*Legends: 1 Approved 2 Approved with Comments 3 Revise & Resubmit 4 Not Compliant/Rejected 5 For Information
LCDCC LCDCC COMMENTS EPC CONTRACTOR’S REPLY LCDCC COMMENTS EPC CONTRACTOR’S LCDCC COMMENTS
ITEM Fire Detection and Alarm Layout Fire Detection and Alarm Layout Fire Detection and Alarm Layout Submittal Name STATUS
CODE REPLY
No. Rev.0 29th March 2018 Rev.1 09-April-2018 Rev.01, 26th April-2018 Rev.# date by LCDCC [by LCDCC]
# Trans No.: LWP1-CA-0075 Trans No.: LWP1-CA-0131 Trans No.: LWP1-CA-0131 [Rev.# date by Contractor] Trans No.: number
All fire alarm devices & equipment shall be
1.
coordinated with other services, A/C Noted Noted. Closed.
diffusers, cable trays, equipment, etc.
Mimic is not part of Scope of work.
However, it will be provided only if
2. Please refer to DWG EL-12928 where Mimic panel shall be apart from repeater requested by QCD.
Mimic panel shall be provided. Open.
Repeater panel is already shown. panel. If not imposed by QCD then LCDCC
shall confirm to provide it with cost
impact if needed.
Please note that as per SOW section
16.9, it states “the speaker system
Voice evacuation speakers shall be
3. should be the same for the Fire Alarm Noted. However, the PA system shall be
separate from Public address system Closed.
and public address systems”. Hence, apart from the fire alarm system.
speakers.
the same was followed in the design of
fire alarm.
Selection of fire alarm detection devices at
4.
staircases, cable tunnels, toilets, etc. shall Noted. Noted. Closed.
be verified to avoid false alarms.
5. Drawing No. EL-12918 – provide 2 No.
Noted & comply. Noted. Closed.
sounder & flashers at grid 8