LUSAIL CITY DISTRICT COOLING COMPANY LLC

REVIEW COMMENTS FORM (RCF)


CONTRACT No.: MQ/LD/DCP/WEST-P1/17/036 dated 01.08.2017 PROJECT NAME: West District Cooling Plant Phase-1
DOCUMENT TYPE: Prequalification Submittal Material Submittal/Sample Method Statement Preliminary Design Detailed Design Drawings Shop Drawings As Built Drawings Others:______________

*Legends: 1 Approved 2 Approved with Comments 3 Revise & Resubmit 4 Not Compliant/Rejected 5 For Information

LCDCC LCDCC COMMENTS EPC CONTRACTOR’S REPLY LCDCC COMMENTS EPC CONTRACTOR’S LCDCC COMMENTS
ITEM Fire Detection and Alarm Layout Fire Detection and Alarm Layout Fire Detection and Alarm Layout Submittal Name STATUS
CODE REPLY
No. Rev.0 29th March 2018 Rev.1 09-April-2018 Rev.01, 26th April-2018 Rev.# date by LCDCC [by LCDCC]
# Trans No.: LWP1-CA-0075 Trans No.: LWP1-CA-0131 Trans No.: LWP1-CA-0131 [Rev.# date by Contractor] Trans No.: number
All fire alarm devices & equipment shall be
1.
coordinated with other services, A/C Noted Noted. Closed.
diffusers, cable trays, equipment, etc.
Mimic is not part of Scope of work.
However, it will be provided only if
2. Please refer to DWG EL-12928 where Mimic panel shall be apart from repeater requested by QCD.
Mimic panel shall be provided. Open.
Repeater panel is already shown. panel. If not imposed by QCD then LCDCC
shall confirm to provide it with cost
impact if needed.
Please note that as per SOW section
16.9, it states “the speaker system
Voice evacuation speakers shall be
3. should be the same for the Fire Alarm Noted. However, the PA system shall be
separate from Public address system Closed.
and public address systems”. Hence, apart from the fire alarm system.
speakers.
the same was followed in the design of
fire alarm.
Selection of fire alarm detection devices at
4.
staircases, cable tunnels, toilets, etc. shall Noted. Noted. Closed.
be verified to avoid false alarms.
5. Drawing No. EL-12918 – provide 2 No.
Noted & comply. Noted. Closed.
sounder & flashers at grid 8

1) Only details related to Fire Alarm 1) Noted


installation were reviewed. Other
detailed shall be submitted
2) Noted and comply
separately.
2) All cable trays/Ladders shall be
Noted.
supported from one side to allow 3) Noted and comply
6. Provide typical installation details of all Fire Please find attached electrical standard easy access.
details drawings numbers: 12903- Open.
Alarm devices & equipment. 3) Fire alarm cable loop above
12906 showing required installation 5) Mounting details are already
false ceiling shall be provided for shown on the previously
details.
all devices installed in false attached drawing 12906
ceiling. (648830-9775-47DD-
4) Mounting details of fire Alarm 0006_01). Attached again for
equipment/devices shall be reference.
indicated.

7. Comments on Fire Fighting submittal shall


Noted Noted. Closed.
be considered.
******* NOTHING FOLLOWS *******

Form No.: LCDCC-GEN-PRC-01-F05


West District Cooling Plant, Phase-1
Rev. No.: 00
Page 1 of 2
Date: 01/08/2017
LUSAIL CITY DISTRICT COOLING COMPANY LLC

REVIEWED BY: ___________________ SIGNATURE: ______________________ DATE: __________________


(Review Engineer)

Form No.: LCDCC-GEN-PRC-01-F05


West District Cooling Plant, Phase-1
Rev. No.: 00
Page 2 of 2
Date: 01/08/2017