You are on page 1of 11

NI LabVIEW Electrical Power Suite

Mediciones de Potencia
Worldwide Technical Support and Product Information
ni.com
National Instruments Corporate Headquarters
11500 N Mopac Expwy Austin, Texas 78759-3504 USA Tel: 512 683 0100
Worldwide Offices
Andean and Caribbean +58 212 503-5310, Argentina 0800 666 0037, Australia 1800 300 800, Austria 43 662 45 79 90 0, Belgium 32
0 2 757 00 20, Brazil 55 11 3262 3599, Canada 800 433 3488, Chile 800 532 951, China 86 21 5050 9800, Czech Republic/Slovakia
420 224 235 774, Denmark 45 45 76 26 00, Finland 358 0 9 725 725 11, France 33 0 1 48 14 24 24, Germany 49 89 741 31 30,
Hungary 36 23 501 580, India 1 800 425 7070, Ireland 353 0 1867 4374, Israel 972 3 6393737, Italy 39 02 413091, Japan 81 3 5472
2970, Korea 82 02 3451 3400, Lebanon 961 0 1 33 28 28, Malaysia 1800 887710, Mexico 01 800 010 0793, Netherlands 31 0 348 433
466, New Zealand 0800 553 322, Norway 47 0 66 90 76 60, Poland 48 22 3390150, Portugal 351 210 311 210, Russia 7 495 783 68
51, Singapore 1800 226 5886, Slovenia/Croatia, Bosnia/Herzegovina, Serbia/Montenegro, Macedonia 386 3 425 42 00, South Africa
27 0 11 805 8197, Spain 34 91 640 0085, Sweden 46 0 8 587 895 00, Switzerland 41 56 200 51 51, Taiwan 886 2 2377 2222,
Thailand 662 278 6777, Turkey 90 212 279 3031, U.K. 44 0 1635 523545, Uruguay 0004 055 114
To comment on National Instruments documentation, refer to the National Instruments Web site at ni.com/info and enter the
info code feedback.
© 2013 National Instruments Corporation. All rights reserved.
Important Information
Warranty
The media on which you receive National Instruments software are warranted not to fail to execute programming instructions, due to defects in materials and
workmanship, for a period of 90 days from date of shipment, as evidenced by receipts or other documentation. National Instruments will, at its option, repair
or replace software media that do not execute programming instructions if National Instruments receives notice of such defects during the warranty period.
National Instruments does not warrant that the operation of the software shall be uninterrupted or error free. A Return Material Authorization (RMA) number
must be obtained from the factory and clearly marked on the outside of the package before any equipment will be accepted for warranty work. National
Instruments will pay the shipping costs of returning to the owner parts which are covered by warranty. National Instruments believes that the information in
this document is accurate. The document has been carefully reviewed for technical accuracy. In the event that technical or typographical errors exist,
National Instruments reserves the right to make changes to subsequent editions of this document without prior notice to holders of this edition. The reader
should consult National Instruments if errors are suspected. In no event shall National Instruments be liable for any damages arising out of or related to this
document or the information contained in it. EXCEPT AS SPECIFIED HEREIN, NATIONAL INSTRUMENTS MAKES NO WARRANTIES, EXPRESS OR IMPLIED, AND
SPECIFICALLY DISCLAIMS ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. CUSTOMER’S RIGHT TO RECOVER DAMAGES CAUSED
BY FAULT OR NEGLIGENCE ON THE PART OF NATIONAL INSTRUMENTS SHALL BE LIMITED TO THE AMOUNT THERETOFORE PAID BY THE
CUSTOMER. NATIONAL INSTRUMENTS WILL NOT BE LIABLE FOR DAMAGES RESULTING FROM LOSS OF DATA, PROFITS, USE OF PRODUCTS,
OR INCIDENTAL OR CONSEQUENTIAL DAMAGES, EVEN IF ADVISED OF THE POSSIBILITY THEREOF. This limitation of the liability of National
Instruments will apply regardless of the form of action, whether in contract or tort, including negligence. Any action against National Instruments must be
brought
within one year after the cause of action accrues. National Instruments shall not be liable for any delay in performance due to causes beyond its reasonable
control. The warranty provided herein does not cover damages, defects, malfunctions, or service failures caused by owner’s failure to follow the National
Instruments installation, operation, or maintenance instructions; owner’s modification of the product; owner’s abuse, misuse, or negligent acts; and power
failure or surges, fire, flood, accident, actions of third parties, or other events outside reasonable control.
Copyright
Under the copyright laws, this publication may not be reproduced or transmitted in any form, electronic or mechanical, including photocopying, recording,
storing in an information retrieval system, or translating, in whole or in part, without the prior written consent of National Instruments Corporation. National
Instruments respects the intellectual property of others, and we ask our users to do the same. NI software is protected by copyright and other intellectual
property laws. Where NI software may be used to reproduce software or other materials belonging to others, you may use NI software only to reproduce
materials that you may reproduce in accordance with the terms of any applicable license or other legal restriction. BSIM3 and BSIM4 are developed by the
Device Research Group of the Department of Electrical Engineering and Computer Science, University of California, Berkeley, and copyrighted by the University
of California.
Trademarks
CompactDAQ, CompactRIO, LabVIEW, National Instruments, and NI, ni.com are trademarks of National Instruments Corporation. Refer to the Terms of Use
section on ni.com/legal for more information about National Instruments trademarks. Other product and company names mentioned herein are trademarks or
trade names of their respective companies.
Patents
For patents covering National Instruments products, refer to ni.com/patents.
Some portions of this product are protected under United States Patent No. 6,560,572.
WARNING REGARDING USE OF NATIONAL INSTRUMENTS PRODUCTS
(1) NATIONAL INSTRUMENTS PRODUCTS ARE NOT DESIGNED WITH COMPONENTS AND TESTING FOR A LEVEL OF RELIABILITY SUITABLE
FOR USE IN OR IN CONNECTION WITH SURGICAL IMPLANTS OR AS CRITICAL COMPONENTS IN ANY LIFE SUPPORT SYSTEMS WHOSE
FAILURE TO PERFORM CAN REASONABLY BE EXPECTED TO CAUSE SIGNIFICANT INJURY TO A HUMAN.
(2) IN ANY APPLICATION, INCLUDING THE ABOVE, RELIABILITY OF OPERATION OF THE SOFTWARE PRODUCTS CAN BE IMPAIRED BY
ADVERSE FACTORS, INCLUDING BUT NOT LIMITED TO FLUCTUATIONS IN ELECTRICAL POWER SUPPLY, COMPUTER HARDWARE
MALFUNCTIONS, COMPUTER OPERATING SYSTEM SOFTWARE FITNESS, FITNESS OF COMPILERS AND DEVELOPMENT SOFTWARE USED TO
DEVELOP AN APPLICATION, INSTALLATION ERRORS, SOFTWARE AND HARDWARE COMPATIBILITY PROBLEMS, MALFUNCTIONS OR
FAILURES OF ELECTRONIC MONITORING OR CONTROL DEVICES, TRANSIENT FAILURES OF ELECTRONIC SYSTEMS (HARDWARE AND/OR
SOFTWARE), UNANTICIPATED USES OR MISUSES, OR ERRORS ON THE PART OF THE USER OR APPLICATIONS DESIGNER (ADVERSE FACTORS
SUCH AS THESE ARE HEREAFTER COLLECTIVELY TERMED “SYSTEM FAILURES”). ANY APPLICATION WHERE A SYSTEM FAILURE WOULD
CREATE A RISK OF HARM TO PROPERTY OR PERSONS (INCLUDING THE RISK OF BODILY INJURY AND DEATH) SHOULD NOT BE RELIANT
SOLELY UPON ONE FORM OF ELECTRONIC SYSTEM DUE TO THE RISK OF SYSTEM FAILURE. TO AVOID DAMAGE, INJURY, OR DEATH, THE
USER OR APPLICATION DESIGNER MUST TAKE REASONABLY PRUDENT STEPS TO PROTECT AGAINST SYSTEM FAILURES, INCLUDING BUT
NOT LIMITED TO BACK-UP OR SHUT DOWN MECHANISMS. BECAUSE EACH END-USER SYSTEM IS CUSTOMIZED AND DIFFERS FROM
NATIONAL INSTRUMENTS' TESTING PLATFORMS AND BECAUSE A USER OR APPLICATION DESIGNER MAY USE NATIONAL INSTRUMENTS
PRODUCTS IN COMBINATION WITH OTHER PRODUCTS IN A MANNER NOT EVALUATED OR CONTEMPLATED BY NATIONAL INSTRUMENTS,
THE USER OR APPLICATION DESIGNER IS ULTIMATELY RESPONSIBLE FOR VERIFYING AND VALIDATING THE SUITABILITY OF NATIONAL
INSTRUMENTS PRODUCTS WHENEVER NATIONAL INSTRUMENTS PRODUCTS ARE INCORPORATED IN A SYSTEM OR APPLICATION,
INCLUDING, WITHOUT LIMITATION, THE APPROPRIATE DESIGN, PROCESS AND SAFETY LEVEL OF SUCH SYSTEM OR APPLICATION.
Contenido
Requerimientos ..................................................................................................... 4
Software ...................................................................................................... 4
Hardware ..................................................................................................... 4
Ejercicio 1. Medición de Potencia ......................................................................... 5
Referencias ........................................................................................................ 11
Requerimientos
Software
 NI LabVIEW 13.0 o superior
 NI LabVIEW Electrical Power Suite

Hardware
 Computadora con LabVIEW 2013
Ejercicio 1. Medición de Potencia

Objetivo

 Identificar y medir las componentes de potencia suministradas a una carga simulada.

Introducción

Se denomina corriente alterna la corriente eléctrica en la que la magnitud y el


sentido varían cíclicamente.

La forma de oscilación de la corriente alterna más comúnmente utilizada es la


oscilación senoidal con la que se consigue una transmisión más eficiente de la energía, a tal
punto que al hablar de corriente alterna se sobrentiende que se refiere a la corriente alterna
senoidal.

El término de corriente alterna contempla que tanto la corriente y el voltaje son


transmitidos en forma de una señal cíclica, comúnmente de forma senoidal. Las señales de
voltaje y corriente, dependiendo de las propiedades de la carga puede que estén desfasadas
la una con la otra. Una carga puede tener las siguientes propiedades.

Resistencia: Oposición que tienen los electrones al moverse a través de un


conductor. No desfasa la corriente con respecto al voltaje.

Capacitancia: Propiedad que tienen los cuerpos para mantener una carga eléctrica.
Desfasa 90° la corriente del voltaje

Inductancia: Medida de la oposición a un cambio de corriente de un inductor o


bobina que almacena energía en presencia de un campo magnético.
Desfasa 90° la corriente del voltaje.

En la realidad no podremos encontrar cargas puramente resistivas, capacitivas o


inductivas. Por lo que dependiendo de sus propiedades, desfasaran cierto ángulo la corriente
del voltaje.

La potencia eléctrica es el producto del voltaje y de la corriente, ante los desfases


previamente mencionados de éstos dos, se utiliza una representación compleja de la
potencia, la cual comprende las siguientes componentes.

Aparente (S): Magnitud del vector, medida en VA (Volts Amperes).

Activa (P): Componente horizontal, potencia capaz transformar energía eléctrica


en trabajo, medida en W (Watts).

Reactiva (Q): Componente vertical, directamente proporcional a la reactancia ya sea


inductiva o capacitiva, medida en VAR (Volt Amperes Reactivos).
En la Figura 1 podemos ver la representación trigonométrica de la potencia compleja,
seguida por la formula que la describe.

Figura 1. Representación trigonométrica de la potencia compleja

Un término utilizado comúnmente para determinar el tipo de carga conectada a un


circuito de corriente alterna es el Factor de Potencia, el cual se define como la relación
entre la potencia activa, P, y la potencia aparente, S. Da una medida de la capacidad de una
carga de absorber potencia activa, por lo que:

 f.d.p = 1 en cargas puramente resistivas.


 f.d.p = 0 en elementos inductivos y capacitivos ideales sin resistencia.
Desarrollo

1. Abra NI LabVIEW, y abra el VI incluido en esta práctica llamado “Medición de Potencia


Solución.vi”.

2. Abrir el diagrama de bloques del programa con ayuda del comando Ctrl+E, se deberá
de ver como se muestra en la Figura 2.

Figura 2. Diagrama de bloques completo.

3. En la Figura 3 identificamos la primera parte del diagrama de bloques, en la cual


simularemos dos señales, las cuales serán de voltaje y corriente. Las dos serán de la
misma frecuencia, y a la señal de corriente le podremos modificar la fase. Todas las
entradas son ingresadas por controles, para que el usuario pueda variar los valores
desde el panel frontal.

Figura 3. Simulación de señales de voltaje y corriente.


4. En la Figura 4 encontramos en la parte superior la función de Build Array, la cual
creará un arreglo con las señales previamente simuladas de voltaje y corriente.
Posteriormente las graficaremos en un Waveform Chart. En la parte inferior de la
Figura 4 encontramos la función de Merge Errors, la cual nos permite unir la
información transmitida por los cables de error en un solo cable.

Figura 4. Graficación de señales simuladas y manejo de señal de error.

5. Después de haber generado las señales de voltaje y corriente, procederemos a


analizarlas con ayuda de la paleta de funciones incluida en el Electrical Power Suite,
en la Figura 5 podemos visualizar las funciones utilizadas de dicha paleta.

Figura 5. SubVIs de medición de parámetros de energía eléctrica.

 RMS: Entrega el voltaje RMS de la señal de voltaje de entrada.


 Frequency: Entrega la frecuencia de la señal de entrada.
 Fundamental Vector: Entrega vectores del voltaje y corriente respectivamente.
 Power: Entrega un cluster con la siguiente información de potencia:
-Potencia Aparente
-Potencia Real o Activa
-Potencia Reactiva
-Factor de Potencia
6. En el segmento del diagrama de bloques mostrado en la Figura 6 encontramos como
generemos un arreglo de los vectores obtenidos de las señales de voltaje y corriente,
posteriormente los graficaremos en su forma polar en el panel frontal. Adicionalmente
multiplicaremos los valores de voltaje por corriente para poder obtener la potencia, y
de igual forma graficarla en su forma polar.

Figura 6. Graficación polar del voltaje, corriente y potencia.

7. En la Figura 2 podemos visualizar que todo el programa está contenido en una


estructura cíclica While, ya que permite al programa ejecutarse cíclicamente y
procesar datos ingresados por el usuario al momento en que lo va modificando. Dicho
ciclo While, como se muestra en la Figura 7, solo finalizará si es que se produce algún
error en alguna parte del programa o si es que el usuario activa el botón de Stop.

Figura 7. Condición de terminación del ciclo While.

8. Al final del programa podemos encontrar el subVI llamado Simple Error Handler, el
cual desplegará una ventana de error si es que se produce un error a lo largo del
programa. Mostrado en la Figura 2.

9. Regresar al panel frontal del programa y ejecutar el VI. Notar la variación de las
distintas componentes de potencia dependiendo del ángulo de desfase entre la
corriente y el voltaje como se muestra en las Figuras 8 y 9.
Figura 8. Simulación de carga en su mayoría resistiva.

Figura 9. Simulación de carga con gran parte reactiva.

FIN DEL EJERCICIO


Referencias

1. LabVIEW Electrical Power Suite


http://sine.ni.com/nips/cds/view/p/lang/es/nid/210502

2. Corriente Alterna
http://es.wikipedia.org/wiki/Corriente_alterna

3. Potencia Eléctrica
http://es.wikipedia.org/wiki/Potencia_el%C3%A9ctrica#Potencia_aparente

4. Factor de Potencia
http://es.wikipedia.org/wiki/Factor_de_potencia