a suspended ceiling or application of ment and with the applicable standards
the finish coating to a fixed ceiling. of the NATIONAL FIRE PROTECTION
ASSOCIATION (NFPA), in addition to
the standards of any authorities having TY3530 — 3 mm bulb
IMPORTANT TY3550 — 5 mm bulb
jurisdiction. Failure to do so may impair
Refer to Technical Data Sheet
the performance of these devices.
TFP2300 for warnings pertaining to
regulatory and health information. The owner is responsible for maintain-
ing their fire protection system and
Always refer to Technical Data
devices in proper operating condition.
Sheet TFP700 for the “INSTALLER
The installing contractor or sprinkler
WARNING” that provides cautions
manufacturer should be contacted with
with respect to handling and instal-
any questions.
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Installation
Cover Plate �������������������������������������������������Brass below. Down drafts through the Sprin-
Retainer �������������������������������������������������������Brass
Ejection Spring ���������������������������� Stainless Steel
kler/Support Cup Assembly can delay
sprinkler operation in a fire situation.
The Series RFII-MRI Concealed
Design Operation
Pendent Sprinklers must be installed
in accordance with this section.
Criteria When exposed to heat from a fire, the General Instructions
Cover Plate, normally soldered to the Do not install any bulb-type sprin-
The Series RFII-MRI Concealed kler if the bulb is cracked or there is
Pendent Sprinklers are intended for Retainer at three points, falls away to
expose the Sprinkler/Support Cup a loss of liquid from the bulb. With the
fire protection systems designed in sprinkler held horizontally, a small air
accordance with the standard installa- Assembly.
bubble should be present. The diam-
tion rules recognized by the applicable The Deflector — supported by the eter of the air bubble is approximately
Listing or Approval agency; for example, Guide Pins — then drops down to its 1/16 in. (1,6 mm) for the 155°F (68°C)
UL Listing is based on NFPA 13. operational position. and 3/32 in. (2,4 mm) for the 200°F
The RFII-MRI Sprinklers are only listed The glass bulb contains a fluid that (93°C) temperature ratings.
with the Series RFII-MRI Concealed expands when exposed to heat. When A leak-tight 1/2 in. NPT sprinkler joint
Cover Plates having a factory applied the rated temperature is reached, the should be obtained by applying a
finish. fluid expands sufficiently to shatter the minimum to maximum torque of 7 to
glass bulb, activating the sprinkler and 14 lb-ft (9,5 to 19,0 N·m). Higher levels
NOTICE allowing water to flow. of torque can distort the sprinkler Inlet
Do not use the RFII-MRI Sprinklers in with consequent leakage or impairment
applications where the air pressure of the sprinkler.
above the ceiling is greater than that
Do not attempt to compensate for
insufficient adjustment in the Sprinkler
TFP182
Page 3 of 4
AIR
AND DUST
LIP OF COVER SEAL
RETAINER PLATE
FIGURE 5
FIGURE 4 OPTIONAL AIR AND DUST SEAL
DISPOSABLE PROTECTIVE CAP FOR SERIES RFII-MRI (TY3550)