Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
Total coil load ....................................................... 16,3 kW Load occurs at ................................................. Jun 1600
Sensible coil load .................................................. 16,0 kW OA DB / WB ................................................... 32,0 / 27,0 °C
Coil L/s at Jun 1600 ............................................. 1328 L/s Entering DB / WB ........................................... 22,8 / 16,1 °C
Max block L/s at Jun 1600 ................................... 1456 L/s Leaving DB / WB ........................................... 12,8 / 12,1 °C
Sum of peak zone L/s .......................................... 1456 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,978 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 4,3 Resulting RH .............................................................. 50 %
W/m² .................................................................. 233,4 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K
Actual max L/s at Jun 1600 .................................. 1456 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ........................................................ 1455 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 20,80 L/(s-m²) Fan static ...................................................................... 0 Pa
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 L/s
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A06-RDC-Commerce 1 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 32,0 °C / 27,0 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 49 m² 9440 - 49 m² - -
Wall Transmission 23 m² 409 - 23 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 49 m² 675 - 49 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 70 m² 0 - 70 m² 0 -
Partitions 23 m² 99 - 23 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1400 W 1400 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 3500 W 3500 - 0 0 -
People 10 674 352 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 16197 352 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A06-RDC-Commerce 1 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NW EXPOSURE
WALL 16 1,471 - 242 - 0
WINDOW 1 32 1,700 0,811 450 7299 0
NE EXPOSURE
WALL 8 1,471 - 168 - 0
WINDOW 1 16 1,700 0,811 225 2141 0
ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 23,4 22,5 51 900,0 10563,8 10550,4 0,0 0,0 0,0
0100 22,8 22,5 51 873,3 10227,9 10220,1 0,0 0,0 0,0
0200 22,2 22,5 51 847,5 9905,5 9902,4 0,0 0,0 0,0
0300 21,8 22,4 52 823,4 9606,9 9607,2 0,0 0,0 0,0
0400 21,4 22,4 52 801,0 9330,7 9333,4 0,0 0,0 0,0
0500 21,3 22,4 52 780,6 9081,1 9085,1 0,0 0,0 0,0
0600 21,5 22,4 52 792,8 9243,6 9232,8 0,0 0,0 0,0
0700 22,1 22,5 51 890,7 10501,2 10434,7 0,0 0,0 0,0
0800 23,2 22,5 51 944,0 11187,5 11095,2 0,0 0,0 0,0
0900 24,7 22,5 51 976,8 11609,9 11504,3 0,0 0,0 0,0
1000 26,4 22,6 51 994,7 11838,4 11727,9 0,0 0,0 0,0
1100 28,4 22,6 51 1000,7 11911,2 11802,1 0,0 0,0 0,0
1200 30,2 22,6 51 1036,7 12377,6 12254,0 0,0 0,0 0,0
1300 31,6 22,6 51 1112,2 13364,0 13207,4 0,0 0,0 0,0
1400 32,6 22,7 50 1198,0 14493,2 14301,9 0,0 0,0 0,0
1500 32,9 22,7 50 1268,8 15427,0 15212,4 0,0 0,0 0,0
1600 32,6 22,7 50 1304,1 15887,9 15670,5 0,0 0,0 0,0
1700 31,7 22,7 50 1254,6 15205,7 15029,9 0,0 0,0 0,0
1800 30,5 22,6 51 1095,5 13079,3 12995,7 0,0 0,0 0,0
1900 29,0 22,6 51 1059,1 12604,6 12536,3 0,0 0,0 0,0
2000 27,4 22,6 51 1024,0 12147,7 12094,8 0,0 0,0 0,0
2100 26,2 22,5 51 990,7 11717,7 11677,6 0,0 0,0 0,0
2200 25,0 22,5 51 958,6 11306,0 11276,8 0,0 0,0 0,0
2300 24,1 22,5 51 928,3 10921,2 10900,8 0,0 0,0 0,0
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
12 3
0,010
0,008
0,006
0,004
0,002
0,000
0 5 10 15 20 25 30 35
Temperature ( °C )
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
Total coil load ....................................................... 26,0 kW Load occurs at ................................................. Dec 1600
Sensible coil load .................................................. 25,6 kW OA DB / WB ................................................... 27,6 / 24,2 °C
Coil L/s at Dec 1600 ............................................ 2130 L/s Entering DB / WB ........................................... 22,8 / 16,0 °C
Max block L/s at Dec 1600 ................................... 2337 L/s Leaving DB / WB ........................................... 12,8 / 12,1 °C
Sum of peak zone L/s .......................................... 2337 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,986 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 4,1 Resulting RH .............................................................. 50 %
W/m² .................................................................. 245,2 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K
Actual max L/s at Dec 1600 ................................. 2337 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ........................................................ 2335 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 22,04 L/(s-m²) Fan static ...................................................................... 0 Pa
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 L/s
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A06-RDC-Hall d'acceuil 1 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 27,6 °C / 24,2 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 81 m² 16933 - 81 m² - -
Wall Transmission 39 m² 418 - 39 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 81 m² 512 - 81 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 106 m² 0 - 106 m² 0 -
Partitions 23 m² 40 - 23 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 2120 W 2120 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 5300 W 5300 - 0 0 -
People 10 674 352 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 25997 352 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A06-RDC-Hall d'acceuil 1 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NW EXPOSURE
WALL 8 1,471 - 17 - 0
WINDOW 1 16 1,700 0,811 102 1129 0
SW EXPOSURE
WALL 23 1,471 - 261 - 0
WINDOW 1 49 1,700 0,811 307 13335 0
SE EXPOSURE
WALL 8 1,471 - 140 - 0
WINDOW 1 16 1,700 0,811 102 2468 0
ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 23,4 22,4 51 1164,4 13536,1 13506,6 0,0 0,0 0,0
0100 22,8 22,4 52 1134,2 13164,3 13141,0 0,0 0,0 0,0
0200 22,2 22,4 52 1104,8 12804,5 12786,5 0,0 0,0 0,0
0300 21,8 22,4 52 1077,4 12471,3 12457,3 0,0 0,0 0,0
0400 21,4 22,4 52 1052,1 12164,0 12152,9 0,0 0,0 0,0
0500 21,3 22,3 52 1029,5 11891,5 11881,8 0,0 0,0 0,0
0600 21,5 22,3 52 1030,3 11910,4 11891,3 0,0 0,0 0,0
0700 22,1 22,4 52 1099,9 12786,2 12727,3 0,0 0,0 0,0
0800 23,2 22,4 51 1146,4 13370,8 13288,4 0,0 0,0 0,0
0900 24,7 22,4 51 1180,5 13799,6 13701,5 0,0 0,0 0,0
1000 26,4 22,4 51 1207,5 14137,3 14028,4 0,0 0,0 0,0
1100 28,4 22,4 51 1241,8 14567,8 14445,7 0,0 0,0 0,0
1200 30,2 22,4 51 1298,3 15279,9 15135,4 0,0 0,0 0,0
1300 31,6 22,5 51 1367,4 16152,4 15982,1 0,0 0,0 0,0
1400 32,6 22,5 51 1472,5 17490,3 17279,6 0,0 0,0 0,0
1500 32,9 22,5 51 1579,2 18853,3 18605,8 0,0 0,0 0,0
1600 32,6 22,6 51 1637,9 19598,2 19340,7 0,0 0,0 0,0
1700 31,7 22,5 51 1580,5 18833,5 18622,2 0,0 0,0 0,0
1800 30,5 22,5 51 1388,0 16343,7 16236,0 0,0 0,0 0,0
1900 29,0 22,5 51 1346,4 15814,7 15723,9 0,0 0,0 0,0
2000 27,4 22,4 51 1305,9 15302,1 15228,5 0,0 0,0 0,0
2100 26,2 22,4 51 1267,8 14821,8 14762,5 0,0 0,0 0,0
2200 25,0 22,4 51 1230,9 14360,6 14313,5 0,0 0,0 0,0
2300 24,1 22,4 51 1196,4 13931,7 13894,3 0,0 0,0 0,0
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
0,016
0,012
0,010
12 3
0,008
0,006
0,004
0,002
0,000
0 5 10 15 20 25 30 35
Temperature ( °C )
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
Total coil load ....................................................... 14,0 kW Load occurs at ................................................. Nov 0900
Sensible coil load .................................................. 13,6 kW OA DB / WB ................................................... 20,8 / 20,5 °C
Coil L/s at Nov 0900 ............................................ 1132 L/s Entering DB / WB ........................................... 22,8 / 16,1 °C
Max block L/s at Nov 0900 ................................... 1246 L/s Leaving DB / WB ........................................... 12,8 / 12,1 °C
Sum of peak zone L/s .......................................... 1246 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,975 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 4,9 Resulting RH .............................................................. 50 %
W/m² .................................................................. 206,1 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K
Actual max L/s at Nov 0900 ................................. 1246 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ........................................................ 1245 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 18,37 L/(s-m²) Fan static ...................................................................... 0 Pa
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 L/s
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A06-RDC-Commerce 3 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Nov 0900 HEATING DATA AT DES HTG
COOLING OA DB / WB 20,8 °C / 20,5 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 44 m² 8372 - 44 m² - -
Wall Transmission 20 m² 170 - 20 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 44 m² -86 - 44 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 68 m² 0 - 68 m² 0 -
Partitions 23 m² -19 - 23 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1356 W 1356 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 3390 W 3390 - 0 0 -
People 10 674 352 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 13857 352 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A06-RDC-Commerce 3 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NE EXPOSURE
WALL 4 1,471 - 15 - 0
WINDOW 1 8 1,700 0,811 -16 459 0
E EXPOSURE
WALL 6 1,471 - 47 - 0
WINDOW 1 12 1,700 0,811 -23 2329 0
SE EXPOSURE
WALL 11 1,471 - 108 - 0
WINDOW 1 24 1,700 0,811 -47 5584 0
ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 23,4 22,5 52 706,8 8258,3 8248,2 0,0 0,0 0,0
0100 22,8 22,4 52 690,5 8056,9 8049,3 0,0 0,0 0,0
0200 22,2 22,4 52 674,8 7862,7 7857,1 0,0 0,0 0,0
0300 21,8 22,4 52 660,3 7685,1 7680,7 0,0 0,0 0,0
0400 21,4 22,4 52 647,0 7522,9 7519,1 0,0 0,0 0,0
0500 21,3 22,4 52 635,2 7379,8 7375,9 0,0 0,0 0,0
0600 21,5 22,4 52 675,9 7904,3 7871,0 0,0 0,0 0,0
0700 22,1 22,6 51 852,5 10187,7 10051,9 0,0 0,0 0,0
0800 23,2 22,6 51 935,8 11272,3 11100,3 0,0 0,0 0,0
0900 24,7 22,6 51 966,4 11664,0 11488,0 0,0 0,0 0,0
1000 26,4 22,6 51 957,7 11535,0 11377,0 0,0 0,0 0,0
1100 28,4 22,6 51 936,8 11249,1 11113,0 0,0 0,0 0,0
1200 30,2 22,6 51 926,1 11099,9 10976,9 0,0 0,0 0,0
1300 31,6 22,6 51 926,4 11098,3 10980,7 0,0 0,0 0,0
1400 32,6 22,6 51 924,7 11071,3 10959,7 0,0 0,0 0,0
1500 32,9 22,6 51 915,6 10946,6 10844,6 0,0 0,0 0,0
1600 32,6 22,6 51 897,4 10704,2 10615,7 0,0 0,0 0,0
1700 31,7 22,6 51 868,0 10316,8 10246,6 0,0 0,0 0,0
1800 30,5 22,5 51 831,2 9836,4 9786,3 0,0 0,0 0,0
1900 29,0 22,5 51 807,8 9534,9 9494,9 0,0 0,0 0,0
2000 27,4 22,5 51 784,9 9241,6 9210,5 0,0 0,0 0,0
2100 26,2 22,5 51 763,5 8969,5 8945,6 0,0 0,0 0,0
2200 25,0 22,5 52 743,0 8711,4 8693,5 0,0 0,0 0,0
2300 24,1 22,5 52 724,1 8474,4 8461,0 0,0 0,0 0,0
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
0,016
0,012
0,010
12 3
0,008
0,006
0,004
0,002
0,000
0 5 10 15 20 25 30 35
Temperature ( °C )
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
Total coil load ....................................................... 22,8 kW Load occurs at ................................................. Jun 1600
Sensible coil load .................................................. 22,5 kW OA DB / WB ................................................... 32,0 / 27,0 °C
Coil L/s at Jun 1600 ............................................. 1867 L/s Entering DB / WB ........................................... 22,8 / 16,0 °C
Max block L/s at Jun 1600 ................................... 2049 L/s Leaving DB / WB ........................................... 12,8 / 12,1 °C
Sum of peak zone L/s .......................................... 2049 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,984 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 4,6 Resulting RH .............................................................. 50 %
W/m² .................................................................. 216,7 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K
Actual max L/s at Jun 1600 .................................. 2049 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ........................................................ 2048 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 19,44 L/(s-m²) Fan static ...................................................................... 0 Pa
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 L/s
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A06-RDC-Commerce 4 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 32,0 °C / 27,0 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 73 m² 12966 - 73 m² - -
Wall Transmission 47 m² 770 - 47 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 73 m² 1012 - 73 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 105 m² 0 - 105 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 2108 W 2108 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 5270 W 5270 - 0 0 -
People 10 674 352 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 22799 352 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A06-RDC-Commerce 4 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NW EXPOSURE
WALL 23 1,471 - 363 - 0
WINDOW 1 49 1,700 0,811 675 10948 0
E EXPOSURE
WALL 16 1,471 - 311 - 0
WINDOW 1 8 1,700 0,811 112 951 0
SE EXPOSURE
WALL 8 1,471 - 96 - 0
WINDOW 1 16 1,700 0,811 225 1066 0
ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 23,4 22,5 51 1289,0 15143,1 15124,0 0,0 0,0 0,0
0100 22,8 22,5 51 1252,4 14682,5 14672,0 0,0 0,0 0,0
0200 22,2 22,5 51 1217,0 14238,9 14235,7 0,0 0,0 0,0
0300 21,8 22,5 51 1183,6 13822,4 13824,7 0,0 0,0 0,0
0400 21,4 22,4 51 1152,2 13433,2 13439,6 0,0 0,0 0,0
0500 21,3 22,4 51 1123,6 13081,2 13090,0 0,0 0,0 0,0
0600 21,5 22,4 51 1129,5 13168,7 13161,8 0,0 0,0 0,0
0700 22,1 22,5 51 1230,2 14468,4 14398,1 0,0 0,0 0,0
0800 23,2 22,5 51 1283,7 15158,2 15058,5 0,0 0,0 0,0
0900 24,7 22,5 51 1311,2 15511,9 15398,9 0,0 0,0 0,0
1000 26,4 22,5 51 1322,3 15654,1 15537,5 0,0 0,0 0,0
1100 28,4 22,5 51 1335,7 15824,7 15703,3 0,0 0,0 0,0
1200 30,2 22,6 51 1414,8 16851,6 16690,4 0,0 0,0 0,0
1300 31,6 22,6 51 1543,7 18536,3 18313,6 0,0 0,0 0,0
1400 32,6 22,7 50 1678,6 20312,2 20031,5 0,0 0,0 0,0
1500 32,9 22,7 50 1790,5 21793,4 21473,0 0,0 0,0 0,0
1600 32,6 22,7 50 1849,3 22562,4 22234,9 0,0 0,0 0,0
1700 31,7 22,7 50 1781,4 21619,6 21355,2 0,0 0,0 0,0
1800 30,5 22,6 51 1549,9 18513,6 18392,1 0,0 0,0 0,0
1900 29,0 22,6 51 1501,9 17884,8 17785,1 0,0 0,0 0,0
2000 27,4 22,6 51 1455,5 17278,3 17200,9 0,0 0,0 0,0
2100 26,2 22,6 51 1411,2 16704,0 16645,3 0,0 0,0 0,0
2200 25,0 22,5 51 1368,2 16150,8 16108,1 0,0 0,0 0,0
2300 24,1 22,5 51 1327,4 15630,1 15600,5 0,0 0,0 0,0
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
12 3
0,010
0,008
0,006
0,004
0,002
0,000
0 5 10 15 20 25 30 35
Temperature ( °C )
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
Total coil load ....................................................... 13,6 kW Load occurs at ................................................. Jun 0900
Sensible coil load .................................................. 13,2 kW OA DB / WB ................................................... 24,1 / 23,8 °C
Coil L/s at Jun 0900 ............................................. 1098 L/s Entering DB / WB ........................................... 22,8 / 16,1 °C
Max block L/s at Jun 0900 ................................... 1206 L/s Leaving DB / WB ........................................... 12,8 / 12,1 °C
Sum of peak zone L/s .......................................... 1206 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,974 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 5,0 Resulting RH .............................................................. 50 %
W/m² .................................................................. 199,7 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K
Actual max L/s at Jun 0900 .................................. 1206 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ........................................................ 1205 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 17,76 L/(s-m²) Fan static ...................................................................... 0 Pa
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 L/s
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A06-RDC-Commerce 5 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 0900 HEATING DATA AT DES HTG
COOLING OA DB / WB 24,1 °C / 23,8 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 44 m² 7560 - 44 m² - -
Wall Transmission 20 m² 263 - 20 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 44 m² 165 - 44 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 68 m² 0 - 68 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1358 W 1358 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 3395 W 3395 - 0 0 -
People 10 674 352 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 13415 352 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A06-RDC-Commerce 5 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NE EXPOSURE
WALL 11 1,471 - 148 - 0
WINDOW 1 24 1,700 0,811 90 4766 0
E EXPOSURE
WALL 6 1,471 - 78 - 0
WINDOW 1 12 1,700 0,811 45 2200 0
SE EXPOSURE
WALL 4 1,471 - 37 - 0
WINDOW 1 8 1,700 0,811 30 594 0
ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 23,4 22,5 51 753,3 8828,5 8835,8 0,0 0,0 0,0
0100 22,8 22,5 52 734,8 8596,8 8606,4 0,0 0,0 0,0
0200 22,2 22,5 52 716,9 8374,7 8386,1 0,0 0,0 0,0
0300 21,8 22,5 52 700,2 8168,0 8180,5 0,0 0,0 0,0
0400 21,4 22,5 52 684,6 7976,4 7989,4 0,0 0,0 0,0
0500 21,3 22,4 52 670,6 7805,8 7818,5 0,0 0,0 0,0
0600 21,5 22,5 52 723,0 8486,4 8461,4 0,0 0,0 0,0
0700 22,1 22,6 51 943,2 11373,2 11218,7 0,0 0,0 0,0
0800 23,2 22,7 50 1048,3 12766,9 12566,3 0,0 0,0 0,0
0900 24,7 22,7 50 1093,9 13367,9 13158,7 0,0 0,0 0,0
1000 26,4 22,7 50 1092,5 13330,0 13139,6 0,0 0,0 0,0
1100 28,4 22,7 50 1058,6 12855,3 12699,7 0,0 0,0 0,0
1200 30,2 22,7 50 1024,3 12383,0 12257,4 0,0 0,0 0,0
1300 31,6 22,7 51 1011,0 12197,8 12086,1 0,0 0,0 0,0
1400 32,6 22,7 51 1002,8 12083,0 11981,0 0,0 0,0 0,0
1500 32,9 22,7 51 988,2 11882,2 11792,6 0,0 0,0 0,0
1600 32,6 22,7 51 965,7 11579,3 11505,1 0,0 0,0 0,0
1700 31,7 22,6 51 932,6 11139,1 11084,4 0,0 0,0 0,0
1800 30,5 22,6 51 892,8 10613,6 10580,0 0,0 0,0 0,0
1900 29,0 22,6 51 866,6 10272,8 10249,7 0,0 0,0 0,0
2000 27,4 22,6 51 841,2 9943,6 9929,7 0,0 0,0 0,0
2100 26,2 22,5 51 817,2 9636,6 9630,1 0,0 0,0 0,0
2200 25,0 22,5 51 794,4 9345,6 9345,1 0,0 0,0 0,0
2300 24,1 22,5 51 773,1 9076,4 9080,4 0,0 0,0 0,0
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
0,016
0,012
0,010
12 3
0,008
0,006
0,004
0,002
0,000
0 5 10 15 20 25 30 35
Temperature ( °C )
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
Total coil load ....................................................... 24,2 kW Load occurs at ................................................. Dec 1500
Sensible coil load .................................................. 23,8 kW OA DB / WB ................................................... 27,9 / 24,3 °C
Coil L/s at Dec 1500 ............................................ 1978 L/s Entering DB / WB ........................................... 22,8 / 16,0 °C
Max block L/s at Dec 1500 ................................... 2165 L/s Leaving DB / WB ........................................... 12,8 / 12,1 °C
Sum of peak zone L/s .......................................... 2165 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,985 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 5,5 Resulting RH .............................................................. 50 %
W/m² .................................................................. 180,5 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K
Actual max L/s at Dec 1500 ................................. 2165 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ........................................................ 2163 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 16,17 L/(s-m²) Fan static ...................................................................... 0 Pa
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 L/s
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A06-RDC-Commerce 6 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 27,9 °C / 24,3 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 61 m² 13246 - 61 m² - -
Wall Transmission 29 m² 400 - 29 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 61 m² 394 - 61 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 134 m² 0 - 134 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 2678 W 2678 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 6695 W 6695 - 0 0 -
People 10 674 352 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 24086 352 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A06-RDC-Commerce 6 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 10 1,471 - 97 - 0
WINDOW 1 24 1,700 0,811 158 6353 0
S EXPOSURE
WALL 6 1,471 - 95 - 0
WINDOW 1 12 1,700 0,811 78 2917 0
SE EXPOSURE
WALL 13 1,471 - 208 - 0
WINDOW 1 24 1,700 0,811 158 3976 0
ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 23,4 22,4 51 1124,1 13073,9 13062,4 0,0 0,0 0,0
0100 22,8 22,4 51 1107,1 12864,4 12856,3 0,0 0,0 0,0
0200 22,2 22,4 51 1090,5 12661,0 12655,7 0,0 0,0 0,0
0300 21,8 22,4 52 1075,1 12471,8 12468,4 0,0 0,0 0,0
0400 21,4 22,4 52 1060,7 12297,1 12294,9 0,0 0,0 0,0
0500 21,3 22,4 52 1048,2 12145,3 12143,1 0,0 0,0 0,0
0600 21,5 22,4 52 1060,0 12302,4 12286,1 0,0 0,0 0,0
0700 22,1 22,4 51 1141,1 13338,5 13269,5 0,0 0,0 0,0
0800 23,2 22,4 51 1187,1 13923,4 13830,0 0,0 0,0 0,0
0900 24,7 22,4 51 1211,6 14233,1 14130,1 0,0 0,0 0,0
1000 26,4 22,4 51 1222,8 14370,1 14266,1 0,0 0,0 0,0
1100 28,4 22,5 51 1242,3 14616,1 14505,8 0,0 0,0 0,0
1200 30,2 22,5 51 1266,0 14914,4 14796,1 0,0 0,0 0,0
1300 31,6 22,5 51 1286,1 15167,4 15044,2 0,0 0,0 0,0
1400 32,6 22,5 51 1318,8 15582,6 15447,3 0,0 0,0 0,0
1500 32,9 22,5 51 1351,1 15991,1 15845,6 0,0 0,0 0,0
1600 32,6 22,5 51 1362,3 16127,2 15985,1 0,0 0,0 0,0
1700 31,7 22,5 51 1329,4 15691,0 15578,1 0,0 0,0 0,0
1800 30,5 22,5 51 1252,1 14687,9 14626,0 0,0 0,0 0,0
1900 29,0 22,5 51 1228,1 14382,2 14332,1 0,0 0,0 0,0
2000 27,4 22,4 51 1204,7 14084,1 14045,4 0,0 0,0 0,0
2100 26,2 22,4 51 1182,8 13806,9 13777,4 0,0 0,0 0,0
2200 25,0 22,4 51 1161,7 13541,8 13520,0 0,0 0,0 0,0
2300 24,1 22,4 51 1142,1 13297,4 13281,5 0,0 0,0 0,0
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
0,016
0,012
0,010
12 3
0,008
0,006
0,004
0,002
0,000
0 5 10 15 20 25 30 35
Temperature ( °C )
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
Total coil load ....................................................... 15,0 kW Load occurs at ................................................. Jun 1600
Sensible coil load .................................................. 14,6 kW OA DB / WB ................................................... 32,0 / 27,0 °C
Coil L/s at Jun 1600 ............................................. 1217 L/s Entering DB / WB ........................................... 22,8 / 16,1 °C
Max block L/s at Jun 1600 ................................... 1333 L/s Leaving DB / WB ........................................... 12,8 / 12,1 °C
Sum of peak zone L/s .......................................... 1333 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,976 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 4,5 Resulting RH .............................................................. 50 %
W/m² .................................................................. 221,1 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K
Actual max L/s at Jun 1600 .................................. 1333 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ........................................................ 1332 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 19,63 L/(s-m²) Fan static ...................................................................... 0 Pa
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 L/s
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A06-RDC-Commerce 8 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 32,0 °C / 27,0 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 44 m² 8429 - 44 m² - -
Wall Transmission 20 m² 360 - 20 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 44 m² 616 - 44 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 68 m² 0 - 68 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1358 W 1358 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 3395 W 3395 - 0 0 -
People 10 674 352 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 14832 352 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A06-RDC-Commerce 8 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NW EXPOSURE
WALL 11 1,471 - 163 - 0
WINDOW 1 24 1,700 0,811 337 5474 0
N EXPOSURE
WALL 6 1,471 - 113 - 0
WINDOW 1 12 1,700 0,811 167 1884 0
NE EXPOSURE
WALL 4 1,471 - 84 - 0
WINDOW 1 8 1,700 0,811 112 1071 0
ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 23,4 22,5 51 833,0 9771,5 9770,3 0,0 0,0 0,0
0100 22,8 22,5 51 810,0 9483,1 9486,6 0,0 0,0 0,0
0200 22,2 22,5 52 787,9 9206,8 9214,1 0,0 0,0 0,0
0300 21,8 22,5 52 767,1 8948,3 8958,4 0,0 0,0 0,0
0400 21,4 22,4 52 747,6 8707,7 8719,8 0,0 0,0 0,0
0500 21,3 22,4 52 730,0 8490,7 8503,7 0,0 0,0 0,0
0600 21,5 22,4 52 737,4 8593,3 8594,6 0,0 0,0 0,0
0700 22,1 22,5 51 810,8 9538,4 9496,0 0,0 0,0 0,0
0800 23,2 22,5 51 852,1 10070,1 10006,7 0,0 0,0 0,0
0900 24,7 22,5 51 880,9 10441,4 10365,0 0,0 0,0 0,0
1000 26,4 22,5 51 901,9 10711,5 10627,4 0,0 0,0 0,0
1100 28,4 22,6 51 917,3 10907,7 10819,4 0,0 0,0 0,0
1200 30,2 22,6 51 956,4 11414,4 11309,8 0,0 0,0 0,0
1300 31,6 22,6 51 1021,8 12269,3 12136,5 0,0 0,0 0,0
1400 32,6 22,7 51 1092,8 13202,3 13041,8 0,0 0,0 0,0
1500 32,9 22,7 50 1151,3 13973,6 13794,8 0,0 0,0 0,0
1600 32,6 22,7 50 1180,5 14352,6 14172,7 0,0 0,0 0,0
1700 31,7 22,7 50 1137,7 13761,6 13618,8 0,0 0,0 0,0
1800 30,5 22,6 51 999,9 11920,2 11859,1 0,0 0,0 0,0
1900 29,0 22,6 51 968,9 11515,0 11467,0 0,0 0,0 0,0
2000 27,4 22,6 51 939,0 11125,5 11090,7 0,0 0,0 0,0
2100 26,2 22,6 51 910,5 10758,4 10734,6 0,0 0,0 0,0
2200 25,0 22,5 51 883,1 10407,0 10392,5 0,0 0,0 0,0
2300 24,1 22,5 51 857,3 10077,9 10070,8 0,0 0,0 0,0
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
12 3
0,010
0,008
0,006
0,004
0,002
0,000
0 5 10 15 20 25 30 35
Temperature ( °C )
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
Total coil load ........................................................ 8,7 kW Load occurs at ................................................. Jun 1000
Sensible coil load ................................................... 8,4 kW OA DB / WB ................................................... 25,8 / 25,5 °C
Coil L/s at Jun 1000 .............................................. 697 L/s Entering DB / WB ........................................... 22,8 / 16,1 °C
Max block L/s at Jun 1000 .................................... 763 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s ........................................... 763 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,959 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 7,2 Resulting RH .............................................................. 51 %
W/m² .................................................................. 138,5 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K
Actual max L/s at Jun 1000 ................................... 763 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ......................................................... 762 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 12,09 L/(s-m²) Fan static ...................................................................... 0 Pa
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 L/s
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A06-RDC-Commerce 9 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1000 HEATING DATA AT DES HTG
COOLING OA DB / WB 25,8 °C / 25,5 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 16 m² 3191 - 16 m² - -
Wall Transmission 8 m² 111 - 8 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 16 m² 93 - 16 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 63 m² 0 - 63 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1262 W 1262 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 3155 W 3155 - 0 0 -
People 10 674 352 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 8486 352 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A06-RDC-Commerce 9 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NE EXPOSURE
WALL 8 1,471 - 111 - 0
WINDOW 1 16 1,700 0,811 93 3191 0
ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 23,4 22,6 52 548,0 6468,1 6480,8 0,0 0,0 0,0
0100 22,8 22,6 52 540,6 6375,0 6388,6 0,0 0,0 0,0
0200 22,2 22,6 52 533,6 6285,9 6300,1 0,0 0,0 0,0
0300 21,8 22,6 52 527,0 6202,9 6217,3 0,0 0,0 0,0
0400 21,4 22,6 52 520,8 6125,8 6140,1 0,0 0,0 0,0
0500 21,3 22,5 52 515,3 6056,9 6070,7 0,0 0,0 0,0
0600 21,5 22,6 52 535,4 6329,0 6322,4 0,0 0,0 0,0
0700 22,1 22,7 51 620,6 7477,3 7401,8 0,0 0,0 0,0
0800 23,2 22,7 51 662,6 8041,9 7941,9 0,0 0,0 0,0
0900 24,7 22,7 51 683,3 8317,3 8211,3 0,0 0,0 0,0
1000 26,4 22,7 51 687,2 8359,8 8261,4 0,0 0,0 0,0
1100 28,4 22,7 51 676,4 8202,4 8121,9 0,0 0,0 0,0
1200 30,2 22,7 51 658,8 7953,7 7893,8 0,0 0,0 0,0
1300 31,6 22,7 51 650,2 7831,5 7782,2 0,0 0,0 0,0
1400 32,6 22,7 51 646,0 7771,7 7728,3 0,0 0,0 0,0
1500 32,9 22,7 51 639,6 7682,3 7646,0 0,0 0,0 0,0
1600 32,6 22,7 51 630,6 7558,8 7530,7 0,0 0,0 0,0
1700 31,7 22,7 51 617,9 7385,6 7367,6 0,0 0,0 0,0
1800 30,5 22,6 51 602,8 7181,7 7174,4 0,0 0,0 0,0
1900 29,0 22,6 51 592,5 7045,7 7043,7 0,0 0,0 0,0
2000 27,4 22,6 51 582,5 6914,4 6917,1 0,0 0,0 0,0
2100 26,2 22,6 51 573,1 6791,8 6798,1 0,0 0,0 0,0
2200 25,0 22,6 51 564,2 6675,5 6684,7 0,0 0,0 0,0
2300 24,1 22,6 51 555,8 6567,7 6578,9 0,0 0,0 0,0
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
12 3 0,010
0,008
0,006
0,004
0,002
0,000
0 5 10 15 20 25 30 35
Temperature ( °C )
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
Total coil load ........................................................ 8,4 kW Load occurs at ................................................. Sep 0900
Sensible coil load ................................................... 8,0 kW OA DB / WB ................................................... 23,6 / 23,3 °C
Coil L/s at Sep 0900 ............................................. 668 L/s Entering DB / WB ........................................... 22,8 / 16,2 °C
Max block L/s at Sep 0900 .................................... 735 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s ........................................... 735 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,957 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 4,0 Resulting RH .............................................................. 51 %
W/m² .................................................................. 247,0 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K
Actual max L/s at Sep 0900 .................................. 735 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ......................................................... 734 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 21,61 L/(s-m²) Fan static ...................................................................... 0 Pa
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 L/s
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A06-RDC-Commerce 10 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Sep 0900 HEATING DATA AT DES HTG
COOLING OA DB / WB 23,6 °C / 23,3 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 28 m² 4881 - 28 m² - -
Wall Transmission 13 m² 159 - 13 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 28 m² 78 - 28 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 34 m² 0 - 34 m² 0 -
Partitions 24 m² 2 - 24 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 680 W 680 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1700 W 1700 - 0 0 -
People 10 674 352 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 8175 352 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A06-RDC-Commerce 10 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NE EXPOSURE
WALL 4 1,471 - 41 - 0
WINDOW 1 8 1,700 0,811 23 1072 0
E EXPOSURE
WALL 6 1,471 - 77 - 0
WINDOW 1 12 1,700 0,811 33 2477 0
SE EXPOSURE
WALL 4 1,471 - 41 - 0
WINDOW 1 8 1,700 0,811 23 1333 0
ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 23,4 22,5 52 436,0 5112,9 5099,1 0,0 0,0 0,0
0100 22,8 22,5 52 424,2 4966,1 4954,2 0,0 0,0 0,0
0200 22,2 22,4 52 412,8 4824,8 4814,5 0,0 0,0 0,0
0300 21,8 22,4 53 402,3 4696,4 4687,1 0,0 0,0 0,0
0400 21,4 22,4 53 392,8 4579,6 4570,8 0,0 0,0 0,0
0500 21,3 22,4 53 384,3 4475,8 4467,1 0,0 0,0 0,0
0600 21,5 22,5 52 415,9 4882,0 4853,1 0,0 0,0 0,0
0700 22,1 22,6 51 549,8 6619,7 6519,9 0,0 0,0 0,0
0800 23,2 22,7 51 613,5 7458,0 7332,2 0,0 0,0 0,0
0900 24,7 22,7 51 639,6 7798,6 7667,9 0,0 0,0 0,0
1000 26,4 22,7 51 635,6 7736,8 7616,9 0,0 0,0 0,0
1100 28,4 22,7 51 614,2 7441,7 7340,3 0,0 0,0 0,0
1200 30,2 22,7 51 599,4 7240,2 7151,0 0,0 0,0 0,0
1300 31,6 22,7 51 596,3 7195,0 7110,7 0,0 0,0 0,0
1400 32,6 22,7 51 593,3 7153,3 7073,4 0,0 0,0 0,0
1500 32,9 22,7 51 585,7 7048,9 6975,3 0,0 0,0 0,0
1600 32,6 22,6 51 572,2 6868,8 6803,9 0,0 0,0 0,0
1700 31,7 22,6 51 551,6 6595,6 6542,1 0,0 0,0 0,0
1800 30,5 22,6 52 526,2 6262,4 6221,4 0,0 0,0 0,0
1900 29,0 22,6 52 509,2 6042,7 6008,4 0,0 0,0 0,0
2000 27,4 22,5 52 492,6 5829,1 5800,8 0,0 0,0 0,0
2100 26,2 22,5 52 477,1 5630,9 5607,5 0,0 0,0 0,0
2200 25,0 22,5 52 462,2 5443,0 5423,7 0,0 0,0 0,0
2300 24,1 22,5 52 448,5 5270,3 5254,2 0,0 0,0 0,0
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
6
Load ( kW )
0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day
Zone: Zone 1
Data for July
7000
6000
5000
W
4000
3000
2000
1000
0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day
0,016
0,012
0,010
12 3
0,008
0,006
0,004
0,002
0,000
0 5 10 15 20 25 30 35
Temperature ( °C )
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
Total coil load ........................................................ 2,1 kW Load occurs at ................................................. Dec 1600
Sensible coil load ................................................... 1,9 kW OA DB / WB ................................................... 27,6 / 24,2 °C
Coil L/s at Dec 1600 ............................................. 161 L/s Entering DB / WB ........................................... 22,7 / 16,3 °C
Max block L/s at Dec 1600 .................................... 179 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s ........................................... 179 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,915 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 5,4 Resulting RH .............................................................. 52 %
W/m² .................................................................. 184,2 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K
Actual max L/s at Dec 1600 .................................. 179 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ......................................................... 179 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 15,56 L/(s-m²) Fan static ...................................................................... 0 Pa
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 L/s
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A06-RDC-B.chef cuisine '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 27,6 °C / 24,2 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 823 - 3 m² - -
Wall Transmission 7 m² 78 - 7 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 19 - 3 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 12 m² 0 - 12 m² 0 -
Partitions 17 m² 30 - 17 m² 0 -
Ceiling 12 m² 20 - 12 m² 0 -
Overhead Lighting 230 W 230 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 575 W 575 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 1990 180 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A06-RDC-B.chef cuisine '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 7 1,471 - 78 - 0
WINDOW 1 3 1,700 0,811 19 823 0
ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 23,4 22,5 54 109,9 1306,6 1287,6 0,0 0,0 0,0
0100 22,8 22,5 54 108,2 1284,5 1266,2 0,0 0,0 0,0
0200 22,2 22,5 54 106,4 1261,7 1244,3 0,0 0,0 0,0
0300 21,8 22,5 54 104,9 1243,5 1226,5 0,0 0,0 0,0
0400 21,4 22,5 54 103,7 1228,4 1211,7 0,0 0,0 0,0
0500 21,3 22,5 54 102,6 1214,3 1197,8 0,0 0,0 0,0
0600 21,5 22,5 54 101,9 1206,2 1189,6 0,0 0,0 0,0
0700 22,1 22,5 54 102,9 1219,1 1201,2 0,0 0,0 0,0
0800 23,2 22,5 54 104,7 1243,8 1223,9 0,0 0,0 0,0
0900 24,7 22,5 54 107,2 1276,5 1254,5 0,0 0,0 0,0
1000 26,4 22,5 54 110,0 1313,8 1289,5 0,0 0,0 0,0
1100 28,4 22,5 54 113,2 1355,0 1328,5 0,0 0,0 0,0
1200 30,2 22,5 54 116,4 1396,3 1367,8 0,0 0,0 0,0
1300 31,6 22,5 54 119,1 1431,9 1401,8 0,0 0,0 0,0
1400 32,6 22,6 53 123,6 1491,4 1458,4 0,0 0,0 0,0
1500 32,9 22,6 53 128,4 1553,8 1518,0 0,0 0,0 0,0
1600 32,6 22,6 53 130,9 1587,0 1550,4 0,0 0,0 0,0
1700 31,7 22,6 53 129,0 1559,5 1525,7 0,0 0,0 0,0
1800 30,5 22,6 53 122,1 1466,4 1439,0 0,0 0,0 0,0
1900 29,0 22,5 54 120,0 1438,6 1412,9 0,0 0,0 0,0
2000 27,4 22,5 54 117,8 1409,9 1385,9 0,0 0,0 0,0
2100 26,2 22,5 54 115,7 1382,7 1360,2 0,0 0,0 0,0
2200 25,0 22,5 54 113,6 1355,3 1334,1 0,0 0,0 0,0
2300 24,1 22,5 54 111,7 1329,8 1309,8 0,0 0,0 0,0
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
0,016
0,012
3 0,010
12
0,008
0,006
0,004
0,002
0,000
0 5 10 15 20 25 30 35
Temperature ( °C )
Calculation Months .................................... Jan to Dec Zone L/s Sizing ................... Sum of space airflow rates
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
Total coil load ........................................................ 2,2 kW Load occurs at ................................................ Aug 1800
Sensible coil load ................................................... 2,1 kW OA DB / WB ................................................... 30,5 / 26,5 °C
Coil L/s at Aug 1800 ............................................. 195 L/s Entering DB / WB ........................................... 21,7 / 15,8 °C
Max block L/s ....................................................... 195 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s ........................................... 195 L/s Coil ADP .................................................................. 11,8 °C
Sensible heat ratio .............................................. 0,972 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 6,0 Resulting RH .............................................................. 54 %
W/m² .................................................................. 166,8 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... 0,09 L/s Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K
Actual max L/s ...................................................... 195 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ......................................................... 195 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 15,01 L/(s-m²) Fan static ...................................................................... 0 Pa
Calculation Months .................................... Jan to Dec Zone L/s Sizing ................... Sum of space airflow rates
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 L/s
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A06-R1-Bureau cantine '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1800 HEATING DATA AT DES HTG
COOLING OA DB / WB 30,5 °C / 26,5 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 34 m² 604 - 34 m² 0 -
Roof Transmission 13 m² 481 - 13 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 3 m² 54 - 3 m² 0 -
Floor Transmission 13 m² 49 - 13 m² 1 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 260 W 260 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 650 W 650 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 2171 60 - 1 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A06-R1-Bureau cantine '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 7 1,471 - 108 - 0
NW EXPOSURE
WALL 11 1,471 - 200 - 0
NE EXPOSURE
WALL 7 1,471 - 152 - 0
SE EXPOSURE
WALL 8 1,471 - 143 - 0
DOOR 3 2,500 - 54 - 0
H EXPOSURE
ROOF 13 1,137 - 481 - 0
ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 23,4 21,2 56 195,1 1911,6 1990,2 0,0 0,0 0,0
0100 22,8 21,1 56 195,1 1857,3 1961,0 0,0 0,0 0,0
0200 22,2 21,0 57 195,1 1802,0 1930,3 0,0 0,0 0,0
0300 21,8 20,8 57 195,1 1749,0 1899,9 0,0 0,0 0,0
0400 21,4 20,7 58 195,1 1698,1 1869,8 0,0 0,0 0,0
0500 21,3 20,6 58 195,1 1648,9 1839,9 0,0 0,0 0,0
0600 21,5 20,5 59 195,1 1602,7 1811,0 0,0 0,0 0,0
0700 22,1 20,4 59 195,1 1561,6 1784,3 0,0 0,0 0,0
0800 23,2 20,3 59 195,1 1539,5 1767,2 0,0 0,0 0,0
0900 24,7 20,3 59 195,1 1549,3 1766,7 0,0 0,0 0,0
1000 26,4 20,4 59 195,1 1595,0 1785,8 0,0 0,0 0,0
1100 28,4 20,5 59 195,1 1672,6 1822,8 0,0 0,0 0,0
1200 30,2 20,7 58 195,1 1768,9 1871,5 0,0 0,0 0,0
1300 31,6 21,0 57 195,1 1869,7 1924,7 0,0 0,0 0,0
1400 32,6 21,2 56 195,1 1965,5 1977,3 0,0 0,0 0,0
1500 32,9 21,4 55 195,1 2047,5 2024,3 0,0 0,0 0,0
1600 32,6 21,5 55 195,1 2108,9 2061,8 0,0 0,0 0,0
1700 31,7 21,6 54 195,1 2147,7 2088,2 0,0 0,0 0,0
1800 30,5 21,7 54 195,1 2159,9 2100,9 0,0 0,0 0,0
1900 29,0 21,7 54 195,1 2145,8 2099,5 0,0 0,0 0,0
2000 27,4 21,6 54 195,1 2111,9 2086,8 0,0 0,0 0,0
2100 26,2 21,6 54 195,1 2068,0 2067,7 0,0 0,0 0,0
2200 25,0 21,5 55 195,1 2017,8 2044,1 0,0 0,0 0,0
2300 24,1 21,4 55 195,1 1965,1 2018,0 0,0 0,0 0,0
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
1,2
1,0
0,8
0,6
0,4
0,2
0,0
00 02 04 06 08 10 12 14 16 18 20 22
01 03 05 07 09 11 13 15 17 19 21 23
Hour of Day
Zone: Zone 1
Data for July
1000
800
600
400
200
0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day
12 3 0,010
0,008
0,006
0,004
0,002
0,000
0 5 10 15 20 25 30 35
Temperature ( °C )
Calculation Months .................................... Jan to Dec Zone L/s Sizing ................... Sum of space airflow rates
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
Total coil load ....................................................... 32,0 kW Load occurs at ................................................. Jun 1600
Sensible coil load .................................................. 30,4 kW OA DB / WB ................................................... 32,0 / 27,0 °C
Coil L/s at Jun 1600 ............................................. 2848 L/s Entering DB / WB ........................................... 21,6 / 15,8 °C
Max block L/s ...................................................... 2848 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s .......................................... 2848 L/s Coil ADP .................................................................. 11,8 °C
Sensible heat ratio .............................................. 0,951 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 7,2 Resulting RH .............................................................. 55 %
W/m² .................................................................. 139,6 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... 1,38 L/s Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K
Actual max L/s ..................................................... 2848 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ........................................................ 2846 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 12,44 L/(s-m²) Fan static ...................................................................... 0 Pa
Calculation Months .................................... Jan to Dec Zone L/s Sizing ................... Sum of space airflow rates
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 L/s
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A06-R1-E.de travail D '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 32,0 °C / 27,0 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 75 m² 10501 - 75 m² - -
Wall Transmission 60 m² 817 - 60 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 75 m² 1039 - 75 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 80 m² 338 - 80 m² 9 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 4580 W 4580 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 11450 W 11449 - 0 0 -
People 44 2966 1549 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 31690 1549 - 9 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A06-R1-E.de travail D '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 11 1,471 - 112 - 0
WINDOW 1 4 1,700 0,811 56 380 0
NW EXPOSURE
WALL 21 1,471 - 321 - 0
WINDOW 1 24 1,700 0,811 337 5474 0
NE EXPOSURE
WALL 2 1,471 - 48 - 0
WINDOW 1 20 1,700 0,811 281 2677 0
E EXPOSURE
WALL 5 1,471 - 104 - 0
WINDOW 1 6 1,700 0,811 83 705 0
SE EXPOSURE
WALL 14 1,471 - 169 - 0
WINDOW 1 16 1,700 0,811 225 1066 0
S EXPOSURE
WALL 7 1,471 - 62 - 0
WINDOW 1 4 1,700 0,811 56 199 0
ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 23,4 20,6 59 2848,4 25543,6 26880,4 0,0 0,0 0,0
0100 22,8 20,5 59 2848,4 25105,3 26560,7 0,0 0,0 0,0
0200 22,2 20,4 60 2848,4 24678,7 26241,2 0,0 0,0 0,0
0300 21,8 20,3 60 2848,4 24287,2 25935,7 0,0 0,0 0,0
0400 21,4 20,2 60 2848,4 23927,5 25644,0 0,0 0,0 0,0
0500 21,3 20,2 61 2848,4 23602,5 25369,0 0,0 0,0 0,0
0600 21,5 20,2 60 2848,4 24060,1 25533,8 0,0 0,0 0,0
0700 22,1 20,6 59 2848,4 26599,6 26900,6 0,0 0,0 0,0
0800 23,2 20,8 58 2848,4 27910,8 27672,2 0,0 0,0 0,0
0900 24,7 21,0 57 2848,4 28572,3 28102,0 0,0 0,0 0,0
1000 26,4 21,0 57 2848,4 28749,1 28266,7 0,0 0,0 0,0
1100 28,4 21,0 57 2848,4 28707,7 28303,7 0,0 0,0 0,0
1200 30,2 21,1 57 2848,4 29016,3 28529,9 0,0 0,0 0,0
1300 31,6 21,2 56 2848,4 29804,5 29034,4 0,0 0,0 0,0
1400 32,6 21,4 56 2848,4 30722,1 29634,1 0,0 0,0 0,0
1500 32,9 21,5 55 2848,4 31426,2 30134,5 0,0 0,0 0,0
1600 32,6 21,6 55 2848,4 31650,6 30374,3 0,0 0,0 0,0
1700 31,7 21,5 55 2848,4 30828,7 30017,0 0,0 0,0 0,0
1800 30,5 21,2 56 2848,4 28766,3 28918,1 0,0 0,0 0,0
1900 29,0 21,1 57 2848,4 28169,7 28569,8 0,0 0,0 0,0
2000 27,4 21,0 57 2848,4 27587,9 28226,6 0,0 0,0 0,0
2100 26,2 20,9 58 2848,4 27038,3 27886,4 0,0 0,0 0,0
2200 25,0 20,8 58 2848,4 26506,0 27542,8 0,0 0,0 0,0
2300 24,1 20,7 58 2848,4 26007,1 27206,4 0,0 0,0 0,0
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
30
25
Load ( kW )
20
15
10
0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day
Zone: Zone 1
Data for July
30000
25000
20000
W
15000
10000
5000
0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day
12 3 0,010
0,008
0,006
0,004
0,002
0,000
0 5 10 15 20 25 30 35
Temperature ( °C )
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
Total coil load ....................................................... 33,3 kW Load occurs at ................................................. Nov 1500
Sensible coil load .................................................. 31,7 kW OA DB / WB ................................................... 29,0 / 25,4 °C
Coil L/s at Nov 1500 ............................................ 2634 L/s Entering DB / WB ........................................... 22,8 / 16,2 °C
Max block L/s at Nov 1500 ................................... 2890 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s .......................................... 2890 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,952 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 6,9 Resulting RH .............................................................. 51 %
W/m² .................................................................. 145,1 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K
Actual max L/s at Nov 1500 ................................. 2890 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ........................................................ 2888 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 12,60 L/(s-m²) Fan static ...................................................................... 0 Pa
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 L/s
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A06-R1-E.de travail G '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Nov 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 29,0 °C / 25,4 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 77 m² 11503 - 77 m² - -
Wall Transmission 85 m² 790 - 85 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 77 m² 644 - 77 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 80 m² 193 - 80 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 4588 W 4588 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 11470 W 11469 - 0 0 -
People 44 2966 1549 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 32153 1549 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A06-R1-E.de travail G '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 21 1,471 - 223 - 0
WINDOW 1 24 1,700 0,811 204 6149 0
NW EXPOSURE
WALL 22 1,471 - 85 - 0
WINDOW 1 4 1,700 0,811 34 296 0
N EXPOSURE
WALL 5 1,471 - 13 - 0
WINDOW 1 6 1,700 0,811 50 249 0
NE EXPOSURE
WALL 14 1,471 - 79 - 0
WINDOW 1 16 1,700 0,811 136 918 0
E EXPOSURE
WALL 5 1,471 - 77 - 0
WINDOW 1 6 1,700 0,811 50 729 0
SE EXPOSURE
WALL 17 1,471 - 313 - 0
WINDOW 1 20 1,700 0,811 170 3162 0
ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 23,4 22,6 52 2127,4 25294,7 25200,1 0,0 0,0 0,0
0100 22,8 22,6 52 2096,5 24894,7 24810,0 0,0 0,0 0,0
0200 22,2 22,6 52 2065,8 24499,7 24423,9 0,0 0,0 0,0
0300 21,8 22,6 52 2037,2 24134,3 24064,8 0,0 0,0 0,0
0400 21,4 22,6 52 2010,6 23796,2 23731,1 0,0 0,0 0,0
0500 21,3 22,6 52 1986,3 23489,3 23426,5 0,0 0,0 0,0
0600 21,5 22,6 52 2020,0 23955,3 23848,0 0,0 0,0 0,0
0700 22,1 22,6 52 2207,4 26482,0 26211,4 0,0 0,0 0,0
0800 23,2 22,7 51 2304,8 27788,9 27451,4 0,0 0,0 0,0
0900 24,7 22,7 51 2355,1 28455,7 28094,5 0,0 0,0 0,0
1000 26,4 22,7 51 2370,8 28651,1 28295,8 0,0 0,0 0,0
1100 28,4 22,7 51 2374,0 28677,9 28336,7 0,0 0,0 0,0
1200 30,2 22,7 51 2383,4 28791,5 28457,0 0,0 0,0 0,0
1300 31,6 22,7 51 2406,8 29097,1 28756,9 0,0 0,0 0,0
1400 32,6 22,7 51 2448,1 29648,8 29288,7 0,0 0,0 0,0
1500 32,9 22,7 51 2485,5 30144,6 29770,5 0,0 0,0 0,0
1600 32,6 22,7 51 2495,9 30269,0 29904,6 0,0 0,0 0,0
1700 31,7 22,7 51 2448,3 29600,0 29291,3 0,0 0,0 0,0
1800 30,5 22,7 51 2337,8 28081,9 27872,8 0,0 0,0 0,0
1900 29,0 22,6 51 2301,0 27586,6 27402,2 0,0 0,0 0,0
2000 27,4 22,6 51 2264,3 27095,2 26934,9 0,0 0,0 0,0
2100 26,2 22,6 51 2228,8 26623,3 26483,4 0,0 0,0 0,0
2200 25,0 22,6 52 2193,4 26156,3 26034,6 0,0 0,0 0,0
2300 24,1 22,6 52 2159,5 25712,3 25605,6 0,0 0,0 0,0
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
30
25
20
Load ( kW )
15
10
0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day
Zone: Zone 1
Data for July
25000
20000
W
15000
10000
5000
0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day
0,016
0,012
0,010
12 3
0,008
0,006
0,004
0,002
0,000
0 5 10 15 20 25 30 35
Temperature ( °C )
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
Total coil load ........................................................ 6,8 kW Load occurs at ................................................. Sep 0900
Sensible coil load ................................................... 6,4 kW OA DB / WB ................................................... 23,6 / 23,3 °C
Coil L/s at Sep 0900 ............................................. 529 L/s Entering DB / WB ........................................... 22,7 / 16,2 °C
Max block L/s at Sep 0900 .................................... 583 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s ........................................... 583 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,936 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 6,3 Resulting RH .............................................................. 51 %
W/m² .................................................................. 159,1 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K
Actual max L/s at Sep 0900 .................................. 583 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ......................................................... 582 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 13,64 L/(s-m²) Fan static ...................................................................... 0 Pa
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 L/s
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A06-R1-Espace lounge '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Sep 0900 HEATING DATA AT DES HTG
COOLING OA DB / WB 23,6 °C / 23,3 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 14 m² 2441 - 14 m² - -
Wall Transmission 17 m² 200 - 17 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 14 m² 39 - 14 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 36 m² 3 - 36 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 854 W 854 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2135 W 2135 - 0 0 -
People 12 809 422 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 6481 422 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A06-R1-Espace lounge '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SE EXPOSURE
WALL 6 1,471 - 70 - 0
WINDOW 1 4 1,700 0,811 11 666 0
E EXPOSURE
WALL 5 1,471 - 68 - 0
WINDOW 1 6 1,700 0,811 17 1238 0
NE EXPOSURE
WALL 6 1,471 - 63 - 0
WINDOW 1 4 1,700 0,811 11 536 0
ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 23,4 22,6 52 423,8 5043,1 5016,2 0,0 0,0 0,0
0100 22,8 22,6 52 417,1 4956,5 4931,4 0,0 0,0 0,0
0200 22,2 22,6 52 410,4 4871,5 4848,1 0,0 0,0 0,0
0300 21,8 22,6 52 404,5 4795,9 4773,5 0,0 0,0 0,0
0400 21,4 22,6 53 399,1 4728,0 4706,1 0,0 0,0 0,0
0500 21,3 22,5 53 394,2 4666,3 4644,6 0,0 0,0 0,0
0600 21,5 22,6 52 408,4 4859,5 4822,9 0,0 0,0 0,0
0700 22,1 22,7 52 472,2 5719,7 5631,0 0,0 0,0 0,0
0800 23,2 22,7 52 503,5 6140,9 6032,6 0,0 0,0 0,0
0900 24,7 22,7 51 517,1 6321,6 6209,1 0,0 0,0 0,0
1000 26,4 22,7 51 516,7 6309,5 6203,9 0,0 0,0 0,0
1100 28,4 22,7 51 508,3 6189,3 6095,7 0,0 0,0 0,0
1200 30,2 22,7 52 503,5 6118,8 6032,9 0,0 0,0 0,0
1300 31,6 22,7 52 504,0 6123,7 6040,1 0,0 0,0 0,0
1400 32,6 22,7 52 504,4 6125,6 6044,4 0,0 0,0 0,0
1500 32,9 22,7 52 501,9 6088,9 6012,1 0,0 0,0 0,0
1600 32,6 22,7 52 495,9 6005,6 5935,3 0,0 0,0 0,0
1700 31,7 22,7 52 486,0 5869,3 5807,9 0,0 0,0 0,0
1800 30,5 22,7 52 473,3 5696,3 5645,0 0,0 0,0 0,0
1900 29,0 22,7 52 464,3 5575,7 5530,2 0,0 0,0 0,0
2000 27,4 22,6 52 455,3 5455,7 5415,5 0,0 0,0 0,0
2100 26,2 22,6 52 446,8 5343,4 5307,6 0,0 0,0 0,0
2200 25,0 22,6 52 438,6 5235,1 5203,1 0,0 0,0 0,0
2300 24,1 22,6 52 430,9 5134,9 5105,9 0,0 0,0 0,0
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
4,0
3,5
3,0
2,5
2,0
1,5
1,0
0,5
0,0
00 02 04 06 08 10 12 14 16 18 20 22
01 03 05 07 09 11 13 15 17 19 21 23
Hour of Day
Zone: Zone 1
Data for July
3000
2500
2000
1500
1000
500
0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day
0,016
0,012
3
0,010
12
0,008
0,006
0,004
0,002
0,000
0 5 10 15 20 25 30 35
Temperature ( °C )
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
Total coil load ........................................................ 6,1 kW Load occurs at ................................................. Sep 1600
Sensible coil load ................................................... 5,8 kW OA DB / WB ................................................... 31,4 / 26,5 °C
Coil L/s at Sep 1600 ............................................. 480 L/s Entering DB / WB ........................................... 22,8 / 16,2 °C
Max block L/s at Sep 1600 .................................... 527 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s ........................................... 527 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,941 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 5,2 Resulting RH .............................................................. 51 %
W/m² .................................................................. 192,8 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K
Actual max L/s at Sep 1600 .................................. 527 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ......................................................... 527 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 16,59 L/(s-m²) Fan static ...................................................................... 0 Pa
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 L/s
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A06-R1-S.de réunion 1 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Sep 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 31,4 °C / 26,5 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 16 m² 2806 - 16 m² - -
Wall Transmission 14 m² 166 - 14 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 16 m² 210 - 16 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 8 m² 29 - 8 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 636 W 636 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1590 W 1590 - 0 0 -
People 6 431 361 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 5868 361 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A06-R1-S.de réunion 1 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NW EXPOSURE
WALL 7 1,471 - 78 - 0
WINDOW 1 8 1,700 0,811 105 1285 0
SW EXPOSURE
WALL 7 1,471 - 88 - 0
WINDOW 1 8 1,700 0,811 105 1521 0
ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 23,4 22,5 53 352,0 4158,0 4144,6 0,0 0,0 0,0
0100 22,8 22,5 53 344,6 4062,5 4051,5 0,0 0,0 0,0
0200 22,2 22,5 53 337,2 3969,3 3960,3 0,0 0,0 0,0
0300 21,8 22,5 53 330,3 3882,1 3874,7 0,0 0,0 0,0
0400 21,4 22,5 53 323,8 3800,7 3794,5 0,0 0,0 0,0
0500 21,3 22,5 53 317,9 3726,8 3721,3 0,0 0,0 0,0
0600 21,5 22,5 53 314,6 3686,7 3680,4 0,0 0,0 0,0
0700 22,1 22,5 53 319,6 3754,7 3742,5 0,0 0,0 0,0
0800 23,2 22,5 53 325,0 3825,9 3808,5 0,0 0,0 0,0
0900 24,7 22,5 53 331,2 3908,1 3885,7 0,0 0,0 0,0
1000 26,4 22,5 53 338,4 4001,9 3974,4 0,0 0,0 0,0
1100 28,4 22,5 53 346,4 4106,7 4074,2 0,0 0,0 0,0
1200 30,2 22,6 52 363,7 4333,2 4290,3 0,0 0,0 0,0
1300 31,6 22,6 52 388,2 4654,8 4598,4 0,0 0,0 0,0
1400 32,6 22,6 52 419,9 5073,9 5000,8 0,0 0,0 0,0
1500 32,9 22,7 51 450,3 5477,3 5390,1 0,0 0,0 0,0
1600 32,6 22,7 51 468,2 5714,0 5622,1 0,0 0,0 0,0
1700 31,7 22,7 51 455,0 5527,9 5451,7 0,0 0,0 0,0
1800 30,5 22,6 52 403,2 4826,3 4787,8 0,0 0,0 0,0
1900 29,0 22,6 52 394,0 4705,3 4671,9 0,0 0,0 0,0
2000 27,4 22,6 52 385,1 4587,7 4559,6 0,0 0,0 0,0
2100 26,2 22,6 52 376,5 4474,8 4451,3 0,0 0,0 0,0
2200 25,0 22,6 52 368,0 4363,7 4344,3 0,0 0,0 0,0
2300 24,1 22,5 52 359,8 4257,9 4241,8 0,0 0,0 0,0
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
3,5
3,0
2,5
2,0
1,5
1,0
0,5
0,0
00 02 04 06 08 10 12 14 16 18 20 22
01 03 05 07 09 11 13 15 17 19 21 23
Hour of Day
Zone: Zone 1
Data for July
5500
5000
4500
4000
3500
3000
W
2500
2000
1500
1000
500
0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day
0,016
0,012
0,010
12 3
0,008
0,006
0,004
0,002
0,000
0 5 10 15 20 25 30 35
Temperature ( °C )
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
Total coil load ....................................................... 13,3 kW Load occurs at ................................................. Jun 1600
Sensible coil load .................................................. 12,4 kW OA DB / WB ................................................... 32,0 / 27,0 °C
Coil L/s at Jun 1600 ............................................. 1027 L/s Entering DB / WB ........................................... 22,8 / 16,3 °C
Max block L/s at Jun 1600 ................................... 1130 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s .......................................... 1130 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,932 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 5,6 Resulting RH .............................................................. 51 %
W/m² .................................................................. 179,6 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K
Actual max L/s at Jun 1600 .................................. 1130 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ........................................................ 1129 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 15,31 L/(s-m²) Fan static ...................................................................... 0 Pa
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
12 3 0,010
0,008
0,006
0,004
0,002
0,000
0 5 10 15 20 25 30 35
Temperature ( °C )
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
Total coil load ....................................................... 13,3 kW Load occurs at ................................................. Jun 1600
Sensible coil load .................................................. 12,4 kW OA DB / WB ................................................... 32,0 / 27,0 °C
Coil L/s at Jun 1600 ............................................. 1027 L/s Entering DB / WB ........................................... 22,8 / 16,3 °C
Max block L/s at Jun 1600 ................................... 1130 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s .......................................... 1130 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,932 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 5,6 Resulting RH .............................................................. 51 %
W/m² .................................................................. 179,6 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K
Actual max L/s at Jun 1600 .................................. 1130 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ........................................................ 1129 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 15,31 L/(s-m²) Fan static ...................................................................... 0 Pa
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
12 3 0,010
0,008
0,006
0,004
0,002
0,000
0 5 10 15 20 25 30 35
Temperature ( °C )
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
Total coil load ........................................................ 5,2 kW Load occurs at ................................................. Jun 1600
Sensible coil load ................................................... 4,8 kW OA DB / WB ................................................... 32,0 / 27,0 °C
Coil L/s at Jun 1600 .............................................. 401 L/s Entering DB / WB ........................................... 22,8 / 16,3 °C
Max block L/s at Jun 1600 .................................... 441 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s ........................................... 441 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,930 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 6,0 Resulting RH .............................................................. 52 %
W/m² .................................................................. 165,8 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K
Actual max L/s at Jun 1600 ................................... 441 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ......................................................... 441 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 14,10 L/(s-m²) Fan static ...................................................................... 0 Pa
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
12 3 0,010
0,008
0,006
0,004
0,002
0,000
0 5 10 15 20 25 30 35
Temperature ( °C )
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
Total coil load ........................................................ 4,7 kW Load occurs at ................................................. Dec 1600
Sensible coil load ................................................... 4,4 kW OA DB / WB ................................................... 27,6 / 24,2 °C
Coil L/s at Dec 1600 ............................................. 364 L/s Entering DB / WB ........................................... 22,8 / 16,3 °C
Max block L/s at Dec 1600 .................................... 401 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s ........................................... 401 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,934 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 5,2 Resulting RH .............................................................. 51 %
W/m² .................................................................. 190,8 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K
Actual max L/s at Dec 1600 .................................. 401 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ......................................................... 400 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 16,29 L/(s-m²) Fan static ...................................................................... 0 Pa
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
0,016
0,012
3
0,010
12
0,008
0,006
0,004
0,002
0,000
0 5 10 15 20 25 30 35
Temperature ( °C )
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
Total coil load ........................................................ 6,3 kW Load occurs at ................................................. Dec 1600
Sensible coil load ................................................... 6,0 kW OA DB / WB ................................................... 27,6 / 24,2 °C
Coil L/s at Dec 1600 ............................................. 496 L/s Entering DB / WB ........................................... 22,7 / 16,2 °C
Max block L/s at Dec 1600 .................................... 547 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s ........................................... 547 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,951 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 7,2 Resulting RH .............................................................. 51 %
W/m² .................................................................. 139,4 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K
Actual max L/s at Dec 1600 .................................. 547 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ......................................................... 547 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 12,16 L/(s-m²) Fan static ...................................................................... 0 Pa
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
0,016
0,012
0,010
12 3
0,008
0,006
0,004
0,002
0,000
0 5 10 15 20 25 30 35
Temperature ( °C )
Calculation Months .................................... Jan to Dec Zone L/s Sizing ................... Sum of space airflow rates
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
Total coil load ........................................................ 2,2 kW Load occurs at ................................................ Aug 1800
Sensible coil load ................................................... 2,1 kW OA DB / WB ................................................... 30,5 / 26,5 °C
Coil L/s at Aug 1800 ............................................. 195 L/s Entering DB / WB ........................................... 21,7 / 15,8 °C
Max block L/s ....................................................... 195 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s ........................................... 195 L/s Coil ADP .................................................................. 11,8 °C
Sensible heat ratio .............................................. 0,972 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 6,0 Resulting RH .............................................................. 54 %
W/m² .................................................................. 166,8 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... 0,09 L/s Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K
Actual max L/s ...................................................... 195 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ......................................................... 195 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 15,01 L/(s-m²) Fan static ...................................................................... 0 Pa
Calculation Months .................................... Jan to Dec Zone L/s Sizing ................... Sum of space airflow rates
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 L/s
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A06-R1-Bureau cantine '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1800 HEATING DATA AT DES HTG
COOLING OA DB / WB 30,5 °C / 26,5 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 34 m² 604 - 34 m² 0 -
Roof Transmission 13 m² 481 - 13 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 3 m² 54 - 3 m² 0 -
Floor Transmission 13 m² 49 - 13 m² 1 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 260 W 260 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 650 W 650 - 0 0 -
People 1 72 60 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 2171 60 - 1 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A06-R1-Bureau cantine '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 7 1,471 - 108 - 0
NW EXPOSURE
WALL 11 1,471 - 200 - 0
NE EXPOSURE
WALL 7 1,471 - 152 - 0
SE EXPOSURE
WALL 8 1,471 - 143 - 0
DOOR 3 2,500 - 54 - 0
H EXPOSURE
ROOF 13 1,137 - 481 - 0
ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 23,4 21,2 56 195,1 1911,6 1990,2 0,0 0,0 0,0
0100 22,8 21,1 56 195,1 1857,3 1961,0 0,0 0,0 0,0
0200 22,2 21,0 57 195,1 1802,0 1930,3 0,0 0,0 0,0
0300 21,8 20,8 57 195,1 1749,0 1899,9 0,0 0,0 0,0
0400 21,4 20,7 58 195,1 1698,1 1869,8 0,0 0,0 0,0
0500 21,3 20,6 58 195,1 1648,9 1839,9 0,0 0,0 0,0
0600 21,5 20,5 59 195,1 1602,7 1811,0 0,0 0,0 0,0
0700 22,1 20,4 59 195,1 1561,6 1784,3 0,0 0,0 0,0
0800 23,2 20,3 59 195,1 1539,5 1767,2 0,0 0,0 0,0
0900 24,7 20,3 59 195,1 1549,3 1766,7 0,0 0,0 0,0
1000 26,4 20,4 59 195,1 1595,0 1785,8 0,0 0,0 0,0
1100 28,4 20,5 59 195,1 1672,6 1822,8 0,0 0,0 0,0
1200 30,2 20,7 58 195,1 1768,9 1871,5 0,0 0,0 0,0
1300 31,6 21,0 57 195,1 1869,7 1924,7 0,0 0,0 0,0
1400 32,6 21,2 56 195,1 1965,5 1977,3 0,0 0,0 0,0
1500 32,9 21,4 55 195,1 2047,5 2024,3 0,0 0,0 0,0
1600 32,6 21,5 55 195,1 2108,9 2061,8 0,0 0,0 0,0
1700 31,7 21,6 54 195,1 2147,7 2088,2 0,0 0,0 0,0
1800 30,5 21,7 54 195,1 2159,9 2100,9 0,0 0,0 0,0
1900 29,0 21,7 54 195,1 2145,8 2099,5 0,0 0,0 0,0
2000 27,4 21,6 54 195,1 2111,9 2086,8 0,0 0,0 0,0
2100 26,2 21,6 54 195,1 2068,0 2067,7 0,0 0,0 0,0
2200 25,0 21,5 55 195,1 2017,8 2044,1 0,0 0,0 0,0
2300 24,1 21,4 55 195,1 1965,1 2018,0 0,0 0,0 0,0
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
1,2
1,0
0,8
0,6
0,4
0,2
0,0
00 02 04 06 08 10 12 14 16 18 20 22
01 03 05 07 09 11 13 15 17 19 21 23
Hour of Day
Zone: Zone 1
Data for July
1000
800
600
400
200
0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day
12 3 0,010
0,008
0,006
0,004
0,002
0,000
0 5 10 15 20 25 30 35
Temperature ( °C )
Calculation Months .................................... Jan to Dec Zone L/s Sizing ................... Sum of space airflow rates
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
Total coil load ....................................................... 32,0 kW Load occurs at ................................................. Jun 1600
Sensible coil load .................................................. 30,4 kW OA DB / WB ................................................... 32,0 / 27,0 °C
Coil L/s at Jun 1600 ............................................. 2848 L/s Entering DB / WB ........................................... 21,6 / 15,8 °C
Max block L/s ...................................................... 2848 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s .......................................... 2848 L/s Coil ADP .................................................................. 11,8 °C
Sensible heat ratio .............................................. 0,951 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 7,2 Resulting RH .............................................................. 55 %
W/m² .................................................................. 139,6 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... 1,38 L/s Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K
Actual max L/s ..................................................... 2848 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ........................................................ 2846 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 12,44 L/(s-m²) Fan static ...................................................................... 0 Pa
Calculation Months .................................... Jan to Dec Zone L/s Sizing ................... Sum of space airflow rates
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 L/s
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A06-R1-E.de travail D '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 32,0 °C / 27,0 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 75 m² 10501 - 75 m² - -
Wall Transmission 60 m² 817 - 60 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 75 m² 1039 - 75 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 80 m² 338 - 80 m² 9 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 4580 W 4580 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 11450 W 11449 - 0 0 -
People 44 2966 1549 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 31690 1549 - 9 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A06-R1-E.de travail D '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 11 1,471 - 112 - 0
WINDOW 1 4 1,700 0,811 56 380 0
NW EXPOSURE
WALL 21 1,471 - 321 - 0
WINDOW 1 24 1,700 0,811 337 5474 0
NE EXPOSURE
WALL 2 1,471 - 48 - 0
WINDOW 1 20 1,700 0,811 281 2677 0
E EXPOSURE
WALL 5 1,471 - 104 - 0
WINDOW 1 6 1,700 0,811 83 705 0
SE EXPOSURE
WALL 14 1,471 - 169 - 0
WINDOW 1 16 1,700 0,811 225 1066 0
S EXPOSURE
WALL 7 1,471 - 62 - 0
WINDOW 1 4 1,700 0,811 56 199 0
ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 23,4 20,6 59 2848,4 25543,6 26880,4 0,0 0,0 0,0
0100 22,8 20,5 59 2848,4 25105,3 26560,7 0,0 0,0 0,0
0200 22,2 20,4 60 2848,4 24678,7 26241,2 0,0 0,0 0,0
0300 21,8 20,3 60 2848,4 24287,2 25935,7 0,0 0,0 0,0
0400 21,4 20,2 60 2848,4 23927,5 25644,0 0,0 0,0 0,0
0500 21,3 20,2 61 2848,4 23602,5 25369,0 0,0 0,0 0,0
0600 21,5 20,2 60 2848,4 24060,1 25533,8 0,0 0,0 0,0
0700 22,1 20,6 59 2848,4 26599,6 26900,6 0,0 0,0 0,0
0800 23,2 20,8 58 2848,4 27910,8 27672,2 0,0 0,0 0,0
0900 24,7 21,0 57 2848,4 28572,3 28102,0 0,0 0,0 0,0
1000 26,4 21,0 57 2848,4 28749,1 28266,7 0,0 0,0 0,0
1100 28,4 21,0 57 2848,4 28707,7 28303,7 0,0 0,0 0,0
1200 30,2 21,1 57 2848,4 29016,3 28529,9 0,0 0,0 0,0
1300 31,6 21,2 56 2848,4 29804,5 29034,4 0,0 0,0 0,0
1400 32,6 21,4 56 2848,4 30722,1 29634,1 0,0 0,0 0,0
1500 32,9 21,5 55 2848,4 31426,2 30134,5 0,0 0,0 0,0
1600 32,6 21,6 55 2848,4 31650,6 30374,3 0,0 0,0 0,0
1700 31,7 21,5 55 2848,4 30828,7 30017,0 0,0 0,0 0,0
1800 30,5 21,2 56 2848,4 28766,3 28918,1 0,0 0,0 0,0
1900 29,0 21,1 57 2848,4 28169,7 28569,8 0,0 0,0 0,0
2000 27,4 21,0 57 2848,4 27587,9 28226,6 0,0 0,0 0,0
2100 26,2 20,9 58 2848,4 27038,3 27886,4 0,0 0,0 0,0
2200 25,0 20,8 58 2848,4 26506,0 27542,8 0,0 0,0 0,0
2300 24,1 20,7 58 2848,4 26007,1 27206,4 0,0 0,0 0,0
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
30
25
Load ( kW )
20
15
10
0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day
Zone: Zone 1
Data for July
30000
25000
20000
W
15000
10000
5000
0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day
12 3 0,010
0,008
0,006
0,004
0,002
0,000
0 5 10 15 20 25 30 35
Temperature ( °C )
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
Total coil load ....................................................... 33,3 kW Load occurs at ................................................. Nov 1500
Sensible coil load .................................................. 31,7 kW OA DB / WB ................................................... 29,0 / 25,4 °C
Coil L/s at Nov 1500 ............................................ 2634 L/s Entering DB / WB ........................................... 22,8 / 16,2 °C
Max block L/s at Nov 1500 ................................... 2890 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s .......................................... 2890 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,952 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 6,9 Resulting RH .............................................................. 51 %
W/m² .................................................................. 145,1 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K
Actual max L/s at Nov 1500 ................................. 2890 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ........................................................ 2888 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 12,60 L/(s-m²) Fan static ...................................................................... 0 Pa
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 L/s
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A06-R1-E.de travail G '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Nov 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 29,0 °C / 25,4 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 77 m² 11503 - 77 m² - -
Wall Transmission 85 m² 790 - 85 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 77 m² 644 - 77 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 80 m² 193 - 80 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 4588 W 4588 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 11470 W 11469 - 0 0 -
People 44 2966 1549 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 32153 1549 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A06-R1-E.de travail G '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 21 1,471 - 223 - 0
WINDOW 1 24 1,700 0,811 204 6149 0
NW EXPOSURE
WALL 22 1,471 - 85 - 0
WINDOW 1 4 1,700 0,811 34 296 0
N EXPOSURE
WALL 5 1,471 - 13 - 0
WINDOW 1 6 1,700 0,811 50 249 0
NE EXPOSURE
WALL 14 1,471 - 79 - 0
WINDOW 1 16 1,700 0,811 136 918 0
E EXPOSURE
WALL 5 1,471 - 77 - 0
WINDOW 1 6 1,700 0,811 50 729 0
SE EXPOSURE
WALL 17 1,471 - 313 - 0
WINDOW 1 20 1,700 0,811 170 3162 0
ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 23,4 22,6 52 2127,4 25294,7 25200,1 0,0 0,0 0,0
0100 22,8 22,6 52 2096,5 24894,7 24810,0 0,0 0,0 0,0
0200 22,2 22,6 52 2065,8 24499,7 24423,9 0,0 0,0 0,0
0300 21,8 22,6 52 2037,2 24134,3 24064,8 0,0 0,0 0,0
0400 21,4 22,6 52 2010,6 23796,2 23731,1 0,0 0,0 0,0
0500 21,3 22,6 52 1986,3 23489,3 23426,5 0,0 0,0 0,0
0600 21,5 22,6 52 2020,0 23955,3 23848,0 0,0 0,0 0,0
0700 22,1 22,6 52 2207,4 26482,0 26211,4 0,0 0,0 0,0
0800 23,2 22,7 51 2304,8 27788,9 27451,4 0,0 0,0 0,0
0900 24,7 22,7 51 2355,1 28455,7 28094,5 0,0 0,0 0,0
1000 26,4 22,7 51 2370,8 28651,1 28295,8 0,0 0,0 0,0
1100 28,4 22,7 51 2374,0 28677,9 28336,7 0,0 0,0 0,0
1200 30,2 22,7 51 2383,4 28791,5 28457,0 0,0 0,0 0,0
1300 31,6 22,7 51 2406,8 29097,1 28756,9 0,0 0,0 0,0
1400 32,6 22,7 51 2448,1 29648,8 29288,7 0,0 0,0 0,0
1500 32,9 22,7 51 2485,5 30144,6 29770,5 0,0 0,0 0,0
1600 32,6 22,7 51 2495,9 30269,0 29904,6 0,0 0,0 0,0
1700 31,7 22,7 51 2448,3 29600,0 29291,3 0,0 0,0 0,0
1800 30,5 22,7 51 2337,8 28081,9 27872,8 0,0 0,0 0,0
1900 29,0 22,6 51 2301,0 27586,6 27402,2 0,0 0,0 0,0
2000 27,4 22,6 51 2264,3 27095,2 26934,9 0,0 0,0 0,0
2100 26,2 22,6 51 2228,8 26623,3 26483,4 0,0 0,0 0,0
2200 25,0 22,6 52 2193,4 26156,3 26034,6 0,0 0,0 0,0
2300 24,1 22,6 52 2159,5 25712,3 25605,6 0,0 0,0 0,0
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
30
25
20
Load ( kW )
15
10
0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day
Zone: Zone 1
Data for July
25000
20000
W
15000
10000
5000
0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day
0,016
0,012
0,010
12 3
0,008
0,006
0,004
0,002
0,000
0 5 10 15 20 25 30 35
Temperature ( °C )
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
Total coil load ....................................................... 42,1 kW Load occurs at .................................................. Jul 1600
Sensible coil load .................................................. 39,4 kW OA DB / WB ................................................... 32,6 / 27,0 °C
Coil L/s at Jul 1600 .............................................. 3278 L/s Entering DB / WB ........................................... 22,7 / 16,2 °C
Max block L/s at Jul 1600 .................................... 3609 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s .......................................... 3609 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,936 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 5,4 Resulting RH .............................................................. 51 %
W/m² .................................................................. 184,0 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K
Actual max L/s at Jul 1600 ................................... 3609 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ........................................................ 3607 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 15,76 L/(s-m²) Fan static ...................................................................... 0 Pa
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 L/s
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A06-R2-E.de travail D '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 32,6 °C / 27,0 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 75 m² 10318 - 75 m² - -
Wall Transmission 60 m² 864 - 60 m² 0 -
Roof Transmission 229 m² 8312 - 229 m² 0 -
Window Transmission 75 m² 1110 - 75 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 80 m² 365 - 80 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 4580 W 4580 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 11450 W 11449 - 0 0 -
People 44 3159 2644 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 40156 2644 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A06-R2-E.de travail D '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 11 1,471 - 124 - 0
WINDOW 1 4 1,700 0,811 60 421 0
NW EXPOSURE
WALL 21 1,471 - 326 - 0
WINDOW 1 24 1,700 0,811 360 5260 0
NE EXPOSURE
WALL 2 1,471 - 48 - 0
WINDOW 1 20 1,700 0,811 300 2575 0
E EXPOSURE
WALL 5 1,471 - 108 - 0
WINDOW 1 6 1,700 0,811 89 715 0
SE EXPOSURE
WALL 14 1,471 - 189 - 0
WINDOW 1 16 1,700 0,811 240 1143 0
S EXPOSURE
WALL 7 1,471 - 68 - 0
WINDOW 1 4 1,700 0,811 60 202 0
H EXPOSURE
ROOF 229 1,137 - 8312 - 0
ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 23,4 22,6 53 2481,8 29403,0 29271,1 0,0 0,0 0,0
0100 22,8 22,5 53 2405,1 28417,3 28313,4 0,0 0,0 0,0
0200 22,2 22,5 53 2334,2 27512,4 27430,4 0,0 0,0 0,0
0300 21,8 22,5 53 2270,1 26701,9 26635,3 0,0 0,0 0,0
0400 21,4 22,5 53 2212,0 25972,9 25916,7 0,0 0,0 0,0
0500 21,3 22,5 53 2159,6 25321,3 25271,2 0,0 0,0 0,0
0600 21,5 22,5 53 2170,5 25491,9 25404,6 0,0 0,0 0,0
0700 22,1 22,5 53 2345,2 27799,1 27567,0 0,0 0,0 0,0
0800 23,2 22,5 53 2440,3 29054,4 28752,2 0,0 0,0 0,0
0900 24,7 22,6 53 2514,8 30036,5 29683,8 0,0 0,0 0,0
1000 26,4 22,6 52 2583,7 30943,7 30549,1 0,0 0,0 0,0
1100 28,4 22,6 52 2660,3 31953,1 31515,0 0,0 0,0 0,0
1200 30,2 22,6 52 2777,0 33498,6 32992,7 0,0 0,0 0,0
1300 31,6 22,7 52 2932,3 35566,1 34972,1 0,0 0,0 0,0
1400 32,6 22,7 52 3089,3 37663,4 36989,0 0,0 0,0 0,0
1500 32,9 22,7 51 3213,4 39317,8 38593,6 0,0 0,0 0,0
1600 32,6 22,7 51 3277,6 40156,4 39429,0 0,0 0,0 0,0
1700 31,7 22,7 51 3235,4 39534,9 38879,5 0,0 0,0 0,0
1800 30,5 22,7 52 3067,9 37216,6 36712,7 0,0 0,0 0,0
1900 29,0 22,7 52 2975,5 35952,0 35524,7 0,0 0,0 0,0
2000 27,4 22,6 52 2866,9 34482,3 34136,6 0,0 0,0 0,0
2100 26,2 22,6 52 2759,4 33042,9 32768,5 0,0 0,0 0,0
2200 25,0 22,6 52 2658,2 31703,2 31487,9 0,0 0,0 0,0
2300 24,1 22,6 52 2565,7 30491,8 30323,5 0,0 0,0 0,0
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
12 3 0,010
0,008
0,006
0,004
0,002
0,000
0 5 10 15 20 25 30 35
Temperature ( °C )
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
Total coil load ........................................................ 6,8 kW Load occurs at ................................................. Sep 0900
Sensible coil load ................................................... 6,4 kW OA DB / WB ................................................... 23,6 / 23,3 °C
Coil L/s at Sep 0900 ............................................. 529 L/s Entering DB / WB ........................................... 22,7 / 16,2 °C
Max block L/s at Sep 0900 .................................... 583 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s ........................................... 583 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,936 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 6,3 Resulting RH .............................................................. 51 %
W/m² .................................................................. 159,1 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K
Actual max L/s at Sep 0900 .................................. 583 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ......................................................... 582 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 13,64 L/(s-m²) Fan static ...................................................................... 0 Pa
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 L/s
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A06-R1-Espace lounge '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Sep 0900 HEATING DATA AT DES HTG
COOLING OA DB / WB 23,6 °C / 23,3 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 14 m² 2441 - 14 m² - -
Wall Transmission 17 m² 200 - 17 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 14 m² 39 - 14 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 36 m² 3 - 36 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 854 W 854 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2135 W 2135 - 0 0 -
People 12 809 422 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 6481 422 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A06-R1-Espace lounge '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SE EXPOSURE
WALL 6 1,471 - 70 - 0
WINDOW 1 4 1,700 0,811 11 666 0
E EXPOSURE
WALL 5 1,471 - 68 - 0
WINDOW 1 6 1,700 0,811 17 1238 0
NE EXPOSURE
WALL 6 1,471 - 63 - 0
WINDOW 1 4 1,700 0,811 11 536 0
ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 23,4 22,6 52 423,8 5043,1 5016,2 0,0 0,0 0,0
0100 22,8 22,6 52 417,1 4956,5 4931,4 0,0 0,0 0,0
0200 22,2 22,6 52 410,4 4871,5 4848,1 0,0 0,0 0,0
0300 21,8 22,6 52 404,5 4795,9 4773,5 0,0 0,0 0,0
0400 21,4 22,6 53 399,1 4728,0 4706,1 0,0 0,0 0,0
0500 21,3 22,5 53 394,2 4666,3 4644,6 0,0 0,0 0,0
0600 21,5 22,6 52 408,4 4859,5 4822,9 0,0 0,0 0,0
0700 22,1 22,7 52 472,2 5719,7 5631,0 0,0 0,0 0,0
0800 23,2 22,7 52 503,5 6140,9 6032,6 0,0 0,0 0,0
0900 24,7 22,7 51 517,1 6321,6 6209,1 0,0 0,0 0,0
1000 26,4 22,7 51 516,7 6309,5 6203,9 0,0 0,0 0,0
1100 28,4 22,7 51 508,3 6189,3 6095,7 0,0 0,0 0,0
1200 30,2 22,7 52 503,5 6118,8 6032,9 0,0 0,0 0,0
1300 31,6 22,7 52 504,0 6123,7 6040,1 0,0 0,0 0,0
1400 32,6 22,7 52 504,4 6125,6 6044,4 0,0 0,0 0,0
1500 32,9 22,7 52 501,9 6088,9 6012,1 0,0 0,0 0,0
1600 32,6 22,7 52 495,9 6005,6 5935,3 0,0 0,0 0,0
1700 31,7 22,7 52 486,0 5869,3 5807,9 0,0 0,0 0,0
1800 30,5 22,7 52 473,3 5696,3 5645,0 0,0 0,0 0,0
1900 29,0 22,7 52 464,3 5575,7 5530,2 0,0 0,0 0,0
2000 27,4 22,6 52 455,3 5455,7 5415,5 0,0 0,0 0,0
2100 26,2 22,6 52 446,8 5343,4 5307,6 0,0 0,0 0,0
2200 25,0 22,6 52 438,6 5235,1 5203,1 0,0 0,0 0,0
2300 24,1 22,6 52 430,9 5134,9 5105,9 0,0 0,0 0,0
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
4,0
3,5
3,0
2,5
2,0
1,5
1,0
0,5
0,0
00 02 04 06 08 10 12 14 16 18 20 22
01 03 05 07 09 11 13 15 17 19 21 23
Hour of Day
Zone: Zone 1
Data for July
3000
2500
2000
1500
1000
500
0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day
0,016
0,012
3
0,010
12
0,008
0,006
0,004
0,002
0,000
0 5 10 15 20 25 30 35
Temperature ( °C )
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
Total coil load ........................................................ 6,1 kW Load occurs at ................................................. Sep 1600
Sensible coil load ................................................... 5,8 kW OA DB / WB ................................................... 31,4 / 26,5 °C
Coil L/s at Sep 1600 ............................................. 480 L/s Entering DB / WB ........................................... 22,8 / 16,2 °C
Max block L/s at Sep 1600 .................................... 527 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s ........................................... 527 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,941 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 5,2 Resulting RH .............................................................. 51 %
W/m² .................................................................. 192,8 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K
Actual max L/s at Sep 1600 .................................. 527 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ......................................................... 527 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 16,59 L/(s-m²) Fan static ...................................................................... 0 Pa
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 L/s
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A06-R1-S.de réunion 1 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Sep 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 31,4 °C / 26,5 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 16 m² 2806 - 16 m² - -
Wall Transmission 14 m² 166 - 14 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 16 m² 210 - 16 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 8 m² 29 - 8 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 636 W 636 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1590 W 1590 - 0 0 -
People 6 431 361 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 5868 361 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A06-R1-S.de réunion 1 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NW EXPOSURE
WALL 7 1,471 - 78 - 0
WINDOW 1 8 1,700 0,811 105 1285 0
SW EXPOSURE
WALL 7 1,471 - 88 - 0
WINDOW 1 8 1,700 0,811 105 1521 0
ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 23,4 22,5 53 352,0 4158,0 4144,6 0,0 0,0 0,0
0100 22,8 22,5 53 344,6 4062,5 4051,5 0,0 0,0 0,0
0200 22,2 22,5 53 337,2 3969,3 3960,3 0,0 0,0 0,0
0300 21,8 22,5 53 330,3 3882,1 3874,7 0,0 0,0 0,0
0400 21,4 22,5 53 323,8 3800,7 3794,5 0,0 0,0 0,0
0500 21,3 22,5 53 317,9 3726,8 3721,3 0,0 0,0 0,0
0600 21,5 22,5 53 314,6 3686,7 3680,4 0,0 0,0 0,0
0700 22,1 22,5 53 319,6 3754,7 3742,5 0,0 0,0 0,0
0800 23,2 22,5 53 325,0 3825,9 3808,5 0,0 0,0 0,0
0900 24,7 22,5 53 331,2 3908,1 3885,7 0,0 0,0 0,0
1000 26,4 22,5 53 338,4 4001,9 3974,4 0,0 0,0 0,0
1100 28,4 22,5 53 346,4 4106,7 4074,2 0,0 0,0 0,0
1200 30,2 22,6 52 363,7 4333,2 4290,3 0,0 0,0 0,0
1300 31,6 22,6 52 388,2 4654,8 4598,4 0,0 0,0 0,0
1400 32,6 22,6 52 419,9 5073,9 5000,8 0,0 0,0 0,0
1500 32,9 22,7 51 450,3 5477,3 5390,1 0,0 0,0 0,0
1600 32,6 22,7 51 468,2 5714,0 5622,1 0,0 0,0 0,0
1700 31,7 22,7 51 455,0 5527,9 5451,7 0,0 0,0 0,0
1800 30,5 22,6 52 403,2 4826,3 4787,8 0,0 0,0 0,0
1900 29,0 22,6 52 394,0 4705,3 4671,9 0,0 0,0 0,0
2000 27,4 22,6 52 385,1 4587,7 4559,6 0,0 0,0 0,0
2100 26,2 22,6 52 376,5 4474,8 4451,3 0,0 0,0 0,0
2200 25,0 22,6 52 368,0 4363,7 4344,3 0,0 0,0 0,0
2300 24,1 22,5 52 359,8 4257,9 4241,8 0,0 0,0 0,0
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
3,5
3,0
2,5
2,0
1,5
1,0
0,5
0,0
00 02 04 06 08 10 12 14 16 18 20 22
01 03 05 07 09 11 13 15 17 19 21 23
Hour of Day
Zone: Zone 1
Data for July
5500
5000
4500
4000
3500
3000
W
2500
2000
1500
1000
500
0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day
0,016
0,012
0,010
12 3
0,008
0,006
0,004
0,002
0,000
0 5 10 15 20 25 30 35
Temperature ( °C )
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
Total coil load ....................................................... 13,3 kW Load occurs at ................................................. Jun 1600
Sensible coil load .................................................. 12,4 kW OA DB / WB ................................................... 32,0 / 27,0 °C
Coil L/s at Jun 1600 ............................................. 1027 L/s Entering DB / WB ........................................... 22,8 / 16,3 °C
Max block L/s at Jun 1600 ................................... 1130 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s .......................................... 1130 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,932 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 5,6 Resulting RH .............................................................. 51 %
W/m² .................................................................. 179,6 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K
Actual max L/s at Jun 1600 .................................. 1130 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ........................................................ 1129 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 15,31 L/(s-m²) Fan static ...................................................................... 0 Pa
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
12 3 0,010
0,008
0,006
0,004
0,002
0,000
0 5 10 15 20 25 30 35
Temperature ( °C )
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
Total coil load ........................................................ 5,2 kW Load occurs at ................................................. Jun 1600
Sensible coil load ................................................... 4,8 kW OA DB / WB ................................................... 32,0 / 27,0 °C
Coil L/s at Jun 1600 .............................................. 401 L/s Entering DB / WB ........................................... 22,8 / 16,3 °C
Max block L/s at Jun 1600 .................................... 441 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s ........................................... 441 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,930 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 6,0 Resulting RH .............................................................. 52 %
W/m² .................................................................. 165,8 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K
Actual max L/s at Jun 1600 ................................... 441 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ......................................................... 441 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 14,10 L/(s-m²) Fan static ...................................................................... 0 Pa
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
12 3 0,010
0,008
0,006
0,004
0,002
0,000
0 5 10 15 20 25 30 35
Temperature ( °C )
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
Total coil load ........................................................ 4,7 kW Load occurs at ................................................. Dec 1600
Sensible coil load ................................................... 4,4 kW OA DB / WB ................................................... 27,6 / 24,2 °C
Coil L/s at Dec 1600 ............................................. 364 L/s Entering DB / WB ........................................... 22,8 / 16,3 °C
Max block L/s at Dec 1600 .................................... 401 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s ........................................... 401 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,934 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 5,2 Resulting RH .............................................................. 51 %
W/m² .................................................................. 190,8 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K
Actual max L/s at Dec 1600 .................................. 401 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ......................................................... 400 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 16,29 L/(s-m²) Fan static ...................................................................... 0 Pa
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
0,016
0,012
3
0,010
12
0,008
0,006
0,004
0,002
0,000
0 5 10 15 20 25 30 35
Temperature ( °C )
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
Total coil load ........................................................ 6,3 kW Load occurs at ................................................. Dec 1600
Sensible coil load ................................................... 6,0 kW OA DB / WB ................................................... 27,6 / 24,2 °C
Coil L/s at Dec 1600 ............................................. 496 L/s Entering DB / WB ........................................... 22,7 / 16,2 °C
Max block L/s at Dec 1600 .................................... 547 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s ........................................... 547 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,951 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 7,2 Resulting RH .............................................................. 51 %
W/m² .................................................................. 139,4 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K
Actual max L/s at Dec 1600 .................................. 547 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ......................................................... 547 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 12,16 L/(s-m²) Fan static ...................................................................... 0 Pa
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
0,016
0,012
0,010
12 3
0,008
0,006
0,004
0,002
0,000
0 5 10 15 20 25 30 35
Temperature ( °C )
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
Total coil load ....................................................... 10,2 kW Load occurs at ................................................ Aug 1600
Sensible coil load ................................................... 9,8 kW OA DB / WB ................................................... 32,6 / 27,0 °C
Coil L/s at Aug 1600 ............................................. 812 L/s Entering DB / WB ........................................... 22,7 / 16,1 °C
Max block L/s at Aug 1600 .................................... 894 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s ........................................... 894 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,958 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 6,3 Resulting RH .............................................................. 51 %
W/m² .................................................................. 158,8 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K
Actual max L/s at Aug 1600 .................................. 894 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ......................................................... 894 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 13,93 L/(s-m²) Fan static ...................................................................... 0 Pa
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 L/s
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A06-R3-Espace lounge '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 32,6 °C / 27,0 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 14 m² 1532 - 14 m² - -
Wall Transmission 17 m² 323 - 17 m² 0 -
Roof Transmission 64 m² 2417 - 64 m² 0 -
Window Transmission 14 m² 209 - 14 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 36 m² 165 - 36 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1284 W 1284 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 3210 W 3210 - 0 0 -
People 12 809 422 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 9949 422 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A06-R3-Espace lounge '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SE EXPOSURE
WALL 6 1,471 - 94 - 0
WINDOW 1 4 1,700 0,811 60 341 0
E EXPOSURE
WALL 5 1,471 - 112 - 0
WINDOW 1 6 1,700 0,811 89 737 0
NE EXPOSURE
WALL 6 1,471 - 117 - 0
WINDOW 1 4 1,700 0,811 60 454 0
H EXPOSURE
ROOF 64 1,137 - 2417 - 0
ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 23,4 22,6 52 637,2 7575,7 7532,5 0,0 0,0 0,0
0100 22,8 22,6 52 618,7 7335,6 7300,2 0,0 0,0 0,0
0200 22,2 22,5 52 601,7 7116,6 7087,1 0,0 0,0 0,0
0300 21,8 22,5 52 586,5 6923,5 6898,0 0,0 0,0 0,0
0400 21,4 22,5 52 572,9 6752,1 6729,1 0,0 0,0 0,0
0500 21,3 22,5 52 560,7 6598,9 6577,4 0,0 0,0 0,0
0600 21,5 22,5 52 568,6 6711,6 6675,7 0,0 0,0 0,0
0700 22,1 22,6 52 628,1 7506,6 7417,6 0,0 0,0 0,0
0800 23,2 22,6 51 658,5 7912,1 7800,1 0,0 0,0 0,0
0900 24,7 22,6 51 678,8 8182,7 8057,2 0,0 0,0 0,0
1000 26,4 22,6 51 693,4 8375,4 8242,0 0,0 0,0 0,0
1100 28,4 22,6 51 706,6 8549,8 8410,1 0,0 0,0 0,0
1200 30,2 22,7 51 727,3 8826,1 8674,6 0,0 0,0 0,0
1300 31,6 22,7 51 754,4 9189,6 9022,3 0,0 0,0 0,0
1400 32,6 22,7 51 779,2 9522,2 9342,5 0,0 0,0 0,0
1500 32,9 22,7 51 796,5 9752,0 9566,9 0,0 0,0 0,0
1600 32,6 22,7 51 803,6 9840,8 9659,0 0,0 0,0 0,0
1700 31,7 22,7 51 798,4 9760,7 9591,5 0,0 0,0 0,0
1800 30,5 22,7 51 781,1 9516,0 9367,4 0,0 0,0 0,0
1900 29,0 22,7 51 759,0 9208,1 9081,4 0,0 0,0 0,0
2000 27,4 22,7 51 732,1 8839,2 8735,7 0,0 0,0 0,0
2100 26,2 22,6 51 705,3 8477,4 8394,2 0,0 0,0 0,0
2200 25,0 22,6 51 680,3 8142,8 8076,4 0,0 0,0 0,0
2300 24,1 22,6 51 657,7 7842,9 7789,6 0,0 0,0 0,0
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
12 3 0,010
0,008
0,006
0,004
0,002
0,000
0 5 10 15 20 25 30 35
Temperature ( °C )
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
Total coil load ........................................................ 7,3 kW Load occurs at ................................................. Sep 1600
Sensible coil load ................................................... 6,9 kW OA DB / WB ................................................... 31,4 / 26,5 °C
Coil L/s at Sep 1600 ............................................. 576 L/s Entering DB / WB ........................................... 22,7 / 16,2 °C
Max block L/s at Sep 1600 .................................... 635 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s ........................................... 635 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,950 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 4,4 Resulting RH .............................................................. 51 %
W/m² .................................................................. 229,1 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K
Actual max L/s at Sep 1600 .................................. 635 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ......................................................... 634 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 19,96 L/(s-m²) Fan static ...................................................................... 0 Pa
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 L/s
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A06-R3-S.de réunion 1 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Sep 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 31,4 °C / 26,5 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 16 m² 2806 - 16 m² - -
Wall Transmission 14 m² 166 - 14 m² 0 -
Roof Transmission 32 m² 1194 - 32 m² 0 -
Window Transmission 16 m² 210 - 16 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 8 m² 29 - 8 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 636 W 636 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1590 W 1590 - 0 0 -
People 6 431 361 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 7062 361 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A06-R3-S.de réunion 1 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NW EXPOSURE
WALL 7 1,471 - 78 - 0
WINDOW 1 8 1,700 0,811 105 1285 0
SW EXPOSURE
WALL 7 1,471 - 88 - 0
WINDOW 1 8 1,700 0,811 105 1521 0
H EXPOSURE
ROOF 32 1,137 - 1194 - 0
ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 23,4 22,5 52 396,0 4667,0 4643,9 0,0 0,0 0,0
0100 22,8 22,5 53 382,4 4495,5 4476,8 0,0 0,0 0,0
0200 22,2 22,5 53 369,8 4335,9 4320,7 0,0 0,0 0,0
0300 21,8 22,4 53 358,1 4190,5 4178,0 0,0 0,0 0,0
0400 21,4 22,4 53 347,4 4057,8 4047,3 0,0 0,0 0,0
0500 21,3 22,4 53 337,8 3938,6 3929,4 0,0 0,0 0,0
0600 21,5 22,4 53 331,2 3858,7 3849,1 0,0 0,0 0,0
0700 22,1 22,4 53 333,7 3894,3 3879,6 0,0 0,0 0,0
0800 23,2 22,4 53 338,4 3957,8 3937,4 0,0 0,0 0,0
0900 24,7 22,4 53 348,2 4084,5 4056,3 0,0 0,0 0,0
1000 26,4 22,5 53 363,3 4279,8 4241,7 0,0 0,0 0,0
1100 28,4 22,5 53 382,8 4530,5 4481,3 0,0 0,0 0,0
1200 30,2 22,5 52 413,6 4928,7 4863,0 0,0 0,0 0,0
1300 31,6 22,6 52 452,0 5428,0 5343,2 0,0 0,0 0,0
1400 32,6 22,6 52 496,5 6010,9 5905,2 0,0 0,0 0,0
1500 32,9 22,7 51 537,0 6546,3 6423,9 0,0 0,0 0,0
1600 32,6 22,7 51 561,5 6868,3 6739,8 0,0 0,0 0,0
1700 31,7 22,7 51 550,4 6710,0 6596,6 0,0 0,0 0,0
1800 30,5 22,6 52 495,9 5972,8 5897,4 0,0 0,0 0,0
1900 29,0 22,6 52 479,8 5759,1 5694,0 0,0 0,0 0,0
2000 27,4 22,6 52 461,7 5518,2 5464,4 0,0 0,0 0,0
2100 26,2 22,6 52 443,7 5281,7 5237,8 0,0 0,0 0,0
2200 25,0 22,5 52 426,5 5058,5 5023,1 0,0 0,0 0,0
2300 24,1 22,5 52 410,6 4853,7 4825,1 0,0 0,0 0,0
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
0,016
0,012
0,010
12 3
0,008
0,006
0,004
0,002
0,000
0 5 10 15 20 25 30 35
Temperature ( °C )
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
Total coil load ........................................................ 5,3 kW Load occurs at ................................................. Jun 1600
Sensible coil load ................................................... 5,0 kW OA DB / WB ................................................... 32,0 / 27,0 °C
Coil L/s at Jun 1600 .............................................. 412 L/s Entering DB / WB ........................................... 22,7 / 16,2 °C
Max block L/s at Jun 1600 .................................... 455 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s ........................................... 455 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,943 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 4,7 Resulting RH .............................................................. 51 %
W/m² .................................................................. 213,9 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K
Actual max L/s at Jun 1600 ................................... 455 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ......................................................... 454 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 18,49 L/(s-m²) Fan static ...................................................................... 0 Pa
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 L/s
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A06-R3-S.de réunion 2 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 32,0 °C / 27,0 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 8 m² 1825 - 8 m² - -
Wall Transmission 7 m² 107 - 7 m² 0 -
Roof Transmission 25 m² 870 - 25 m² 0 -
Window Transmission 8 m² 112 - 8 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 15 m² 64 - 15 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 492 W 492 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1230 W 1230 - 0 0 -
People 5 359 301 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 5059 301 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A06-R3-S.de réunion 2 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NW EXPOSURE
WALL 7 1,471 - 107 - 0
WINDOW 1 8 1,700 0,811 112 1825 0
H EXPOSURE
ROOF 25 1,137 - 870 - 0
ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 23,4 22,5 53 292,8 3457,8 3440,1 0,0 0,0 0,0
0100 22,8 22,5 53 283,1 3333,9 3319,6 0,0 0,0 0,0
0200 22,2 22,5 53 274,0 3219,2 3207,6 0,0 0,0 0,0
0300 21,8 22,5 53 265,8 3116,2 3106,6 0,0 0,0 0,0
0400 21,4 22,5 53 258,4 3023,4 3015,2 0,0 0,0 0,0
0500 21,3 22,4 53 251,6 2939,5 2932,3 0,0 0,0 0,0
0600 21,5 22,4 53 246,5 2877,6 2870,3 0,0 0,0 0,0
0700 22,1 22,4 53 246,2 2876,8 2866,7 0,0 0,0 0,0
0800 23,2 22,4 53 248,0 2901,8 2888,2 0,0 0,0 0,0
0900 24,7 22,4 53 253,6 2975,9 2956,8 0,0 0,0 0,0
1000 26,4 22,5 53 263,5 3105,3 3078,9 0,0 0,0 0,0
1100 28,4 22,5 53 277,2 3281,8 3246,7 0,0 0,0 0,0
1200 30,2 22,5 52 301,7 3599,9 3550,4 0,0 0,0 0,0
1300 31,6 22,6 52 333,8 4019,9 3953,0 0,0 0,0 0,0
1400 32,6 22,7 52 366,3 4448,6 4365,6 0,0 0,0 0,0
1500 32,9 22,7 51 393,5 4810,2 4715,7 0,0 0,0 0,0
1600 32,6 22,7 51 409,8 5024,8 4926,5 0,0 0,0 0,0
1700 31,7 22,7 51 402,6 4921,0 4833,8 0,0 0,0 0,0
1800 30,5 22,7 52 365,4 4414,0 4355,0 0,0 0,0 0,0
1900 29,0 22,6 52 353,8 4258,0 4207,2 0,0 0,0 0,0
2000 27,4 22,6 52 340,6 4080,6 4038,7 0,0 0,0 0,0
2100 26,2 22,6 52 327,4 3906,5 3872,5 0,0 0,0 0,0
2200 25,0 22,6 52 314,9 3742,8 3715,5 0,0 0,0 0,0
2300 24,1 22,5 52 303,4 3593,4 3571,4 0,0 0,0 0,0
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
12 3 0,010
0,008
0,006
0,004
0,002
0,000
0 5 10 15 20 25 30 35
Temperature ( °C )
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
Total coil load ........................................................ 6,3 kW Load occurs at ................................................. Jun 1600
Sensible coil load ................................................... 5,9 kW OA DB / WB ................................................... 32,0 / 27,0 °C
Coil L/s at Jun 1600 .............................................. 490 L/s Entering DB / WB ........................................... 22,7 / 16,2 °C
Max block L/s at Jun 1600 .................................... 541 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s ........................................... 541 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,942 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 5,0 Resulting RH .............................................................. 51 %
W/m² .................................................................. 199,9 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K
Actual max L/s at Jun 1600 ................................... 541 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ......................................................... 541 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 17,28 L/(s-m²) Fan static ...................................................................... 0 Pa
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 L/s
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A06-R3-S.de réunion 3 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 32,0 °C / 27,0 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 8 m² 1825 - 8 m² - -
Wall Transmission 15 m² 290 - 15 m² 0 -
Roof Transmission 31 m² 1107 - 31 m² 0 -
Window Transmission 8 m² 112 - 8 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 15 m² 62 - 15 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 626 W 626 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1565 W 1565 - 0 0 -
People 6 431 361 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 6017 361 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A06-R3-S.de réunion 3 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NW EXPOSURE
WALL 7 1,471 - 107 - 0
WINDOW 1 8 1,700 0,811 112 1825 0
NE EXPOSURE
WALL 9 1,471 - 183 - 0
H EXPOSURE
ROOF 31 1,137 - 1107 - 0
ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 23,4 22,5 52 362,2 4291,3 4264,6 0,0 0,0 0,0
0100 22,8 22,5 53 350,8 4145,7 4123,4 0,0 0,0 0,0
0200 22,2 22,5 53 340,2 4010,4 3991,8 0,0 0,0 0,0
0300 21,8 22,5 53 330,5 3888,0 3872,1 0,0 0,0 0,0
0400 21,4 22,5 53 321,7 3776,7 3762,8 0,0 0,0 0,0
0500 21,3 22,5 53 313,5 3675,5 3662,9 0,0 0,0 0,0
0600 21,5 22,5 53 307,2 3597,1 3584,9 0,0 0,0 0,0
0700 22,1 22,4 53 305,7 3581,4 3566,4 0,0 0,0 0,0
0800 23,2 22,5 53 306,7 3597,4 3578,5 0,0 0,0 0,0
0900 24,7 22,5 53 312,6 3676,3 3650,9 0,0 0,0 0,0
1000 26,4 22,5 53 324,1 3827,7 3793,1 0,0 0,0 0,0
1100 28,4 22,5 53 340,5 4040,9 3994,9 0,0 0,0 0,0
1200 30,2 22,5 52 368,3 4404,9 4341,3 0,0 0,0 0,0
1300 31,6 22,6 52 403,9 4874,0 4789,5 0,0 0,0 0,0
1400 32,6 22,7 52 439,8 5348,7 5245,2 0,0 0,0 0,0
1500 32,9 22,7 51 469,8 5748,3 5631,2 0,0 0,0 0,0
1600 32,6 22,7 51 488,0 5989,1 5867,4 0,0 0,0 0,0
1700 31,7 22,7 51 481,9 5897,7 5787,9 0,0 0,0 0,0
1800 30,5 22,7 52 444,8 5388,1 5309,2 0,0 0,0 0,0
1900 29,0 22,7 52 432,1 5215,8 5147,0 0,0 0,0 0,0
2000 27,4 22,6 52 417,1 5013,8 4956,3 0,0 0,0 0,0
2100 26,2 22,6 52 402,1 4813,3 4765,7 0,0 0,0 0,0
2200 25,0 22,6 52 387,7 4623,9 4584,8 0,0 0,0 0,0
2300 24,1 22,6 52 374,4 4450,0 4417,8 0,0 0,0 0,0
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
12 3 0,010
0,008
0,006
0,004
0,002
0,000
0 5 10 15 20 25 30 35
Temperature ( °C )
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
Total coil load ........................................................ 5,4 kW Load occurs at ................................................. Dec 1600
Sensible coil load ................................................... 5,1 kW OA DB / WB ................................................... 27,6 / 24,2 °C
Coil L/s at Dec 1600 ............................................. 423 L/s Entering DB / WB ........................................... 22,7 / 16,2 °C
Max block L/s at Dec 1600 .................................... 466 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s ........................................... 466 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,944 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 4,6 Resulting RH .............................................................. 51 %
W/m² .................................................................. 219,0 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K
Actual max L/s at Dec 1600 .................................. 466 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ......................................................... 466 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 18,96 L/(s-m²) Fan static ...................................................................... 0 Pa
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 L/s
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A06-R3-S.de réunion 4 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 27,6 °C / 24,2 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 8 m² 2223 - 8 m² - -
Wall Transmission 7 m² 77 - 7 m² 0 -
Roof Transmission 25 m² 732 - 25 m² 0 -
Window Transmission 8 m² 51 - 8 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 15 m² 26 - 15 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 492 W 492 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1230 W 1230 - 0 0 -
People 5 359 301 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 5190 301 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A06-R3-S.de réunion 4 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 7 1,471 - 77 - 0
WINDOW 1 8 1,700 0,811 51 2223 0
H EXPOSURE
ROOF 25 1,137 - 732 - 0
ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 23,4 22,4 53 256,6 3006,7 2990,1 0,0 0,0 0,0
0100 22,8 22,4 53 248,9 2910,5 2896,5 0,0 0,0 0,0
0200 22,2 22,4 53 241,8 2822,2 2810,2 0,0 0,0 0,0
0300 21,8 22,4 54 235,5 2744,2 2733,7 0,0 0,0 0,0
0400 21,4 22,4 54 229,9 2675,0 2665,4 0,0 0,0 0,0
0500 21,3 22,4 54 224,9 2613,5 2604,5 0,0 0,0 0,0
0600 21,5 22,4 54 221,4 2572,5 2563,2 0,0 0,0 0,0
0700 22,1 22,4 54 222,8 2591,4 2579,1 0,0 0,0 0,0
0800 23,2 22,4 54 226,1 2634,9 2619,0 0,0 0,0 0,0
0900 24,7 22,4 54 233,2 2726,3 2705,1 0,0 0,0 0,0
1000 26,4 22,4 53 244,0 2864,9 2836,8 0,0 0,0 0,0
1100 28,4 22,4 53 257,7 3039,1 3003,2 0,0 0,0 0,0
1200 30,2 22,5 53 272,8 3232,7 3189,0 0,0 0,0 0,0
1300 31,6 22,5 53 287,8 3424,4 3373,7 0,0 0,0 0,0
1400 32,6 22,5 52 307,6 3679,3 3619,4 0,0 0,0 0,0
1500 32,9 22,6 52 327,1 3930,8 3862,7 0,0 0,0 0,0
1600 32,6 22,6 52 339,0 4083,4 4012,4 0,0 0,0 0,0
1700 31,7 22,6 52 335,9 4037,8 3972,9 0,0 0,0 0,0
1800 30,5 22,5 52 316,3 3776,8 3726,9 0,0 0,0 0,0
1900 29,0 22,5 52 307,0 3654,2 3611,0 0,0 0,0 0,0
2000 27,4 22,5 53 295,8 3508,6 3472,7 0,0 0,0 0,0
2100 26,2 22,5 53 284,8 3365,8 3336,3 0,0 0,0 0,0
2200 25,0 22,5 53 274,5 3232,8 3208,8 0,0 0,0 0,0
2300 24,1 22,5 53 265,1 3113,3 3093,5 0,0 0,0 0,0
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
0,016
0,012
0,010
12 3
0,008
0,006
0,004
0,002
0,000
0 5 10 15 20 25 30 35
Temperature ( °C )
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
Total coil load ........................................................ 7,6 kW Load occurs at ................................................. Nov 1600
Sensible coil load ................................................... 7,3 kW OA DB / WB ................................................... 28,7 / 25,3 °C
Coil L/s at Nov 1600 ............................................. 606 L/s Entering DB / WB ........................................... 22,7 / 16,1 °C
Max block L/s at Nov 1600 .................................... 672 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s ........................................... 672 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,959 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 5,9 Resulting RH .............................................................. 51 %
W/m² .................................................................. 168,9 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K
Actual max L/s at Nov 1600 .................................. 672 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ......................................................... 671 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 14,92 L/(s-m²) Fan static ...................................................................... 0 Pa
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 L/s
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A06-R3-S.de réunion 5 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Nov 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 28,7 °C / 25,3 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 8 m² 2106 - 8 m² - -
Wall Transmission 16 m² 252 - 16 m² 0 -
Roof Transmission 45 m² 1444 - 45 m² 0 -
Window Transmission 8 m² 67 - 8 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 40 m² 94 - 40 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 900 W 900 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2250 W 2250 - 0 0 -
People 5 359 301 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 7471 301 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A06-R3-S.de réunion 5 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 7 1,471 - 85 - 0
WINDOW 1 8 1,700 0,811 67 2106 0
SE EXPOSURE
WALL 9 1,471 - 168 - 0
H EXPOSURE
ROOF 45 1,137 - 1444 - 0
ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 23,4 22,5 52 415,7 4913,0 4873,4 0,0 0,0 0,0
0100 22,8 22,5 52 403,5 4757,3 4723,1 0,0 0,0 0,0
0200 22,2 22,5 52 392,3 4614,6 4584,8 0,0 0,0 0,0
0300 21,8 22,5 52 382,4 4490,6 4463,9 0,0 0,0 0,0
0400 21,4 22,4 52 373,7 4381,8 4357,1 0,0 0,0 0,0
0500 21,3 22,4 52 365,8 4284,2 4260,8 0,0 0,0 0,0
0600 21,5 22,4 53 359,8 4210,6 4187,1 0,0 0,0 0,0
0700 22,1 22,4 53 358,9 4202,8 4175,7 0,0 0,0 0,0
0800 23,2 22,4 53 361,9 4246,2 4213,0 0,0 0,0 0,0
0900 24,7 22,4 52 371,9 4378,2 4334,6 0,0 0,0 0,0
1000 26,4 22,5 52 388,8 4600,0 4542,1 0,0 0,0 0,0
1100 28,4 22,5 52 411,2 4892,1 4817,3 0,0 0,0 0,0
1200 30,2 22,5 52 436,4 5221,6 5129,6 0,0 0,0 0,0
1300 31,6 22,6 52 461,4 5549,4 5441,9 0,0 0,0 0,0
1400 32,6 22,6 51 490,1 5926,8 5802,4 0,0 0,0 0,0
1500 32,9 22,6 51 516,5 6274,3 6136,1 0,0 0,0 0,0
1600 32,6 22,6 51 532,7 6485,4 6342,5 0,0 0,0 0,0
1700 31,7 22,6 51 531,1 6455,9 6322,2 0,0 0,0 0,0
1800 30,5 22,6 51 510,0 6164,7 6053,8 0,0 0,0 0,0
1900 29,0 22,6 51 495,8 5971,4 5874,7 0,0 0,0 0,0
2000 27,4 22,6 52 478,2 5733,7 5652,6 0,0 0,0 0,0
2100 26,2 22,6 52 460,6 5499,2 5431,8 0,0 0,0 0,0
2200 25,0 22,5 52 444,1 5281,5 5225,5 0,0 0,0 0,0
2300 24,1 22,5 52 429,1 5086,4 5039,6 0,0 0,0 0,0
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
0,016
0,012
0,010
12 3
0,008
0,006
0,004
0,002
0,000
0 5 10 15 20 25 30 35
Temperature ( °C )
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
Total coil load ....................................................... 43,0 kW Load occurs at ................................................. Sep 1600
Sensible coil load .................................................. 40,1 kW OA DB / WB ................................................... 31,4 / 26,5 °C
Coil L/s at Sep 1600 ............................................ 3334 L/s Entering DB / WB ........................................... 22,7 / 16,3 °C
Max block L/s at Sep 1600 ................................... 3671 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s .......................................... 3671 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,934 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 6,1 Resulting RH .............................................................. 51 %
W/m² .................................................................. 162,9 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K
Actual max L/s at Sep 1600 ................................. 3671 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ........................................................ 3669 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 13,93 L/(s-m²) Fan static ...................................................................... 0 Pa
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 L/s
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A06-R1-S.de réunion 1 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Sep 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 31,4 °C / 26,5 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 16 m² 2806 - 16 m² - -
Wall Transmission 14 m² 166 - 14 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 16 m² 210 - 16 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 8 m² 29 - 8 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 636 W 636 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1590 W 1590 - 0 0 -
People 6 431 361 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 5868 361 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A06-R1-S.de réunion 1 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NW EXPOSURE
WALL 7 1,471 - 78 - 0
WINDOW 1 8 1,700 0,811 105 1285 0
SW EXPOSURE
WALL 7 1,471 - 88 - 0
WINDOW 1 8 1,700 0,811 105 1521 0
TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' A06-R1-Espace lounge '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Sep 0900 HEATING DATA AT DES HTG
COOLING OA DB / WB 23,6 °C / 23,3 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 14 m² 2441 - 14 m² - -
Wall Transmission 17 m² 200 - 17 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 14 m² 39 - 14 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 36 m² 3 - 36 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 854 W 854 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2135 W 2135 - 0 0 -
People 12 809 422 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 6481 422 - 0 0
TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' A06-R1-Espace lounge '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SE EXPOSURE
WALL 6 1,471 - 70 - 0
WINDOW 1 4 1,700 0,811 11 666 0
E EXPOSURE
WALL 5 1,471 - 68 - 0
WINDOW 1 6 1,700 0,811 17 1238 0
NE EXPOSURE
WALL 6 1,471 - 63 - 0
WINDOW 1 4 1,700 0,811 11 536 0
TABLE 1.3.A. COMPONENT LOADS FOR SPACE '' A06-R1-S.de réunion 2 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 32,0 °C / 27,0 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 8 m² 1825 - 8 m² - -
Wall Transmission 7 m² 107 - 7 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 8 m² 112 - 8 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 15 m² 64 - 15 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 492 W 492 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1230 W 1230 - 0 0 -
People 5 359 301 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 4189 301 - 0 0
TABLE 1.3.B. ENVELOPE LOADS FOR SPACE '' A06-R1-S.de réunion 2 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NW EXPOSURE
WALL 7 1,471 - 107 - 0
WINDOW 1 8 1,700 0,811 112 1825 0
TABLE 1.4.A. COMPONENT LOADS FOR SPACE '' A06-R1-S.de réunion 3 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 32,0 °C / 27,0 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 8 m² 1825 - 8 m² - -
Wall Transmission 15 m² 290 - 15 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 8 m² 112 - 8 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 15 m² 62 - 15 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 626 W 626 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1565 W 1565 - 0 0 -
People 6 431 361 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 4910 361 - 0 0
TABLE 1.4.B. ENVELOPE LOADS FOR SPACE '' A06-R1-S.de réunion 3 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NW EXPOSURE
WALL 7 1,471 - 107 - 0
WINDOW 1 8 1,700 0,811 112 1825 0
NE EXPOSURE
WALL 9 1,471 - 183 - 0
TABLE 1.5.A. COMPONENT LOADS FOR SPACE '' A06-R1-S.de reunion 4 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 27,6 °C / 24,2 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 8 m² 2223 - 8 m² - -
Wall Transmission 7 m² 77 - 7 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 8 m² 51 - 8 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 15 m² 26 - 15 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 492 W 492 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1230 W 1230 - 0 0 -
People 5 359 301 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 4458 301 - 0 0
TABLE 1.5.B. ENVELOPE LOADS FOR SPACE '' A06-R1-S.de reunion 4 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 7 1,471 - 77 - 0
WINDOW 1 8 1,700 0,811 51 2223 0
TABLE 1.6.A. COMPONENT LOADS FOR SPACE '' A06-R1-S.de réunion 5 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 27,6 °C / 24,2 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 8 m² 2223 - 8 m² - -
Wall Transmission 16 m² 233 - 16 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 8 m² 51 - 8 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 40 m² 70 - 40 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 900 W 900 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2250 W 2250 - 0 0 -
People 5 359 301 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 6085 301 - 0 0
TABLE 1.6.B. ENVELOPE LOADS FOR SPACE '' A06-R1-S.de réunion 5 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 7 1,471 - 77 - 0
WINDOW 1 8 1,700 0,811 51 2223 0
SE EXPOSURE
WALL 9 1,471 - 156 - 0
ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 23,4 22,6 52 2623,7 31176,7 31018,8 0,0 0,0 0,0
0100 22,8 22,6 53 2578,3 30582,3 30449,6 0,0 0,0 0,0
0200 22,2 22,6 53 2533,7 29999,0 29889,5 0,0 0,0 0,0
0300 21,8 22,5 53 2492,4 29464,0 29373,8 0,0 0,0 0,0
0400 21,4 22,5 53 2454,3 28972,1 28897,8 0,0 0,0 0,0
0500 21,3 22,5 53 2419,3 28523,5 28461,9 0,0 0,0 0,0
0600 21,5 22,5 53 2416,4 28499,0 28425,3 0,0 0,0 0,0
0700 22,1 22,6 53 2505,0 29684,8 29531,1 0,0 0,0 0,0
0800 23,2 22,6 53 2564,4 30478,1 30274,6 0,0 0,0 0,0
0900 24,7 22,6 52 2611,4 31106,3 30864,5 0,0 0,0 0,0
1000 26,4 22,6 52 2649,6 31616,5 31344,9 0,0 0,0 0,0
1100 28,4 22,6 52 2685,1 32090,7 31792,8 0,0 0,0 0,0
1200 30,2 22,6 52 2770,0 33227,1 32866,1 0,0 0,0 0,0
1300 31,6 22,6 52 2895,1 34904,4 34454,3 0,0 0,0 0,0
1400 32,6 22,7 52 3054,4 37052,8 36492,7 0,0 0,0 0,0
1500 32,9 22,7 52 3203,3 39065,6 38410,7 0,0 0,0 0,0
1600 32,6 22,7 51 3285,9 40174,9 39482,0 0,0 0,0 0,0
1700 31,7 22,7 52 3209,8 39100,3 38495,0 0,0 0,0 0,0
1800 30,5 22,7 52 2939,2 35393,8 35017,2 0,0 0,0 0,0
1900 29,0 22,6 52 2882,5 34632,0 34294,6 0,0 0,0 0,0
2000 27,4 22,6 52 2827,1 33883,1 33589,3 0,0 0,0 0,0
2100 26,2 22,6 52 2773,8 33167,8 32913,3 0,0 0,0 0,0
2200 25,0 22,6 52 2721,1 32465,2 32247,1 0,0 0,0 0,0
2300 24,1 22,6 52 2671,0 31799,9 31614,1 0,0 0,0 0,0
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
0,016
0,012
3
0,010
12
0,008
0,006
0,004
0,002
0,000
0 5 10 15 20 25 30 35
Temperature ( °C )
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
Total coil load ....................................................... 43,0 kW Load occurs at ................................................. Sep 1600
Sensible coil load .................................................. 40,1 kW OA DB / WB ................................................... 31,4 / 26,5 °C
Coil L/s at Sep 1600 ............................................ 3334 L/s Entering DB / WB ........................................... 22,7 / 16,3 °C
Max block L/s at Sep 1600 ................................... 3671 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s .......................................... 3671 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,934 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 6,1 Resulting RH .............................................................. 51 %
W/m² .................................................................. 162,9 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K
Actual max L/s at Sep 1600 ................................. 3671 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ........................................................ 3669 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 13,93 L/(s-m²) Fan static ...................................................................... 0 Pa
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 L/s
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A06-R1-S.de réunion 1 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Sep 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 31,4 °C / 26,5 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 16 m² 2806 - 16 m² - -
Wall Transmission 14 m² 166 - 14 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 16 m² 210 - 16 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 8 m² 29 - 8 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 636 W 636 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1590 W 1590 - 0 0 -
People 6 431 361 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 5868 361 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A06-R1-S.de réunion 1 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NW EXPOSURE
WALL 7 1,471 - 78 - 0
WINDOW 1 8 1,700 0,811 105 1285 0
SW EXPOSURE
WALL 7 1,471 - 88 - 0
WINDOW 1 8 1,700 0,811 105 1521 0
TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' A06-R1-Espace lounge '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Sep 0900 HEATING DATA AT DES HTG
COOLING OA DB / WB 23,6 °C / 23,3 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 14 m² 2441 - 14 m² - -
Wall Transmission 17 m² 200 - 17 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 14 m² 39 - 14 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 36 m² 3 - 36 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 854 W 854 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2135 W 2135 - 0 0 -
People 12 809 422 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 6481 422 - 0 0
TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' A06-R1-Espace lounge '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SE EXPOSURE
WALL 6 1,471 - 70 - 0
WINDOW 1 4 1,700 0,811 11 666 0
E EXPOSURE
WALL 5 1,471 - 68 - 0
WINDOW 1 6 1,700 0,811 17 1238 0
NE EXPOSURE
WALL 6 1,471 - 63 - 0
WINDOW 1 4 1,700 0,811 11 536 0
TABLE 1.3.A. COMPONENT LOADS FOR SPACE '' A06-R1-S.de réunion 2 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 32,0 °C / 27,0 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 8 m² 1825 - 8 m² - -
Wall Transmission 7 m² 107 - 7 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 8 m² 112 - 8 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 15 m² 64 - 15 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 492 W 492 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1230 W 1230 - 0 0 -
People 5 359 301 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 4189 301 - 0 0
TABLE 1.3.B. ENVELOPE LOADS FOR SPACE '' A06-R1-S.de réunion 2 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NW EXPOSURE
WALL 7 1,471 - 107 - 0
WINDOW 1 8 1,700 0,811 112 1825 0
TABLE 1.4.A. COMPONENT LOADS FOR SPACE '' A06-R1-S.de réunion 3 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 32,0 °C / 27,0 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 8 m² 1825 - 8 m² - -
Wall Transmission 15 m² 290 - 15 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 8 m² 112 - 8 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 15 m² 62 - 15 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 626 W 626 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1565 W 1565 - 0 0 -
People 6 431 361 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 4910 361 - 0 0
TABLE 1.4.B. ENVELOPE LOADS FOR SPACE '' A06-R1-S.de réunion 3 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NW EXPOSURE
WALL 7 1,471 - 107 - 0
WINDOW 1 8 1,700 0,811 112 1825 0
NE EXPOSURE
WALL 9 1,471 - 183 - 0
TABLE 1.5.A. COMPONENT LOADS FOR SPACE '' A06-R1-S.de reunion 4 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 27,6 °C / 24,2 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 8 m² 2223 - 8 m² - -
Wall Transmission 7 m² 77 - 7 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 8 m² 51 - 8 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 15 m² 26 - 15 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 492 W 492 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1230 W 1230 - 0 0 -
People 5 359 301 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 4458 301 - 0 0
TABLE 1.5.B. ENVELOPE LOADS FOR SPACE '' A06-R1-S.de reunion 4 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 7 1,471 - 77 - 0
WINDOW 1 8 1,700 0,811 51 2223 0
TABLE 1.6.A. COMPONENT LOADS FOR SPACE '' A06-R1-S.de réunion 5 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 27,6 °C / 24,2 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 8 m² 2223 - 8 m² - -
Wall Transmission 16 m² 233 - 16 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 8 m² 51 - 8 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 40 m² 70 - 40 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 900 W 900 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2250 W 2250 - 0 0 -
People 5 359 301 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 6085 301 - 0 0
TABLE 1.6.B. ENVELOPE LOADS FOR SPACE '' A06-R1-S.de réunion 5 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 7 1,471 - 77 - 0
WINDOW 1 8 1,700 0,811 51 2223 0
SE EXPOSURE
WALL 9 1,471 - 156 - 0
ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 23,4 22,6 52 2623,7 31176,7 31018,8 0,0 0,0 0,0
0100 22,8 22,6 53 2578,3 30582,3 30449,6 0,0 0,0 0,0
0200 22,2 22,6 53 2533,7 29999,0 29889,5 0,0 0,0 0,0
0300 21,8 22,5 53 2492,4 29464,0 29373,8 0,0 0,0 0,0
0400 21,4 22,5 53 2454,3 28972,1 28897,8 0,0 0,0 0,0
0500 21,3 22,5 53 2419,3 28523,5 28461,9 0,0 0,0 0,0
0600 21,5 22,5 53 2416,4 28499,0 28425,3 0,0 0,0 0,0
0700 22,1 22,6 53 2505,0 29684,8 29531,1 0,0 0,0 0,0
0800 23,2 22,6 53 2564,4 30478,1 30274,6 0,0 0,0 0,0
0900 24,7 22,6 52 2611,4 31106,3 30864,5 0,0 0,0 0,0
1000 26,4 22,6 52 2649,6 31616,5 31344,9 0,0 0,0 0,0
1100 28,4 22,6 52 2685,1 32090,7 31792,8 0,0 0,0 0,0
1200 30,2 22,6 52 2770,0 33227,1 32866,1 0,0 0,0 0,0
1300 31,6 22,6 52 2895,1 34904,4 34454,3 0,0 0,0 0,0
1400 32,6 22,7 52 3054,4 37052,8 36492,7 0,0 0,0 0,0
1500 32,9 22,7 52 3203,3 39065,6 38410,7 0,0 0,0 0,0
1600 32,6 22,7 51 3285,9 40174,9 39482,0 0,0 0,0 0,0
1700 31,7 22,7 52 3209,8 39100,3 38495,0 0,0 0,0 0,0
1800 30,5 22,7 52 2939,2 35393,8 35017,2 0,0 0,0 0,0
1900 29,0 22,6 52 2882,5 34632,0 34294,6 0,0 0,0 0,0
2000 27,4 22,6 52 2827,1 33883,1 33589,3 0,0 0,0 0,0
2100 26,2 22,6 52 2773,8 33167,8 32913,3 0,0 0,0 0,0
2200 25,0 22,6 52 2721,1 32465,2 32247,1 0,0 0,0 0,0
2300 24,1 22,6 52 2671,0 31799,9 31614,1 0,0 0,0 0,0
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
0,016
0,012
3
0,010
12
0,008
0,006
0,004
0,002
0,000
0 5 10 15 20 25 30 35
Temperature ( °C )
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
Total coil load ....................................................... 45,3 kW Load occurs at ................................................ Aug 1600
Sensible coil load .................................................. 42,8 kW OA DB / WB ................................................... 32,6 / 27,0 °C
Coil L/s at Aug 1600 ............................................ 3560 L/s Entering DB / WB ........................................... 22,7 / 16,2 °C
Max block L/s at Aug 1600 ................................... 3933 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s .......................................... 3933 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,946 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 5,4 Resulting RH .............................................................. 51 %
W/m² .................................................................. 183,9 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K
Actual max L/s at Aug 1600 ................................. 3933 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ........................................................ 3930 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 15,98 L/(s-m²) Fan static ...................................................................... 0 Pa
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 L/s
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A06-R3-S.de réunion 2 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 32,0 °C / 27,0 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 8 m² 1825 - 8 m² - -
Wall Transmission 7 m² 107 - 7 m² 0 -
Roof Transmission 25 m² 870 - 25 m² 0 -
Window Transmission 8 m² 112 - 8 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 15 m² 64 - 15 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 492 W 492 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1230 W 1230 - 0 0 -
People 5 359 301 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 5059 301 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A06-R3-S.de réunion 2 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NW EXPOSURE
WALL 7 1,471 - 107 - 0
WINDOW 1 8 1,700 0,811 112 1825 0
H EXPOSURE
ROOF 25 1,137 - 870 - 0
TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' A06-R3-Espace lounge '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 32,6 °C / 27,0 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 14 m² 1532 - 14 m² - -
Wall Transmission 17 m² 323 - 17 m² 0 -
Roof Transmission 64 m² 2417 - 64 m² 0 -
Window Transmission 14 m² 209 - 14 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 36 m² 165 - 36 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1284 W 1284 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 3210 W 3210 - 0 0 -
People 12 809 422 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 9949 422 - 0 0
TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' A06-R3-Espace lounge '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SE EXPOSURE
WALL 6 1,471 - 94 - 0
WINDOW 1 4 1,700 0,811 60 341 0
E EXPOSURE
WALL 5 1,471 - 112 - 0
WINDOW 1 6 1,700 0,811 89 737 0
NE EXPOSURE
WALL 6 1,471 - 117 - 0
WINDOW 1 4 1,700 0,811 60 454 0
H EXPOSURE
ROOF 64 1,137 - 2417 - 0
TABLE 1.3.A. COMPONENT LOADS FOR SPACE '' A06-R3-S.de réunion 1 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Sep 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 31,4 °C / 26,5 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 16 m² 2806 - 16 m² - -
Wall Transmission 14 m² 166 - 14 m² 0 -
Roof Transmission 32 m² 1194 - 32 m² 0 -
Window Transmission 16 m² 210 - 16 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 8 m² 29 - 8 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 636 W 636 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1590 W 1590 - 0 0 -
People 6 431 361 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 7062 361 - 0 0
TABLE 1.3.B. ENVELOPE LOADS FOR SPACE '' A06-R3-S.de réunion 1 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NW EXPOSURE
WALL 7 1,471 - 78 - 0
WINDOW 1 8 1,700 0,811 105 1285 0
SW EXPOSURE
WALL 7 1,471 - 88 - 0
WINDOW 1 8 1,700 0,811 105 1521 0
H EXPOSURE
ROOF 32 1,137 - 1194 - 0
TABLE 1.4.A. COMPONENT LOADS FOR SPACE '' A06-R3-S.de réunion 3 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 32,0 °C / 27,0 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 8 m² 1825 - 8 m² - -
Wall Transmission 15 m² 290 - 15 m² 0 -
Roof Transmission 31 m² 1107 - 31 m² 0 -
Window Transmission 8 m² 112 - 8 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 15 m² 62 - 15 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 626 W 626 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1565 W 1565 - 0 0 -
People 6 431 361 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 6017 361 - 0 0
TABLE 1.4.B. ENVELOPE LOADS FOR SPACE '' A06-R3-S.de réunion 3 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NW EXPOSURE
WALL 7 1,471 - 107 - 0
WINDOW 1 8 1,700 0,811 112 1825 0
NE EXPOSURE
WALL 9 1,471 - 183 - 0
H EXPOSURE
ROOF 31 1,137 - 1107 - 0
TABLE 1.5.A. COMPONENT LOADS FOR SPACE '' A06-R3-S.de réunion 4 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 27,6 °C / 24,2 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 8 m² 2223 - 8 m² - -
Wall Transmission 7 m² 77 - 7 m² 0 -
Roof Transmission 25 m² 732 - 25 m² 0 -
Window Transmission 8 m² 51 - 8 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 15 m² 26 - 15 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 492 W 492 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1230 W 1230 - 0 0 -
People 5 359 301 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 5190 301 - 0 0
TABLE 1.5.B. ENVELOPE LOADS FOR SPACE '' A06-R3-S.de réunion 4 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 7 1,471 - 77 - 0
WINDOW 1 8 1,700 0,811 51 2223 0
H EXPOSURE
ROOF 25 1,137 - 732 - 0
TABLE 1.6.A. COMPONENT LOADS FOR SPACE '' A06-R3-S.de réunion 5 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Nov 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 28,7 °C / 25,3 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 8 m² 2106 - 8 m² - -
Wall Transmission 16 m² 252 - 16 m² 0 -
Roof Transmission 45 m² 1444 - 45 m² 0 -
Window Transmission 8 m² 67 - 8 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 40 m² 94 - 40 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 900 W 900 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2250 W 2250 - 0 0 -
People 5 359 301 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 7471 301 - 0 0
TABLE 1.6.B. ENVELOPE LOADS FOR SPACE '' A06-R3-S.de réunion 5 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 7 1,471 - 85 - 0
WINDOW 1 8 1,700 0,811 67 2106 0
SE EXPOSURE
WALL 9 1,471 - 168 - 0
H EXPOSURE
ROOF 45 1,137 - 1444 - 0
ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 23,4 22,5 52 2644,4 31369,2 31146,8 0,0 0,0 0,0
0100 22,8 22,5 52 2563,2 30312,4 30135,4 0,0 0,0 0,0
0200 22,2 22,5 52 2487,9 29338,1 29199,9 0,0 0,0 0,0
0300 21,8 22,5 53 2420,2 28469,4 28362,7 0,0 0,0 0,0
0400 21,4 22,5 53 2359,1 27690,2 27608,8 0,0 0,0 0,0
0500 21,3 22,5 53 2303,8 26989,7 26928,5 0,0 0,0 0,0
0600 21,5 22,5 53 2280,4 26705,7 26641,5 0,0 0,0 0,0
0700 22,1 22,5 53 2342,5 27530,1 27403,8 0,0 0,0 0,0
0800 23,2 22,5 53 2389,3 28152,1 27980,7 0,0 0,0 0,0
0900 24,7 22,5 53 2453,4 28999,9 28773,3 0,0 0,0 0,0
1000 26,4 22,5 52 2541,3 30158,4 29863,1 0,0 0,0 0,0
1100 28,4 22,5 52 2651,9 31615,8 31240,0 0,0 0,0 0,0
1200 30,2 22,6 52 2818,0 33813,7 33322,0 0,0 0,0 0,0
1300 31,6 22,6 52 3020,3 36505,2 35878,4 0,0 0,0 0,0
1400 32,6 22,7 51 3235,3 39385,3 38621,2 0,0 0,0 0,0
1500 32,9 22,7 51 3420,1 41872,1 40999,4 0,0 0,0 0,0
1600 32,6 22,7 51 3527,9 43316,5 42396,4 0,0 0,0 0,0
1700 31,7 22,7 51 3485,6 42704,2 41848,3 0,0 0,0 0,0
1800 30,5 22,7 51 3263,3 39646,6 38979,6 0,0 0,0 0,0
1900 29,0 22,7 51 3166,2 38324,5 37736,4 0,0 0,0 0,0
2000 27,4 22,6 52 3051,7 36774,7 36277,4 0,0 0,0 0,0
2100 26,2 22,6 52 2938,1 35250,4 34837,2 0,0 0,0 0,0
2200 25,0 22,6 52 2831,1 33825,2 33486,3 0,0 0,0 0,0
2300 24,1 22,6 52 2733,2 32533,1 32257,6 0,0 0,0 0,0
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
12 3 0,010
0,008
0,006
0,004
0,002
0,000
0 5 10 15 20 25 30 35
Temperature ( °C )
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
Total coil load ....................................................... 74,9 kW Load occurs at .................................................. Jul 1600
Sensible coil load .................................................. 70,6 kW OA DB / WB ................................................... 32,6 / 27,0 °C
Coil L/s at Jul 1600 .............................................. 5868 L/s Entering DB / WB ........................................... 22,8 / 16,2 °C
Max block L/s at Jul 1600 .................................... 6454 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s .......................................... 6454 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,943 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 6,1 Resulting RH .............................................................. 51 %
W/m² .................................................................. 163,5 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K
Actual max L/s at Jul 1600 ................................... 6454 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ........................................................ 6450 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 14,09 L/(s-m²) Fan static ...................................................................... 0 Pa
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 L/s
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A06-R1-E.de travail D '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 32,0 °C / 27,0 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 75 m² 10501 - 75 m² - -
Wall Transmission 60 m² 817 - 60 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 75 m² 1039 - 75 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 80 m² 338 - 80 m² 10 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 4580 W 4580 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 11450 W 11449 - 0 0 -
People 44 2966 1549 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 31690 1549 - 10 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A06-R1-E.de travail D '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 11 1,471 - 112 - 0
WINDOW 1 4 1,700 0,811 56 380 0
NW EXPOSURE
WALL 21 1,471 - 321 - 0
WINDOW 1 24 1,700 0,811 337 5474 0
NE EXPOSURE
WALL 2 1,471 - 48 - 0
WINDOW 1 20 1,700 0,811 281 2677 0
E EXPOSURE
WALL 5 1,471 - 104 - 0
WINDOW 1 6 1,700 0,811 83 705 0
SE EXPOSURE
WALL 14 1,471 - 169 - 0
WINDOW 1 16 1,700 0,811 225 1066 0
S EXPOSURE
WALL 7 1,471 - 62 - 0
WINDOW 1 4 1,700 0,811 56 199 0
TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' A06-R2-E.de travail D '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 32,6 °C / 27,0 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 75 m² 10318 - 75 m² - -
Wall Transmission 60 m² 864 - 60 m² 0 -
Roof Transmission 229 m² 8312 - 229 m² 0 -
Window Transmission 75 m² 1110 - 75 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 80 m² 365 - 80 m² 10 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 4580 W 4580 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 11450 W 11449 - 0 0 -
People 44 3159 2644 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 40156 2644 - 10 0
TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' A06-R2-E.de travail D '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 11 1,471 - 124 - 0
WINDOW 1 4 1,700 0,811 60 421 0
NW EXPOSURE
WALL 21 1,471 - 326 - 0
WINDOW 1 24 1,700 0,811 360 5260 0
NE EXPOSURE
WALL 2 1,471 - 48 - 0
WINDOW 1 20 1,700 0,811 300 2575 0
E EXPOSURE
WALL 5 1,471 - 108 - 0
WINDOW 1 6 1,700 0,811 89 715 0
SE EXPOSURE
WALL 14 1,471 - 189 - 0
WINDOW 1 16 1,700 0,811 240 1143 0
S EXPOSURE
WALL 7 1,471 - 68 - 0
WINDOW 1 4 1,700 0,811 60 202 0
H EXPOSURE
ROOF 229 1,137 - 8312 - 0
ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 23,4 22,6 52 4628,3 54946,6 54731,4 0,0 0,0 0,0
0100 22,8 22,6 52 4519,7 53522,6 53366,4 0,0 0,0 0,0
0200 22,2 22,6 52 4417,4 52191,1 52085,9 0,0 0,0 0,0
0300 21,8 22,5 52 4324,5 50989,1 50925,0 0,0 0,0 0,0
0400 21,4 22,5 52 4239,8 49900,4 49869,2 0,0 0,0 0,0
0500 21,3 22,5 53 4163,2 48923,8 48917,7 0,0 0,0 0,0
0600 21,5 22,5 53 4208,3 49552,1 49478,2 0,0 0,0 0,0
0700 22,1 22,6 52 4572,0 54398,7 54022,6 0,0 0,0 0,0
0800 23,2 22,6 52 4764,4 56965,2 56445,6 0,0 0,0 0,0
0900 24,7 22,6 52 4887,3 58608,8 58001,1 0,0 0,0 0,0
1000 26,4 22,6 52 4968,6 59692,8 59031,8 0,0 0,0 0,0
1100 28,4 22,6 52 5041,2 60660,9 59954,7 0,0 0,0 0,0
1200 30,2 22,7 52 5179,3 62514,9 61714,8 0,0 0,0 0,0
1300 31,6 22,7 51 5390,9 65370,6 64426,3 0,0 0,0 0,0
1400 32,6 22,7 51 5613,7 68385,5 67298,1 0,0 0,0 0,0
1500 32,9 22,7 51 5788,2 70743,9 69559,4 0,0 0,0 0,0
1600 32,6 22,8 51 5868,5 71807,0 70603,2 0,0 0,0 0,0
1700 31,7 22,7 51 5766,9 70363,5 69281,9 0,0 0,0 0,0
1800 30,5 22,7 51 5449,4 65982,9 65178,8 0,0 0,0 0,0
1900 29,0 22,7 52 5313,1 64121,7 63427,3 0,0 0,0 0,0
2000 27,4 22,7 52 5162,2 62070,3 61496,4 0,0 0,0 0,0
2100 26,2 22,6 52 5014,7 60081,3 59617,2 0,0 0,0 0,0
2200 25,0 22,6 52 4874,8 58209,2 57842,2 0,0 0,0 0,0
2300 24,1 22,6 52 4746,1 56498,9 56214,7 0,0 0,0 0,0
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
12 3 0,010
0,008
0,006
0,004
0,002
0,000
0 5 10 15 20 25 30 35
Temperature ( °C )
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
Total coil load ....................................................... 75,2 kW Load occurs at ................................................. Oct 1600
Sensible coil load .................................................. 71,0 kW OA DB / WB ................................................... 30,3 / 25,9 °C
Coil L/s at Oct 1600 ............................................. 5899 L/s Entering DB / WB ........................................... 22,8 / 16,2 °C
Max block L/s at Oct 1600 ................................... 6492 L/s Leaving DB / WB ........................................... 12,8 / 12,2 °C
Sum of peak zone L/s .......................................... 6492 L/s Coil ADP .................................................................. 11,7 °C
Sensible heat ratio .............................................. 0,944 Bypass Factor ........................................................ 0,100
m²/kW .................................................................... 6,1 Resulting RH .............................................................. 51 %
W/m² .................................................................. 163,9 Design supply temp. ................................................ 12,8 °C
Water flow @ 5,6 °K rise ....................................... N/A Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0,0 °K
Actual max L/s at Oct 1600 .................................. 6492 L/s Fan motor BHP ........................................................ 0,00 BHP
Standard L/s ........................................................ 6488 L/s Fan motor kW .......................................................... 0,00 kW
Actual max L/(s-m²) ............................................ 14,15 L/(s-m²) Fan static ...................................................................... 0 Pa
Calculation Months .................................... Jan to Dec Zone L/s Sizing ....................... Peak zone sensible load
Sizing Data ................................................ Calculated Space L/s Sizing ............... Individual peak space loads
1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 0 L/s
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' A06-R1-E.de travail G '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Nov 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 29,0 °C / 25,4 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 77 m² 11503 - 77 m² - -
Wall Transmission 85 m² 790 - 85 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 77 m² 644 - 77 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 80 m² 193 - 80 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 4588 W 4588 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 11470 W 11469 - 0 0 -
People 44 2966 1549 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 32153 1549 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' A06-R1-E.de travail G '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 21 1,471 - 223 - 0
WINDOW 1 24 1,700 0,811 204 6149 0
NW EXPOSURE
WALL 22 1,471 - 85 - 0
WINDOW 1 4 1,700 0,811 34 296 0
N EXPOSURE
WALL 5 1,471 - 13 - 0
WINDOW 1 6 1,700 0,811 50 249 0
NE EXPOSURE
WALL 14 1,471 - 79 - 0
WINDOW 1 16 1,700 0,811 136 918 0
E EXPOSURE
WALL 5 1,471 - 77 - 0
WINDOW 1 6 1,700 0,811 50 729 0
SE EXPOSURE
WALL 17 1,471 - 313 - 0
WINDOW 1 20 1,700 0,811 170 3162 0
TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' A06-R2-E.de travail G '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Oct 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 30,3 °C / 25,9 °C HEATING OA DB / WB 22,0 °C / 22,0 °C
OCCUPIED T-STAT 22,0 °C OCCUPIED T-STAT 21,0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 77 m² 10703 - 77 m² - -
Wall Transmission 85 m² 1071 - 85 m² 0 -
Roof Transmission 229 m² 8224 - 229 m² 0 -
Window Transmission 77 m² 849 - 77 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 80 m² 260 - 80 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 4588 W 4588 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 11470 W 11469 - 0 0 -
People 44 3159 2644 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 40323 2644 - 0 0
TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' A06-R2-E.de travail G '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 21 1,471 - 271 - 0
WINDOW 1 24 1,700 0,811 268 5553 0
NW EXPOSURE
WALL 22 1,471 - 182 - 0
WINDOW 1 4 1,700 0,811 45 488 0
N EXPOSURE
WALL 5 1,471 - 30 - 0
WINDOW 1 6 1,700 0,811 66 248 0
NE EXPOSURE
WALL 14 1,471 - 154 - 0
WINDOW 1 16 1,700 0,811 179 1115 0
E EXPOSURE
WALL 5 1,471 - 99 - 0
WINDOW 1 6 1,700 0,811 66 723 0
SE EXPOSURE
WALL 17 1,471 - 336 - 0
WINDOW 1 20 1,700 0,811 224 2576 0
H EXPOSURE
ROOF 229 1,137 - 8224 - 0
ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 23,4 22,6 52 4585,9 54455,3 54177,4 0,0 0,0 0,0
0100 22,8 22,6 52 4482,9 53106,9 52886,3 0,0 0,0 0,0
0200 22,2 22,5 52 4385,4 51837,7 51667,1 0,0 0,0 0,0
0300 21,8 22,5 52 4296,4 50687,1 50557,4 0,0 0,0 0,0
0400 21,4 22,5 53 4215,0 49641,0 49544,4 0,0 0,0 0,0
0500 21,3 22,5 53 4141,3 48700,0 48629,2 0,0 0,0 0,0
0600 21,5 22,5 53 4187,8 49344,5 49206,7 0,0 0,0 0,0
0700 22,1 22,6 52 4549,9 54165,1 53725,9 0,0 0,0 0,0
0800 23,2 22,6 52 4741,9 56723,1 56141,0 0,0 0,0 0,0
0900 24,7 22,6 52 4866,0 58377,8 57707,6 0,0 0,0 0,0
1000 26,4 22,6 52 4950,2 59500,3 58775,3 0,0 0,0 0,0
1100 28,4 22,6 52 5033,3 60606,6 59829,3 0,0 0,0 0,0
1200 30,2 22,6 52 5142,9 62072,8 61225,1 0,0 0,0 0,0
1300 31,6 22,7 52 5284,0 63965,5 63027,2 0,0 0,0 0,0
1400 32,6 22,7 51 5453,7 66250,7 65205,0 0,0 0,0 0,0
1500 32,9 22,7 51 5598,3 68194,3 67067,5 0,0 0,0 0,0
1600 32,6 22,7 51 5664,0 69058,4 67916,5 0,0 0,0 0,0
1700 31,7 22,7 51 5583,6 67921,0 66877,8 0,0 0,0 0,0
1800 30,5 22,7 52 5344,2 64628,6 63798,4 0,0 0,0 0,0
1900 29,0 22,7 52 5222,4 62968,7 62239,4 0,0 0,0 0,0
2000 27,4 22,6 52 5084,3 61096,4 60478,8 0,0 0,0 0,0
2100 26,2 22,6 52 4948,0 59261,3 58746,3 0,0 0,0 0,0
2200 25,0 22,6 52 4817,5 57518,5 57095,4 0,0 0,0 0,0
2300 24,1 22,6 52 4696,8 55916,8 55572,6 0,0 0,0 0,0
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2945,5 W/(L/s)
Site Altitude = 5,8 m
0,016
0,012
0,010
12 3
0,008
0,006
0,004
0,002
0,000
0 5 10 15 20 25 30 35
Temperature ( °C )