fan Sizing Data

Actual max L/s at Dec 1600 .................................. 547 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ......................................................... 547 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 12,16 L/(s-m²) Fan static ...................................................................... 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s ..................................................... 0 L/s L/s/person ................................................................ 0,00 L/s/person
L/(s-m²) ................................................................. 0,00 L/(s-m²)

Hourly Analysis Program v4.90 Page 1 of 6


Zone Sizing Summary for A06-R1-Salle de réunion 5
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:05

Air System Information


Air System Name ............. A06-R1-Salle de réunion 5 Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area ................................................................ 45,0 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 6,1 547 5 Dec 1600 0,0 45,0 12,16

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
A06-R1-S.de réunion 5 1 6,1 Dec 1600 547 0,0 45,0 12,16

Hourly Analysis Program v4.90 Page 2 of 6


Air System Design Load Summary for A06-R1-Salle de réunion 5
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:05

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Dec 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 27,6 °C / 24,2 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 8 m² 2223 - 8 m² - -
Wall Transmission 16 m² 233 - 16 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 8 m² 51 - 8 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 40 m² 70 - 40 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 900 W 900 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2250 W 2250 - 0 0 -
People 5 359 301 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 6085 301 - 0 0
Zone Conditioning - 5964 301 - -51 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 496 L/s 0 - 5 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 496 L/s 0 - 5 L/s 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 5964 301 - -51 0
Central Cooling Coil - 5964 308 - -51 0
Preheat Coil - 0 - - 0 -
Terminal Reheat Coils - 0 - - 0 -
>> Total Conditioning - 5964 308 - -51 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 3 of 6


System Psychrometrics for A06-R1-Salle de réunion 5
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:05

December DESIGN COOLING DAY, 1600

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 27,6 0,01774 0 400 0 0
Vent - Return Mixing Outlet 22,7 0,00877 496 1942 - -
Preheat Coil Outlet 22,7 0,00877 496 1942 0 -
Central Cooling Coil Outlet 12,8 0,00856 496 1942 5964 308
Supply Fan Outlet 12,8 0,00856 496 1942 0 -
Cold Supply Duct Outlet 12,8 0,00856 496 1942 - -
Zone Air - 22,7 0,00877 496 1942 5964 301
Return Plenum Outlet 22,7 0,00877 496 1942 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 6085 Cooling 5964 22,7 496 1942 0 0

Hourly Analysis Program v4.90 Page 4 of 6


System Psychrometrics for A06-R1-Salle de réunion 5
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:05

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 22,0 0,01667 0 400 0 0
Vent - Return Mixing Outlet 20,5 0,00866 5 800 - -
Preheat Coil Outlet 20,5 0,00866 5 800 0 -
Central Cooling Coil Outlet 12,8 0,00866 5 800 51 0
Supply Fan Outlet 12,8 0,00866 5 800 0 -
Cold Supply Duct Outlet 12,8 0,00866 5 800 - -
Zone Air - 20,5 0,00866 5 800 51 0
Return Plenum Outlet 20,5 0,00866 5 800 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 0 Heating 51 20,5 5 800 0 0

Hourly Analysis Program v4.90 Page 5 of 6


Psychrometric Analysis for A06-R1-Salle de réunion 5
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:05

Location: OUIDAH, BENIN


Altitude: 5,8 m.
Data for: December DESIGN COOLING DAY, 1600
0,020
1. Central Cooling Coil Outlet
2. Supply Fan Outlet
3. Room Air
0,018

0,016

Specific Humidity ( kg/kg )


0,014

0,012

0,010
12 3

0,008

0,006

0,004

0,002

0,000
0 5 10 15 20 25 30 35
Temperature ( °C )

Hourly Analysis Program v4.90 Page 6 of 6


Air System Sizing Summary for A06-R3-Espace lounge
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:09

Air System Information


Air System Name .................. A06-R3-Espace lounge Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area ................................................................ 64,2 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ....................................................... 10,2 kW Load occurs at ................................................ Aug 1600
Sensible coil load ................................................... 9,8 kW OA DB / WB ................................................... 32,6 / 27,0 °C
Coil L/s at Aug 1600 ............................................. 812 L/s Entering DB / WB ........................................... 22,7 / 16,1 °C
Max block L/s at Aug 1600 .................................... 894 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s ........................................... 894 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,958 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 6,3 Resulting RH .............................................................. 51 %
W/m² .................................................................. 158,8 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K

Preheat Coil Sizing Data


No heating coil loads occurred during this calculation.

Supply Fan Sizing Data

Actual max L/s at Aug 1600 .................................. 894 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ......................................................... 894 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 13,93 L/(s-m²) Fan static ...................................................................... 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s ..................................................... 0 L/s L/s/person ................................................................ 0,00 L/s/person
L/(s-m²) ................................................................. 0,00 L/(s-m²)

Hourly Analysis Program v4.90 Page 1 of 11


Zone Sizing Summary for A06-R3-Espace lounge
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:09

Air System Information


Air System Name .................. A06-R3-Espace lounge Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area ................................................................ 64,2 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 9,9 894 9 Aug 1600 0,0 64,2 13,93

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
A06-R3-Espace lounge 1 9,9 Aug 1600 894 0,0 64,2 13,93

Hourly Analysis Program v4.90 Page 2 of 11


Ventilation Sizing Summary for A06-R3-Espace lounge
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:09

1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 L/s

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (m²) Occupants (L/s) (L/s/person) (L/(s-m²)) (L/s) (% of supply) (L/s)
Zone 1
A06-R3-Espace lounge 1 64,2 12,0 894,3 0,00 0,00 0,0 0,0 0,0
Totals (incl. Space Multipliers) 894,3 0,0

Hourly Analysis Program v4.90 Page 3 of 11


Air System Design Load Summary for A06-R3-Espace lounge
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:09

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 32,6 °C / 27,0 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 14 m² 1532 - 14 m² - -
Wall Transmission 17 m² 323 - 17 m² 0 -
Roof Transmission 64 m² 2417 - 64 m² 0 -
Window Transmission 14 m² 209 - 14 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 36 m² 165 - 36 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1284 W 1284 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 3210 W 3210 - 0 0 -
People 12 809 422 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 9949 422 - 0 0
Zone Conditioning - 9765 422 - -84 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 812 L/s 0 - 9 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 812 L/s 0 - 9 L/s 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 9765 422 - -84 0
Central Cooling Coil - 9765 428 - -84 0
Preheat Coil - 0 - - 0 -
Terminal Reheat Coils - 0 - - 0 -
>> Total Conditioning - 9765 428 - -84 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 4 of 11


Zone Design Load Summary for A06-R3-Espace lounge
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:09

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 32,6 °C / 27,0 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 14 m² 1532 - 14 m² - -
Wall Transmission 17 m² 323 - 17 m² 0 -
Roof Transmission 64 m² 2417 - 64 m² 0 -
Window Transmission 14 m² 209 - 14 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 36 m² 165 - 36 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1284 W 1284 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 3210 W 3210 - 0 0 -
People 12 809 422 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 9949 422 - 0 0

Hourly Analysis Program v4.90 Page 5 of 11


Space Design Load Summary for A06-R3-Espace lounge
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:09

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A06-R3-Espace lounge '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 32,6 °C / 27,0 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 14 m² 1532 - 14 m² - -
Wall Transmission 17 m² 323 - 17 m² 0 -
Roof Transmission 64 m² 2417 - 64 m² 0 -
Window Transmission 14 m² 209 - 14 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 36 m² 165 - 36 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1284 W 1284 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 3210 W 3210 - 0 0 -
People 12 809 422 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 9949 422 - 0 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A06-R3-Espace lounge '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SE EXPOSURE
WALL 6 1,471 - 94 - 0
WINDOW 1 4 1,700 0,811 60 341 0
E EXPOSURE
WALL 5 1,471 - 112 - 0
WINDOW 1 6 1,700 0,811 89 737 0
NE EXPOSURE
WALL 6 1,471 - 117 - 0
WINDOW 1 4 1,700 0,811 60 454 0
H EXPOSURE
ROOF 64 1,137 - 2417 - 0

Hourly Analysis Program v4.90 Page 6 of 11


Hourly Air System Design Day Loads for A06-R3-Espace lounge
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:09

DESIGN MONTH: JULY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 23,4 637 7,5 7,9 0,0 0,0 0,0 0,0 0,0 0,0
0100 22,8 619 7,3 7,7 0,0 0,0 0,0 0,0 0,0 0,0
0200 22,2 602 7,1 7,5 0,0 0,0 0,0 0,0 0,0 0,0
0300 21,8 587 6,9 7,3 0,0 0,0 0,0 0,0 0,0 0,0
0400 21,4 573 6,7 7,1 0,0 0,0 0,0 0,0 0,0 0,0
0500 21,3 561 6,6 7,0 0,0 0,0 0,0 0,0 0,0 0,0
0600 21,5 569 6,7 7,1 0,0 0,0 0,0 0,0 0,0 0,0
0700 22,1 628 7,4 7,8 0,0 0,0 0,0 0,0 0,0 0,0
0800 23,2 658 7,8 8,2 0,0 0,0 0,0 0,0 0,0 0,0
0900 24,7 679 8,1 8,5 0,0 0,0 0,0 0,0 0,0 0,0
1000 26,4 693 8,2 8,7 0,0 0,0 0,0 0,0 0,0 0,0
1100 28,4 707 8,4 8,8 0,0 0,0 0,0 0,0 0,0 0,0
1200 30,2 727 8,7 9,1 0,0 0,0 0,0 0,0 0,0 0,0
1300 31,6 754 9,0 9,4 0,0 0,0 0,0 0,0 0,0 0,0
1400 32,6 779 9,3 9,8 0,0 0,0 0,0 0,0 0,0 0,0
1500 32,9 797 9,6 10,0 0,0 0,0 0,0 0,0 0,0 0,0
1600 32,6 804 9,7 10,1 0,0 0,0 0,0 0,0 0,0 0,0
1700 31,7 798 9,6 10,0 0,0 0,0 0,0 0,0 0,0 0,0
1800 30,5 781 9,4 9,8 0,0 0,0 0,0 0,0 0,0 0,0
1900 29,0 759 9,1 9,5 0,0 0,0 0,0 0,0 0,0 0,0
2000 27,4 732 8,7 9,2 0,0 0,0 0,0 0,0 0,0 0,0
2100 26,2 705 8,4 8,8 0,0 0,0 0,0 0,0 0,0 0,0
2200 25,0 680 8,1 8,5 0,0 0,0 0,0 0,0 0,0 0,0
2300 24,1 658 7,8 8,2 0,0 0,0 0,0 0,0 0,0 0,0

Hourly Analysis Program v4.90 Page 7 of 11


Hourly Zone Loads for A06-R3-Espace lounge
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:09

ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 23,4 22,6 52 637,2 7575,7 7532,5 0,0 0,0 0,0
0100 22,8 22,6 52 618,7 7335,6 7300,2 0,0 0,0 0,0
0200 22,2 22,5 52 601,7 7116,6 7087,1 0,0 0,0 0,0
0300 21,8 22,5 52 586,5 6923,5 6898,0 0,0 0,0 0,0
0400 21,4 22,5 52 572,9 6752,1 6729,1 0,0 0,0 0,0
0500 21,3 22,5 52 560,7 6598,9 6577,4 0,0 0,0 0,0
0600 21,5 22,5 52 568,6 6711,6 6675,7 0,0 0,0 0,0
0700 22,1 22,6 52 628,1 7506,6 7417,6 0,0 0,0 0,0
0800 23,2 22,6 51 658,5 7912,1 7800,1 0,0 0,0 0,0
0900 24,7 22,6 51 678,8 8182,7 8057,2 0,0 0,0 0,0
1000 26,4 22,6 51 693,4 8375,4 8242,0 0,0 0,0 0,0
1100 28,4 22,6 51 706,6 8549,8 8410,1 0,0 0,0 0,0
1200 30,2 22,7 51 727,3 8826,1 8674,6 0,0 0,0 0,0
1300 31,6 22,7 51 754,4 9189,6 9022,3 0,0 0,0 0,0
1400 32,6 22,7 51 779,2 9522,2 9342,5 0,0 0,0 0,0
1500 32,9 22,7 51 796,5 9752,0 9566,9 0,0 0,0 0,0
1600 32,6 22,7 51 803,6 9840,8 9659,0 0,0 0,0 0,0
1700 31,7 22,7 51 798,4 9760,7 9591,5 0,0 0,0 0,0
1800 30,5 22,7 51 781,1 9516,0 9367,4 0,0 0,0 0,0
1900 29,0 22,7 51 759,0 9208,1 9081,4 0,0 0,0 0,0
2000 27,4 22,7 51 732,1 8839,2 8735,7 0,0 0,0 0,0
2100 26,2 22,6 51 705,3 8477,4 8394,2 0,0 0,0 0,0
2200 25,0 22,6 51 680,3 8142,8 8076,4 0,0 0,0 0,0
2300 24,1 22,6 51 657,7 7842,9 7789,6 0,0 0,0 0,0

Hourly Analysis Program v4.90 Page 8 of 11


System Psychrometrics for A06-R3-Espace lounge
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:09

August DESIGN COOLING DAY, 1600

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 32,6 0,02036 0 400 0 0
Vent - Return Mixing Outlet 22,7 0,00874 812 2102 - -
Preheat Coil Outlet 22,7 0,00874 812 2102 0 -
Central Cooling Coil Outlet 12,8 0,00856 812 2102 9765 428
Supply Fan Outlet 12,8 0,00856 812 2102 0 -
Cold Supply Duct Outlet 12,8 0,00856 812 2102 - -
Zone Air - 22,7 0,00874 812 2102 9765 422
Return Plenum Outlet 22,7 0,00874 812 2102 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 9949 Cooling 9765 22,7 812 2102 0 0

Hourly Analysis Program v4.90 Page 9 of 11


System Psychrometrics for A06-R3-Espace lounge
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:09

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 22,0 0,01667 0 400 0 0
Vent - Return Mixing Outlet 20,5 0,00866 9 800 - -
Preheat Coil Outlet 20,5 0,00866 9 800 0 -
Central Cooling Coil Outlet 12,8 0,00866 9 800 84 0
Supply Fan Outlet 12,8 0,00866 9 800 0 -
Cold Supply Duct Outlet 12,8 0,00866 9 800 - -
Zone Air - 20,5 0,00866 9 800 84 0
Return Plenum Outlet 20,5 0,00866 9 800 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 0 Heating 84 20,5 9 800 0 0

Hourly Analysis Program v4.90 Page 10 of 11


Psychrometric Analysis for A06-R3-Espace lounge
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:09

Location: OUIDAH, BENIN


Altitude: 5,8 m.
Data for: August DESIGN COOLING DAY, 1600

1. Central Cooling Coil Outlet


2. Supply Fan Outlet
3. Room Air 0,024
0,022
0,020

Specific Humidity ( kg/kg )


0,018
0,016
0,014
0,012

12 3 0,010
0,008
0,006
0,004
0,002
0,000
0 5 10 15 20 25 30 35
Temperature ( °C )

Hourly Analysis Program v4.90 Page 11 of 11


Air System Sizing Summary for A06-R3-Salle de réunion 1
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:10

Air System Information


Air System Name ............. A06-R3-Salle de réunion 1 Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area ................................................................ 31,8 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ........................................................ 7,3 kW Load occurs at ................................................. Sep 1600
Sensible coil load ................................................... 6,9 kW OA DB / WB ................................................... 31,4 / 26,5 °C
Coil L/s at Sep 1600 ............................................. 576 L/s Entering DB / WB ........................................... 22,7 / 16,2 °C
Max block L/s at Sep 1600 .................................... 635 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s ........................................... 635 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,950 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 4,4 Resulting RH .............................................................. 51 %
W/m² .................................................................. 229,1 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K

Preheat Coil Sizing Data


No heating coil loads occurred during this calculation.

Supply Fan Sizing Data

Actual max L/s at Sep 1600 .................................. 635 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ......................................................... 634 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 19,96 L/(s-m²) Fan static ...................................................................... 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s ..................................................... 0 L/s L/s/person ................................................................ 0,00 L/s/person
L/(s-m²) ................................................................. 0,00 L/(s-m²)

Hourly Analysis Program v4.90 Page 1 of 11


Zone Sizing Summary for A06-R3-Salle de réunion 1
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:10

Air System Information


Air System Name ............. A06-R3-Salle de réunion 1 Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area ................................................................ 31,8 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 7,1 635 6 Sep 1600 0,0 31,8 19,96

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
A06-R3-S.de réunion 1 1 7,1 Sep 1600 635 0,0 31,8 19,96

Hourly Analysis Program v4.90 Page 2 of 11


Ventilation Sizing Summary for A06-R3-Salle de réunion 1
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:10

1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 L/s

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (m²) Occupants (L/s) (L/s/person) (L/(s-m²)) (L/s) (% of supply) (L/s)
Zone 1
A06-R3-S.de réunion 1 1 31,8 6,0 634,8 0,00 0,00 0,0 0,0 0,0
Totals (incl. Space Multipliers) 634,8 0,0

Hourly Analysis Program v4.90 Page 3 of 11


Air System Design Load Summary for A06-R3-Salle de réunion 1
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:10

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Sep 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 31,4 °C / 26,5 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 16 m² 2806 - 16 m² - -
Wall Transmission 14 m² 166 - 14 m² 0 -
Roof Transmission 32 m² 1194 - 32 m² 0 -
Window Transmission 16 m² 210 - 16 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 8 m² 29 - 8 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 636 W 636 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1590 W 1590 - 0 0 -
People 6 431 361 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 7062 361 - 0 0
Zone Conditioning - 6926 361 - -59 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 576 L/s 0 - 6 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 576 L/s 0 - 6 L/s 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 6926 361 - -59 0
Central Cooling Coil - 6926 361 - -59 0
Preheat Coil - 0 - - 0 -
Terminal Reheat Coils - 0 - - 0 -
>> Total Conditioning - 6926 361 - -59 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 4 of 11


Zone Design Load Summary for A06-R3-Salle de réunion 1
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:10

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Sep 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 31,4 °C / 26,5 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 16 m² 2806 - 16 m² - -
Wall Transmission 14 m² 166 - 14 m² 0 -
Roof Transmission 32 m² 1194 - 32 m² 0 -
Window Transmission 16 m² 210 - 16 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 8 m² 29 - 8 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 636 W 636 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1590 W 1590 - 0 0 -
People 6 431 361 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 7062 361 - 0 0

Hourly Analysis Program v4.90 Page 5 of 11


Space Design Load Summary for A06-R3-Salle de réunion 1
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:10

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A06-R3-S.de réunion 1 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Sep 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 31,4 °C / 26,5 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 16 m² 2806 - 16 m² - -
Wall Transmission 14 m² 166 - 14 m² 0 -
Roof Transmission 32 m² 1194 - 32 m² 0 -
Window Transmission 16 m² 210 - 16 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 8 m² 29 - 8 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 636 W 636 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1590 W 1590 - 0 0 -
People 6 431 361 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 7062 361 - 0 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A06-R3-S.de réunion 1 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NW EXPOSURE
WALL 7 1,471 - 78 - 0
WINDOW 1 8 1,700 0,811 105 1285 0
SW EXPOSURE
WALL 7 1,471 - 88 - 0
WINDOW 1 8 1,700 0,811 105 1521 0
H EXPOSURE
ROOF 32 1,137 - 1194 - 0

Hourly Analysis Program v4.90 Page 6 of 11


Hourly Air System Design Day Loads for A06-R3-Salle de réunion 1
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:10

DESIGN MONTH: JULY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 23,4 396 4,6 5,0 0,0 0,0 0,0 0,0 0,0 0,0
0100 22,8 382 4,5 4,8 0,0 0,0 0,0 0,0 0,0 0,0
0200 22,2 370 4,3 4,7 0,0 0,0 0,0 0,0 0,0 0,0
0300 21,8 358 4,2 4,5 0,0 0,0 0,0 0,0 0,0 0,0
0400 21,4 347 4,0 4,4 0,0 0,0 0,0 0,0 0,0 0,0
0500 21,3 338 3,9 4,3 0,0 0,0 0,0 0,0 0,0 0,0
0600 21,5 331 3,8 4,2 0,0 0,0 0,0 0,0 0,0 0,0
0700 22,1 334 3,9 4,2 0,0 0,0 0,0 0,0 0,0 0,0
0800 23,2 338 3,9 4,3 0,0 0,0 0,0 0,0 0,0 0,0
0900 24,7 348 4,1 4,4 0,0 0,0 0,0 0,0 0,0 0,0
1000 26,4 363 4,2 4,6 0,0 0,0 0,0 0,0 0,0 0,0
1100 28,4 383 4,5 4,8 0,0 0,0 0,0 0,0 0,0 0,0
1200 30,2 414 4,9 5,2 0,0 0,0 0,0 0,0 0,0 0,0
1300 31,6 452 5,3 5,7 0,0 0,0 0,0 0,0 0,0 0,0
1400 32,6 496 5,9 6,3 0,0 0,0 0,0 0,0 0,0 0,0
1500 32,9 537 6,4 6,8 0,0 0,0 0,0 0,0 0,0 0,0
1600 32,6 561 6,7 7,1 0,0 0,0 0,0 0,0 0,0 0,0
1700 31,7 550 6,6 6,9 0,0 0,0 0,0 0,0 0,0 0,0
1800 30,5 496 5,9 6,3 0,0 0,0 0,0 0,0 0,0 0,0
1900 29,0 480 5,7 6,1 0,0 0,0 0,0 0,0 0,0 0,0
2000 27,4 462 5,5 5,8 0,0 0,0 0,0 0,0 0,0 0,0
2100 26,2 444 5,2 5,6 0,0 0,0 0,0 0,0 0,0 0,0
2200 25,0 426 5,0 5,4 0,0 0,0 0,0 0,0 0,0 0,0
2300 24,1 411 4,8 5,2 0,0 0,0 0,0 0,0 0,0 0,0

Hourly Analysis Program v4.90 Page 7 of 11


Hourly Zone Loads for A06-R3-Salle de réunion 1
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:10

ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 23,4 22,5 52 396,0 4667,0 4643,9 0,0 0,0 0,0
0100 22,8 22,5 53 382,4 4495,5 4476,8 0,0 0,0 0,0
0200 22,2 22,5 53 369,8 4335,9 4320,7 0,0 0,0 0,0
0300 21,8 22,4 53 358,1 4190,5 4178,0 0,0 0,0 0,0
0400 21,4 22,4 53 347,4 4057,8 4047,3 0,0 0,0 0,0
0500 21,3 22,4 53 337,8 3938,6 3929,4 0,0 0,0 0,0
0600 21,5 22,4 53 331,2 3858,7 3849,1 0,0 0,0 0,0
0700 22,1 22,4 53 333,7 3894,3 3879,6 0,0 0,0 0,0
0800 23,2 22,4 53 338,4 3957,8 3937,4 0,0 0,0 0,0
0900 24,7 22,4 53 348,2 4084,5 4056,3 0,0 0,0 0,0
1000 26,4 22,5 53 363,3 4279,8 4241,7 0,0 0,0 0,0
1100 28,4 22,5 53 382,8 4530,5 4481,3 0,0 0,0 0,0
1200 30,2 22,5 52 413,6 4928,7 4863,0 0,0 0,0 0,0
1300 31,6 22,6 52 452,0 5428,0 5343,2 0,0 0,0 0,0
1400 32,6 22,6 52 496,5 6010,9 5905,2 0,0 0,0 0,0
1500 32,9 22,7 51 537,0 6546,3 6423,9 0,0 0,0 0,0
1600 32,6 22,7 51 561,5 6868,3 6739,8 0,0 0,0 0,0
1700 31,7 22,7 51 550,4 6710,0 6596,6 0,0 0,0 0,0
1800 30,5 22,6 52 495,9 5972,8 5897,4 0,0 0,0 0,0
1900 29,0 22,6 52 479,8 5759,1 5694,0 0,0 0,0 0,0
2000 27,4 22,6 52 461,7 5518,2 5464,4 0,0 0,0 0,0
2100 26,2 22,6 52 443,7 5281,7 5237,8 0,0 0,0 0,0
2200 25,0 22,5 52 426,5 5058,5 5023,1 0,0 0,0 0,0
2300 24,1 22,5 52 410,6 4853,7 4825,1 0,0 0,0 0,0

Hourly Analysis Program v4.90 Page 8 of 11


System Psychrometrics for A06-R3-Salle de réunion 1
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:10

September DESIGN COOLING DAY, 1600

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 31,4 0,01984 0 400 0 0
Vent - Return Mixing Outlet 22,7 0,00878 576 1980 - -
Preheat Coil Outlet 22,7 0,00878 576 1980 0 -
Central Cooling Coil Outlet 12,8 0,00856 576 1980 6926 361
Supply Fan Outlet 12,8 0,00856 576 1980 0 -
Cold Supply Duct Outlet 12,8 0,00856 576 1980 - -
Zone Air - 22,7 0,00878 576 1980 6926 361
Return Plenum Outlet 22,7 0,00878 576 1980 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 7062 Cooling 6926 22,7 576 1980 0 0

Hourly Analysis Program v4.90 Page 9 of 11


System Psychrometrics for A06-R3-Salle de réunion 1
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:10

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 22,0 0,01667 0 400 0 0
Vent - Return Mixing Outlet 20,4 0,00866 6 800 - -
Preheat Coil Outlet 20,4 0,00866 6 800 0 -
Central Cooling Coil Outlet 12,8 0,00866 6 800 59 0
Supply Fan Outlet 12,8 0,00866 6 800 0 -
Cold Supply Duct Outlet 12,8 0,00866 6 800 - -
Zone Air - 20,4 0,00866 6 800 59 0
Return Plenum Outlet 20,4 0,00866 6 800 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 0 Heating 59 20,4 6 800 0 0

Hourly Analysis Program v4.90 Page 10 of 11


Psychrometric Analysis for A06-R3-Salle de réunion 1
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:10

Location: OUIDAH, BENIN


Altitude: 5,8 m.
Data for: September DESIGN COOLING DAY, 1600
0,020
1. Central Cooling Coil Outlet
2. Supply Fan Outlet
3. Room Air
0,018

0,016

Specific Humidity ( kg/kg )


0,014

0,012

0,010
12 3

0,008

0,006

0,004

0,002

0,000
0 5 10 15 20 25 30 35
Temperature ( °C )

Hourly Analysis Program v4.90 Page 11 of 11


Air System Sizing Summary for A06-R3:Salle de réunion 2
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:07

Air System Information


Air System Name ............. A06-R3:Salle de réunion 2 Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area ................................................................ 24,6 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ........................................................ 5,3 kW Load occurs at ................................................. Jun 1600
Sensible coil load ................................................... 5,0 kW OA DB / WB ................................................... 32,0 / 27,0 °C
Coil L/s at Jun 1600 .............................................. 412 L/s Entering DB / WB ........................................... 22,7 / 16,2 °C
Max block L/s at Jun 1600 .................................... 455 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s ........................................... 455 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,943 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 4,7 Resulting RH .............................................................. 51 %
W/m² .................................................................. 213,9 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K

Preheat Coil Sizing Data


No heating coil loads occurred during this calculation.

Supply Fan Sizing Data

Actual max L/s at Jun 1600 ................................... 455 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ......................................................... 454 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 18,49 L/(s-m²) Fan static ...................................................................... 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s ..................................................... 0 L/s L/s/person ................................................................ 0,00 L/s/person
L/(s-m²) ................................................................. 0,00 L/(s-m²)

Hourly Analysis Program v4.90 Page 1 of 11


Zone Sizing Summary for A06-R3:Salle de réunion 2
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:07

Air System Information


Air System Name ............. A06-R3:Salle de réunion 2 Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area ................................................................ 24,6 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 5,1 455 5 Jun 1600 0,0 24,6 18,49

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
A06-R3-S.de réunion 2 1 5,1 Jun 1600 455 0,0 24,6 18,49

Hourly Analysis Program v4.90 Page 2 of 11


Ventilation Sizing Summary for A06-R3:Salle de réunion 2
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:07

1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 L/s

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (m²) Occupants (L/s) (L/s/person) (L/(s-m²)) (L/s) (% of supply) (L/s)
Zone 1
A06-R3-S.de réunion 2 1 24,6 5,0 454,7 0,00 0,00 0,0 0,0 0,0
Totals (incl. Space Multipliers) 454,7 0,0

Hourly Analysis Program v4.90 Page 3 of 11


Air System Design Load Summary for A06-R3:Salle de réunion 2
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:07

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 32,0 °C / 27,0 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 8 m² 1825 - 8 m² - -
Wall Transmission 7 m² 107 - 7 m² 0 -
Roof Transmission 25 m² 870 - 25 m² 0 -
Window Transmission 8 m² 112 - 8 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 15 m² 64 - 15 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 492 W 492 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1230 W 1230 - 0 0 -
People 5 359 301 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 5059 301 - 0 0
Zone Conditioning - 4960 301 - -42 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 412 L/s 0 - 5 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 412 L/s 0 - 5 L/s 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 4960 301 - -42 0
Central Cooling Coil - 4960 301 - -42 0
Preheat Coil - 0 - - 0 -
Terminal Reheat Coils - 0 - - 0 -
>> Total Conditioning - 4960 301 - -42 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 4 of 11


Zone Design Load Summary for A06-R3:Salle de réunion 2
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:07

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 32,0 °C / 27,0 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 8 m² 1825 - 8 m² - -
Wall Transmission 7 m² 107 - 7 m² 0 -
Roof Transmission 25 m² 870 - 25 m² 0 -
Window Transmission 8 m² 112 - 8 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 15 m² 64 - 15 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 492 W 492 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1230 W 1230 - 0 0 -
People 5 359 301 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 5059 301 - 0 0

Hourly Analysis Program v4.90 Page 5 of 11


Space Design Load Summary for A06-R3:Salle de réunion 2
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:07

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A06-R3-S.de réunion 2 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 32,0 °C / 27,0 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 8 m² 1825 - 8 m² - -
Wall Transmission 7 m² 107 - 7 m² 0 -
Roof Transmission 25 m² 870 - 25 m² 0 -
Window Transmission 8 m² 112 - 8 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 15 m² 64 - 15 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 492 W 492 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1230 W 1230 - 0 0 -
People 5 359 301 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 5059 301 - 0 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A06-R3-S.de réunion 2 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NW EXPOSURE
WALL 7 1,471 - 107 - 0
WINDOW 1 8 1,700 0,811 112 1825 0
H EXPOSURE
ROOF 25 1,137 - 870 - 0

Hourly Analysis Program v4.90 Page 6 of 11


Hourly Air System Design Day Loads for A06-R3:Salle de réunion 2
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:07

DESIGN MONTH: JULY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 23,4 293 3,4 3,7 0,0 0,0 0,0 0,0 0,0 0,0
0100 22,8 283 3,3 3,6 0,0 0,0 0,0 0,0 0,0 0,0
0200 22,2 274 3,2 3,5 0,0 0,0 0,0 0,0 0,0 0,0
0300 21,8 266 3,1 3,4 0,0 0,0 0,0 0,0 0,0 0,0
0400 21,4 258 3,0 3,3 0,0 0,0 0,0 0,0 0,0 0,0
0500 21,3 252 2,9 3,2 0,0 0,0 0,0 0,0 0,0 0,0
0600 21,5 247 2,9 3,2 0,0 0,0 0,0 0,0 0,0 0,0
0700 22,1 246 2,9 3,2 0,0 0,0 0,0 0,0 0,0 0,0
0800 23,2 248 2,9 3,2 0,0 0,0 0,0 0,0 0,0 0,0
0900 24,7 254 3,0 3,3 0,0 0,0 0,0 0,0 0,0 0,0
1000 26,4 264 3,1 3,4 0,0 0,0 0,0 0,0 0,0 0,0
1100 28,4 277 3,2 3,5 0,0 0,0 0,0 0,0 0,0 0,0
1200 30,2 302 3,6 3,9 0,0 0,0 0,0 0,0 0,0 0,0
1300 31,6 334 4,0 4,3 0,0 0,0 0,0 0,0 0,0 0,0
1400 32,6 366 4,4 4,7 0,0 0,0 0,0 0,0 0,0 0,0
1500 32,9 394 4,7 5,0 0,0 0,0 0,0 0,0 0,0 0,0
1600 32,6 410 4,9 5,2 0,0 0,0 0,0 0,0 0,0 0,0
1700 31,7 403 4,8 5,1 0,0 0,0 0,0 0,0 0,0 0,0
1800 30,5 365 4,4 4,7 0,0 0,0 0,0 0,0 0,0 0,0
1900 29,0 354 4,2 4,5 0,0 0,0 0,0 0,0 0,0 0,0
2000 27,4 341 4,0 4,3 0,0 0,0 0,0 0,0 0,0 0,0
2100 26,2 327 3,9 4,2 0,0 0,0 0,0 0,0 0,0 0,0
2200 25,0 315 3,7 4,0 0,0 0,0 0,0 0,0 0,0 0,0
2300 24,1 303 3,6 3,9 0,0 0,0 0,0 0,0 0,0 0,0

Hourly Analysis Program v4.90 Page 7 of 11


Hourly Zone Loads for A06-R3:Salle de réunion 2
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:07

ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 23,4 22,5 53 292,8 3457,8 3440,1 0,0 0,0 0,0
0100 22,8 22,5 53 283,1 3333,9 3319,6 0,0 0,0 0,0
0200 22,2 22,5 53 274,0 3219,2 3207,6 0,0 0,0 0,0
0300 21,8 22,5 53 265,8 3116,2 3106,6 0,0 0,0 0,0
0400 21,4 22,5 53 258,4 3023,4 3015,2 0,0 0,0 0,0
0500 21,3 22,4 53 251,6 2939,5 2932,3 0,0 0,0 0,0
0600 21,5 22,4 53 246,5 2877,6 2870,3 0,0 0,0 0,0
0700 22,1 22,4 53 246,2 2876,8 2866,7 0,0 0,0 0,0
0800 23,2 22,4 53 248,0 2901,8 2888,2 0,0 0,0 0,0
0900 24,7 22,4 53 253,6 2975,9 2956,8 0,0 0,0 0,0
1000 26,4 22,5 53 263,5 3105,3 3078,9 0,0 0,0 0,0
1100 28,4 22,5 53 277,2 3281,8 3246,7 0,0 0,0 0,0
1200 30,2 22,5 52 301,7 3599,9 3550,4 0,0 0,0 0,0
1300 31,6 22,6 52 333,8 4019,9 3953,0 0,0 0,0 0,0
1400 32,6 22,7 52 366,3 4448,6 4365,6 0,0 0,0 0,0
1500 32,9 22,7 51 393,5 4810,2 4715,7 0,0 0,0 0,0
1600 32,6 22,7 51 409,8 5024,8 4926,5 0,0 0,0 0,0
1700 31,7 22,7 51 402,6 4921,0 4833,8 0,0 0,0 0,0
1800 30,5 22,7 52 365,4 4414,0 4355,0 0,0 0,0 0,0
1900 29,0 22,6 52 353,8 4258,0 4207,2 0,0 0,0 0,0
2000 27,4 22,6 52 340,6 4080,6 4038,7 0,0 0,0 0,0
2100 26,2 22,6 52 327,4 3906,5 3872,5 0,0 0,0 0,0
2200 25,0 22,6 52 314,9 3742,8 3715,5 0,0 0,0 0,0
2300 24,1 22,5 52 303,4 3593,4 3571,4 0,0 0,0 0,0

Hourly Analysis Program v4.90 Page 8 of 11


System Psychrometrics for A06-R3:Salle de réunion 2
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:07

June DESIGN COOLING DAY, 1600

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 32,0 0,02059 0 400 0 0
Vent - Return Mixing Outlet 22,7 0,00882 412 2173 - -
Preheat Coil Outlet 22,7 0,00882 412 2173 0 -
Central Cooling Coil Outlet 12,8 0,00857 412 2173 4960 301
Supply Fan Outlet 12,8 0,00857 412 2173 0 -
Cold Supply Duct Outlet 12,8 0,00857 412 2173 - -
Zone Air - 22,7 0,00881 412 2173 4960 301
Return Plenum Outlet 22,7 0,00881 412 2173 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 5059 Cooling 4960 22,7 412 2173 0 0

Hourly Analysis Program v4.90 Page 9 of 11


System Psychrometrics for A06-R3:Salle de réunion 2
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:07

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 22,0 0,01667 0 400 0 0
Vent - Return Mixing Outlet 20,4 0,00866 5 800 - -
Preheat Coil Outlet 20,4 0,00866 5 800 0 -
Central Cooling Coil Outlet 12,8 0,00866 5 800 42 0
Supply Fan Outlet 12,8 0,00866 5 800 0 -
Cold Supply Duct Outlet 12,8 0,00866 5 800 - -
Zone Air - 20,4 0,00866 5 800 42 0
Return Plenum Outlet 20,4 0,00866 5 800 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 0 Heating 42 20,4 5 800 0 0

Hourly Analysis Program v4.90 Page 10 of 11


Psychrometric Analysis for A06-R3:Salle de réunion 2
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:07

Location: OUIDAH, BENIN


Altitude: 5,8 m.
Data for: June DESIGN COOLING DAY, 1600

1. Central Cooling Coil Outlet


2. Supply Fan Outlet
3. Room Air 0,024
0,022
0,020

Specific Humidity ( kg/kg )


0,018
0,016
0,014
0,012

12 3 0,010
0,008
0,006
0,004
0,002
0,000
0 5 10 15 20 25 30 35
Temperature ( °C )

Hourly Analysis Program v4.90 Page 11 of 11


Air System Sizing Summary for A06-R3:Salle de réunion 3
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:08

Air System Information


Air System Name ............. A06-R3:Salle de réunion 3 Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area ................................................................ 31,3 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ........................................................ 6,3 kW Load occurs at ................................................. Jun 1600
Sensible coil load ................................................... 5,9 kW OA DB / WB ................................................... 32,0 / 27,0 °C
Coil L/s at Jun 1600 .............................................. 490 L/s Entering DB / WB ........................................... 22,7 / 16,2 °C
Max block L/s at Jun 1600 .................................... 541 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s ........................................... 541 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,942 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 5,0 Resulting RH .............................................................. 51 %
W/m² .................................................................. 199,9 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K

Preheat Coil Sizing Data


No heating coil loads occurred during this calculation.

Supply Fan Sizing Data

Actual max L/s at Jun 1600 ................................... 541 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ......................................................... 541 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 17,28 L/(s-m²) Fan static ...................................................................... 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s ..................................................... 0 L/s L/s/person ................................................................ 0,00 L/s/person
L/(s-m²) ................................................................. 0,00 L/(s-m²)

Hourly Analysis Program v4.90 Page 1 of 11


Zone Sizing Summary for A06-R3:Salle de réunion 3
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:08

Air System Information


Air System Name ............. A06-R3:Salle de réunion 3 Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area ................................................................ 31,3 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 6,0 541 5 Jun 1600 0,0 31,3 17,28

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
A06-R3-S.de réunion 3 1 6,0 Jun 1600 541 0,0 31,3 17,28

Hourly Analysis Program v4.90 Page 2 of 11


Ventilation Sizing Summary for A06-R3:Salle de réunion 3
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:08

1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 L/s

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (m²) Occupants (L/s) (L/s/person) (L/(s-m²)) (L/s) (% of supply) (L/s)
Zone 1
A06-R3-S.de réunion 3 1 31,3 6,0 540,9 0,00 0,00 0,0 0,0 0,0
Totals (incl. Space Multipliers) 540,9 0,0

Hourly Analysis Program v4.90 Page 3 of 11


Air System Design Load Summary for A06-R3:Salle de réunion 3
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:08

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 32,0 °C / 27,0 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 8 m² 1825 - 8 m² - -
Wall Transmission 15 m² 290 - 15 m² 0 -
Roof Transmission 31 m² 1107 - 31 m² 0 -
Window Transmission 8 m² 112 - 8 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 15 m² 62 - 15 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 626 W 626 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1565 W 1565 - 0 0 -
People 6 431 361 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 6017 361 - 0 0
Zone Conditioning - 5895 361 - -50 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 490 L/s 0 - 5 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 490 L/s 0 - 5 L/s 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 5895 361 - -50 0
Central Cooling Coil - 5895 361 - -50 0
Preheat Coil - 0 - - 0 -
Terminal Reheat Coils - 0 - - 0 -
>> Total Conditioning - 5895 361 - -50 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 4 of 11


Zone Design Load Summary for A06-R3:Salle de réunion 3
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:08

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 32,0 °C / 27,0 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 8 m² 1825 - 8 m² - -
Wall Transmission 15 m² 290 - 15 m² 0 -
Roof Transmission 31 m² 1107 - 31 m² 0 -
Window Transmission 8 m² 112 - 8 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 15 m² 62 - 15 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 626 W 626 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1565 W 1565 - 0 0 -
People 6 431 361 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 6017 361 - 0 0

Hourly Analysis Program v4.90 Page 5 of 11


Space Design Load Summary for A06-R3:Salle de réunion 3
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:08

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A06-R3-S.de réunion 3 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 32,0 °C / 27,0 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 8 m² 1825 - 8 m² - -
Wall Transmission 15 m² 290 - 15 m² 0 -
Roof Transmission 31 m² 1107 - 31 m² 0 -
Window Transmission 8 m² 112 - 8 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 15 m² 62 - 15 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 626 W 626 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1565 W 1565 - 0 0 -
People 6 431 361 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 6017 361 - 0 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A06-R3-S.de réunion 3 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NW EXPOSURE
WALL 7 1,471 - 107 - 0
WINDOW 1 8 1,700 0,811 112 1825 0
NE EXPOSURE
WALL 9 1,471 - 183 - 0
H EXPOSURE
ROOF 31 1,137 - 1107 - 0

Hourly Analysis Program v4.90 Page 6 of 11


Hourly Air System Design Day Loads for A06-R3:Salle de réunion 3
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:08

DESIGN MONTH: JULY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 23,4 362 4,3 4,6 0,0 0,0 0,0 0,0 0,0 0,0
0100 22,8 351 4,1 4,5 0,0 0,0 0,0 0,0 0,0 0,0
0200 22,2 340 4,0 4,4 0,0 0,0 0,0 0,0 0,0 0,0
0300 21,8 331 3,9 4,2 0,0 0,0 0,0 0,0 0,0 0,0
0400 21,4 322 3,8 4,1 0,0 0,0 0,0 0,0 0,0 0,0
0500 21,3 314 3,7 4,0 0,0 0,0 0,0 0,0 0,0 0,0
0600 21,5 307 3,6 3,9 0,0 0,0 0,0 0,0 0,0 0,0
0700 22,1 306 3,6 3,9 0,0 0,0 0,0 0,0 0,0 0,0
0800 23,2 307 3,6 3,9 0,0 0,0 0,0 0,0 0,0 0,0
0900 24,7 313 3,7 4,0 0,0 0,0 0,0 0,0 0,0 0,0
1000 26,4 324 3,8 4,2 0,0 0,0 0,0 0,0 0,0 0,0
1100 28,4 340 4,0 4,4 0,0 0,0 0,0 0,0 0,0 0,0
1200 30,2 368 4,3 4,7 0,0 0,0 0,0 0,0 0,0 0,0
1300 31,6 404 4,8 5,2 0,0 0,0 0,0 0,0 0,0 0,0
1400 32,6 440 5,2 5,6 0,0 0,0 0,0 0,0 0,0 0,0
1500 32,9 470 5,6 6,0 0,0 0,0 0,0 0,0 0,0 0,0
1600 32,6 488 5,9 6,2 0,0 0,0 0,0 0,0 0,0 0,0
1700 31,7 482 5,8 6,1 0,0 0,0 0,0 0,0 0,0 0,0
1800 30,5 445 5,3 5,7 0,0 0,0 0,0 0,0 0,0 0,0
1900 29,0 432 5,1 5,5 0,0 0,0 0,0 0,0 0,0 0,0
2000 27,4 417 5,0 5,3 0,0 0,0 0,0 0,0 0,0 0,0
2100 26,2 402 4,8 5,1 0,0 0,0 0,0 0,0 0,0 0,0
2200 25,0 388 4,6 4,9 0,0 0,0 0,0 0,0 0,0 0,0
2300 24,1 374 4,4 4,8 0,0 0,0 0,0 0,0 0,0 0,0

Hourly Analysis Program v4.90 Page 7 of 11


Hourly Zone Loads for A06-R3:Salle de réunion 3
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:08

ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 23,4 22,5 52 362,2 4291,3 4264,6 0,0 0,0 0,0
0100 22,8 22,5 53 350,8 4145,7 4123,4 0,0 0,0 0,0
0200 22,2 22,5 53 340,2 4010,4 3991,8 0,0 0,0 0,0
0300 21,8 22,5 53 330,5 3888,0 3872,1 0,0 0,0 0,0
0400 21,4 22,5 53 321,7 3776,7 3762,8 0,0 0,0 0,0
0500 21,3 22,5 53 313,5 3675,5 3662,9 0,0 0,0 0,0
0600 21,5 22,5 53 307,2 3597,1 3584,9 0,0 0,0 0,0
0700 22,1 22,4 53 305,7 3581,4 3566,4 0,0 0,0 0,0
0800 23,2 22,5 53 306,7 3597,4 3578,5 0,0 0,0 0,0
0900 24,7 22,5 53 312,6 3676,3 3650,9 0,0 0,0 0,0
1000 26,4 22,5 53 324,1 3827,7 3793,1 0,0 0,0 0,0
1100 28,4 22,5 53 340,5 4040,9 3994,9 0,0 0,0 0,0
1200 30,2 22,5 52 368,3 4404,9 4341,3 0,0 0,0 0,0
1300 31,6 22,6 52 403,9 4874,0 4789,5 0,0 0,0 0,0
1400 32,6 22,7 52 439,8 5348,7 5245,2 0,0 0,0 0,0
1500 32,9 22,7 51 469,8 5748,3 5631,2 0,0 0,0 0,0
1600 32,6 22,7 51 488,0 5989,1 5867,4 0,0 0,0 0,0
1700 31,7 22,7 51 481,9 5897,7 5787,9 0,0 0,0 0,0
1800 30,5 22,7 52 444,8 5388,1 5309,2 0,0 0,0 0,0
1900 29,0 22,7 52 432,1 5215,8 5147,0 0,0 0,0 0,0
2000 27,4 22,6 52 417,1 5013,8 4956,3 0,0 0,0 0,0
2100 26,2 22,6 52 402,1 4813,3 4765,7 0,0 0,0 0,0
2200 25,0 22,6 52 387,7 4623,9 4584,8 0,0 0,0 0,0
2300 24,1 22,6 52 374,4 4450,0 4417,8 0,0 0,0 0,0

Hourly Analysis Program v4.90 Page 8 of 11


System Psychrometrics for A06-R3:Salle de réunion 3
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:08

June DESIGN COOLING DAY, 1600

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 32,0 0,02059 0 400 0 0
Vent - Return Mixing Outlet 22,7 0,00882 490 2186 - -
Preheat Coil Outlet 22,7 0,00882 490 2186 0 -
Central Cooling Coil Outlet 12,8 0,00857 490 2186 5895 361
Supply Fan Outlet 12,8 0,00857 490 2186 0 -
Cold Supply Duct Outlet 12,8 0,00857 490 2186 - -
Zone Air - 22,7 0,00882 490 2186 5895 361
Return Plenum Outlet 22,7 0,00882 490 2186 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 6017 Cooling 5895 22,7 490 2186 0 0

Hourly Analysis Program v4.90 Page 9 of 11


System Psychrometrics for A06-R3:Salle de réunion 3
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:08

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 22,0 0,01667 0 400 0 0
Vent - Return Mixing Outlet 20,5 0,00866 5 800 - -
Preheat Coil Outlet 20,5 0,00866 5 800 0 -
Central Cooling Coil Outlet 12,8 0,00866 5 800 50 0
Supply Fan Outlet 12,8 0,00866 5 800 0 -
Cold Supply Duct Outlet 12,8 0,00866 5 800 - -
Zone Air - 20,5 0,00866 5 800 50 0
Return Plenum Outlet 20,5 0,00866 5 800 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 0 Heating 50 20,5 5 800 0 0

Hourly Analysis Program v4.90 Page 10 of 11


Psychrometric Analysis for A06-R3:Salle de réunion 3
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:08

Location: OUIDAH, BENIN


Altitude: 5,8 m.
Data for: June DESIGN COOLING DAY, 1600

1. Central Cooling Coil Outlet


2. Supply Fan Outlet
3. Room Air 0,024
0,022
0,020

Specific Humidity ( kg/kg )


0,018
0,016
0,014
0,012

12 3 0,010
0,008
0,006
0,004
0,002
0,000
0 5 10 15 20 25 30 35
Temperature ( °C )

Hourly Analysis Program v4.90 Page 11 of 11


Air System Sizing Summary for A06-R3-Salle de réunion 4
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:10

Air System Information


Air System Name ............. A06-R3-Salle de réunion 4 Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area ................................................................ 24,6 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ........................................................ 5,4 kW Load occurs at ................................................. Dec 1600
Sensible coil load ................................................... 5,1 kW OA DB / WB ................................................... 27,6 / 24,2 °C
Coil L/s at Dec 1600 ............................................. 423 L/s Entering DB / WB ........................................... 22,7 / 16,2 °C
Max block L/s at Dec 1600 .................................... 466 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s ........................................... 466 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,944 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 4,6 Resulting RH .............................................................. 51 %
W/m² .................................................................. 219,0 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K

Preheat Coil Sizing Data


No heating coil loads occurred during this calculation.

Supply Fan Sizing Data

Actual max L/s at Dec 1600 .................................. 466 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ......................................................... 466 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 18,96 L/(s-m²) Fan static ...................................................................... 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s ..................................................... 0 L/s L/s/person ................................................................ 0,00 L/s/person
L/(s-m²) ................................................................. 0,00 L/(s-m²)

Hourly Analysis Program v4.90 Page 1 of 11


Zone Sizing Summary for A06-R3-Salle de réunion 4
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:10

Air System Information


Air System Name ............. A06-R3-Salle de réunion 4 Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area ................................................................ 24,6 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 5,2 466 5 Dec 1600 0,0 24,6 18,96

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
A06-R3-S.de réunion 4 1 5,2 Dec 1600 466 0,0 24,6 18,96

Hourly Analysis Program v4.90 Page 2 of 11


Ventilation Sizing Summary for A06-R3-Salle de réunion 4
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:10

1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 L/s

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (m²) Occupants (L/s) (L/s/person) (L/(s-m²)) (L/s) (% of supply) (L/s)
Zone 1
A06-R3-S.de réunion 4 1 24,6 5,0 466,5 0,00 0,00 0,0 0,0 0,0
Totals (incl. Space Multipliers) 466,5 0,0

Hourly Analysis Program v4.90 Page 3 of 11


Air System Design Load Summary for A06-R3-Salle de réunion 4
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:10

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Dec 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 27,6 °C / 24,2 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 8 m² 2223 - 8 m² - -
Wall Transmission 7 m² 77 - 7 m² 0 -
Roof Transmission 25 m² 732 - 25 m² 0 -
Window Transmission 8 m² 51 - 8 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 15 m² 26 - 15 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 492 W 492 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1230 W 1230 - 0 0 -
People 5 359 301 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 5190 301 - 0 0
Zone Conditioning - 5086 301 - -43 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 423 L/s 0 - 5 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 423 L/s 0 - 5 L/s 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 5086 301 - -43 0
Central Cooling Coil - 5086 302 - -43 0
Preheat Coil - 0 - - 0 -
Terminal Reheat Coils - 0 - - 0 -
>> Total Conditioning - 5086 302 - -43 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 4 of 11


Zone Design Load Summary for A06-R3-Salle de réunion 4
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:10

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Dec 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 27,6 °C / 24,2 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 8 m² 2223 - 8 m² - -
Wall Transmission 7 m² 77 - 7 m² 0 -
Roof Transmission 25 m² 732 - 25 m² 0 -
Window Transmission 8 m² 51 - 8 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 15 m² 26 - 15 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 492 W 492 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1230 W 1230 - 0 0 -
People 5 359 301 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 5190 301 - 0 0

Hourly Analysis Program v4.90 Page 5 of 11


Space Design Load Summary for A06-R3-Salle de réunion 4
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:10

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A06-R3-S.de réunion 4 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 27,6 °C / 24,2 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 8 m² 2223 - 8 m² - -
Wall Transmission 7 m² 77 - 7 m² 0 -
Roof Transmission 25 m² 732 - 25 m² 0 -
Window Transmission 8 m² 51 - 8 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 15 m² 26 - 15 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 492 W 492 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1230 W 1230 - 0 0 -
People 5 359 301 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 5190 301 - 0 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A06-R3-S.de réunion 4 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 7 1,471 - 77 - 0
WINDOW 1 8 1,700 0,811 51 2223 0
H EXPOSURE
ROOF 25 1,137 - 732 - 0

Hourly Analysis Program v4.90 Page 6 of 11


Hourly Air System Design Day Loads for A06-R3-Salle de réunion 4
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:10

DESIGN MONTH: JULY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 23,4 257 3,0 3,3 0,0 0,0 0,0 0,0 0,0 0,0
0100 22,8 249 2,9 3,2 0,0 0,0 0,0 0,0 0,0 0,0
0200 22,2 242 2,8 3,1 0,0 0,0 0,0 0,0 0,0 0,0
0300 21,8 236 2,7 3,0 0,0 0,0 0,0 0,0 0,0 0,0
0400 21,4 230 2,7 3,0 0,0 0,0 0,0 0,0 0,0 0,0
0500 21,3 225 2,6 2,9 0,0 0,0 0,0 0,0 0,0 0,0
0600 21,5 221 2,6 2,9 0,0 0,0 0,0 0,0 0,0 0,0
0700 22,1 223 2,6 2,9 0,0 0,0 0,0 0,0 0,0 0,0
0800 23,2 226 2,6 2,9 0,0 0,0 0,0 0,0 0,0 0,0
0900 24,7 233 2,7 3,0 0,0 0,0 0,0 0,0 0,0 0,0
1000 26,4 244 2,8 3,1 0,0 0,0 0,0 0,0 0,0 0,0
1100 28,4 258 3,0 3,3 0,0 0,0 0,0 0,0 0,0 0,0
1200 30,2 273 3,2 3,5 0,0 0,0 0,0 0,0 0,0 0,0
1300 31,6 288 3,4 3,7 0,0 0,0 0,0 0,0 0,0 0,0
1400 32,6 308 3,6 3,9 0,0 0,0 0,0 0,0 0,0 0,0
1500 32,9 327 3,9 4,2 0,0 0,0 0,0 0,0 0,0 0,0
1600 32,6 339 4,0 4,3 0,0 0,0 0,0 0,0 0,0 0,0
1700 31,7 336 4,0 4,3 0,0 0,0 0,0 0,0 0,0 0,0
1800 30,5 316 3,7 4,0 0,0 0,0 0,0 0,0 0,0 0,0
1900 29,0 307 3,6 3,9 0,0 0,0 0,0 0,0 0,0 0,0
2000 27,4 296 3,5 3,8 0,0 0,0 0,0 0,0 0,0 0,0
2100 26,2 285 3,3 3,6 0,0 0,0 0,0 0,0 0,0 0,0
2200 25,0 274 3,2 3,5 0,0 0,0 0,0 0,0 0,0 0,0
2300 24,1 265 3,1 3,4 0,0 0,0 0,0 0,0 0,0 0,0

Hourly Analysis Program v4.90 Page 7 of 11


Hourly Zone Loads for A06-R3-Salle de réunion 4
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:10

ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 23,4 22,4 53 256,6 3006,7 2990,1 0,0 0,0 0,0
0100 22,8 22,4 53 248,9 2910,5 2896,5 0,0 0,0 0,0
0200 22,2 22,4 53 241,8 2822,2 2810,2 0,0 0,0 0,0
0300 21,8 22,4 54 235,5 2744,2 2733,7 0,0 0,0 0,0
0400 21,4 22,4 54 229,9 2675,0 2665,4 0,0 0,0 0,0
0500 21,3 22,4 54 224,9 2613,5 2604,5 0,0 0,0 0,0
0600 21,5 22,4 54 221,4 2572,5 2563,2 0,0 0,0 0,0
0700 22,1 22,4 54 222,8 2591,4 2579,1 0,0 0,0 0,0
0800 23,2 22,4 54 226,1 2634,9 2619,0 0,0 0,0 0,0
0900 24,7 22,4 54 233,2 2726,3 2705,1 0,0 0,0 0,0
1000 26,4 22,4 53 244,0 2864,9 2836,8 0,0 0,0 0,0
1100 28,4 22,4 53 257,7 3039,1 3003,2 0,0 0,0 0,0
1200 30,2 22,5 53 272,8 3232,7 3189,0 0,0 0,0 0,0
1300 31,6 22,5 53 287,8 3424,4 3373,7 0,0 0,0 0,0
1400 32,6 22,5 52 307,6 3679,3 3619,4 0,0 0,0 0,0
1500 32,9 22,6 52 327,1 3930,8 3862,7 0,0 0,0 0,0
1600 32,6 22,6 52 339,0 4083,4 4012,4 0,0 0,0 0,0
1700 31,7 22,6 52 335,9 4037,8 3972,9 0,0 0,0 0,0
1800 30,5 22,5 52 316,3 3776,8 3726,9 0,0 0,0 0,0
1900 29,0 22,5 52 307,0 3654,2 3611,0 0,0 0,0 0,0
2000 27,4 22,5 53 295,8 3508,6 3472,7 0,0 0,0 0,0
2100 26,2 22,5 53 284,8 3365,8 3336,3 0,0 0,0 0,0
2200 25,0 22,5 53 274,5 3232,8 3208,8 0,0 0,0 0,0
2300 24,1 22,5 53 265,1 3113,3 3093,5 0,0 0,0 0,0

Hourly Analysis Program v4.90 Page 8 of 11


System Psychrometrics for A06-R3-Salle de réunion 4
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:10

December DESIGN COOLING DAY, 1600

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 27,6 0,01774 0 400 0 0
Vent - Return Mixing Outlet 22,7 0,00881 423 2139 - -
Preheat Coil Outlet 22,7 0,00881 423 2139 0 -
Central Cooling Coil Outlet 12,8 0,00857 423 2139 5086 302
Supply Fan Outlet 12,8 0,00857 423 2139 0 -
Cold Supply Duct Outlet 12,8 0,00857 423 2139 - -
Zone Air - 22,7 0,00881 423 2139 5086 301
Return Plenum Outlet 22,7 0,00881 423 2139 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 5190 Cooling 5086 22,7 423 2139 0 0

Hourly Analysis Program v4.90 Page 9 of 11


System Psychrometrics for A06-R3-Salle de réunion 4
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:10

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 22,0 0,01667 0 400 0 0
Vent - Return Mixing Outlet 20,4 0,00866 5 800 - -
Preheat Coil Outlet 20,4 0,00866 5 800 0 -
Central Cooling Coil Outlet 12,8 0,00866 5 800 43 0
Supply Fan Outlet 12,8 0,00866 5 800 0 -
Cold Supply Duct Outlet 12,8 0,00866 5 800 - -
Zone Air - 20,4 0,00866 5 800 43 0
Return Plenum Outlet 20,4 0,00866 5 800 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 0 Heating 43 20,4 5 800 0 0

Hourly Analysis Program v4.90 Page 10 of 11


Psychrometric Analysis for A06-R3-Salle de réunion 4
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:10

Location: OUIDAH, BENIN


Altitude: 5,8 m.
Data for: December DESIGN COOLING DAY, 1600
0,020
1. Central Cooling Coil Outlet
2. Supply Fan Outlet
3. Room Air
0,018

0,016

Specific Humidity ( kg/kg )


0,014

0,012

0,010
12 3

0,008

0,006

0,004

0,002

0,000
0 5 10 15 20 25 30 35
Temperature ( °C )

Hourly Analysis Program v4.90 Page 11 of 11


Air System Sizing Summary for A06-R3-Salle de réunion 5
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:11

Air System Information


Air System Name ............. A06-R3-Salle de réunion 5 Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area ................................................................ 45,0 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ........................................................ 7,6 kW Load occurs at ................................................. Nov 1600
Sensible coil load ................................................... 7,3 kW OA DB / WB ................................................... 28,7 / 25,3 °C
Coil L/s at Nov 1600 ............................................. 606 L/s Entering DB / WB ........................................... 22,7 / 16,1 °C
Max block L/s at Nov 1600 .................................... 672 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s ........................................... 672 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,959 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 5,9 Resulting RH .............................................................. 51 %
W/m² .................................................................. 168,9 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K

Preheat Coil Sizing Data


No heating coil loads occurred during this calculation.

Supply Fan Sizing Data

Actual max L/s at Nov 1600 .................................. 672 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ......................................................... 671 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 14,92 L/(s-m²) Fan static ...................................................................... 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s ..................................................... 0 L/s L/s/person ................................................................ 0,00 L/s/person
L/(s-m²) ................................................................. 0,00 L/(s-m²)

Hourly Analysis Program v4.90 Page 1 of 11


Zone Sizing Summary for A06-R3-Salle de réunion 5
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:11

Air System Information


Air System Name ............. A06-R3-Salle de réunion 5 Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area ................................................................ 45,0 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 7,5 672 7 Nov 1600 0,0 45,0 14,92

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
A06-R3-S.de réunion 5 1 7,5 Nov 1600 672 0,0 45,0 14,92

Hourly Analysis Program v4.90 Page 2 of 11


Ventilation Sizing Summary for A06-R3-Salle de réunion 5
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:11

1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 L/s

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (m²) Occupants (L/s) (L/s/person) (L/(s-m²)) (L/s) (% of supply) (L/s)
Zone 1
A06-R3-S.de réunion 5 1 45,0 5,0 671,5 0,00 0,00 0,0 0,0 0,0
Totals (incl. Space Multipliers) 671,5 0,0

Hourly Analysis Program v4.90 Page 3 of 11


Air System Design Load Summary for A06-R3-Salle de réunion 5
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:11

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Nov 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 28,7 °C / 25,3 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 8 m² 2106 - 8 m² - -
Wall Transmission 16 m² 252 - 16 m² 0 -
Roof Transmission 45 m² 1444 - 45 m² 0 -
Window Transmission 8 m² 67 - 8 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 40 m² 94 - 40 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 900 W 900 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2250 W 2250 - 0 0 -
People 5 359 301 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 7471 301 - 0 0
Zone Conditioning - 7291 301 - -63 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 606 L/s 0 - 7 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 606 L/s 0 - 7 L/s 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 7291 301 - -63 0
Central Cooling Coil - 7291 309 - -63 0
Preheat Coil - 0 - - 0 -
Terminal Reheat Coils - 0 - - 0 -
>> Total Conditioning - 7291 309 - -63 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 4 of 11


Zone Design Load Summary for A06-R3-Salle de réunion 5
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:11

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Nov 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 28,7 °C / 25,3 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 8 m² 2106 - 8 m² - -
Wall Transmission 16 m² 252 - 16 m² 0 -
Roof Transmission 45 m² 1444 - 45 m² 0 -
Window Transmission 8 m² 67 - 8 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 40 m² 94 - 40 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 900 W 900 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2250 W 2250 - 0 0 -
People 5 359 301 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 7471 301 - 0 0

Hourly Analysis Program v4.90 Page 5 of 11


Space Design Load Summary for A06-R3-Salle de réunion 5
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:11

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A06-R3-S.de réunion 5 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Nov 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 28,7 °C / 25,3 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 8 m² 2106 - 8 m² - -
Wall Transmission 16 m² 252 - 16 m² 0 -
Roof Transmission 45 m² 1444 - 45 m² 0 -
Window Transmission 8 m² 67 - 8 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 40 m² 94 - 40 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 900 W 900 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2250 W 2250 - 0 0 -
People 5 359 301 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 7471 301 - 0 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A06-R3-S.de réunion 5 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 7 1,471 - 85 - 0
WINDOW 1 8 1,700 0,811 67 2106 0
SE EXPOSURE
WALL 9 1,471 - 168 - 0
H EXPOSURE
ROOF 45 1,137 - 1444 - 0

Hourly Analysis Program v4.90 Page 6 of 11


Hourly Air System Design Day Loads for A06-R3-Salle de réunion 5
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:11

DESIGN MONTH: JULY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 23,4 416 4,9 5,2 0,0 0,0 0,0 0,0 0,0 0,0
0100 22,8 404 4,7 5,0 0,0 0,0 0,0 0,0 0,0 0,0
0200 22,2 392 4,6 4,9 0,0 0,0 0,0 0,0 0,0 0,0
0300 21,8 382 4,5 4,8 0,0 0,0 0,0 0,0 0,0 0,0
0400 21,4 374 4,4 4,6 0,0 0,0 0,0 0,0 0,0 0,0
0500 21,3 366 4,3 4,6 0,0 0,0 0,0 0,0 0,0 0,0
0600 21,5 360 4,2 4,5 0,0 0,0 0,0 0,0 0,0 0,0
0700 22,1 359 4,2 4,5 0,0 0,0 0,0 0,0 0,0 0,0
0800 23,2 362 4,2 4,5 0,0 0,0 0,0 0,0 0,0 0,0
0900 24,7 372 4,3 4,6 0,0 0,0 0,0 0,0 0,0 0,0
1000 26,4 389 4,5 4,8 0,0 0,0 0,0 0,0 0,0 0,0
1100 28,4 411 4,8 5,1 0,0 0,0 0,0 0,0 0,0 0,0
1200 30,2 436 5,1 5,4 0,0 0,0 0,0 0,0 0,0 0,0
1300 31,6 461 5,4 5,7 0,0 0,0 0,0 0,0 0,0 0,0
1400 32,6 490 5,8 6,1 0,0 0,0 0,0 0,0 0,0 0,0
1500 32,9 516 6,1 6,4 0,0 0,0 0,0 0,0 0,0 0,0
1600 32,6 533 6,3 6,7 0,0 0,0 0,0 0,0 0,0 0,0
1700 31,7 531 6,3 6,6 0,0 0,0 0,0 0,0 0,0 0,0
1800 30,5 510 6,1 6,4 0,0 0,0 0,0 0,0 0,0 0,0
1900 29,0 496 5,9 6,2 0,0 0,0 0,0 0,0 0,0 0,0
2000 27,4 478 5,7 6,0 0,0 0,0 0,0 0,0 0,0 0,0
2100 26,2 461 5,4 5,7 0,0 0,0 0,0 0,0 0,0 0,0
2200 25,0 444 5,2 5,5 0,0 0,0 0,0 0,0 0,0 0,0
2300 24,1 429 5,0 5,3 0,0 0,0 0,0 0,0 0,0 0,0

Hourly Analysis Program v4.90 Page 7 of 11


Hourly Zone Loads for A06-R3-Salle de réunion 5
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:11

ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 23,4 22,5 52 415,7 4913,0 4873,4 0,0 0,0 0,0
0100 22,8 22,5 52 403,5 4757,3 4723,1 0,0 0,0 0,0
0200 22,2 22,5 52 392,3 4614,6 4584,8 0,0 0,0 0,0
0300 21,8 22,5 52 382,4 4490,6 4463,9 0,0 0,0 0,0
0400 21,4 22,4 52 373,7 4381,8 4357,1 0,0 0,0 0,0
0500 21,3 22,4 52 365,8 4284,2 4260,8 0,0 0,0 0,0
0600 21,5 22,4 53 359,8 4210,6 4187,1 0,0 0,0 0,0
0700 22,1 22,4 53 358,9 4202,8 4175,7 0,0 0,0 0,0
0800 23,2 22,4 53 361,9 4246,2 4213,0 0,0 0,0 0,0
0900 24,7 22,4 52 371,9 4378,2 4334,6 0,0 0,0 0,0
1000 26,4 22,5 52 388,8 4600,0 4542,1 0,0 0,0 0,0
1100 28,4 22,5 52 411,2 4892,1 4817,3 0,0 0,0 0,0
1200 30,2 22,5 52 436,4 5221,6 5129,6 0,0 0,0 0,0
1300 31,6 22,6 52 461,4 5549,4 5441,9 0,0 0,0 0,0
1400 32,6 22,6 51 490,1 5926,8 5802,4 0,0 0,0 0,0
1500 32,9 22,6 51 516,5 6274,3 6136,1 0,0 0,0 0,0
1600 32,6 22,6 51 532,7 6485,4 6342,5 0,0 0,0 0,0
1700 31,7 22,6 51 531,1 6455,9 6322,2 0,0 0,0 0,0
1800 30,5 22,6 51 510,0 6164,7 6053,8 0,0 0,0 0,0
1900 29,0 22,6 51 495,8 5971,4 5874,7 0,0 0,0 0,0
2000 27,4 22,6 52 478,2 5733,7 5652,6 0,0 0,0 0,0
2100 26,2 22,6 52 460,6 5499,2 5431,8 0,0 0,0 0,0
2200 25,0 22,5 52 444,1 5281,5 5225,5 0,0 0,0 0,0
2300 24,1 22,5 52 429,1 5086,4 5039,6 0,0 0,0 0,0

Hourly Analysis Program v4.90 Page 8 of 11


System Psychrometrics for A06-R3-Salle de réunion 5
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:11

November DESIGN COOLING DAY, 1600

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 28,7 0,01910 0 400 0 0
Vent - Return Mixing Outlet 22,7 0,00873 606 1734 - -
Preheat Coil Outlet 22,7 0,00873 606 1734 0 -
Central Cooling Coil Outlet 12,8 0,00856 606 1734 7291 309
Supply Fan Outlet 12,8 0,00856 606 1734 0 -
Cold Supply Duct Outlet 12,8 0,00856 606 1734 - -
Zone Air - 22,7 0,00873 606 1734 7291 301
Return Plenum Outlet 22,7 0,00873 606 1734 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 7471 Cooling 7291 22,7 606 1734 0 0

Hourly Analysis Program v4.90 Page 9 of 11


System Psychrometrics for A06-R3-Salle de réunion 5
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:11

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 22,0 0,01667 0 400 0 0
Vent - Return Mixing Outlet 20,6 0,00866 7 800 - -
Preheat Coil Outlet 20,6 0,00866 7 800 0 -
Central Cooling Coil Outlet 12,8 0,00866 7 800 63 0
Supply Fan Outlet 12,8 0,00866 7 800 0 -
Cold Supply Duct Outlet 12,8 0,00866 7 800 - -
Zone Air - 20,6 0,00866 7 800 63 0
Return Plenum Outlet 20,6 0,00866 7 800 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 0 Heating 63 20,6 7 800 0 0

Hourly Analysis Program v4.90 Page 10 of 11


Psychrometric Analysis for A06-R3-Salle de réunion 5
Project Name: A06 01/05/2024
Prepared by: ATOMAS 06:11

Location: OUIDAH, BENIN


Altitude: 5,8 m.
Data for: November DESIGN COOLING DAY, 1600
0,020
1. Central Cooling Coil Outlet
2. Supply Fan Outlet
3. Room Air
0,018

0,016

Specific Humidity ( kg/kg )


0,014

0,012

0,010
12 3

0,008

0,006

0,004

0,002

0,000
0 5 10 15 20 25 30 35
Temperature ( °C )

Hourly Analysis Program v4.90 Page 11 of 11


Air System Sizing Summary for A06-R1-Batiment centrale R+1
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:36

Air System Information


Air System Name ............................. A06-R1-Niveau 1 Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area .............................................................. 263,6 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ....................................................... 43,0 kW Load occurs at ................................................. Sep 1600
Sensible coil load .................................................. 40,1 kW OA DB / WB ................................................... 31,4 / 26,5 °C
Coil L/s at Sep 1600 ............................................ 3334 L/s Entering DB / WB ........................................... 22,7 / 16,3 °C
Max block L/s at Sep 1600 ................................... 3671 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s .......................................... 3671 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,934 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 6,1 Resulting RH .............................................................. 51 %
W/m² .................................................................. 162,9 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K

Preheat Coil Sizing Data


No heating coil loads occurred during this calculation.

Supply Fan Sizing Data

Actual max L/s at Sep 1600 ................................. 3671 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ........................................................ 3669 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 13,93 L/(s-m²) Fan static ...................................................................... 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s ..................................................... 0 L/s L/s/person ................................................................ 0,00 L/s/person
L/(s-m²) ................................................................. 0,00 L/(s-m²)

Hourly Analysis Program v4.90 Page 1 of 16


Zone Sizing Summary for A06-R1-Salle de réunion 1
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:36

Air System Information


Air System Name ............. A06-R1-Salle de réunion 1 Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area .............................................................. 263,6 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 40,8 3671 37 Sep 1600 0,0 263,6 13,93

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
A06-R1-S.de réunion 1 3 5,9 Sep 1600 527 0,0 31,8 16,59
A06-R1-Espace lounge 1 6,5 Sep 0900 583 0,0 42,7 13,64
A06-R1-S.de réunion 2 1 4,2 Jun 1600 377 0,0 24,6 15,31
A06-R1-S.de réunion 3 1 4,9 Jun 1600 441 0,0 31,3 14,10
A06-R1-S.de reunion 4 1 4,5 Dec 1600 401 0,0 24,6 16,29
A06-R1-S.de réunion 5 1 6,1 Dec 1600 547 0,0 45,0 12,16

Hourly Analysis Program v4.90 Page 2 of 16


Ventilation Sizing Summary for A06-R1-Salle de réunion 1
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:36

1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 L/s

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (m²) Occupants (L/s) (L/s/person) (L/(s-m²)) (L/s) (% of supply) (L/s)
Zone 1
A06-R1-S.de réunion 1 3 31,8 6,0 527,4 0,00 0,00 0,0 0,0 0,0
A06-R1-Espace lounge 1 42,7 12,0 582,5 0,00 0,00 0,0 0,0 0,0
A06-R1-S.de réunion 2 1 24,6 5,0 376,5 0,00 0,00 0,0 0,0 0,0
A06-R1-S.de réunion 3 1 31,3 6,0 441,3 0,00 0,00 0,0 0,0 0,0
A06-R1-S.de reunion 4 1 24,6 5,0 400,7 0,00 0,00 0,0 0,0 0,0
A06-R1-S.de réunion 5 1 45,0 5,0 547,0 0,00 0,00 0,0 0,0 0,0
Totals (incl. Space Multipliers) 3930,3 0,0

Hourly Analysis Program v4.90 Page 3 of 16


Air System Design Load Summary for A06-R1-Salle de réunion 1
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:36

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Sep 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 31,4 °C / 26,5 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 95 m² 15572 - 95 m² - -
Wall Transmission 103 m² 1419 - 103 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 95 m² 1230 - 95 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 143 m² 560 - 143 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 5272 W 5272 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 13180 W 13179 - 0 0 -
People 51 3609 2766 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 40842 2766 - 0 0
Zone Conditioning - 40110 2766 - -344 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 3334 L/s 0 - 37 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 3334 L/s 0 - 37 L/s 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 40110 2766 - -344 0
Central Cooling Coil - 40110 2841 - -344 0
Preheat Coil - 0 - - 0 -
Terminal Reheat Coils - 0 - - 0 -
>> Total Conditioning - 40110 2841 - -344 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 4 of 16


Zone Design Load Summary for A06-R1-Salle de réunion 1
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:36

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Sep 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 31,4 °C / 26,5 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 95 m² 15572 - 95 m² - -
Wall Transmission 103 m² 1419 - 103 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 95 m² 1230 - 95 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 143 m² 560 - 143 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 5272 W 5272 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 13180 W 13179 - 0 0 -
People 51 3609 2766 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 40842 2766 - 0 0

Hourly Analysis Program v4.90 Page 5 of 16


Space Design Load Summary for A06-R1-Salle de réunion 1
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:36

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A06-R1-S.de réunion 1 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Sep 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 31,4 °C / 26,5 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 16 m² 2806 - 16 m² - -
Wall Transmission 14 m² 166 - 14 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 16 m² 210 - 16 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 8 m² 29 - 8 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 636 W 636 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1590 W 1590 - 0 0 -
People 6 431 361 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 5868 361 - 0 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A06-R1-S.de réunion 1 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NW EXPOSURE
WALL 7 1,471 - 78 - 0
WINDOW 1 8 1,700 0,811 105 1285 0
SW EXPOSURE
WALL 7 1,471 - 88 - 0
WINDOW 1 8 1,700 0,811 105 1521 0

Hourly Analysis Program v4.90 Page 6 of 16


Space Design Load Summary for A06-R1-Salle de réunion 1
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:36

TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' A06-R1-Espace lounge '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Sep 0900 HEATING DATA AT DES HTG
COOLING OA DB / WB 23,6 °C / 23,3 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 14 m² 2441 - 14 m² - -
Wall Transmission 17 m² 200 - 17 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 14 m² 39 - 14 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 36 m² 3 - 36 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 854 W 854 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2135 W 2135 - 0 0 -
People 12 809 422 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 6481 422 - 0 0

TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' A06-R1-Espace lounge '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SE EXPOSURE
WALL 6 1,471 - 70 - 0
WINDOW 1 4 1,700 0,811 11 666 0
E EXPOSURE
WALL 5 1,471 - 68 - 0
WINDOW 1 6 1,700 0,811 17 1238 0
NE EXPOSURE
WALL 6 1,471 - 63 - 0
WINDOW 1 4 1,700 0,811 11 536 0

Hourly Analysis Program v4.90 Page 7 of 16


Space Design Load Summary for A06-R1-Salle de réunion 1
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:36

TABLE 1.3.A. COMPONENT LOADS FOR SPACE '' A06-R1-S.de réunion 2 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 32,0 °C / 27,0 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 8 m² 1825 - 8 m² - -
Wall Transmission 7 m² 107 - 7 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 8 m² 112 - 8 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 15 m² 64 - 15 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 492 W 492 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1230 W 1230 - 0 0 -
People 5 359 301 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 4189 301 - 0 0

TABLE 1.3.B. ENVELOPE LOADS FOR SPACE '' A06-R1-S.de réunion 2 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NW EXPOSURE
WALL 7 1,471 - 107 - 0
WINDOW 1 8 1,700 0,811 112 1825 0

Hourly Analysis Program v4.90 Page 8 of 16


Space Design Load Summary for A06-R1-Salle de réunion 1
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:36

TABLE 1.4.A. COMPONENT LOADS FOR SPACE '' A06-R1-S.de réunion 3 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 32,0 °C / 27,0 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 8 m² 1825 - 8 m² - -
Wall Transmission 15 m² 290 - 15 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 8 m² 112 - 8 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 15 m² 62 - 15 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 626 W 626 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1565 W 1565 - 0 0 -
People 6 431 361 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 4910 361 - 0 0

TABLE 1.4.B. ENVELOPE LOADS FOR SPACE '' A06-R1-S.de réunion 3 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NW EXPOSURE
WALL 7 1,471 - 107 - 0
WINDOW 1 8 1,700 0,811 112 1825 0
NE EXPOSURE
WALL 9 1,471 - 183 - 0

Hourly Analysis Program v4.90 Page 9 of 16


Space Design Load Summary for A06-R1-Salle de réunion 1
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:36

TABLE 1.5.A. COMPONENT LOADS FOR SPACE '' A06-R1-S.de reunion 4 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 27,6 °C / 24,2 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 8 m² 2223 - 8 m² - -
Wall Transmission 7 m² 77 - 7 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 8 m² 51 - 8 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 15 m² 26 - 15 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 492 W 492 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1230 W 1230 - 0 0 -
People 5 359 301 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 4458 301 - 0 0

TABLE 1.5.B. ENVELOPE LOADS FOR SPACE '' A06-R1-S.de reunion 4 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 7 1,471 - 77 - 0
WINDOW 1 8 1,700 0,811 51 2223 0

Hourly Analysis Program v4.90 Page 10 of 16


Space Design Load Summary for A06-R1-Salle de réunion 1
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:36

TABLE 1.6.A. COMPONENT LOADS FOR SPACE '' A06-R1-S.de réunion 5 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 27,6 °C / 24,2 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 8 m² 2223 - 8 m² - -
Wall Transmission 16 m² 233 - 16 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 8 m² 51 - 8 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 40 m² 70 - 40 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 900 W 900 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2250 W 2250 - 0 0 -
People 5 359 301 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 6085 301 - 0 0

TABLE 1.6.B. ENVELOPE LOADS FOR SPACE '' A06-R1-S.de réunion 5 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 7 1,471 - 77 - 0
WINDOW 1 8 1,700 0,811 51 2223 0
SE EXPOSURE
WALL 9 1,471 - 156 - 0

Hourly Analysis Program v4.90 Page 11 of 16


Hourly Air System Design Day Loads for A06-R1-Salle de réunion 1
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:36

DESIGN MONTH: JULY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 23,4 2624 31,0 33,7 0,0 0,0 0,0 0,0 0,0 0,0
0100 22,8 2578 30,4 33,2 0,0 0,0 0,0 0,0 0,0 0,0
0200 22,2 2534 29,9 32,6 0,0 0,0 0,0 0,0 0,0 0,0
0300 21,8 2492 29,4 32,1 0,0 0,0 0,0 0,0 0,0 0,0
0400 21,4 2454 28,9 31,6 0,0 0,0 0,0 0,0 0,0 0,0
0500 21,3 2419 28,5 31,2 0,0 0,0 0,0 0,0 0,0 0,0
0600 21,5 2416 28,4 31,2 0,0 0,0 0,0 0,0 0,0 0,0
0700 22,1 2505 29,5 32,3 0,0 0,0 0,0 0,0 0,0 0,0
0800 23,2 2564 30,3 33,0 0,0 0,0 0,0 0,0 0,0 0,0
0900 24,7 2611 30,9 33,7 0,0 0,0 0,0 0,0 0,0 0,0
1000 26,4 2650 31,3 34,2 0,0 0,0 0,0 0,0 0,0 0,0
1100 28,4 2685 31,8 34,6 0,0 0,0 0,0 0,0 0,0 0,0
1200 30,2 2770 32,9 35,6 0,0 0,0 0,0 0,0 0,0 0,0
1300 31,6 2895 34,5 37,2 0,0 0,0 0,0 0,0 0,0 0,0
1400 32,6 3054 36,5 39,3 0,0 0,0 0,0 0,0 0,0 0,0
1500 32,9 3203 38,4 41,2 0,0 0,0 0,0 0,0 0,0 0,0
1600 32,6 3286 39,5 42,3 0,0 0,0 0,0 0,0 0,0 0,0
1700 31,7 3210 38,5 41,2 0,0 0,0 0,0 0,0 0,0 0,0
1800 30,5 2939 35,0 37,8 0,0 0,0 0,0 0,0 0,0 0,0
1900 29,0 2883 34,3 37,0 0,0 0,0 0,0 0,0 0,0 0,0
2000 27,4 2827 33,6 36,3 0,0 0,0 0,0 0,0 0,0 0,0
2100 26,2 2774 32,9 35,6 0,0 0,0 0,0 0,0 0,0 0,0
2200 25,0 2721 32,2 34,9 0,0 0,0 0,0 0,0 0,0 0,0
2300 24,1 2671 31,6 34,3 0,0 0,0 0,0 0,0 0,0 0,0

Hourly Analysis Program v4.90 Page 12 of 16


Hourly Zone Loads for A06-R1-Salle de réunion 1
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:36

ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 23,4 22,6 52 2623,7 31176,7 31018,8 0,0 0,0 0,0
0100 22,8 22,6 53 2578,3 30582,3 30449,6 0,0 0,0 0,0
0200 22,2 22,6 53 2533,7 29999,0 29889,5 0,0 0,0 0,0
0300 21,8 22,5 53 2492,4 29464,0 29373,8 0,0 0,0 0,0
0400 21,4 22,5 53 2454,3 28972,1 28897,8 0,0 0,0 0,0
0500 21,3 22,5 53 2419,3 28523,5 28461,9 0,0 0,0 0,0
0600 21,5 22,5 53 2416,4 28499,0 28425,3 0,0 0,0 0,0
0700 22,1 22,6 53 2505,0 29684,8 29531,1 0,0 0,0 0,0
0800 23,2 22,6 53 2564,4 30478,1 30274,6 0,0 0,0 0,0
0900 24,7 22,6 52 2611,4 31106,3 30864,5 0,0 0,0 0,0
1000 26,4 22,6 52 2649,6 31616,5 31344,9 0,0 0,0 0,0
1100 28,4 22,6 52 2685,1 32090,7 31792,8 0,0 0,0 0,0
1200 30,2 22,6 52 2770,0 33227,1 32866,1 0,0 0,0 0,0
1300 31,6 22,6 52 2895,1 34904,4 34454,3 0,0 0,0 0,0
1400 32,6 22,7 52 3054,4 37052,8 36492,7 0,0 0,0 0,0
1500 32,9 22,7 52 3203,3 39065,6 38410,7 0,0 0,0 0,0
1600 32,6 22,7 51 3285,9 40174,9 39482,0 0,0 0,0 0,0
1700 31,7 22,7 52 3209,8 39100,3 38495,0 0,0 0,0 0,0
1800 30,5 22,7 52 2939,2 35393,8 35017,2 0,0 0,0 0,0
1900 29,0 22,6 52 2882,5 34632,0 34294,6 0,0 0,0 0,0
2000 27,4 22,6 52 2827,1 33883,1 33589,3 0,0 0,0 0,0
2100 26,2 22,6 52 2773,8 33167,8 32913,3 0,0 0,0 0,0
2200 25,0 22,6 52 2721,1 32465,2 32247,1 0,0 0,0 0,0
2300 24,1 22,6 52 2671,0 31799,9 31614,1 0,0 0,0 0,0

Hourly Analysis Program v4.90 Page 13 of 16


System Psychrometrics for A06-R1-Salle de réunion 1
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:36

September DESIGN COOLING DAY, 1600

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 31,4 0,01984 0 400 0 0
Vent - Return Mixing Outlet 22,7 0,00886 3334 2442 - -
Preheat Coil Outlet 22,7 0,00886 3334 2442 0 -
Central Cooling Coil Outlet 12,8 0,00857 3334 2442 40110 2841
Supply Fan Outlet 12,8 0,00857 3334 2442 0 -
Cold Supply Duct Outlet 12,8 0,00857 3334 2442 - -
Zone Air - 22,7 0,00885 3334 2442 40110 2766
Return Plenum Outlet 22,7 0,00885 3334 2442 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 40842 Cooling 40110 22,7 3334 2442 0 0

Hourly Analysis Program v4.90 Page 14 of 16


System Psychrometrics for A06-R1-Salle de réunion 1
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:36

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 22,0 0,01667 0 400 0 0
Vent - Return Mixing Outlet 20,6 0,00866 37 800 - -
Preheat Coil Outlet 20,6 0,00866 37 800 0 -
Central Cooling Coil Outlet 12,8 0,00866 37 800 344 0
Supply Fan Outlet 12,8 0,00866 37 800 0 -
Cold Supply Duct Outlet 12,8 0,00866 37 800 - -
Zone Air - 20,6 0,00866 37 800 344 0
Return Plenum Outlet 20,6 0,00866 37 800 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 0 Heating 344 20,6 37 800 0 0

Hourly Analysis Program v4.90 Page 15 of 16


Psychrometric Analysis for A06-R1-Salle de réunion 1
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:36

Location: OUIDAH, BENIN


Altitude: 5,8 m.
Data for: September DESIGN COOLING DAY, 1600
0,020
1. Central Cooling Coil Outlet
2. Supply Fan Outlet
3. Room Air
0,018

0,016

Specific Humidity ( kg/kg )


0,014

0,012

3
0,010
12
0,008

0,006

0,004

0,002

0,000
0 5 10 15 20 25 30 35
Temperature ( °C )

Hourly Analysis Program v4.90 Page 16 of 16


Air System Sizing Summary for A06-R1-Batiment centrale R+2
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:36

Air System Information


Air System Name ............................. A06-R2-Niveau 2 Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area .............................................................. 263,6 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ....................................................... 43,0 kW Load occurs at ................................................. Sep 1600
Sensible coil load .................................................. 40,1 kW OA DB / WB ................................................... 31,4 / 26,5 °C
Coil L/s at Sep 1600 ............................................ 3334 L/s Entering DB / WB ........................................... 22,7 / 16,3 °C
Max block L/s at Sep 1600 ................................... 3671 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s .......................................... 3671 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,934 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 6,1 Resulting RH .............................................................. 51 %
W/m² .................................................................. 162,9 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K

Preheat Coil Sizing Data


No heating coil loads occurred during this calculation.

Supply Fan Sizing Data

Actual max L/s at Sep 1600 ................................. 3671 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ........................................................ 3669 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 13,93 L/(s-m²) Fan static ...................................................................... 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s ..................................................... 0 L/s L/s/person ................................................................ 0,00 L/s/person
L/(s-m²) ................................................................. 0,00 L/(s-m²)

Hourly Analysis Program v4.90 Page 1 of 16


Zone Sizing Summary for A06-R1-Salle de réunion 1
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:36

Air System Information


Air System Name ............. A06-R1-Salle de réunion 1 Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area .............................................................. 263,6 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 40,8 3671 37 Sep 1600 0,0 263,6 13,93

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
A06-R1-S.de réunion 1 3 5,9 Sep 1600 527 0,0 31,8 16,59
A06-R1-Espace lounge 1 6,5 Sep 0900 583 0,0 42,7 13,64
A06-R1-S.de réunion 2 1 4,2 Jun 1600 377 0,0 24,6 15,31
A06-R1-S.de réunion 3 1 4,9 Jun 1600 441 0,0 31,3 14,10
A06-R1-S.de reunion 4 1 4,5 Dec 1600 401 0,0 24,6 16,29
A06-R1-S.de réunion 5 1 6,1 Dec 1600 547 0,0 45,0 12,16

Hourly Analysis Program v4.90 Page 2 of 16


Ventilation Sizing Summary for A06-R1-Salle de réunion 1
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:36

1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 L/s

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (m²) Occupants (L/s) (L/s/person) (L/(s-m²)) (L/s) (% of supply) (L/s)
Zone 1
A06-R1-S.de réunion 1 3 31,8 6,0 527,4 0,00 0,00 0,0 0,0 0,0
A06-R1-Espace lounge 1 42,7 12,0 582,5 0,00 0,00 0,0 0,0 0,0
A06-R1-S.de réunion 2 1 24,6 5,0 376,5 0,00 0,00 0,0 0,0 0,0
A06-R1-S.de réunion 3 1 31,3 6,0 441,3 0,00 0,00 0,0 0,0 0,0
A06-R1-S.de reunion 4 1 24,6 5,0 400,7 0,00 0,00 0,0 0,0 0,0
A06-R1-S.de réunion 5 1 45,0 5,0 547,0 0,00 0,00 0,0 0,0 0,0
Totals (incl. Space Multipliers) 3930,3 0,0

Hourly Analysis Program v4.90 Page 3 of 16


Air System Design Load Summary for A06-R1-Salle de réunion 1
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:36

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Sep 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 31,4 °C / 26,5 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 95 m² 15572 - 95 m² - -
Wall Transmission 103 m² 1419 - 103 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 95 m² 1230 - 95 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 143 m² 560 - 143 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 5272 W 5272 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 13180 W 13179 - 0 0 -
People 51 3609 2766 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 40842 2766 - 0 0
Zone Conditioning - 40110 2766 - -344 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 3334 L/s 0 - 37 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 3334 L/s 0 - 37 L/s 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 40110 2766 - -344 0
Central Cooling Coil - 40110 2841 - -344 0
Preheat Coil - 0 - - 0 -
Terminal Reheat Coils - 0 - - 0 -
>> Total Conditioning - 40110 2841 - -344 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 4 of 16


Zone Design Load Summary for A06-R1-Salle de réunion 1
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:36

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Sep 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 31,4 °C / 26,5 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 95 m² 15572 - 95 m² - -
Wall Transmission 103 m² 1419 - 103 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 95 m² 1230 - 95 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 143 m² 560 - 143 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 5272 W 5272 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 13180 W 13179 - 0 0 -
People 51 3609 2766 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 40842 2766 - 0 0

Hourly Analysis Program v4.90 Page 5 of 16


Space Design Load Summary for A06-R1-Salle de réunion 1
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:36

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A06-R1-S.de réunion 1 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Sep 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 31,4 °C / 26,5 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 16 m² 2806 - 16 m² - -
Wall Transmission 14 m² 166 - 14 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 16 m² 210 - 16 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 8 m² 29 - 8 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 636 W 636 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1590 W 1590 - 0 0 -
People 6 431 361 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 5868 361 - 0 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A06-R1-S.de réunion 1 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NW EXPOSURE
WALL 7 1,471 - 78 - 0
WINDOW 1 8 1,700 0,811 105 1285 0
SW EXPOSURE
WALL 7 1,471 - 88 - 0
WINDOW 1 8 1,700 0,811 105 1521 0

Hourly Analysis Program v4.90 Page 6 of 16


Space Design Load Summary for A06-R1-Salle de réunion 1
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:36

TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' A06-R1-Espace lounge '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Sep 0900 HEATING DATA AT DES HTG
COOLING OA DB / WB 23,6 °C / 23,3 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 14 m² 2441 - 14 m² - -
Wall Transmission 17 m² 200 - 17 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 14 m² 39 - 14 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 36 m² 3 - 36 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 854 W 854 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2135 W 2135 - 0 0 -
People 12 809 422 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 6481 422 - 0 0

TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' A06-R1-Espace lounge '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SE EXPOSURE
WALL 6 1,471 - 70 - 0
WINDOW 1 4 1,700 0,811 11 666 0
E EXPOSURE
WALL 5 1,471 - 68 - 0
WINDOW 1 6 1,700 0,811 17 1238 0
NE EXPOSURE
WALL 6 1,471 - 63 - 0
WINDOW 1 4 1,700 0,811 11 536 0

Hourly Analysis Program v4.90 Page 7 of 16


Space Design Load Summary for A06-R1-Salle de réunion 1
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:36

TABLE 1.3.A. COMPONENT LOADS FOR SPACE '' A06-R1-S.de réunion 2 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 32,0 °C / 27,0 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 8 m² 1825 - 8 m² - -
Wall Transmission 7 m² 107 - 7 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 8 m² 112 - 8 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 15 m² 64 - 15 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 492 W 492 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1230 W 1230 - 0 0 -
People 5 359 301 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 4189 301 - 0 0

TABLE 1.3.B. ENVELOPE LOADS FOR SPACE '' A06-R1-S.de réunion 2 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NW EXPOSURE
WALL 7 1,471 - 107 - 0
WINDOW 1 8 1,700 0,811 112 1825 0

Hourly Analysis Program v4.90 Page 8 of 16


Space Design Load Summary for A06-R1-Salle de réunion 1
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:36

TABLE 1.4.A. COMPONENT LOADS FOR SPACE '' A06-R1-S.de réunion 3 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 32,0 °C / 27,0 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 8 m² 1825 - 8 m² - -
Wall Transmission 15 m² 290 - 15 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 8 m² 112 - 8 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 15 m² 62 - 15 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 626 W 626 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1565 W 1565 - 0 0 -
People 6 431 361 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 4910 361 - 0 0

TABLE 1.4.B. ENVELOPE LOADS FOR SPACE '' A06-R1-S.de réunion 3 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NW EXPOSURE
WALL 7 1,471 - 107 - 0
WINDOW 1 8 1,700 0,811 112 1825 0
NE EXPOSURE
WALL 9 1,471 - 183 - 0

Hourly Analysis Program v4.90 Page 9 of 16


Space Design Load Summary for A06-R1-Salle de réunion 1
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:36

TABLE 1.5.A. COMPONENT LOADS FOR SPACE '' A06-R1-S.de reunion 4 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 27,6 °C / 24,2 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 8 m² 2223 - 8 m² - -
Wall Transmission 7 m² 77 - 7 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 8 m² 51 - 8 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 15 m² 26 - 15 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 492 W 492 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1230 W 1230 - 0 0 -
People 5 359 301 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 4458 301 - 0 0

TABLE 1.5.B. ENVELOPE LOADS FOR SPACE '' A06-R1-S.de reunion 4 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 7 1,471 - 77 - 0
WINDOW 1 8 1,700 0,811 51 2223 0

Hourly Analysis Program v4.90 Page 10 of 16


Space Design Load Summary for A06-R1-Salle de réunion 1
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:36

TABLE 1.6.A. COMPONENT LOADS FOR SPACE '' A06-R1-S.de réunion 5 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 27,6 °C / 24,2 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 8 m² 2223 - 8 m² - -
Wall Transmission 16 m² 233 - 16 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 8 m² 51 - 8 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 40 m² 70 - 40 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 900 W 900 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2250 W 2250 - 0 0 -
People 5 359 301 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 6085 301 - 0 0

TABLE 1.6.B. ENVELOPE LOADS FOR SPACE '' A06-R1-S.de réunion 5 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 7 1,471 - 77 - 0
WINDOW 1 8 1,700 0,811 51 2223 0
SE EXPOSURE
WALL 9 1,471 - 156 - 0

Hourly Analysis Program v4.90 Page 11 of 16


Hourly Air System Design Day Loads for A06-R1-Salle de réunion 1
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:36

DESIGN MONTH: JULY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 23,4 2624 31,0 33,7 0,0 0,0 0,0 0,0 0,0 0,0
0100 22,8 2578 30,4 33,2 0,0 0,0 0,0 0,0 0,0 0,0
0200 22,2 2534 29,9 32,6 0,0 0,0 0,0 0,0 0,0 0,0
0300 21,8 2492 29,4 32,1 0,0 0,0 0,0 0,0 0,0 0,0
0400 21,4 2454 28,9 31,6 0,0 0,0 0,0 0,0 0,0 0,0
0500 21,3 2419 28,5 31,2 0,0 0,0 0,0 0,0 0,0 0,0
0600 21,5 2416 28,4 31,2 0,0 0,0 0,0 0,0 0,0 0,0
0700 22,1 2505 29,5 32,3 0,0 0,0 0,0 0,0 0,0 0,0
0800 23,2 2564 30,3 33,0 0,0 0,0 0,0 0,0 0,0 0,0
0900 24,7 2611 30,9 33,7 0,0 0,0 0,0 0,0 0,0 0,0
1000 26,4 2650 31,3 34,2 0,0 0,0 0,0 0,0 0,0 0,0
1100 28,4 2685 31,8 34,6 0,0 0,0 0,0 0,0 0,0 0,0
1200 30,2 2770 32,9 35,6 0,0 0,0 0,0 0,0 0,0 0,0
1300 31,6 2895 34,5 37,2 0,0 0,0 0,0 0,0 0,0 0,0
1400 32,6 3054 36,5 39,3 0,0 0,0 0,0 0,0 0,0 0,0
1500 32,9 3203 38,4 41,2 0,0 0,0 0,0 0,0 0,0 0,0
1600 32,6 3286 39,5 42,3 0,0 0,0 0,0 0,0 0,0 0,0
1700 31,7 3210 38,5 41,2 0,0 0,0 0,0 0,0 0,0 0,0
1800 30,5 2939 35,0 37,8 0,0 0,0 0,0 0,0 0,0 0,0
1900 29,0 2883 34,3 37,0 0,0 0,0 0,0 0,0 0,0 0,0
2000 27,4 2827 33,6 36,3 0,0 0,0 0,0 0,0 0,0 0,0
2100 26,2 2774 32,9 35,6 0,0 0,0 0,0 0,0 0,0 0,0
2200 25,0 2721 32,2 34,9 0,0 0,0 0,0 0,0 0,0 0,0
2300 24,1 2671 31,6 34,3 0,0 0,0 0,0 0,0 0,0 0,0

Hourly Analysis Program v4.90 Page 12 of 16


Hourly Zone Loads for A06-R1-Salle de réunion 1
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:36

ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 23,4 22,6 52 2623,7 31176,7 31018,8 0,0 0,0 0,0
0100 22,8 22,6 53 2578,3 30582,3 30449,6 0,0 0,0 0,0
0200 22,2 22,6 53 2533,7 29999,0 29889,5 0,0 0,0 0,0
0300 21,8 22,5 53 2492,4 29464,0 29373,8 0,0 0,0 0,0
0400 21,4 22,5 53 2454,3 28972,1 28897,8 0,0 0,0 0,0
0500 21,3 22,5 53 2419,3 28523,5 28461,9 0,0 0,0 0,0
0600 21,5 22,5 53 2416,4 28499,0 28425,3 0,0 0,0 0,0
0700 22,1 22,6 53 2505,0 29684,8 29531,1 0,0 0,0 0,0
0800 23,2 22,6 53 2564,4 30478,1 30274,6 0,0 0,0 0,0
0900 24,7 22,6 52 2611,4 31106,3 30864,5 0,0 0,0 0,0
1000 26,4 22,6 52 2649,6 31616,5 31344,9 0,0 0,0 0,0
1100 28,4 22,6 52 2685,1 32090,7 31792,8 0,0 0,0 0,0
1200 30,2 22,6 52 2770,0 33227,1 32866,1 0,0 0,0 0,0
1300 31,6 22,6 52 2895,1 34904,4 34454,3 0,0 0,0 0,0
1400 32,6 22,7 52 3054,4 37052,8 36492,7 0,0 0,0 0,0
1500 32,9 22,7 52 3203,3 39065,6 38410,7 0,0 0,0 0,0
1600 32,6 22,7 51 3285,9 40174,9 39482,0 0,0 0,0 0,0
1700 31,7 22,7 52 3209,8 39100,3 38495,0 0,0 0,0 0,0
1800 30,5 22,7 52 2939,2 35393,8 35017,2 0,0 0,0 0,0
1900 29,0 22,6 52 2882,5 34632,0 34294,6 0,0 0,0 0,0
2000 27,4 22,6 52 2827,1 33883,1 33589,3 0,0 0,0 0,0
2100 26,2 22,6 52 2773,8 33167,8 32913,3 0,0 0,0 0,0
2200 25,0 22,6 52 2721,1 32465,2 32247,1 0,0 0,0 0,0
2300 24,1 22,6 52 2671,0 31799,9 31614,1 0,0 0,0 0,0

Hourly Analysis Program v4.90 Page 13 of 16


System Psychrometrics for A06-R1-Salle de réunion 1
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:36

September DESIGN COOLING DAY, 1600

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 31,4 0,01984 0 400 0 0
Vent - Return Mixing Outlet 22,7 0,00886 3334 2442 - -
Preheat Coil Outlet 22,7 0,00886 3334 2442 0 -
Central Cooling Coil Outlet 12,8 0,00857 3334 2442 40110 2841
Supply Fan Outlet 12,8 0,00857 3334 2442 0 -
Cold Supply Duct Outlet 12,8 0,00857 3334 2442 - -
Zone Air - 22,7 0,00885 3334 2442 40110 2766
Return Plenum Outlet 22,7 0,00885 3334 2442 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 40842 Cooling 40110 22,7 3334 2442 0 0

Hourly Analysis Program v4.90 Page 14 of 16


System Psychrometrics for A06-R1-Salle de réunion 1
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:36

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 22,0 0,01667 0 400 0 0
Vent - Return Mixing Outlet 20,6 0,00866 37 800 - -
Preheat Coil Outlet 20,6 0,00866 37 800 0 -
Central Cooling Coil Outlet 12,8 0,00866 37 800 344 0
Supply Fan Outlet 12,8 0,00866 37 800 0 -
Cold Supply Duct Outlet 12,8 0,00866 37 800 - -
Zone Air - 20,6 0,00866 37 800 344 0
Return Plenum Outlet 20,6 0,00866 37 800 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 0 Heating 344 20,6 37 800 0 0

Hourly Analysis Program v4.90 Page 15 of 16


Psychrometric Analysis for A06-R1-Salle de réunion 1
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:36

Location: OUIDAH, BENIN


Altitude: 5,8 m.
Data for: September DESIGN COOLING DAY, 1600
0,020
1. Central Cooling Coil Outlet
2. Supply Fan Outlet
3. Room Air
0,018

0,016

Specific Humidity ( kg/kg )


0,014

0,012

3
0,010
12
0,008

0,006

0,004

0,002

0,000
0 5 10 15 20 25 30 35
Temperature ( °C )

Hourly Analysis Program v4.90 Page 16 of 16


Air System Sizing Summary for A06-R3: Batiment centrale R+3
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:38

Air System Information


Air System Name ............................. A06-R3:Niveau 3 Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area .............................................................. 246,1 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ....................................................... 45,3 kW Load occurs at ................................................ Aug 1600
Sensible coil load .................................................. 42,8 kW OA DB / WB ................................................... 32,6 / 27,0 °C
Coil L/s at Aug 1600 ............................................ 3560 L/s Entering DB / WB ........................................... 22,7 / 16,2 °C
Max block L/s at Aug 1600 ................................... 3933 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s .......................................... 3933 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,946 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 5,4 Resulting RH .............................................................. 51 %
W/m² .................................................................. 183,9 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K

Preheat Coil Sizing Data


No heating coil loads occurred during this calculation.

Supply Fan Sizing Data

Actual max L/s at Aug 1600 ................................. 3933 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ........................................................ 3930 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 15,98 L/(s-m²) Fan static ...................................................................... 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s ..................................................... 0 L/s L/s/person ................................................................ 0,00 L/s/person
L/(s-m²) ................................................................. 0,00 L/(s-m²)

Hourly Analysis Program v4.90 Page 1 of 16


Zone Sizing Summary for A06-R3:Salle de réunion 2
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:38

Air System Information


Air System Name ............. A06-R3:Salle de réunion 2 Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area .............................................................. 246,1 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 43,8 3933 39 Aug 1600 0,0 246,1 15,98

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
A06-R3-S.de réunion 2 2 5,1 Jun 1600 455 0,0 24,6 18,49
A06-R3-Espace lounge 1 9,9 Aug 1600 894 0,0 64,2 13,93
A06-R3-S.de réunion 1 1 7,1 Sep 1600 635 0,0 31,8 19,96
A06-R3-S.de réunion 3 1 6,0 Jun 1600 541 0,0 31,3 17,28
A06-R3-S.de réunion 4 1 5,2 Dec 1600 466 0,0 24,6 18,96
A06-R3-S.de réunion 5 1 7,5 Nov 1600 672 0,0 45,0 14,92

Hourly Analysis Program v4.90 Page 2 of 16


Ventilation Sizing Summary for A06-R3:Salle de réunion 2
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:38

1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 L/s

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (m²) Occupants (L/s) (L/s/person) (L/(s-m²)) (L/s) (% of supply) (L/s)
Zone 1
A06-R3-S.de réunion 2 2 24,6 5,0 454,7 0,00 0,00 0,0 0,0 0,0
A06-R3-Espace lounge 1 64,2 12,0 894,3 0,00 0,00 0,0 0,0 0,0
A06-R3-S.de réunion 1 1 31,8 6,0 634,8 0,00 0,00 0,0 0,0 0,0
A06-R3-S.de réunion 3 1 31,3 6,0 540,9 0,00 0,00 0,0 0,0 0,0
A06-R3-S.de réunion 4 1 24,6 5,0 466,5 0,00 0,00 0,0 0,0 0,0
A06-R3-S.de réunion 5 1 45,0 5,0 671,5 0,00 0,00 0,0 0,0 0,0
Totals (incl. Space Multipliers) 4117,5 0,0

Hourly Analysis Program v4.90 Page 3 of 16


Air System Design Load Summary for A06-R3:Salle de réunion 2
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:38

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 32,6 °C / 27,0 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 71 m² 11167 - 71 m² - -
Wall Transmission 83 m² 1288 - 83 m² 0 -
Roof Transmission 246 m² 9264 - 246 m² 0 -
Window Transmission 71 m² 1050 - 71 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 143 m² 656 - 143 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 4922 W 4922 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 12305 W 12304 - 0 0 -
People 44 3106 2346 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 43757 2346 - 0 0
Zone Conditioning - 42819 2346 - -371 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 3560 L/s 0 - 39 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 3560 L/s 0 - 39 L/s 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 42819 2346 - -371 0
Central Cooling Coil - 42819 2435 - -371 0
Preheat Coil - 0 - - 0 -
Terminal Reheat Coils - 0 - - 0 -
>> Total Conditioning - 42819 2435 - -371 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 4 of 16


Zone Design Load Summary for A06-R3:Salle de réunion 2
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:38

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 32,6 °C / 27,0 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 71 m² 11167 - 71 m² - -
Wall Transmission 83 m² 1288 - 83 m² 0 -
Roof Transmission 246 m² 9264 - 246 m² 0 -
Window Transmission 71 m² 1050 - 71 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 143 m² 656 - 143 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 4922 W 4922 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 12305 W 12304 - 0 0 -
People 44 3106 2346 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 43757 2346 - 0 0

Hourly Analysis Program v4.90 Page 5 of 16


Space Design Load Summary for A06-R3:Salle de réunion 2
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:38

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A06-R3-S.de réunion 2 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 32,0 °C / 27,0 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 8 m² 1825 - 8 m² - -
Wall Transmission 7 m² 107 - 7 m² 0 -
Roof Transmission 25 m² 870 - 25 m² 0 -
Window Transmission 8 m² 112 - 8 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 15 m² 64 - 15 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 492 W 492 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1230 W 1230 - 0 0 -
People 5 359 301 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 5059 301 - 0 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A06-R3-S.de réunion 2 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NW EXPOSURE
WALL 7 1,471 - 107 - 0
WINDOW 1 8 1,700 0,811 112 1825 0
H EXPOSURE
ROOF 25 1,137 - 870 - 0

Hourly Analysis Program v4.90 Page 6 of 16


Space Design Load Summary for A06-R3:Salle de réunion 2
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:38

TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' A06-R3-Espace lounge '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 32,6 °C / 27,0 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 14 m² 1532 - 14 m² - -
Wall Transmission 17 m² 323 - 17 m² 0 -
Roof Transmission 64 m² 2417 - 64 m² 0 -
Window Transmission 14 m² 209 - 14 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 36 m² 165 - 36 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1284 W 1284 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 3210 W 3210 - 0 0 -
People 12 809 422 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 9949 422 - 0 0

TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' A06-R3-Espace lounge '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SE EXPOSURE
WALL 6 1,471 - 94 - 0
WINDOW 1 4 1,700 0,811 60 341 0
E EXPOSURE
WALL 5 1,471 - 112 - 0
WINDOW 1 6 1,700 0,811 89 737 0
NE EXPOSURE
WALL 6 1,471 - 117 - 0
WINDOW 1 4 1,700 0,811 60 454 0
H EXPOSURE
ROOF 64 1,137 - 2417 - 0

Hourly Analysis Program v4.90 Page 7 of 16


Space Design Load Summary for A06-R3:Salle de réunion 2
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:38

TABLE 1.3.A. COMPONENT LOADS FOR SPACE '' A06-R3-S.de réunion 1 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Sep 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 31,4 °C / 26,5 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 16 m² 2806 - 16 m² - -
Wall Transmission 14 m² 166 - 14 m² 0 -
Roof Transmission 32 m² 1194 - 32 m² 0 -
Window Transmission 16 m² 210 - 16 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 8 m² 29 - 8 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 636 W 636 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1590 W 1590 - 0 0 -
People 6 431 361 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 7062 361 - 0 0

TABLE 1.3.B. ENVELOPE LOADS FOR SPACE '' A06-R3-S.de réunion 1 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NW EXPOSURE
WALL 7 1,471 - 78 - 0
WINDOW 1 8 1,700 0,811 105 1285 0
SW EXPOSURE
WALL 7 1,471 - 88 - 0
WINDOW 1 8 1,700 0,811 105 1521 0
H EXPOSURE
ROOF 32 1,137 - 1194 - 0

Hourly Analysis Program v4.90 Page 8 of 16


Space Design Load Summary for A06-R3:Salle de réunion 2
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:38

TABLE 1.4.A. COMPONENT LOADS FOR SPACE '' A06-R3-S.de réunion 3 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 32,0 °C / 27,0 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 8 m² 1825 - 8 m² - -
Wall Transmission 15 m² 290 - 15 m² 0 -
Roof Transmission 31 m² 1107 - 31 m² 0 -
Window Transmission 8 m² 112 - 8 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 15 m² 62 - 15 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 626 W 626 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1565 W 1565 - 0 0 -
People 6 431 361 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 6017 361 - 0 0

TABLE 1.4.B. ENVELOPE LOADS FOR SPACE '' A06-R3-S.de réunion 3 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NW EXPOSURE
WALL 7 1,471 - 107 - 0
WINDOW 1 8 1,700 0,811 112 1825 0
NE EXPOSURE
WALL 9 1,471 - 183 - 0
H EXPOSURE
ROOF 31 1,137 - 1107 - 0

Hourly Analysis Program v4.90 Page 9 of 16


Space Design Load Summary for A06-R3:Salle de réunion 2
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:38

TABLE 1.5.A. COMPONENT LOADS FOR SPACE '' A06-R3-S.de réunion 4 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 27,6 °C / 24,2 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 8 m² 2223 - 8 m² - -
Wall Transmission 7 m² 77 - 7 m² 0 -
Roof Transmission 25 m² 732 - 25 m² 0 -
Window Transmission 8 m² 51 - 8 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 15 m² 26 - 15 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 492 W 492 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1230 W 1230 - 0 0 -
People 5 359 301 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 5190 301 - 0 0

TABLE 1.5.B. ENVELOPE LOADS FOR SPACE '' A06-R3-S.de réunion 4 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 7 1,471 - 77 - 0
WINDOW 1 8 1,700 0,811 51 2223 0
H EXPOSURE
ROOF 25 1,137 - 732 - 0

Hourly Analysis Program v4.90 Page 10 of 16


Space Design Load Summary for A06-R3:Salle de réunion 2
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:38

TABLE 1.6.A. COMPONENT LOADS FOR SPACE '' A06-R3-S.de réunion 5 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Nov 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 28,7 °C / 25,3 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 8 m² 2106 - 8 m² - -
Wall Transmission 16 m² 252 - 16 m² 0 -
Roof Transmission 45 m² 1444 - 45 m² 0 -
Window Transmission 8 m² 67 - 8 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 40 m² 94 - 40 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 900 W 900 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2250 W 2250 - 0 0 -
People 5 359 301 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 7471 301 - 0 0

TABLE 1.6.B. ENVELOPE LOADS FOR SPACE '' A06-R3-S.de réunion 5 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 7 1,471 - 85 - 0
WINDOW 1 8 1,700 0,811 67 2106 0
SE EXPOSURE
WALL 9 1,471 - 168 - 0
H EXPOSURE
ROOF 45 1,137 - 1444 - 0

Hourly Analysis Program v4.90 Page 11 of 16


Hourly Air System Design Day Loads for A06-R3:Salle de réunion 2
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:38

DESIGN MONTH: JULY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 23,4 2644 31,1 33,4 0,0 0,0 0,0 0,0 0,0 0,0
0100 22,8 2563 30,1 32,5 0,0 0,0 0,0 0,0 0,0 0,0
0200 22,2 2488 29,2 31,5 0,0 0,0 0,0 0,0 0,0 0,0
0300 21,8 2420 28,4 30,7 0,0 0,0 0,0 0,0 0,0 0,0
0400 21,4 2359 27,6 29,9 0,0 0,0 0,0 0,0 0,0 0,0
0500 21,3 2304 26,9 29,2 0,0 0,0 0,0 0,0 0,0 0,0
0600 21,5 2280 26,6 29,0 0,0 0,0 0,0 0,0 0,0 0,0
0700 22,1 2342 27,4 29,8 0,0 0,0 0,0 0,0 0,0 0,0
0800 23,2 2389 28,0 30,4 0,0 0,0 0,0 0,0 0,0 0,0
0900 24,7 2453 28,8 31,1 0,0 0,0 0,0 0,0 0,0 0,0
1000 26,4 2541 29,9 32,2 0,0 0,0 0,0 0,0 0,0 0,0
1100 28,4 2652 31,2 33,6 0,0 0,0 0,0 0,0 0,0 0,0
1200 30,2 2818 33,3 35,7 0,0 0,0 0,0 0,0 0,0 0,0
1300 31,6 3020 35,9 38,2 0,0 0,0 0,0 0,0 0,0 0,0
1400 32,6 3235 38,6 41,0 0,0 0,0 0,0 0,0 0,0 0,0
1500 32,9 3420 41,0 43,3 0,0 0,0 0,0 0,0 0,0 0,0
1600 32,6 3528 42,4 44,8 0,0 0,0 0,0 0,0 0,0 0,0
1700 31,7 3486 41,8 44,2 0,0 0,0 0,0 0,0 0,0 0,0
1800 30,5 3263 39,0 41,3 0,0 0,0 0,0 0,0 0,0 0,0
1900 29,0 3166 37,7 40,0 0,0 0,0 0,0 0,0 0,0 0,0
2000 27,4 3052 36,3 38,6 0,0 0,0 0,0 0,0 0,0 0,0
2100 26,2 2938 34,8 37,2 0,0 0,0 0,0 0,0 0,0 0,0
2200 25,0 2831 33,5 35,8 0,0 0,0 0,0 0,0 0,0 0,0
2300 24,1 2733 32,3 34,6 0,0 0,0 0,0 0,0 0,0 0,0

Hourly Analysis Program v4.90 Page 12 of 16


Hourly Zone Loads for A06-R3:Salle de réunion 2
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:38

ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 23,4 22,5 52 2644,4 31369,2 31146,8 0,0 0,0 0,0
0100 22,8 22,5 52 2563,2 30312,4 30135,4 0,0 0,0 0,0
0200 22,2 22,5 52 2487,9 29338,1 29199,9 0,0 0,0 0,0
0300 21,8 22,5 53 2420,2 28469,4 28362,7 0,0 0,0 0,0
0400 21,4 22,5 53 2359,1 27690,2 27608,8 0,0 0,0 0,0
0500 21,3 22,5 53 2303,8 26989,7 26928,5 0,0 0,0 0,0
0600 21,5 22,5 53 2280,4 26705,7 26641,5 0,0 0,0 0,0
0700 22,1 22,5 53 2342,5 27530,1 27403,8 0,0 0,0 0,0
0800 23,2 22,5 53 2389,3 28152,1 27980,7 0,0 0,0 0,0
0900 24,7 22,5 53 2453,4 28999,9 28773,3 0,0 0,0 0,0
1000 26,4 22,5 52 2541,3 30158,4 29863,1 0,0 0,0 0,0
1100 28,4 22,5 52 2651,9 31615,8 31240,0 0,0 0,0 0,0
1200 30,2 22,6 52 2818,0 33813,7 33322,0 0,0 0,0 0,0
1300 31,6 22,6 52 3020,3 36505,2 35878,4 0,0 0,0 0,0
1400 32,6 22,7 51 3235,3 39385,3 38621,2 0,0 0,0 0,0
1500 32,9 22,7 51 3420,1 41872,1 40999,4 0,0 0,0 0,0
1600 32,6 22,7 51 3527,9 43316,5 42396,4 0,0 0,0 0,0
1700 31,7 22,7 51 3485,6 42704,2 41848,3 0,0 0,0 0,0
1800 30,5 22,7 51 3263,3 39646,6 38979,6 0,0 0,0 0,0
1900 29,0 22,7 51 3166,2 38324,5 37736,4 0,0 0,0 0,0
2000 27,4 22,6 52 3051,7 36774,7 36277,4 0,0 0,0 0,0
2100 26,2 22,6 52 2938,1 35250,4 34837,2 0,0 0,0 0,0
2200 25,0 22,6 52 2831,1 33825,2 33486,3 0,0 0,0 0,0
2300 24,1 22,6 52 2733,2 32533,1 32257,6 0,0 0,0 0,0

Hourly Analysis Program v4.90 Page 13 of 16


System Psychrometrics for A06-R3:Salle de réunion 2
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:38

August DESIGN COOLING DAY, 1600

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 32,6 0,02036 0 400 0 0
Vent - Return Mixing Outlet 22,7 0,00880 3560 2115 - -
Preheat Coil Outlet 22,7 0,00880 3560 2115 0 -
Central Cooling Coil Outlet 12,8 0,00857 3560 2115 42819 2435
Supply Fan Outlet 12,8 0,00857 3560 2115 0 -
Cold Supply Duct Outlet 12,8 0,00857 3560 2115 - -
Zone Air - 22,7 0,00879 3560 2115 42819 2346
Return Plenum Outlet 22,7 0,00879 3560 2115 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 43757 Cooling 42819 22,7 3560 2115 0 0

Hourly Analysis Program v4.90 Page 14 of 16


System Psychrometrics for A06-R3:Salle de réunion 2
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:38

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 22,0 0,01667 0 400 0 0
Vent - Return Mixing Outlet 20,6 0,00866 39 800 - -
Preheat Coil Outlet 20,6 0,00866 39 800 0 -
Central Cooling Coil Outlet 12,8 0,00866 39 800 371 0
Supply Fan Outlet 12,8 0,00866 39 800 0 -
Cold Supply Duct Outlet 12,8 0,00866 39 800 - -
Zone Air - 20,6 0,00866 39 800 371 0
Return Plenum Outlet 20,6 0,00866 39 800 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 0 Heating 371 20,6 39 800 0 0

Hourly Analysis Program v4.90 Page 15 of 16


Psychrometric Analysis for A06-R3:Salle de réunion 2
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:38

Location: OUIDAH, BENIN


Altitude: 5,8 m.
Data for: August DESIGN COOLING DAY, 1600

1. Central Cooling Coil Outlet


2. Supply Fan Outlet
3. Room Air 0,024
0,022
0,020

Specific Humidity ( kg/kg )


0,018
0,016
0,014
0,012

12 3 0,010
0,008
0,006
0,004
0,002
0,000
0 5 10 15 20 25 30 35
Temperature ( °C )

Hourly Analysis Program v4.90 Page 16 of 16


Air System Sizing Summary for A06-R1-Espace de travail D
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:27

Air System Information


Air System Name ........... A06-R1-Espace de travail D Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area .............................................................. 458,0 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ....................................................... 74,9 kW Load occurs at .................................................. Jul 1600
Sensible coil load .................................................. 70,6 kW OA DB / WB ................................................... 32,6 / 27,0 °C
Coil L/s at Jul 1600 .............................................. 5868 L/s Entering DB / WB ........................................... 22,8 / 16,2 °C
Max block L/s at Jul 1600 .................................... 6454 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s .......................................... 6454 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,943 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 6,1 Resulting RH .............................................................. 51 %
W/m² .................................................................. 163,5 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K

Preheat Coil Sizing Data


No heating coil loads occurred during this calculation.

Supply Fan Sizing Data

Actual max L/s at Jul 1600 ................................... 6454 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ........................................................ 6450 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 14,09 L/(s-m²) Fan static ...................................................................... 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s ..................................................... 0 L/s L/s/person ................................................................ 0,00 L/s/person
L/(s-m²) ................................................................. 0,00 L/(s-m²)

Hourly Analysis Program v4.90 Page 1 of 12


Zone Sizing Summary for A06-R1-Espace de travail D
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:27

Air System Information


Air System Name ........... A06-R1-Espace de travail D Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area .............................................................. 458,0 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 71,8 6454 65 Jul 1600 0,0 458,0 14,09

Zone Terminal Sizing Data

Reheat Zone Zone


Reheat Coil Htg Htg Mixing
Coil Water Coil Water Box Fan
Load L/s Load L/s Airflow
Zone Name (kW) @ 11,1 °K (kW) @ 11,1 °K (L/s)
Zone 1 0,0 - 0,0 - 0

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
A06-R1-E.de travail D 1 31,7 Jun 1600 2848 0,0 229,0 12,44
A06-R2-E.de travail D 1 40,2 Jul 1600 3609 0,0 229,0 15,76

Hourly Analysis Program v4.90 Page 2 of 12


Ventilation Sizing Summary for A06-R1-Espace de travail D
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:27

1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 L/s

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (m²) Occupants (L/s) (L/s/person) (L/(s-m²)) (L/s) (% of supply) (L/s)
Zone 1
A06-R1-E.de travail D 1 229,0 44,0 2848,4 0,00 0,00 0,0 0,0 0,0
A06-R2-E.de travail D 1 229,0 44,0 3609,5 0,00 0,00 0,0 0,0 0,0
Totals (incl. Space Multipliers) 6457,9 0,0

Hourly Analysis Program v4.90 Page 3 of 12


Air System Design Load Summary for A06-R1-Espace de travail D
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:27

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 32,6 °C / 27,0 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 150 m² 20635 - 150 m² - -
Wall Transmission 121 m² 1728 - 121 m² 0 -
Roof Transmission 229 m² 8312 - 229 m² 0 -
Window Transmission 150 m² 2220 - 150 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 159 m² 729 - 159 m² 19 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 9160 W 9159 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 22900 W 22899 - 0 0 -
People 88 6125 4193 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 71807 4193 - 19 0
Zone Conditioning - 70603 4193 - -603 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 5868 L/s 0 - 65 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 5868 L/s 0 - 65 L/s 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 70603 4193 - -603 0
Central Cooling Coil - 70603 4264 - -614 0
Preheat Coil - 0 - - 0 -
Terminal Reheat Coils - 0 - - 11 -
>> Total Conditioning - 70603 4264 - -603 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 4 of 12


Zone Design Load Summary for A06-R1-Espace de travail D
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:27

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 32,6 °C / 27,0 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 150 m² 20635 - 150 m² - -
Wall Transmission 121 m² 1728 - 121 m² 0 -
Roof Transmission 229 m² 8312 - 229 m² 0 -
Window Transmission 150 m² 2220 - 150 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 159 m² 729 - 159 m² 19 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 9160 W 9159 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 22900 W 22899 - 0 0 -
People 88 6125 4193 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 71807 4193 - 19 0

Hourly Analysis Program v4.90 Page 5 of 12


Space Design Load Summary for A06-R1-Espace de travail D
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:27

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A06-R1-E.de travail D '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 32,0 °C / 27,0 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 75 m² 10501 - 75 m² - -
Wall Transmission 60 m² 817 - 60 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 75 m² 1039 - 75 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 80 m² 338 - 80 m² 10 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 4580 W 4580 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 11450 W 11449 - 0 0 -
People 44 2966 1549 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 31690 1549 - 10 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A06-R1-E.de travail D '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 11 1,471 - 112 - 0
WINDOW 1 4 1,700 0,811 56 380 0
NW EXPOSURE
WALL 21 1,471 - 321 - 0
WINDOW 1 24 1,700 0,811 337 5474 0
NE EXPOSURE
WALL 2 1,471 - 48 - 0
WINDOW 1 20 1,700 0,811 281 2677 0
E EXPOSURE
WALL 5 1,471 - 104 - 0
WINDOW 1 6 1,700 0,811 83 705 0
SE EXPOSURE
WALL 14 1,471 - 169 - 0
WINDOW 1 16 1,700 0,811 225 1066 0
S EXPOSURE
WALL 7 1,471 - 62 - 0
WINDOW 1 4 1,700 0,811 56 199 0

Hourly Analysis Program v4.90 Page 6 of 12


Space Design Load Summary for A06-R1-Espace de travail D
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:27

TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' A06-R2-E.de travail D '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 32,6 °C / 27,0 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 75 m² 10318 - 75 m² - -
Wall Transmission 60 m² 864 - 60 m² 0 -
Roof Transmission 229 m² 8312 - 229 m² 0 -
Window Transmission 75 m² 1110 - 75 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 80 m² 365 - 80 m² 10 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 4580 W 4580 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 11450 W 11449 - 0 0 -
People 44 3159 2644 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 40156 2644 - 10 0

TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' A06-R2-E.de travail D '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 11 1,471 - 124 - 0
WINDOW 1 4 1,700 0,811 60 421 0
NW EXPOSURE
WALL 21 1,471 - 326 - 0
WINDOW 1 24 1,700 0,811 360 5260 0
NE EXPOSURE
WALL 2 1,471 - 48 - 0
WINDOW 1 20 1,700 0,811 300 2575 0
E EXPOSURE
WALL 5 1,471 - 108 - 0
WINDOW 1 6 1,700 0,811 89 715 0
SE EXPOSURE
WALL 14 1,471 - 189 - 0
WINDOW 1 16 1,700 0,811 240 1143 0
S EXPOSURE
WALL 7 1,471 - 68 - 0
WINDOW 1 4 1,700 0,811 60 202 0
H EXPOSURE
ROOF 229 1,137 - 8312 - 0

Hourly Analysis Program v4.90 Page 7 of 12


Hourly Air System Design Day Loads for A06-R1-Espace de travail D
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:27

DESIGN MONTH: JULY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 23,4 4628 54,7 58,8 0,0 0,0 0,0 0,0 0,0 0,0
0100 22,8 4520 53,4 57,5 0,0 0,0 0,0 0,0 0,0 0,0
0200 22,2 4417 52,1 56,2 0,0 0,0 0,0 0,0 0,0 0,0
0300 21,8 4324 50,9 55,0 0,0 0,0 0,0 0,0 0,0 0,0
0400 21,4 4240 49,9 54,0 0,0 0,0 0,0 0,0 0,0 0,0
0500 21,3 4163 48,9 53,0 0,0 0,0 0,0 0,0 0,0 0,0
0600 21,5 4208 49,5 53,7 0,0 0,0 0,0 0,0 0,0 0,0
0700 22,1 4572 54,0 58,2 0,0 0,0 0,0 0,0 0,0 0,0
0800 23,2 4764 56,4 60,7 0,0 0,0 0,0 0,0 0,0 0,0
0900 24,7 4887 58,0 62,3 0,0 0,0 0,0 0,0 0,0 0,0
1000 26,4 4969 59,0 63,3 0,0 0,0 0,0 0,0 0,0 0,0
1100 28,4 5041 60,0 64,2 0,0 0,0 0,0 0,0 0,0 0,0
1200 30,2 5179 61,7 65,9 0,0 0,0 0,0 0,0 0,0 0,0
1300 31,6 5391 64,4 68,6 0,0 0,0 0,0 0,0 0,0 0,0
1400 32,6 5614 67,3 71,5 0,0 0,0 0,0 0,0 0,0 0,0
1500 32,9 5788 69,6 73,8 0,0 0,0 0,0 0,0 0,0 0,0
1600 32,6 5868 70,6 74,9 0,0 0,0 0,0 0,0 0,0 0,0
1700 31,7 5767 69,3 73,4 0,0 0,0 0,0 0,0 0,0 0,0
1800 30,5 5449 65,2 69,4 0,0 0,0 0,0 0,0 0,0 0,0
1900 29,0 5313 63,4 67,5 0,0 0,0 0,0 0,0 0,0 0,0
2000 27,4 5162 61,5 65,7 0,0 0,0 0,0 0,0 0,0 0,0
2100 26,2 5015 59,6 63,8 0,0 0,0 0,0 0,0 0,0 0,0
2200 25,0 4875 57,8 62,0 0,0 0,0 0,0 0,0 0,0 0,0
2300 24,1 4746 56,2 60,4 0,0 0,0 0,0 0,0 0,0 0,0

Hourly Analysis Program v4.90 Page 8 of 12


Hourly Zone Loads for A06-R1-Espace de travail D
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:27

ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 23,4 22,6 52 4628,3 54946,6 54731,4 0,0 0,0 0,0
0100 22,8 22,6 52 4519,7 53522,6 53366,4 0,0 0,0 0,0
0200 22,2 22,6 52 4417,4 52191,1 52085,9 0,0 0,0 0,0
0300 21,8 22,5 52 4324,5 50989,1 50925,0 0,0 0,0 0,0
0400 21,4 22,5 52 4239,8 49900,4 49869,2 0,0 0,0 0,0
0500 21,3 22,5 53 4163,2 48923,8 48917,7 0,0 0,0 0,0
0600 21,5 22,5 53 4208,3 49552,1 49478,2 0,0 0,0 0,0
0700 22,1 22,6 52 4572,0 54398,7 54022,6 0,0 0,0 0,0
0800 23,2 22,6 52 4764,4 56965,2 56445,6 0,0 0,0 0,0
0900 24,7 22,6 52 4887,3 58608,8 58001,1 0,0 0,0 0,0
1000 26,4 22,6 52 4968,6 59692,8 59031,8 0,0 0,0 0,0
1100 28,4 22,6 52 5041,2 60660,9 59954,7 0,0 0,0 0,0
1200 30,2 22,7 52 5179,3 62514,9 61714,8 0,0 0,0 0,0
1300 31,6 22,7 51 5390,9 65370,6 64426,3 0,0 0,0 0,0
1400 32,6 22,7 51 5613,7 68385,5 67298,1 0,0 0,0 0,0
1500 32,9 22,7 51 5788,2 70743,9 69559,4 0,0 0,0 0,0
1600 32,6 22,8 51 5868,5 71807,0 70603,2 0,0 0,0 0,0
1700 31,7 22,7 51 5766,9 70363,5 69281,9 0,0 0,0 0,0
1800 30,5 22,7 51 5449,4 65982,9 65178,8 0,0 0,0 0,0
1900 29,0 22,7 52 5313,1 64121,7 63427,3 0,0 0,0 0,0
2000 27,4 22,7 52 5162,2 62070,3 61496,4 0,0 0,0 0,0
2100 26,2 22,6 52 5014,7 60081,3 59617,2 0,0 0,0 0,0
2200 25,0 22,6 52 4874,8 58209,2 57842,2 0,0 0,0 0,0
2300 24,1 22,6 52 4746,1 56498,9 56214,7 0,0 0,0 0,0

Hourly Analysis Program v4.90 Page 9 of 12


System Psychrometrics for A06-R1-Espace de travail D
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:27

July DESIGN COOLING DAY, 1600

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 32,6 0,02036 0 400 0 0
Vent - Return Mixing Outlet 22,8 0,00881 5868 2310 - -
Preheat Coil Outlet 22,8 0,00881 5868 2310 0 -
Central Cooling Coil Outlet 12,8 0,00857 5868 2310 70603 4264
Supply Fan Outlet 12,8 0,00857 5868 2310 0 -
Cold Supply Duct Outlet 12,8 0,00857 5868 2310 - -
Zone Air - 22,8 0,00881 5868 2310 70603 4193
Return Plenum Outlet 22,8 0,00881 5868 2310 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 71807 Cooling 70603 22,8 5868 2310 0 0

Hourly Analysis Program v4.90 Page 10 of 12


System Psychrometrics for A06-R1-Espace de travail D
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:27

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 22,0 0,01667 0 400 0 0
Vent - Return Mixing Outlet 20,7 0,00865 65 800 - -
Preheat Coil Outlet 20,7 0,00865 65 800 0 -
Central Cooling Coil Outlet 12,8 0,00865 65 800 614 0
Supply Fan Outlet 12,8 0,00865 65 800 0 -
Cold Supply Duct Outlet 12,8 0,00865 65 800 - -
Zone Air - 20,7 0,00865 65 800 603 0
Return Plenum Outlet 20,7 0,00865 65 800 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 -19 Heating 603 20,7 65 800 11 0

Hourly Analysis Program v4.90 Page 11 of 12


Psychrometric Analysis for A06-R1-Espace de travail D
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:27

Location: OUIDAH, BENIN


Altitude: 5,8 m.
Data for: July DESIGN COOLING DAY, 1600

1. Central Cooling Coil Outlet


2. Supply Fan Outlet
3. Room Air 0,024
0,022
0,020

Specific Humidity ( kg/kg )


0,018
0,016
0,014
0,012

12 3 0,010
0,008
0,006
0,004
0,002
0,000
0 5 10 15 20 25 30 35
Temperature ( °C )

Hourly Analysis Program v4.90 Page 12 of 12


Air System Sizing Summary for A06-R1-Espace de travail G
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:29

Air System Information


Air System Name ........... A06-R1-Espace de travail G Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area .............................................................. 458,8 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ....................................................... 75,2 kW Load occurs at ................................................. Oct 1600
Sensible coil load .................................................. 71,0 kW OA DB / WB ................................................... 30,3 / 25,9 °C
Coil L/s at Oct 1600 ............................................. 5899 L/s Entering DB / WB ........................................... 22,8 / 16,2 °C
Max block L/s at Oct 1600 ................................... 6492 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s .......................................... 6492 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,944 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 6,1 Resulting RH .............................................................. 51 %
W/m² .................................................................. 163,9 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K

Preheat Coil Sizing Data


No heating coil loads occurred during this calculation.

Supply Fan Sizing Data

Actual max L/s at Oct 1600 .................................. 6492 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ........................................................ 6488 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 14,15 L/(s-m²) Fan static ...................................................................... 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s ..................................................... 0 L/s L/s/person ................................................................ 0,00 L/s/person
L/(s-m²) ................................................................. 0,00 L/(s-m²)

Hourly Analysis Program v4.90 Page 1 of 12


Zone Sizing Summary for A06-R1-Espace de travail G
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:29

Air System Information


Air System Name ........... A06-R1-Espace de travail G Number of zones .......................................................... 1
Equipment Class ....................................... SPLT AHU Floor Area .............................................................. 458,8 m²
Air System Type .................................................. VAV Location ............................................... OUIDAH, BENIN

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 72,2 6492 65 Oct 1600 0,0 458,8 14,15

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
A06-R1-E.de travail G 1 32,2 Nov 1500 2890 0,0 229,4 12,60
A06-R2-E.de travail G 1 40,3 Oct 1600 3624 0,0 229,4 15,80

Hourly Analysis Program v4.90 Page 2 of 12


Ventilation Sizing Summary for A06-R1-Espace de travail G
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:29

1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 L/s

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (m²) Occupants (L/s) (L/s/person) (L/(s-m²)) (L/s) (% of supply) (L/s)
Zone 1
A06-R1-E.de travail G 1 229,4 44,0 2890,1 0,00 0,00 0,0 0,0 0,0
A06-R2-E.de travail G 1 229,4 44,0 3624,4 0,00 0,00 0,0 0,0 0,0
Totals (incl. Space Multipliers) 6514,5 0,0

Hourly Analysis Program v4.90 Page 3 of 12


Air System Design Load Summary for A06-R1-Espace de travail G
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:29

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Oct 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 30,3 °C / 25,9 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 154 m² 21405 - 154 m² - -
Wall Transmission 170 m² 2143 - 170 m² 0 -
Roof Transmission 229 m² 8224 - 229 m² 0 -
Window Transmission 154 m² 1697 - 154 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 159 m² 521 - 159 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 9176 W 9175 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 22940 W 22939 - 0 0 -
People 88 6125 4193 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 72229 4193 - 0 0
Zone Conditioning - 70964 4193 - -611 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 5899 L/s 0 - 65 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 5899 L/s 0 - 65 L/s 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 70964 4193 - -611 0
Central Cooling Coil - 70964 4230 - -611 0
Preheat Coil - 0 - - 0 -
Terminal Reheat Coils - 0 - - 0 -
>> Total Conditioning - 70964 4230 - -611 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 4 of 12


Zone Design Load Summary for A06-R1-Espace de travail G
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:29

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Oct 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 30,3 °C / 25,9 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 154 m² 21405 - 154 m² - -
Wall Transmission 170 m² 2143 - 170 m² 0 -
Roof Transmission 229 m² 8224 - 229 m² 0 -
Window Transmission 154 m² 1697 - 154 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 159 m² 521 - 159 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 9176 W 9175 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 22940 W 22939 - 0 0 -
People 88 6125 4193 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 72229 4193 - 0 0

Hourly Analysis Program v4.90 Page 5 of 12


Space Design Load Summary for A06-R1-Espace de travail G
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:29

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A06-R1-E.de travail G '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Nov 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 29,0 °C / 25,4 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 77 m² 11503 - 77 m² - -
Wall Transmission 85 m² 790 - 85 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 77 m² 644 - 77 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 80 m² 193 - 80 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 4588 W 4588 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 11470 W 11469 - 0 0 -
People 44 2966 1549 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 32153 1549 - 0 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A06-R1-E.de travail G '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 21 1,471 - 223 - 0
WINDOW 1 24 1,700 0,811 204 6149 0
NW EXPOSURE
WALL 22 1,471 - 85 - 0
WINDOW 1 4 1,700 0,811 34 296 0
N EXPOSURE
WALL 5 1,471 - 13 - 0
WINDOW 1 6 1,700 0,811 50 249 0
NE EXPOSURE
WALL 14 1,471 - 79 - 0
WINDOW 1 16 1,700 0,811 136 918 0
E EXPOSURE
WALL 5 1,471 - 77 - 0
WINDOW 1 6 1,700 0,811 50 729 0
SE EXPOSURE
WALL 17 1,471 - 313 - 0
WINDOW 1 20 1,700 0,811 170 3162 0

Hourly Analysis Program v4.90 Page 6 of 12


Space Design Load Summary for A06-R1-Espace de travail G
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:29

TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' A06-R2-E.de travail G '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Oct 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 30,3 °C / 25,9 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 77 m² 10703 - 77 m² - -
Wall Transmission 85 m² 1071 - 85 m² 0 -
Roof Transmission 229 m² 8224 - 229 m² 0 -
Window Transmission 77 m² 849 - 77 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 80 m² 260 - 80 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 4588 W 4588 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 11470 W 11469 - 0 0 -
People 44 3159 2644 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 40323 2644 - 0 0

TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' A06-R2-E.de travail G '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 21 1,471 - 271 - 0
WINDOW 1 24 1,700 0,811 268 5553 0
NW EXPOSURE
WALL 22 1,471 - 182 - 0
WINDOW 1 4 1,700 0,811 45 488 0
N EXPOSURE
WALL 5 1,471 - 30 - 0
WINDOW 1 6 1,700 0,811 66 248 0
NE EXPOSURE
WALL 14 1,471 - 154 - 0
WINDOW 1 16 1,700 0,811 179 1115 0
E EXPOSURE
WALL 5 1,471 - 99 - 0
WINDOW 1 6 1,700 0,811 66 723 0
SE EXPOSURE
WALL 17 1,471 - 336 - 0
WINDOW 1 20 1,700 0,811 224 2576 0
H EXPOSURE
ROOF 229 1,137 - 8224 - 0

Hourly Analysis Program v4.90 Page 7 of 12


Hourly Air System Design Day Loads for A06-R1-Espace de travail G
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:29

DESIGN MONTH: JULY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 23,4 4586 54,2 58,3 0,0 0,0 0,0 0,0 0,0 0,0
0100 22,8 4483 52,9 57,0 0,0 0,0 0,0 0,0 0,0 0,0
0200 22,2 4385 51,7 55,7 0,0 0,0 0,0 0,0 0,0 0,0
0300 21,8 4296 50,6 54,6 0,0 0,0 0,0 0,0 0,0 0,0
0400 21,4 4215 49,5 53,6 0,0 0,0 0,0 0,0 0,0 0,0
0500 21,3 4141 48,6 52,7 0,0 0,0 0,0 0,0 0,0 0,0
0600 21,5 4188 49,2 53,4 0,0 0,0 0,0 0,0 0,0 0,0
0700 22,1 4550 53,7 57,9 0,0 0,0 0,0 0,0 0,0 0,0
0800 23,2 4742 56,1 60,4 0,0 0,0 0,0 0,0 0,0 0,0
0900 24,7 4866 57,7 62,0 0,0 0,0 0,0 0,0 0,0 0,0
1000 26,4 4950 58,8 63,1 0,0 0,0 0,0 0,0 0,0 0,0
1100 28,4 5033 59,8 64,1 0,0 0,0 0,0 0,0 0,0 0,0
1200 30,2 5143 61,2 65,5 0,0 0,0 0,0 0,0 0,0 0,0
1300 31,6 5284 63,0 67,2 0,0 0,0 0,0 0,0 0,0 0,0
1400 32,6 5454 65,2 69,4 0,0 0,0 0,0 0,0 0,0 0,0
1500 32,9 5598 67,1 71,4 0,0 0,0 0,0 0,0 0,0 0,0
1600 32,6 5664 67,9 72,2 0,0 0,0 0,0 0,0 0,0 0,0
1700 31,7 5584 66,9 71,0 0,0 0,0 0,0 0,0 0,0 0,0
1800 30,5 5344 63,8 68,0 0,0 0,0 0,0 0,0 0,0 0,0
1900 29,0 5222 62,2 66,3 0,0 0,0 0,0 0,0 0,0 0,0
2000 27,4 5084 60,5 64,7 0,0 0,0 0,0 0,0 0,0 0,0
2100 26,2 4948 58,7 62,9 0,0 0,0 0,0 0,0 0,0 0,0
2200 25,0 4818 57,1 61,3 0,0 0,0 0,0 0,0 0,0 0,0
2300 24,1 4697 55,6 59,6 0,0 0,0 0,0 0,0 0,0 0,0

Hourly Analysis Program v4.90 Page 8 of 12


Hourly Zone Loads for A06-R1-Espace de travail G
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:29

ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 23,4 22,6 52 4585,9 54455,3 54177,4 0,0 0,0 0,0
0100 22,8 22,6 52 4482,9 53106,9 52886,3 0,0 0,0 0,0
0200 22,2 22,5 52 4385,4 51837,7 51667,1 0,0 0,0 0,0
0300 21,8 22,5 52 4296,4 50687,1 50557,4 0,0 0,0 0,0
0400 21,4 22,5 53 4215,0 49641,0 49544,4 0,0 0,0 0,0
0500 21,3 22,5 53 4141,3 48700,0 48629,2 0,0 0,0 0,0
0600 21,5 22,5 53 4187,8 49344,5 49206,7 0,0 0,0 0,0
0700 22,1 22,6 52 4549,9 54165,1 53725,9 0,0 0,0 0,0
0800 23,2 22,6 52 4741,9 56723,1 56141,0 0,0 0,0 0,0
0900 24,7 22,6 52 4866,0 58377,8 57707,6 0,0 0,0 0,0
1000 26,4 22,6 52 4950,2 59500,3 58775,3 0,0 0,0 0,0
1100 28,4 22,6 52 5033,3 60606,6 59829,3 0,0 0,0 0,0
1200 30,2 22,6 52 5142,9 62072,8 61225,1 0,0 0,0 0,0
1300 31,6 22,7 52 5284,0 63965,5 63027,2 0,0 0,0 0,0
1400 32,6 22,7 51 5453,7 66250,7 65205,0 0,0 0,0 0,0
1500 32,9 22,7 51 5598,3 68194,3 67067,5 0,0 0,0 0,0
1600 32,6 22,7 51 5664,0 69058,4 67916,5 0,0 0,0 0,0
1700 31,7 22,7 51 5583,6 67921,0 66877,8 0,0 0,0 0,0
1800 30,5 22,7 52 5344,2 64628,6 63798,4 0,0 0,0 0,0
1900 29,0 22,7 52 5222,4 62968,7 62239,4 0,0 0,0 0,0
2000 27,4 22,6 52 5084,3 61096,4 60478,8 0,0 0,0 0,0
2100 26,2 22,6 52 4948,0 59261,3 58746,3 0,0 0,0 0,0
2200 25,0 22,6 52 4817,5 57518,5 57095,4 0,0 0,0 0,0
2300 24,1 22,6 52 4696,8 55916,8 55572,6 0,0 0,0 0,0

Hourly Analysis Program v4.90 Page 9 of 12


System Psychrometrics for A06-R1-Espace de travail G
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:29

October DESIGN COOLING DAY, 1600

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 30,3 0,01934 0 400 0 0
Vent - Return Mixing Outlet 22,8 0,00881 5899 2302 - -
Preheat Coil Outlet 22,8 0,00881 5899 2302 0 -
Central Cooling Coil Outlet 12,8 0,00857 5899 2302 70964 4230
Supply Fan Outlet 12,8 0,00857 5899 2302 0 -
Cold Supply Duct Outlet 12,8 0,00857 5899 2302 - -
Zone Air - 22,8 0,00881 5899 2302 70964 4193
Return Plenum Outlet 22,8 0,00881 5899 2302 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 72229 Cooling 70964 22,8 5899 2302 0 0

Hourly Analysis Program v4.90 Page 10 of 12


System Psychrometrics for A06-R1-Espace de travail G
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:29

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 22,0 0,01667 0 400 0 0
Vent - Return Mixing Outlet 20,6 0,00866 65 800 - -
Preheat Coil Outlet 20,6 0,00866 65 800 0 -
Central Cooling Coil Outlet 12,8 0,00866 65 800 611 0
Supply Fan Outlet 12,8 0,00866 65 800 0 -
Cold Supply Duct Outlet 12,8 0,00866 65 800 - -
Zone Air - 20,6 0,00866 65 800 611 0
Return Plenum Outlet 20,6 0,00866 65 800 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 0 Heating 611 20,6 65 800 0 0

Hourly Analysis Program v4.90 Page 11 of 12


Psychrometric Analysis for A06-R1-Espace de travail G
Project Name: A06 01/08/2024
Prepared by: ATOMAS 04:29

Location: OUIDAH, BENIN


Altitude: 5,8 m.
Data for: October DESIGN COOLING DAY, 1600
0,020
1. Central Cooling Coil Outlet
2. Supply Fan Outlet
3. Room Air
0,018

0,016

Specific Humidity ( kg/kg )


0,014

0,012

0,010
12 3

0,008

0,006

0,004

0,002

0,000
0 5 10 15 20 25 30 35
Temperature ( °C )

Hourly Analysis Program v4.90 Page 12 of 12

You might also like