Professional Documents
Culture Documents
22350
22350
Graduate School
MASTER OF SCIENCE
by
KelseyLee H.Schafer
its water cooling system. The goal of this study is to investigate the potential benefits of an
affordable, easily manufactured and installed system incorporating phase change materials (PCM)
to augment the thermal capacity of these pre-existing stratified tanks. A 187-gallon laboratory TES
tank has been constructed and installed into the chilled water system at the University of
Cincinnati’s east power plant. A rack made of PVC with cylindrical copper tubes full of PCM
placed along its height was set in the center of the laboratory TES tank to test the effects of
augmenting the University’s TES tanks with PCM. The laboratory TES tank was tested first
without the PCM (sensible thermal storage) in order to gather reference data, and then was tested
with the cylinders of PCM (sensible and latent thermal storage) augmenting thermal capacity.
Separate charge and discharge half-cycle tests were run with flowrates between 0 and 2.5 GPM,
and then continuing half-cycle tests were run with a controlled flow rate of 2.5 GPM. Charge time,
discharge time, thermocline thickness, storage capacity, half figure of merit (FOM), and system
efficiency were calculated for each test and used to draw conclusions on tank performance. It was
found that the use of PCM in the laboratory stratified TES tank increased the thermal storage
capacity of the tank by approximately 10% while thermocline thickness remained nearly the same,
i
ii
Acknowledgements
With special thanks to Joe Harrell, who funded this research, and to Dave Jeffries, Dan Pumphrey,
Jeff Finan, and Debbie Hausman, who helped purchase materials and assemble the LabTES tank
system and were great friends during the time I spend working at the Utility Plant. Also, special
thanks to my advisor, Dr. Michael Kazmierczak, who worked with me on both nights and
weekends to ensure the success of this thesis. Last I would like to thank my family, my friends,
iii
Table of Contents
Acknowledgements ...................................................................................................................... iii
1 Introduction ........................................................................................................................... 1
1.1 Relevance of Study ................................................................................................................ 2
1.2 Objectives .............................................................................................................................. 2
2 Literature Review ................................................................................................................. 3
2.1 Stratified Tanks ..................................................................................................................... 3
2.2 Stratified Tanks in Use at University of Cincinnati ............................................................ 11
2.3 PCM/Heat Exchanger .......................................................................................................... 14
3 Thermal Storage Calculations ........................................................................................... 18
3.1 Thermal Storage for Un-Augmented Tank ......................................................................... 18
3.2 Thermal Storage for Tank Augmented with PureTemp 8 ................................................... 19
4 Experimental Design and Instrumentation ...................................................................... 21
4.1 Laboratory Stratified Thermal Energy Storage (LabTES) Tank ......................................... 21
4.2 Test Tubes and Rack ........................................................................................................... 23
4.3 Flow Circuit Accessories .................................................................................................... 25
4.4 Measurement and Instrumentation ...................................................................................... 27
5 Procedure & Data Reduction ............................................................................................. 31
5.1 Test Procedure ..................................................................................................................... 31
5.2 Data Analysis ...................................................................................................................... 34
6 Sensible (Un-augmented) Stratified TES Tank ................................................................ 38
6.1 Effects of Varying Flow Rate.............................................................................................. 39
6.2 Charge Time ........................................................................................................................ 40
6.3 Thermocline and Thermocline Thickness ........................................................................... 40
6.4 Integrated Capacity and System Efficiency ........................................................................ 45
6.5 Half FOM ............................................................................................................................ 47
6.6 Conclusions ......................................................................................................................... 49
7 Nominally Augmented Stratified TES Tank .................................................................... 51
7.1 Effects of Subcooling and Latent Heat ............................................................................... 54
7.2 Charge/Discharge Time....................................................................................................... 57
iv
7.3 Thermocline Thickness ....................................................................................................... 59
7.4 Thermal Capacity ................................................................................................................ 62
7.5 Conclusions ......................................................................................................................... 68
8 Overall Conclusions and Future Work ............................................................................. 71
8.1 Conclusions ......................................................................................................................... 71
8.2 Recommended Future Work ............................................................................................... 73
References .................................................................................................................................... 75
Appendices ................................................................................................................................... 78
Appendix A: Additional Figures ............................................................................................... 78
Appendix B: Matlab Codes ....................................................................................................... 83
Appendix C: Properties of PureTemp 8 .................................................................................... 94
Appendix D: Addition Thermal Capacity Calculations ............................................................ 96
v
1 Introduction
Stratified thermal energy storage (TES) tanks are tall, well-insulated tanks filled with a chosen
thermal energy storage material. These tanks are often installed in line with water cooling system
to augment the system’s capacity while reducing the operating costs. TES tanks are already used
energy prices by storing energy at night during off-peak hours. This energy is then expended during
day time hours when energy prices are higher. The process of storing energy in a TES tank is
called charging, and the process of expending that energy is called discharging. Stratified tanks
which store hot and cold water in the same tank are extremely advantageous for thermal energy
storage due to their simplicity, excellent thermal efficiency, and overall cost effectiveness.
For sensible storage, water is widely considered the best storage material to use in these tanks.
However, in recent years, there has been rising interest in latent heat storage methods, which take
advantage of the large amount of energy expended or stored or released during the phase change
of a storage material. For latent heat storage to be used, the storage material must have a freezing
point that is within the operating temperature range of the system in which the TES tank is to be
installed. For example, a typical chilled water cooling system operates between 40℉ and 50℉.
Therefore, water, which freezes at around 32℉, could not offer any latent heat storage in such a
system. Recent advances in materials engineering have produced phase change materials (PCM)
specifically designed to have the desired thermal properties required to store latent heat energy at
desired temperatures. These PCMs come in a variety of forms such as paraffin waxes, plant-based
oils, or even water-glycol mixtures. These technological advances make PCMs a potential tool for
augmenting thermal storage. One way to integrate PCM with a stratified TES tank is to place
1
sealed containers filled with PCM into the tank, which would theoretically behave much like ice
cubes in a drink. This thesis will examine the feasibility and possible benefits of such an approach.
At the University of Cincinnati there are two large stratified chilled water TES tanks, which store
chilled water at night for use during the day in the warmer months of the year. It is desirable to
increase the thermal energy storage capacity of these tanks to meet the future cooling needs of the
university. It is vital to know the effects that integrating PCM into these TES tanks would have on
over-all system performance. Currently, we’ve found no existing literature studying these effects
in cold storage tanks. Because integrating PCM could have unforeseen effects on the TES tanks at
conduct preliminary testing with PCM on a smaller laboratory TES tank to reduce risk.
1.2 Objectives
1. Design and build a laboratory stratified TES (LabTES) Tank with necessary instrumentation.
Demonstrate and document thermocline development in LabTES tank for different flow rates.
2. Use PCM to augment LabTES tank capacity using a simple PCM-filled tube arrangement.
3. Measure the performance enhancement for tank when using PCM and determine any negative
4. Determine the feasibility of using a similar method to augment stratified TES tanks at
University of Cincinnati.
2
2 Literature Review
In order to understand how to best augment University of Cincinnati’s thermal energy storage
tanks, a study was made of the existing literature on the following subjects: (1) stratified TES
tanks, (2) the thermal energy storage tanks already built on campus at the University of Cincinnati,
and (3) the phase change materials to be incorporated in the tanks. An overview of the past research
in stratified tanks gives a basic understanding of the system parameters and requirements to build
the mini-TES tank, and an analysis of the TES tanks currently in use at U.C. yields the more
detailed specifications for building our experimental set-up. Last, a study of research in phase
change materials gives an understanding of what kind of PCM should be applied to augment the
tanks. This literature review summarizes the current body of knowledge on these topics.
In simplest terms, a naturally stratified water tank is a vessel in which the more buoyant warmer
water has floated to the top while the cooler water has remained at the bottom, separated by a
thermocline. When studying stratified tanks, it’s important to take into account the fluid mechanics
effecting stratification as well as how the thermocline behaves. This will ultimately affect the
In a study of chilled-water storage [1], Wildin and Truman conducted several experiments with
large and scale model storage tanks. Some of the tanks used a membrane or walls or baffles to
achieve stratification, while others use natural stratification by buoyant forces. It was concluded
that naturally stratified tanks are not only more simple to design and operate but also more
3
Wildin followed this study with a report [2] on diffuser design, which described simple
mathematical formulas for designing the length of the diffuser and the inlet opening height based
on the Reynolds number and Froude number, respectively. The procedure relates the flow rate per
unit length of the diffuser to the temperature difference (∆T) and Reynolds number of the fluid and
then uses the flow rate per unit length and the desired Froude number to calculate the height of the
slots in the diffuser where water enters the tank. Results of this report also compared the figure of
merit (FOM) as a function of tank outlet temperature for a small radial diffuser, a large radial
diffuser, and an octagonal diffuser and found that the octagonal diffuser provide the highest FOM.
These findings supported the octagonal diffuser as the better option for increasing tank efficiency.
Wildin’s studies became the basis of current ASHRAE standards for stratified tanks.
In 1989, Truman and Wildin [3] collaborated to produce a finite difference model for stratified
tanks which accounted for the conduction and convection between the wall and floor of the tank
and the liquid as well as mixing and the heat loss from the tank to the surroundings. Two-
dimensional heat conduction was used for modeling the tank walls and floor with a one-
dimensional vertical temperature distribution was used for the liquid in the tank. This model called
Zurigat et al [4] took this modeling study a step further, comparing six different models by Sharp,
Han and Wu, Cole and Bellinger, Cabelli, Wildin and Truman, and himself. In a series of tank
charging experiments, Zurigat examined how well each of these models agreed with experimental
data. Each model was one-dimensional and assumed a constant temperature for water entering the
tank. Results of this study concluded that the models of Cole and Bellinger, Zurigat, and Wildin
and Truman are superior in accuracy to others though they are not as computationally efficient.
4
Zurigat also concluded that his own model was best in accuracy because it incorporates inlet
mixing correlations in order to make more accurate predictions when mixing is significant. Other
models struggled to predict temperature distributions in areas of the tank where mixing was severe.
Wildin’s next study in 1991 [5] of flow near the diffuser inlet focused on the effect of the Reynolds
number (Re) and Froude number (Fr) on the gravity currents traveling through a stratified tank and
on the thermocline. The Froude number was maintained below 2, and eight different charging tests
were run each with a Reynolds number in the range of 159 to 633. Results showed that for the
tested values of Fr, values of Re above 200 produced a thicker thermocline. Also, Re values above
400 produced significant mixing in the tank, increasing the slope of the temperature gradient and
rendering stratification ineffective. Gravity currents were found to traverse the tank with greater
velocity as Re increased and were found inside the thermocline as well as below it. The study also
found that the difference between the temperature of the chilled water entering the tank and the
temperature of the water at the inlet increased with increasing Reynolds number, decreasing the
effective storage.
Much of research up to this point in time was done using scale model stratified tanks. Bahnfleth
[6] later recognized the lack of data for full scale existing stratified tanks and did further research.
cylindrical tank with radial parallel plate diffusers and a constant inlet flow rate. A series of charge
and discharge cycles were analyzed, and values for integrated capacity, figure of merit, and lost
capacity were calculated. Results showed that the uncertainty in both the integrated capacity and
figure of merit were highly influenced by the accuracy of the flow rate measurement. It was
determined that even a fairly accurate flow meter would not be sufficient to improve those
uncertainties, making measures of integrated capacity and figure of merit less meaningful. Instead,
5
it was found that especially for taller tanks, the measurement for lost capacity involved less
uncertainty.
In 2001, Stewart [7] challenged the current ASHRAE guidelines, which were based mostly upon
small cylindrical tanks of 35,000 gallons or less, and investigated whether these guidelines were
too stringent when applied to larger tanks. Stewart collected data from five different stratified tanks
already being used in industry. It was found that four out of the five tanks were never completely
discharged but rather discharged only enough to meet the cooling load and then charged again (i.e.
partially discharged). For this reason, the figure of merit could not be calculated. However, the
thermocline thickness could be measured, and this could be used to approximate the efficiency of
the tanks. Results showed that for larger tanks, a Reynolds number of up to 6000 would not
significantly increase thermocline thickness. The study also suggested that further research into
Around the same time, Musser and Bahnfleth [8, 9, 10] followed up his study of large stratified
tanks with a parametric study of inlet diffuser performance. A CFD model was created and
implemented on two large scale tanks. Modeling focused on the lower region of the tanks near the
inlet where the thermocline develops. The CFD model assumed a uniform inlet velocity profile
and laminar flow. Both the effects of turbulence and inlet temperature variation were considered
in the creation of the model. Comparison of experimental thermocline data from these tanks with
thermocline predictions based on the CFD model validated the laminar CFD model.
This CFD model was used in a series of numerical experiments Musser and Bahnfleth [8, 9, 10]
performed in order to quantify the effects of six diffuser and tank design parameters on the inlet
6
and analysis of sixteen tests on large scale stratified tanks. This study led to the development of
first-order regression models for thermocline thickness and equivalent lost tank height (similar to
lost capacity) based on the inlet Richardson number, the ratio of diffuser diameter to diffuser
height, and the ratio of diffuser diameter to tank diameter. Results of this study found the ratio of
diffuser radius to tank radius and the inlet Richardson number to be the most significant flow
parameters for tanks with slot-type diffusers and found Reynolds number to be of secondary
importance. The study also concluded that larger Richardson number and smaller inlet slot height
Thermal efficiency is the ratio of the energy that is able to be taken out of a storage tank to energy
put in, basically the ratio of the discharging capacity to the charging capacity. The primary measure
of thermal efficiency in a stratified tank is the discharge capacity, meaning the amount of thermal
energy the tank is able to store and provide to the system it augments. This is exemplified by
Bahnfleth’s measure of system efficiency. Another common measure of efficiency is the figure of
merit (FOM), which is the ratio of integrated discharge capacity for a given volume to the ideal
capacity that could have been withdrawn in the absence of mixing and losses to the environment
[6]. The figure of merit is usually calculated for the entire process of charging and discharging.
However, in his experiments Bahnfleth also used the half-cycle FOM, which is calculated for only
one discharge or one charge process. Lost capacity is another more practical measure of tank
performance. It is defined by Bahnfleth as the capacity that cannot be removed from the tank due
According to the study by Zurigat, Ghajar, and Maloney [4] on one-dimensional modeling of
stratified tanks, there are four major causes of loss of stored energy and thermal efficiency. These
7
are heat gain from the water in tank from the surroundings, thermal diffusion through the
thermocline, convection currents in the water causing mixing, and mixing introduced at the inlet
Several aspects of heat gain to the water in the tank must be considered. The top surface of the
water is left exposed to atmospheric pressure and will suffer convective gain as will the outer walls
of the tank. There is also gain from the water through the tank walls themselves. Heat gain through
the floor of the tank is of lesser concern than these but should still be considered. These problems
are fairly easily minimized by properly insulating the walls and floor of the tank as well as any
pipes leading to and away from the tank. Building tanks underground offers very effective
insulation though the precise amount of insulation depends heavily on the soil moisture content.
Another way to minimize these heat loss effects is to minimize the ratio of the surface area of the
tank to its volume. The EPRI Stratified Chilled-Water Storage Design Guide [11] suggests that a
cylindrical shaped tank offers the optimum aspect ratio of surface area to volume.
When studying thermal storage, it is important to consider the effect that the thermocline has on
the efficiency of the storage system. The thermocline separates cooler, denser water below from
the warmer, less dense water above it. This separation is called stratification. The thermocline also
acts as a barrier to mass and heat transfer, meaning, that the mixing of water above the thermocline
has less effect on the water below the thermocline. The thermocline is created by a gravity current
which is initiated by the temperature difference between the water entering the tank and the water
at the inlet. The Froude number and Reynolds number determine the thickness of this gravity
current which then determines the thickness of the thermocline. As time passes, diffusion between
the warm and cool water increases the thickness of the thermocline. Heat gain from the tank walls
mentioned above also contributes minorly to the thickening of the thermocline. Increasing
8
thermocline thickness decreases the amount of usable chilled water in the tank, thus reducing the
Mixing at the inlet and in the rest of the tank also causes increased thermocline thickness. Mixing
is mass and heat transfer that occurs between the warmer and cool water, effectively eliminating
stratification. It caused by undesirably high Reynolds and Froude numbers as well as by unwanted
convection currents and vertical fluid momentum. The dimensionless Froude number (Fr) is the
ratio of the inertial forces to the gravitational forces on a fluid element. Wildin [5] suggested a
value of Fr less than 1 because Fr is less than 1 a gravity current forms at the inlet and helps to
prevent mixing (flow near inlet). Reynolds number is the ratio of inertial to viscous forces on a
fluid element. A low Reynolds number and Froude number and reduced mixing can be achieved
Tank dimensions and geometry and diffuser design must both be carefully considered in the
design of a thermal energy storage system. Thermal energy storage tanks are most commonly
square or cylindrical in geometry, and single-tank systems are preferred due to simplicity and
decreased surface area to volume ratio. Diffusers are pipe systems at the bottom and top of the
tank that distribute the inlet and outlet flow. This section will expand upon the details of tank sizing
The dimensions of a storage tank are especially important for reducing mixing and preserving
usable storage capacity. As discussed before, a vertical cylinder is the most effective geometry to
minimize the surface area to volume ration. The walls of the tank should be vertical because any
9
curvature in the tank walls will cause unwanted horizontal motion in the flow through the tank.
Tank depth also plays an important role. According to the EPRI Chilled Water Storage Guide
asserts that tanks less than 5 feet tall will significantly decrease usable tank volume. The tank used
in this experiment is approximately 5.3 feet tall. The volume of the tank should be chosen based
upon the cooling needs of the system. However, tank height becomes less influential on usable
volume as tank height increases higher than 6 feet. And significantly increasing the surface area at
the top of the tank exposes more water to ambient air, which increases heat gain. Therefore, as
tank size and volume increase, tank insulation must also be improved.
radial geometry. These pipes have rectangular slot holes at intervals along the pipes to allow exit
and entrance of inlet and outlet water at distributed places in the tank. Labyrinthine diffusers are
made up of a complex, matrix-like system of pipes spanning the bottom and top areas of the tank.
Radial diffusers are composed of smaller diameter pipes extending outward from a main inlet pipe
in the center of the tank. Hexagonal diffusers are made up of pipes arranged in the configuration
of one or two concentric hexagons. The diffusers used in this experiment are hexagonal.
A properly designed diffuser at the inlet and outlet of a thermal energy storage tank distributes the
flow of incoming and outgoing flow to reduce mixing and unwanted currents in the tank and helps
to ensure natural stratification within the tank. According to ASHRAE standards diffusers should
be designed to ensure a Froude number of less than 2. And a desirable Reynolds number is under
1,000 [2]. The design of the diffusers in this experiment was based on this Reynolds and Froude
10
number criteria. The diameter of the hexagon geometry and height of the rectangular slotted holes
along the diffuser pipes were calculated using a method prescribed by Wildin [2].
One of the goals of this study is to augment the capacity of the large TES tanks at University of
Cincinnati power plants. In order to do this, one must first be familiar with the structural
specifications and normal operation of the University TES tanks. This section offers a brief
description of the east and west campus thermal energy storage tanks.
There are two large thermal energy storage tanks at the University of Cincinnati, one located
underground at U.C. east campus power plant and another located under the training football field
on the university campus. Both tanks run within the larger water system that runs throughout the
entire university. Just like the laboratory TES tank built for this experiment, these two large tanks
use the operating temperature range supplied by the chillers at the east campus power plant. Unlike
the laboratory TES tank, however, the larger tanks are not usually charged completely, or
discharged completely. Instead, the water in the tanks if chilled just enough to accommodate the
load required by the university’s larger water system on any given day. This means that in the
winter or colder months, when the cooling load at the university is much smaller, the two tanks
are operated with very small temperature differentials or not at all. The tanks are primarily used
The tank at the east campus power plant was built in 1997. Reference Figure 2.1 and 2.2 for a side
and top view schematic of the east campus power plant tank. This tank is 90 ft. long by 82 ft. wide
11
Figure 2.1 Side View East Campus Power Plant Tank
12
Figure 2.3 Side View Campus Football Field Tank
13
by 24 ft. deep and is filled with approximately three million gallons of water. This gives the tank
an approximate thermal storage capacity of 20,932 Ton-hours. The tank under the campus football
field was built in 2012. Reference Figure 2.3 and 2.4 for a side and top view schematic of this tank.
This tank is 167 ft. long by 126 ft. wide by 27 ft. deep and is filled with approximately four million
gallons of water. This gives the tank an approximate thermal storage capacity of 27,909 Ton-hours.
and its chemical compatibility with the materials making up the heat exchanger. Phase change
materials (PCM) are defined as materials that take advantage of the latent heat involved in
solidifying liquefying, evaporating, or condensing in order to store or release large amounts of heat
energy. The PCM used in this experiment is called PureTemp 8 and is supplied by Entropy
Solutions, Inc. It is a non-toxic, renewable, and biodegradable PCM made from vegetable
products. PureTemp 8 was chosen for this experiment based on its theoretical fusion temperature,
its high specific and latent heat values, its chemical compatibility with other materials in the
experimental set up, and its exceptional lifespan of over 20,000 thermal cycles without thermal
degradation. This section will give a short history of the available literature on phase change
Over the past forty years, rising climate change and energy consumption has prompted scientific
advances in energy storage technologies which improve energy and cost efficiency. Shortages of
petroleum products in the 1970s brought on the investigation of storage materials other than ice.
Feasibility studies and conferences continued into the late 1990s and early 2000s when thermal
14
In 2008, Dr. Harald Mehling and Prof. Luisa Cabeza collaborated to write Heat and Cold Storage
with PCM [12], a comprehensive book detailing the basic concepts of thermal storage and design
of latent heat storage systems, experimental methods of determining the thermal properties of
PCMs, and the many possible applications of phase change technology. This book draws on
Mehling and Cabeza’s past work in the area of thermal storage as well as on past work in thermal
PCMs are thermal storage materials that are carefully developed to have specific thermal properties
which allow them to take advantage of latent heat energy at a temperature that is within the
operating temperature range of the system they are used in. Simply put, PCMs are designed to
have a certain desired fusion temperature. This desired fusion temperature should be greater than
the chilled water temperature in the cooling system but less than the warm return water
temperature. In order to change phase and store latent energy efficiently in a system, there are five
important thermal properties of the PCM that must be considered: (1) fusion temperature, (2)
thermal conductivity, (3) specific heat, (4) latent heat, and (5) chemical compatibility. These are
The temperature of fusion (𝑇𝑓 ) of a material is the temperature at which the material changes phase.
This value is often determined using a T-history test or conventional calorimetry methods like
differential thermal analysis or differential scanning calorimetry [13]. In the case of such as
experiment, PureTemp 8 was selected because it is designed to change from a liquid to a solid at
a fusion temperature of 8℃ = 46.4℉. However, this is an ideal value. In reality, the fusion
temperature of a PCM may vary slightly from sample to sample of the same PCM. This is because
most PCMs are not pure materials but rather mixes of materials. Because the fusion temperature
15
may vary from sample to sample, it is important that the system have a larger operating temperature
range.
Thermal Conductivity (k), according to Mehling and Cabeza [12], is the ability of a material to
transport heat while the material itself does not move. The thermal conductivity of a material
determines the rate at which heat transfers to and from a material. A higher rate of heat transfer
will ensure that both latent and sensible energy will be transferred to and from the PCM more
rapidly. Therefore, a PCM must have a relatively high thermal conductivity to accompany a high
Specific Heat (c) is the amount of thermal energy that can be stored in a unit of mass for every
degree of temperature change during a change in temperature that is not at the fusion temperature.
𝐽
Specific heat is expressed in 𝑔℃ . Latent heat (L) is the amount of thermal energy that can be stored
or released in a unit of mass during the process of phase change. Consequently, latent heat is
expressed in units of J/g. The specific heat of a PCM is usually significantly less than that of water,
which is commonly used as a thermal storage medium. However, the high value of latent heat in a
PCM is meant to make up for this deficiency. Thus it is extremely important for a PCM to have a
high latent heat value in order to increase the overall storage capacity of the system. The specific
𝐽 𝐽
heat of PureTemp 8 are 2.15 for liquid PCM and 1.85 for solid PCM, and value of latent
𝑔℃ 𝑔℃
𝑗
heat is 178 𝑔. For more information about the properties of PureTemp 8, see Appendix C.
The term chemical compatibility refers to the ability of a PCM to interact with other system
16
polyethylene plastics as well as some types of rubber sealants but is non-reactant with metals.
Therefore, it’s vital to consider what materials the PCM comes in contact with. For this reason,
the heat exchanger tubes used to contain the PCM were made of either metal or PVC.
17
3 Thermal Storage Calculations
This chapter offers theoretical calculations for ideal thermal storage capacity of the un-augmented
and augmented laboratory TES tank. Simple thermodynamic analysis was used to calculate the
amount of thermal energy stored in the laboratory TES tank assuming no flow of water is running
The ideal charging situation for the thermal storage tank implies four assumptions: 1. The entire
tank cools from the initial temperature to the final temperature in the time it takes for the
thermocline to pass once from the bottom of the tank to the top (one charge cycle). 2. The initial
temperatures of both the water and the PCM in the tank are equal to return water temperature.
𝑇𝑊𝑖 = 12℃ and 𝑇𝑃𝑖 = 12℃. 3. As chilled water enters the tank, both the water and the PCM cool
at roughly the same rate to the temperature of the chilled supply water, 𝑇𝑊𝑓 = 6℃ and 𝑇𝑃𝑓 = 6℃.
Thus, the total change in temperature ∆𝑇 = 6℃. 4. There are no energy losses from the water and
PCM in the tank to the environment or the tank itself. 5. The inlet water temperature is constant.
These assumptions also apply for the discharging process with the exception that the initial
temperature is equal to the chilled water temperature, and the final temperature is equal to the
return water temperature. 𝑇𝑊𝑖 = 6℃, 𝑇𝑃𝑖 = 6℃, 𝑇𝑊𝑓 = 12℃, and 𝑇𝑃𝑓 = 12℃ for the discharge
cycle. Also, for the discharge cycle, the thermocline travels from the top of the tank to the bottom.
experiment, there is no latent component of energy storage in the un-augmented tank. Therefore,
the total thermal storage of the un-augmented tank is equal to the sensible heat storage of the water
in the tank.
18
𝑄𝑇𝑎𝑛𝑘 = 𝑄𝑊 = (𝜌𝑉𝑊 𝐶∆𝑇)𝑊 (Eq. 3.1)
𝑘𝑔 𝑘𝐽 1 𝑘𝐽
𝑄𝑊 = 1000 3
∙ 0.7072 𝑚3 ∙ 4.204 ∙ 6℃ ∙ (Eq. 3.2)
𝑚 𝑘𝑔℃ 12660 ton ∙ hr
ideal capacity of the water plus the ideal capacity of the PCM. The ideal capacity of the PCM is
calculated below as the sum of the sensible storage of liquid PCM, the latent heat, and the sensible
storage of the solid PCM, where the theoretical phase change temperature of PureTemp 8, 𝑇𝐹 =
𝑘𝑔 𝑘𝐽 𝑘𝐽 𝑘𝐽 1 𝑘𝐽 (Eq. 3.5)
𝑄𝑃 = 860 ∙ .01094 𝑚3 [2.15 ∙ 4℃ + 180 + 1.85 ∙ 2℃]
𝑚3 𝑘𝑔℃ 𝑘𝑔 𝑘𝑔℃ 12660 ton ∙ hr
The sensible storage in the volume of water filling the rest of the tank is calculated in the same
way as before. Note that the value for volume used here accounts for both the presence of the PCM
𝑘𝑔 𝑘𝐽 1 𝑘𝐽
𝑄𝑊 = 1000 ∙ 0.705 𝑚3 ∙ 4.204 ∙ 6℃ ∙ 12660 ton∙hr = 1.405 ton ∙ hr (Eq. 3.7)
𝑚3 𝑘𝑔℃
19
Thus, the ideal storage capacity of the augmented tank is as follows.
With a volume fraction of 1.527%, the ideal improvement in thermal storage is calculated to be
9.821%. The storage capacity of the copper heat exchangers themselves, the PVC rack supporting
the heat exchangers, and the PVC distribution rings in the tank is assumed to be negligible as it is
less than .5% of the total thermal capacity of the tank. Refer to Appendix D for this calculation.
20
4 Experimental Design and Instrumentation
The experimental set-up for the LabTES experiments was designed and built according to
standards set forth in the EPRI Stratified Chilled-Water Storage Design Guide [11], ASHRAE
standards, and standards described in the Design Guide for Cool Thermal Storage from the
American Society of Heating, Refrigerating, and Air-Conditioning Engineers, Inc. [14]. The
system consists of a stratified thermal storage tank with flow distribution rings, a rack of tubes
filled with PCM, the necessary piping, valves, pump, and instrumentation, and a data acquisition
The main test section of the LabTES tank set-up (Figure 4.1) is a 66-inch-tall plastic storage tank
29 3⁄16 inches in diameter, which holds 187 gallons of water. The tank was designed as a small-
scale simulation (with the same rise rate range) of the larger commercial TES tanks used in the
University of Cincinnati Central Power Plant. The tank is open at the top, exposed to atmospheric
pressure. It has an inlet and outlet at the top of the tank (upper inlet and outlet) and at the bottom
Two circular, PVC distribution rings, each with twelve rectangular slots, are mounted inside the
LabTES tank connected to the inlets/outlets both upper and lower. The process for designing the
height of these slots and the diameter of the rings is given in by Wildin [5]. This design process is
based on the criteria that the dimensionless Froude number is less than 1. The slots are designed
to be .5 inches wide and .75 inches in height and face alternatingly inward and outward from the
center of the tank. The diameter of each distribution ring is one half the diameter of the tank. These
21
Figure 4.1 Photograph of LabTES System
Chilled Water
Outlet
Return Water
Inlet (Return 1)
Chilled Water
Inlet (Supply) Return Water
Outlet
22
distribution rings prevent turbulent flow in and out of the TES tank to prevent unwanted mixing
of the chilled water at the bottom of the thermocline and the warmer water at the top. The rings
also ensure that the flow rate into the TES tank and the flow rate out are equal, preserving a
constant volume of water in the tank. Refer to Fig. 4.2 for a drawing and photograph of the
distribution ring (left) and an overhead view looking through the open top down into the tank
(right).
When the system charges, chilled water at about 6 ℃ flows from the utility plant chilled water
supply line into the LabTES tank through the lower inlet while warmer water at the top of the
thermocline flows out through the upper outlet and is pumped back into the utility plant return
water line. During charging, the lower outlet and upper inlet are closed. When the system
discharges, warmer water at about 12 ℃ flows from a separate utility plant return water line into
the LabTES tank through the upper inlet, and chilled water at the bottom of the thermocline flows
out through the lower outlet and is pumped back into the utility plant return water line. The upper
outlet and lower inlet are closed. Figure 4.3 shows the flow path of water through the tank.
A ladder-like, vertical rack was built from PVC to hold up to eighteen tubes of PCM. For the
standard test case, the nine tubes are mounted horizontally one above the other on the rack about
6 inches apart in height. An RTD is inserted into the center of each tube to measure the temperature
of the PCM. At first, for the purposes of this experiment, different materials were considered for
the tube wall. One set of nine tubes was made of copper, another of PVC, and another of
Aluminum. Ultimately, the copper set was chosen over the aluminum an PVC for its high thermal
23
Figure 4.3 Flow Paths of Water Through LabTES Tank in Charging and Discharging
Charging Flow Path Discharging Flow Path
24
conductivity. Each coper tube is filled with a fatty acid type phase change material called
PureTemp 8 provided by Entropy Solutions Inc. Figure 4.4 shows the tubes and rack.
The TES tank has two inlets: The chilled water supply and the warm water return. The pipes to
these inlets are ½” copper. At both return and supply inlets are a ½” full port ball shut off valve, a
½” Y type strainer, a ½” pressure regulator set to allow 60 psig, a pressure gauge (0-100 psig), a
½” CWR control valve, a manually operated shut off valve, and an RDT to measure the inlet
temperature (Figure 4.5 Items 1-6). At both outlets of the tank, there in an outlet temperature RTD
and a 2” actuated PVC valve (Figure 4.5 Item 10). All pipes exiting the tank are 2” PVC.
Collection Tank
Water discharged from the TES tank flows into the 470-gallon rectangular collection tank (Figure
4.5 Item 11), where the flow rate is measured. Flow into the collection tank enters at the bottom to
prevent any disturbance at the surface of the water where the magnetostrictive level transmitter
(Figure 4.5 Item 12) floats. The tank sits on a square, wooden base 14.125 inches off the floor.
This tank is either manually or automatically drained after each charge test and each discharge test
to prevent overflow.
Pump
To empty water from the collection tank back into the power plant’s water supply, a Pump-Goulds
eSV Model 3SV12GF4C60 Multi-Stage Pump (Figure 4.5 Item 14) is located just after the
isolation valve (Figure 4.5 Item 13). The pump is rated at 3 HP and 3500 RPM. It runs with a flow
rate between 3 and 10 GPM. The pump does not run continuously. Its purpose is to drain the
25
Figure 4.5 LabTES System Diagram
6
3 5 12
10
1 12 4
Return 1 7
Return 2
11
8
16
13
15
Supply 9 14
1. ½” full port ball shut off valve 6. Inlet and outlet RDTs 12. Magnetostrictive level
2. ½” Y type strainer 7. Upper distribution header transmitter
3. ½” pressure regulator allows 8. Test section (thermal 13. Pump isolation valve
60 psig storage tank) 14. Pump
4. Pressure gauge (0-100 psig) 9. Lower distribution header 15. Pressure gauge (0-100 psig)
5. ½” CWR control valve & 10. 2” actuated PVC valve 16. Pump check valve &
manual shut off valve 11. 470-gallon collection tank isolation valve
Flow path of water during charging process from upper inlet (Return 1) to lower outlet
Flow path of water during discharging process from lower inlet (Supply) to upper outlet
26
collection tank when the water level rises to the set point height programmed in the programmable
logic controller. After the pump is a pressure gauge (0-100 psig), a check valve, and another
isolation valve (Figure 4.5 Items 15-16). Because the pipe exiting the pump flows vertically, the
check valve is necessary to prevent back flow due to gravity. Upon leaving the pump, water is
Temperature
Temperature data was taken using 120-inch-long hermetically sealed RTDs (Figure 4.5 Item 6)
from Omega. RTDs were calibrated against a constant temperature water bath. RTDs were placed
at the inlets and outlets of the LabTES tank as well as other locations inside the tank. Inside the
LabTES tank, an RTD was placed in the water at the same level of each PCM tube to display the
thermocline in the tank, and an RTD was placed inside each of the nine PCM tubes. These RTDs
inside the tank provide data used to measure the thermocline and to calculate other important
Pressure
An analog pressure gauge (0-100 psig) was placed just upstream of the CWR control valve on both
the chilled water supply line and the return water supply line. Pressure regulators placed just
upstream of the gauges ensure the pressure in the system remains at around 75 psig. By keeping
the system pressure constant, we eliminated pressure fluctuations in the supply line as a factor in
the experiment. There is also a pressure gauge located just downstream of the pump. For further
assurance, the CWR control valve (Figure 4.5 Item 5) automatically adjusts the inlet flow rate in
27
Volumetric Flow Rate
The volumetric flow rate through the system is designed to be 2.5 GPM or less and is measured
by a Jogler Magnetostrictive Level Transmitter, Model LGT-6000 mounted inside the collection
tank (Figure 4.5 Item 12). The magnetostrictive level transmitter consists of a transmitter head,
sensor pickup, waveguide probe, and the waveguide float. The metal float floats at the surface of
the water in the tank and travels up and down along the vertical length of the waveguide probe.
The transmitter head sends a current through the waveguide probe creating a magnetic field that
interferes with the magnetic field of the float. From the reaction of the float’s magnetic field to
that of the probe, a torsional force is created. The length of time between the sending of the current
from the transmitter to the time the transmitter detects the torsional force is proportional to the
voltage output of the transmitter. The transmitter reads the water level every .1 seconds, and the
flow rate in the system is calculated as the difference in water level divided by the difference in
time. The accuracy of the level transmitter is +/- 0.015 inches. A 4-20 mA output signal sends
To supplement the above method of measuring the volumetric flow rate, a measuring stick was
placed in the main test section to measure the water level in the test section. During testing, this
water level is monitored and recorded. The water level in the tank remains constant. Therefore, the
flow into the tank and the flow out are equal.
The programmable logic controller (PLC) is a graphical user interface created using RS Logics
5000. It is used to set the charging and discharging flow rates, control the pump and valves, and
collect and record all data for the experiments. The program features a time clock with hours,
minutes, and seconds to which all the data is synced. It also offers separate manual and automatic
28
Figure 4.6 PLC System Controller and Data Logger Screens
29
modes for the pump. A discharge process and a charge process are programed into the PLC. When
charging the tank, the PLC sends commands to open the lower inlet valve and the upper outlet
valve, setting a user-defined set point flow rate. In contrast, when discharging the tank, the PLC
sends commands to open the upper inlet valve and the lower outlet valve, again setting the flow
rate of the inlet valve to the user-defined set point. The graphical user interface of the PLC features
a home screen where the user input is entered, a maintenance screen for managing any maintenance
to the system, a data table screen, and a temperature data screen, which shows an image of the TES
tank complete with temperature indicators (See Figure 4.6). The PLC stores the data in an excel
sheet at the end of each day and sends it to the Utility Plant network.
30
5 Procedure & Data Reduction
Figure 5.1 shows the basic procedure for each half cycle charge and discharge test ran in this study.
First, these charge and discharge tests were run without any PCM or copper tubes mounted in the
tank (i.e. a sensible configuration). Then these charge and discharge tests were run with nine
copper tubes filled with PCM mounted on the rack in the center of the tank (i.e. a nominally
augmented configuration). The steps taken to perform each test and the calculation performed for
Looking at the PLC control screen, the operator checked the campus chiller’s output temperature
and the system’s return water temperature conditions. The difference between these two
temperatures was the operating ∆T. The operator ensured that the operating ∆T was greater than
8℉ before beginning any test. Next, the operator mounted the number of tubes (configuration)
desired for test in the appropriate sections of tank. For sensible tests, no tubes of PCM were used.
For nominally augmented tests, nine 2” diameter copper tubes (one tube in each section) were
filled with PureTemp 8 PCM and mounted. An RTD was inserted through the sealed cap into the
center of each tube. Last, the PLC control screen was used to select the desired flow rate.
For charging tests, the operator discharged the tank until all 18 water RTDs read ~50℉ (campus
return water temperature). For discharging tests, the operator charged the tank until all 18 water
RTDs read ~40℉ (campus chilled water temperature). For nominally augmented tests, the tank
31
was charged or discharged until all 18 water and PCM RTDs read the appropriate initial
Refer to Figure 5.2 for a schematic of the LABTES tank explaining which inlet and outlet valves
should be open and shut for specific charging and discharging processes. For charging tests, the
bottom manual inlet valve was opened, and the top inlet valve was closed. For discharging tests,
the top manual inlet valve was opened, and the bottom inlet valve was closed. Then the start button
on home screen of the PLC control screen was pressed to begin the test.
The system was allowed to run until the tank reached the new initial uniform temperature. The
time when the tank’s outlet RTD temperature reached the average temperature of inlet water ±.5℉
was recorded as the charge/discharge time. The system was allowed to continuously charge or
discharge in order to set up for the next test. If a charge test was performed first, the tank continued
charging until the beginning of the next discharge test. Likewise, if a discharge test was performed
first, the tank continued discharging until the beginning of the next charge test. The operator then
returned to step 2 and proceeded to perform a test for opposite process. Once the test for the
opposite process finished, the operator pressed the stop button on home screen of PLC controller.
32
Figure 5.1: Procedure for Charging and Discharging the LABTES Tank
3. Begin
Charge/
Discharge
1. Prepare system process
configuration
2. Bring Tank to initial
(Set-up Tubes with PCM) Uniform Temperature
4. Finish
Charge/
Discharge
process
(Chiller)
nominally
~𝟒𝟎℉
33
5.2 Data Analysis
Flow Rate
The flow rate was calculated using water level measurements taken at a rate of 1 measurement per
second by the magnetostrictive level meter located in the auxiliary tank. The volume of water that
enters the auxiliary tank in one second is calculated as the difference between two successive water
level readings multiplied by the area of the bottom of the tank. Then this rate is this value is
converted into units of gallons per minute. This is also converted to a mass flow rate (𝑚̇).
Regardless of whether the tank was augmented or un-augmented, the temperature difference was
calculated as the absolute difference between the initial bulk temperature of the water in the tank
and the average temperature of the water leaving the tank at the outlet. This temperature difference
was expressed in degrees Fahrenheit. In other words, the temperature difference was calculated as
the absolute difference between the cold temperature 𝑇𝑐 and the hot temperature 𝑇ℎ of the tank for
each test. The bulk initial temperature was calculated as the average of the temperature readings
from RTDs placed in the water equally spaced along the height of the tank at the time of start of
Thermocline thickness was calculated using the method suggested by Stewart (9). An RTD in the
water at about mid-height in the tank was chosen. As the thermocline rose or fell, the temperature
history of this RTD showed the thermocline. The time that the RTD measured 𝑇𝑐 +.5℉ (𝑡1 ) and the
time that the RTD measured 𝑇ℎ −.5℉ (𝑡2 ) were recorded, and the difference in minutes between
34
Figure 5.3 How to Identify the Thermocline Using the Temperature History of an RTD
35
these times was multiplied by the rise rate (RR) of water through the tank. The units of the rise
rate are inches per minute. This produced the thermocline thickness expressed in inches.
The experimental charge time was calculated as the time between when the charge or discharge
test began and the time the outlet temperature of the tank reached within .5℉ of the average inlet
temperature, expressed in minutes. The theoretical charge time was calculated by dividing the
volume of water in the tank in the gallons by the volumetric flow rate of water through the tank.
The half figure of merit was calculated individually for each charge and discharge process. It was
calculated as the integrated capacity (𝐶𝑖𝑛𝑡 ) of the storage tank divided by the maximum capacity
possible (𝐶𝑚𝑎𝑥 ) for each test for the same time duration. The integrated capacity of the tank is
calculated as follows where 𝑐 is the specific heat of water, 𝑇𝑖𝑛 is the average inlet temperature of
𝑡 ̇ (Eq. 5.1)
𝐶𝑖𝑛𝑡 = 𝑚̇ 𝑐 ∑𝑡𝑓𝑖𝑛𝑎𝑙 |𝑇 − 𝑇𝑜𝑢𝑡 | ∆𝑡
𝑖𝑛𝑖𝑡𝑖𝑎𝑙 𝑖𝑛
where ∆𝑡 = 1 second
𝑡 ̇ (Eq. 5.2)
1 𝐶𝑖𝑛𝑡 𝑚̇ 𝑐 ∑𝑡𝑓𝑖𝑛𝑎𝑙 |𝑇 − 𝑇𝑜𝑢𝑡 | ∆𝑡
𝑖𝑛𝑖𝑡𝑖𝑎𝑙 𝑖𝑛
𝐹𝑂𝑀 = ∙ 100% = ∙ 100%
2 𝐶𝑚𝑎𝑥 𝑚̇ 𝑐 (𝑇ℎ − 𝑇𝑐 )(𝑡𝑓𝑖𝑛𝑎𝑙 − 𝑡𝑖𝑛𝑖𝑡𝑖𝑎𝑙 )
Note that the temperature difference |𝑇𝑖𝑛 − 𝑇𝑜𝑢𝑡 | is an absolute value in this equation because in
discharging, 𝑇𝑜𝑢𝑡 is less than 𝑇𝑖𝑛 , and in charging, the 𝑇𝑖𝑛 is less than 𝑇𝑜𝑢𝑡 . 𝐶𝑚𝑎𝑥 increases faster
than 𝐶𝑖𝑛𝑡 once |𝑇𝑖𝑛 − 𝑇𝑜𝑢𝑡 | becomes small after the water in the tank has been replaced once.
36
System Efficiency
The system efficiency (𝜂) was calculated as the ratio of the integrated thermal capacity stored in
the tank during charging (𝐶𝑖𝑛𝑡 𝐶 ) to the integrated thermal capacity retrieved from the tank during
discharging (𝐶𝑖𝑛𝑡 𝐷 ).
37
6 Sensible (Un-augmented) Stratified TES Tank
Before augmenting the LabTES tank with pipes full of PCM, it was important to first verify that
the tank functioned as expected without any augmentation. Therefore, as a control for the
augmented stratified tank testing, the tank was first tested without any heat exchanger pipes in the
tank. The PVC rack with 18 RTDs placed linearly along its height was suspended in the center of
the tank. This was called the sensible configuration because the system did not involve any latent
heat storage. The flowrate of water through the tank has important effects on the charge/discharge
time and the thermocline and thus on the efficiency of the tank. It was found that the precision of
the flowrate was difficult to control. Therefore, many separate charge and discharge cycles were
run in the sensible configuration using varying flowrates between 0 and 2.6 GPM to characterize
the effects of flowrate on tank behavior. Results of these tests are listed in Tables 6.1 and 6.2.
38
Table 6.2: Results for Sensible Discharging Tests
According to the literature, varying flowrate has several effects on the behavior of the tank.
Increasing flow rate increases the Reynolds number and the amount of mixing within the tank,
thus decreasing efficiency (Half FOM). However, because the flowrates used in this experiment
do not cause the Fr number to be greater than 1, the mild increase in flowrate examined in this
experiment should not significantly affect the efficiency. It may also be observed that increasing
flow rate did not directly correlate to increased thermocline thickness in the above tests. Rather, it
is theorized that the residence time of the water in the TES tank in conjunction with the heat gain
through the sides and top of the tank from the surrounding air that varied in temperature from
approximately 65 to 70℉ caused the thermocline thicknesses to be much less predictable than
expected.
39
6.2 Charge Time
Figure 6.1 shows the outlet water temperatures during charging and discharging (Tests # 6 and #
12). The charge time (𝑡𝑐 ) for each test is marked by a dotted line. As shown in Figure 6.2,
experimental discharge times closely follow the theoretical model for charge time at a given flow
rates. Values for experimental charge time are consistently higher than theoretical values. This
may be because when charging the tank, the inlet water must work against ambient heat transfer
warming the tank whereas in discharging the ambient heat transfer works with the warmer inlet
water to bring the tank back up to the temperature of the return water. For both charging and
discharging tests, it was found that agreement with the theoretical model was best at higher flow
rates. This is most likely because increasing flow rate causes proportional decrease in
charge/discharge time allowing less time for unwanted external heat gain to occur.
# 1, 3, and 7). Figure 6.4 shows the passage of the thermocline with time for three different
discharging tests (Tests # 10, 12, and 15). Each subplot shows one thermocline profile for each of
eight RTDs located along the vertical axis of the TES tank. This method of using the temperature
profile of a single RTD to view the thermocline profile is described in detail by Dr. William
Stewart [9] and echoed in studies by Dr. William Bahnfleth. During charging tests, the thermocline
passes the lowest RTD in the tank first and the highest RTD in the tank last, and for discharging
tests, the thermocline passes the highest RTD in the tank first, moving downward.
In Figures 6.3 and 6.4, it is obvious that increasing flowrate causes a proportional decrease in
charge time. The thickness and shape of the thermocline, however, is not accurately depicted in
40
Figure 6.1 Water Outlet Temperatures Vs. Water Inlet Temperatures
𝒕𝒄 =97 min.
𝐓𝐚𝐧𝐤 𝐕𝐨𝐥𝐮𝐦𝐞
𝐓𝐡𝐞𝐨𝐫𝐞𝐭𝐢𝐜𝐚𝐥 𝐂𝐡𝐚𝐫𝐠𝐞(𝐃𝐢𝐬𝐜𝐡𝐚𝐫𝐠𝐞) 𝐓𝐢𝐦𝐞 =
𝐅𝐥𝐨𝐰 𝐑𝐚𝐭𝐞
41
Figure 6.3 Thermoclines Measured from RTDs at Different Heights in the Tank
Figure 6.4 Thermoclines Measured from RTDs at Different Heights in the Tank
42
these figures because the number of minutes the thermocline takes to pass is not completely
indicative of thermocline thickness. Note that for lower flow rates, the thermocline profiles seem
more stretched out over the time axis. This does not mean that thermocline thickness is greater at
lower flow rates. This time it takes for the thermocline to pass must be multiplied by the average
rise rate in the tank in order to calculate the experimental thermocline thickness values listed in
Tables 6.1 and 6.2. And the average of these 8 thermocline thickness values from the different
From beginning to end of the charging or discharging process, the thermocline thickness does not
remain constant as the thermocline traverses the tank. Figure 6.5, shows the thermocline thickness
measured at each RTD along the height of the tank for discharging Test #15 and charging Test #
6, demonstrating how the thermocline thickness behaves over the course of the thermocline
passing from top to bottom or from bottom to top of the tank. Just as Bahnfleth observed in his
own studies, for each of Tests # 1 through # 15, the thermocline thickness increased slightly as the
thermocline traversed the tank from inlet to outlet. This increase in thickness is thought to be
attributed to unwanted mixing and diffusion across the thermocline. Longer residence times of
Average thermocline thickness is shown in Figure 6.6 for all sensible tests. The effects of ∆T and
flow were examined to determine their possible influence on thermocline thickness. Figure 6.6
plots thermocline thicknesses with respect to these factors. By this analysis, it was concluded that
∆T, experimental charge/discharge time, and heat losses effect thermocline thickness more than
increase in flow rate provided that Froude number is less than 1. On average, in these tests, the
thermocline Thickness is approximately 12” thick and occupied 17% of the height of the TES tank.
43
Figure 6.5: Showing Thickening of Thermocline during Charging & Discharging
Test # 15
Figure 6.6: Relating Thermocline Thickness to Temperature Difference and Flow Rate
44
In studies by Bahnfleth on larger commercial size TES tanks, the thermocline took up only 10 %
of the tank [10]. This suggests that the LabTES tank should have been designed to be taller.
and 6.2) Note that integrated capacity increases as ∆T increases. The average integrated capacity
for values of ∆T=8 to 12 ℉ was 1.37 Ton-hours in charging and 1.10 Ton-hours in discharging.
This trend agrees well with the mathematical definition of integrated thermal capacity given earlier
in Chapter 5. Discrepancies between the trend lines and the data point may be attributed to varying
conditions in the overall cooling system the tank is embedded in as well as measurement error in
the charge/discharge time and flow rate. Measured integrated capacity values needed to charge the
tank are consistently higher in charging than in discharging. This is due to unwanted heat transfer
between the tank and the environment. This contributes to an overall system efficiency and half
Note none of the charging tests have a corresponding discharge test with the same exact ∆T.
Indeed, most commercial stratified TES tanks do not run discharge processes immediately
following charging processes but instead store the built up thermal capacity for some time before
retrieving it. In order to better characterize the values of integrated capacity over the same range
of ∆T, one linear trend line was drawn for the charging data points and one trend line for the
discharging data points because by definition, capacity should be linearly related to ∆T. The values
of integrated capacity on these two trend lines are then used to calculate the system efficiency
values (8th column of Tables 6.1 and 6.2) for each ∆T as plotted in Figure 6.8. The system
efficiency compares the integrated capacity required to charge the tank to the integrated capacity
45
Figure 6.7 Relationship Between Integrated Capacity and Temperature Difference
46
retrieved from the tank during discharging. According to calculations, on average 80.9% of the
capacity stored in charging is retrieved for tests with values of ∆𝑇 = 6 to 12 ℉ with slightly higher
between 9 and 11 ℉ is 88.6%, and the average half FOM for discharging tests with a ∆T between
9 and 12 ℉ is 86.4%. Half FOM is calculated as per Eq. 5.2. The initial bulk temperature in the
tank and the inlet water temperature varied for each test causing varying values of ∆T. Tests with
values of ∆T outside these ranges were not included in these averages because tests with smaller
values of ∆T tend to exhibit significantly higher values of half FOM. This trend can be seen in the
results for Tests # 4 and # 11. Figure 6.9 shows data for half FOM plotted in relation to ∆T and
flow rate. Though linear trend lines are shown, note that the data points are scattered, suggesting
no obvious function relating these terms. Analysis of the data showed that the calculation of half
FOM is not a strong function of m ̇ or ∆T. Because the Froude number for all tests is less than 1,
it was not expected that half FOM would be significantly affected by mass flow rate (𝑚̇). This
Half FOM may potentially depend on several factors within the test. For this reason, further
analysis was done in order to determine the most influential factors effecting half FOM. Figure
6.10 shows the relationship between thermocline thickness and half FOM for tests with similar
values of ∆T. Only tests with values of ∆T between 9 and 12℉ are shown. Charging and
discharging tests are shown with separate trend lines, and both trends show a steady decrease in
thermocline thickness as half FOM improves. In this respect, the LabTES tank performed as
expected.
47
Figure 6.9 Relating Half FOM to Temperature Difference and Flow Rate
48
As demonstrated in Figure 6.10, experimental values of Half FOM do depend inversely on
thermocline thickness. This conclusion agrees with similar findings in past literature. However, it
was found that charge/discharge time most effected half FOM. Half FOM dropped if the tank
was charged or discharged for much longer than it takes for the mass of water in the tank to be
replaced once.
6.6 Conclusions
Based on the data shown, the LabTES tank performed as expected in accordance with result from
prior literature. Relationships between experimental flow rates and plug flow charge/discharge
times and the relationships between experimental thermocline thickness and half FOM are
consistent with those observed in other TES tanks studied by Bahnfleth and Stewart. The
thermocline (~12” thick) in LabTES tank was easily and repeatably established and moved up and
down to charge or discharge the chilled water tank over the range of flow rates and operating
temperature differences investigated. Larger than expected time increase were attributed to
thermocline thickness and external heat gain. The successful design, building, and sensible test
data obtained from the stratified LabTES tank produced the necessary reference data/ comparison
The significant heat gain due to the surface of the water being exposed to ambient temperature and
the limited amount of insulation on the sides and bottom of the tank prevent the LabTES tank from
keeping chilled water cold for more than a day. Heat gain in the LabTES tank may also be due to
the smaller size of the tank in comparison to the much larger TES tanks used on campus. For this
reason, the LabTES tank cannot adequately store thermal energy in accordance with the schedule
of energy output for the power plant. Heat gain over extended charge/discharge times was
considered during further testing. To minimize heat gain in augmented tests, charge/discharge
49
times were reduced by using higher flowrates that would still allow for a Froude number less than
1. Adding more outer insulation to tank would prevent unwanted external heat gain and improve
FOM but was not done to keep the tank parameters the same, except for the inclusion of PCM, to
keep the comparison fair. External heat gain is less of a problem in the larger TES tanks at
University of Cincinnati, which can maintain water at a chilled temperature for at least 7 days
because they hold a much larger mass of water. The large TES tanks are also underground,
50
7 Nominally Augmented Stratified TES Tank
Following system validation (i.e. sensible testing), all further tests were conducted with a
combination of PCM-filled tubes placed along the PVC rack to augment the thermal storage
capacity of the tank. See Figure 7.1. A combination of nine copper tubes was chosen as the nominal
case for augmented testing. Copper was chosen as the pipe material for its high thermal
conductivity. One RTD was placed in each PCM tube and one in the water just outside each tube,
making nine PCM RTDs and nine water RTDs. As in sensible tests, the tank was first operated
using varying flowrates between 0 and 2.6 GPM. Further tests were performed with a set point
flow rate of 2.5 GPM. The results of these tests are listed in Tables 7.1 and 7.2. Experimental
charge/discharge time was examined in two different ways. The experimental charge/discharge
time for the water in the tank is defined as the time from starting the charge/discharge to when the
top/bottom water RTD reaches within .5 ℉ of the inlet water temperature and is recorded on the
right side of the Experimental Charge Time column. On the left side is the time that it took for the
top/bottom PCM RTD to reach the same criteria. The integrated capacity column shows values
calculated based on experimental charge/discharge time of the PCM on the left and of the water
on the right.
51
Figure 7.1 Schematic of LabTES Tank
Tank is augmented with nominal configuration of copper pipes, showing numbered copper
tubes and positions of RTDs in both water and PCM.
Tube 1
Tube 2
Tube 3
Tube 4
Tube 5
Tube 6
Tube 7
Tube 8
Tube 9
52
Table 7.1: Results for Augmented Charging Tests
Test Average ∆T Experiment Theory Experiment Integrated System
Flow Rate (℉) Charge Time Charge 80% TT Capacity Efficiency
# (GPM) (min.) Time (in.) Charging 𝜂
(min.) (Ton-Hrs) (%)
PCM Water PCM Water
16 0.76 8.87 1062 357 208 10.73 1.50 1.47 86.6%
53
7.1 Effects of Subcooling and Latent Heat
Figure 7.2 shows the behavior of the temperature in each tube of PCM with respect to time during
the charging process in Test # 21. Each tube exhibits the same pattern of behavior. The charging
process is broken down here into four different regions delineated by the letters listed on Figures
7.2 and 7.3. The average inlet chilled water supply temperature in Figure 7.2 is 41.2.℉. For the
A-B: Sensible Heat Transfer- As chilled water enters the tank, the temperature of the PCM inside
the tubes decreases. The nine tubes are placed one above the other inside the tank. Therefore, the
PCM temperatures decrease one after another as the chilled water rises from section 9 at the bottom
of the tank to section 1 at the top of the tank until all tubes reach the fusion temperature of the
PCM.
B-C: Subcooling- The temperature of the PCM then drops significantly below the expected fusion
temperature of 46.4 ℉ (8℃) during subcooling. Puretemp8 does not solidify immediately upon
reaching the fusion temperature but instead must be cooled to an even lower temperature in order
for crystallization to begin so that freezing can occur. This phenomenon is referred to as
subcooling. The average temperature that the PCM in each tube must be cooled to, before
C-D: Latent Heat Transfer- After subcooling, all nine PCM temperatures then rise to about 44
℉ first the bottom tube and last the tubes near the top. During latent heat transfer, the temperature
of the PCM stays fairly constant as the PCM releases its latent energy of phase change.
D-E: Sensible Heat Transfer- Once the latent energy of phase change is transferred, it can be
assumed that all of the PCM is in a solid state. From this point forward, the frozen PCM cools
54
sensibly toward the temperature of the inlet water. Note that the rate of temperature drop after
phase change is not as sharp as compared to the sensible drop before the phase change due to
Variances in the amount of subcooling observed in each tube may be due to small variances in
sample size of PCM in each tube and the random nature of crystallization. Each individual liquid
element in a PCM sample reaches the temperature just below the freezing point crystallizes at a
slightly different time. Nucleation sites for crystallization are formed, and the rate of heat transfer
into the PCM tube as well as the rate of heat transfer between individual liquid PCM elements then
determines the rate of crystallization and thus the amount of subcooling. The effects of subcooling
are especially significant when the temperature differential between the inlet water temperature
and the freezing point is small. The larger the degree of subcooling is in comparison to this
temperature difference, the more negative impact subcooling has on the efficiency of the system.
Figure 7.3 shows the behavior of the temperature in each tube of PCM with respect to time during
A-B: Sensible Heat Transfer- At the onset of discharging, the tubes of PCM begin quickly rising
in temperature in order, one after the next, starting with tube 1 at the top of the tank where the
return water enters and moving downward to tube 9 at the bottom of the tank. However, because
subcooling doesn’t occur during the melting process, points B and C are at the same time.
C-D: Latent Heat Transfer- Once the tubes reach the fusion temperature and melting begins, the
temperature rises much more slowly, remaining fairly constant, until the latent heat energy is
overcome. Like subcooling, melting is much less predictable than sensible heating, and the tube
55
Figure 7.2 Tube Temperatures and Phase Change During Charging
Sensible Cooling
Subcooling
B
Latent Heat Transfer
C D Sensible Cooling
Sensible Heating
E
Sensible Heating
B,C D
A
56
temperatures no longer increase in the same order as they did before melting because each one
D-E: Sensible Heat Transfer- After melting, PCM temperature increases sharply once the latent
heat energy is overcome, moving toward the warm inlet water temperature.
Note that in discharging, the difference between the PCM fusion temperature and temperature of
the return water entering the tank is about 6 ℉, whereas in charging the difference between the
PCM fusion temperature and the chilled water entering the tank is only about 3 ℉. Because this
temperature difference is larger in discharging, the latent heat of phase change is overcome more
quickly than in charging. This can be seen when comparing the time scales of Figures 7.2 and 7.3.
Figure 7.4 shows the charge and discharge times for both the water and the PCM in the tank during
the augmented charge and discharge Tests, #16 through # 27. The charge/discharge times for water
in the nominally augmented tests were comparable to those of the sensible tests. As in sensible
tests, the experimental charge/discharge times for water are longer than the expected values.
However, the discrepancy between experimental and theoretical discharge times for water did
increase slightly in the augmented case. Charge time for both PCM and water decreases as flow
rate increases just as it did in sensible tests. The PCM tubes take up volume, leaving less water in
the tank in the augmented case. Therefore, values of theoretical charge time (plotted by the black
line in Figure 7.4) in augmented tests are slightly less than those in sensible tests at similar flow
rates. Experimental charge/discharge times in Tables 7.1 and 7.2 show the PCM took significantly
longer than the water to approach the inlet water temperature in both charging and discharging.
This is clearly shown by the PCM temperatures for discharging in Figure 7.5. This is because of
57
Figure 7.4 Experimental Charge Times of Water and PCM
58
the latent heat involved in the phase change and added conduction resistance of the PCM itself.
Note that for charging at flowrates less than 2 GPM the difference between PCM and water charge
times is significantly higher. The increased charge times for PCM indicate that in order to take full
advantage of the latent and sensible thermal storage of the PCM, the tank must be charged for
longer than it takes for the mass of water in the tank to be replaced once. The increased discharge
time means that it took longer for the water exiting the tank to heat up to the return water
temperature, implying that the tank was able to output cooler water for a longer period of time
during discharging.
Using the elapsed time of the thermocline passing and the rise rate, a value of thermocline
thickness was calculated using each of the nine water RTDs. The most accurate thermocline values
came from the temperature histories of the water RTDs located in the middle sections of the tank,
farther from the distribution ring openings. The average of these more accurate values was
recorded as the experimental 80% thermocline thickness for each test in Tables 7.1 and 7.2. Figures
7.6a and 7.6b, show the temperature traces for Tests # 22 and # 26, respectively, as compared to
the thermoclines of these augmented tests to those of sensible Tests # 7 and # 15, which exhibited
similar flow rates. When comparing the results for thermocline thickness in the nominal
augmented case to those of the sensible case listed in Tables 6.1 and 6.2, it can be concluded that
the presence of PCM has the most effect on system performance during discharging. In the
augmented case, the thermocline thickness in discharging is significantly larger. Because the PCM
changes phase early in the discharge process, when the difference between the initial bulk water
temperature in the tank and the inlet water temperature is higher, the PCM changes phase more
59
Figure 7.6a Thermoclines Measured from RTDs at Different Heights in the Tank
Figure 7.6b Thermoclines Measured from RTDs at Different Heights in the Tank
60
Figure 7.7: Relating Thermocline Thickness to Temperature Difference and Flow Rate
61
quickly. When the PCM changes phase more quickly, the faster internal heat transfer going on in
the tank increases thermocline thickness. Conversely, the PCM changes phase late in the charging
process when the temperature difference is small, and therefore phase change is slow and effects
thermocline thickness much less. In charging, the values of thermocline thickness for the
augmented case are not significantly different from those of the sensible case.
Figure 7.7 plots thermocline thickness with respect to temperature difference and flow rate for
both sensible and augmented tests. As in sensible tests, thermocline thickness in augmented tests
was not a strong function of temperature difference or flowrate for Froude numbers less than 1.
Note that with the small packing factor used in these augmented tests, the thermocline and thermal
stratification of water in the tank was not disrupted. Increasing packing factor, though increasing
thermal capacity, if made too large is expected to disrupt stratification, making the tank ineffective.
discharge Tests # 12 (sensible) and # 23(augmented with PCM). The area enclosed between the
sensible inlet and outlet lines is equal to the thermal capacity for cooling released to the power
plant system during the sensible (no PCM) discharge process. The area enclosed between the
nominal inlet and outlet lines is equal to the thermal capacity for cooling released to the power
plant system during the nominally augmented (with PCM) discharge process. These areas are
mathematically expressed as integrals from the starting time of the discharge process to the time
that the inlet line intersects with the outlet line (within .5 ℉). Note that this intersection occurs
much later in the nominally augmented case than it does in the sensible case. When calculating the
area from the measured data in 1-minute time increments, the cooling capacity delivered by the
sensible discharge is 1.16 ton-hours, whereas the cooling capacity delivered by the nominally
62
Figure 7.8 Comparing Sensible and Nominal Outlet Temperatures
With PCM
With PCM
63
Figure 7.9 Comparing Integrated Capacity in Charging and Discharging
64
augmented discharge is 1.31 ton-hours. From this it can be concluded that if the PCM is fully
charged and fully discharged, the nominal augmentation of the TES tank does provide significantly
Figure 7.8 (bottom) shows the temperature histories over time of the inlet and outlet RTDs for the
charge tests # 6 and # 18 (without and with PCM, respectively). Once again, the thermal capacity
for both the sensible and augmented tests can be calculated as the area enclosed between the
respective inlet and outlet lines. When calculated, the cooling capacity needed, based on water
charge time, for the sensible charge is 1.33 ton-hours, and the cooling capacity required by the
nominally augmented charge is 1.20 ton-hours, .13 ton-hours less since the PCM tubes take up
Figure 7.9 plots the integrated capacity, based on water charge time, for nominally augmented tests
16 to 27 along with linear trend lines to estimate the relationship between integrated capacity and
discharging are then used to calculate the values of system efficiency plotted in Figure 7.10. The
average system efficiency for nominally augmented tests was 87.5%, significantly higher than in
sensible tests due to higher integrated capacity in discharge. Note that the system efficiency is
slightly higher when temperature difference is higher. This is because larger temperature
differences allow for faster phase change of the PCM, storing or releasing large amounts of thermal
Notice that the values of system efficiency in discharging for the augmented case is significantly
higher than that in the sensible discharging case. The higher system efficiency in the augmented
discharging case can be attributed to a significant discrepancy in the average mass of water that
went through the tank during augmented charging tests and average mass of water that went
65
through the tank during augmented discharging tests. In Tables 7.1 and 7.2, observe that the values
for flow rate in discharging are consistently higher than those in charging. This may also possibly
contribute to the higher values of thermocline thickness observed in discharging. Also, the
experimental water charge time is generally much greater in discharging than it is in charging.
This means that over all a significantly greater amount of water mass traveled through the tank
during discharging tests than in charging tests. This means that values for integrated capacity in
discharging were greater than they would have been had the discharging tests used the same
amount of water mass as was used in the charging tests. These higher values of integrated capacity
in discharging artificially boosted values of system efficiency. It can be concluded that both system
efficiency and integrated capacity are not exclusively related to temperature differential but also
to the mass the passes through the tank. Therefore, in future tests, the water mass used in charging
Figure 7.11 compares the integrated capacity retrieved from the TES tank during discharging from
the sensible case verses the nominally augmented case. Note that both trend lines for the nominally
augmented case show greater integrated capacity values than the trend line for the sensible case.
The trend line for the nominally augmented integrated capacity, based on PCM charge time, shows
the greatest augmentation because this is the case in which the tank is discharged for the longest
period of time. Further tests are desired in order to verify the slopes of these trend lines. However,
the trend lines, plotted in Figure 7.11 were used to calculate the percentage of augmentation shown
in Figure 7.12 by dividing the difference between the integrated capacity given by either nominal
trend line and the sensible trend line at the same value of ∆𝑇 in Figure 7.11 over the value of
integrated capacity given by the sensible trend line and multiplying that by 100%. Based on this
66
Figure 7.11: Comparing Integrated Capacity in Discharging
67
calculation, it was found that when discharging the nominally augmented tank only long enough
for all RTDs in the tank to reach near the inlet temperature (i.e. curve based on water charge time),
the integrated capacity retrieved from the augmented tank was 5-15% higher than the integrated
capacity retrieved from a completely sensible tank operated at the same temperature difference.
Measured augmentation based on PCM charge time is much higher, even higher than our ideal
theoretical prediction obtained in chapter 3 of 9.821% at ∆T= 6 ℃ (10.8 ℉). However, the
measured augmentation calculation gives more reasonable values as the temperature difference is
7.5 Conclusions
Tests # 16 through # 27 show that the TES tank still performs its original function when
augmented. In fact, it was found that the augmented TES tank outputs a larger mass of cooler water
over a longer period of time than the purely sensible tank. The practicality of augmenting the
thermal storage of a stratified tank using tubes full of PCM can perhaps be measured by the
increased discharge times of the water in the tank rather than by increased half FOM or system
efficiency. Increased water discharge time indicates that the water exiting the tank during
discharging takes longer to warm up. This means that at a constant mass flow rate, the augmented
tank delivers a larger mass of cool water to the system. If given this, then augmenting the tank
with PCM delivers output chilled water for longer periods of time, and hence more capacity. This
would be an advantage to any system that the TES tank is employed in.
One must, however, also consider the amount of cooling capacity used to charge the TES tank in
the first place as well as the amount of cold storage lost to the tank’s surroundings during the time
in between the end of the charging process and the start of the discharge process. If the tank is not
68
well insulated and operated in a specific manner, this increased capacity may not necessarily
Based on these nominally augmented experiments, the best practices for charging the LabTES tank
are as follows. The augmented tank must be charged until the PCM reaches the inlet water
temperature, ensuring that the PCM is in the solid phase. When using flowrates above 2 GPM, this
does not take a significantly longer time than it would take for the water to reach the inlet water
temperature. Charge time for the PCM becomes significantly longer than charge time for water
when using flowrates below 2 GPM, decreasing half FOM. For this reason, all further experiments
The most efficient way to discharge the TES tank is to begin discharging immediately at the end
of the charging process and discharge the tank completely. However, most commercial TES tanks
are not operated that way and are instead discharged only enough to cover a specific cooling load
needed by the system at the time. According to Figure 7.4, the largest difference between the
nominal and sensible discharging capacities occurred at the end on the discharge process.
Therefore, in order to take full advantage of the extra capacity provided by augmentation, a TES
Ideally, we would want the PCM to charge in the same amount of time it takes for the thermocline
to pass through the tank. However, as the experiments here revealed, because the PCM takes longer
to charge and discharge than it takes for the tank water to be replaced, the overall efficiency of the
charging process would have to be sacrificed in order to achieve the maximum possible capacity.
It is hypothesized that increasing the rate of heat transfer between the PCM and the water might
allow for the PCM to charge in a shorter time period. However, in order for the tank to gain more
69
capacity the tank would still have to be charged for longer than it takes to replace the mass of water
The packing factor is the percentage by mass of the storage medium in the tank that is PCM, and
the mass packing factor for the nominal augmented case is only 1.63%. The rest of the storage
medium in the tank is water. Because the packing factor is small, it was not expected that the
presence of PCM in the tank would affect the thermocline significantly. While an increased
packing factor is desirable to increase latent storage capacity, increasing the packing factor may
have a more significant negative effect on the thermocline and the system efficiency for the tank.
70
8 Overall Conclusions and Future Work
Over all, the LabTES experiments were successful and provided a more detailed knowledge of
challenges involved in the implementation of stratified cold storage augmented with PCM. The
following is a summary of the conclusions and lessons learned from these experiments.
8.1 Conclusions
All original objectives of this study were met. The nominally augmented tank outputs a larger mass
of cooler water over a longer period of time than the purely sensible tank. According to the
approximately 10% more thermal capacity during the discharging process than the sensible tank
delivered, making the experiment an overall success. Regardless of the internal heat transfer
involved with the PCM augmentation, the laboratory TES tank still performed its original function,
and the thermocline was not significantly disrupted. These findings provided proof of concept for
The laboratory stratified TES tank was designed and was installed with its accessories and
instrumentation in line with the chilled water and return water supplies of the University of
Cincinnati east power plant. The tank containing only water and using only sensible thermal
storage was charged and discharged multiple times in order to gather reference data. Using this
data, it was verified that the laboratory TES tank behaved as expected in accordance with literature
describing other commercial TES tanks. However, the small size and depth of the laboratory TES
tank did allow for increased unwanted external heat transfer and a shorter residence time for the
thermocline to form and travel the height of the tank. The tank was successfully augmented with
a PVC rack holding 9 copper tubes filled with PureTemp8 PCM. Charge and discharge tests were
71
run in order to obtain new tank performance data which was then compared to the reference data
Current set-up requires optimization. In future studies, there are several improvements that could
be made to the laboratory TES tank system. It is recommended that the laboratory TES tank depth
be increased to at least 15 ft. There should also be a significant increase in the amount of insulation
around the tank. And the air temperature outside the tank should be carefully controlled and made
as constant as possible. It is also essential to improve the flow rate control and measurement
instrumentation. An increased number of RTDs to measure temperature both inside the PCM tubes
and in the water surrounding them inside the tank would offer better insight into the behavior of
the thermocline and allow for more accurate thermal modeling of the tank.
The performance enhancement for tank when using PCM was determined using calculations of
integrated capacity, half FOM, and system efficiency as described by Bahnfleth in his experiments
with full scale stratified tanks [6]. Because the nominally augmented tank provided more increased
integrated capacity in discharging, the values of system efficiency in the nominally augmented
tests were also higher than in sensible tests. However, it is desirable to have more data points to
verify that this level of augmentation can be consistently reproduced. Possible negative effects on
thermocline and tank stratification were considered. It was theorized that increasing the packing
factor of the PCM would eventually degrade the thermocline. However, the small mass packing
factor used in this study did not prevent stratification. Two extra discharge cycles were ran using
different numbers of PCM tubes in the tank to examine the effect of larger and smaller packing
factors on the thermocline. This data can be viewed in Appendix A, Figure A.6.
72
This study ultimately provided proof of concept for the inclusion of PCM to augment stratified
TES tanks at University of Cincinnati. A system of cheaply produced cylindrical heat exchanger
tubes could feasibly be used to integrate latent thermal storage with the sensible thermal storage
of the stratified TES tanks. However, further testing will be required in order for full integration
to take place.
thermocline to pass. (The 2” diameter PCM tubes used as heat exchangers in the current
experimental set-up take longer to charge than it takes for the tank water to be replaced.) This goal
might be achieved through optimizing the material, size, shape, wall thickness, and location of the
heat exchangers in the tank. Simply changing the material of the heat exchanger could improve
the thermal conductivity of the tube walls and provide greater heat transfer. Future experiments
should be performed to examine whether smaller or large diameter tubes should be used. Though
other shapes of heat exchangers would be less affordable than tubes, the pros and cons of spherical
heat exchangers verses cylinders or the possibility of adding internal fins to the heat exchangers
should be investigated. The heat transfer between the PCM and the water might also be affected
by the heat exchanger’s location in tank. Heat exchangers located closer to the bottom of the tank
in charging would be exposed to the greatest temperature difference for the longest amount of time
possible, driving heat transfer. Likewise, heat exchangers located toward the top of the tank during
discharging would experience faster heat transfer. All of these factors will have to be taken into
account to produce a system that would be optimized for integration with the University of
73
Just as important to the optimization of internal heat transfer is the type of PCM used in the system.
When selecting a PCM to use in the University tanks, there must be thorough in house studies to
confirm the thermal conductivity, specific heat, latent heat, and chemical compatibility of the
PCM. Special attention should be paid to the freezing and melting points of the PCM because the
operating temperature range used in the University of Cincinnati water cooling system is relatively
small. It is desirable for the PCM to have a freezing and melting temperature that is halfway
between the average chilled water inlet temperature and the average return water temperature of
the system. It is also vital that the subcooling of the PCM be minimized as much as possible to
ensure consistent solidification in the intended time period. And last, chemical compatibility
between the PCM and the material of the heat exchanger should be considered. The PCM should
be a non-toxic material that will not cause excess corrosion of the heat exchanger and would not
harm the water quality in the case of a leak in the heat exchanger wall.
In support of these optimizations, thermal and mathematical modeling should be performed. This
should include the modeling of the heat transfer between the PCM inside the heat exchanger tube
and the water surrounding it. When there is a temperature difference between the water and the
PCM, it is possible for a thermal plume to form around the heat exchanger causing unwanted
mixing in the tank. It is important that these thermal plume effects also be modeled around tubes
during charging and discharging. Future modeling of the accurate internal heat transfer in the tank
and heat exchanger tubes will result in knowledge of how much mass of the PCM is in solid or
liquid phase at any given time in the charging and discharging process.
74
References
1. Wildin, M., Truman, C. (1985). Evaluation of Stratified Chilled Water Storage Techniques,
Vol. 1: Findings, Vol. 2: Appendices. Electric Power Research Institute Report EM-4352.
2. Wildin, M. (1990). Diffuser Design for Naturally Stratified Thermal Storage. ASHRAE
3. Truman, C., Wildin M. (1989). Finite Difference Model for Heat Transfer in a Stratified
Thermal Storage Tank with Throughflow. Numerical Heat Transfer with Personal
Models for Stratified Thermal Storage Tanks. ASME Journal of Solar Energy Engineering,
111(3), 204-210.
5. Wildin, M. (1991). Flow Near the Inlet and Design Parameters for Stratified Chilled Water
Performance in Stratified Chilled Water Storage Tanks with Radial Diffusers: Part 1—
Performance in Stratified Chilled Water Storage Tanks with Radial Diffusers: Part 2—
75
Dimensional Analysis, Parametric Simulations and Simplified Model Development.
10. Bahnfleth, W., Musser, A. (1999). Parametric Study of Charging Inlet Diffuser
Performance in Stratified Chilled Water Storage Tanks with Radial Diffusers. Final Report.
11. Mackie, E. and Reeves G. (1988). Stratified chilled-water storage design guide, EPRI EM-
4852.
12. Mehling, H., Cabeza, L. (2008). Heat and Cold Storage with PCM. Berlin Heidelberg:
Springer-Verlag.
13. Zhang, Y., Jiang, Y. & Jiang, Y. (1999). A Simple Method, the T-History Method, of
Determining the Heat of Fusion, Specific Heat and Thermal Conductivity of Phase-Change
14. Dorgan, C., Elleson, J. (1993). Design Guide for Cool Thermal Storage. ASHRAE
Transactions.
15. Bergman, T., Levine, A., Incropera, F., Dewitt, D. (2011). Fundamentals of Heat and Mass
17. Wildin, M., Mackie, E., Harrison W. (1990). Stratified Thermal Storage: A New/Old
18. Grubbs J. (2012). University of Cincinnati West Campus Thermal Storage System
76
19. Lazaro A., Gunther E., Mehling H., Hiebler S., Marin J., Zalba B. (2006). Verification of
20. Günther, E., Hiebler, S., Mehling, H. (2006). Determination of the Heat Storage Capacity
Stockton USA.
21. Marin, J., Zalba B., Cabeza L., Mehling H. (2003). Determination of the Enthalpy-
Temperature Curves of Phase Change Materials with the T-History Method – Improvement
23. Yinping, Z., Yi, J., and Yi, J. (1999). A Simple Method, the T-History Method, of
Determining the Heat of Fusion, Specific Heat and Thermal Conductivity of Phase-Change
77
Appendices
78
Figure A.2: Thermoclines of Sensible Tests in 15 minute Increments Charging
120 min
75 min
45 min
90 min 60 min
30 min
45 min
60 min
15 min
30 min
30 min
0 min 15 min 0 min 0 min
0 min 0 min
0 min
15 min
30 min
15 min
30 min
60 min
45 min 30 min
90 min 45 min
60 min
60 min
120 min 75 min
75 min
90 min
150 min 105 min
79
Figure A.4: Comparing Thermoclines of Nominally Augmented and Sensible Tests in 15
Minute Increments Charging
90 min 90 min
75 min 75 min
60 min
60 min
45 min
45 min
30 min
30 min
15 min
15 min 0 min
0 min
0 min
0 min
15 min
15 min
30 min
30 min
45 min
45 min
60 min
90 min
60 min 75 min 75 min
80
Figure A.6: Testing Different Packing Factors of PCM
81
82
Appendix B: Matlab Codes
Because calculations had to be run many times over for each different test data set, an overarching
code was made in order to call the function “TES Analysis” that would perform all the desired
calculations for the data analysis of each test. This “RUN” code is as follows:
%%%%%Run AAAALLLL the Data!!!!!! Create a spreadsheet with the results!
clear
close
clc
filename='TESCalc_25July2016.xlsx';
VFRMethod=1;
syms E dTwater
E=.1*dTwater;
%%Running data for sensible tests%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%
sheet=1;
%%Sensible Charging
TESAnalysis_Sensible(xlsread('625C20140530.xlsx','A8:AD272'),0.8600,filename,
sheet,'B3',E,VFRMethod);
TESAnalysis_Sensible(xlsread('625sensible20140908to10.xlsx','A8:AD1299'),0.88
66,filename,sheet,'B4',E,VFRMethod);
TESAnalysis_Sensible(xlsread('125C20140529.xlsx','A8:AD195'),1.4700,filename,
sheet,'B5',E,VFRMethod);
TESAnalysis_Sensible(xlsread('125sensible20140916.xlsx','A8:AD171'),1.5739,fi
lename,sheet,'B6',E,VFRMethod);
TESAnalysis_Sensible(xlsread('125sensible20140905.xlsx','A8:AD249'),1.8339,fi
lename,sheet,'B7',E,VFRMethod);
TESAnalysis_Sensible(xlsread('250sensible20140903.xlsx','A8:AD199'),2.1353,fi
lename,sheet,'B8',E,VFRMethod);
TESAnalysis_Sensible(xlsread('218C20140528.xlsx','A8:AD122'),2.2146,filename,
sheet,'B9',E,VFRMethod);
TESAnalysis_Sensible(xlsread('250sensible20140915.xlsx','A8:AD190'),2.2182,fi
lename,sheet,'B10',E,VFRMethod);
TESAnalysis_Sensible(xlsread('250C20140527_2.xlsx','A8:AD159'),2.2500,filenam
e,sheet,'B10',E,VFRMethod);
%%Sensibble Discharging
TESAnalysis_Sensible(xlsread('250sensible20140903.xlsx','A200:AD1228'),0.3906
,filename,sheet,'B13',E,VFRMethod);
83
TESAnalysis_Sensible(xlsread('625sensible20140908to10.xlsx','A1300:AD2550'),0
.9452,filename,sheet,'B14',E,VFRMethod);
TESAnalysis_Sensible(xlsread('625D20140530.xlsx','A8:AD335'),1.0400,filename,
sheet,'B15',E,VFRMethod);
TESAnalysis_Sensible(xlsread('125sensible20140905.xlsx','A250:AD1454'),1.5854
,filename,sheet,'B16',E,VFRMethod);
TESAnalysis_Sensible(xlsread('125sensible20140916.xlsx','A173:AD2201'),1.7267
,filename,sheet,'B17',E,VFRMethod);
TESAnalysis_Sensible(xlsread('125D20140529.xlsx','A8:AD175'),1.7300,filename,
sheet,'B18',E,VFRMethod);
TESAnalysis_Sensible(xlsread('250D20140527.xlsx','A8:AD103'),2.1500,filename,
sheet,'B19',E,VFRMethod);
TESAnalysis_Sensible(xlsread('250sensible20140915.xlsx','A193:AD593'),2.4545,
filename,sheet,'B20',E,VFRMethod);
TESAnalysis_Sensible(xlsread('218D20140528.xlsx','A8:AD185'),2.4600,filename,
sheet,'B20',E,VFRMethod);
TESAnalysis_Nominal1(xlsread('DoubleChargeCopper625_20140626to28.xlsx','A8:AD
403'),0.7552,filename,sheet,'B3',E,VFRMethod);
TESAnalysis_Nominal2(xlsread('Single125C20140618.xlsx','A8:AD509'),1.2794,fil
ename,sheet,'B4',E,VFRMethod);
TESAnalysis_Nominal(xlsread('CompleteCopperCharge_20140609to10.xlsx','A8:AD13
78'),2.2146,filename,sheet,'B11',E,VFRMethod);
TESAnalysis_Nominal(xlsread('2hchargeWaitcharge_20140707.xlsx','A8:AD490'),2.
1971,filename,sheet,'B7',E,VFRMethod);
TESAnalysis_Nominal(xlsread('2hchargeWaitchargeWaitCharge_20140709.xlsx','A8:
AD772'),2.2189,filename,sheet,'B9',E,VFRMethod);
TESAnalysis_Nominal(xlsread('2hchargeWaitchargeWaitCharge_20140708.xlsx','A8:
AD750'),2.1808,filename,sheet,'B6',E,VFRMethod);
TESAnalysis_Nominal(xlsread('2hchargeWaitchargeWaitCharge_20140710to11.xlsx',
'A8:AD1719'),2.2200,filename,sheet,'B10',E,VFRMethod);
TESAnalysis_Nominal(xlsread('2hchargeWaitcharge_20140702.xlsx','A8:AD1443'),2
.1219,filename,sheet,'B5',E,VFRMethod);
84
TESAnalysis_Nominal(xlsread('CompleteCopperDischarge250_20140623.xlsx','A8:AD
1386'),2.5104,filename,sheet,'B16',E,VFRMethod);
TESAnalysis_Nominal(xlsread('CopperDischarge125_20140625.xlsx','A8:AD1056'),1
.6524,filename,sheet,'B13',E,VFRMethod);
TESAnalysis_Nominal(xlsread('2hchargeWaitcharge_20140707.xlsx','A492:AD1380')
,2.4368,filename,sheet,'B14',E,VFRMethod);
TESAnalysis_Nominal(xlsread('2hchargeWaitchargeWaitCharge_20140709.xlsx','A77
4:AD1357'),2.4829,filename,sheet,'B15',E,VFRMethod);
TESAnalysis_Nominal(xlsread('2hchargeWaitchargeWaitCharge_20140708.xlsx','A76
0:AD1378'),2.6274,filename,sheet,'B17',E,VFRMethod);
A slightly modified version of this code was used to perform the necessary data analysis
calculations for each test. However the generalized code is as follows:
% This function calculates the Mass of Water and Mass of PCM present in the
% tank, the Mass Packing Factor, the Experimental and Theoretical
% Charge/Discharge Times, Temperature Difference, Average Thermocline
Thickness, Integrated and Maximum
% Capacity, and Half FOM and enters these values into output vectors.
function [vector,TTtable,Tin, TinitialBulk,data] =
TESAnalysis_Nominal(data,VFR,filename,sheet,xlRange,E, VFRMethod)
SetUp='9Cu';
%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%
%%%%%%%%%%%%%%%% DEFINE CONSTANTS %%%%%%%%%%%%%%%%%%%%%%%%%%
%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%
85
switch SetUp
case 'Sensible'
Vtubes=0; %m^3
VPCMAlone=0;%m^3
case '9Cu'
Vtubes=.0135; %m^3
VPCMAlone=.01147;%m^3
case '4Cu'
Vtubes=.006; %m^3
VPCMAlone=.01147/9*4;%m^3
case '9Al'
Vtubes=.0198; %m^3
VPCMAlone=.01336;%m^3
case '2222'
Vtubes=.0138; %m^3
VPCMAlone=(.01147/9*2)+(.01336/9*2)+(.014275/16*2)+(.011943/9
*2);%m^3
case '16Al15'
Vtubes=.0208; %m^3
VPCMAlone=.014275;%m^3
case '9PVC'
Vtubes=.0171; %m^3
VPCMAlone=.011943;%m^3
case '4Al2+4Al15'
Vtubes=.014; %m^3
VPCMAlone=(.01336/9*4)+(.014275/16*4);%m^3
case '9Cu9Al'
Vtubes=.0333; %m^3
VPCMAlone=.01147+.01336;%m^3
otherwise
disp('you spelled your SetUp variable wrong');
end
V=H*A-Vrack-Vheader-Vtubes; %m^3
M=rhoh2o*V;%Kg water alone
MPCMAlone=VPCMAlone*rhoPCMlq;%kg
lastwaterRTD=data(1:length(data),12);
lastPCMRTD=data(1:length(data),3);
ChargeTimeWater=lastwaterRTD-Tin;
ChargeTimeWater(1:2)=1;
ChargeTimePCM=lastPCMRTD-Tin;
86
ChargeTimePCM(1:2)=1;
elseif data(1,2)==1
mode='Discharging'
inlet=26;%collum number to reference in data matrix
outlet=28;%collum number to reference in data matrix
Th(1:2)=0;
for i=3:length(data)
Tin(i,1)=mean(data(2:i,inlet));%average system return temp
end
TinitialBulk=mean(data(1,12:20));%initial bulk temperature of
tank
lastwaterRTD=data(1:length(data),20);
lastPCMRTD=data(1:length(data),11);
ChargeTimeWater=Tin-lastwaterRTD;
ChargeTimeWater(1:2)=1;
ChargeTimePCM=Tin-lastPCMRTD;
ChargeTimePCM(1:2)=1;
else
disp('not a charge or discharge. Check your data.')
end
%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%
%%%%%%%%%%%%%%%%%%% Calculatiions %%%%%%%%%%%%%%%%%%%%%%%%%
%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%
% RiseRate
Aft=((29+3/16)/2/12)^2*pi;%Area of tank in ft^2.
RiseRate=VFR*0.133681/Aft*12;%in/min
87
mode='Charging'
Tc=TinletWater
Th=TinitialBulk
elseif data(1,2)==1
mode='Discharging'
Tc=TinitialBulk
Th=TinletWater
else
disp('not a charge or discharge. Check your data.')
end
RTD=[outlet,13,14,15,16,17,18,19];
TTtable=zeros(1,10);
for n=1:8
[t1(1,n),t2(1,n),T1(1,n),T2(1,n),Tone(1,n),Ttwo(1,n),Temp,Time] =
...
FindingThermoclineV4_nograph(data,RTD(n),Tc,Th,mode,E);
TTref=[2,3,4,6,7,8];
TTtable(n)=abs(t2(n)-t1(n))*RiseRate;
TTtable(9)=mean(TTtable(TTref)); % average 80% thermocline
thickness
TTtable(10)=abs(TTtable(2)-TTtable(8));% how much does
thermocline thickness increase over course of process?
end
TTavg=TTtable(9)
%%%%%%Half FOM
dt=1;%minutes
Tinlet=F2C(data(1:ChargeTimeWater,inlet));
Toutlet=F2C(data(1:ChargeTimeWater,outlet));
CintWater=sum(ch2o.*MFR.*abs(Tinlet-Toutlet)*dt)./12660;%ton-hr
Tinlet2=F2C(data(1:ChargeTimePCM,inlet));
Toutlet2=F2C(data(1:ChargeTimePCM,outlet));
CintPCM=sum(ch2o.*MFR.*abs(Tinlet2-Toutlet2)*dt)./12660;%ton-hr
Cmax=MFR*(ChargeTimeWater)*ch2o*abs(F2C(Th)-F2C(Tc))/12660% ton-hr
CmaxPCM=MFR*(ChargeTimePCM)*ch2o*abs(F2C(Th)-F2C(Tc))/12660;% ton-hr
HalfFOM=CintWater/Cmax*100;
HalfFOMPCM=CintPCM/CmaxPCM*100;
if isempty(ChargeTimePCM)==1
ChargeTimePCM=0;
CmaxPCM=0;
HalfFOMPCM=0;
end
%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%
%Ideal Sensible Integrated Capacity for same dT and flow rate
CmaxSensibleIdeal=MFR*(ChargeTimeTheory)*ch2o*abs(F2C(Th)-
F2C(Tc))/12660;% ton-hr
88
%%%%%%The Vector
vector=[VFR,dTwater,TTavg,ChargeTimePCM,ChargeTimeWater,ChargeTimeTheory,Half
FOMPCM,HalfFOM,CintPCM,CintWater,Cmax,CmaxSensibleIdeal];
vector(13:22)=fliplr(TTtable);
Supporting Functions
“FindingThermoclineV4”
function [t1,t2,T1,T2,Tone,Ttwo,Temp,Time] =
FindingThermoclineV4_nograph(data,RTD,Tc,Th,mode,E)
close all
%Delta T
dT=abs(Tc-Th);
RTD=RTD
%Defining %80 of the dT. The thermcline lies between these temperatures.
switch mode
case 'Charging'
T1=Th-(E);
T2=Tc+(E);
case 'Discharging'
T1=Tc+(E);
T2=Th-(E);
end
Temp=data(1:end,RTD);
Time=[1:1:length(Temp)];
%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%
%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%
Tone= interp1(Time,Temp,t1);
t1=t1;
switch mode
case 'Charging'
if Temp(t1)<T1&&T1<Temp(t1-1)
break
89
else t1=t1-1;
end
case 'Discharging'
if (Temp(t1)>T1&&T1>Temp(t1-1))
break
else t1=t1-1;
end
end
end
while Tone-T1>0 &&t1>=1&&t1<=length(Time)
Tone= interp1(Time,Temp,t1);
t1=t1;
switch mode
case 'Charging'
t1=t1-.0001;
case 'Discharging'
t1=t1-.0001;
end
if abs(Tone-T1)<=.0001
break
end
end
if t1<=1||t1>=length(Time)
disp('Use a different RTD for t1')
end
%Loop uses tlimit as initial guess for th (time at which temperature is
%equal to Th) and iterates to find th
t2=find(Temp>=T1,1);%t2=find(floor(Temp)==round(mean(Temp)),1)
if isempty(t2)==1
t2=1;
end
Ttwo=T1;
while T2-Ttwo>0 &&t2>=1&&t2<=length(Temp)
Ttwo= interp1(Time,Temp,t2)
t2=t2;
switch mode
case 'Charging'
if Temp(t2)>T2&&T2>Temp(t2+1)
break
else t2=t2+1;
end
case 'Discharging'
if Temp(t2)<T2&&T2<Temp(t2+1)
break
else t2=t2+1;
end
end
end
Ttwo= interp1(Time,Temp,t2);
t2=t2;
90
switch mode
case 'Charging'
t2=t2+.0001;
case 'Discharging'
t2=t2+.0001;
end
if abs(Ttwo-T2)<=.0001
break
end
end
%disp('t2 loop ran')
if t2<=1||t2>=length(Time)
%disp('Use a different RTD for t2')
end
case 'Charging'
t1=find(Temp<T2,1);%t1=find(floor(Temp)==round(mean(Temp)),1)
if isempty(t1)==1
disp('alt t1')
t1=length(data);%t1=find(ceil(Temp)==round(mean(Temp)),1)
end
Tone=T2;
while Tone-T1>=0 &&t1>=1&&t1<=length(Time)
Tone= interp1(Time,Temp,t1);
t1=t1;
switch mode
case 'Charging'
if Temp(t1)<T1&&T1<Temp(t1-1)
%disp('first t1 loop ran')
break
else t1=t1-1;
end
case 'Discharging'
if (Temp(t1)>T1&&T1>Temp(t1-1))
%disp('first t1 loop ran')
break
else t1=t1-1;
end
end
end
while Tone-T1>0 &&t1>=1&&t1<=length(Time)
Tone= interp1(Time,Temp,t1);
t1=t1;
91
switch mode
case 'Charging'
t1=t1-.0001;
case 'Discharging'
t1=t1-.0001;
end
if abs(Tone-T1)<=.0001
break
end
end
%disp('t1 loop ran')
if t1<=1||t1>=length(Time)
%disp('Use a different RTD for t1')
end
%Loop uses tlimit as initial guess for th (time at which temperature is
%equal to Th) and iterates to find th
t2=find(Temp<T1,1);%t2=find(floor(Temp)==round(mean(Temp)),1)
if isempty(t2)==1
%disp('alt t2')
t2=find(Temp>=T1,1);%t2=find(ceil(Temp)==round(mean(Temp)),1)
end
Ttwo=T1;
while T2-Ttwo>0 &&t2>=1&&t2<=length(Temp)
Ttwo= interp1(Time,Temp,t2);
t2=t2;
switch mode
case 'Charging'
if Temp(t2)>T2&&T2>Temp(t2+1)
%disp('first t2 loop ran')
break
else t2=t2+1;
end
case 'Discharging'
if Temp(t2)<T2&&T2<Temp(t2+1)
%disp('first t2 loop ran')
break
else t2=t2+1;
end
end
end
%disp('end first loop')
while T2-Ttwo>=0 &&t2>=1&&t2<=length(Temp)
Ttwo= interp1(Time,Temp,t2);
t2=t2;
switch mode
case 'Charging'
t2=t2+.0001;
case 'Discharging'
t2=t2+.0001;
end
if abs(Ttwo-T2)<=.0001
break
end
end
92
%disp('t2 loop ran')
if t2<=1||t2>=length(Time)
%disp('Use a different RTD for t2')
end
end
end
“levelmeterFR”
%This code uses the time record of flowrate from the PLC controler,
eliminates bad data points, and calculates the average flow rate
function [ flowrate,data ] = levelmeterFR(
data,ChargeTimeWater,lowlim,highlim )
%UNTITLED8 Summary of this function goes here
% Detailed explanation goes here
highlim=3;
data=data(1:ChargeTimeWater+1,24);
figure (1)
hist(data,[min(data):.1:max(data)]);
pause(5);
r=find(data(1:length(data),1)>lowlim);
data=data(r,1);
figure (2)
hist(data,[min(data):.1:max(data)]);
pause(5);
r=find(data<highlim);
data=data(r);
figure (3)
hist(data,[min(data):.1:max(data)]);
pause(5);
flowrate=mean(data);
end
93
Appendix C: Properties of PureTemp 8
94
Table A.1: Cost of PCM Only
Gallons of PCM Required at Price Per Gallon Cost of PCM
95
Appendix D: Addition Thermal Capacity Calculations
The following Matlab code was used to calculate the thermal capacity of the PVC rack, the PVC
distribution rings (headers), and the copper heat exchangers in the augmented tank.
Code
clear
clc
%Calculating the mass of the PVC rack and PVC headers...
Vrack=.0045; % Volume of PVC rack submerged in m^3
Vheader=.00082685192; %Volume of two PVC headers in m^3
rhoPVCrack=1450;%kg/m^3 Rigid PVC
rhoPVCheaders=1350;%kg/m^3 Flexible PVC
MassRack=rhoPVCrack*Vrack;%kg
Massheaders=rhoPVCheaders*Vheader;%kg
%Calculating the mass of the copper tubes. Vtubes was found using a water
%displacement test...
Vtubes=.0135; %m^3
VPCMAlone=.01147;%m^3
Vcopper=Vtubes-VPCMAlone;%m^3
rhoCu=8940;%kg/m^3
MassCu=rhoCu*Vcopper;%kg
Results
96
StorageCapacityTubes = 0.0034 Ton-Hours
sum = 0.007 Ton-Hours = 0.4509% of the theoretical thermal capacity of the augmented tank
The PVC rack with distribution rings and the copper tubes both contribute about equally to the
thermal capacity of the tank. However, both contributions are very small and negligible in
97