Series ELO-231B – 11.2 K-factor


Upright and Pendent Sprinklers
Standard Response, Standard Coverage
General concentration of chemicals, and gas/
chemical velocity, should be consid-
Description ered, as a minimum, along with the cor-
rosive nature of the chemical to which
TYCO Series ELO-231B 11.2K Standard the sprinklers will be exposed.
Response, Standard Coverage Upright An upright intermediate level version
and Pendent Sprinklers (Ref. Figure 1) of the Series ELO-231B Sprinklers for
are automatic sprinklers of the frangible in-rack applications can be obtained by
bulb type. They are standard response, utilizing the Series ELO-231B Upright
spray sprinklers that produce a hemi- Sprinkler with the WSG-2 Guard &
spherical water distribution pattern Shield, and a pendent intermediate
below the deflector. level version of the Series ELO-231B
The 11.2 K-factor, ELO-231B Sprinklers Sprinklers can be obtained by utilizing
were subjected to full-scale, high-piled the Series ELO-231B Pendent Sprinkler
storage fire tests to qualify their use with the WS-2 Shield. If there is a pos-
in lieu of 5.6 or 8.0 K-factor standard sibility of the pendent intermediate level
spray sprinklers for the protection of version being exposed to mechanical
high-piled storage. damage, a G-2 Guard can be added.

Higher flow rates can be achieved at NOTICE


much lower pressures with the 11.2
K-factor, ELO-231B Sprinklers, making The 11.2 K-factor, Series ELO-231B
their use highly advantageous in high Upright and Pendent Sprinklers
density applications, such as the pro- described herein must be installed
tection of high-piled storage. and maintained in compliance with this
document, as well as with the applica-
Wax or lead coatings can be used ble standards of the National Fire Pro-
to extend the life of the copper alloy tection Association (NFPA), in addition
components used in Series ELO-231B to the standards of any other authori-
sprinklers beyond that which would ties having jurisdiction. Failure to do so
otherwise be obtained when exposed may impair the performance of these
to corrosive atmospheres. Although devices.
wax, lead, and polyester coated sprin-
klers have passed the standard corro- The owner is responsible for main-
sion tests of the applicable approval taining their fire protection system

Sprinkler
agencies, the testing is not repre- and devices in proper operating con-
sentative of all possible corrosive dition. Contact the installing contrac-
tor or product manufacturer with any
atmospheres. Consequently, it is rec-
ommended that the end-user be con- questions. Identification
sulted with respect to the suitability
of these corrosion resistant coatings
Installation of Series ELO-231B Pendent
Sprinklers in recessed escutcheons will Numbers (SINs)
for any given corrosive environment. void all sprinkler warranties, as well as TY5151 – Upright 11.2K, 3/4” NPT
The effects of ambient temperature, possibly void the sprinkler’s Approvals TY5251 – Pendent 11.2K, 3/4” NPT
and/or Listings. TY5851 – Upright 11.2K, 1/2” NPT
TY5151 is a redesignation for Central
IMPORTANT SIN C5151.
Always refer to Technical Data TY5251 is a redesignation for Central,
Sheet TFP700 for the “INSTALLER Gem, and Star SINs C5251, G1871,
WARNING” that provides cautions and S2531, respectively.
with respect to handling and instal-
lation of sprinkler systems and com- TY5851 is a redesignation for Central
ponents. Improper handling and SIN C5851.
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.

Page 1 of 4 NOVEMBER 2016 TFP342


TFP342
Page 2 of 4

1/2" (12,7 mm) Components:


NOMINAL MAKE-IN
1 - Frame
3/4" 2 - Seal
NPT 1 Assembly
3 - Cap
2-13/16" 2 4 - Bulb
(71,4 mm) WRENCH THREAD 5 - Compression
TYP. FLATS RELIEF 3 Screw
6 - Deflector *
4

1/2" 3/4" 5 * Temperature


NPT NPT rating is
indicated on
6
7/16" (11,1 mm) 1/2" (12,7 mm) deflector.
NOMINAL MAKE-IN NOMINAL MAKE-IN
UPRIGHT UPRIGHT PENDENT CROSS
TY5851 TY5151 TY5251 SECTION
FIGURE 1
SERIES ELO-231B 11.2K UPRIGHT 3/4” NPT (TY5151), UPRIGHT 1/2” NPT (TY5851), AND
PENDENT 3/4” NPT (TY5251) SPRINKLERS, STANDARD RESPONSE

Technical Design "FITTING SIDE"


TOWARDS SPRINKLER
Data Criteria FITTING

Approvals UL and C-UL


UL and C-UL Listed Listing Requirements
FM Approved TYCO Series ELO-231B 11.2K Standard
NYC Approved Response, Standard Coverage Upright
(Refer to Table A for complete approval and Pendent Sprinklers are to be WRENCH
information, including corrosion-resis- installed in accordance with NFPA 13 RECESS
standard sprinkler position and area/ (END "A")
tant status. The approvals apply to
the service conditions indicated in the density flow calculation requirements
Design Criteria section.) for light, ordinary, or extra hazard occu- FIGURE 2
pancies, as well as high-piled storage W-TYPE 3
Maximum Working Pressure SPRINKLER WRENCH
occupancies (solid-piled, palletized,
175 psi (12,1 bar)
rack storage, bin box, and shelf storage
Discharge Coefficient
K=11.2 gpm/psi½ (161,4 lpm/bar½)
including but not limited to Class I-IV
and Group A plastics) with a minimum Operation
Temperature Ratings residual (flowing) pressure of 7 psi (0,5
The glass bulb contains a fluid that
Refer to Table A bar) for wet or dry pipe systems.
expands when exposed to heat. When
Finishes FM Approval Requirements the rated temperature is reached, the
Refer to Table A The 11.2 K-factor, Model ELO-231B fluid expands sufficiently to shatter the
Physical Characteristics (TY5151, TY5251 & TY5851) Sprinklers glass bulb, allowing the sprinkler to
Frame �������������������������������������������������������Bronze are to be installed in accordance with activate and water to flow.
Cap �����������������������������������������������������������Bronze the applicable control mode density/
Sealing Assembly. . Beryllium Nickel w/TEFLON area guidelines provided by FM Global.
Bulb (5 mm dia.) ����������������������������������������� Glass (FM Approval guidelines may differ
Compression Screw ���������������������������������Bronze
Deflector ���������������������������������������������������Bronze
from UL and C-UL Listing criteria.)
TFP342
Page 3 of 4

SPRINKLER FINISH
SPRINKLER TEMPERATURE BULB
TYPE RATING LIQUID NATURAL CHROME LEAD WAX WAX-OVER-LEAD
BRASS PLATED COATED COATED COATED
155°F (68°C) Red
UPRIGHT 3
200°F (93°C) Green 1, 2, 3, 4
(TY5151 & TY5851)
286°F (141°C) Blue 3 3*
155°F (68°C) Red
PENDENT 3
200°F (93°C) Green 1, 2, 3, 4
(TY5251)
286°F (141°C) Blue 3 3*
Notes:
1. Listed by Underwriters Laboratories, Inc. (UL)
2. Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL)
3. Approved by FM Global (FM Approvals)
4. Approved by the City of New York (NYC) under MEA 291-04-E
* Listed/Approved for a maximum ceiling temperature of 150°F (66°C).
TABLE A
11.2K SERIES ELO-231B UPRIGHT AND PENDENT SPRINKLERS, STANDARD RESPONSE
LABORATORY LISTINGS AND APPROVALS

Installation Step 2. Tighten the sprinkler into the


sprinkler fitting using only the W-Type 3
The steel rod should be heated only
to the point at which it can begin to
Sprinkler Wrench (Ref. Figure 2), except melt the wax, and appropriate precau-
TYCO Series ELO-231B 11.2K Stan-
that an 8 or 10 inch adjustable wrench tions need to be taken, when handling
dard Response, Standard Coverage
is to be used for wax-coated sprinklers. the heated rod, in order to prevent the
Upright and Pendent Sprinklers must
With reference to Figure 1, the W-Type installer from being burned.
be installed in accordance with this
3 Sprinkler Wrench or the adjustable
section. If attempts to retouch the wax coating
wrench, as applicable, is to be applied
A leak-tight 3/4 inch NPT sprinkler joint with complete coverage are unsuc-
to the wrench flats.
should be obtained by applying a min- cessful, additional wax can be ordered
When installing wax-coated sprinklers in the form of a wax stick (the end
imum-to-maximum torque of 10 to 20
with the adjustable wrench, additional of which is color-coded). Only the
lbs.-ft. (13,4 to 26,8 Nm). A leak-tight
care needs to be exercised to prevent correct color-coded wax is to be
1/2 inch NPT sprinkler joint should be
damage to the wax coating on the used, and retouching of wrench flats
obtained by applying a minimum-to-
sprinkler wrench flats or frame arms and frame arms is only permitted at
maximum torque of 7 to 14 lbs.-ft. (9,5
and, consequently, exposure of bare the time of initial sprinkler installation.
to 19,0 Nm). Higher levels of torque
metal to the corrosive environment. With the steel rod heated as previ-
can distort the sprinkler inlet with con-
The jaws of the wrench should be ously described, touch the rod to the
sequent leakage or impairment of the
opened sufficiently wide to pass over area requiring additional wax with the
sprinkler.
the wrench flats without damaging the rod angled downward, and then touch
Notes: Do not install any bulb type wax coating. Before wrench-tightening the wax stick to the rod approximately
sprinkler if the bulb is cracked or there the sprinkler, the jaws of the wrench are 1/2 inch away from the area requiring
is a loss of liquid from the bulb. With to be adjusted to just contact the sprin- retouching. The wax will melt and run
the sprinkler held horizontally, a small kler wrench flats. After wrench-tight- down onto the sprinkler.
air bubble should be present. The ening the sprinkler, loosen the wrench
diameter of the air bubble is approxi- jaws before removing the wrench.
mately 1/16 inch (1,6 mm) for the 155°F
After installation, the sprinkler
(68°C) to 3/32 inch (2,4 mm) for the
wrench flats and frame arms must
286°F (141°C) temperature ratings.
be inspected and the wax coating
Do not attempt to make up for insuf- retouched (repaired) whenever the
ficient adjustment in the escutcheon coating has been damaged and bare
plate by under- or over-tightening the metal is exposed. The wax coating
sprinkler. Re-adjust the position of the on the wrench flats can be retouched
sprinkler fitting to suit. by gently applying a heated 1/8 inch
The Series ELO-231B Upright and diameter steel rod to the areas of wax
Pendent Sprinklers must be installed that have been damaged, to smooth it
in accordance with the following back over areas where bare metal is
instructions. exposed.

Note: Pendent sprinklers are to be Notes: Only retouching of the wax


installed in the pendent position; coating applied to the wrench flats
upright sprinklers are to be installed in and frame arms is permitted, and
the upright position. the retouching is to be performed
only at the time of the initial sprinkler
Step 1. With pipe thread sealant installation.
applied to the pipe threads, hand-
tighten the sprinkler into the sprinkler
fitting.
TFP342
Page 4 of 4

P/N*  50 — XXX — X — XXX

SIN SPRINKLER TEMPERATURE


FINISH RATING

501 11.2K UPRIGHT (1/2” NPT) TY5851 NATURAL


1 155 155°F (68°C)
BRASS

510 11.2K UPRIGHT (3/4” NPT) TY5151 WAX


6 200 200°F (93°C)
COATED

512 11.2K PENDENT (3/4” NPT) TY5251 LEAD


7 286 286°F (141°C)
COATED
WAX-OVER-LEAD
8 COATED
CHROME
9 PLATED

TABLE B
SERIES ELO231 11.2K UPRIGHT AND PENDENT SPRINKLERS, STANDARD RESPONSE
PART NUMBER SELECTION

Care and Frequent visual inspections are rec-


ommended to be initially performed Limited
Maintenance for corrosion resistant sprinklers, after
the installation has been completed, to Warranty
TYCO Series ELO-231B 11.2K Standard verify the long term potential integrity For warranty terms and conditions, visit
Response, Standard Coverage Upright of the sprinkler coatings. Thereafter, www.tyco-fire.com.
and Pendent Sprinklers must be main- annual inspections per NFPA 25 should

Ordering
tained and serviced in accordance with suffice; however, instead of inspecting
this section. from the floor level, a random sampling

Procedure
of close-up visual inspections should
Before closing a fire protection system be made, so as to better determine the
control valve for maintenance work on exact sprinkler condition and the long
the fire protection system that it con- term integrity of the corrosion resistant Sprinkler Assemblies with
trols, permission to shut down the coating, as it may be affected by the NPT Thread Connection
affected fire protection system must corrosive conditions present. Specify: Series ELO-231B 11.2K Stan-
be obtained from the proper authorities dard Response (specify Pendent
and all personnel who may be affected The owner is responsible for the or Upright) Sprinkler, SIN (specify),
by this action must be notified. inspection, testing, and maintenance of (specify temperature rating), with
their fire protection system and devices (specify) finish, P/N (specify from Table
Sprinklers that are found to be leaking in compliance with this document, as B)
or exhibiting visible signs of corrosion well as with the applicable standards
must be replaced. of the National Fire Protection Asso- Sprinkler Wrench
ciation (e.g., NFPA 25), in addition to Specify: W-Type 3 Sprinkler Wrench,
Automatic sprinklers must never be P/N 56-895-1-001
painted, plated, coated or other- the standards of any other authorities
wise altered after leaving the factory. having jurisdiction. Contact the install- Wax Sticks
Modified sprinklers must be replaced. ing contractor or product manufacturer (for retouching wrench-damaged wax
Sprinklers that have been exposed to with any questions. coating)
corrosive products of combustion, but It is recommended that automatic Specify: (specify Color) color-coded
have not operated, should be replaced sprinkler systems be inspected, tested, Wax Stick for retouching (specify tem-
if they cannot be completely cleaned and maintained by a qualified Inspec- perature rating) temperature rated
by wiping the sprinkler with a cloth or tion Service in accordance with local Series ELO-231B Sprinklers, P/N
by brushing it with a soft bristle brush. requirements and/or national codes. (specify):
Care must be exercised to avoid Red for 155°F . . . . . . . . . . . . . . . . 56-065-1-155
damage to the sprinklers before, Blue for 200°F and 286°F 56-065-1-286
during, and after installation. Sprin-
klers damaged by dropping, striking, Notes: Each wax stick is suitable for
wrench twist/slippage, or the like, must retouching up to twenty-five sprinklers.
be replaced. Also, replace any sprin- The wax used for 286°F sprinklers is
kler that has a cracked bulb or that has the same as for 200°F sprinklers, and,
lost liquid from its bulb (Ref. Installa- therefore, the 286°F sprinkler is limited
tion section). to the same maximum ceiling tempera-
ture as the 200°F sprinkler (i.e., 150°F).