Contacts

Series TY-B — 5.6 and 8.0 K-factor


Upright and Pendent Intermediate Level Sprinklers
Standard Response
General rosive atmospheres. Consequently,
it is recommended that the end user
Description be consulted with respect to the suit-
ability of these coatings for any given
The Series TY-B, 5.6 and 8.0 K-fac- corrosive environment. The effects of
tor Upright and Pendent Intermediate ambient temperature, concentration of
Level Sprinklers described in this data chemicals, and gas/chemical velocity,
sheet are automatic sprinklers of the should be considered, as a minimum,
“standard response” 5 mm frangible along with the corrosive nature of the
bulb type. They are “standard spray” chemical to which the sprinklers will be
sprinklers intended for use in fire sprin- exposed.
kler systems designed in accordance
with the standard installation rules NOTICE
recognized by the applicable Listing The Series TY-B Sprinklers described
or Approval agency for example, UL herein must be installed and main-
Listing is based on NFPA requirements. tained in compliance with this docu-
Both the Pendent and Upright Sprin- ment, as well as with the applicable
klers produce a hemispherical water standards of the National Fire Protec-
distribution pattern below the deflector. tion Association, in addition to the stan-
Intermediate Level Sprinklers are pri- dards of any other authorities having
marily designed for use in rack storage jurisdiction. Failure to do so may impair
sprinkler systems where their thermally the performance of these devices.
sensitive elements must be shielded The owner is responsible for maintain-
from the water spray of higher ele- ing their fire protection system and
vation sprinklers that could operate devices in proper operating condition.
earlier during a fire. Intermediate Level The installing contractor or sprinkler
Sprinklers are also used in other appli- manufacturer should be contacted with
cations such as beneath open gridded any questions.
catwalks.
Corrosion resistant coatings, where
applicable, are utilized to extend the life
Sprinkler
of copper alloy sprinklers beyond that
which would otherwise be obtained
Identification
when exposed to corrosive atmo-
spheres. Although corrosion resistant
Numbers Temperature Ratings
See Table A
coated sprinklers have passed the TY3153 ����� Upright 5.6K, 1/2 in. NPT
standard corrosion tests of the appli- TY3251 ����Pendent 5.6K, 1/2 in. NPT Finishes
cable approval agencies, the testing is TY4153 ����� Upright 8.0K, 3/4 in. NPT Sprinkler: See Table A
not representative of all possible cor- TY4251 ����Pendent 8.0K, 3/4 in. NPT Physical Characteristics
Frame �������������������������������������������������������Bronze

IMPORTANT
Technical Button ������������������������������������������� Brass/Copper
Sealing Assembly ��������������������������������� Beryllium
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
Data Nickel w/TEFLON
Bulb ������������������������������������������������������������� Glass
Compression Screw ���������������������������������Bronze
regulatory and health information. Approvals Deflector �������������������������������������������������� Copper
UL and C-UL Listed Shield �����������������������������������������������Plated Steel
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER FM and NYC Approved
WARNING” that provides cautions (See Table A for complete approval informa-
with respect to handling and instal- tion including corrosion resistant status.)
lation of sprinkler systems and com- Maximum Working Pressure
ponents. Improper handling and 175 psi (12,1 bar)
installation can permanently damage
a sprinkler system or its compo- Discharge Coefficient
nents and cause the sprinkler to fail K = 5.6 gpm/psi½ (80,6 Lpm/bar½)
to operate in a fire situation or cause K = 8.0 gpm/psi½ (115,2 Lpm/bar½)
it to operate prematurely.

Page 1 of 6 MAY 2020 TFP351


TFP351
Page 2 of 6

* Temperature rating is indicated on deflector, ** Pipe thread connections per ISO 7-1 can be
shield, or adjacent to orifice seat on frame. provided on special request.

3-1/2" (88,9 mm) DIA, 1/2" ** 7/16" (11,1 mm)


NPT NOMINAL MAKE-IN
SHIELD
SCREW O-RING

7/16" UPRIGHT
(11,1 mm) SHIELD * 2-3/16"
2-3/8"
NOMINAL WRENCH MODEL S2 (55,6 mm)
(60,3 mm)
MAKE-IN FLATS SHIELD
WRENCH
FLATS

1/2" ** 3-1/2" (88,9 mm) DIA,


NPT
UPRIGHT PENDENT
(FACTORY ASSEMBLED) (FIELD ASSEMBLED - SEE INSTALLATION SECTION)
FIGURE 1
SERIES TY-B UPRIGHT (TY3153) AND PENDENT (TY3251) SPRINKLERS
STANDARD RESPONSE INTERMEDIATE LEVEL SPRINKLERS,
5.6 K-FACTOR, 1/2 IN. NPT

* Temperature rating is indicated on deflector, ** Pipe thread connections per ISO 7-1 can be
shield, or adjacent to orifice seat on frame. provided on special request.

3-1/2" (88,9 mm) DIA, 3/4" ** 1/2" (12,7 mm)


NPT NOMINAL MAKE-IN
SHIELD
SCREW O-RING

1/2" UPRIGHT 2-5/16"


2-7/16" (12,7 mm) SHIELD *
WRENCH (58,7 mm)
(61,9 mm) NOMINAL MODEL S2
MAKE-IN FLATS SHIELD
WRENCH
FLATS

3/4" ** 3-1/2" (88,9 mm) DIA,


NPT
UPRIGHT PENDENT
(FACTORY ASSEMBLED) (FIELD ASSEMBLED - SEE INSTALLATION SECTION)
FIGURE 2
SERIES TY-B UPRIGHT (TY4153) AND PENDENT (TY4251) SPRINKLERS
STANDARD RESPONSE INTERMEDIATE LEVEL SPRINKLERS,
8.0 K-FACTOR, 3/4 IN. NPT
TFP351
Page 3 of 6

Sprinkler Finish (See Note 5)


Bulb
K-Factor Type Temperature Wax Over
Liquid Natural Lead Wax Lead
Brass** Coated Coated** Coated**
135°F (57°C) Orange
155°F (68°C) Red
175°F (79°C) Yellow
Upright 1, 2, 3, 4 1, 2, 3, 4 N/A
(TY3153) 200°F (93°C) Green

286°F (141°C) Blue


5.6 360°F (182°C) Mauve
1/2 in. NPT
135°F (57°C) Orange
155°F (68°C) Red
1, 2, 3, 4
Pendent 175°F (79°C) Yellow
1, 2, 3, 4 1**, 2**, 3**, 4**
(TY3251) 200°F (93°C) Green
286°F (141°C) Blue 1*, 2*, 3*, 4*
360°F (182°C) Mauve N/A
135°F (57°C) Orange
155°F (68°C) Red

Upright 175°F (79°C) Yellow


1, 2, 3, 4 1, 2, 3, 4 N/A
(TY4153) 200°F (93°C) Green
286°F (141°C) Blue

8.0 360°F (182°C) Mauve


3/4 in. NPT 135°F (57°C) Orange
155°F (68°C) Red
1, 2, 3, 4
Pendent 175°F (79°C) Yellow
1, 2, 3, 4 1**, 2**, 3**, 4**
(TY4251) 200°F (93°C) Green
286°F (141°C) Blue 1*, 2*, 3*, 4*
360°F (182°C) Mauve N/A
NOTES:
1. UL Listed.
2. C-UL Listed.
3. FM Approved.
4. Approved by the City of New York under MEA 354-01-E.
5. Where Lead Coated, Wax Coated, and Wax over Lead Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as Cor-
rosion Resistant Sprinklers. Where Lead Coated, Wax Coated, and Wax over Lead Coated Sprinklers are noted to be FM Approved, the sprinklers are FM
Approved as Corrosion Resistant Sprinklers.
*150°F (66°C) Maximum Ceiling Temperature.
** With Zinc Plated Shield.
N/A: Not Available

TABLE A
LABORATORY LISTINGS AND APPROVALS

Operation Design
The glass bulb contains a fluid which
expands when exposed to heat. When
Criteria
the rated temperature is reached, the The Series TY-B Pendent and Upright
fluid expands sufficiently to shatter the Intermediate Level Sprinklers are
glass bulb, allowing the sprinkler to intended for fire protection systems
activate and water to flow. designed in accordance with the stan-
dard installation rules recognized by the
applicable Listing or Approval agency
(for example, UL Listing is based on
the requirements of NFPA 13, and FM
Approval is based on the requirements
of FM’s Loss Prevention Data Sheets).
TFP351
Page 4 of 6

Installation Step C. With pipe thread sealant


applied to the pipe threads, hand
The Series TY-B, Upright and Pendent tighten the sprinkler into the sprinkler
Intermediate Level Sprinklers must fitting. WRENCH RECESS
be installed in accordance with this Step D. Tighten the sprinkler into the (END "A" USED FOR
section. sprinkler fitting using only the W-Type 1/2" NPT MODELS)
General Instructions 6 Sprinkler Wrench (see Figure 3). With
Do not install any bulb type sprinkler reference to Figure 1 or 2, the W-Type
if the bulb is cracked or there is a loss 6 Sprinkler Wrench is to be applied to
the wrench flats. WRENCH RECESS
of liquid from the bulb. With the sprin- (END "B" USED FOR
kler held horizontally, a small air bubble Step E. Rotate the S2 Shield clock- 3/4" NPT MODELS)
should be present. The diameter of the wise (looking up) so that it slightly com-
air bubble is approximately 1/16 in. presses the O-Ring between the Shield FIGURE 3
(1,6 mm) for the 135°F (57°C) to 3/32 in. and sprinkler fitting. W-TYPE 6 SPRINKLER
(2,4 mm) for the 360°F (182°C) tempera- WRENCH
ture ratings. Wax Coated Sprinklers
When installing wax coated sprinklers of a wax stick (the end of which is color
A leak tight 1/2 in. NPT sprinkler joint with the adjustable Crescent wrench, coded). Only the correct color coded wax
should be obtained with a torque of additional care needs to be exercised is to be used, and retouching of wrench
7 to 14 b-ft (9,5 to 19,0 N·m). A leak to prevent damage to the wax coating flats and frame arms is only permitted
tight 3/4 in. NPT sprinkler joint should on the sprinkler wrench flats or frame at the time of initial sprinkler installation.
be obtained with a torque of 10 to 20 arms and, consequently, exposure of With the steel rod heated as previously
lb-ft (13,4 to 26,8 N·m). Higher levels bare metal to the corrosive environ- described, touch the rod to the area
of torque may distort the sprinkler inlet ment. The jaws of the wrench should be requiring additional wax with the rod angled
and cause leakage or impairment of the opened sufficiently wide to pass over downward, and then touch the wax stick to
sprinkler. the wrench flats without damaging the the rod approximately one-half inch away
Upright Sprinklers wax coating. Before wrench tightening from the area requiring retouching. The wax
The Series TY-B Intermediate Level the sprinkler, the jaws of the wrench will melt and run down onto the sprinkler.
Upright Sprinklers must be installed are to be adjusted to just contact the
in accordance with the following sprinkler wrenching flanges. After
instructions. wrench tightening the sprinkler, loosen
the wrench jaws before removing the
Step 1. With pipe thread sealant wrench.
applied to the pipe threads, hand
tighten the sprinkler into the sprinkler After installation, the sprinkler
fitting. wrench flats and frame arms must
be inspected and the wax coating
Step 2. Tighten the sprinkler into the retouched (repaired) whenever the
sprinkler fitting using only the W-Type coating has been damaged and bare
6 Sprinkler Wrench (see Figure 3), metal is exposed. The wax coating on
except that an 8 in. or 10 in. adjust- the wrench flats can be retouched by
able Crescent wrench is to be used for gently applying a heated 1/8 in. diam-
wax coated sprinklers. With reference eter steel rod to the areas of wax that
to Figure 1 or 2, the W-Type 6 Sprin- have been damaged, to smooth it
kler Wrench or the Crescent wrench, back over areas where bare metal is
as applicable, is to be applied to the exposed.
wrench flats.
Notes:
Pendent Sprinklers Only retouching of the wax coating applied
The Series TY-B Intermediate Level to the wrench flats and frame arms is
Pendent Sprinklers must be installed permitted, and the retouching is to be
in accordance with the following performed only at the time of the initial
instructions. sprinkler installation.
Step A. Thread the S2 Shield onto the The steel rod should be heated only to
sprinkler threads with the stamped the point at which it can begin to melt the
markings toward the deflector and wax, and appropriate precautions need
just to the end of the threads. The final to be taken, when handling the heated
assembly step is easier to accom- rod, in order to prevent the installer from
plish if the Shield is not disengaged by being burned.
continuing to turn the Shield past the If attempts to retouch the wax coating
threads. with complete coverage are unsuccessful,
Step B. Roll the O-Ring over the sprin- additional wax can be ordered in the form
kler threads until it seats against the
Shield.
TFP351
Page 5 of 6

Care and Limited Ordering


Maintenance Warranty Procedure
The Series TY-B, Upright and Pendent For warranty terms and conditions, visit Contact your local distributor for avail-
Intermediate Level Sprinklers must be www.tyco-fire.com. ability. When placing an order, indi-
maintained and serviced in accordance cate the full product name and Part
with this section. Numbers (P/N).
Before closing a fire protection system Upright Sprinkler Assemblies with
main control valve for maintenance Shield and NPT Thread
work on the fire protection system that Connections
it controls, permission to shut down the Specify: Series TY-B (specify SIN),
affected fire protection system must be (specify K-factor), Upright Intermedi-
obtained from the proper authorities ate Level Sprinkler Standard Response,
and all personnel who may be affected (specify) temperature rating, with
by this action must be notified. (specify finish or coating), P/N (specify
Sprinklers that are found to be leaking from Table B)
or exhibiting visible signs of corrosion Pendent Sprinkler Assemblies with
must be replaced. (Shield Ordered Separately) and
Automatic sprinklers must never be NPT Thread Connections
painted, plated, coated or other- Specify: Series TY-B (Specify SIN),
wise altered after leaving the factory. (specify K-factor), Pendent Sprinkler
Modified sprinklers must be replaced. Standard Response, (specify) tem-
Sprinklers that have been exposed to perature rating, with (specify finish or
corrosive products of combustion, but coating), P/N (specify from Table C)
have not operated, should be replaced Model S2 Pendent Shield & O-Ring
if they cannot be completely cleaned Specify: S2 Pendent Shield & O-Ring
by wiping the sprinkler with a cloth or for use with (specify 1/2 in. NPT or 3/4
by brushing it with a soft bristle brush. in. NPT) Series TY-B Pendent Sprin-
Care must be exercised to avoid klers, P/N (specify):
damage to the sprinklers before, 1/2 in. NPT S2 Pendent
during, and after installation. Sprin- Shield & O-Ring . . . . . . . . . . P/N 56-070-9-332
klers damaged by dropping, strik- 3/4 in. NPT S2 Pendent
ing, wrench twist/slippage, or the like, Shield & O-Ring . . . . . . . . . . P/N 56-070-9-342
must be replaced. Replace any sprin-
kler that has a cracked bulb or that has Sprinkler Wrench
lost liquid from its bulb, see the Instal- Specify: W-Type 6 Sprinkler Wrench,
lation Section. P/N 56-000-6-387
The owner is responsible for the Wax Sticks
inspection, testing, and maintenance of (for retouching wrench damaged
their fire protection system and devices wax coating)
in compliance with this document, as Specify: (Specify color) color coded
well as with the applicable standards Wax Stick for retouching (specify)
of the National Fire Protection Asso- temperature rating temperature rated
ciation, such as NFPA 25, in addition Series TY-B Sprinklers, P/N (specify):
to the standards of any other authori- Black for 135°F (57°C) ������������� P/N 56-065-1-135
ties having jurisdiction. The installing Red for 155°F (68°C) ��������������� P/N 56-065-1-155
contractor or sprinkler manufacturer Yellow for 175°F (79°C) ����������� P/N 56-065-1-175
should be contacted relative to any Blue for 200°F (93°C)
and 286°F (141°C) . . . . . . . . . . P/N 56-065-1-286
questions.
It is recommended that automatic Notes:
sprinkler systems be inspected, tested, Each wax stick is suitable for retouching
and maintained by a qualified Inspec- up to twenty-five sprinklers.
tion Service in accordance with local The wax used for 286°F (141°C) sprinklers
requirements and/or national code. is the same as for 200°F (93°C) sprinklers,
and, therefore, the 286°F (141°C) sprinkler
is limited to the same maximum ceiling
temperature as the 200°F (93°C) sprinkler,
which is 150°F (66°C).
TFP351
Page 6 of 6

P/N 57 – XXX – X – XXX

TEMPERATURE
SIN SPRINKLER
RATING

533 5.6K UPRIGHT (1/2 in. NPT) TY3153 1 NATURAL BRASS 135 135°F (57°C)

543 8.0K UPRIGHT (3/4 in. NPT) TY4153 7 LEAD COATED 155 155°F (68°C)

175 175°F (79°C)

200 200°F (93°C)

286 286°F (141°C)

360 360°F (182°C)

TABLE B
SERIES TY-B UPRIGHT INTERMEDIATE LEVEL SPRINKLERS
PART NUMBER SELECTION
(Upright Shield Included With Sprinkler)

P/N 57 – XXX – X – XXX

TEMPERATURE
SIN SPRINKLER
RATING

571 5.6K PENDENT (1/2 in. NPT) TY3251 1 NATURAL BRASS 135 135°F (57°C)

WAX COATED
591 8.0K PENDENT (3/4 in. NPT) TY4251 6 155 155°F (68°C)
286°F (141°C) MAXIMUM

7 LEAD COATED 175 175°F (79°C)

WAX OVER LEAD


8 200 200°F (93°C)
286°F (141°C) MAXIMUM

286 286°F (141°C)

360 360°F (182°C)

TABLE C
SERIES TY-B PENDENT SPRINKLERS
PART NUMBER SELECTION
(Model S2 Pendent Shield & O-Ring Must Be Separately Ordered)

1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700


© 2020 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.

NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;
TEFLON is a registered trademark of DuPont