Model WS Specific Application Window Sprinklers


Horizontal and Pendent Vertical Sidewall
5.6 K-factor
General the Model WS Window Sprinklers
can be used as an open sprinkler for
Description “Outside Sprinkler Protection against
Exposure Fire”, using the design
The TYCO Model WS Specific requirements of NFPA.
Application Window Sprinklers are fast As with any specific application sprin-
response, glass bulb-type spray sprin- kler, the installation instructions
klers available in Horizontal Sidewall included in this data sheet must be
and Pendent Vertical Sidewall models. precisely followed. If there are addi-
These sprinklers are the first to be tional local or jurisdictional installation
specifically Listed to provide complete standards/codes for window sprinklers
wetting and coverage for heat strength- on glazed window systems, this docu-
ened, tempered, or ceramic glass ment does not relieve the designer/
windows using closed sprinklers. installer from these requirements.
As part of the testing, the gas flow Consult your local jurisdiction to verify
required to achieve the time/temper- if or when these additional guidelines
ature relationship specified in ASTM must be followed.
E119 was established in a test furnace
without sprinkler protection. A window NOTICE
assembly protected with the TYCO TYCO Model WS Specific Application
Model WS Window Sprinklers was Window Sprinklers described herein
then installed in the test furnace, and must be installed and maintained in
the same gas flow conditions were compliance with this document, as
maintained for a two-hour test period. well as with the applicable standards
No cracking or visible damage to the recognized by the approval agency, in
window was permitted during the test addition to the standards of any author-
period, even when a hose stream was ities having jurisdiction. Failure to do so
directed at the window. may impair the performance of these
devices.

Multnomah County Health Department Headquarters


The success of the Model WS Window
Sprinklers is based on their fast The owner is responsible for main-
response thermal sensitivity and on taining their fire protection system and
their specially designed deflectors that devices in proper operating condition.
ensure that the spray pattern wets the The installing contractor or manufac-
entire surface of the window. turer should be contacted with any
Based on successful testing, the questions.
Model WS Window Sprinklers can be
used as interior protection of windows
or glazing in a sprinklered building or Sprinkler

Appeal Exhibit H
Identification (16-227322-CO)
non-sprinklered building in accordance
with Section 104 of the IBC (“Alternate
Materials, Design and Methods of
Construction and Equipment”). Also, Number (SIN)
TY3388 - Horizontal Sidewall
IMPORTANT TY3488 - Pendent Vertical Sidewall
Always refer to Technical Data TY3388 is a re-designation for C3388
Sheet TFP700 for the “INSTALLER TY3488 is a re-designation for C3488
WARNING” that provides cautions
with respect to handling and instal-
lation of sprinkler systems and
components. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.

Page 1 of 8 MAY 2014 TFP620


Multnomah County Health Department Headquarters
TFP620 (16-227322-CO)
Page 2 of 8 Appeal Exhibit H

Technical Components:

Data 1 - Frame
2 - Button * Temperature
3 - Sealing rating is
Approvals Assembly indicated on
UL and C-UL Listed 4 - Bulb Deflector.
NYC under MEA 289-04-E 5 - Compression
Screw
Approvals only apply to the service 6 - Deflector *
conditions indicated in the Design 1 2 3 4 5 6*
Criteria section.
Additional Recognition CROSS SECTION PLAN
ICC Evaluation Service (ESR-2397)
Ontario Building Code THREAD SPRINKLER INDICATED TOP
Pipe Thread Connection RELIEF FRAME ARMS OF SPRINKLER
1/2 inch NPT DEFLECTOR

Discharge Coefficient 1/2"


K=5.6 GPM/psi1/2 (80,6 LPM/bar1/2) NPT
13/16"
Temperature Ratings (20,6 mm)
155°F (68°C) CENTERLINE
200°F (93°C) OF SPRINKLER
WATERWAY 1-5/8" DIA.
Finish (41,3 mm)
Natural Brass, Signal White (RAL9003)
Polyester, and Chrome Plated
7/16" (11,1 mm) WRENCH
Physical Characteristics NOMINAL MAKE-IN FLATS ORIENT
Frame . . . . . . . . . . . . . . . . . . . . . . . . Brass
Button . . . . . . . . . . . . . . . . Bronze/Copper DEFLECTOR
Sealing Assembly . . . . . Beryllium Nickel 2-1/8" TOWARDS
w/TEFLON (54,0 mm) WINDOW
Bulb . . . . . . . . . . . . . . . . . . . . . . . . . . Glass
(3 mm dia.) SIDE ELEVATION
Compression Screw ������������������������� Brass
Deflector . . . . . . . . . . . . . . . Brass/Bronze FIGURE 1
MODEL WS WINDOW SPRINKLER
Operation HORIZONTAL SIDEWALL

The glass bulb contains a fluid that Components:


expands when exposed to heat. When
the rated temperature is reached, the 1 - Frame 4 - Bulb * Temperature
fluid expands sufficiently to shatter the 2 - Button 5 - Compression rating is indicated
3 - Sealing Screw on Deflector. 1/2" 7/16" (11,1 mm)
glass bulb, allowing the sprinkler to NPT NOMINAL MAKE-IN
Assembly 6 - Deflector *
activate and water to flow.
1
WRENCH
FLATS
2
ORIENT
3 FLOW ARROW SPRINKLER
FRAME 2-1/8"
(INDICATED ON
ARMS (54,0 mm)
DEFLECTOR)
4 TOWARDS
WINDOW
5

CENTERLINE TOP OF
OF SPRINKLER 6* SPRINKLER 1-1/32"
WATERWAY DEFLECTOR (26,2 mm)

5/8" 2-1/16"
(15,9 mm) (52,4 mm)

CROSS SECTION TOWARDS WINDOW ELEVATION


FIGURE 2
MODEL WS WINDOW SPRINKLER
PENDENT VERTICAL SIDEWALL
Multnomah County Health Department Headquarters
(16-227322-CO) TFP620
Appeal Exhibit H Page 3 of 8

Design Criteria NOTE: Refer to FireLite Plus WS


ceramic glass technical data sheet for
Intermediate Horizontal Mullions
Intermediate Horizontal Mullions were
The TYCO Model WS Specific other classification limitations at www. not tested with the Model WS Window
Application Window Sprinklers are UL fireglass.com. Sprinklers. Their use is outside the
scope of the “Specific Application”
and C-UL Listed and NYC Approved • Non-operable, stronger glass window Listing for the window sprinklers. Refer
(MEA 335-01-E) for use as “Specific assemblies, not less than 1/4 in. (6 to Figure 3B-3.
Application Window Sprinkler” and as mm) thick.
open sprinklers for “Outside” use. Deflector Location
Type of Window Frame/Mullion Sprinkler Deflectors must be located as
These sprinklers are also recognized by Non-combustible Frame with a stan-
Underwriters Laboratories of Canada described below in order to ensure that
dard EPDM rubber gasket seal the entire surface of the glass window
(ULC), and the Ontario Building Code
for use in the Province of Ontario, Vertical joints of glass panes must be is covered. Sprinkler Deflectors are
Canada as providing a two-hour equiv- connected by butt-joints using a sili- positioned with respect to the window
alency for a fire separation assembly cone sealant between the individual frame, not the ceiling.
when installed in accordance with this panes or by Noncombustible Mullions. • Horizontal Sidewall: Locate within the
code. (Refer to Figures 3B-1 and 3B-2) outside edge of the window frame
from 1/2 to 4 in. (12,7 mm to 101,6
Area of Use Maximum Length of Window mm) away from the glass and 2 ± 1
When acceptable to the Authority Assembly in. (50,8 mm ± 25,4 mm) down from
Having Jurisdiction and unless modi- Unlimited the top of the exposed glass. Refer
fied by a local jurisdictional standard or to Figure 3C.
code mentioned previously, the TYCO Maximum Height of Window
Model WS Window Sprinklers may be Assembly • Pendent Vertical Sidewall: Locate
used in either a sprinklered or unsprin- 13 ft. (3,96 m) 4 to 12 in. (101,6 mm to 304,8 mm)
klered building to protect non-operable from the face of the glass and 3 ± 1
(Refer to Figures 3C and 3D)
window openings that are part of a fire in. (76,2 mm ± 25,4 mm) down from
separation provided: Maximum Distance Between the top of exposed glass. Refer to
Window Sprinklers Figure 3D.
• in an interior fire separation, the
window sprinklers are installed on 8 ft. (2,44 m)
Minimum Clearance from Face of
both sides of the window in the fire (Refer to Figures 3B-1 and 3B-2) Glass to Combustible Materials
separation (Figure 3A-1), For glass types other than FireLite
Minimum Distance Between Plus WS ceramic glass by TGP, all
• in jurisdictions where exterior spatial Window Sprinklers
separation (that is, separation combustible materials shall be kept
6 ft. (1,83 m) unless separated by a
from adjacent space) is defined as baffle or mullion of sufficient depth to 2 in. (50,8 mm) from the front face of
protecting an adjacent building from act as a baffle. the glass. This can be accomplished
a fire in your building, window sprin- by a minimum 36 in. (914,4 mm) pony
klers are installed on the interior side A mullion will act as a baffle, when wall or other method acceptable to the
of the building (Figure 3A-2), or in the case of the Pendent Vertical authority having jurisdiction.
Sidewall, the mullion extends to the
• in jurisdictions where exterior spatial back of the sprinkler deflector, and in Escutcheon Assemblies
separation is defined as protecting the case of the Horizontal Sidewall, the The Model WS Window Sprinklers
your building from a fire in an adja- mullion extends to the sprinkler wrench can be used with any metallic flush or
cent building (that is, exposure flat. extended escutcheons, provided the
protection), open window sprinklers dimensions from the sprinkler deflector
(Refer to Figures 3B-1 and 3B-2)
are installed on the exterior side of to the window frame and glass surface
the building (Figure 3A-3). Minimum Distance from Standard as specified in this data sheet are
Sprinklers maintained. These sprinklers are not
System Protection Type 6 ft. (1,83 m) unless separated by a listed for recessed applications.
• Interior: Wet Systems baffle
Recommended Hydraulic
• Outside Exposure: Deluge Requirements
Sprinkler Location
Glass Type • Mullioned Glazing Assemblies: The authority having jurisdiction should
The following types and thicknesses of Locate window sprinklers within each be consulted to determine the hydraulic
glass are recognized for use with TYCO mullioned glazing segment. Refer to requirements for each installation.
Model WS Window Sprinklers: Figure 3B-1.
Interior Protection Sprinklered
• Non-operable, heat-strengthened, • Butt-Jointed Glazing Assemblies: Building
tempered, single-glazed (single Locate window sprinklers on Identify which compartmented area
pane), not less than 1/4 in. (6 mm) maximum 8 ft. (2,44 m) centers. Refer has the most hydraulically demanding
thick; to Figure 3B-2. window sprinklers. Calculate up to the
Maximum Distance from Vertical most demanding 46.5 linear feet of
• Non-operable, heat-strengthened, Model WS Window Sprinklers on one
tempered, double-glazed (double Mullion
4 ft. (1,22 m) side of the glazing. The 46.5 linear feet
pane or insulated), not less than 1/4 (14,2 linear meters) is based upon 1.2
in. (6 mm) thick; (Refer to Figure 3B-1) x the square root of the system area
• Non-operable, UL Classified and Minimum Distance from Vertical of operation, when the system area of
labeled FireLite Plus WS ceramic Mullions operation is 1500 sq.-ft. in accordance
glass by Technical Glass Products 4 in. (101,6 mm) with NFPA 13 Light/Ordinary Hazard
(TGP), not less than 5/16 in. (8 mm) density curves.
thick; or, (Refer to Figure 3B-1)
Multnomah County Health Department Headquarters
TFP620 (16-227322-CO)
Page 4 of 8 Appeal Exhibit H

Where the area of Glazing is less than


When acceptable to the Authority Having Jurisdiction the Model WS Specific Application
14.2 linear meters, all window sprinklers
Window Sprinklers may be used in either a sprinklered or unsprinklered building to protect
on one side shall be calculated.
nonoperable window openings that are in an interior fire separation, the window sprinklers
If an area reduction for quick response are installed on both sides of the window in the fire separation.
sprinklers is utilized, the linear length of
the calculated window sprinklers may
be reduced, but in no case shall be less
than 36 linear feet (1.2 x √900).
INSIDE
If a single fire can be expected to
operate Model WS Window Sprinklers
and sprinklers within the design area of
a hydraulically calculated system, the
INSIDE
water demand of the window sprinklers
shall be added to the water demand
of the hydraulic calculations and shall
be balanced to the calculated area
demand. FIGURE 3A-1 - INTERIOR FIRE SEPARATION
If the window sprinklers are located in
an area other than the hydraulic design
area, the demand of the window sprin- When acceptable to the Authority Having Jurisdiction the Model WS Specific Application
klers is not required to be added to Window Sprinklers may be used in either a sprinklered or unsprinklered building to protect
the demand of the remote hydraulic nonoperable window openings that are part of a fire separation provided in jurisdictions
design area. However, it is necessary where exterior spatial separation is defined as protecting an adjacent building from a fire
to prove hydraulically the simultaneous in your building, window sprinklers are installed on the interior side of the glass.
operation of the Model WS Window
Sprinklers and the ceiling sprinklers
adjacent to the window sprinklers.
OUTSIDE
Interior Protection Non-Sprinklered
Building
Calculate all sprinklers on the most
demanding side of the glazing INSIDE
assembly within the enclosure.
EXPOSURE
Exterior Exposure Protection SIDE
Calculate all sprinklers controlled by the
deluge valve using the design require- FIGURE 3A-2 - EXTERIOR FIRE SEPARATION - SPRINKLERS INSIDE
ments of NFPA.
Duration of Water Supply When acceptable to the Authority Having Jurisdiction the Model WS Specific Application
Duration of water supply must comply
Window Sprinklers may be used in either a sprinklered or unsprinklered building to protect
with requirements of NFPA. If window
nonoperable window openings that are part of a fire separation provided in jurisdictions
sprinklers are used to provide the
where exterior spatial separation is defined as protecting your building from a fire in an
equivalency of a fire rating, the water
adjacent building, open window sprinklers are installed on the exterior side of the glass.
supply must be capable of supplying
water for the required rating period.
Minimum Flow per Sprinkler
INSIDE
20 GPM (75,7 LPM) for sprinkler
spacing of 6 to 8 ft. (1,83 to 2,44 m)
or 15 GPM (56,8 LPM) for sprinkler
spacing less than 6 ft. (1,83 m).
OUTSIDE
Maximum Pressure per Sprinkler
EXPOSURE
• Horizontal Sidewall: 70 psi (4,83 bar)*
SIDE
* The 70 psi is only for cold solder
purposes. If there is a baffle or a FIGURE 3A-3 - EXTERIOR FIRE SEPARATION - SPRINKLERS OUTSIDE
mullion of sufficient depth to act as a
baffle, separating the sprinklers, the FIGURE 3A (A-1 TO A-3)
maximum pressure is 175 psi (12,07 TYPICAL NON-OPERABLE WINDOW OPENINGS
bar).
• Vertical Sidewall: 175 psi (12,07 bar)

Condition 1 & 2
(See exhibit C-1 & C-2)
Condition 1 Multnomah County Health Department Headquarters
(See exhibit C-1 & C-2) (16-227322-CO) TFP620
Appeal Exhibit H Page 5 of 8

HORIZONTAL
6'-0" (1,83 m) OR VERTICAL 8'-0" (2,44 m)
MINIMUM * MODEL WS MAXIMUM
SPRINKLER

* Minimum distance between


Window Sprinklers is 6'-0"
(1,83 m) unless separated MULLION 4'-0" (1,22 m) MAXIMUM
by a baffle or mullion of 0'-4" (101,6 mm) MINIMUM
sufficient depth to act as a
baffle.

FIGURE 3B-1 - MULTIPLE WINDOWS SEPARATED BY MULLIONS

HORIZONTAL
6'-0" (1,83 m) OR VERTICAL 8'-0" (2,44 m)
MINIMUM MODEL WS MAXIMUM
SPRINKLER
MULLION
Window Sprinklers are NOT
required to be located with BUTT JOINT
respect to horizontal or 4'-0" (1,22 m) MAXIMUM
vertical butt joints. 0'-4" (101,6 mm) MINIMUM

FIGURE 3B-2 - MULTIPLE WINDOWS SEPARATED BY BUTT JOINTS

HORIZONTAL OR
VERTICAL MODEL MULLION
WS SPRINKLER

Window Sprinklers are NOT


listed to protect windows INTERMEDIATE
when intermediate horizontal MULLION
mullions are present.

FIGURE 3B-3 - WINDOWS WITH HORIZONTAL MULLIONS

FIGURE 3B (B-1 TO B-3)


WINDOW MULLIONS AND BUTT JOINTS
Multnomah County Health Department Headquarters
TFP620 (16-227322-CO)
Page 6 of 8 Appeal Exhibit H

"TOP" BUILDING
INDICATED ON STRUCTURE
SPRINKLER DEFLECTOR

NO MAXIMUM
DISTANCE

WINDOW
FRAME

2" (50,8 mm)


± 1" (25,4 mm)
NO
MAXIMUM
HEIGHT 1/2" (12,7 mm)
TO 4" (101,6 mm) FOR GLASS TYPES
OTHER THAN FIRELITE
PLUS WS CERAMIC GLASS
13'-0" NON-OPERABLE BY TGP, ALL COMBUSTIBLE
(3,96 m) GLASS WINDOW MATERIALS SHALL BE
MAXIMUM KEPT 2" (50,8 mm) MINIMUM
EXPOSED FROM SPRINKLERED FACE
GLAZING INSTALLATION NOTE: OF GLAZING. THIS MAY BE
HEIGHT POSITION SPRINKLER DONE THROUGH USE OF
MINIMUM 3'-0" (0,9 m)
WITH FRAME ARMS
PONY WALL
ALIGNED VERTICALLY
AND MARKED SIDE OF
DEFLECTOR FACING
AND PARALLEL MODEL WS SPRINKLER
TO GLAZING SHOWN ON ONE SIDE OF
GLAZING FOR CLARITY

FIGURE 3C
MODEL WS HORIZONTAL SIDEWALL SPRINKLER
TYPICAL INSTALLATION

Installation Step 1. Install the pendent vertical side-


wall sprinkler only in the pendent posi-
Step 4. With reference to Figures 1 or
2, apply End A of W-Type 20 Sprinkler
The TYCO Model WS Specific tion with the center-line of the sprinkler Wrench only (Figure 4) to the sprinkler
Application Window Sprinklers must parallel to the glass surface. Orient the wrench flats and tighten the sprinkler
be installed in accordance with this sprinkler so that the direction of flow into the sprinkler fitting.
section. indicated on the sprinkler deflector is
facing the window.
General Instructions Step 2. Install the horizontal side-
Do not install any bulb-type sprinkler if wall sprinkler only in the horizontal
the bulb is cracked or there is a loss position with the center-line of the
of liquid from the bulb. With the sprin- sprinkler perpendicular to the glass
kler held horizontally, a small air bubble surface. Orient the sprinkler so that the
should be present. The diameter of the word “Top” indicated on the sprinkler
air bubble is approximately 1/16 in. (1,6 deflector is facing the top of window
mm). frame.
A leak-tight 1/2 inch NPT sprinkler Step 3. With pipe-thread sealant
joint should be obtained by applying a applied to the pipe threads, hand-
minimum-to-maximum torque of 7 to tighten the sprinkler into the sprinkler
14 ft.-lbs. (9,5 to 19,0 Nm). Higher levels fitting.
of torque may distort the sprinkler inlet
with consequent leakage or impairment
of the sprinkler.
Condition 1 & 2 Multnomah County Health Department Headquarters
(See exhibit C-1 & C-2) (16-227322-CO) TFP620
Appeal Exhibit H Page 7 of 8

CENTERLINE BUILDING
OF SPRINKLER STRUCTURE
WATERWAY

NO MAXIMUM
DISTANCE

WINDOW
FLOW DIRECTION FRAME
INDICATED ON
SPRINKLER
DEFLECTOR 3" (76,2 mm)
± 1" (25,4 mm)
NO
MAXIMUM
HEIGHT 4" (101,6 mm)
TO 12" (304,8 mm) FOR GLASS TYPES
OTHER THAN FIRELITE
PLUS WS CERAMIC GLASS
13'-0" NON-OPERABLE BY TGP, ALL COMBUSTIBLE
(3,96 m) GLASS WINDOW MATERIALS SHALL BE
MAXIMUM KEPT 2" (50,8 mm) MINIMUM
EXPOSED FROM SPRINKLERED FACE
GLAZING INSTALLATION NOTE: OF GLAZING. THIS MAY BE
HEIGHT POSITION SPRINKLER DONE THROUGH USE OF
MINIMUM 3'-0" (0,9 m)
WITH FRAME ARMS
PONY WALL
ALIGNED PARALLEL
TO GLAZING AND
DEFLECTOR FLOW
ARROW POINTED MODEL WS SPRINKLER
TOWARD GLAZING SHOWN ON ONE SIDE OF
GLAZING FOR CLARITY

FIGURE 3D
MODEL WS PENDENT VERTICAL SIDEWALL SPRINKLER
TYPICAL INSTALLATION

Care and have not operated, should be replaced


if they cannot be completely cleaned
Automatic sprinkler systems are recom-
mended to be inspected, tested, and
Maintenance by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
maintained by a qualified Inspection
Service in accordance with local
The TYCO Model WS Specific requirements and/or national codes.
Care must be exercised to avoid
Application Window Sprinklers must damage to the sprinklers - before,
be maintained and serviced in accor- during, and after installation. Sprinklers
dance with this section. damaged by dropping, striking, wrench
Before closing a fire protection system twist/slippage, or the like, must be
main control valve for maintenance replaced. Also, replace any sprinkler
work on the fire protection system that has a cracked bulb or that has lost
that it controls, obtain permission to liquid from its bulb. (Ref. Installation
shut down the affected fire protection Section.)
systems from the proper authorities
and notify all personnel who may be The owner is responsible for the
affected by this action. inspection, testing, and maintenance of
Sprinklers which are found to be their fire protection system and devices
leaking or exhibiting visible signs of in compliance with this document, as
corrosion must be replaced. well as with the applicable standards
recognized by the Approval agency
Automatic sprinklers must never be (e.g., NFPA 25), in addition to the stan-
painted, plated, coated, or other- dards of any authorities having jurisdic-
wise altered after leaving the factory. tion. Contact the installing contractor or
Modified sprinklers must be replaced. sprinkler manufacturer regarding any
Sprinklers that have been exposed to questions.
corrosive products of combustion, but
Multnomah County Health Department Headquarters
TFP620 (16-227322-CO)
Page 8 of 8 Appeal Exhibit H

RECESSED BUILDING
CEILING STRUCTURE
SPACE

WINDOW
FRAME

INSTALLATION NOTE: FOR GLASS TYPES


INSTALL VERTICAL AND OTHER THAN FIRELITE
HORIZONTAL MODEL PLUS WS CERAMIC GLASS
WS SPRINKLERS BY TGP, ALL COMBUSTIBLE
INTO RECESSED MATERIALS SHALL BE
TYPICAL KEPT 2" (50,8 mm) MINIMUM
WINDOW CEILING SPACES.
FROM SPRINKLERED FACE
COVERING DO NOT PLACE BLINDS,
OF GLAZING. THIS MAY BE
CURTAINS OR OTHER
DONE THROUGH USE OF
WINDOW COVERINGS MINIMUM 3'-0" (0,9 m)
BETWEEN SPRINKLER PONY WALL
AND GLAZING

NONOPERABLE MODEL WS SPRINKLER


GLASS WINDOW SHOWN ON ONE SIDE OF
GLAZING FOR CLARITY

FIGURE 3E
MODEL WS PENDENT VERTICAL SIDEWALL SPRINKLER
RECESSED CEILING TYPICAL INSTALLATION

Ordering Model WS Pendent Vertical Sidewall


Window Sprinkler with NPT Thread

WRENCH RECESS
Procedure Specify: Model WS Specific Application
Window Sprinkler TY3488, Pendent
Contact your local distributor for avail- Vertical Sidewall, with (specify) temper-
(USE END "A" FOR
ability. When placing an order, indicate ature rating, (specify) finish, and P/N
MODEL WS)
the full product name and Part Number (specify)
(P/N).
FIGURE 4 155°F (68°C)
W-TYPE 20 SPRINKLER Model WS HSW Window Sprinkler Natural Brass . . . . . . . . P/N 50-304-1-155
WRENCH with NPT Thread Signal White (RAL9003)
Specify: Model WS Specific Application Polyester . . . . . . . . . . . . P/N 50-304-4-155

Limited Window Sprinkler TY3388, Horizontal


Sidewall, with (specify) temperature
Chrome Plated . . . . . . . P/N 50-304-9-155
200°F (93°C)
Warranty rating, (specify) finish, and P/N (specify) Natural Brass . . . . . . . . P/N 50-304-1-200
Signal White (RAL9003)
Polyester . . . . . . . . . . . . P/N 50-304-4-200
For warranty terms and conditions, 155°F (68°C) Chrome Plated . . . . . . . P/N 50-304-9-200
Natural Brass . . . . . . . . P/N 50-305-1-155
visit www.tyco-fire.com. Signal White (RAL9003) Sprinkler Wrench
Polyester . . . . . . . . . . . . P/N 50-305-4-155 Specify: W-Type 20 Sprinkler Wrench,
Chrome Plated . . . . . . . P/N 50-305-9-155 P/N 56-000-1-106
200°F (93°C)
Natural Brass . . . . . . . . P/N 50-305-1-200
Signal White (RAL9003)
Polyester . . . . . . . . . . . . P/N 50-305-4-200
Chrome Plated . . . . . . . P/N 50-305-9-200
GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700
Copyright © 2014 Tyco Fire Products, LP. All rights reserved.
TEFLON is a trademark of The DuPont Corporation
Technical Glass Products and fireglass are registered trademarks of Technical Glass Products