Worldwide

www.tyco-fire.com
Contacts

RAPID RESPONSE Series LFII Residential Sprinklers


4.4 K-factor Horizontal Sidewall
Wet Pipe Systems
General adjustment provided by the Recessed
Escutcheon reduces the accuracy to
Description which the pipe nipples to the sprinklers
must be cut.
The TYCO RAPID RESPONSE Series The Series LFII Residential Sprinklers
LFII Residential Horizontal Sidewall has been designed with heat sensitivity
Sprinklers (TY2334) are decorative, and water distribution characteristics
fast response, frangible bulb sprinklers proven to help in the control of residen-
designed for use in residential occu- tial fires and to improve the chance for
pancies such as homes, apartments, occupants to escape or be evacuated.
dormitories, and hotels. When aesthet-
Corrosion-resistant coatings, where
ics and optimized flow characteristics
applicable, are utilized to extend the life
are the major consideration, the Series
of copper alloy sprinklers beyond that
LFII Residential Sprinklers (TY2334)
which would otherwise be obtained
should be the first choice.
when exposed to corrosive atmo-
The Series LFII Residential Sprinklers spheres. Although corrosion-resistant
are intended for use in the following coated sprinklers have passed the
scenarios: standard corrosion tests of the appli-
• wet pipe residential sprinkler sys- cable Approval agencies, the testing is
tems for one-and two-family dwell- not representative of all possible cor-
ings and mobile homes per NFPA rosive atmospheres. Consequently,
13D it is recommended that the end user
be consulted with respect to the suit-
• wet pipe residential sprinkler sys- ability of these coatings for any given
tems for residential occupancies up corrosive environment. The effects of
to and including four stories in height ambient temperature, concentration of
per NFPA 13R chemicals, and gas/chemical velocity
• wet pipe sprinkler systems for the should be considered, as a minimum,
residential portions of any occu- along with the corrosive nature of the
pancy per NFPA 13 chemical to which the sprinklers will be
exposed.
The recessed version of the Series
LFII Residential Sprinklers is intended NOTICE
for use in areas with finished walls.
It employs a two-piece Style 20 The Series LFII Residential Horizontal
Recessed Escutcheon. The Recessed Sidewall Sprinklers (TY2334) described
Escutcheon provides 1/4 in. (6,4 mm) herein must be installed and main-
of recessed adjustment or up to 1/2 in. tained in compliance with this docu-
(12,7 mm) of total adjustment from the ment and with the applicable standards
flush mounting surface position. The of the NATIONAL FIRE PROTECTION
ASSOCIATION (NFPA), in addition to
the standards of any authorities having Sprinkler
IMPORTANT
Refer to Technical Data Sheet
jurisdiction. Failure to do so may impair
the performance of these devices. Identification
TFP2300 for warnings pertaining to
regulatory and health information. The owner is responsible for main-
taining their fire protection system
Number (SIN)
Always refer to Technical Data and devices in proper operating con- TY2334
Sheet TFP700 for the “INSTALLER dition. Contact the installing contrac-
WARNING” that provides cautions tor or product manufacturer with any
with respect to handling and instal- questions.
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.

Page 1 of 6 SEPTEMBER 2019 TFP412


TFP412
Page 2 of 6

Components: WRENCH
1 - Frame FLATS
WRENCH
2 - Button FLATS

TOP
3 - Sealing
TOP-OF-
Assembly 1/2" NPT
DEFLECTOR
4 - Bulb
5 - Compression 7/16" (11,1 mm)
Screw NOMINAL 2-7/8" DIA.
6 - Deflector * 6* 5 4 2 MAKE-IN (73,0 mm)

CENTERLINE
* Temperature rating OF WATERWAY
is indicated on top
of Deflector. 1 STYLE 20
7/16"
(11,1 mm) 3 RECESSED
1-1/2" ESCUTCHEON
END-OF- (38,1 mm) ESCUTCHEON
DEFLECTOR 2-1/8" PLATE SEATING
BOSS (54,0 mm) SURFACE RECESSED
FIGURE 1
RAPID RESPONSE SERIES LFII RESIDENTIAL HORIZONTAL SIDEWALL
AND RECESSED HORIZONTAL SIDEWALL SPRINKLERS (TY2334)

7/16±1/8"
(11,1±3,2 mm)

MOUNTING FACE OF WRENCH RECESS


SURFACE SPRINKLER (END "A" USED
FITTING FOR TY2334)
CLOSURE
TOP-OF-
DEFLECTOR
FIGURE 3
W-TYPE 6
TY2334
SPRINKLER WRENCH
2-7/8" DIA.
(73,0 mm)
WRENCH
2-1/4" DIA. RECESS
(57,2 mm)
7/16"
(11,1 mm)

MOUNTING
PLATE

END-OF-
DEFLECTOR 1/8"
BOSS (3,2 mm)
PUSH WRENCH
1-1/4" (31,8 mm) 1/2" (12,7 mm) IN TO ENSURE
ENGAGEMENT
1" (25,4 mm) 1/4" (6,4 mm) WITH SPRINKLER
FIGURE 2 WRENCHING AREA
STYLE 20 RECESSED ESCUTCHEON FIGURE 4
FOR USE WITH THE RAPID RESPONSE SERIES LFII W-TYPE 7 RECESSED
RESIDENTIAL HORIZONTAL SIDEWALL SPRINKLER (TY2334) SPRINKLER WRENCH

Technical See the Design Criteria section for details


on these approvals.
Finishes
Natural Brass, Signal White Polyester

Data
Coated, or Chrome Plated
Maximum Working Pressure
Maximum 175 psi (12,1 bar) Physical Characteristics
Approvals Frame ���������������������������������������������������������Brass
Discharge Coefficient Button �������������������������������������������������������Bronze
UL and C-UL Listed K= 4.4 GPM/psi½ (63,4 LPM/bar ½ ) Sealing Assembly. . Beryllium Nickel w/ TEFLON
Certified to all requirements of Bulb ��������������������������������������������������� 3 mm Glass
NSF/ANSI 61 Temperature Rating
Compression Screw ���������������������������������Bronze
Australian WaterMark Certified 155°F (68°C) or 175°F (79°C) Deflector �������������������������������������������������� Copper
Note: Sprinklers with a polyester finish
are UL Listed as corrosion-resistant
sprinklers.
TFP412
Page 3 of 6

Operation • A minimum discharge of 0.1 gpm/ft2


over the “design area” comprised of
Series LFII Residential Horizontal
Sidewall Sprinklers
the four most hydraulically demand- The Series LFII Horizontal Sidewall
The glass bulb contains a fluid that
ing sprinklers for the actual cover- Sprinklers must be installed in accor-
expands when exposed to heat. When
age areas being protected by the dance with the following instructions.
the rated temperature is reached, the
fluid expands sufficiently to shatter the four sprinklers. Step 1. Horizontal sidewall sprinklers
glass bulb allowing the sprinkler to acti- Obstruction to Water Distribution are to be installed in the horizontal
vate and flow water. Sprinklers are to be located in accor- position with their centerline of water-
dance with the obstruction rules of way perpendicular to the back wall and
Design NFPA 13D, 13R, and 13 as applicable
for residential sprinklers as well as with
parallel to the ceiling. The word “TOP”
on the Deflector is to face towards
Criteria the obstruction criteria described within
the Technical Data Sheet TFP490.
the ceiling with the front edge of the
Deflector parallel to the ceiling.
The TYCO RAPID RESPONSE Series Step 2. With pipe thread sealant
Operational Sensitivity
LFII (TY2334) Residential Horizontal applied to the pipe threads, hand
The sprinklers are to be installed with
Sidewall Sprinklers are UL and C-UL tighten the sprinkler into the sprinkler
an end of defector-boss to wall dis-
Listed for installation in accordance fitting.
tance of 1-1/8 in. to 6 in.
with this section.
In addition the top-of-deflector-to- Step 3. Tighten the sprinkler into
Residential Sprinkler Design Guide ceiling distance is to be within the the sprinkler fitting using only the
When conditions exist that are outside range (see Table A) being hydraulically W-Type 6 Sprinkler Wrench (see Fig-
the scope of the provided criteria, refer calculated. ure 3). With reference to Figure 1, the
to the Residential Sprinkler Design W-Type 6 Sprinkler Wrench is to be
Guide TFP490 for the manufactur- Sprinkler Spacing applied to the wrench flats.
er’s recommendations that may be The minimum spacing between sprin-
acceptable to the local authority having klers is 8 ft (2,4 m). The maximum Series LFII Residential Recessed
jurisdiction. spacing between sprinklers cannot Horizontal Sidewall Sprinklers
exceed the width of the coverage area The Series LFII Recessed Horizontal
System Type (see Table A) being hydraulically calcu- Sidewall Sprinklers must be installed
Only wet pipe systems may be utilized. lated, for example, maximum 12 ft for a in accordance with the following
Ceiling Type 12 ft x 12 ft coverage area, or 16 ft for a instructions.
Smooth flat horizontal, or beamed, or 16 ft x 20 ft coverage area. Step A. Recessed horizontal sidewall
sloped, in accordance with the 2013 sprinklers are to be installed in the hor-
Edition of NFPA 13D, 13R, or 13 as
applicable.
Installation izontal position with their centerline of
waterway perpendicular to the back
The TYCO RAPID RESPONSE Series wall and parallel to the ceiling. The
Hydraulic Design
LFII (TY2334) Residential Horizontal word “TOP” on the Deflector is to face
(NFPA 13D and 13R) Sidewall Sprinklers must be installed
For systems designed to NFPA 13D or towards the ceiling.
in accordance with this section.
NFPA 13R, the minimum required sprin- Step B. After installing the Style 20
kler flow rate are given in Table A as a General Instructions Mounting Plate over the sprinkler
function of temperature rating and the Do not install any bulb-type sprinkler threads and with pipe thread seal-
maximum allowable coverage areas. if the bulb is cracked or there is a loss ant applied to the pipe threads, hand
The sprinkler flow rate is the minimum of liquid from the bulb. With the sprin- tighten the sprinkler into the sprinkler
required discharge from each of the kler held horizontally, a small air bubble fitting.
total number of design sprinklers as should be present. The diameter of the
air bubble is approximately 1/16 in. Step C. Tighten the sprinkler into the
specified in NFPA 13D or NFPA 13R.
(1,6 mm). sprinkler fitting using only the W-Type
Hydraulic Design 7 Recessed Sprinkler Wrench (see Fig-
(NFPA 13) A leak-tight 1/2 in. NPT sprinkler joint ure 4). With reference to Figure 1, the
For systems designed to NFPA 13, the should be obtained by applying a W-Type 7 Recessed Sprinkler Wrench
number of design sprinklers is to be minimum to maximum torque of 7 to is to be applied to the sprinkler wrench
the four most hydraulically demanding 14 lb-ft (9,5 to 19,0 N∙m). Higher levels flats.
sprinklers. The minimum required dis- of torque can distort the sprinkler Inlet
with consequent leakage or impairment Step D. After the wall has been
charge from each of the four sprinklers installed or the finish coat has been
is to be the greater of the following: of the sprinkler.
applied, slide on the Style 20 Closure
• The flow rates given in Table A as a Do not attempt to compensate for over the Series LFII Sprinkler and push
function of temperature rating and insufficient adjustment in the sprinkler the Closure over the Mounting Plate
the maximum allowable coverage by under- or over-tightening the sprin- until its flange comes in contact with
area. kler. Re-adjust the position of the sprin- the wall.
kler fitting to suit.
TFP412
Page 4 of 6

WET PIPE SYSTEM


Max. Minimum Flow and Residual Pressure(b, c)
Max. Coverage
Area (a) Spacing Ordinary Temp. Rating Intermediate Temp. Rating
ft 155°F (68°C) 175°F (79°C) Minimum
Width x Length (d) Deflector to Installation Spacing
ft x ft (m)
Flow Pressure Flow Pressure Ceiling Type ft
(m x m) GPM PSI GPM PSI (m)
(L/min) (bar) (L/min) (bar)
12 x 12 12 13 8.7 13 8.7
(3,7 x 3,7) (3,7) (49,2) (0,60) (49,2) (0,60)
14 x 14 14 14 10.1 14 10.1
(4,3 x 4,3) (4,3) (53,0) (0,70) (53,0) (0,70)
16 x 16 16 16 13.2 16 13.2
(4,9 x 4,9) (4,9) (60,6) (0,91) (60,6) (0,91)
16 x 18 16 19 18.6 19 18.6 4 in. to
(4,9 x 5,5) (4,9) (71,9) (1,28) (71,9) (1,28) 6 in.
16 x 20 16 23 27.3 23 27.3
(4,9 x 6,1) (4,9) (87,1) (1,88) (87,1) (1,88)
18 x 18 18 23 27.3 23 27.3
(5,5 x 5,5) (5,5) (87,1) (1,88) (87,1) (1,88)
Recessed
18 x 20 18 26 34.9 26 34.9 using Style 20
(5,5 x 6,1) (5,5) (98,4) (2,41) (98,4) (2,41) Escutcheon or 8
12 x 12 12 13 8.7 13 8.7 non-recessed (2,4)
(3,7 x 3,7) (3,7) (49,2) (0,60) (49,2) (0,60) per NFPA 13D,
13R, or 13
14 x 14 14 14 10.1 14 10.1
(4,3 x 4,3) (4,3) (53,0) (0,70) (53,0) (0,70)
16 x 16 16 17 14.9 17 14.9
(4,9 x 4,9) (4,9) (64,3) (1,03) (64,3) (1,03)
16 x 18 16 20 20.7 20 20.7 6 in. to
(4,9 x 5,5) (4,9) (75,7) (1,43) (75,7) (1,43) 12 in.
16 x 20 16 23 27.3 23 27.3
(4,9 x 6,1) (4,9) (87,1) (1,88) (87,1) (1,88)
18 x 18 18 23 27.3 23 27.3
(5,5 x 5,5) (5,5) (87,1) (1,88) (87,1) (1,88)
18 x 20 18 26 34.9 26 34.9
(5,5 x 6,1) (5,5) (98,4) (2,41) (98,4) (2,41)
Notes:
a. For coverage area dimensions less than or between those indicated, use the minimum required flow for the next highest coverage area for which hydraulic design criteria
are stated.
b. Requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated using the nominal K-factor. See Hydraulic
Design under the Design Criteria section.
c. For NFPA 13 residential applications, the greater of 0.1 gpm/ft 2 over the design area or the flow in accordance with the criteria in this table must be used.
d. The Width x Length dimension refers to the Width (backwall where the sprinkler is located) times the Length (horizontal throw of sprinkler).

TABLE A
WET PIPE SYSTEMS
SERIES LFII (TY2334) RESIDENTIAL HORIZONTAL SIDEWALL
AND RECESSED HORIZONTAL SIDEWALL SPRINKLERS
NFPA 13D, 13R AND 13 WET PIPE HYDRAULIC DESIGN CRITERIA
TFP412
Page 5 of 6

Care and Limited Ordering


Maintenance Warranty Procedure
The TYCO RAPID RESPONSE Series For warranty terms and conditions, Contact your local distributor for avail-
LFII (TY2334) Residential Horizontal visit www.tyco-fire.com. ability. When placing an order, indicate
Sidewall Sprinklers must be maintained the full product name and Part Number
and serviced in accordance with this (P/N):
section.
Sprinkler Assembly
Before closing a fire protection system Specify: Series LFII (TY2334), K=4.4,
main control valve for maintenance Residential Horizontal Sidewall Sprin-
work on the fire protection system kler, (specify) temperature rating,
which it controls, permission to shut (specify) finish, P/N (specify):
down the affected fire protection 155°F (68°C)
system must be obtained from the Natural Brass . . . . . . . . . . . . . . . . . 51-215-1-155
proper authorities and all personnel Signal White (RAL9003)
who may be affected by this action Polyester1 . . . . . . . . . . . . . . . . . . . . 51-215-4-155
must be notified. Chrome Plated . . . . . . . . . . . . . . . . 51-215-9-155
175°F (79°C)
Absence of an Escutcheon Plate may Natural Brass . . . . . . . . . . . . . . . . . 51-215-1-175
delay the sprinkler operation in a fire Signal White (RAL9003)
situation. Polyester1 . . . . . . . . . . . . . . . . . . . . 51-215-4-175
Chrome Plated �������������������������������51-215-9-175
The owner must assure that the sprin-
1. UL Listed as corrosion-resistant.
klers are not used for hanging any
objects and that the sprinklers are only Recessed Escutcheon
cleaned by means of gently dusting Specify: Style 20 Recessed Escutcheon
with a feather duster; otherwise, non- with (specify*) finish, P/N (specify*).
operation in the event of a fire or inad- * Refer to Technical Data Sheet TFP770.
vertent operation may result.
Sprinkler Wrench
Sprinklers which are found to be Specify: W-Type 6 Sprinkler Wrench,
leaking or exhibiting visible signs of P/N 56-000-6-387
corrosion must be replaced.
Specify: W-Type 7 Sprinkler Wrench,
Automatic sprinklers must never be P/N 56-850-4-001
painted, plated, coated, or other-
wise altered after leaving the factory.
Modified sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid
damage to the sprinklers - before,
during, and after installation. Sprin-
klers damaged by dropping, striking,
wrench twist/slippage, or the like, must
be replaced. Also, replace any sprinkler
that has a cracked bulb or that has lost
liquid from its bulb. See the Installation
section for additional information.
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards
of the NATIONAL FIRE PROTECTION
ASSOCIATION, for example, NFPA 25,
in addition to the standards of any other
authorities having jurisdiction. Contact
the installing contractor or product
manufacturer with any questions.
Automatic sprinkler systems are rec-
ommended to be inspected, tested,
and maintained by a qualified Inspec-
tion Service in accordance with local
requirements and/or national codes.
TFP412
Page 6 of 6

1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700


© 2019 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.

NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;
TEFLON is a registered trademark of DuPont