2SWLRQ

Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500

Series TY-FRB — 2.8, 4.2, 5.6, and 8.0 K-factor


Upright, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage
tained when exposed to corrosive at-
General mospheres. Although corrosion resis-
tant coated sprinklers have passed the
Description standard corrosion tests of the appli-
cable approval agencies, the testing is
The Series TY-FRB, 2.8, 4.2, 5.6, and not representative of all possible cor-
8.0 K-factor, Upright and Pendent rosive atmospheres. Consequently, it
Sprinklers described in this data sheet is recommended that the end user be
are quick response - standard cover- consulted with respect to the suitability
age, decorative 3 mm glass bulb type of these coatings for any given corro-
spray sprinklers designed for use in sive environment. The effects of ambi-
light or ordinary hazard, commercial ent temperature, concentration of
occupancies such as banks, hotels, chemicals, and gas/chemical velocity,
shopping malls, etc. should be considered, as a minimum,
The recessed version of the Series along with the corrosive nature of the
TY-FRB Pendent Sprinkler, where ap- chemical to which the sprinklers will be
plicable, is intended for use in areas exposed.
with a finished ceiling. It uses either a An intermediate level versions of the
two-piece Style 10 (1/2 inch NPT) or Series TY-FRB Pendent Sprinklers
Style 40 (3/4 inch NPT) Recessed Es- are detailed in Technical Data Sheet
cutcheon with 1/2 inch (12,7 mm) of TFP356, and Sprinkler Guards are de-
recessed adjustment or up to 3/4 inch tailed in Technical Data Sheet TFP780
(19,1 mm) of total adjustment from the
flush pendent position, or a two-piece WARNINGS
Style 20 (1/2 inch NPT) or Style 30 (3/4 The Series TY-FRB Sprinklers de-
inch NPT) Recessed Escutcheon with scribed herein must be installed and
1/4 inch (6,4 mm) of recessed adjust- maintained in compliance with this
ment or up to 1/2 inch (12,7 mm) of document, as well as with the applica-
total adjustment from the flush pen- ble standards of the National Fire Pro-
dent position. The adjustment pro- tection Association, in addition to the
vided by the Recessed Escutcheon re- standards of any other authorities hav-
duces the accuracy to which the fixed ing jurisdiction. Failure to do so may Model/Sprinkler
pipe drops to the sprinklers must be impair the performance of these de-
cut. vices. Identification
Corrosion resistant coatings, where
applicable, are utilized to extend the
The owner is responsible for maintain-
ing their fire protection system and de-
Numbers
life of copper alloy sprinklers beyond vices in proper operating condition. TY1131 - Upright 2.8K, 1/2"NPT
that which would otherwise be ob- The installing contractor or sprinkler TY1231 - Pendent 2.8K, 1/2"NPT
manufacturer should be contacted TY2131 - Upright 4.2K, 1/2"NPT
with any questions. TY2231 - Pendent 4.2K, 1/2"NPT
IMPORTANT TY3131 - Upright 5.6K, 1/2"NPT
Always refer to Technical Data TY3231 - Pendent 5.6K, 1/2"NPT
Sheet TFP700 for the “INSTALLER TY4131 - Upright 8.0K, 3/4"NPT
WARNING” that provides cautions TY4231 - Pendent 8.0K, 3/4"NPT
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.

Page 1 of 10 APRIL, 2006 TFP171


Page 2 of 10 TFP171

ESCUTCHEON 7/16" (11,1 mm) STYLE 10 or 20


PLATE SEATING NOMINAL RECESSED
SURFACE 1/2" ** MAKE-IN ESCUTCHEON SSU *
NPT DEFLECTOR
6

5
7/16"
2-1/4" (11,1 mm) 4
(57,2 mm) NOMINAL
MAKE-IN 2
1-9/16" 2-3/16" 3
(39,7 mm) WRENCH (55,6 mm)
FLATS 1

7
SSP DEFLECTOR * 2-7/8" (73,0 mm) DIA. 1/2" NPT **

PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION

1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to


2 - Button Assembly 5 - Compression 7 - Bushing orifice seat on frame.
Screw
** Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 1
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY1131) AND PENDENT (TY1231) SPRINKLERS
2.8 K-FACTOR, 1/2 INCH NPT

ESCUTCHEON 7/16" (11,1 mm) STYLE 10 or 20


PLATE SEATING NOMINAL RECESSED
SURFACE 1/2" ** MAKE-IN ESCUTCHEON SSU *
NPT DEFLECTOR
6*

7/16" 5
2-3/16" (11,1 mm)
(55,6 mm) NOMINAL 4
MAKE-IN
1-1/2" 2
2-3/16"
(38,1 mm) WRENCH (55,6 mm)
FLATS 3

1
SSP DEFLECTOR * 2-7/8" (73,0 mm) DIA. 1/2" NPT **

PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION


1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression orifice seat on frame.
Screw
** Pipe thread connections per ISO 7/1 can be provided on
special request.

FIGURE 2
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY2131) AND PENDENT (TY2231) SPRINKLERS
4.2 K-FACTOR, 1/2 INCH NPT
TFP171 Page 3 of 10

ESCUTCHEON 7/16" (11,1 mm) STYLE 10 or 20


PLATE SEATING NOMINAL RECESSED
SURFACE 1/2" ** MAKE-IN ESCUTCHEON SSU *
NPT DEFLECTOR
6*

7/16" 5
2-3/16" (11,1 mm)
(55,6 mm) NOMINAL 4
MAKE-IN
1-1/2" 2
2-3/16"
(38,1 mm) WRENCH (55,6 mm)
FLATS 3

1
SSP DEFLECTOR * 2-7/8" (73,0 mm) DIA. 1/2" NPT **

PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION


1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression orifice seat on frame.
Screw
** Pipe thread connections per ISO 7/1 can be provided on
special request.

FIGURE 3
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY3131) AND PENDENT (TY3231) SPRINKLERS
5.6 K-FACTOR, 1/2 INCH NPT

ESCUTCHEON 1/2" (12,7 mm) STYLE 30 or 40


PLATE SEATING NOMINAL RECESSED
SURFACE 3/4" ** MAKE-IN ESCUTCHEON SSU *
NPT DEFLECTOR
6*

1/2" 5
2-5/16" (12,7 mm)
(58,7 mm) NOMINAL 4
MAKE-IN
2
1-9/16" 2-1/4"
(39,7 mm) WRENCH (57,2 mm)
FLATS 3

1
SSP DEFLECTOR * 2-7/8" (73,0 mm) DIA. 3/4" NPT **
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION

1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to


2 - Button Assembly 5 - Compression orifice seat on frame.
Screw
** Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 4
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY4131) AND PENDENT (TY4231) SPRINKLERS
8.0 K-FACTOR, 3/4 INCH NPT
Page 4 of 10 TFP171

SPRINKLER FINISH (See Note 7)


K TYPE TEMP. BULB NATURAL CHROME WHITE***
Technical
LIQUID BRASS PLATED POLYESTER Data
135°F/57°C Orange Approvals
PENDENT UL and C-UL Listed.
155°F/68°C Red
(TY1231) 1, 2, 3, 5 FM, LPCB, and NYC Approved.
and 175°F/79°C Yellow (Refer to Table A and B for complete
UPRIGHT 200°F/93°C Green approval information including corro-
(TY1131) sion resistant status.)
2.8 286°F/141°C Blue
1/2" Maximum Working Pressure
NPT 135°F/57°C Orange Refer to Table C.
RECESSED
155°F/68°C Red Discharge Coefficient
PENDENT
K = 2.8 GPM/psi1/2 (40,3 LPM/bar1/2)
(TY1231)* 175°F/79°C Yellow
K = 4.2 GPM/psi1/2 (60,5 LPM/bar1/2)
Figure 5 200°F/93°C Green 1, 2, 5 K = 5.6 GPM/psi1/2 (80,6 LPM/bar1/2)
K = 8.0 GPM/psi1/2 (115,2 LPM/bar1/2)
135°F/57°C Orange
RECESSED Temperature Ratings
155°F/68°C Red
PENDENT Refer to Table A and B
(TY1231)** 175°F/79°C Yellow
Finishes
Figure 6 200°F/93°C Green Sprinkler: Refer to Table A and B.
Recessed Escutcheon: White Coated,
135°F/57°C Orange
Chrome Plated, or Brass Plated.
PENDENT
155°F/68°C Red
(TY2231)
and 175°F/79°C Yellow Physical Characteristics
UPRIGHT Frame . . . . . . . . . . . . Bronze
200°F/93°C Green Button . . . . . . . . Brass/Copper
(TY2131)
4.2 286°F/141°C Blue Sealing Assembly . . . . . . . . . .
1/2" 1, 2 . . . . . Beryllium Nickel w/Teflon†
NPT 135°F/57°C Orange Bulb . . . . . . . . . . . . . . Glass
RECESSED Compression Screw . . . . . Bronze
155°F/68°C Red
PENDENT Deflector . . . . . . . Copper/Bronze
(TY2231)* 175°F/79°C Yellow Bushing (K=2.8) . . . . . . . Bronze
Figure 7 200°F/93°C Green

RECESSED
135°F/57°C Orange Operation
155°F/68°C Red
PENDENT The glass Bulb contains a fluid which
(TY2231)** 175°F/79°C Yellow expands when exposed to heat. When
Figure 8 the rated temperature is reached, the
200°F/93°C Green
fluid expands sufficiently to shatter the
glass Bulb, allowing the sprinkler to
NOTES:
activate and water to flow.
1. Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers.
2. Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL) as Quick Re-
sponse Sprinklers.
3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprin-
Design
klers.
5. Approved by the City of New York under MEA 354-01-E. Criteria
7. Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed, the sprin-
klers are UL and C-UL Listed as Corrosion Resistant Sprinklers. The Series TY-FRB Pendent and Up-
* Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment right Sprinklers are intended for fire
Recessed Escutcheon, as applicable. protection systems designed in ac-
** Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment cordance with the standard installation
Recessed Escutcheon, as applicable. rules recognized by the applicable
*** Frame and Deflector only. Listings and approvals apply to color (Special Order). Listing or Approval agency (e.g., UL
N/A: Not Available Listing is based on the requirements of

† DuPont Registered Trademark


NFPA 13, and FM Approval is based
TABLE A on the requirements of FM’s Loss Pre-
LABORATORY LISTINGS AND APPROVALS vention Data Sheets ). Only the Style
2.8 AND 4.2 K-FACTOR SPRINKLERS 10, 20, 30, or 40 Recessed Escutch-
eon, as applicable, is to be used for
recessed pendent installations.
TFP171 Page 5 of 10

SPRINKLER FINISH (See Note 8)


K TYPE TEMP. BULB NATURAL CHROME WHITE*** LEAD
LIQUID BRASS PLATED POLYESTER COATED

135°F/57°C Orange
PENDENT
155°F/68°C Red
(TY3231) 1, 2, 3, 4, 5, 6, 7 1, 2, 3, 5
and 175°F/79°C Yellow
UPRIGHT 200°F/93°C Green
(TY3131)
5.6 286°F/141°C Blue
1/2"
NPT 135°F/57°C Orange
RECESSED
155°F/68°C Red
PENDENT 1, 2, 4, 5 N/A
(TY3231)* 175°F/79°C Yellow
Figure 9 200°F/93°C Green
135°F/57°C Orange
RECESSED
155°F/68°C Red
PENDENT 1, 2, 3, 4, 5 1, 2, 4, 5 N/A
(TY3231)** 175°F/79°C Yellow
Figure 10 200°F/93°C Green
135°F/57°C Orange
PENDENT
155°F/68°C Red
(TY4231) 1, 2, 5
and 175°F/79°C Yellow 1, 2, 3, 4, 5, 6, 7
UPRIGHT 200°F/93°C Green
(TY4131)
8.0 286°F/141°C Blue
3/4"
NPT 135°F/57°C Green
RECESSED
155°F/68°C Orange
PENDENT 1, 2, 4, 5 N/A
(TY4231)* 175°F/79°C Red
Figure 11 200°F/93°C Yellow
135°F/57°C Orange
RECESSED
155°F/68°C Red
PENDENT 1, 2, 3, 4, 5 N/A
(TY4231)** 175°F/79°C Yellow
Figure 12 200°F/93°C Green

NOTES:
1. Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers.
2. Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL) as Quick Response Sprinklers.
3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers.
4. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k/04) as Quick Response Sprinklers; however, the
LPCB does not rate the thermal sensitivity of recessed sprinklers.
5. Approved by the City of New York under MEA 354-01-E.
6. VdS Approved (For details contact Tyco Fire & Building Products, Enschede, Netherlands, Tel. 31-53-428-4444/Fax 31-53-428-3377).
7. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06) as Quick Response Sprinklers.
8. Where Polyester Coated and Lead Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as
Corrosion Resistant Sprinklers. Where Lead Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as a
Corrosion Resistant Sprinklers.
* Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable.
** Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment Recessed Escutcheon, as applicable.
*** Frame and Deflector only. Listings and approvals apply to color (Special Order).
N/A: Not Available

TABLE B
LABORATORY LISTINGS AND APPROVALS
5.6 AND 8.0 K-FACTOR SPRINKLERS
Page 6 of 10 TFP171

SPRINKLER FINISH
K TYPE NATURAL CHROME WHITE LEAD
BRASS PLATED POLYESTER COATED

PENDENT (TY3231)
and
2.8 UPRIGHT (TY3131) 175 PSI (12,1 BAR) N/A
1/2" RECESSED PENDENT
NPT (TY323)

PENDENT (TY4231)
and
4.2 UPRIGHT (TY4131) 175 PSI (12,1 BAR) N/A
3/4" RECESSED PENDENT
NPT (TY4231)

PENDENT (TY3231)
and 250 PSI (17,2 BAR) 175 PSI (12,1 BAR)
5.6 UPRIGHT (TY3131) OR
1/2" 175 PSI (12,1 BAR)
RECESSED PENDENT
NPT (TY323) N/A
(SEE NOTE 1)

PENDENT (TY4231)
and 175 PSI (12,1 BAR) 175 PSI (12,1 BAR)
8.0 UPRIGHT (TY4131)
3/4" RECESSED PENDENT
NPT (TY4231) N/A

NOTES:
1. The maximum working pressure of 250 psi (17,2 bar) only applies to the Listing by Underwriters Laboratories Inc. (UL); the Listing by
Underwriters Laboratories, Inc. for use in Canada (C-UL); and , the Approval by the City of New York.

TABLE C, MAXIMUM WORKING PRESSURE

nections. Higher levels of torque may The Series TY-FRB Recessed Pen-
Installation distort the sprinkler inlet and cause
leakage or impairment of the sprinkler.
dent Sprinklers must be installed in
accordance with the following instruc-
The Series TY-FRB Sprinklers must tions.
be installed in accordance with the fol- Do not attempt to make-up for insuffi-
lowing instructions: cient adjustment in the escutcheon Step A. After installing the Style 10.
plate by under- or over-tightening the 20, 30, or 40 Mounting Plate, as appli-
NOTES sprinkler. Readjust the position of the cable, over the sprinkler threads and
Do not install any bulb type sprinkler if sprinkler fitting to suit. with pipe thread sealant applied to the
the bulb is cracked or there is a loss of pipe threads, hand tighten the sprin-
The Series TY-FRB Pendent and Up-
liquid from the bulb. With the sprinkler kler into the sprinkler fitting.
right Sprinklers must be installed in
held horizontally, a small air bubble accordance with the following instruc- Step B. Tighten the sprinkler into the
should be present. The diameter of the tions. sprinkler fitting using only the W-Type
air bubble is approximately 1/16 inch 7 Recessed Sprinkler Wrench (Ref.
(1,6 mm) for the 135°F/57°C to 3/32 Step 1. Pendent sprinklers are to be
Figure 14). With reference to Figure 1,
inch (2,4 mm) for the 286°F/141°C installed in the pendent position, and
2, 3, and 4, the W-Type 7 Recessed
temperature ratings. upright sprinklers are to be installed in
Sprinkler Wrench is to be applied to
the upright position.
A leak tight 1/2 inch NPT sprinkler joint the sprinkler wrench flats.
should be obtained with a torque of 7 Step 2. With pipe thread sealant ap-
Step C. After the ceiling has been in-
to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi- plied to the pipe threads, hand tighten
stalled or the finish coat has been ap-
mum of 21 ft. lbs. (28,5 Nm) of torque the sprinkler into the sprinkler fitting.
plied, slide on the Style 10, 20, 30, or
may be used to install sprinklers with Step 3. Tighten the sprinkler into the 40 Closure over the Series TY-FRB
1/2 NPT connections. A leak tight 3/4 sprinkler fitting using only the W-Type Sprinkler and push the Closure over
inch NPT sprinkler joint should be ob- 6 Sprinkler Wrench (Ref. Figure 13). the Mounting Plate until its flange
tained with a torque of 10 to 20 ft.lbs. With reference to Figures 1, 2, 3, and comes in contact with the ceiling.
(13,4 to 26,8 Nm). A maximum of 30 4, the W-Type 6 Sprinkler Wrench is to
ft.lbs. (40,7 Nm) of torque is to be used be applied to the sprinkler wrench
to install sprinklers with 3/4 NPT con- flats.
TFP171 Page 7 of 10

2-7/8" DIA. 2-7/8" DIA.


(73,0 mm) 3/4" (19,1 mm) (73,0 mm)
5/8±1/4" 1/2±1/8" 1/2" (12,7 mm)
(15,9±6,4 mm) 1/4" (6,4 mm) (12,7±3,2 mm) 1/4" (6,4 mm)
2-1/4" DIA. 2-1/4" DIA.
(57,2 mm) (57,2 mm)
FACE OF MOUNTING FACE OF MOUNTING
SPRINKLER PLATE SPRINKLER PLATE
FITTING FITTING
1/8" 1/8"
(3,2 mm) (3,2 mm)

MOUNTING
MOUNTING SURFACE
SURFACE

SERIES 1-5/16" (33,3 mm) SERIES 1-5/16" (33,3 mm)


CLOSURE CLOSURE
TY-FRB 13/16" (20,6 mm) TY-FRB 1-1/16" (27,0 mm)

FIGURE 5 FIGURE 6
SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON
2.8 K-FACTOR, 1/2 INCH NPT 2.8 K-FACTOR, 1/2 INCH NPT

2-7/8" DIA. 2-7/8" DIA.


(73,0 mm) 3/4" (19,1 mm) (73,0 mm)
5/8±1/4" 1/2±1/8" 1/2" (12,7 mm)
(15,9±6,4 mm) 1/4" (6,4 mm) (12,7±3,2 mm) 1/4" (6,4 mm)
2-1/4" DIA. 2-1/4" DIA.
(57,2 mm) (57,2 mm)
FACE OF MOUNTING FACE OF MOUNTING
SPRINKLER PLATE SPRINKLER PLATE
FITTING FITTING
1/8" 1/8"
(3,2 mm) (3,2 mm)

MOUNTING
MOUNTING SURFACE
SURFACE
SERIES 1-1/4" (31,8 mm) SERIES 1-1/4" (31,8 mm)
CLOSURE CLOSURE
TY-FRB 3/4" (19,1 mm) TY-FRB 1" (25,4 mm)

FIGURE 7 FIGURE 8
SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON
4.2 K-FACTOR, 1/2 INCH NPT 4.2 K-FACTOR, 1/2 INCH NPT

objects; otherwise, non-operation in by brushing it with a soft bristle brush.


Care and the event of a fire or inadvertent opera-
tion may result.
Care must be exercised to avoid dam-
age to the sprinklers - before, during,
Maintenance Absence of an escutcheon, which is and after installation. Sprinklers dam-
The Series TY-FRB Sprinklers must used to cover a clearance hole, may aged by dropping, striking, wrench
be maintained and serviced in accord- delay the time to sprinkler operation in twist/slippage, or the like, must be re-
ance with the following instructions: a fire situation. placed. Also, replace any sprinkler
that has a cracked bulb or that has lost
Sprinklers that are found to be leaking
NOTES liquid from its bulb. (Ref. Installation
or exhibiting visible signs of corrosion
Before closing a fire protection system Section).
must be replaced.
main control valve for maintenance Frequent visual inspections are rec-
work on the fire protection system that Automatic sprinklers must never be
ommended to be initially performed for
it controls, permission to shut down the painted, plated, coated or otherwise
corrosion resistant coated sprinklers,
affected fire protection system must be altered after leaving the factory. Modi-
after the installation has been com-
obtained from the proper authorities fied sprinklers must be replaced.
pleted, to verify the integrity of the cor-
and all personnel who may be affected Sprinklers that have been exposed to
rosion resistant coating. Thereafter,
by this action must be notified. corrosive products of combustion, but
annual inspections per NFPA 25
have not operated, should be replaced
The owner must assure that the sprin- should suffice; however, instead of in-
if they cannot be completely cleaned
klers are not used for hanging of any specting from the floor level, a random
by wiping the sprinkler with a cloth or
Page 8 of 10 TFP171

2-7/8" DIA. 2-7/8" DIA.


(73,0 mm) 3/4" (19,1 mm) (73,0 mm)
5/8±1/4" 1/2±1/8" 1/2" (12,7 mm)
(15,9±6,4 mm) 1/4" (6,4 mm) (12,7±3,2 mm) 1/4" (6,4 mm)
2-1/4" DIA. 2-1/4" DIA.
(57,2 mm) (57,2 mm)
FACE OF MOUNTING FACE OF MOUNTING
SPRINKLER PLATE SPRINKLER PLATE
FITTING FITTING
1/8" 1/8"
(3,2 mm) (3,2 mm)

MOUNTING
MOUNTING SURFACE
SURFACE
SERIES 1-1/4" (31,8 mm) SERIES 1-1/4" (31,8 mm)
CLOSURE CLOSURE
TY-FRB 3/4" (19,1 mm) TY-FRB 1" (25,4 mm)

FIGURE 9 FIGURE 10
SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON
5.6 K-FACTOR, 1/2 INCH NPT 5.6 K-FACTOR, 1/2 INCH NPT

2-7/8" DIA. 2-7/8" DIA.


(73,0 mm) 3/4" (19,1 mm) (73,0 mm) 1/2" (12,7 mm)
5/8±1/4" 1/2±1/8"
(15,9±6,4 mm) 2-1/4" DIA. 1/4" (6,4 mm) (12,7±3,2 mm) 2-1/4" DIA. 1/4" (6,4 mm)
(57,2 mm) (57,2 mm)
FACE OF MOUNTING FACE OF MOUNTING
SPRINKLER PLATE SPRINKLER PLATE
FITTING FITTING
1/8" 1/8"
(3,2 mm) (3,2 mm)

MOUNTING
MOUNTING SURFACE
SURFACE

CLOSURE SERIES 1-5/16" (33,3 mm) CLOSURE SERIES 1-5/16" (33,3 mm)
TY-FRB 13/16" (20,6 mm) TY-FRB 1-1/16" (27,0 mm)

FIGURE 11 FIGURE 12
SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 40 RECESSED ESCUTCHEON STYLE 30 RECESSED ESCUTCHEON
8.0 K-FACTOR, 3/4 INCH NPT 8.0 K-FACTOR, 3/4 INCH NPT

sampling of close-up visual inspec- WRENCH


tions should be made, so as to better RECESS
determine the exact sprinkler condi-
tion and the long term integrity of the WRENCH RECESS
corrosion resistant coating, as it may (END "A" USED FOR
be affected by the corrosive conditions 1/2" NPT MODELS)
present.
The owner is responsible for the in-
spection, testing, and maintenance of WRENCH RECESS
their fire protection system and de- (END "B" USED FOR PUSH WRENCH
vices in compliance with this docu- IN TO ENSURE
3/4" NPT MODELS) ENGAGEMENT
ment, as well as with the applicable WITH SPRINKLER
standards of the National Fire Protec- FIGURE 13 WRENCHING AREA
tion Association (e.g., NFPA 25), in W-TYPE 6 SPRINKLER
addition to the standards of any other WRENCH FIGURE 14
authorities having jurisdiction. The in- W-TYPE 7 RECESSED
stalling contractor or sprinkler manu- SPRINKLER WRENCH
facturer should be contacted relative tested, and maintained by a qualified
to any questions. Inspection Service in accordance with
It is recommended that automatic local requirements and/or national
sprinkler systems be inspected, codes.
TFP171 Page 9 of 10

P/N 57 — XXX — X — XXX


TEMPERATURE
MODEL/SIN RATING
SPRINKLER
330 2.8K UPRIGHT (1/2"NPT) TY1131 135 135°F/57°C

331 2.8K PENDENT (1/2"NPT) TY1231 1 NATURAL BRASS 155 155°F/68°C

340 4.2K UPRIGHT (1/2"NPT) TY2131 4 WHITE POLYESTER 175 175°F/79°C

341 4.2K PENDENT (1/2"NPT) TY2231 3 WHITE (RAL9010)* 200 200°F/93°C

370 5.6K UPRIGHT (1/2"NPT) TY3131 9 CHROME PLATED 286 286°F/141°C

371 5.6K PENDENT (1/2"NPT) TY3231 7 LEAD COATED

390 8.0K UPRIGHT (3/4"NPT) TY4131

391 8.0K PENDENT (3/4"NPT) TY4231 * Eastern Hemisphere sales only.

TABLE D
PART NUMBER SELECTION
SERIES TY-FRB PENDENT AND UPRIGHT SPRINKLERS

charges, regardless of whether TFBP


Limited was informed about the possibility of
such damages, and in no event shall
Ordering
Warranty TFBP’s liability exceed an amount Procedure
equal to the sales price.
Products manufactured by Tyco Fire & When placing an order, indicate the
Building Products (TFBP) are war- The foregoing warranty is made in lieu full product name. Refer to the Price
ranted solely to the original Buyer for of any and all other warranties, ex- List for complete listing of Part Num-
ten (10) years against defects in mate- press or implied, including warranties bers.
rial and workmanship when paid for of merchantability and fitness for a par-
ticular purpose. Contact your local distributor for avail-
and properly installed and maintained
ability.
under normal use and service. This This limited warranty sets forth the ex-
warranty will expire ten (10) years clusive remedy for claims based on Sprinkler Assemblies with NPT
from date of shipment by TFBP. No failure of or defect in products, materi- Thread Connections:
warranty is given for products or com- als or components, whether the claim Specify: (Specify Model/SIN), Quick
ponents manufactured by companies is made in contract, tort, strict liability Response, (specify K-factor), (specify
not affiliated by ownership with TFBP or any other legal theory. temperature rating), Series TY-FRB
or for products and components which
This warranty will apply to the full ex- (specify Pendent or Upright) Sprinkler
have been subject to misuse, improper
tent permitted by law. The invalidity, in with (specify type of finish or coating),
installation, corrosion, or which have
whole or part, of any portion of this P/N (specify from Table D).
not been installed, maintained, modi-
fied or repaired in accordance with ap- warranty will not affect the remainder.
Recessed Escutcheon:
plicable Standards of the National Fire Specify: Style (10, 20, 30, or 40) Re-
Protection Association, and/or the cessed Escutcheon with (specify*) fin-
standards of any other Authorities
ish, P/N (specify*).
Having Jurisdiction. Materials found
by TFBP to be defective shall be either * Refer to Technical Data Sheet TFP770.
repaired or replaced, at TFBP’s sole
option. TFBP neither assumes, nor Sprinkler Wrench:
authorizes any person to assume for it, Specify: W-Type 6 Sprinkler Wrench,
any other obligation in connection with P/N 56-000-6-387.
the sale of products or parts of prod-
ucts. TFBP shall not be responsible for Specify: W-Type 7 Sprinkler Wrench,
sprinkler system design errors or inac- P/N 56-850-4-001.
curate or incomplete information sup-
plied by Buyer or Buyer’s repre-
sentatives.
In no event shall TFBP be liable, in
contract, tort, strict liability or under
any other legal theory, for incidental,
indirect, special or consequential dam-
ages, including but not limited to labor
Page 10 of 10 TFP171

TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446
2SWLRQ

Customer Service/Sales:
Tel: (414) 570-5000 / (800) 558-5236
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
Fax: (414) 570-5010 / (800) 877-1295

Series RFII — 5.6 K-factor


“Royal Flush II” Pendent Concealed Sprinklers
Quick & Standard Response, Standard Coverage
Cap. The Protective Cap is temporarily
General removed for installation, and then it
can be replaced to help protect the
Description sprinkler while the ceiling is being in-
stalled or finished. The tip of the Pro-
The Series RFII Quick Response tective Cap can also be used to mark
(3 mm bulb) & Standard Response (5 the center of the ceiling hole into plas-
mm bulb), 5.6 K-Factor, “Royal Flush ter board, ceiling tiles, etc. by gently
II” Concealed Pendent Sprinklers are pushing the ceiling product against the
decorative sprinklers featuring a flat Protective Cap. When the ceiling in-
cover plate designed to conceal the stallation is complete the Protective
sprinkler. It is the best choice for archi- Cap is removed and the Cover Plate
tecturally sensitive areas such as hotel Assembly installed.
lobbies, office buildings, churches, As an option, the Series RFII Standard
and restaurants. Response (5 mm bulb) “Royal Flush II”
Each unit includes a Cover Plate As- Concealed Pendent Sprinklers may be
sembly that conceals the sprinkler op- fitted with a silicone Air and Dust Seal UL, C-UL, and NYC. Maximum 175
erating components above the ceiling. (Ref. Fig. 5). The Air and Dust Seal is psi (12,1 bar) by FM.
The separable two-piece design of the intended for sensitive areas where it is
Cover Plate and Support Cup Assem-
blies allows installation of the sprin-
desirable to stop air and dust travel
through the cover plate from the area Technical
klers and pressure testing of the fire
protection system prior to installation
above the ceiling.
WARNINGS
Data
of a suspended ceiling or application
of the finish coating to a fixed ceiling. The Series RFII Concealed Pendent Approvals for Series RFII
They also permit removal of sus- Sprinklers described herein must be UL and C-UL Listed. FM Approved.
pended ceiling panels for access to installed and maintained in compli- NYC under MEA 353-01-E. LPCB (Ref.
building service equipment without ance with this document, as well as No. 094a/09 for TY3551 & 094a/10 for
having to first shut down the fire pro- with the applicable standards of the TY3531) Approved.
tection system and remove sprinklers. National Fire Protection Association, The approvals apply only to the serv-
in addition to the standards of any ice conditions indicated in the Design
Also, the separable two-piece design other authorities having jurisdiction.
of the the Sprinkler provides for 1/2 Criteria section and maximum pres-
Failure to do so may impair the per- sure ratings indicated in the
inch (12,7 mm) of vertical adjustment, formance of these devices.
to reduce the accuracy to which the Model/Sprinkler Identification Num-
length of fixed pipe drops to the sprin- The owner is responsible for maintain- bers section.
klers must be cut. ing their fire protection system and de- Approvals for Air & Dust Seal
vices in proper operating condition. (Part #10908100)
The Series RFII Sprinklers are The installing contractor or sprinkler
shipped with a Disposable Protective UL and C-UL Listed for use with the
manufacturer should be contacted RFII (TY3551 & TY3504) Standard Re-
with any questions. sponse Concealed Sprinkler.
IMPORTANT Temperature Ratings
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
Model/Sprinkler 155F/68C Sprinkler - 135F/57C Plate
200F/93C Sprinkler - 165F/74C Plate
WARNING” that provides cautions
with respect to handling and instal-
Identification Discharge Coefficient
K = 5.6 GPM/psi1/2 (80,6 LPM/bar1/2)
lation of sprinkler systems and com-
ponents. Improper handling and in-
Numbers Adjustment
1/2 inch (12,7 mm)
stallation can permanently damage TY3551 (5mm bulb) & TY3531 (3 mm
bulb): maximum 175 psi (12,1 bar) by Finishes
a sprinkler system or its compo- Cover Plate: Chrome Plated, Brass
nents and cause the sprinkler to fail UL, C-UL, FM, LPCB and NYC.
TY3504 (5 mm bulb) & TY3505 (3 mm Plated, or White Painted (Custom paint
to operate in a fire situation or cause matches and colors other than white
it to operate prematurely. bulb): maximum 250 psi (17,3 bar) by
are available on request.)

Page 1 of 4 JULY, 2004 TFP181


Page 2 of 4 TFP181

Physical Characteristics 1/2" NPT SEALING


Frame . . . . . . . . . . . . . Bronze ASSEMBLY
Support Cup . Chrome Plated Steel
Guide Pins . . . . . . Stainless Steel
FRAME
Deflector . . . . . . . . . . . Bronze CAP
Compression Screw . . . . . . Brass
Bulb . . . . . . . . . . . . . . . Glass
Cap . . . . . . . . Bronze or Copper SUPPORT
Sealing Assembly . . . . . . . . . . CUP WITH BULB
. . . . . Beryllium Nickel w/Teflon* ROLL FORMED
THREADS
Cover Plate . . . . . . . . . . . Brass
Retainer . . . . . . . . . . . . Brass COMPRESSION
Ejection Spring . . . . Stainless Steel SCREW
GUIDE
Patents PINS (2)
U.S.A. 4,014,388
DEFLECTOR
(DROPPED

Operation DEFLECTOR POSITION)

When exposed to heat from a fire, the SPRINKLER/SUPPORT CUP


Cover Plate, which is normally sol- ASSEMBLY
dered to the Retainer at three points,
THREAD INTO RETAINER
falls away to expose the Sprinkler As- SUPPORT CUP WITH THREAD
sembly. At this point the Deflector sup- UNTIL MOUNTING DIMPLES
ported by the Guide Pins drops down SURFACE IS
to its operational position. FLUSH WITH EJECTION
CEILING SPRING
The glass Bulb contains a fluid that
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass Bulb, activating the sprinkler and
allowing water to flow. SOLDER COVER
TABS (3) COVER PLATE/RETAINER PLATE
ASSEMBLY
Design FIGURE 1
SERIES RFII CONCEALED SPRINKLER
Criteria ASSEMBLY
The RFII (TY3551 & TY3504), 5 mm
Bulb Type, Concealed Pendent Sprin- Step 1. The sprinkler must only be
klers are UL and C-UL Listed as stand-
ard response - standard spray sprin-
Installation installed in the pendent position and
with the centerline of the sprinkler per-
klers for use in accordance with the The Series RFII must be installed in pendicular to the mounting surface.
current NFPA standard. They are FM accordance with the following instruc- Step 2. Remove the Protective Cap.
Approved as standard response - tions:
standard spray sprinklers for use in Step 3. With pipe thread sealant ap-
accordance with the current FM Loss NOTES plied to the pipe threads, hand tighten
Prevention Data Sheets. Do not install any bulb type sprinkler if the sprinkler into the sprinkler fitting.
the bulb is cracked or there is a loss of Step 4. Wrench tighten the sprinkler
The RFII (TY3531 & TY3505) 3 mm liquid from the bulb. With the sprinkler
Bulb Type, Concealed Pendent Sprin- using only the RFII Sprinkler Wrench
held horizontally, a small air bubble (Ref. Figure 3). The RFII Sprinkler
klers are UL and C-UL Listed as quick should be present. The diameter of the
response - standard spray sprinklers Wrench is to be applied to the Sprin-
air bubble is approximately 1/16 inch kler as shown in Figure 3.
for use in accordance with the current (1,6 mm) for the 155°F/68°C and 3/32
NFPA standard. They are FM Ap- inch (2,4 mm) for the 200°F/93°C tem- Step 5. Replace the Protective Cap
proved as standard response - stand- perature ratings. (Ref. Figure 4) by pushing it upwards
ard spray sprinklers for use in accord- until it bottoms out against the Support
ance with the current FM Loss A leak tight 1/2 inch NPT sprinkler joint Cup. The Protective Cap helps prevent
Prevention Data Sheets. should be obtained with a torque of 7 damage to the Deflector and Arms dur-
to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi- ing ceiling installation and/or during
The Series RFII Concealed Pendent mum of 21 ft.lbs. (28,5 Nm) of torque
Sprinklers are only listed and ap- application of the finish coating of the
is to be used to install sprinklers. ceiling. It may also be used to locate
proved with the Series RFII Concealed Higher levels of torque may distort the
Cover Plates having a metallic or white the center of the clearance hole by
sprinkler inlet with consequent leak- gently pushing the ceiling material up
painted finish. age or impairment of the sprinkler. against the center point of the Protec-
The Series RFII must not be used in Do not attempt to compensate for in- tive Cap.
applications where the air pressure sufficient adjustment in the Sprinkler
above the ceiling is greater than that Assembly by under- or over-tightening NOTE
below. Down drafts through the Sup- the Sprinkler/Support Cup Assembly. As long as the Protective Cap remains
port Cup could delay sprinkler opera- Readjust the position of the sprinkler in place, the system is considered to
tion in a fire situation. fitting to suit. be “Out of Service”.

* Registered Trademark of DuPont


TFP181 Page 3 of 4

FACE OF CLEARANCE HOLE CLEARANCE


SPRINKLER DIAMETER HOLE
FITTING DIMENSION C

SPRINKLER
SUPPORT CUP
ASSEMBLY

1/2" (12,7 mm)


THREADED
D ADJUSTMENT

FACE OF CEILING,
RETAINING RING FIGURE 4
MOUNTING DISPOSABLE PROTECTIVE CAP
SURFACE

Step 6. After the ceiling has been com-


pleted with the 2-1/2 inch (63,5 mm)
diameter clearance hole and in prepa-
ration for installing the Cover Plate As-
sembly, remove and discard the Pro-
tective Cap, and verify that the
3/16" to 11/16" MANUFACTURER DEFLECTOR COVER PLATE Deflector moves up and down freely. If
(4,8 to 17,5 mm) PRESET GAP IN DROPPED RETAINER the Sprinkler has been damaged and
REFERENCE 3/32" (2,4 mm) POSITION ASSEMBLY the Deflector does not move up and
down freely, replace the entire Sprin-
COVER PLATE COVER PLATE kler assembly. Do not attempt to mod-
PROFILE DEPTH DIAMETER ify or repair a damaged sprinkler.
DIMENSION B DIMENSION A Step 7. When installing an Air and
Dust Seal, refer to Figure 5, otherwise
proceed to Step 8. To attach the Air and
A: 3-1/4" (82,6 mm) C: 2-3/8" to 2-5/8" (60,3 to 66,7 mm) Dust Seal, verify the angle of the out-
B: 3/16" (4,8 mm) D: 1-3/4" to 2-1/4" (44,5 to 57,2 mm) side edge of the seal is oriented ac-
cording to Figure 5. Start the edge of
the Retainer in the grooved slot of the
FIGURE 2 Air and Dust Seal and continue around
SERIES RFII CONCEALED SPRINKLER the retainer until the entire Air and
INSTALLATION DIMENSIONS Dust Seal is engaged.
NOTE
The Air and Dust Seal is only to be
installed on the periphery of the Re-
tainer.
FRAME
ARM
Step 8. Screw on the Cover Plate/Re-
tainer Assembly until the Retainer -
Figure 2 (or Air and Dust Seal - Figure
SUPPORT 5) contacts with the ceiling. Do not
CUP continue to screw on the Cover
Plate/Retainer Assembly such that it
lifts a ceiling panel out of its normal
position. If the Cover Plate/Retainer
Assembly cannot be engaged with the
Support Cup or the Cover Plate/Re-
7/8" (23 mm) tainer Assembly cannot be engaged
SQUARE sufficiently to contact the ceiling, the
Sprinkler Fitting must be repositioned.
ALIGN
ARROWS WITH
FRAME ARMS
Care and
Maintenance
ACCEPTS The Series RFII must be maintained
1/2" SOCKET and serviced in accordance with the
DRIVE following instructions:
NOTES
FIGURE 3 Absence of the Cover Plate Assembly
RFII SPRINKLER WRENCH may delay sprinkler operation in a fire
situation.
Page 4 of 4 TFP181

When properly installed, there is a SUPPORT SPRINKLER FACE OF ORIENT


nominal 3/32 inch (2,4 mm) air gap CUP CEILING SEAL
between the lip of the Cover Plate and BEVEL AS
the ceiling, as shown in Figure 2. This SHOWN
COVER
air gap is necessary for proper opera- PLATE
tion of the sprinkler. If the ceiling is to RETAINER
be repainted after the installation of ASSEMBLY
the Sprinkler, care must be exercised
to ensure that the new paint does NOT
seal off any of the air gap. CLEAN
ROOM
Factory painted Cover Plates MUST SEAL
LIP OF COVER
NOT be repainted. They should be re- RETAINER PLATE
placed, if necessary, by factory
painted units. FIGURE 5
Do not pull the Cover Plate relative to OPTIONAL AIR AND DUST SEAL FOR SERIES RFII (TY3551 & TY3504)
the Enclosure. Separation may result.
Before closing a fire protection system Inspection Service in accordance with DAMAGES, AND IN NO EVENT
main control valve for maintenance local requirements and/or national SHALL TYCO FIRE PRODUCTS’ LI-
work on the fire protection system that codes. ABILITY EXCEED AN AMOUNT
it controls, permission to shut down the EQUAL TO THE SALES PRICE.
affected fire protection system must be
obtained from the proper authorities
and all personnel who may be affected
Limited THE FOREGOING WARRANTY IS
MADE IN LIEU OF ANY AND ALL
by this action must be notified. Warranty OTHER WARRANTIES EXPRESS OR
IMPLIED, INCLUDING WARRANTIES
Sprinklers that are found to be leaking OF MERCHANTABILITY AND FIT-
or exhibiting visible signs of corrosion Products manufactured by Tyco Fire
Products are warranted solely to the NESS FOR A PARTICULAR PUR-
must be replaced. POSE.
original Buyer for ten (10) years
Automatic sprinklers must never be against defects in material and work-
painted, plated, coated or otherwise
altered after leaving the factory. Modi-
manship when paid for and properly
installed and maintained under normal
Ordering
fied sprinklers must be replaced.
Sprinklers that have been exposed to
use and service. This warranty will ex-
pire ten (10) years from date of ship-
Procedure
corrosive products of combustion, but ment by Tyco Fire Products. No war-
have not operated, should be replaced When placing an order, indicate the full
ranty is given for products or product name. Contact your local dis-
if they cannot be completely cleaned components manufactured by compa-
by wiping the sprinkler with a cloth or tributor for availability.
nies not affiliated by ownership with
by brushing it with a soft bristle brush. Sprinkler Assembly:
Tyco Fire Products or for products and
Care must be exercised to avoid dam- Specify: (SIN), (specify temperature
components which have been subject
age to the sprinklers - before, during, rating) Series RFII Concealed Pen-
to misuse, improper installation, corro-
and after installation. Sprinklers dam- dent Sprinkler, P/N (specify).
sion, or which have not been installed,
aged by dropping, striking, wrench maintained, modified or repaired in ac- 155F/68C 200F/93C
twist/slippage, or the like, must be re- cordance with applicable Standards of TY3551 51-790-1-155 51-790-1-200
placed. Also, replace any sprinkler that the National Fire Protection Associa- TY3504 51-796-1-155 51-796-1-200
has a cracked bulb or that has lost tion, and/or the standards of any other TY3531 51-792-1-155 51-792-1-200
liquid from its bulb. (Ref. Installation TY3505 51-797-1-155 51-797-1-200
Authorities Having Jurisdiction. Mate-
Section). rials found by Tyco Fire Products to be
If a sprinkler must be removed, do not defective shall be either repaired or Separately Ordered Cover Plate:
reinstall it or a replacement without replaced, at Tyco Fire Products’ sole Specify: (specify temperature rating)
reinstalling the Cover Plate Assembly. option. Tyco Fire Products neither as- Series RFII Concealed Cover Plate
If a Cover Plate Assembly becomes sumes, nor authorizes any person to with (specify finish), P/N (specify).
dislodged during service, replace it im- assume for it, any other obligation in
135F/57C(a) 165F/74C*(b)
mediately. connection with the sale of products or Brass 56-792-1-135 56-792-1-165
parts of products. Tyco Fire Products Bright Brass 56-792-2-135 56-792-2-165
The owner is responsible for the in- shall not be responsible for sprinkler Chrome 56-792-9-135 56-792-9-165
spection, testing, and maintenance of system design errors or inaccurate or Brushed Chrome 56-792-8-135 56-792-8-165
White 56-792-0-135 56-792-0-165
their fire protection system and de- incomplete information supplied by White (RAL9010)* 56-792-3-135 56-792-3-165
vices in compliance with this docu- Buyer or Buyer’s representatives. Bright White 56-792-4-135 56-792-4-165
ment, as well as with the applicable Off White 56-792-5-135 56-792-5-165
IN NO EVENT SHALL TYCO FIRE Black 56-792-6-135 56-792-6-165
standards of the National Fire Protec- PRODUCTS BE LIABLE, IN CON- Custom 56-792-X-135 56-792-X-165
tion Association (e.g., NFPA 25), in TRACT, TORT, STRICT LIABILITY OR (a) For use with 155F/68C sprinklers.
addition to the standards of any other UNDER ANY OTHER LEGAL THE- (b) For use with 200F/93C sprinklers.
authorities having jurisdiction. The in- ORY, FOR INCIDENTAL, INDIRECT, * Eastern Hemisphere sales only.
stalling contractor or sprinkler manu- SPECIAL OR CONSEQUENTIAL
facturer should be contacted relative to DAMAGES, INCLUDING BUT NOT Sprinkler Wrench:
any questions. LIMITED TO LABOR CHARGES, RE- Specify: RFII Sprinkler Wrench,
It is recommended that automatic GARDLESS OF WHETHER TYCO P/N 56-000-1-075.
sprinkler systems be inspected, FIRE PRODUCTS WAS INFORMED Air and Dust Seal:
tested, and maintained by a qualified ABOUT THE POSSIBILITY OF SUCH Specify: Air and Dust Seal,
P/N 56-908-1-001.