BUILDING NAME (PANEL):SHURA ISLAND - MAIN KITCHEN 1.All Dimension Hear Are Shown in Meters Unless Otherwise Noted.
2.This Drawing is to be read for fire alarm system only.
ADDRESS No. FLOOR No. LOOP TYPE LABEL 3.All installations shall be in accordance with the requirements of NFPA 72.
4.All type fire extinguishing panel shall be listed and comply with the
requirements of NFPA 2001.
ADDRESS FIRE ALARM GENT LOOP No.1 6.All conduit shall be electrical metallic tubing (EMT) ,UL listed .
7.All fire fighting isolating control valves shall be UL listed indicating valves
1 GF 1 P L1/D1/GF/SD/LOCKER ROOM and shall be provided with supervisory switches to be connected with monitor
module in the fire alarm system.
8.All HVAC units must be switched off in case of fire through control module
8 GF
AFC 1 MCP L1/D8/GF/MCP/STAFF ENTRANCE Key Plan DESCRIPTION
P SMOKE DETECTOR WITH ISOLATOR
L1/D11/GF/SD/CONTROL OFFICE
SOUNDER WITH FLASHER OUTER
11 GF 1 P SFI
ELE
SOUNDER WITH FLASHER INDOR
ELECTRICAL FIRE PUMP
DSL DIESEL FIRE PUMP
12 GF 1 P L1/D12/GF/SD/CORRIDOR STAFF EN FW
TW
DD
FLOW SWITCH
TAMPER SWITCH
DUCT DETECTOR WITH ISOLATOR
14 GF 1 P L1/D14/GF/SD/CORRIDOR STAFF EN
15 GF 1 P L1/D15/GF/SD/REST ROOM
16 GF 1 P L1/D16/GF/SD/RECEIVING OFFICE Consultant :
21 GF 1 MM L1/D21/GF/MM/ZCV-TS
22 GF 1 MM L1/D22/GF/MM/ZCV-FS
23 GF 1 P L1/D23/GF/SD/DRY STORE Safety Consultant :
Project Name :
ROO-OO2M06-ACC-XX-XX-SDW-FR-05011 C0
GENERAL NOTE:
BUILDING NAME (PANEL):SHURA ISLAND - MAIN KITCHEN 1.All Dimension Hear Are Shown in Meters Unless Otherwise Noted.
2.This Drawing is to be read for fire alarm system only.
ADDRESS No. FLOOR No. LOOP TYPE LABEL 3.All installations shall be in accordance with the requirements of NFPA 72.
4.All type fire extinguishing panel shall be listed and comply with the
requirements of NFPA 2001.
ADDRESS FIRE ALARM GENT LOOP No.1 6.All conduit shall be electrical metallic tubing (EMT) ,UL listed .
7.All fire fighting isolating control valves shall be UL listed indicating valves
1 GF 1 P L1/D1/GF/SD/LOCKER ROOM and shall be provided with supervisory switches to be connected with monitor
module in the fire alarm system.
8.All HVAC units must be switched off in case of fire through control module
8 GF
AFC 1 MCP L1/D8/GF/MCP/STAFF ENTRANCE Key Plan DESCRIPTION
P SMOKE DETECTOR WITH ISOLATOR
L1/D11/GF/SD/CONTROL OFFICE
SOUNDER WITH FLASHER OUTER
11 GF 1 P SFI
ELE
SOUNDER WITH FLASHER INDOR
ELECTRICAL FIRE PUMP
DSL DIESEL FIRE PUMP
12 GF 1 P L1/D12/GF/SD/CORRIDOR STAFF EN FW
TW
DD
FLOW SWITCH
TAMPER SWITCH
DUCT DETECTOR WITH ISOLATOR
14 GF 1 P L1/D14/GF/SD/CORRIDOR STAFF EN
15 GF 1 P L1/D15/GF/SD/REST ROOM
16 GF 1 P L1/D16/GF/SD/RECEIVING OFFICE Consultant :
21 GF 1 MM L1/D21/GF/MM/ZCV-TS
22 GF 1 MM L1/D22/GF/MM/ZCV-FS
23 GF 1 P L1/D23/GF/SD/DRY STORE Safety Consultant :
Project Name :
FA
ROO-OO2M06-ACC 04/10/2023 As Shown
ROO-OO2M06-ACC-XX-XX-SDW-FR-05011 C0
GENERAL NOTE:
BUILDING NAME (PANEL):SHURA ISLAND - MAIN KITCHEN 1.All Dimension Hear Are Shown in Meters Unless Otherwise Noted.
2.This Drawing is to be read for fire alarm system only.
ADDRESS No. FLOOR No. LOOP TYPE LABEL 3.All installations shall be in accordance with the requirements of NFPA 72.
4.All type fire extinguishing panel shall be listed and comply with the
requirements of NFPA 2001.
24 GF 1 P L1/D24/GF/SD/DRY STORE 6.All conduit shall be electrical metallic tubing (EMT) ,UL listed .
7.All fire fighting isolating control valves shall be UL listed indicating valves
25 GF 1 MM L1/D25/GF/MM/PUMP RM-RISER ACV and shall be provided with supervisory switches to be connected with monitor
module in the fire alarm system.
8.All HVAC units must be switched off in case of fire through control module
26 GF 1 MM L1/D26/GF/MM/ELE PUMP RUN in the fire alarm system.
9.All makeup fans in kitchen hood must be switched off in case of fire through
32 GF
AFC 1 MM L1/D32/GF/MM/DSL PUMP RUN Key Plan DESCRIPTION
P SMOKE DETECTOR WITH ISOLATOR
38 GF 1 MM L1/D38/GF/MM/ELE PUMP-TS/SUCTION
39 GF 1 MM L1/D39/GF/MM/PUMP RM -TS/SUCTION
40 GF 1 HD L1/D40/GF/HD/PUMP ROOM Consultant :
167 GF 1 HD L1/D167/GF/HD/PUMP ROOM
41 GF 1 P L1/D41/GF/SD/DRY STORE
42 GF 1 P L1/D42/GF/SD/CHEMICAL ROOM
43 GF 1 P L1/D43/GF/SD/STORE ROOM Main Contract :
44 GF 1 P L1/D44/GF/SD/BAKERY STORE
45 GF 1 DD L1/D45/GF/DD/BKRY STRE RETN DUCT
46 GF 1 P L1/D46/GF/SD/BAKERY WASH AR Safety Consultant :
Project Name :
FA
ROO-OO2M06-ACC 04/10/2023 As Shown
A -01
Drawing Number REVISIONS:
ROO-OO2M06-ACC-XX-XX-SDW-FR-05011 C0
GENERAL NOTE:
BUILDING NAME (PANEL):SHURA ISLAND - MAIN KITCHEN 1.All Dimension Hear Are Shown in Meters Unless Otherwise Noted.
2.This Drawing is to be read for fire alarm system only.
ADDRESS No. FLOOR No. LOOP TYPE LABEL 3.All installations shall be in accordance with the requirements of NFPA 72.
4.All type fire extinguishing panel shall be listed and comply with the
requirements of NFPA 2001.
47 GF 1 HD L1/D47/GF/HD/BAKERY AREA 6.All conduit shall be electrical metallic tubing (EMT) ,UL listed .
7.All fire fighting isolating control valves shall be UL listed indicating valves
48 GF 1 MM L1/D48/GF/MM/KITCHEN HOOD#6 and shall be provided with supervisory switches to be connected with monitor
module in the fire alarm system.
8.All HVAC units must be switched off in case of fire through control module
49 GF 1 HD L1/D49/GF/HD/BAKERY AREA in the fire alarm system.
9.All makeup fans in kitchen hood must be switched off in case of fire through
57 GF 1 P L1/D57/GF/SD/NEW ROOM MM
GF
SF
INTERFACE MONITOR MODULE
GROUND FLOOR
SERVICE FLOOR
SFO
59 GF 1 P L1/D59/GF/SD/PASTRY AREA FW
TW
DD
FLOW SWITCH
TAMPER SWITCH
DUCT DETECTOR WITH ISOLATOR
61 GF 1 HD L1/D61/GF/HD/BAKERY AREA
62 GF 1 P L1/D62/GF/SD/BAKERY WASH
63 GF 1 P L1/D63/GF/SD/BAKERY STORE Consultant :
64 GF 1 DD L1/D64/GF/DD/STORE RM RTN DUCT
65 GF 1 P L1/D65/GF/SD/STORE ROOM
66 GF 1 P L1/D66/GF/SD/CHEMICAL ROOM
67 GF 1 P L1/D67/GF/SD/FLOUR STORE Main Contract :
68 GF 1 P L1/D68/GF/SD/RECEIVING AREA
69 GF 1 P L1/D69/GF/SD/RECEIVING AREA
70 GF 1 MM L1/D70/GF/MM/FF-DRY LINE VALVE Safety Consultant :
Project Name :
ROO-OO2M06-ACC-XX-XX-SDW-FR-05011 C0
GENERAL NOTE:
BUILDING NAME (PANEL):SHURA ISLAND - MAIN KITCHEN 1.All Dimension Hear Are Shown in Meters Unless Otherwise Noted.
2.This Drawing is to be read for fire alarm system only.
ADDRESS No. FLOOR No. LOOP TYPE LABEL 3.All installations shall be in accordance with the requirements of NFPA 72.
4.All type fire extinguishing panel shall be listed and comply with the
requirements of NFPA 2001.
71 GF 1 SFI L1/D71/GF/SFI/DEBOXING AREA 6.All conduit shall be electrical metallic tubing (EMT) ,UL listed .
7.All fire fighting isolating control valves shall be UL listed indicating valves
72 GF 1 P L1/D72/GF/SD/DEBOXING AREA and shall be provided with supervisory switches to be connected with monitor
module in the fire alarm system.
8.All HVAC units must be switched off in case of fire through control module
73 GF 1 P L1/D73/GF/SD/DEBOXING AREA in the fire alarm system.
9.All makeup fans in kitchen hood must be switched off in case of fire through
82 GF 1 P SFI
ELE
SOUNDER WITH FLASHER INDOR
ELECTRICAL FIRE PUMP
DSL DIESEL FIRE PUMP
Project Name :
ADDRESS No. FLOOR No. LOOP TYPE LABEL 3.All installations shall be in accordance with the requirements of NFPA 72.
4.All type fire extinguishing panel shall be listed and comply with the
requirements of NFPA 2001.
95 GF 1 DD L1/D95/GF/DD/SEN KITCHN RTN DUCT 6.All conduit shall be electrical metallic tubing (EMT) ,UL listed .
7.All fire fighting isolating control valves shall be UL listed indicating valves
96 GF 1 MM L1/D96/GF/MM/KITCHEN HOOD #5 and shall be provided with supervisory switches to be connected with monitor
module in the fire alarm system.
8.All HVAC units must be switched off in case of fire through control module
97 GF 1 P L1/D97/GF/SD/POT WASH AREA in the fire alarm system.
9.All makeup fans in kitchen hood must be switched off in case of fire through
L1/D99/GF/SD/CHEF'S OFFICE
control module in the fire alarm system.
99 GF 1 P 11. The fire alarm system shall be installed strictly in accordance with the
requirements of NFPA 72,NFPA 110, NFPA 170.
Project Name :
ROO-OO2M06-ACC-XX-XX-SDW-FR-05011 C0
GENERAL NOTE:
BUILDING NAME (PANEL):SHURA ISLAND - MAIN KITCHEN 1.All Dimension Hear Are Shown in Meters Unless Otherwise Noted.
2.This Drawing is to be read for fire alarm system only.
ADDRESS No. FLOOR No. LOOP TYPE LABEL 3.All installations shall be in accordance with the requirements of NFPA 72.
4.All type fire extinguishing panel shall be listed and comply with the
requirements of NFPA 2001.
142 GF 1 CM L1/D142/GF/CM/EL RM/HVAC MCC OFF 6.All conduit shall be electrical metallic tubing (EMT) ,UL listed .
7.All fire fighting isolating control valves shall be UL listed indicating valves
143 GF 1 CM L1/D143-GF-CM-EL RM-SMDB-MK02 and shall be provided with supervisory switches to be connected with monitor
module in the fire alarm system.
8.All HVAC units must be switched off in case of fire through control module
Client :
Consultant :
Main Contract :
Safety Consultant :
Project Name :
ROO-OO2M06-ACC-XX-XX-SDW-FR-05011 C0
GENERAL NOTE:
BUILDING NAME (PANEL):SHURA ISLAND - MAIN KITCHEN 1.All Dimension Hear Are Shown in Meters Unless Otherwise Noted.
2.This Drawing is to be read for fire alarm system only.
ADDRESS No. FLOOR No. LOOP TYPE LABEL 3.All installations shall be in accordance with the requirements of NFPA 72.
4.All type fire extinguishing panel shall be listed and comply with the
requirements of NFPA 2001.
ADDRESS FIRE ALARM GENT LOOP No.2 6.All conduit shall be electrical metallic tubing (EMT) ,UL listed .
7.All fire fighting isolating control valves shall be UL listed indicating valves
1 SF 2 MM L2/D1/MM/SF/TS-ZCV/DRY STORE and shall be provided with supervisory switches to be connected with monitor
module in the fire alarm system.
8.All HVAC units must be switched off in case of fire through control module
2 SF 2 MM L2/D2/MM/SF/FS-ZCV/DRY STORE in the fire alarm system.
9.All makeup fans in kitchen hood must be switched off in case of fire through
9 SF 2 P L2/D9/SD/SF/ABV PASTRY AR HD
MCP
CM
HEAT DETECTOR WITH ISOLATOR
MANUAL CALL POINT
INTERFACE CONTROL MODULE
Project Name :
FA
ROO-OO2M06-ACC 04/10/2023 As Shown
A -01
Drawing Number REVISIONS:
ROO-OO2M06-ACC-XX-XX-SDW-FR-05011 C0
GENERAL NOTE:
BUILDING NAME (PANEL):SHURA ISLAND - MAIN KITCHEN 1.All Dimension Hear Are Shown in Meters Unless Otherwise Noted.
2.This Drawing is to be read for fire alarm system only.
ADDRESS No. FLOOR No. LOOP TYPE LABEL 3.All installations shall be in accordance with the requirements of NFPA 72.
4.All type fire extinguishing panel shall be listed and comply with the
requirements of NFPA 2001.
24 SF 2 P L2/D24/SD/SF/ABV POT WSH AR 6.All conduit shall be electrical metallic tubing (EMT) ,UL listed .
7.All fire fighting isolating control valves shall be UL listed indicating valves
25 SF 2 P L2/D25/SD/SF/ABV SENR KTCHN and shall be provided with supervisory switches to be connected with monitor
module in the fire alarm system.
8.All HVAC units must be switched off in case of fire through control module
26 SF 2 P L2/D26/SD/SF/ABV PACKING AR in the fire alarm system.
9.All makeup fans in kitchen hood must be switched off in case of fire through
Main Contract :
Safety Consultant :
Project Name :
ROO-OO2M06-ACC-XX-XX-SDW-FR-05011 C0