Classificatio Recommendations /
Item Category Findings/Observations
n Actions to be taken
Consult contractor for FDAS
FDAS - for All Home (Covering
Major (NETS - John Lennon - 0917-
GF and 2F - All Home Area)
*with existing troubles: Open 434-2121)for FDAS
Consult contractor
Major Circuit, Panel 1 Main Failure, (NETS - John Lennon - 0917-
Beacon Alarm 434-2121)
Consult contractor for FDAS
and Nippon for coodination of
Major *not interfaced with Elevator
installation (NETS - John
Lennon - 0917-434-2121)
*2F has active FDAS but
sounder and strobe light is
insufficient to prompt warning Consult contractor for FDAS
Major and alertness to the building (NETS - John Lennon - 0917-
occupants in case of 434-2121)
Fire Detection and emergencies
1
Alarm System (FDAS) *GF has 2 defective sounders
and GF only has 2 call points Consult contractor for FDAS
Major but defective. GF Smoke (NETS - John Lennon - 0917-
detectors are defective and GF 434-2121)
Zone 1 is Disabled.
Install Additional Smoke
*Stockroom/Storage Room has Detectors. Consult contractor
Major
no Smoke detector for FDAS (NETS - John Lennon
- 0917-434-2121)
Remarks:
Classificatio Recommendations /
Item Category Findings/Observations
n Actions to be taken
Consult contractor for FDAS
*No heat detectors at Kitchen
Major (NETS - John Lennon - 0917-
Area
Fire Detection and 434-2121)
1 Minor *Smoke detectors with cover Remove covers for easy detection
Alarm System (FDAS) Consult contractor for FDAS
*No smoke detector at Bar
Major (NETS - John Lennon - 0917-
Area
434-2121)
2 Fire Hose Cabinet N/A
NOTE: Fire Extinguishers
3 Fire Extinguishers should be monitored/checked
atleast once a month
4 Emergency Exits N/A
5 Evacuation Plan C/o Mall Admin
NOTE: Emergency lights
should be monitored/checked
6 Emergency Lights
atleast once a month or once
every two months
Automatic Fire
7 Sprinkler System OK
(AFSS)
Remarks:
Classificatio Recommendations /
Item Category Findings/Observations
n Actions to be taken
Consult accredited supplier for
*No smoke detectors at FDAS for installation of
Fire Detection and Major specified area (Fire code: Every Additional Smoke detectors.
1 enclosed room should have at
Alarm System (FDAS) (NETS - John Lennon - 0917-
least smoke detector) 434-2121)
Minor *Smoke detectors with cover Remove covers for easy detection
2 Fire Hose Cabinet N/A
Provide Fire extinguisher
within the Area. Locations of
Fire Extinguishers must be
*No Fire Extinguisher within the tagged with a signage (Fire
3 Fire Extinguishers Major
area Extinguisher Here). NOTE: It
also must be
monitored/checked at least
once or twice a month
4 Emergency Exits N/A
5 Evacuation Plan C/o Mall Admin
NOTE: Emergency lights
should be monitored/checked
6 Emergency Lights
atleast once a month or once
every two months
Provide additional sprinkler
Automatic Fire heads per room. Consult
*Lacks Spinkler heads at other
7 Sprinkler System Major accredited supplier for Fire
rooms
(AFSS) Protection (Nemickho - Elmer -
0920-782-1691)
Remarks:
Classificatio Recommendations /
Item Category Findings/Observations
n Actions to be taken
*Some Call Points are not
Remove displays that blocked
Major accessible (blocked by stock
the call point
displays)
Consult FDAS Contractor for
Fire Detection and *FDAS Panel with existing rectification of troubles (NETS
1 Major
Alarm System (FDAS) troubles - John Lennon - 0917-434-
2121)
*Smoke detectors with cover
Minor Remove covers for easy detection
(Some Areas and Utility Rooms)
Remarks:
Classificatio Recommendations /
Item Category Findings/Observations
n Actions to be taken
Fire Detection and Connected to All Day
1 OK
Alarm System (FDAS) Supermarket FDAS
2 Fire Hose Cabinet N/A
NOTE: Locations of Fire
Extinguishers must be tagged
with a signage (Fire
3 Fire Extinguishers
Extinguisher Here). It also
must be monitored/checked at
least once or twice a month
4 Emergency Exits N/A
5 Evacuation Plan C/o Mall Admin
NOTE: Emergency lights
should be monitored/checked
6 Emergency Lights
atleast once a month or once
every two months
Automatic Fire
7 Sprinkler System OK
(AFSS)
Remarks:
Classificatio Recommendations /
Item Category Findings/Observations
n Actions to be taken
Clear obstruction for easy
Minor - Admin *Call point is obstructed
Fire Detection and access during emergencies
1 Consult contractor for FDAS
Alarm System (FDAS) *Call point near finds-finds
Major (NETS - John Lennon - 0917-
entrance is defective
434-2121)
*Fire Hose Cabinet not readily Clear obstruction for easy
2 Fire Hose Cabinet Minor - Admin accessible since it is
access during emergencies
obstructed with stocks
*Fire Exit Door not readily Open barrel bolt during mall
4 Emergency Exits Minor accessible and it has a barrel operating hours and clear fire
bolt. exit of obstruction
5 Evacuation Plan C/o Mall Admin
NOTE: Emergency lights
should be monitored/checked
6 Emergency Lights
atleast once a month or once
every two months
Automatic Fire
7 Sprinkler System OK
(AFSS)
Remarks:
Classificatio Recommendations /
Item Category Findings/Observations
n Actions to be taken
Fire Detection and Connected to All Day
1 OK
Alarm System (FDAS) Supermarket FDAS
2 Fire Hose Cabinet N/A
*With Fire Extinguisher within
Minor - Admin the area but without Locations of Fire Extinguishers
monitoring must be tagged with a
signage (Fire Extinguisher
Here). NOTE: It also must be
monitored/checked at least
3 Fire Extinguishers Minor - Admin *Insufficient Fire Extinguisher once or twice a month
Remarks:
Classificatio Recommendations /
Item Category Findings/Observations
n Actions to be taken
*FDAS at Cinema not fully
Major functional since it is still on- C/o Mall Admin
Fire Detection and going installation
1
Alarm System (FDAS) Consult contractor for FDAS
*No smoke detector at Popcorn
Major (NETS - John Lennon - 0917-
factory
434-2121)
2 Fire Hose Cabinet N/A
*With Fire Extinguisher within
the area but without Locations of Fire Extinguishers
Minor - Admin
monitoring (Cinema Hallway, must be tagged with a
Offices and Projection Room) signage (Fire Extinguisher
3 Fire Extinguishers
Here). NOTE: It also must be
monitored/checked at least
Minor - Admin *Insufficient Fire Extinguisher once or twice a month
Remarks: