You are on page 1of 3

PCS-9881/ 9882

Ethernet Switch

PCS-9881 and PCS-9882 Ethernet switches are intended


for the interconnection of 10/100/1000M adaptive Ethernet
devices using twisted-wire/Fiber optical connection in
substation automation system. It adopts industrial level
components and chips to ensure the reliable and high-
Functions speed data exchange so as to compensate the insufficient
application of commercial switch in a substation automation
system. The PCS-9881 and PCS-9882 are fully compatible
Fully compatible with IEC 61850, GOOSE and smart
with IEC 61850 and GOOSE communication in a smart
substation
substation automation system with distributed network or ring
• Support QoS (IEEE 802.1p) message priority contro. network.
Four queues are provided to ensure the priority of
important message in GOOSE.
• Message from two or more interfaces can be integrated
to supervisory port via mirror image technology.
• Single-mode and multi-mode optical transceiver are • Link aggregation: support link aggregation based on
available. port, MAC address, and etc.
• QoS control: support message priority control based
Ethernet Interfaces
on IEEE 802.1p and strict priority & weighted priority
• Ten 10/100M/1000Mbps self-adaptive ethernet ports, strategy.
supporting MDI/MDIX automatic identification, adaptive
to crossover and straight-through network cable. VLAN
• The 100Mbps fiber ports adopt SFP slot, the optical • Supporting port-based VLAN
transceiver complying with IEEE802.3 100BASE-FX • Supporting IEEE 802.1Q-based VLAN
fiber ethernet standard can be adopted to support hot
• Supporting the intercross VLANs setup.
plugging.
• Supporting inserting, modifying or deleting the VLAN
• Six 1000Mbps SFP slots complying with IEEE802.3
tags of messages.
1000BASE-SX 1000Mbps ethernet (1.25GBd) standard
can be adopted to support hot plugging.
Supporting Redundant Ring Net
• Switching mode adopts non-blocking store and forward.
• Supporting STP (802.1D) and RSTP (802.1w), fast
• Supporting 802.3x Flow Control. switch to backup link in case of communication link
failure.
Flow Control
• Supporting connection via ring net.
• Networking storm suppression: set the upper limit
of forwarding rate of broadcasting, multicasting and Management
addressing-failure message of switches. • Supporting command line management such as Web,
• Port rate control: set the upper limit of message Telnet and CLI.
forwarding rate and burst rate of each port. • Supporting simple network management protocol
• Flow imaging function: monitor the inflow/outflow data SNMP v1/v2c.
from other ports to a specified port.

Technical Data
AC Power Supply
Rated Voltage (Un) 110V AC, 220V AC
Variation (80% ~ 120%)Un
500ms for interruption without de-energizing, dips 60% of Un without reset up to 12 cycles;
Voltage dips and voltage
dips 30% of Un without reset up to 30 cycles;
short interruptions (IEC 61000-4-11:2004)
dips 20% of Un without reset up to 300 cycles

Read more on the web


www.nrelect.com read more on www.nrelect.com 297
PCS-9882A, PCS-9882C, PCS-9882D: <20W
Burden
PCS-9882B: <40W

DC Power Supply
110V DC, 125V DC, 220V DC, 250V DC;
Rated Voltage (Un)
48V DC power supply is available if a specified power supply module is selected
Variation (80% ~ 120%)Un
IEC 61000-4-17:2002
Ripple in the DC auxiliary voltage
Max 15% of the DC value.
IEC 61000-4-29:2000
Voltage dips and voltage short interruptions
20ms for interruption without de-energizing, dips 60% of Un without reset up to 100ms
PCS-9881: <13W
PCS-9882A: <10W
Burden (no load) PCS-9882B: <9W
PCS-9882C: <8W
PCS-9882D: <8W
PCS-9881: <26W
PCS-9882A: <16W
Burden (Full load) PCS-9882B: <31W
PCS-9882C: <14W
PCS-9882D: <14W

Mechanical Specifications
Enclosure dimensions (WxHxD) 482.6 ×44.4 ×216 (Unit: mm)
Trepanning dimensions 450×44.45 (unit: mm), M6 screw
Upper/Left/Right side: IP50
Protection class Front side: IP40, up to IP51
Rear side: IP30

Atmospheric Environment
Standard IEC60255-6:1988
Service temperature range -25°C ~ +55°C
Transport and storage temperature range -40°C ~ +70°C
Permissible humidity 5% ~ 95%, condensation not permissible

Communication Interfaces
Interface Type RJ45
Transmission Rate 100Mbits/s
100Mbits/s Ethernet Port Transmission standard 10Base-T/100Base-TX
Transmission distance < 100 meters
Safety level Isolation to ELV level
Characteristic Glass optical fiber
Connector type LC
Transmission standard 100Base-FX
50/125 multi mode fiber
100Mbits/s Optical Fiber Port
Fiber type 62.5/125 multi mode fiber
9/125 single mode fiber
Multi mode: <2km
Transmission distance
Single mode: <40km
Characteristic Glass optical fiber
Connector type LC
Transmission standard 100Base-FX
50/125 multi mode fiber
Fiber type 62.5/125 multi mode fiber
1000Mbits/s Optical Fiber Port 9/125 single mode fiber
Multi mode: <500m
Single mode: <10km
Transmission distance If procured by users themselves, the
transmission distance is subject to
the SFP transceiver module.

Read more on the web


298 read more on www.nrelect.com www.nrelect.com
Type test
- Environmental tests
Dry cold test Per IEC60068-2-1:2007
Dry heat test Per IEC60068-2-2:2007
Damp heat test, cyclic Per IEC60068-2-30:2005

- Mechanical tests
Vibration Per IEC 60255-21-1:1988 Class I
Shock and bump Per IEC 60255-21-2:1988 Class I

- Electrical tests
Standard IEC 60255-27:2005
Dielectric tests Test voltage 2kV, 50Hz, 1min
Standard IEC 60255-5:2000
Impulse voltage tests Test voltage 5kV
Overvoltage category III
Insulation resistance measurements Isolation resistance >100MΩ@500VDC

- Electromagnetic Compatibility
Per IEC 60255-22-1:2007
1MHz burst disturbance test Common mode: class III 2.5kV
Differential mode: class III 1.0kV
Per IEC60255-22-2:2008 class IV
Electrostatic discharge test For contact discharge: 8kV
For air discharge: 15kV
Radio frequency interference tests Per IEC 60255-22-3:2007 class III
Frequency sweep
- Radiated amplitude-modulated 10V/m(rms), f=80…1000MHz
Spot frequency
- Radiated amplitude-modulated 10Vm(rms), f=80MHz/160MHz/450MHz/900MHz
- Radiated pulse-modulated 10Vm(rms), f=900MHz
Per IEC 60255-22-4:2008
Fast transient disturbance tests Power supply, I/O, Earth: class IV, 4kV, 2.5kHz, 5/50ns
Communication terminals: class IV, 2kV, 5kHz, 5/50ns
Per IEC 60255-22-5:2008
Power supply, AC input, I/O port: class IV, 1.2/50us
Surge immunity test Common mode: 4kV
Differential mode: 2kV
Per IEC 60255-22-6:2001
Conducted RF Electromagnetic Disturbance
Power supply, AC, I/O, Comm. Terminal: Class III, 10Vrms, 150 kHz~80MHz
Per IEC 61000-4-8:2001
Power Frequency Magnetic Field Immunity
class V, 100A/m for 1min, 1000A/m for 3s
Per IEC 61000-4-9:2001
Pulse Magnetic Field Immunity
class V, 6.4/16μs, 1000A/m for 3s
IEC 61000-4-10:2001
Damped oscillatory magnetic field immunity
class V, 100kHz & 1MHz–100A/m
IEC60255-11: 2008
Auxiliary power supply performance Voltage dips: Up to 300ms for dips to 40% of rated voltage without reset
Voltage short interruptions: 100ms for interruption without rebooting