Professional Documents
Culture Documents
www.tyco-fire.com
Contacts
1/2" NPT
2-11/16" FACTORY
(68,3 mm) ASSEMBLED
UPRIGHT 7/16"
7/16" SHIELD MODEL S5 (11,1 mm)
(11,1 mm)
PENDENT NOMINAL
NOMINAL
WRENCH SHIELD MAKE-IN
MAKE-IN
FLANGES WITH 2-5/8"
O-RINGS (66,7 mm)
WRENCH
AREA
UPRIGHT PENDENT
(FACTORY ASSEMBLED) (FIELD ASSEMBLED - SEE INSTALLATION SECTION)
FIGURE 1
STANDARD RESPONSE SERIES TY-L UPRIGHT (TY3113) AND PENDENT (TY3211) SPRINKLERS
INTERMEDIATE LEVEL SPRINKLERS, 5.6 K-FACTOR, 1/2 INCH NPT
3/4" NPT
2-3/4" FACTORY
(69,9 mm) ASSEMBLED
UPRIGHT 1/2"
1/2" SHIELD (12,7 mm)
(12,7 mm) MODEL S5
PENDENT NOMINAL
NOMINAL MAKE-IN
MAKE-IN WRENCH SHIELD
FLANGES WITH 2-11/16"
O-RINGS (68,3 mm)
WRENCH
AREA
UPRIGHT PENDENT
(FACTORY ASSEMBLED) (FIELD ASSEMBLED - SEE INSTALLATION SECTION)
FIGURE 2
STANDARD RESPONSE SERIES TY-L UPRIGHT (TY4113) AND PENDENT (TY4211) SPRINKLERS
INTERMEDIATE LEVEL SPRINKLERS, 8.0 K-FACTOR, 3/4 INCH NPT
SPRINKLER FINISH
Operation Installation
A copper tube sealed by two stainless The Series TY-L Sprinklers must
WRENCH
steel balls holds a fusible alloy. When be installed in accordance with this RECESS
the rated temperature is reached, the section.
alloy melts, the balls are forced toward NOTE: A leak-tight 1/2 inch NPT sprin-
each other releasing the tension mech- kler joint should be obtained by apply-
anism, allowing the sprinkler to operate. ing a minimum-to-maximum torque
of 7 to 14 ft.-lbs. (9,5 to 19,0 Nm). A
Design leak tight 3/4 inch NPT sprinkler joint
should be obtained by applying a min- FIGURE 3
Criteria imum-to-maximum torque of 10 to 20 W-TYPE 9 SPRINKLER
ft.-lbs. (13,4 to 26,8 Nm). Higher levels WRENCH
The Series TY-L Pendent and Upright of torque may distort the sprinkler inlet
Intermediate Level Sprinklers are and cause leakage or impairment of the
intended for fire protection systems
designed in accordance with the stan-
dard installation rules recognized by
sprinkler.
Upright Sprinklers
Care and
the applicable Listing or Approval
agency (e.g., UL Listing is based on
The Series TY-L Intermediate Level
Upright Sprinklers must be installed
Maintenance
the requirements of NFPA 13, and FM in accordance with the following The Series TY-L Sprinklers must be
Approval is based on the requirements instructions. maintained and serviced in accordance
of FM Global’s Loss Prevention Data with this section.
Step 1. With pipe thread sealant
Sheets). applied to the pipe threads, hand Before closing a fire protection system
tighten the sprinkler into the sprinkler main control valve for maintenance
fitting. work on the fire protection system that
it controls, permission to shut down the
Step 2. Tighten the sprinkler into the affected fire protection system must be
sprinkler fitting using only the W-Type obtained from the proper authorities
9 Sprinkler Wrench (Ref. Figure 3). With and all personnel who may be affected
reference to Figure 1 or 2, the W-Type by this action must be notified.
9 Sprinkler Wrench is to be applied to
the wrenching area. Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
Pendent Sprinklers must be replaced.
The Series TY-L Intermediate Level
Pendent Sprinklers must be installed Automatic sprinklers must never be
in accordance with the following painted, plated, coated or otherwise
instructions. altered after leaving the factory. Modi-
fied or over-heated sprinklers must be
Step 1. Roll one of the two required replaced.
O-Rings over the sprinkler threads until
it seats against the sprinkler wrenching Care must be exercised to avoid
area flange as shown in Figure 1 or 2, damage to the sprinklers before,
as applicable. during, and after installation. Sprin-
klers damaged by dropping, striking,
Step 2. Install the Shield over the sprin- wrench twist/slippage, or the like, must
kler threads, and then roll the second be replaced.
O-Ring over the sprinkler threads until
it is seated firmly against the Shield. The owner is responsible for the
inspection, testing, and maintenance of
Step 3. With pipe thread sealant their fire protection system and devices
applied, hand tighten the sprinkler into in compliance with this document, as
the sprinkler fitting. well as with the applicable standards
Step 4. Tighten the sprinkler into the of the National Fire Protection Asso-
sprinkler fitting using only the W-Type ciation (e.g., NFPA 25), in addition to
9 Sprinkler Wrench (Ref. Figure 3). The the standards of any other authorities
wrench is to be applied to the sprinkler having jurisdiction. Contact the install-
wrenching area shown in Figure 1 or 2, ing contractor or product manufacturer
as applicable. with any questions.
When installed correctly, the O-Rings It is recommended that automatic
will be slightly compressed and the sprinkler systems be inspected, tested,
Shield will be held firmly in place. and maintained by a qualified Inspec-
tion Service in accordance with local
requirements and/or national codes.
TFP350
Page 4 of 4
SIN TEMPERATURE
SPRINKLER RATING
253 5.6K UPRIGHT (1/2” NPT) TY3113 1 NATURAL BRASS 165 165°F (74°C)
TABLE B
PART NUMBER SELECTION
SERIES TY-L UPRIGHT INTERMEDIATE LEVEL SPRINKLERS
(UPRIGHT SHIELD INCLUDED WITH SPRINKLER)
SIN TEMPERATURE
SPRINKLER RATING
112 5.6K PENDENT (1/2” NPT) TY3211 1 NATURAL BRASS 165 165°F (74°C)
TABLE C
PART NUMBER SELECTION
SERIES TY-L PENDENT SPRINKLERS
(MODEL S5 PENDENT SHIELD & O-RING MUST BE SEPARATELY ORDERED)