Model ESFR-25
25.2 K-factor Pendent Sprinkler
Early Suppression, Fast Response
General compared to ESFR Sprinklers having
nominal K-factors of 14.0 and 16.8.
Description This feature offers flexibility when
sizing system piping, as well as pos-
The TYCO Model ESFR-25 Pendent sibly reducing or eliminating the need
Sprinklers are Early Suppression, Fast for a system fire pump.
Response (ESFR) sprinklers with a The Model ESFR-25 Sprinklers can
nominal K-factor of 25.2. The sprinkler eliminate the use of in-rack sprinklers
assembly is shown in Figure 1. They are when protecting high-piled storage of
suppression-mode sprinklers that are specific materials up to the following
especially advantageous as a means of heights:
eliminating the use of in-rack sprinklers
• NFPA: 40 ft (12,2 m) with ceilings up
when protecting high-piled storage.
to 45 ft (13,7m)
The Model ESFR-25 Sprinklers are pri-
• FM: 45 ft (13,7 m) with ceilings up to
marily used for ceiling-only sprinkler
50 ft (15,2 m)
protection of, but not limited to, the fol-
lowing storage applications: For more specific criteria, see Table B
• Most encapsulated or non-encap-
and the applicable design standard. Sprinkler
sulated common materials including
cartoned, unexpanded plastics
The Model ESFR-25 Sprinklers are
listed by Underwriters Laboratories Identification
• Uncartoned (exposed) expanded
plastics in accordance with NFPA 13
(UL) for specific applications with
a maximum storage height of 43 ft Number (SIN)
and FM Global standards (13,1 m) with a maximum ceiling height See Table A
of 48 ft (14,6 m) without the require-
• Some storage arrangements of rub-
Technical
ment for in-rack sprinklers. Refer to the
ber tires, roll paper, flammable liq-
Specific Application Listing (UL) for the
uids, aerosols, and automotive
Data
design criteria.
components
For more specific criteria, see Table B
and the applicable design standard. NOTICE Approvals
The Model ESFR-25 Sprinklers UL and C-UL Listed
The Model ESFR-25 Pendent Sprin- described herein must be installed FM Approved
klers provide the system designer and maintained in compliance with this VdS Approved
with hydraulic and sprinkler place- document, as well as with the applica- NYC Approved under MEA 356-01-E
ment options not presently available to ble standards of the National Fire Pro- LPCB Certified (Cert. Nos. 094b and 007l
the traditional ESFR sprinklers having tection Association (NFPA), in addition
nominal K-factors of 14.0 and 16.8. In Finish
to the standards of any authorities
particular, the Model ESFR-25 Sprin- having jurisdiction, such as FM Global. Natural Brass
kler is designed to operate at substan- Failure to do so may impair the perfor-
tially lower-end head pressures, as Physical Characteristics
mance of these devices. Frame ���������������������������������������������������������Brass
Deflector ���������������������������������������������������Bronze
The owner is responsible for main- Compression Screw �������������������� Stainless Steel
IMPORTANT taining their fire protection system Hook ��������������������������������������������������������MONEL
Refer to Technical Data Sheet and devices in proper operating con- Strut ���������������������������������������������������������MONEL
TFP2300 for warnings pertaining to dition. Contact the installing contrac- Link Assembly ��������������������������������Solder, Nickel
regulatory and health information. tor or product manufacturer with any Button. . . . . . . . . . . . . . . Copper/Stainless Steel
Sealing Assembly. . Beryllium Nickel w/TEFLON
Always refer to Technical Data questions.
Sheet TFP700 for the “INSTALLER In all cases, the appropriate NFPA or Additional Technical Data
WARNING” that provides cautions FM Global installation standard, or See Table A
with respect to handling and instal- other applicable standard, must be
lation of sprinkler systems and com- referenced to ensure applicability and
ponents. Improper handling and to obtain complete installation guide-
installation can permanently damage lines. The general guidelines in this
a sprinkler system or its compo- data sheet are not intended to provide
nents and cause the sprinkler to fail complete installation criteria.
to operate in a fire situation or cause
it to operate prematurely.

Page 1 of 6 APRIL 2021 TFP312


TFP312
Page 2 of 6

1 1" NPT

Components: 8 1-13/16"
9/16" (46,0 mm)
1 - Frame
(14,3 mm)
2 - Deflector
7 NOMINAL
3 - Compression MAKE-IN
Screw
4 - Hook 6
5 - Strut
3-13/16" CENTERLINE
6 - Link Assembly THERMAL
5 (96,8 mm)
7 - Button SENSING
8 - Sealing ELEMENT
Assembly
4
WRENCH
FLATS
3

2
TEMPERATURE
RATING
2" (50,8 mm)
FIGURE 1
MODEL ESFR-25 PENDENT SPRINKLER, 25.2K
EARLY SUPPRESSION, FAST RESPONSE

Operation Item Description

The fusible link assembly is com- Sprinkler Identification Number (SIN) TY9226
prised of two link halves that are joined
together by a thin layer of solder. When K-factor, gpm/psi½ (Lpm/bar½) 25.2 gpm/psi½ (362,9 Lpm/bar½)
the rated temperature is reached, the
165˚F (74˚C)
solder melts and the two link halves Temperature Rating ˚F (˚C) 212˚F (100˚C)
separate, activating the sprinkler and
flowing water. Thread Size 1 in. NPT or ISO 7-R 1

Design Sprinkler Orientation Pendent

Criteria Maximum Working Pressure, psi (bar) 175 psi (12,1 bar)

The following general guidelines pro- TABLE A


vided for the TYCO Model ESFR-25 MODEL ESFR-25 PENDENT SPRINKLER
Pendent Sprinklers can be used for a TECHNICAL DATA
quick reference.
Roof Construction Maximum Spacing
The National Fire Protection Associa-
Unobstructed or obstructed construc- • 12 ft (3,7 m) for building heights up
tion (NFPA) and FM Global (FM Approv-
tion, such as smooth ceiling, bar joists, to 30 ft (9,1 m)
als) provide installation standards that
beam and girder. • 10 ft (3,1 m) for building heights
must be used to properly design an
automatic sprinkler system utilizing Note: Where the depths of the solid greater than 30 ft (9,1 m)
Early Suppression, Fast Response structural members, as in beams and Minimum Spacing
(ESFR) Sprinklers. The guidelines pro- stem, exceed 12 in. (302 mm), install 8 ft (2,4 m)
vided by NFPA and FM Global may ESFR Sprinklers in each channel
differ. Consequently, the appropri- formed by the structural members. Minimum Clearance to Commodity
ate standard must be used for a given 36 in. (914 mm)
Ceiling Slope
installation. NFPA
Maximum 2 in. rise for 12 in. run (16.7%)
General guidelines are not intended to Deflector-to-Ceiling Distance
provide complete installation criteria. Maximum Coverage Area 6 in. to 18 in. (152 mm to 457 mm)
In all cases, the appropriate NFPA or 100 ft² (9,3 m²)
FM Global
FM Global installation standard must Minimum Coverage Area Centerline of Thermal Sensing
be referenced to ensure applicabil- 64 ft² (5,8 m²) per Element-to-Ceiling Distance
ity and to obtain complete installation NFPA 13 / FM Global 2-0 Refer to FM Global 2-0 for Storage
guidelines. For more information, see Sprinklers.
Table B.
TFP312
Page 3 of 6

Storage Type NFPA FM Global

Sprinkler Type ESFR Storage

Response Type FR QR

System Type Wet Wet

165˚F (74˚C) 165˚F (74˚C)


Temperature Rating ˚F (˚C) 212˚F (100˚C) 212˚F (100˚C)
Open Frame (i.e., no solid shelves), Single, Double, Multiple- Refer to FM Global
Row, or Portable Rack Storage of Class I-IV and Group A or Refer to NFPA 13 2-0 and 8-9
B Plastics
Solid Pile or Palletized Storage of Class I-IV and Group A or Refer to FM Global
Refer to NFPA 13
B Plastics 2-0 and 8-9

Refer to FM Global
Idle Pallet Storage Refer to NFPA 13 2-0, 8-9, and 8-24

Refer to FM Global
Rubber Tire Storage Refer to NFPA 13 2-0 and 8-3

Roll Paper Storage Refer to NFPA 13 Refer to FM Global 8-21


(Refer to the Standard)

Flammable/Ignitable Liquid Storage Refer to NFPA 30 Refer to FM Global 7-29


(Refer to the Standard)

Aerosol Storage Refer to NFPA 30B Refer to FM Global 7-31


(Refer to the Standard)

Automotive Components in Portable Racks Refer to NFPA 13 N/A


(Control mode only; refer to the Standard)
N/A – Not Applicable

TABLE B
MODEL ESFR-25 PENDENT SPRINKLER
COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW

Specific Installation Installing the Sprinkler


To install the sprinkler, perform the fol-
Application TYCO Model ESFR-25 Early Suppres-
sion, Fast Response 25.2K Pendent
lowing steps:

Listing (UL)
Note: Install the Model ESFR-25
Sprinklers must be installed in accor- Pendent Sprinkler in the pendent posi-
dance with this section. tion as shown in Figure 2.
TYCO Model ESFR-25 Pendent Sprin- General Instructions Step 1. With pipe thread sealant
klers are listed by Underwriters Labo- Damage to the fusible link assembly applied, hand-tighten the sprinkler into
ratories (UL) for Specific Applications during installation can be avoided by the sprinkler fitting. Do not apply pres-
with a ceiling height greater than 45 handling the sprinkler by the frame sure to the link assembly, and handle
ft (13,7 m) up to and including 48 ft arms only and by using the appropriate the sprinkler only by the frame arms.
(14,6 m), and a storage arrangement up sprinkler wrench. Do not apply pres-
to and including 43 ft (13,1 m). Step 2. Wrench-tighten the sprin-
sure to the fusible link assembly. Failure
For guidelines about the TYCO Model to do so can lead to an unstable link kler using only the W-Type 1 Sprinkler
ESFR-25 Pendent Sprinkler Specific assembly and premature activation of Wrench as shown in Figure 2, and by
Applications Listing (UL) Design Crite- the sprinkler. Damaged sprinklers must fully engaging (seating) the wrench on
ria, see Table C. be replaced. the sprinkler wrench flats as shown in
Figure 1.
A leak-tight 1 in. NPT sprinkler joint
should be obtained by applying a min- Step 3. After installation, inspect the
imum-to-maximum torque of 20 to 30 link assembly of each sprinkler for
lb-ft (26,8 to 40,2 N∙m). Higher levels damage. In particular, verify that the
of torque can distort the sprinkler inlet link assembly and hook are posi-
with consequent leakage or impairment tioned as shown in Figure 1, and that
of the sprinkler. the link assembly is not bent, creased,
or forced out of normal position in any
way. Replace damaged sprinklers.
TFP312
Page 4 of 6

Description Specification, UL

Sprinkler Type ESFR

165˚F (74˚C)
Temperature Rating ˚F (˚C) 212˚F (100˚C)

Response Type QR

Pendent, frame arms aligned with pipe,


Sprinkler Position deflectors parallel with ceiling or roof

System Type Wet

Maximum Area of Coverage 100 ft2 (9,3 m2)

Minimum Area of Coverage 64 ft2 (5,8 m2)

Maximum Slope Ceiling 2 in. rise for 12 in. run (16.7%)

Maximum Spacing 10 ft (3,1 m)

Minimum Spacing 8 ft (2,4 m)

Minimum of 4 in. (100 mm) from walls but no more than 1/2 the
Deflector Distance from Walls allowable distance permitted between sprinklers

Deflector to Top of Storage Minimum of 36 in. (914 mm)

Deflector to Ceiling Distance 6 in. to 14 in. (152 mm to 356 mm)

Maximum Ceiling Height 48 ft (14,6 m)

Maximum Storage Height 43 ft (13,1 m)

Storage Arrangement Palletized, solid piled, open frame; single row or double row

Commodity Class I - IV, Cartoned unexpanded plastic

NFPA 13 for ESFR Sprinklers based upon 45 psi (3,1 bar) design
Sprinkler System Design pressure 169 gpm (640 Lpm) with 12 sprinkler remote area

Obstruction Criteria Reference NFPA 13, Chapter 8

Minimum Aisle Width 5 ft (1,5 m)

Hose Stream allowance and Water Supply Duration 250 gpm for 60 minutes (950 Lpm for 60 minutes)

TABLE C
MODEL ESFR-25 PENDENT SPRINKLER
SPECIFIC APPLICATION LISTING (UL)
COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW
TFP312
Page 5 of 6

Automatic sprinklers must never be


painted, plated, coated, or other- Ordering
"FITTING SIDE"
TOWARDS SPRINKLER
wise altered after leaving the factory.
Modified sprinklers must be replaced. Procedure
FITTING Sprinklers that have been exposed to Contact your local distributor for avail-
corrosive products of combustion, but ability. When placing an order, indicate
have not operated, should be replaced the full product name and part number
if they cannot be completely cleaned (P/N).
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush. Sprinkler Assemblies with
Care must be exercised to avoid 1 in. NPT Thread Connection
damage to the sprinklers before, Specify: Model ESFR-25 (TY9226),
WRENCH during, and after installation. Sprin- K=25.2, Early Suppression, Fast
RECESS klers damaged by dropping, striking, Response Pendent Sprinkler with
wrench twist/slippage, or the like, must 1 in. NPT thread connection, (specify)
be replaced. Also, replace any sprinkler temperature rating, Natural Brass,
FIGURE 2 that has a cracked bulb or that has lost P/N (specify):
W-TYPE 1 liquid from its bulb. For more informa- 165°F (74°C) . . . . . . . . . . . . . . . . . . 58-441-1-165
SPRINKLER WRENCH tion, see the Installation section. 212°F (100°C) . . . . . . . . . . . . . . . . . 58-441-1-214

The owner is responsible for the Special Order


Care and inspection, testing, and maintenance of
their fire protection system and devices
Sprinkler Assemblies with
ISO 7-1 Thread Connection
Maintenance in compliance with the following docu-
ments and standards:
Specify: Model ESFR-25 (TY9226),
K= 25 . 2, Early Suppression,
TYCO Model ESFR-25 Early Suppres- Fast Response Sprinkler with
sion, Fast Response 25.2K Pendent • This technical data sheet ISO 7-1 thread connection, (specify)
Sprinklers must be maintained and ser- • Applicable standards of the National temperature rating), Natural Brass,
viced in accordance with this section. Fire Protection Association such as P/N (specify):
Before closing a fire protection system NFPA 25 165°F (74°C) . . . . . . . . . . . . . . . . . 58-442-1-165
main control valve for maintenance 212°F (100°C) . . . . . . . . . . . . . . . . 58-442-1-214
• Standards of any authorities having
work on the fire protection system jurisdiction Sprinkler Wrench
that it controls, obtain permission to Specify: W-Type 1 Sprinkler Wrench,
shut down the affected fire protection Contact the installing contractor
or product manufacturer with any P/N 56-872-1-025
system from the proper authorities
and notify all personnel who may be questions.
affected by this action. Automatic sprinkler systems are rec-
Sprinklers which are found to be ommended to be inspected, tested,
leaking or exhibiting visible signs of and maintained by a qualified Inspec-
corrosion must be replaced. tion Service in accordance with local
requirements and/or national codes.

Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
TFP312
Page 6 of 6

1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700


© 2021 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;
MONEL and INCONEL are registered trademarks of Special Metals Corporation;
TEFLON is a trademark of The Chemours Company FC, LLC

You might also like