www.tyco-fire.com
Contacts
Design
Criteria SOLDER
TABS (3) COVER PLATE/RETAINER
COVER
PLATE
The Series RFII-MRI Concealed ASSEMBLY
Pendent Sprinklers are UL and C-UL FIGURE 1
Listed for use in light hazard occupan- SERIES RFII-MRI CONCEALED SPRINKLER
cies, using the design criteria in Table
A, in addition to the requirements
specified in the current NFPA 13 for RESPONSE MINIMUM
SPACING
extended coverage pendent sprinklers. RATING FLOW/PRESSURE
The RFII-MRI Sprinklers are only listed 16 ft x 16 ft 26.0 GPM / 21.6 PSI
QUICK (4,9 m x 4,9 m) (98,4 LPM / 1,49 BAR)
with the Series RFII-MRI Concealed
Cover Plates with a factory-applied 18 ft x 18 ft 33.0 GPM / 34.7 PSI
QUICK
finish. (5,5 m x 5,5 m) (124,9 LPM / 2,39 BAR)
20 ft x 20 ft 40.0 GPM / 51 PSI
QUICK
NOTICE (6,1 m x 6,1 m) (151,4 LPM / 3,52 BAR)
Operation
can delay sprinkler operation in a fire The Deflector, supported by the Guide
situation. Pins, then drops down to its operational
When exposed to heat from a fire, the position.
Cover Plate, normally soldered to the The glass bulb contains a fluid that
Retainer at three points, falls away to expands when exposed to heat. When
expose the Sprinkler/Support Cup the rated temperature is reached, the
Assembly. fluid expands sufficiently to shatter the
glass bulb, activating the sprinkler and
allowing water to flow.
TFP262
Page 3 of 4
FACE OF
SPRINKLER
CLEARANCE HOLE
DIAMETER
Installation
FITTING DIMENSION C The Series RFII-MRI Concealed
Pendent Sprinklers must be installed
SPRINKLER
in accordance with this section.
SUPPORT CUP General Instructions
ASSEMBLY Do not install any bulb-type sprinkler
if the bulb is cracked or there is a loss
1/2" (12,7 mm) of liquid from the bulb. With the sprin-
THREADED kler held horizontally, a small air bubble
ADJUSTMENT should be present. The diameter of the
D
air bubble is approximately 1/16 in.
FACE (1,6 mm) for the 155°F (68°C) and 3/32
OF CEILING, in. (2,4 mm) for the 200°F (93°C) tem-
RETAINING RING perature ratings.
MOUNTING Obtain a 1/2 in. NPT sprinkler joint
SURFACE by applying a minimum to maximum
torque of 7 to 14 lb-ft (9,5 to 19,0 N·m).
Higher levels of torque can distort the
sprinkler Inlet with consequent leakage
or impairment of the sprinkler.
Do not attempt to compensate for
3/16" to 11/16" MANUFACTURER DEFLECTOR COVER PLATE insufficient adjustment in the Sprinkler
(4,8 to 17,5 mm) PRESET GAP IN DROPPED RETAINER by under- or over-tightening the Sprin-
REFERENCE 3/32" (2,4 mm) POSITION ASSEMBLY kler/Support Cup Assembly. Re-adjust
the position of the sprinkler fitting to
COVER PLATE COVER PLATE
suit.
PROFILE DEPTH DIAMETER Step 1. Install the sprinkler only in the
DIMENSION B DIMENSION A pendent position with the centerline
A: 3-1/4 inches (82,6 mm) C: 2-3/8 to 2-5/8 inches (60,3 to 66,7 mm) of the sprinkler perpendicular to the
mounting surface.
B: 3/16 inches (4,8 mm) D: 1-3/4 to 2-1/4 inches (44,5 to 57,2 mm)
Step 2. Remove the Protective Cap.
FIGURE 2
SERIES RFII-MRI CONCEALED SPRINKLER Step 3. With pipe thread sealant
INSTALLATION DIMENSIONS applied to the pipe threads, hand-
tighten the sprinkler into the sprinkler
fitting.
Step 4. Wrench-tighten the sprinkler
using only the RFII Sprinkler Wrench
FRAME shown in Figure 3. Apply the RFII Sprin-
ARM kler Wrench to the Sprinkler as shown
in the figure.
SUPPORT Step 5. Replace the Protective Cap by
CUP pushing it upwards until it bottoms out
against the Support Cup, see Figure 4.
The Protective Cap helps prevent
damage to the Deflector and Frame
Arms when installing or finishing the
ceiling. You can also use it to locate the
7/8" (23 mm)
center of the clearance hole by gently
SQUARE
pushing the ceiling material up against
the center point of the Protective Cap.
ALIGN
ARROWS WITH NOTICE
FRAME ARMS
As long as the Protective Cap remains
in place, the system is considered “Out
ACCEPTS of Service”.
1/2" SOCKET Step 6. After the ceiling has been
DRIVE completed with the 2-1/2 in. (63,5 mm)
FIGURE 3 diameter clearance hole and in prep-
RFII-MRI SPRINKLER WRENCH aration for installing the Cover Plate/
Retainer Assembly, remove and discard
the Protective Cap.
TFP262
Page 4 of 4
CLEARANCE
HOLE
When properly installed, there is a
nominal 3/32 in. (2,4 mm) air gap Limited
between the lip of the Cover Plate and
the ceiling, as shown in Figure 2. This Warranty
air gap is necessary for proper oper-
For warranty terms and conditions, visit
ation of the sprinkler. If the ceiling
www.tyco-fire.com.
requires repainting after sprinkler instal-
lation, ensure that the new paint does
not seal off any of the air gap. Ordering
Do not pull the Cover Plate relative to
the Enclosure. Separation may result. Procedure
Replace sprinklers that are leaking or Contact your local distributor for
exhibiting visible signs of corrosion. availability. When placing an order,
indicate the full product name and Part
Never repaint, plate, coat, or otherwise
Number (P/N).
alter automatic sprinklers after they
leave the factory. Never repaint fac- Sprinkler/Support Cup Assembly
FIGURE 4 tory-painted Cover Plates. If neces- Specify: Series RFII-MRI Non-Mag-
DISPOSABLE PROTECTIVE CAP sary, replace them with factory-painted netic Concealed Pendent Sprinkler,
units. Non-factory applied paint can TY3537, (specify) temperature rating,
Verify that the Deflector moves up and adversely delay or prevent sprinkler P/N (specify):
down freely. If the Sprinkler is damaged operation in the event of a fire.
155°F (68°C) ����������������������������������� 51-802-1-155
and the Deflector does not move up Replace modified or over-heated
and down freely, replace the entire 200°F (93°C) ���������������������������������� 51-802-1-200
sprinklers.
Sprinkler. Do not attempt to modify or Separately Ordered
repair a damaged sprinkler. Exercise care to avoid damage to
the sprinklers before, during, and Cover Plate/Retainer Assembly:
Step 7. Screw on the Cover Plate/ after installation. Replace sprinklers Specify: (temperature rating from
Retainer Assembly until its flange damaged by dropping, striking, wrench below) Non-Magnetic Series RFII-MRI
makes contact with the ceiling. Do not twisting, wrench slipping, or the like. Concealed Cover Plate with (specify)
continue to screw on the Cover Plate/ Also, replace any sprinkler that has a finish, P/N (specify):
Retainer Assembly so that it lifts a cracked bulb or that has lost liquid from 139°F (59°C)a 165°F (74°C) b
ceiling panel out of its normal position. its bulb. See the Installation Section. Grey White
If you cannot engage the Cover Plate/ (RAL9002). . . . . 56-794-0-135 56-794-0-165
Retainer Assembly with the Support If you must remove a sprinkler, do not Brass. . . . . . . . . . . 56-794-1-135 56-794-1-165
Cup or you cannot engage the Cover reinstall it or a replacement without Signal White
Plate/Retainer Assembly sufficiently to reinstalling the Cover Plate/Retainer (RAL9003). . . . . 56-794-4-135 56-794-4-165
Assembly. If a Cover Plate/Retainer Jet Black
contact the ceiling, you must reposition
Assembly becomes dislodged during (RAL9005). . . . . 56-794-6-135 59-794-6-165
the Sprinkler Fitting. service, replace it immediately. Custom. . . . . . . . . 56-794-X-135 56-794-X-165