Professional Documents
Culture Documents
25, 2019
Location: Brgy. Tagapo, Sta. Rosa, Laguna Conducted by: Carlos A. Fabillar
Severity of shock
- Severity of shock is not determined by voltage alone but depends on:
1. Amount of current
2. Path/passage of current
3. Length of time of exposure
4. Type of current
5. Physical condition of victim
Electrical Risks
1. Burn by electrocution
2. Cardiac arrest by shock
3. Fire through sparks
4. Explosion by ignition
5. Burn by arc flashes
Hazard of electricity
- Electrical energy causing direct tissue damage, altering cell membrane resting
potential, and muscle paralysis tetany
- Conversion of electrical energy into thermal energy, causing massive tissue
destruction, and coagulative necrosis
- Mechanical injury with direct trauma resulting from falls and violent muscle
contraction
DC Electricity Hazards
- High voltage DC tends to cause a single muscle contraction, often throwing the
victim away from the source
- This result in a shorter duration of exposure but brief contact with a DC source can
also result in disturbances in the cardiac rhythm
AC Electricity Hazard
- AC exposure to the same voltage tends to be three times more dangerous than DC
current
- The repetitive nature of AC increases the likelihood of current delivery to the heart
during the vulnerable recovery period of the cardiac cycle, which can result to
ventricular fibrillation
- Electrical burns
First Degree – mild and injure only the outer layer of skin. The skin becomes red, but
turns white when touch. The area may also be painful to touch
Second Degree – deeper, more severe, and very painful. Blister may form on the
burned area. This type of burns takes 2 weeks to heal
Third Degree – deepest and most serious kind. The skin becomes white and leathery,
but it does not feel very tender when touched.
- Energized substation
Only qualified employee shall work on or adjacent to energized control panel
- Safe working distance from Power Lines
1. When operating near High Voltage Power Lines
Normal Voltage Minimum Required
Phase to Phase Clearance
50KV 10ft (3.1 m)
50KV – 200KV 15ft (4.3 m)
200 KV – 350 KV 20 ft (6.1 m)
5. Insulation
- Use double insulated Royal Cord for tools
- Provide good insulation for appliances
- Ensure insulation between feet and moist ground
6. Use appropriate PPE
7. Use LOTO
8. JHA
9. Only certified/authorize electrician is allowed to conduct activity
Best practices is regular inspection
1. Check that wiring, movable wires, switches and all electrical machines and
equipment are provided with complete insulation cover and enclosures
2. If faulty, they must be repaired immediately
3. Before using electrical equipment, check that the earth conductor is connected and
not damaged, and the earth pole is not floating
4. Before using welding machines, check the electrode holder, safety devices, and tools
such as Automatic Voltage Reducing devices for AC welding machines and GFCI are
complete