www.tyco-fire.com
Contacts
Sprinkler Finish 6
Bulb
Hazard Type Temperature Liquid Natural Chrome Polyester* Lead
Brass Plated Coated
135°F (57°C) Orange
Upright
K=11.2 (TY5137) 155°F (68°C) Red 1, 2, 3**, 4, 5
Light Pendent 175°F (79°C) Yellow
K=11.2 (TY5237) 200°F (93°C) Green
Table B describes K=14.0 (TY6237) 1, 2, 4, 5 1, 2, 4, 5
UL and C-UL 286°F (141°C) Blue
Sensitivity Rating 135°F (57°C) Orange
Table C describes Recessed Pendent 1, 2, 3, 4, 5
FM 155°F (68°C) Red
K=11.2 (TY5237)
Sensitivity Rating K=14.0 (TY6237) 175°F (79°C) Yellow N/A
With Style 30
Escutcheon 200°F (93°C) Green 1, 2, 4, 5
286°F (141°C) Blue
TABLE A
LABORATORY LISTINGS AND APPROVALS
HC-1
Linear Spacing Area Spacing
ft ft Ceiling Height
Ceiling Type K-factor Style Response
ft
Min Max Min Max
Noncombustible Unobstructed, 11.2 EC Pendent or
10 20 100 400 Up to 30 Noncombustible Obstructed, or 14.0 EC Upright
Combustible Unobstructed
Noncombustible Unobstructed, Pendent
11.2 EC
10 20 100 400 Up to 30 Noncombustible Obstructed, or Recessed
14.0 EC
Combustible Unobstructed Style 30
11.2 EC Pendent or
10 20 100 400 Up to 30 Combustible Obstructed 14.0 EC Upright Quick
Pendent
11.2 EC
10 20 100 400 Up to 30 Combustible Obstructed Recessed
14.0 EC Style 30
HC-2
Linear Spacing Area Spacing
ft ft Ceiling Height
Ceiling Type K-factor Style Response
ft
Min Max Min Max
Pendent or
10 20 100 400 Up to 30 11.2 EC Upright
Pendent or
10 20 100 400 Up to 30 Noncombustible Unobstructed, 14.0 EC Upright Quick
Combustible Unobstructed
Over 30 and 11.2 EC 14.0
10 16 100 256 Upright
up to 45 EC
HC-3
Linear Spacing Area Spacing
ft ft Ceiling Height
Ceiling Type K-Factor Style Response
ft
Min Max Min Max
10 16 100 256 Up to 30 11.2 EC Upright
Pendent or
10 20 100 400 Up to 30 14.0 EC
Noncombustible Unobstructed, Upright
Quick
Combustible Unobstructed
Over 30 and 11.2 EC,
10 16 100 256 Upright
up to 45 14.0 EC
NOTES
• The design for K 11.2 EC (K 160 EC) sprinklers should not include fewer than six sprinklers or have a design pressure of less than 12 psi (0,8 bar); similarly the design for K 14.0
EC (K 200 EC)sprinklers should not include fewer than four sprinklers or have a design pressure of less than 18 psi (1,2 bar).
• For flow criteria, refer to FM Loss Prevention Data Sheet 3-26.
• Refer to FM Loss Prevention Data Sheet 2-0 for permitted K-Factor/Area Combinations.
TABLE C
SENSITIVITY RATING FOR FM APPROVAL OF SERIES EC-11 OR EC-14 SPRINKLERS
exceed 30 in. (762 mm). The maxi- plane 1 in. (25,4 mm) beneath the specific ordinary hazard (non-storage
mum permitted concrete tee length bottom of the concrete tee stems, and/or non-flammable or combustible
is 32 ft (9,8 m). However, where the the obstruction to sprinkler dis- liquid) occupancies. Information pro-
concrete tee length exceeds 32 ft charge criteria requirements of vided in the FM Loss Prevention Data
(9,8 m), non-combustible baffles, NFPA 13 for extended coverage Sheets relates to, but is not limited to,
equal in height to the depth of the upright and pendent sprinklers hydraulic design, ceiling slope, and
tees, can be installed so that the applies. obstructions, minimum and maximum
space between the tees does not allowable spacing, and deflector-to-
exceed 32 ft (9,8 m) in length. FM Approval Requirements
ceiling distance.
Series EC-11 and EC-14 Extended
2. The sprinkler deflectors are to be Coverage Upright and Pendent Sprin- These criteria may differ from UL
located in a horizontal plane at or klers are to be installed in accor- and/or NFPA criteria. Therefore, the
above 1 in. (25,4 mm) below the dance with the applicable FM Loss designer should review and become
bottom of the concrete tee stems. Prevention Data Sheet for limited use familiar with FM requirements before
3. When the sprinkler deflectors are in buildings of specific roof construc- proceeding with design.
located higher than a horizontal tion and for the protection of certain
TFP220
Page 5 of 8
TABLE D
FLOW CRITERIA FOR UL AND C-UL LISTING OF SERIES EC-11 AND EC-14 SPRINKLERS
MOUNTING MOUNTING
SURFACE 1/8" SURFACE 1/8"
(3,2 mm) (3,2 mm)
WRENCH
HEX
FIGURE 6
W-TYPE 22 RECESSED
SPRINKLER WRENCH
TFP220
Page 7 of 8
SPRINKLER TEMPERATURE
SIN FINISH1 RATING
TABLE E
SERIES EC-11 AND EC-14 UPRIGHT AND PENDENT SPRINKLERS
PART NUMBER SELECTION
NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;
TEFLON is a trademark of The Chemours Company FC, LLC
Worldwide
www.tyco-fire.com
Contacts
TFP220
Change History Appendix
Page 1, updated QR code and URL; Page 1, Approvals sub-section, added EAC Approved; Page 8,
changed corporate address and telephone number to 1467 Elmwood Avenue, Cranston, RI 02910
08-22
| Telephone +1-401-781-8220, formerly 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone
+1-215-362-0700.
11-21 Added QR code and URL to allow convenient access to electronic version from printed document.
Added pendent orientation for 11.2 K-factor variant in Hazard Class 2 (HC-2) Ceiling Height up to 30
06-19
feet to Sensitivity Rating for FM Approval Table C.
10-18 Updated Table B to identify which K=14 Upright sprinklers are not Quick or Standard Reponse.
Updated Tyco® branding and document format; Added Johnson Controls copyright; Added disclaimer
stating specifications and information subject to change without notice; Added reference to Regulatory
08-18
and Health Warning Technical Data Sheet TFP2300; Changed metric conversion factor in Table D to 1
ft = 0.3048 m, formerly 1 ft = 0.348 m.
Expanded applicability of laboratory listings and approvals relative to hazard, sprinkler type and tem-
12-17
perature rating.
11-14 Added Jet Black (RAL9005) sprinkler finish to Part Number Selection Table E.
Corrected sprinkler orientation in Design Criteria, UL and C-UL Specific Application Listing Require-
ments for Installation under Concrete Tees sub-section, pendent EC-11 and EC-14 sprinklers are also
09-14
subject to NFPA 13 discharge criteria requirements when installed with deflectors located higher than
a horizontal plane 1 inch (25,4 mm) beneath the bottoms of concrete tee stems.
06-14 Corrected SIN numbers shown in Figure 1 caption.
05-14 Corrected Sensitivity Ratings in Table C.
Changed ceiling heights per FM Approval to limited to 45 feet; formerly over 30 feet; Added option for
02-14 Open sprinklers to Ordering Procedure (Open indicates a sprinkler assembly without Bulb, Button or
Sealing Assembly).
Added Sensitivity Ratings to Ordinary Hazard applications in Table B, formerly Not Applicable (N/A);
11-13
Added Flow and Pressure criteria to Table D.
02-12 Corrected typographical errors in coverage areas provided in Table D.
09-11 Updated to reflect current legal and department standards.
07-11 Updated patent information.
12-07 Added reference to new UL Listed and FM Approved Style 60 Two-Piece Flush Escutcheon.
Changed UL and C-UL Listied sensitivity rating of operating temperatures up to 200°F (93°C) to to quick
02-07
response for ordinary hazard 14’ x 14’ coverage areas; formerly standard response.
Added UL and C-UL Listed installation criteria for non-combustible web members greater than 1 inch
09-04 within trusses and or bar joists; Added UL and C-UL Listed installation criteria for pendent sprinklers
located beneath concrete tees.
Added NYC Approved; Changed recessed sprinkler wrench to W-Type 22 which accommodates pro-
04-04
tective Sprinkler Strap, formerly W-Type 4.
Updated Listings and Approvals; Added Style 30 Recessed Escutcheon to Table B under ordinary hazard
02-04
for UL and C-UL; Added NYC Approved to Table A as applicable.
Corrected FM sensitivity rating in Table for ordinary hazard recessed style to Not Applicable (N/A), for-
04-03
merly Standard Response (SR).
Page 1 of 2
TFP220 CHANGE HISTORY APPENDIX, CONTINUED
Page 2 of 2