Professional Documents
Culture Documents
www.tyco-fire.com
Contacts
Sprinkler
agencies, the testing is not repre- and devices in proper operating con-
sentative of all possible corrosive dition. Contact the installing contrac-
tor or product manufacturer with any
atmospheres. Consequently, it is rec-
ommended that the end-user be con- questions. Identification
sulted with respect to the suitability
of these corrosion resistant coatings
Installation of Series ELO-231B Pendent
Sprinklers in recessed escutcheons will Numbers (SINs)
for any given corrosive environment. void all sprinkler warranties, as well as TY5151 – Upright 11.2K, 3/4” NPT
The effects of ambient temperature, possibly void the sprinkler’s Approvals TY5251 – Pendent 11.2K, 3/4” NPT
and/or Listings. TY5851 – Upright 11.2K, 1/2” NPT
TY5151 is a redesignation for Central
IMPORTANT SIN C5151.
Always refer to Technical Data TY5251 is a redesignation for Central,
Sheet TFP700 for the “INSTALLER Gem, and Star SINs C5251, G1871,
WARNING” that provides cautions and S2531, respectively.
with respect to handling and instal-
lation of sprinkler systems and com- TY5851 is a redesignation for Central
ponents. Improper handling and SIN C5851.
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
SPRINKLER FINISH
SPRINKLER TEMPERATURE BULB
TYPE RATING LIQUID NATURAL CHROME LEAD WAX WAX-OVER-LEAD
BRASS PLATED COATED COATED COATED
155°F (68°C) Red
UPRIGHT 3
200°F (93°C) Green 1, 2, 3, 4
(TY5151 & TY5851)
286°F (141°C) Blue 3 3*
155°F (68°C) Red
PENDENT 3
200°F (93°C) Green 1, 2, 3, 4
(TY5251)
286°F (141°C) Blue 3 3*
Notes:
1. Listed by Underwriters Laboratories, Inc. (UL)
2. Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL)
3. Approved by FM Global (FM Approvals)
4. Approved by the City of New York (NYC) under MEA 291-04-E
* Listed/Approved for a maximum ceiling temperature of 150°F (66°C).
TABLE A
11.2K SERIES ELO-231B UPRIGHT AND PENDENT SPRINKLERS, STANDARD RESPONSE
LABORATORY LISTINGS AND APPROVALS
P/N* 50 — XXX — X — XXX
TABLE B
SERIES ELO231 11.2K UPRIGHT AND PENDENT SPRINKLERS, STANDARD RESPONSE
PART NUMBER SELECTION
Ordering
tained and serviced in accordance with suffice; however, instead of inspecting
this section. from the floor level, a random sampling
Procedure
of close-up visual inspections should
Before closing a fire protection system be made, so as to better determine the
control valve for maintenance work on exact sprinkler condition and the long
the fire protection system that it con- term integrity of the corrosion resistant Sprinkler Assemblies with
trols, permission to shut down the coating, as it may be affected by the NPT Thread Connection
affected fire protection system must corrosive conditions present. Specify: Series ELO-231B 11.2K Stan-
be obtained from the proper authorities dard Response (specify Pendent
and all personnel who may be affected The owner is responsible for the or Upright) Sprinkler, SIN (specify),
by this action must be notified. inspection, testing, and maintenance of (specify temperature rating), with
their fire protection system and devices (specify) finish, P/N (specify from Table
Sprinklers that are found to be leaking in compliance with this document, as B)
or exhibiting visible signs of corrosion well as with the applicable standards
must be replaced. of the National Fire Protection Asso- Sprinkler Wrench
ciation (e.g., NFPA 25), in addition to Specify: W-Type 3 Sprinkler Wrench,
Automatic sprinklers must never be P/N 56-895-1-001
painted, plated, coated or other- the standards of any other authorities
wise altered after leaving the factory. having jurisdiction. Contact the install- Wax Sticks
Modified sprinklers must be replaced. ing contractor or product manufacturer (for retouching wrench-damaged wax
Sprinklers that have been exposed to with any questions. coating)
corrosive products of combustion, but It is recommended that automatic Specify: (specify Color) color-coded
have not operated, should be replaced sprinkler systems be inspected, tested, Wax Stick for retouching (specify tem-
if they cannot be completely cleaned and maintained by a qualified Inspec- perature rating) temperature rated
by wiping the sprinkler with a cloth or tion Service in accordance with local Series ELO-231B Sprinklers, P/N
by brushing it with a soft bristle brush. requirements and/or national codes. (specify):
Care must be exercised to avoid Red for 155°F . . . . . . . . . . . . . . . . 56-065-1-155
damage to the sprinklers before, Blue for 200°F and 286°F 56-065-1-286
during, and after installation. Sprin-
klers damaged by dropping, striking, Notes: Each wax stick is suitable for
wrench twist/slippage, or the like, must retouching up to twenty-five sprinklers.
be replaced. Also, replace any sprin- The wax used for 286°F sprinklers is
kler that has a cracked bulb or that has the same as for 200°F sprinklers, and,
lost liquid from its bulb (Ref. Installa- therefore, the 286°F sprinkler is limited
tion section). to the same maximum ceiling tempera-
ture as the 200°F sprinkler (i.e., 150°F).