Fire stopping of service penetrations
7th edition August 2019
Overview

The contribution to building protection to the building. And fire can spread so fast in smoke filled corridors that would disorientate
by installed fire stopping products is often residential homes that the whole house can burn an impede the evacuation leading to possible
undervalued by businesses. The media very rarely down before the fire department even arrives. loss of life. The building itself would be unusable
reports on the reduction and positive effects of Isolating rooms where fires are more likely, reduces and even unsafe and could be condemned; the
fires in compartmentalised buildings, even though the effects of fire spreading to the rest of the business would lose its manufacturing capability,
thousands of lives and the buildings themselves building and increases the time the fire fighters leading to loss of business in the short term and/or
are saved each year. I guess there’s nothing to have to put it out before it spreads. even the possible closure in the long term.
write about when the destructive impact of a
fire is prevented. Compartmentalisation works A fire compartment can be designed to restrain a For over 26 years, Polyseam have developed
by preventing the spread of fire, and preventing fire for 60 minutes, which could be sufficient time products to simplify the installation of fire stopping
shocking injury, or death to both people and to evacuate the building safely. And for the fire of service penetrations. Solutions to problems
animals, and untold damage to buildings. department to arrive and extinguish the fire, that is do not have to be complicated, expensive and
if the fire does not burn out on its own due to lack time-consuming, instead we offer simple solutions
One often reads about the heroics of fire of oxygen, material, or both. designed and tested in apertures and Services,
departments, or that the fire was halted by installed in real situations and solved through
the sprinklerSystem, rarely is it attributed to Compartmentalisation is not the only complex chemistry. Who are we to tell construction
compartmentalisation. Why is that? Is it too consideration. Compartmentalisation of rooms professionals how to insulate a pipe, or cut a hole
complex to be considered? Of course not, it is an (where fires are most obvious) should also take in a gypsum wall? No… it is far more beneficial for
easy and cost effective way to protect a building into account the number of occupants and where those working in the sector to receive solutions
against the spread of smoke and fire. I compiled occupants are located; the types of activities being adapted to meet their requirements for products,
this handbook to demonstrate the ease and performed on the premises; the fire evacuation installation and performance.
effectiveness of compartmentalisation, and to route; the fire alarm system and other systems
raise awareness of the short movies showing the linked to the fire alarm. This is evident in the I truly hope you find this handbook useful
installation in real time (available on YouTube, designs the architect has incorporated into our (combined with all the other things we are doing),
just search for Protecta). new factory built in Huddersfield city centre. and enables us to work together to build safely in
the future.
Today, time is the reason compartmentalisation Without my important modifications to the
is the most effective method to use against fire original plans, the whole site would be exposed to
spread. A fire can spread so quickly, that it is unnecessary and preventable risk from fire, and Kjetil Bogstad
impossible for any fire department to quickly the following consequences: employees would be CEO of Polyseam
extinguish it without causing large scale damage exposed to the dangers of an evacuation through & Handbook Editor
Contents

Which products should be used and where? Technical solutions

Linear seals 4 Appendix I – Linear seal solutions 17 – 42

Penetrating services 5 Appendix II – Service penetration solutions with gaps ≤ 10mm 43 – 81

General rules to fire classifications Appendix III – Service penetration solutions with gaps ≤ 30mm 82 – 188

Aperture sizes and allowed services 6 Appendix IV – Service penetration solutions in larger apertures 189 – 279

Additional aperture sizes in floors 6 Appendix V – Apertures with mixed services 280 – 316

Service sizes 7 Index to technical solutions 317 – 322

Fire classifications – what do they mean? 8

Pipe end configurations 9

Surrounding constructions 10

Supporting constructions and service supports 11

Mixed services within the same aperture 11

Onsite problems and solutions

Single sided access 12

Restrictive fire seals and the pattress solution 13

Frequently asked questions 14 – 16


Which products should be used where?
In most cases, the type of product chosen depends on the size and configuration of the seal or aperture to be fire protected, the
construction type and the type of services (if any) that penetrates the construction. This can be simplified by saying that where there
are no gaps or gaps less than 10mm, the putty cord product or collars are used, small gaps above 10mm a sealant is normally used and
for larger apertures the board and mortar products are used. These solutions are given in general in the two following tables, and the
details are given in the technical appendixes found in this handbook, which can easily be located using the index on the last pages.

Typical sample of penetrating services with Typical sample of penetrating services with Typical sample of penetrating services with
gap widths between 0 and 10mm gap widths between 10 and 30mm gaps above 30mm or mixed services

Product Selector - Linear Seals


Properties Construction Seal Size Product
Normal Walls and floors Up to 100mm wide Protecta FR Acrylic
Water proof and high movement Up to 30mm wide Protecta FR IPT
Extra wide with some movement Walls Up to 1,200mm wide Protecta FR Board
Floors Up to 800mm wide
Extra wide and loadbearing Up to 800mm wide Protecta EX Mortar

Page |4
Product Selector - Penetrating Services
Seal Size Construction Services Protecta Product(s)
Gap between Walls and floors Cables FR Putty Cord
0 and 10mm Metal pipes; un-insulated or mineral wool insulations
Metal pipes; combustible insulations FR Collar
Plastic pipes
Ventilation ducts FR Putty Cord & FR Damper
Gap between Cables FR Acrylic
10 and 30mm Metal pipes; un-insulated or mineral wool insulations
Metal pipes; combustible insulations FR Acrylic & FR Graphite
Plastic pipes FR Acrylic, FR Graphite or FR Collar
Ventilation ducts FR Acrylic & FR Damper
Gap above Walls Cables and cable trays FR Board
30mm and Metal pipes; un-insulated or mineral wool insulations
mixed Metal pipes; combustible insulations FR Board & FR Pipe Wrap
services Plastic pipes
Ventilation ducts FR Board & FR Damper
Floors Cables and cable trays EX Mortar
Metal pipes; un-insulated or mineral wool insulations
Metal pipes; combustible insulations EX Mortar & FR Pipe Wrap
Plastic pipes
Ventilation ducts EX Mortar & FR Damper

Page |5
General rules to fire classifications
Aperture sizes and allowed services
The technical drawings in this handbook show the maximum size allowed of any aperture or linear seal as tested, and as shown also in
the product's installation instructions. The maximum allowed cross sectional area of a rectangular aperture, can be used to calculate
the maximum allowed cross sectional area of a circular aperture. To calculate the maximum allowed cross sectional area of a circular
aperture, simply calculate the size in for instance cm2 and then use this to calculate the allowed diameter (Ø):
A rectangular aperture of 1200 x 2400mm would have a cross sectional area (A) 28,800cm2
radius = √(A/Π) = √(28,800/3,14) = √9172 = 96cm
Ø = radius x 2 = 96x2 = Ø192cm
An approval for a circular aperture is not allowed to be used in a rectangular aperture. The total amount of cross sectional area
occupied by services (including insulation) should not exceed 60% of the penetration cross sectional area.

Additional aperture sizes in floors


Under EN 1366-3 rules, results from tests in floors with a penetration seal length of minimum 1m apply to any length as long as
perimeter length to seal area ratio is not smaller than that of the test specimen. The following aperture sizes are therefore allowed
where 2400 x 1200 mm is described in this handbook and in the products installation instructions.
Maximum Aperture Sizes within Floors or between Floors and Walls
1200 mm width x 2400 mm length (tested)
1100 mm width x 2900 mm length (allowed)
1000 mm width x 4000 mm length (allowed)
900 mm width x 7000 mm length (allowed)
≤ 800 mm width x ∞ (infinite) length (allowed)

Page |6
Service sizes
The test standard (EN1366-3) groups services to be tested for approval. For instance, all cables in the group up to a certain diameter
must be tested otherwise, approval is only granted for the exact specimen tested, and this has no practical value.
For cables, there are many groups to test to obtain full approval. For example to obtain approval for all cables up to 21mm diameter, it
is necessary to test the following cables: type A1, A2, A3 (A cables are 5 x 1.5mm2) and B (1 x 95mm2). The position of the cables in the
test is also subject to how the cables are allowed to be positioned in practical. The testing of cables on cable trays normally consists of
4 cable trays packed with different types of cables, wires and conduits.
Our specifications for installation are simplified to allow the installation to be performed correctly and with the least complexity,
however testing to achieve the specifications is anything but simple. In general we specify service sizes with the symbol ≤ in front.
Without this symbol, the size of the service is exactly as specified. The same can be said for pipes. For metal pipes testing consists of a
certain design group which includes pipe diameter and wall thickness. However, where we do not specify this, it is because we have
tested all the different wall thicknesses available. For plastic pipes testing also includes the different plastics, eg: PVC, PE and so on.

Example of standard configuration for cable


penetration systems according to EN 1366-3

Page |7
Fire classifications; what do they mean?
In Europe we all use the same system to classify fire
resistance, not only in fire stop seals, but also in walls,
floors, doors and so on. In fire stopping, only a few letters
are used to indicate the result and what protection the
installation gives.
E - Integrity, the time it takes for fire to physically spread
through a fire seal. At the point of failure one can see the
glow of the fire through the seal, flames coming through or
via a cotton pad which catches fire when held close to the
seal by the test technician. This is the simplest classification
to achieve.
I - Insulation, the temperature, measured on the non-fire
side has increased by 180°C on either the fire seal or the
services. This is measured through many thermocouples
placed in strategic locations. The intention is to replicate the
lowest possible temperature that can actually start a fire,
even though the fire itself has not passed through the fire
seal. This is the more difficult classification to achieve.
Picture shows a fire test after 2 hours at BM Trada in UK
In most European countries, there is a demand that the fire classification should include both integrity E and insulation I. However, if
the fire seal is in an area where no combustible material are close by, and no combustible materials are likely to be placed closed by,
an engineering judgment could be taken to approve usage of the integrity classification only. This is why we state both classifications in
this handbook.
The letters are followed by a number, which is how long in minutes the integrity and insulation were maintained. For instance, the
classification E 60 is integrity for one hour, whilst EI 120 is both integrity and insulation for two hours.
Page |8
Pipe end configurations
When testing pipes, one can choose not to cap (or close) or to cap the pipe inside or outside the furnace. The configuration chosen
depends on the intended application of the pipe and/or the installation environment. The code defining if a pipe is capped is stated
after the fire classification. For instance EI 60 C/U means the pipe was capped inside the furnace, and uncapped outside the furnace.
Field of application rules for pipe end configuration:
Tested
U/U C/U U/C C/C
Covered U/U - NO NO NO
C/U YES - NO NO
U/C YES YES - NO
C/C YES YES YES -
Our engineering judgment based on EN 1366-3:2009:
Intended use of pipe Pipe end condition
Rainwater pipe, plastic At drainage U/U 1)
Not at drainage C/C 2)
Drainage or sewage pipe, plastic Ventilated drain U/U 1)
Unventilated drain U/C 1)
Drain w/water trap U/C 1)
Not at drainage C/C 2)
Pipe in closed circuit (water, gas, air, electricity etc.) C/C 2) 3)
Flue gas recovery system pipe, plastic U/C 1)
Pipe with open ends and ≥ 50cm length on both sides, plastic U/U 2)
Pipe supported by suspension system, Fire rated support C/U 1)
metal Non-fire rated U/C 1)
Waste disposal shaft pipe, metal U/C 1)
1)
Stated in EN 1366-3:2009. 2) Polyseam’ s judgment based on tests. 3) Metal pipes should have fire rated support.
Page |9
Surrounding constructions
The wall or floor construction used in a test will limit the scope of certification. The general rule is that the wall or floor thickness
tested will be the minimum allowed thickness of the wall or floor. Also, if a gypsum (flexible) wall is tested then approvals for a
concrete/masonry wall are also obtained, but not the other way around. So if only concrete/masonry walls have been tested, the test
data cannot be used for a gypsum wall. Certifications for floors are only possible by performing floor tests, and this test data cannot be
used to obtain certification for walls.
The standard flexible wall constructions specified in the test standard are:
Nominal minimum Thickness of gypsum board Number of Indicative fire
overall thickness in mm EN 520 Type F in mm layers each side resistance in minutes
69 - 75 12.5 1 30
94 - 100 12.5 2 60
94 - 100 12.5 2 90
122 - 130 15.0 2 120

The standard rigid wall constructions specified in the test standard are:
Thickness of aerated concrete Indicative fire
(650 +/- 200) kg/m3 in mm resistance in minutes
75 +/- 10 30
100 +/- 10 60
125 +/- 10 90
150 +/- 10 120
175 +/- 10 180
200 +/- 10 240

The standard construction for concrete floors shall have a density of (650 +/- 200) kg/m3 and a thickness of 150mm.

P a g e | 10
Supporting constructions and service supports
The supporting constructions (fire rated walls and floors) should be classified in accordance with EN 13501-2 for the required fire
resistance period.
Services in floors should have the first support located 250mm from the top face, and services in walls should have the first support
located 270mm from both faces of the wall. Thereafter the services should be supported according to the support system
manufacturer’s installation instructions.

Mixed services within the same aperture


The systems, Protecta FR Board and Protecta EX Mortar, may be used to provide a
penetration seal with cables, cable trays, metallic pipes, ventilation ducts, composite pipes
and plastic pipes, with and without insulation, with mixed services within the same
seal/aperture. The technical solutions in the following pages can be combined where the fire
seals are built the same, however, the fire and sound classifications will for the whole seal be
no better than the lowest classification given on any through service, what we term ‘worst-
case-scenario’.
The technical solutions on the last pages of this handbook are for mixed services, but do not
include all the different options and are provided as a quick guide. Here you can select the
fire resistance and see what fire stopping system you require for a whole group of services,
this simplifies the engineering and is of course very useful and helpful.

P a g e | 11
Normal on-site problems and solutions
Single sided access
On construction sites there may be cases where an aperture for a fire seal that is to be installed is only accessible from one side. With
many of the Protecta® products this scenario is already tested, certified and included in this handbook, but one issue is the Protecta FR
Board system which requires the sealing of gaps from both sides of a wall after insertion. However this is solvable by using an
additional inner board with the coating facing towards the installer; it will result in the same fire seal as the certified solutions. Below
are the detailed descriptions and this is especially useful with risers or shafts with gypsum boards on only one side.

STEP 1 STEP 2 STEP 3 STEP 4

Install FR Board
Install FR Board Install FR Board 50mm 1-S with the
30mm 1-S with 50mm. This board coated side towards
the coated side does not need to be you flush with the
Frame the aperture with towards you coated. Any FR Pipe wall surface. Any FR
2 layers of 12.5mm Wraps must be Pipe Wraps must be
gypsum boards. This is installed in this board installed in this
not necessary in concrete board as well
or masonry walls

All services and


The depth of the frame All services and openings must be
must be minimum openings must be sealed with FR
130mm, flush with the sealed with FR Acrylic from the
installation side. If the Acrylic from the installation side
frame is deeper than the installation side
wall, the frame must stick
Note: The above descriptions are just showing how to install the FR Board system
out on the backside. If the
from one side. This must be used together with the product approvals for FR Board
wall is deeper than
2 x 50mm 1-S system in drywalls, masonry or concrete walls. The same concept
130mm the frame must
Installation side may be used with the FR Board 2 x 60mm 2-S system in masonry or concrete walls.
have the same depth as
the wall

P a g e | 12
Restrictive fire seals and the pattress solution
Some fire seals in walls can be restrictive, so it is difficult to insert the different pieces of the Protecta FR Board. Therefore Polyseam
has tested a pattress system, where the boards are installed on the surface of the wall instead of inside the aperture. This is then an
additional way of fixing the boards, but the fire classifications will still be limited to the different services given in this handbook, for
drywalls with the system 2 x 50mm 1-S. Furthermore, any FR Pipe Wraps must be included.
There are two ways the pattress system can be installed, as follows:

System 1: The aperture located within the wall System 2: The aperture located towards the soffit

Drywall, masonry or
Concrete floor
concrete wall ≥ 100mm
Maximum aperture
Maximum aperture
1100 x 1100mm
550mm high x
1100mm wide
All services, openings and
50mm FR Board 1-S joints must be sealed
All services, openings and
oversailing aperture with FR Acrylic on both
50mm FR Board 1-S joints must be sealed
by 50mm on both sides
oversailing aperture with FR Acrylic on both
sides of the wall
by 50mm on both sides
sides of the wall,
fixed to the wall on
Board edges must three sides
be coated with FR FR Board fixed with Visible board edges FR Board fixed to wall
Coating on both ≥ 5x100mm single thread must be coated with ≥ 5x100mm single
sides wood, masonry or with FR Coating on thread wood, masonry or
concrete screws and both sides concrete screws and
FR Board bonded to penny washers of steel at penny washers of steel at
the wall with FR 300mm centres FR Board bonded to 300mm centres
Coating on both the wall with FR
sides Coating on both Drywall, masonry or
sides concrete wall ≥ 100mm
Maximum fire classification EI 120, limited by Maximum fire classification EI 120, limited by
the approvals for the penetrating services the approvals for the penetrating services

P a g e | 13
A: Yes. The EuroNorm allows this but tests and approvals for concrete or
FAQ’s masonry walls cannot be used in drywalls.
GENERAL
Q: What certifications are available? Q: I have a cable going through a drywall on one side and it does not
A: The Protecta® fire stopping range has ETA certifications and the CE-mark penetrate the wall, however the instructions show only double sided fire
for Europe and Africa, UL-EU International certifications for Asia and South seals?
America and local certifications for the United Arab Emirates, New Zealand A: Use the normal instructions for double sided seals, the wall boards on
and Australia. the other side will do the same job as the fire seal which will result in a
double sided fire seal.

Q: Where are the products manufactured?


A: The Protecta® range is manufactured at the Polyseam factory in Q: I am to do a fire seal in a swimming pool area and need something
Huddersfield, United Kingdom. moisture proof, what should I use?
A: For smaller seals you can use either the Protecta FR IPT sealant or the FR
Putty Cord. For larger seals you can use Protecta FR Board, but after you
CONSTRUCTIONS have sealed the gaps and openings with FR Acrylic, apply a layer of FR
Coating on top of the acrylic.
Q: I am doing a fire seal in a drywall with calcium silicate boards and not
normal gypsum boards, is that ok?
A: Yes, as long as the wall is classified according to EN 13501-2 for the Q: Can the firestop details given in concrete floors be used in timber floors?
required fire resistance period, and the wall thickness is equal or greater A: No, that is not allowed.
than the approval for the fire stopping product.

FIRE SEALS
Q: I have a fire seal in a floor, can I use the approvals for a drywall?
Q: Is it acceptable that instead of a minimum 100mm depth of Protecta EX
A: No. The EuroNorm states that fire seals in floors have to be tested and
mortar, I can use a 50mm stonewool slab with 50mm depth of mortar?
approved independently from walls.
A: No. But where 50mm depth of mortar on 50mm stonewool is
mentioned, you can use 100mm depth of mortar instead and with no
Q: Can approvals for drywalls be used in concrete walls? stone wool.
P a g e | 14
Q: I have a special fire seal that is not mentioned in any of the solutions,
FAQ’s what do I do?
Q: Do I need to remove a shuttering stone wool board when the shutter is A: Please contact us and we will assess if we can make an Engineering
not shown as part of the approval for EX Mortar in a floor? Judgment.
A: No, the shutter will only increase the fire resistance.

CABLES
Q: A solution states a 12.5mm depth of Protecta FR Acrylic on a 12.5mm
Q: The instructions mention cables, but does that include all types of
backing of stonewool, can I instead seal with 25mm FR Acrylic and skip the
cables?
backing?
A: Yes. We have tested groups of cables which gives approvals for all kinds,
A: Yes, the FR Acrylic will give better fire resistance than the stonewool
including aluminium, copper and fibre optic cables.
backing material so if the total depth is the same or greater this is ok.

Q: There is a solution for a double sided seal with FR Acrylic at 15mm depth PIPES
in a rigid wall. Can I instead seal this single sided at 30mm depth? Q: I have a penetrating pipe made of iron, but it is not mentioned in the
A: No. The fire seal will be weaker as the penetration speed of the fire will instructions?
increase during heating of the material. With a double sided fire seal the A: Iron is the base metal of steel, so use the instructions for steel pipes.
fire has to effectively ‘start again’ when it meets the second seal. However,
as a fire stopping solution it is better to do a single sided seal on both
sides, resulting in a higher fire resistance. Q: I am to fire seal a PE-HD (or HD-PE) pipe, can I use the instructions for PE
pipes?

Q: It is stated that I use stonewool backing with Protecta FR Acrylic, can I A: Yes. You can fire seal all PE pipes that are manufactured to EN 1519-1,
instead use Protecta Backing material? EN 12201-2 and EN 12666-1. This normally includes LD-PE, MD-PE, HD-PE
and PE-X pipes.
A: Yes, the Protecta backing is made of AES fibre which has greater fire
resistant than stonewool. However, if Protecta Backing is stated, you
cannot use a stonewool backing.

P a g e | 15
FAQ’s
Q: It is stated ‘alupex’ pipes in the instructions; can I use Geberit Mepla
MLC pipes?
A: Yes. Alupex is a general term for composite aluminium pipes. They
consist of an aluminium core that is covered on the inner and outer sides
with thin plastic. Some alupex pipes on the market are:

 FRÄNKISCHE alpex F50 PROFI


 GEBERIT Mepla MLC
 JRG Sanipex MT
 KE KELIT Kelox
 REHAU Rautitan stabil
 TECEflex
 UPONOR MLC
 VIEGA Sanfix Fosta

Q: I am to fire seal a Blazemaster cPVC pipe but I have heard it reacts with
fire stopping products?
A: Protecta FR Acrylic should be used; it has been independently tested
and does not react with BlazeMaster or other cPVC pipes.

P a g e | 16
Appendix I
-
Linear seal solutions

P a g e | 17
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease. Protecta FR Acrylic Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Minimum seal depth 25mm Protecta Mineral Fibre BIO
surfaces that cannot tolerate direct contact; Maximum seal width 100mm
appropriate surface preparation should be made Application Fire rated linear seals in rigid
(contact Polyseam for guidance in these cases). For floors or between floors and
paints sensitive to sealing compounds, priming with walls
a PVA primer is recommended.
3. When installing Protecta® FR Acrylic in hollow floor Construction Minimum floor thickness of 150
slabs or boards, fire seals specified as single sided mm and comprise aerated
should be installed from the soffit side of the floor concrete or concrete with a
assuming there is sufficient thickness of concrete minimum density of 650kg/m3.
below the void to follow the installation guide.
Fire & Sound classification
Where this is not the case, tubular voids should be
filled with stone wool normally the same thickness
Single sided top face position
as the depth of the floor slab. Alternatively, simply
EI 180 & E 180
fire seal on both sides.
4. When installing any backing material, cut this slightly Sound reduction (seal only)
oversize and insert into the gap ensuring a tight Backing with Protecta 62 dB
friction fit. Ensure correct depth is achieved. Mineral Fibre BIO
5. Fill the gap or joint with Protecta® FR Acrylic to the minimum 25mm deep
required depth.
6. Apply the sealant generously to prevent air bubbles.
Finish the bead with a moist spatula, pallet knife or
brush.
7. Protecta® FR Acrylic can be over-painted with most
emulsion or alkyd (gloss) paints.

Polyseam Ltd, 15 St Andrews Road,


ETA 13/0879 & 13/0880
Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 24/5/18
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 18
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease. Protecta FR Acrylic Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Minimum seal depth 10mm Stone wool
surfaces that cannot tolerate direct contact; Maximum seal width 100mm
appropriate surface preparation should be made Application Fire rated linear seals in rigid
(contact Polyseam for guidance in these cases). For floors or between floors and
paints sensitive to sealing compounds, priming with walls
a PVA primer is recommended.
3. When installing Protecta® FR Acrylic in hollow floor Construction Minimum floor thickness of 150
slabs or boards, fire seals specified as single sided mm and comprise aerated
should be installed from the soffit side of the floor concrete or concrete with a
assuming there is sufficient thickness of concrete minimum density of 650kg/m3.
below the void to follow the installation guide.
Fire & Sound classification
Where this is not the case, tubular voids should be
filled with stone wool normally the same thickness
Single sided top face position
as the depth of the floor slab. Alternatively, simply
EI 240 & E 240
fire seal on both sides.
4. When installing any backing material, cut this slightly Sound reduction (minimum 12mm depth)
oversize and insert into the gap ensuring a tight Backing with stone wool
62 dB
friction fit. Ensure correct depth is achieved. minimum 90mm deep
5. Fill the gap or joint with Protecta® FR Acrylic to the
required depth.
6. Apply the sealant generously to prevent air bubbles.
Finish the bead with a moist spatula, pallet knife or
brush.
7. Protecta® FR Acrylic can be over-painted with most
emulsion or alkyd (gloss) paints.

Polyseam Ltd, 15 St Andrews Road,


ETA 13/0879 & 13/0880
Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 24/5/18
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 19
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Protecta Mineral Fibre BIO
Backing with Protecta
surfaces that cannot tolerate direct contact;
Mineral Fibre BIO
appropriate surface preparation should be made Application Fire rated linear seals in rigid
minimum 25mm deep
(contact Polyseam for guidance in these cases). For floors or between floors and
paints sensitive to sealing compounds, priming with walls
a PVA primer is recommended.
3. When installing Protecta® FR Acrylic in hollow floor Construction Minimum floor thickness of 150
slabs or boards, fire seals specified as single sided mm and comprise aerated
should be installed from the soffit side of the floor concrete or concrete with a
assuming there is sufficient thickness of concrete minimum density of 650kg/m3.
below the void to follow the installation guide.
Fire & Sound classification
Where this is not the case, tubular voids should be
filled with stone wool normally the same thickness
Single sided soffit face position
as the depth of the floor slab. Alternatively, simply
EI 60 & E 120
fire seal on both sides.
4. When installing any backing material, cut this slightly Sound reduction (seal only)
oversize and insert into the gap ensuring a tight 62 dB
friction fit. Ensure correct depth is achieved.
5. Fill the gap or joint with Protecta® FR Acrylic to the
required depth. Protecta FR Acrylic
6. Apply the sealant generously to prevent air bubbles. Minimum seal depth 25mm
Finish the bead with a moist spatula, pallet knife or Maximum seal width 100mm
brush.
7. Protecta® FR Acrylic can be over-painted with most
emulsion or alkyd (gloss) paints.

Polyseam Ltd, 15 St Andrews Road,


ETA 13/0879 & 13/0880
Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 24/5/18
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 20
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Stone wool
surfaces that cannot tolerate direct contact; Backing with stone wool Protecta FR Acrylic
appropriate surface preparation should be made minimum 25mm deep Minimum seal depth 15mm Application Fire rated linear seals in rigid
(contact Polyseam for guidance in these cases). For floors or between floors and
paints sensitive to sealing compounds, priming with walls
a PVA primer is recommended.
3. When installing any backing material, cut this slightly Construction Minimum floor thickness of 150
oversize and insert into the gap ensuring a tight mm and comprise aerated
friction fit. Ensure correct depth is achieved. concrete or concrete with a
4. Fill the gap or joint with Protecta® FR Acrylic to the minimum density of 650kg/m3.
required depth.
Fire & Sound classification
5. Apply the sealant generously to prevent air bubbles.
Finish the bead with a moist spatula, pallet knife or
Up to 100mm wide double sided seal with low
brush.
density stone wool EI 120 & E 120
6. Protecta® FR Acrylic can be over-painted with most
emulsion or alkyd (gloss) paints. Up to 100mm wide double sided seal with stone
wool ≥ 140kg/m3 EI 180 & E 180

Up to 30mm wide double sided seal with low


density stone wool EI 240 & E 240

Sound reduction (seal only) 62 dB

Polyseam Ltd, 15 St Andrews Road,


ETA 13/0879 & 13/0880 Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 24/5/18
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 21
Client:
Installation Instructions

1. All surfaces must be clean and sound, free from dirt,


grease and other contaminants. The surfaces may be
Job Title:
damp but not running wet. Use a wet brush to clean
surfaces before application to remove loose material Protecta FR IPT Products Protecta FR IPT
and to ensure good contact for adhesion. Primers are Minimum seal depth 25mm Protecta Mineral Fibre BIO
not usually required. Maximum seal width 30mm
2. Cut nozzle to the desired angle and gun firmly into the Application Fire rated, water proof and
joint to give a good solid fill. Strike off the sealant movement linear seals in rigid
flush with the joint sides within ten minutes of floors or between floors and
application, before surface skinning occurs. The walls
sealant will have low shrinkage during cure and if a
flush surface it is recommended to leave the sealant Construction Minimum floor thickness of 150
proud. mm and comprise aerated
3. Protecta® FR IPT can be tooled to a smooth finish using concrete or concrete with a
a moist plastic stick or similar within 30 minutes of minimum density of 650kg/m3.
Fire, Sealant & Sound classification
application. IPT Tooling designed for the optimum
finish is recommended instead of soap and water as
Single sided top face position
it forms a film between the stick and the sealant.
EI 180 & E 240
4. Do not spray the sealant with water or other fluids
before skin formation (<30 min). Uncured sealant is Backing with Protecta Classification CE
soluble in water prior to skinning due to its Mineral Fibre BIO Facade (interior) 25HM
environmentally friendly IPT chemistry that uses minimum 48mm deep Sanitary joints XS1
water instead of solvents.
5. Protecta® FR IPT can be over-painted with most Sound reduction (seal only)
emulsion or alkyd (gloss) paints. 62 dB

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0902
Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 24/5/18
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 22
Client:
Installation Instructions

1. All surfaces must be clean and sound, free from dirt,


grease and other contaminants. The surfaces may be
Job Title:
damp but not running wet. Use a wet brush to clean
surfaces before application to remove loose material
Products Protecta FR IPT
and to ensure good contact for adhesion. Primers Stone wool
are not usually required. Backing with stone wool Protecta FR IPT
2. Cut nozzle to the desired angle and gun firmly into the minimum 20mm deep Minimum seal depth 15mm Application Fire rated, water proof and
joint to give a good solid fill. Strike off the sealant movement linear seals in rigid
flush with the joint sides within ten minutes of floors or between floors and
application, before surface skinning occurs. The walls
sealant will have low shrinkage during cure and if a
flush surface it is recommended to leave the sealant Construction Minimum floor thickness of 150
proud. mm and comprise aerated
3. Protecta® FR IPT can be tooled to a smooth finish using concrete or concrete with a
a moist plastic stick or similar within 30 minutes of minimum density of 650kg/m3.
Fire, Sealant & Sound classification
application. IPT Tooling designed for the optimum
finish is recommended instead of soap and water as
Up to 30mm wide double sided seal with low
it forms a film between the stick and the sealant.
density stone wool
4. Do not spray the sealant with water or other fluids EI 240 & E 240
before skin formation (<30 min). Uncured sealant is
soluble in water prior to skinning due to its Classification CE
environmentally friendly IPT chemistry that uses Facade (interior) 25HM
water instead of solvents. Sanitary joints XS1
5. Protecta® FR IPT can be over-painted with most
emulsion or alkyd (gloss) paints. Sound reduction (seal only)
62 dB

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0902 Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 24/5/18
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 23
Client:
Installation Instructions

1. Before installing Protecta® FR Board ensure that the


surrounding construction is free from all loose
Job Title:
contaminants, dust and grease.
2. The board can be positioned to either side of the
All gaps and openings must be Products Protecta FR Board
construction or anywhere in between. Protecta FR Acrylic
sealed with FR Acrylic both
3. Cut the required board(s) to suit the linear seal
sides
width. All exposed and cut edges of the board can be Application Fire rated linear seals between
sealed with Protecta® FR Coating or Protecta® FR floor slabs or between floor
Acrylic prior to fitting which will act as an adhesive slab and wall
and ensure a smoke tight seal.
4. All joints, gaps or imperfections in the installed seal Construction Minimum floor thickness of 150
must be filled with Protecta® FR Acrylic on both mm and comprise aerated
sides. concrete or concrete with a
5. Protecta® FR Board can be over-painted with most minimum density of 650kg/m3
emulsion or alkyd (gloss) paints.
Fire & Sound classification

Up to 120mm wide seal friction fitted at any


position fully within the cavity
EI 120 & E 240

1 layer 60mm Up to 800mm wide seal friction fitted at any


FR Board 2-S position fully within the cavity
EI 90 & E 120

Sound reduction (seal only)


55 dB

Polyseam Ltd, 15 St Andrews Road,


ETA 13/0673 Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 24/5/18
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 24
Client:
Installation Instructions

1. Ensure the faces of the aperture opening are free of


dust and any other contaminants. The faces may be
Job Title:
moistened for better adhesion.
2. Bare metal in contact with the seal must be
Products Protecta EX Mortar
protected against corrosion using a suitable Stone wool shutter
primer/protection system.
Protecta EX Mortar
3. The seal can be positioned to either side of the Application Fire rated linear seals between
Minimum seal depth 50mm
construction or anywhere in between. floor slabs or between floor
4. When installing Protecta® EX Mortar in hollow floor slab and wall
slabs or boards, tubular voids should be filled with
stone wool normally the same thickness as the Construction Minimum floor thickness of 150
depth of the floor slab. mm and comprise aerated
5. Install a stone wool shutter board to achieve the concrete or concrete with a
required thickness of mortar. Make sure that this minimum density of 650kg/m3
achieves a very tight seal – any small openings
Fire & Sound classification
should be sealed with Protecta® FR Acrylic
6. Pour clean water into a suitable mixing vessel and
Up to 800mm wide seal at any position fully
pour enough mortar to obtain the required
within the cavity
consistency. Mix well to avoid lumps. Always add the EI 180 & E 180
mortar to the water, do not reverse this mixing
process. For different mix ratios and drying times, Sound reduction (seal only)
50mm stone wool
please refer to the Technical Data Sheet. 64 dB
shutter ≥ 150kg/m3
7. Once the desired consistency is achieved pour or
trowel the mortar onto the shutter board making
sure that it flows into all corners and around
services. Apply a firm pressure to the mortar to
eliminate any trapped air bubbles. Build up to the
required depth.

Polyseam Ltd, 15 St Andrews Road,


ETA 13/0672
Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 24/5/18
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 25
Client:
Installation Instructions

1. Ensure the faces of the aperture opening are free of


dust and any other contaminants. The faces may be
Job Title:
moistened for better adhesion.
2. Bare metal in contact with the seal must be
Products Protecta EX Mortar
protected against corrosion using a suitable
primer/protection system. Application Fire rated and loadbearing
Protecta EX Mortar
3. The seal can be positioned to either side of the linear seals between floor slabs
Minimum seal depth 100mm
construction or anywhere in between. or between floor slab and wall
4. When installing Protecta® EX Mortar in hollow floor
slabs or boards, level the fire seal with the soffit side. Construction Minimum floor thickness of 150
Ensure there is sufficient thickness of concrete mm and comprise aerated
below the void for the depth of mortar. Where this concrete or concrete with a
is not the case, tubular voids should be filled with minimum density of 650kg/m3
stone wool normally the same thickness as the
depth of the floor slab. Alternatively, simply fire seal
Fire & Sound classification
on both sides.
5. Install a shutter board to achieve the required
Up to 800mm wide seal at any position fully
thickness of mortar. Make sure that this achieves a
within the cavity
very tight seal. EI 240 & E 240
6. Pour clean water into a suitable mixing vessel and
pour enough mortar to obtain the required Sound reduction (seal only)
consistency. Mix well to avoid lumps. Always add the 64 dB
mortar to the water, do not reverse this mixing
process. For different mix ratios and drying times,
please refer to the Technical Data Sheet.
7. Once the desired consistency is achieved pour or
trowel the mortar onto the shutter board making
sure that it flows into all corners and around
services. Apply a firm pressure to the mortar to
eliminate any trapped air bubbles. Build up to the
required depth.

Loadbearing Properties

Soft body impact, serviceability 500Nm. Soft body impact, safety in use 700Nm. Hard body impact
serviceability 6Nm. Hard body impact, safety in use 10Nm. Concentrated load up to 15kN. Polyseam Ltd, 15 St Andrews Road,
ETA 13/0672
Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 24/5/18
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 26
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Stone wool
surfaces that cannot tolerate direct contact; Application Fire rated linear seals in rigid
appropriate surface preparation should be made walls or between wall and floor
(contact Polyseam for guidance in these cases). For Construction Minimum wall thickness of 150
paints sensitive to sealing compounds, priming with mm and comprise concrete,
a PVA primer is recommended. aerated concrete or masonry,
3. When installing any backing material, cut this slightly Protecta FR Acrylic with a density of ≥ 650 kg/m3
oversize and insert into the gap ensuring a tight Backing with stone wool
friction fit. Ensure correct depth is achieved. Fire & Sound classification
4. Fill the gap or joint with Protecta® FR Acrylic to the
required depth. Single sided horizontal seal with minimum seal
depth 25mm, max seal width 30mm and
5. Apply the sealant generously to prevent air bubbles.
backing minimum 20mm deep EI 60 & E 240
Finish the bead with a moist spatula, pallet knife or
brush.
Single sided horizontal seal with minimum seal
6. Protecta® FR Acrylic can be over-painted with most depth 10mm, max seal width 50mm and
emulsion or alkyd (gloss) paints. backing minimum 60mm deep EI 60 & E 240

Single sided vertical seal with minimum seal


depth 10mm, max seal width 50mm and
backing minimum 60mm deep EI 120 & E 120

Sound reduction (minimum depth 12mm) 62 dB

Polyseam Ltd, 15 St Andrews Road,


ETA 13/0879 & 13/0880 Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 24/5/18
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 27
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Protecta Mineral Fibre BIO
surfaces that cannot tolerate direct contact;
appropriate surface preparation should be made Application Fire rated linear seals in rigid
(contact Polyseam for guidance in these cases). For walls or between wall and floor
paints sensitive to sealing compounds, priming with Protecta FR Acrylic
a PVA primer is recommended. Minimum seal depth Construction Minimum wall thickness of 150
3. When installing any backing material, cut this slightly Backing with Protecta mm and comprise concrete,
25mm. Maximum
oversize and insert into the gap ensuring a tight Mineral Fibre BIO aerated concrete or masonry,
seal width 30mm
friction fit. Ensure correct depth is achieved. minimum 48mm deep with a density of ≥ 650 kg/m3
4. Fill the gap or joint with Protecta® FR Acrylic to the
required depth.
Fire & Sound classification
5. Apply the sealant generously to prevent air bubbles.
Finish the bead with a moist spatula, pallet knife or
Single sided horizontal seal
brush.
EI 120 & E 240
6. Protecta® FR Acrylic can be over-painted with most
emulsion or alkyd (gloss) paints. Sound reduction (seal only)
62 dB

Polyseam Ltd, 15 St Andrews Road,


ETA 13/0879 & 13/0880
Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 24/5/18
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 28
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Stone wool
surfaces that cannot tolerate direct contact;
appropriate surface preparation should be made Application Fire rated linear seals in rigid
(contact Polyseam for guidance in these cases). For walls or between wall and floor
paints sensitive to sealing compounds, priming with
a PVA primer is recommended. Protecta FR Acrylic Construction Minimum wall thickness of 150
3. When installing any backing material, cut this slightly Minimum seal depth mm and comprise concrete,
oversize and insert into the gap ensuring a tight Backing with stone wool 15mm. Maximum aerated concrete or masonry,
friction fit. Ensure correct depth is achieved. minimum 20mm deep seal width 30mm with a density of ≥ 650 kg/m3
4. Fill the gap or joint with Protecta® FR Acrylic to the
required depth.
Fire & Sound classification
5. Apply the sealant generously to prevent air bubbles.
Finish the bead with a moist spatula, pallet knife or
Double sided in horizontal or vertical seals
brush.
EI 240 & E 240
6. Protecta® FR Acrylic can be over-painted with most
emulsion or alkyd (gloss) paints. Sound reduction (seal only)
62 dB

Polyseam Ltd, 15 St Andrews Road,


ETA 13/0879 & 13/0880
Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 24/5/18
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 29
Client:
Installation Instructions

1. All surfaces must be clean and sound, free from dirt,


grease and other contaminants. The surfaces may be
Job Title:
damp but not running wet. Use a wet brush to clean
surfaces before application to remove loose material
Products Protecta FR IPT
and to ensure good contact for adhesion. Primers Stone wool
are not usually required.
2. Cut nozzle to the desired angle and gun firmly into Application Fire rated, water proof and
the joint to give a good solid fill. Strike off the sealant movement linear seals in rigid
flush with the joint sides within ten minutes of Protecta FR IPT walls or between wall and floor
application, before surface skinning occurs. The Minimum seal depth
sealant will have low shrinkage during cure and if a 15mm. Maximum Construction Minimum wall thickness of 150
Backing with stone wool
flush surface it is recommended to leave the sealant seal width 30mm mm and comprise concrete,
minimum 45mm deep aerated concrete or masonry,
proud.
3. Protecta® FR IPT can be tooled to a smooth finish with a density of ≥ 650 kg/m3
using a moist plastic stick or similar within 30
Fire & Sound classification
minutes of application. IPT Tooling designed for the
optimum finish is recommended instead of soap and
Single sided in horizontal seals
water as it forms a film between the stick and the
EI 60 & E 240
sealant.
4. Do not spray the sealant with water or other fluids Classification CE
before skin formation (<30 min). Uncured sealant is Facade (interior) 25HM
soluble in water prior to skinning due to its Sanitary joints XS1
environmentally friendly IPT chemistry that uses
water instead of solvents. Sound reduction (seal only)
5. Protecta® FR IPT can be over-painted with most 62 dB
emulsion or alkyd (gloss) paints.

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0902
Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 9/7/19
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 30
Client:
Installation Instructions

1. All surfaces must be clean and sound, free from dirt,


grease and other contaminants. The surfaces may be
Job Title:
damp but not running wet. Use a wet brush to clean
surfaces before application to remove loose material
Products Protecta FR IPT
and to ensure good contact for adhesion. Primers Stone wool
are not usually required. Application Fire rated, water proof and
2. Cut nozzle to the desired angle and gun firmly into movement linear seals in rigid
the joint to give a good solid fill. Strike off the sealant walls or between wall and floor
flush with the joint sides within ten minutes of Construction Minimum wall thickness of 100
application, before surface skinning occurs. The mm and comprise concrete,
sealant will have low shrinkage during cure and if a aerated concrete or masonry,
flush surface it is recommended to leave the sealant Protecta FR IPT with a density of ≥ 650 kg/m3
proud. Backing with stone wool Fire, Sealant & Sound classification
3. Protecta® FR IPT can be tooled to a smooth finish
using a moist plastic stick or similar within 30 Double sided horizontal or vertical seals with
minimum seal depth 12.5mm, max seal width
minutes of application. IPT Tooling designed for the
30mm and backing minimum 12.5mm deep
optimum finish is recommended instead of soap and
EI 120 & E 120
water as it forms a film between the stick and the
sealant. Double sided horizontal seals with minimum
4. Do not spray the sealant with water or other fluids seal depth 15mm, max seal width 30mm and
before skin formation (<30 min). Uncured sealant is backing minimum 45mm deep EI 240 & E 240
soluble in water prior to skinning due to its
environmentally friendly IPT chemistry that uses Classification CE Facade (interior) 25HM
water instead of solvents. Sanitary joints XS1
5. Protecta® FR IPT can be over-painted with most
emulsion or alkyd (gloss) paints. Sound reduction (seal only) 62 dB

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0902 Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 9/7/19
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 31
Client:
Installation Instructions

1. Before installing Protecta® FR Board ensure that the


surrounding construction is free from all loose
Job Title:
contaminants, dust and grease.
2. The board can be positioned to either side of the
Products Protecta FR Board
construction or anywhere in between. Protecta FR Acrylic
3. Cut the required board(s) to suit the linear seal
width. All exposed and cut edges of the board can be Application Fire rated linear seals in rigid
sealed with Protecta® FR Coating or Protecta® FR walls or between wall and floor
Acrylic prior to fitting which will act as an adhesive
and ensure a smoke tight seal. Construction Minimum wall thickness of 150
4. All joints, gaps or imperfections in the installed seal mm and comprise concrete,
must be filled with Protecta® FR Acrylic on both aerated concrete or masonry,
sides. 1 layer 60mm All gaps and openings with a density of ≥ 650 kg/m3
5. Protecta® FR Board can be over-painted with most FR Board 2-S must be sealed with
emulsion or alkyd (gloss) paints. FR Acrylic both sides
Fire & Sound classification

Up to 1200mm wide horizontal seals friction


fitted at any position fully within the cavity
EI 90 & E 240

Sound reduction (seal only)


55 dB

Polyseam Ltd, 15 St Andrews Road,


ETA 13/0673
Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 24/5/18
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 32
Client:
Installation Instructions

1. Before installing Protecta® FR Board ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Board
2. The boards should be flush with the surface of the Protecta FR Acrylic
construction on both sides to maximize the fire
resistance. Application Fire rated linear seals in rigid
3. Cut the required board(s) to suit the linear seal walls or between wall and floor
width. All exposed and cut edges of the board can be
sealed with Protecta® FR Coating or Protecta® FR Construction Minimum wall thickness of 100
Acrylic prior to fitting which will act as an adhesive mm and comprise concrete,
and ensure a smoke tight seal. aerated concrete or masonry,
2 layers 50mm with a density of ≥ 650 kg/m3
4. All joints, gaps or imperfections in the installed seal All gaps and openings
FR Board 1-S
must be filled with Protecta® FR Acrylic on both must be sealed with
sides. FR Acrylic both sides
Fire & Sound classification
5. Protecta® FR Board can be over-painted with most
emulsion or alkyd (gloss) paints.
Up to 1200mm wide horizontal seals friction
fitted at any position fully within the cavity
EI 120 & E 120

Sound reduction (seal only)


55 dB

Polyseam Ltd, 15 St Andrews Road,


ETA 13/0673
Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 24/5/18
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 33
Client:
Installation Instructions

1. Before installing Protecta® FR Board ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Board
2. The boards should be flush with the surface of the Protecta FR Acrylic
construction on both sides to maximize the fire
resistance. If this is not possible, there should be an Application Fire rated linear seals in rigid
air gap of at least 30mm between the boards. walls or between wall and floor
3. Cut the required board(s) to suit the linear seal
width. All exposed and cut edges of the board can be Construction Minimum wall thickness of 150
sealed with Protecta® FR Coating or Protecta® FR mm and comprise concrete,
Acrylic prior to fitting which will act as an adhesive aerated concrete or masonry,
2 layers 60mm with a density of ≥ 650 kg/m3
and ensure a smoke tight seal. All gaps and openings
FR Board 2-S
4. All joints, gaps or imperfections in the installed seal must be sealed with
must be filled with Protecta® FR Acrylic on both FR Acrylic both sides
Fire & Sound classification
sides.
5. Protecta® FR Board can be over-painted with most
Up to 1200mm wide horizontal seals flush with
emulsion or alkyd (gloss) paints.
the surface on both sides fully within the cavity
EI 180 & E 240

Sound reduction (seal only)


55 dB

Polyseam Ltd, 15 St Andrews Road,


ETA 13/0673
Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 24/5/18
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 34
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all surrounding construction is free from
Job Title:
all loose contaminants, dust and grease.
2. Where Protecta® FR Acrylic is to be installed against
Products Protecta FR Acrylic
surfaces that cannot tolerate direct contact;
appropriate surface preparation should be made Application Fire rated linear seals in flexible
(contact Polyseam for guidance in these cases). For walls
paints sensitive to sealing compounds, priming with
a PVA primer is recommended. Construction Minimum wall thickness of 75
3. When installing the sealant in gypsum boards, the Protecta FR Acrylic mm and comprise steel studs
exposed edges of the board can be wetted with Minimum seal depth or timber studs* lined on both
water, or Protecta® FR Acrylic diluted with water to Steel partition track 12.5mm faces with minimum 1 layer of
prime the surfaces helping adhesion and preventing 12.5 mm thick boards.
excessive joint shrinkage.
4. Fill the gap or joint with Protecta® FR Acrylic to the
Fire & Sound classification
required depth.
5. Apply the sealant generously to prevent air bubbles.
Both sides in horizontal seals with maximum
Finish the bead with a moist spatula, pallet knife or
seal width 25mm EI 45 & E 60
brush.
6. Protecta® FR Acrylic can be over-painted with most Both sides in vertical seals with maximum seal
emulsion or alkyd (gloss) paints. width 15mm EI 45 & E 60

Sound reduction (seal only) 62 dB

Polyseam Ltd, 15 St Andrews Road,


ETA 13/0879 & 13/0880
Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 8/4/18
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 35
Client:
Installation Instructions

1. All surfaces must be clean and sound, free from dirt,


grease and other contaminants. The surfaces may be
Job Title:
damp but not running wet. Use a wet brush to clean
surfaces before application to remove loose material
Products Protecta FR IPT
and to ensure good contact for adhesion. Primers
are not usually required. Application Fire rated, water proof and
2. Cut nozzle to the desired angle and gun firmly into movement linear seals in
the joint to give a good solid fill. Strike off the sealant flexible walls
flush with the joint sides within ten minutes of
application, before surface skinning occurs. The Protecta FR IPT Construction Minimum wall thickness of 75
sealant will have low shrinkage during cure and if a Minimum seal depth mm and comprise steel studs
flush surface it is recommended to leave the sealant Steel partition track 12.5mm or timber studs* lined on both
proud. faces with minimum 1 layer of
3. Protecta® FR IPT can be tooled to a smooth finish 12.5 mm thick boards.
using a moist plastic stick or similar within 30
minutes of application. IPT Tooling designed for the
Fire & Sound classification
optimum finish is recommended instead of soap and
water as it forms a film between the stick and the
Both sides in horizontal seals with maximum
sealant. seal width 25mm EI 45 & E 60
4. Do not spray the sealant with water or other fluids
before skin formation (<30 min). Uncured sealant is Classification CE Facade (interior) 25HM
soluble in water prior to skinning due to its Sanitary joints XS1
environmentally friendly IPT chemistry that uses
water instead of solvents. Sound reduction (seal only) 62 dB
5. Protecta® FR IPT can be over-painted with most
emulsion or alkyd (gloss) paints.

Polyseam Ltd, 15 St Andrews Road,


Huddersfield, West Yorkshire, HD1 6SB
ETA 18/0902
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 2/7/19
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 36
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all surrounding construction is free from
Job Title:
all loose contaminants, dust and grease.
2. Where Protecta® FR Acrylic is to be installed against
Products Protecta FR Acrylic
surfaces that cannot tolerate direct contact;
appropriate surface preparation should be made Application Fire rated linear seals in flexible
(contact Polyseam for guidance in these cases). For walls
paints sensitive to sealing compounds, priming with
a PVA primer is recommended. Construction Minimum wall thickness of 100
3. When installing the sealant in gypsum boards, the Protecta FR Acrylic mm and comprise steel studs
exposed edges of the board can be wetted with Minimum seal depth or timber studs* lined on both
water, or Protecta® FR Acrylic diluted with water to Steel partition track 12.5mm faces with minimum 2 layers of
prime the surfaces helping adhesion and preventing 12.5 mm thick boards.
excessive joint shrinkage.
4. Fill the gap or joint with Protecta® FR Acrylic to the
Fire & Sound classification
required depth.
5. Apply the sealant generously to prevent air bubbles.
Both sides in horizontal seals with maximum
Finish the bead with a moist spatula, pallet knife or
seal width 25mm EI 90 & E 90
brush.
6. Protecta® FR Acrylic can be over-painted with most Both sides in vertical seals with maximum seal
emulsion or alkyd (gloss) paints. width 15mm EI 90 & E 90

Sound reduction (seal only) 62 dB

Polyseam Ltd, 15 St Andrews Road,


ETA 13/0879 & 13/0880
Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 8/4/18
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 37
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all surrounding construction is free from
Job Title:
all loose contaminants, dust and grease.
2. Where Protecta® FR Acrylic is to be installed against
Products Protecta FR Acrylic
surfaces that cannot tolerate direct contact; Stone wool
appropriate surface preparation should be made
(contact Polyseam for guidance in these cases). For Application Fire rated linear seals in flexible
paints sensitive to sealing compounds, priming with walls
a PVA primer is recommended.
3. When installing the sealant in gypsum boards, the Protecta FR Acrylic Construction Minimum wall thickness of 100
Backing with mineral Minimum seal depth
exposed edges of the board can be wetted with mm and comprise steel studs
stone wool minimum 12.5mm or timber studs* lined on both
water, or Protecta® FR Acrylic diluted with water to
12.5mm deep against faces with minimum 2 layers of
prime the surfaces helping adhesion and preventing
steel partition track 12.5 mm thick boards.
excessive joint shrinkage.
4. When installing any backing material, cut this slightly
Fire & Sound classification
oversize and insert into the gap ensuring a tight
friction fit. Ensure correct depth is achieved.
Both sides in horizontal seals with maximum
5. Fill the gap or joint with Protecta® FR Acrylic to the
seal width 30mm EI 120 & E 120
required depth.
6. Apply the sealant generously to prevent air bubbles. Both sides in vertical seals with maximum seal
Finish the bead with a moist spatula, pallet knife or width 15mm EI 90 & E 90
brush.
7. Protecta® FR Acrylic can be over-painted with most Sound reduction (seal only) 62 dB
emulsion or alkyd (gloss) paints.

Polyseam Ltd, 15 St Andrews Road,


ETA 13/0879 & 13/0880
Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 8/4/18
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 38
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all surrounding construction is free from
Job Title:
all loose contaminants, dust and grease.
2. Where Protecta® FR Acrylic is to be installed against
Products Protecta FR Acrylic
surfaces that cannot tolerate direct contact;
appropriate surface preparation should be made Application Fire rated linear seals in flexible
(contact Polyseam for guidance in these cases). For walls
paints sensitive to sealing compounds, priming with
a PVA primer is recommended. Construction Minimum wall thickness of 100
3. When installing the sealant in gypsum boards, the Protecta FR Acrylic mm and comprise steel studs
exposed edges of the board can be wetted with Minimum seal depth or timber studs* lined on both
water, or Protecta® FR Acrylic diluted with water to 25mm faces with minimum 2 layers of
Steel partition track 12.5 mm thick boards.
prime the surfaces helping adhesion and preventing
excessive joint shrinkage.
4. Fill the gap or joint with Protecta® FR Acrylic to the
Fire & Sound classification
required depth.
5. Apply the sealant generously to prevent air bubbles.
Both sides in horizontal seals with maximum
Finish the bead with a moist spatula, pallet knife or
seal width 30mm EI 120 & E 120
brush.
6. Protecta® FR Acrylic can be over-painted with most Both sides in vertical seals with maximum seal
emulsion or alkyd (gloss) paints. width 15mm EI 90 & E 90

Sound reduction (seal only) 62 dB

Polyseam Ltd, 15 St Andrews Road,


ETA 13/0879 & 13/0880
Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 8/4/18
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 39
Client:
Installation Instructions

1. All surfaces must be clean and sound, free from dirt,


grease and other contaminants. The surfaces may be
Job Title:
damp but not running wet. Use a wet brush to clean
surfaces before application to remove loose material
Products Protecta FR IPT
and to ensure good contact for adhesion. Primers
are not usually required. Application Fire rated, water proof and
2. Cut nozzle to the desired angle and gun firmly into movement linear seals in
the joint to give a good solid fill. Strike off the sealant flexible walls
flush with the joint sides within ten minutes of
application, before surface skinning occurs. The Protecta FR IPT Construction Minimum wall thickness of 100
sealant will have low shrinkage during cure and if a Minimum seal depth mm and comprise steel studs
flush surface it is recommended to leave the sealant Steel partition track 12.5mm or timber studs* lined on both
proud. faces with minimum 2 layers of
3. Protecta® FR IPT can be tooled to a smooth finish 12.5 mm thick boards.
using a moist plastic stick or similar within 30
Fire & Sound classification
minutes of application. IPT Tooling designed for the
optimum finish is recommended instead of soap and
Both sides in horizontal seals with maximum
water as it forms a film between the stick and the
seal width 25mm EI 60 & E 90
sealant.
4. Do not spray the sealant with water or other fluids Both sides in vertical seals with maximum seal
before skin formation (<30 min). Uncured sealant is width 15mm EI 120 & E 120
soluble in water prior to skinning due to its
environmentally friendly IPT chemistry that uses Classification CE Facade (interior) 25HM
water instead of solvents. Sanitary joints XS1
5. Protecta® FR IPT can be over-painted with most
emulsion or alkyd (gloss) paints. Sound reduction (seal only) 62 dB

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0902 Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 8/7/19
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 40
Client:
Installation Instructions

1. All surfaces must be clean and sound, free from dirt,


grease and other contaminants. The surfaces may be
Job Title:
damp but not running wet. Use a wet brush to clean
surfaces before application to remove loose material
Products Protecta FR IPT
and to ensure good contact for adhesion. Primers Stone wool
are not usually required.
2. Cut nozzle to the desired angle and gun firmly into the Application Fire rated, water proof and
joint to give a good solid fill. Strike off the sealant movement linear seals in
flush with the joint sides within ten minutes of Backing with mineral Protecta FR IPT flexible walls
application, before surface skinning occurs. The stone wool minimum Minimum seal depth
sealant will have low shrinkage during cure and if a 12.5mm Construction Minimum wall thickness of 100
12.5mm deep against
flush surface it is recommended to leave the sealant mm and comprise steel studs
steel partition track
proud. or timber studs* lined on both
3. Protecta® FR IPT can be tooled to a smooth finish using faces with minimum 2 layers of
a moist plastic stick or similar within 30 minutes of 12.5 mm thick boards.
application. IPT Tooling designed for the optimum
Fire, Sealant & Sound classification
finish is recommended instead of soap and water as
it forms a film between the stick and the sealant.
Both sides in horizontal and vertical seals with
4. Do not spray the sealant with water or other fluids maximum seal width 30mm EI 120 & E 120
before skin formation (<30 min). Uncured sealant is
soluble in water prior to skinning due to its Classification CE Facade (interior) 25HM
environmentally friendly IPT chemistry that uses Sanitary joints XS1
water instead of solvents.
5. Protecta® FR IPT can be over-painted with most Sound reduction (seal only) 62 dB
emulsion or alkyd (gloss) paints.

Polyseam Ltd, 15 St Andrews Road,


Huddersfield, West Yorkshire, HD1 6SB
ETA 18/0902
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 8/4/18
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 41
Client:
Installation Instructions

1. Before installing Protecta® FR Board ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Board
2. The coated side of the board should be flush with the Protecta FR Acrylic
surface of the gypsum on both sides. In seals longer
than 2400mm, uninterrupted separating studs will Application Fire rated linear seals in flexible
be required at 2400mm centres or less. walls
3. Cut the required board(s) to suit the linear seal
width. All exposed and cut edges of the board can be Construction Minimum wall thickness of 100
sealed with Protecta® FR Coating or Protecta® FR mm and comprise steel studs
Acrylic prior to fitting which will act as an adhesive or timber studs* lined on both
2 layers 50mm faces with minimum 2 layers of
and ensure a smoke tight seal. All gaps and openings
FR Board 1-S 12.5 mm thick boards
4. All joints, gaps or imperfections in the installed seal must be sealed with
must be filled with Protecta® FR Acrylic on both FR Acrylic both sides
Fire & Sound classification
sides.
5. Protecta® FR Board can be over-painted with most
Up to 1200mm wide horizontal seals flush with
emulsion or alkyd (gloss) paints.
the surface on both sides fully within the cavity
EI 120 & E 120

Sound reduction (seal only)


55 dB

Polyseam Ltd, 15 St Andrews Road,


ETA 13/0673
Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 24/5/18
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 42
Appendix II
-
Service penetration solutions with gaps ≤ 10mm

P a g e | 43
Client:
Installation Instructions

1. Before installing Protecta® FR Putty Cord ensure that


Job Title:
the surface of all service penetrations and
surrounding construction is wiped clean, dry, free
from all loose contaminants, dust, oils and grease.
Products Protecta FR Putty Cord Ø15mm
2. Place the Putty Cord around the services so that it Apertures with less
seals the services to the floor all the way round. than 10mm annular Application Fire stopping of cables in rigid
width around services floors
3. Press the Putty Cord into the floor and services with
your thumbs to form a fillet or V shape joint, Protecta FR Putty Cord Construction Minimum floor thickness of 150
ensuring good contact is made all the way round the on top side oversailing mm and comprise aerated
services and the floor. the aperture concrete or concrete with a
minimum density of 650kg/m3

Fire & Sound classification

Single cables ≤ Ø 21mm EI 120 & E 120

Single cables ≤ Ø 50mm EI 90 & E 120

Single cables ≤ Ø 80mm EI 60 & E 120

Cables ≤ Ø 21mm in tied bundles ≤ Ø 50mm


EI 60 & E 120

Cables

Polyseam Ltd, 15 St Andrews Road,


Huddersfield, West Yorkshire, HD1 6SB
ETA 16/0322
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 29/5/18
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 44
Client:
Installation Instructions

1. Before fitting the collar ensure that any gaps


between the cable bundle and the separating
Job Title:
element are sealed with a bead of Protecta® FR
Acrylic to cover the opening.
Apertures with less Products Protecta FR Collar
2. Place a suitable collar around the cable bundle and than 10mm annular Protecta FR Acrylic
ensure that the collar shell and fixing lugs are width around services
positioned tightly to the surface of the floor, so that Application Fire stopping of plastic pipes in
the fixings can be inserted fully. rigid floors
Any gaps must be sealed
3. Where the surface is uneven, apply a sealing bead of Cable bundle with a bead of Protecta Construction Minimum floor thickness of 150
Protecta® FR Acrylic between the floor and the collar FR Acrylic on soffit side mm and comprise aerated
shell. concrete or concrete with a
minimum density of 650kg/m3
4. Attach the collar with ≥ Ø4 x 40mm long masonry
screws or expansion bolts. Fire & Sound classification

Cables ≤ Ø 21mm, in a bundle ≤ Ø55mm, with


collars ≤ Ø55mm at ≥ 30mm height
EI 120 & E 120
Cables ≤ Ø 21mm, in a bundle ≤ Ø100mm, with
collars ≤ Ø110mm at ≥ 50mm height
EI 90 & E 90
Cables ≤ Ø 21mm, in a bundle ≤ Ø160mm, with
collars ≤ Ø160mm at ≥ 60mm height
Masonry screws Protecta FR Collar EI 180 & E 180
or expansion bolts on soffit side
Sound reduction (seal only) 58dB

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0854
Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 27/7/19
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 45
Client:
Installation Instructions

1. Before installing Protecta® FR Putty Cord ensure that


Job Title:
the surface of all service penetrations and
surrounding construction is wiped clean, dry, free
from all loose contaminants, dust, oils and grease.
Products Protecta FR Putty Cord Ø15mm
2. Place the Putty Cord around the services so that it Apertures with less
seals the services to the floor all the way round. than 10mm annular Application Fire stopping of steel pipes in
width around services rigid floors
3. Press the Putty Cord into the floor and services with
your thumbs to form a fillet or V shape joint, Protecta FR Putty Cord Construction Minimum floor thickness of 150
ensuring good contact is made all the way round the on top side oversailing mm and comprise aerated
services and the floor. the aperture concrete or concrete with a
minimum density of 650kg/m3

Fire & Sound classification

Steel pipes ≤ Ø 22mm


EI 120 C/U & E 120 C/U

Steel pipes

Polyseam Ltd, 15 St Andrews Road,


Huddersfield, West Yorkshire, HD1 6SB
ETA 16/0322
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 29/5/18
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 46
Client:
Installation Instructions

1. Before installing Protecta® FR Putty Cord ensure that


Job Title:
the surface of all service penetrations and
surrounding construction is wiped clean, dry, free
from all loose contaminants, dust, oils and grease.
Products Protecta FR Putty Cord Ø15mm
2. Place the Putty Cord around the services so that it Apertures with less
seals the services to the floor all the way round. than 10mm annular Application Fire stopping of steel pipes in
width around services rigid floors
3. Press the Putty Cord into the floor and services with
your thumbs to form a fillet or V shape joint, Protecta FR Putty Cord Construction Minimum floor thickness of 150
ensuring good contact is made all the way round the on top side oversailing mm and comprise aerated
services and the floor. the aperture concrete or concrete with a
minimum density of 650kg/m3

Fire & Sound classification

Steel pipes ≤ Ø40mm with 20mm thick


continuous pipe insulation
EI 240 C/U & E 240 C/U

Steel pipes ≤ Ø324mm with 30-80mm thick


continuous pipe insulation
EI 240 C/U & E 240 C/U
Pipe insulation of stone
wool ≥ 80kg/m3

Steel pipes

Polyseam Ltd, 15 St Andrews Road,


Huddersfield, West Yorkshire, HD1 6SB
ETA 16/0322
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 11/11/18
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 47
Client:
Installation Instructions

1. Before installing Protecta® FR Putty Cord ensure that


Job Title:
the surface of all service penetrations and
surrounding construction is wiped clean, dry, free
from all loose contaminants, dust, oils and grease.
Products Protecta FR Putty Cord Ø15mm
2. Place the Putty Cord around the services so that it Apertures with less
seals the services to the floor all the way round. than 10mm annular Application Fire stopping of steel pipes in
width around services rigid floors
3. Press the Putty Cord into the floor and services with
your thumbs to form a fillet or V shape joint, Protecta FR Putty Cord Construction Minimum floor thickness of 150
ensuring good contact is made all the way round the on top side oversailing mm and comprise aerated
services and the floor. the aperture concrete or concrete with a
minimum density of 650kg/m3

Fire & Sound classification

Steel pipes ≤ Ø40mm with ≥ 20mm thick pipe


insulation
EI 240 C/U & E 240 C/U

Steel pipes ≤ Ø324mm with ≥ 30mm thick pipe


insulation
EI 60 C/U & E 240 C/U
Pipe insulation of stone
wool ≥ 80kg/m3
≥ 50cm on both sides

Steel pipes

Polyseam Ltd, 15 St Andrews Road,


Huddersfield, West Yorkshire, HD1 6SB
ETA 16/0322
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 29/5/18
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 48
Client:
Installation Instructions

1. Before installing Protecta® FR Putty Cord ensure that


Job Title:
the surface of all service penetrations and
surrounding construction is wiped clean, dry, free
from all loose contaminants, dust, oils and grease.
Products Protecta FR Putty Cord Ø15mm
2. Place the Putty Cord around the services so that it Apertures with less
seals the services to the floor all the way round. than 10mm annular Application Fire stopping of copper pipes in
width around services rigid floors
3. Press the Putty Cord into the floor and services with
your thumbs to form a fillet or V shape joint, Protecta FR Putty Cord Construction Minimum floor thickness of 150
ensuring good contact is made all the way round the on top side oversailing mm and comprise aerated
services and the floor. the aperture concrete or concrete with a
minimum density of 650kg/m3

Fire & Sound classification

Copper pipes ≤ Ø 6mm


EI 120 C/C & E 120 C/C

Copper pipes ≤ Ø 10mm


EI 90 C/C & E 120 C/C

Copper pipes

Polyseam Ltd, 15 St Andrews Road,


Huddersfield, West Yorkshire, HD1 6SB
ETA 16/0322
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 29/5/18
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 49
Client:
Installation Instructions

1. Before installing Protecta® FR Putty Cord ensure that


Job Title:
the surface of all service penetrations and
surrounding construction is wiped clean, dry, free
from all loose contaminants, dust, oils and grease.
Products Protecta FR Putty Cord Ø15mm
2. Place the Putty Cord around the services so that it Apertures with less
seals the services to the floor all the way round. than 10mm annular Application Fire stopping of copper pipes in
width around services rigid floors
3. Press the Putty Cord into the floor and services with
your thumbs to form a fillet or V shape joint, Protecta FR Putty Cord Construction Minimum floor thickness of 150
ensuring good contact is made all the way round the on top side oversailing mm and comprise aerated
services and the floor. the aperture concrete or concrete with a
minimum density of 650kg/m3

Fire & Sound classification

Copper pipes ≤ Ø12mm with 20mm thick


continuous pipe insulation
EI 240 C/C & E 240 C/C

Copper pipes ≤ Ø54mm with 30-80mm thick


continuous pipe insulation
EI 240 C/C & E 240 C/C
Pipe insulation of stone
wool ≥ 80kg/m3

Copper pipes

Polyseam Ltd, 15 St Andrews Road,


Huddersfield, West Yorkshire, HD1 6SB
ETA 16/0322
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 11/11/18
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 50
Client:
Installation Instructions

1. Before installing Protecta® FR Putty Cord ensure that


Job Title:
the surface of all service penetrations and
surrounding construction is wiped clean, dry, free
from all loose contaminants, dust, oils and grease.
Products Protecta FR Putty Cord Ø15mm
2. Place the Putty Cord around the services so that it Apertures with less
seals the services to the floor all the way round. than 10mm annular Application Fire stopping of copper pipes in
width around services rigid floors
3. Press the Putty Cord into the floor and services with
your thumbs to form a fillet or V shape joint, Protecta FR Putty Cord Construction Minimum floor thickness of 150
ensuring good contact is made all the way round the on top side oversailing mm and comprise aerated
services and the floor. the aperture concrete or concrete with a
minimum density of 650kg/m3

Fire & Sound classification

Copper pipes ≤ Ø12mm with ≥ 20mm thick pipe


insulation
EI 240 C/C & E 240 C/C

Copper pipes ≤ Ø54mm with ≥ 20mm thick pipe


insulation
EI 60 C/C & E 240 C/C
Pipe insulation of stone
wool ≥ 80kg/m3
≥ 50cm on both sides

Copper pipes

Polyseam Ltd, 15 St Andrews Road,


Huddersfield, West Yorkshire, HD1 6SB
ETA 16/0322
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 29/5/18
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 51
Client:
Installation Instructions Apertures with less
than 10mm annular
1. Before fitting the collar ensure that any gaps width around services
between the pipe and the separating element are Stonewool plug Job Title:
sealed with 20mm deep stonewool to plug the from soffit side
opening. Plastic pipe
Products Protecta FR Collar
2. Place a suitable collar around the pipe and ensure Stonewool
that the collar shell and fixing lugs are positioned
tightly to the surface of the floor, so that the fixings Application Fire stopping of plastic pipes in
can be inserted fully. rigid floors

3. Where the surface is uneven, apply a sealing bead of Construction Minimum floor thickness of 150
Protecta® FR Acrylic between the floor and the collar mm and comprise aerated
shell. concrete or concrete with a
minimum density of 650kg/m3
4. Attach the collar with ≥ Ø4 x 40mm long masonry
screws or expansion bolts. Masonry screws Protecta FR Collar
or expansion bolts on soffit side
Fire & Sound classification

Fire classifications in tables on the left. For full


Services Min. Classification Services Min. Classification specifications, please refer to the Installation
Collar Collar Instructions.
Height Height
≤ Ø50mm PVC-U & PVC-C 30mm EI 60 C/C, EI 60 U/C, EI 60 C/U, EI 60 U/U (E 90) ≤ Ø50mm PP 30mm EI 120 C/C, EI 120 U/C, EI 120 C/U, EI 120 U/U Sound reduction (seal only)
≤ Ø90mm PVC-U & PVC-C 50mm EI 120 C/C, EI 120 U/C, EI 60 C/U, EI 60 U/U ≤ Ø110mm PP 50mm EI 120 C/C, EI 120 U/C, EI 60 C/U, EI 60 U/U 58dB
≤ Ø110mm PVC-U & PVC-C 30mm EI 60 C/C, EI 60 U/C, EI 60 C/U, EI 60 U/U ≤ Ø140mm PP 60mm EI 120 C/C, EI 120 U/C, EI 60 C/U, EI 60 U/U
≤ Ø110mm PVC-U & PVC-C 50mm EI 120 C/C, EI 90 U/C (E 120), EI 60 C/U ≤ Ø160mm PP 60mm EI 180 C/C, EI 180 U/C, EI 60 C/U, EI 60 U/U
≤ Ø160mm PVC-U & PVC-C 60mm EI 120 C/C, EI 120 U/C, EI 60 C/U, EI 60 U/U ≤ Ø200mm PP 60mm EI 120 C/C
≤ Ø200mm PVC-U & PVC-C 60mm EI 60 C/C (E 120) ≤ Ø250mm PP 75mm EI 60 C/C
≤ Ø315mm PVC-U & PVC-C 75mm EI 60 C/C Ø315x28.6mm PP 75mm EI 60 C/C
≤ Ø400mm PVC-U & PVC-C 100mm EI 60 C/C ≤ Ø400mm PP 100mm EI 30 C/C
≤ Ø55mm PE, ABS & SAN+PVC 30mm EI 60 C/C, EI 60 U/C, EI 60 C/U, EI 60 U/U
≤ Ø50mm PE, ABS & SAN+PVC 50mm EI 240 C/C, EI 240 U/C, EI 60 C/U, EI 60 U/U
≤ Ø110mm PE, ABS & SAN+PVC 30mm EI 60 C/C, EI 60 U/C
≤ Ø110mm PE, ABS & SAN+PVC 50mm EI 120 C/C, EI 120 U/C, EI 60 C/U, EI 60 U/U
≤ Ø160mm PE, ABS & SAN+PVC 60mm EI 120 C/C, EI 120 U/C, EI 60 C/U, EI 60 U/U
≤ Ø200mm PE, ABS & SAN+PVC 60mm EI 120 C/C (E 240)
≤ Ø250mm PE, ABS & SAN+PVC 75mm EI 240 C/C
Ø315x18.7mm PE, ABS & SAN+PVC 75mm EI 240 C/C Polyseam Ltd, 15 St Andrews Road,
Ø400x36.3mm PE, ABS & SAN+PVC 100mm EI 90 C/C Huddersfield, West Yorkshire, HD1 6SB
ETA 18/0854
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 27/7/19
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 52
Client:
Installation Instructions Apertures with less
than 10mm annular
1. Place a suitable collar around the pipe and ensure width around services
that the collar shell and fixing lugs are positioned
Job Title:
tightly to the surface of the floor, so that the fixings
can be inserted fully.
Products Protecta FR Collar
2. Where the surface is uneven, apply a sealing bead of Gaps must be sealed with a Protecta FR Acrylic
Protecta® FR Acrylic between the floor and the collar Plastic pipe bead of Protecta FR Acrylic
shell. on top of the collar Application Fire stopping of plastic pipes in
Masonry screws rigid floors
3. Attach the collar with ≥ Ø4 x 40mm long masonry or expansion bolts
screws or expansion bolts. Protecta FR Collar Construction Minimum floor thickness of 150
on the top side mm and comprise aerated
4. After fitting the collar ensure that the gaps between concrete or concrete with a
the pipe and the collar are sealed with a bead of minimum density of 650kg/m3
Protecta® FR Acrylic to cover the opening.

Fire & Sound classification

Fire classifications in tables on the left. For full


specifications, please refer to the Installation
Instructions.

Sound reduction (seal only)


58dB

Services Minimum Collar Classification


Height
≤ Ø50mm PVC-U & PVC-C 50mm EI 240 C/C, EI 240 U/C
≤ Ø110mm PVC-U & PVC-C 50mm EI 120 C/C, EI 120 U/C
≤ Ø160mm PVC-U & PVC-C 60mm EI 180 C/C, EI 180 U/C (E 240)
≤ Ø50mm PE, ABS & SAN+PVC 50mm EI 240 C/C, EI 240 U/C
≤ Ø110mm PE, ABS & SAN+PVC 50mm EI 60 C/C, EI 60 U/C (E 240)
≤ Ø160mm PE, ABS & SAN+PVC 60mm EI 60 C/C, EI 60 U/C
≤ Ø50mm PP 50mm EI 180 C/C, EI 180 U/C (E 240)
≤ Ø110mm PP 50mm EI 90 C/C, EI 90 U/C (E 180)
≤ Ø160mm PP 60mm EI 60 C/C, EI 60 U/C (E 240) Polyseam Ltd, 15 St Andrews Road,
Huddersfield, West Yorkshire, HD1 6SB
ETA 18/0854
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 27/7/19
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 53
Client:
Installation Instructions Apertures with less
than 10mm annular
1. Before fitting the collar ensure that any gaps width around services
between the pipe and the separating element are Stonewool plug Job Title:
sealed with 20mm deep stonewool to plug the from soffit side
opening. Composite plastic pipe
Products Protecta FR Collar
2. Place a suitable collar around the pipe and ensure Stonewool
that the collar shell and fixing lugs are positioned
tightly to the surface of the floor, so that the fixings Application Fire stopping of composite
can be inserted fully. plastic pipes in rigid floors

3. Where the surface is uneven, apply a sealing bead of Construction Minimum floor thickness of 150
Protecta® FR Acrylic between the floor and the collar mm and comprise aerated
shell. concrete or concrete with a
minimum density of 650kg/m3
4. Attach the collar with ≥ Ø4 x 40mm long masonry
screws or expansion bolts. Masonry screws Protecta FR Collar
or expansion bolts on soffit side
Fire & Sound classification

Services Minimum Collar Classification Fire classifications in tables on the left. For full
Height specifications, please refer to the Installation
≤ Ø32mm Aquatherm Green SDR9 30mm EI 240 C/C Instructions.
≤ Ø50mm Aquatherm Green SDR9 50mm EI 240 C/C
≤ Ø110mm Aquatherm Green SDR9 50mm EI 120 C/C Sound reduction (seal only)
≤ Ø50mm BluePower 50mm EI 180 C/C, EI 180 U/C, EI 180 C/U, EI 180 U/U 58dB
≤ Ø110mm BluePower 50mm EI 180 C/C, EI 180 U/C, EI 180 C/U
Ø125mm BluePower 60mm EI 180 C/C, EI 180 U/C, EI 180 C/U
Ø160mm BluePower 60mm EI 240 C/C, EI 240 U/C, EI 240 C/U
≤ Ø50mm Geberit Silent-PP 50mm EI 240 C/C, EI 240 U/C, EI 240 C/U, EI 240 U/U
≤ Ø110mm Geberit Silent-PP 50mm EI 180 C/C, EI 180 U/C, EI 180 C/U
≤ Ø50mm Polo-Kal NG pipes 50mm EI 240 C/C, EI 240 U/C, EI 240 C/U, EI 240 U/U
≤ Ø110mm Polo-Kal NG pipes 50mm EI 240 C/C, EI 240 U/C, EI 240 C/U
Ø125mm Polo-Kal NG pipes 60mm EI 240 C/C, EI 240 U/C
Ø160mm Polo-Kal NG pipes 60mm EI 240 C/C, EI 240 U/C (E 240 C/U)
≤ Ø50mm Rehau Raupiano Plus 50mm EI 240 C/C, EI 240 U/C, EI 240 C/U, EI 240 U/U
≤ Ø110mm Rehau Raupiano Plus 50mm EI 120 C/C, EI 120 U/C, EI 120 C/U
Ø125mm Rehau Raupiano Plus 60mm EI 180 C/C, EI 180 U/C, EI 180 C/U
Ø160mm Rehau Raupiano Plus 60mm EI 240 C/C, EI 240 U/C (E 240 C/U)
≤ Ø50mm Wavin SiTech 50mm EI 240 C/C, EI 240 U/C, EI 240 C/U, EI 240 U/U Polyseam Ltd, 15 St Andrews Road,
≤ Ø110mm Wavin SiTech 50mm EI 180 C/C, EI 180 U/C, EI 180 C/U Huddersfield, West Yorkshire, HD1 6SB
ETA 18/0854
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 27/7/19
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 54
Client:
Installation Instructions

1. Before installing Protecta® FR Putty Cord ensure that


the surface of all service penetrations and
Job Title:
surrounding construction is wiped clean, dry, free
from all loose contaminants, dust, oils and grease.
Products Protecta FR Putty Cord Ø15mm
2. Place the Putty Cord around the services so that it
seals the services to the wall all the way round. Apertures with less Application Fire stopping of cables in rigid
than 10mm annular walls
3. Press the Putty Cord into the wall and services with width around services
your thumbs to form a fillet or V shape joint, Construction Minimum wall thickness of 100
ensuring good contact is made all the way round the mm and comprise concrete,
services and the wall. aerated concrete or masonry,
with a density of ≥ 650 kg/m3

Protecta FR Putty Cord Fire & Sound classification


on both sides oversailing
the aperture Cables ≤ Ø 21mm, single or in a bundle
≤ Ø 50mm
EI 120 & E 120

Cables ≤ Ø 80mm, single or in a bundle


≤ Ø 50mm
EI 60 & E 60
Cables

Polyseam Ltd, 15 St Andrews Road,


Huddersfield, West Yorkshire, HD1 6SB
ETA 16/0322
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 29/5/18
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 55
Client:
Installation Instructions

1. Before fitting the collars ensure that any gaps


between the cable bundle and the separating
Job Title:
element are sealed with a bead of Protecta® FR
Acrylic to cover the opening.
Products Protecta FR Collar
2. Place a suitable collar around the cable bundle and Protecta FR Acrylic
Apertures with less
ensure that the collar shell and fixing lugs are than 10mm annular
positioned tightly to the surface of the wall, so that Application Fire stopping of cable bundles
width around services in rigid walls
the fixings can be inserted fully.

3. Where the surface is uneven, apply a sealing bead of Construction Minimum wall thickness of 100
Protecta® FR Acrylic between the wall and the collar Any gaps must be sealed mm and comprise concrete,
shell. with a bead of Protecta aerated concrete or masonry,
Masonry screws
FR Acrylic on both sides with a density of ≥ 650 kg/m3
or expansion
4. Attach the collar with ≥ Ø4 x 40mm long masonry
bolts
screws or expansion bolts. Fire & Sound classification

Cable bundle Cables ≤ Ø 21mm, in a bundle ≤ Ø110mm, with


collars ≤ Ø110mm at ≥ 30mm height
EI 60 & E 120
Cables ≤ Ø 80mm, in a bundle ≤ Ø110mm, with
collars ≤ Ø110mm at ≥ 50mm height
EI 60 & E 120
Cables ≤ Ø 80mm, in a bundle ≤ Ø160mm, with
collars ≤ Ø160mm at ≥ 60mm height
Protecta FR Collar to EI 60 & E 120
both sides of the wall
Sound reduction (seal only) 58dB

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0854
Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 27/7/19
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 56
Client:
Installation Instructions

1. Before installing Protecta® FR Putty Cord ensure that


Job Title:
the surface of all service penetrations and
surrounding construction is wiped clean, dry, free
from all loose contaminants, dust, oils and grease.
Apertures with less Products Protecta FR Putty Cord Ø15mm
2. Place the Putty Cord around the services so that it than 10mm annular
seals the services to the wall all the way round. width around services Application Fire stopping of steel pipes in
rigid walls
3. Press the Putty Cord into the wall and services with
your thumbs to form a fillet or V shape joint, Construction Minimum wall thickness of 100
ensuring good contact is made all the way round the mm and comprise concrete,
services and the wall. aerated concrete or masonry,
with a density of ≥ 650 kg/m3

Protecta FR Putty Cord Fire & Sound classification


on both sides oversailing
Steel pipes ≤ Ø 22mm
the aperture
EI 60 C/U & E 120 C/U

Steel pipes ≤ Ø 30mm


EI 45 C/U & E 120 C/U

Steel pipes

Polyseam Ltd, 15 St Andrews Road,


Huddersfield, West Yorkshire, HD1 6SB
ETA 16/0322
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 29/5/18
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 57
Client:
Installation Instructions

1. Before installing Protecta® FR Putty Cord ensure that


Job Title:
the surface of all service penetrations and
surrounding construction is wiped clean, dry, free
from all loose contaminants, dust, oils and grease.
Apertures with less Products Protecta FR Putty Cord Ø15mm
2. Place the Putty Cord around the services so that it than 10mm annular
seals the services to the wall all the way round. width around services Application Fire stopping of steel pipes in
rigid walls
3. Press the Putty Cord into the wall and services with
your thumbs to form a fillet or V shape joint, Construction Minimum wall thickness of 100
ensuring good contact is made all the way round the mm and comprise concrete,
services and the wall. aerated concrete or masonry,
with a density of ≥ 650 kg/m3

Protecta FR Putty Cord Fire & Sound classification


on both sides oversailing
Steel pipes ≤ Ø40mm with 20mm thick
the aperture
continuous pipe insulation
EI 120 C/U & E 120 C/U

Steel pipes ≤ Ø324mm with 30-80mm thick


continuous pipe insulation
EI 60 C/U & E 90 C/U
Steel pipes
Pipe insulation of stone
wool ≥ 80kg/m3

Polyseam Ltd, 15 St Andrews Road,


Huddersfield, West Yorkshire, HD1 6SB
ETA 16/0322
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 11/11/18
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 58
Client:
Installation Instructions

1. Before installing Protecta® FR Putty Cord ensure that


Job Title:
the surface of all service penetrations and
surrounding construction is wiped clean, dry, free
from all loose contaminants, dust, oils and grease.
Apertures with less Products Protecta FR Putty Cord Ø15mm
2. Place the Putty Cord around the services so that it than 10mm annular
seals the services to the wall all the way round. Application Fire stopping of steel pipes in
width around services
rigid walls
3. Press the Putty Cord into the wall and services with
your thumbs to form a fillet or V shape joint, Construction Minimum wall thickness of 100
ensuring good contact is made all the way round the mm and comprise concrete,
services and the wall. aerated concrete or masonry,
with a density of ≥ 650 kg/m3

Protecta FR Putty Cord Fire & Sound classification


on both sides oversailing
the aperture Steel pipes ≤ Ø40mm with ≥ 20mm thick pipe
insulation
EI 120 C/U & E 120 C/U

Steel pipes ≤ Ø324mm with ≥ 30mm thick pipe


insulation
EI 120 C/U & E 120 C/U
Pipe insulation of stone
Steel pipes
wool ≥ 80kg/m3
≥ 50cm on both sides

Polyseam Ltd, 15 St Andrews Road,


Huddersfield, West Yorkshire, HD1 6SB
ETA 16/0322
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 11/11/18
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 59
Client:
Installation Instructions

1. Before installing Protecta® FR Putty Cord ensure that


Job Title:
the surface of all service penetrations and
surrounding construction is wiped clean, dry, free
from all loose contaminants, dust, oils and grease.
Apertures with less Products Protecta FR Putty Cord Ø15mm
2. Place the Putty Cord around the services so that it than 10mm annular
seals the services to the wall all the way round. width around services Application Fire stopping of copper pipes in
rigid walls
3. Press the Putty Cord into the wall and services with
your thumbs to form a fillet or V shape joint, Construction Minimum wall thickness of 100
ensuring good contact is made all the way round the mm and comprise concrete,
services and the wall. aerated concrete or masonry,
with a density of ≥ 650 kg/m3

Protecta FR Putty Cord Fire & Sound classification


on both sides oversailing
Copper pipes ≤ Ø 6mm
the aperture
EI 120 C/C & E 120 C/C

Copper pipes ≤ Ø 12mm


EI 60 C/C & E 120 C/C

Copper pipes

Polyseam Ltd, 15 St Andrews Road,


Huddersfield, West Yorkshire, HD1 6SB
ETA 16/0322
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 29/5/18
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 60
Client:
Installation Instructions

1. Before installing Protecta® FR Putty Cord ensure that


Job Title:
the surface of all service penetrations and
surrounding construction is wiped clean, dry, free
from all loose contaminants, dust, oils and grease.
Apertures with less Products Protecta FR Putty Cord Ø15mm
2. Place the Putty Cord around the services so that it than 10mm annular
seals the services to the wall all the way round. width around services Application Fire stopping of copper pipes in
rigid walls
3. Press the Putty Cord into the wall and services with
your thumbs to form a fillet or V shape joint, Construction Minimum wall thickness of 100
ensuring good contact is made all the way round the mm and comprise concrete,
services and the wall. aerated concrete or masonry,
with a density of ≥ 650 kg/m3

Protecta FR Putty Cord Fire & Sound classification


on both sides oversailing
Copper pipes ≤ Ø12mm with 20mm thick
the aperture
continuous pipe insulation
EI 60 C/C & E 90 C/C

Copper pipes ≤ Ø54mm with 30-80mm thick


continuous pipe insulation
EI 60 C/C & E 90 C/C
Copper pipes
Pipe insulation of stone
wool ≥ 80kg/m3

Polyseam Ltd, 15 St Andrews Road,


Huddersfield, West Yorkshire, HD1 6SB
ETA 16/0322
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 11/11/18
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 61
Client:
Installation Instructions

1. Before installing Protecta® FR Putty Cord ensure that


Job Title:
the surface of all service penetrations and
surrounding construction is wiped clean, dry, free
from all loose contaminants, dust, oils and grease.
Apertures with less Products Protecta FR Putty Cord Ø15mm
2. Place the Putty Cord around the services so that it than 10mm annular
seals the services to the wall all the way round. Application Fire stopping of copper pipes in
width around services
rigid walls
3. Press the Putty Cord into the wall and services with
your thumbs to form a fillet or V shape joint, Construction Minimum wall thickness of 100
ensuring good contact is made all the way round the mm and comprise concrete,
services and the wall. aerated concrete or masonry,
with a density of ≥ 650 kg/m3

Protecta FR Putty Cord Fire & Sound classification


on both sides oversailing
the aperture Copper pipes ≤ Ø54mm with ≥ 20mm thick pipe
insulation
EI 60 C/C & E 90 C/C

Pipe insulation of stone


Copper pipes
wool ≥ 80kg/m3
≥ 50cm on both sides

Polyseam Ltd, 15 St Andrews Road,


Huddersfield, West Yorkshire, HD1 6SB
ETA 16/0322
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 29/5/18
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 62
Client:
Installation Instructions

1. Before installing Protecta® FR Putty Cord ensure that


Job Title:
the surface of all service penetrations and
surrounding construction is wiped clean, dry, free
from all loose contaminants, dust, oils and grease.
Apertures with less Products Protecta FR Putty Cord Ø15mm
2. Place the Putty Cord around the services so that it than 10mm annular
seals the services to the wall all the way round. width around services Application Fire stopping of alupex pipes in
rigid walls
3. Press the Putty Cord into the wall and services with
your thumbs to form a fillet or V shape joint, Construction Minimum wall thickness of 100
ensuring good contact is made all the way round the mm and comprise concrete,
services and the wall. aerated concrete or masonry,
with a density of ≥ 650 kg/m3

Protecta FR Putty Cord Fire & Sound classification


on both sides oversailing
Alupex pipes ≤ Ø 16mm
the aperture
EI 120 C/C & E 120 C/C

Alupex pipes ≤ Ø 20mm


EI 90 C/C & E 120 C/C

Alupex pipes

Polyseam Ltd, 15 St Andrews Road,


Huddersfield, West Yorkshire, HD1 6SB
ETA 16/0322
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 11/11/18
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 63
Client:
Installation Instructions Apertures with less
than 8mm annular Any gaps must be sealed
1. Before fitting the collars ensure that any gaps
between the pipe and the separating element are
width around services with a bead of Protecta Job Title:
FR Acrylic on both sides
sealed with a bead of Protecta® FR Acrylic to cover
the opening. Masonry screws or
Products Protecta FR Collar
expansion bolts
2. Place a suitable collar around the pipe and ensure Protecta FR Acrylic
that the collar shell and fixing lugs are positioned
Plastic pipe Application Fire stopping of plastic pipes in
tightly to the surface of the wall, so that the fixings
can be inserted fully. rigid walls

3. Where the surface is uneven, apply a sealing bead of Construction Minimum wall thickness of 100
Protecta® FR Acrylic between the wall and the collar mm and comprise concrete,
shell. aerated concrete or masonry,
with a density of ≥ 650 kg/m3
4. Attach the collar with ≥ Ø4 x 40mm long masonry
Protecta FR Collar to
screws or expansion bolts.
both sides of the wall
Fire & Sound classification

Fire classifications in table on the left. For full


specifications, please refer to the Installation
Instructions.
Services Minimum Collar Classification
Height Sound reduction (seal only)
≤ Ø50mm PVC-U & PVC-C 30mm EI 60 C/C, EI 60 U/C, EI 60 C/U, EI 60 U/U (E 90) 58dB
≤ Ø110mm PVC-U & PVC-C 30mm EI 60 C/C, EI 60 U/C
≤ Ø140mm PVC-U & PVC-C 50mm EI 60 C/C, EI 60 U/C, EI 60 C/U, EI 60 U/U (E 90)
≤ Ø160mm PVC-U & PVC-C 60mm EI 90 C/C, EI 90 U/C, EI 60 C/U, EI 60 U/U
Ø315x9.2mm PVC-U & PVC-C 75mm EI 60 C/C
≤ Ø50mm PE, ABS & SAN+PVC 30mm EI 60 C/C, EI 60 U/C (E 90)
≤ Ø50mm PE, ABS & SAN+PVC 50mm EI 90 C/C, EI 90 U/C, EI 90 C/U, EI 90 U/U (E 120)
≤ Ø110mm PE, ABS & SAN+PVC 30mm EI 60 C/C, EI 60 U/C
≤ Ø110mm PE, ABS & SAN+PVC 50mm EI 60 C/C, EI 60 U/C, EI 60 C/U, EI 60 U/U (E 90)
≤ Ø140mm PE, ABS & SAN+PVC 60mm EI 60 C/C, EI 60 U/C, EI 60 C/U, EI 60 U/U (E 90)
Ø160mm PE, ABS & SAN+PVC 60mm EI 90 C/C, EI 90 U/C, EI 90 C/U, EI 90 U/U
Ø200x18.2mm PE, ABS & SAN+PVC 75mm EI 60 C/C
Ø250x22.7mm PE, ABS & SAN+PVC 75mm EI 60 C/C
≤ Ø50mm PP 30mm EI 60 C/C, EI 60 U/C, EI 60 C/U, EI 60 U/U (E 90)
≤ Ø110mm PP 30mm EI 60 C/C, EI 60 U/C (E 90)
≤ Ø110mm PP 50mm EI 60 C/C, EI 60 U/C, EI 60 C/U, EI 60 U/U (E 90) Polyseam Ltd, 15 St Andrews Road,
≤ Ø160mm PP 60mm EI 60 C/C, EI 60 U/C, EI 60 C/U, EI 60 U/U Huddersfield, West Yorkshire, HD1 6SB
ETA 18/0854
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 27/7/19
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 64
Client:
Installation Instructions Apertures with less
than 8mm annular Any gaps must be sealed
1. Before fitting the collars ensure that any gaps
between the pipe and the separating element are
width around services with a bead of Protecta Job Title:
FR Acrylic on both sides
sealed with a bead of Protecta® FR Acrylic to cover
the opening. Masonry screws or
Products Protecta FR Collar
expansion bolts
2. Place a suitable collar around the pipe and ensure Protecta FR Acrylic
that the collar shell and fixing lugs are positioned Plastic pipe
tightly to the surface of the wall, so that the fixings Application Fire stopping of plastic pipes in
can be inserted fully. rigid walls

3. Where the surface is uneven, apply a sealing bead of Construction Minimum wall thickness of 120
Protecta® FR Acrylic between the wall and the collar mm and comprise concrete,
shell. aerated concrete or masonry,
with a density of ≥ 650 kg/m3
4. Attach the collar with ≥ Ø4 x 40mm long masonry
Protecta FR Collar to
screws or expansion bolts.
both sides of the wall
Fire & Sound classification

Fire classifications in table on the left. For full


specifications, please refer to the Installation
Instructions.
Services Minimum Collar Classification
Height
≤ Ø110mm PVC-U & PVC-C 50mm EI 120 C/C Sound reduction (seal only)
≤ Ø160mm PVC-U & PVC-C 60mm EI 120 C/C 58dB
≤ Ø50mm PE, ABS & SAN+PVC 50mm EI 120 C/C
≤ Ø110mm PE, ABS & SAN+PVC 50mm EI 90 C/C (E 120)
Ø110x3.4mm PE, ABS & SAN+PVC 50mm EI 120 C/C
≤ Ø160mm PE, ABS & SAN+PVC 60mm EI 90 C/C
Ø160x9.5mm PE, ABS & SAN+PVC 60mm EI 120 C/C
≤ Ø50mm PP 50mm EI 120 C/C
≤ Ø110mm PP 50mm EI 90 C/C (E 120)
≤ Ø140mm PP 60mm EI 90 C/C (E 120)
Ø160mm PP 60mm EI 120 C/C

Polyseam Ltd, 15 St Andrews Road,


Huddersfield, West Yorkshire, HD1 6SB
ETA 18/0854
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 27/7/19
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 65
Client:
Installation Instructions Apertures with less
than 8mm annular Any gaps must be sealed
1. Before fitting the collars ensure that any gaps
between the pipe and the separating element are
width around services with a bead of Protecta Job Title:
FR Acrylic on both sides
sealed with a bead of Protecta® FR Acrylic to cover
the opening. Masonry screws or Products Protecta FR Collar
expansion bolts Protecta FR Acrylic
2. Place a suitable collar around the pipe and ensure
that the collar shell and fixing lugs are positioned
tightly to the surface of the wall, so that the fixings Plastic pipe Application Fire stopping of plastic pipes in
can be inserted fully. rigid walls

3. Where the surface is uneven, apply a sealing bead of Construction Minimum wall thickness of 150
Protecta® FR Acrylic between the wall and the collar mm and comprise concrete,
shell. aerated concrete or masonry,
with a density of ≥ 650 kg/m3
4. Attach the collar with ≥ Ø4 x 40mm long masonry
screws or expansion bolts. Protecta FR Collar to
both sides of the wall Fire & Sound classification

Fire classifications in table on the left. For full


specifications, please refer to the Installation
Instructions.

Services Minimum Collar Classification Sound reduction (seal only)


Height 58dB
≤ Ø50mm PVC-U & PVC-C 50mm EI 180 C/C, EI 180 U/C, EI 180 C/U, EI 180 U/U (E 240)
≤ Ø110mm PVC-U & PVC-C 50mm EI 180 C/C, EI 180 U/C, EI 180 C/U, EI 180 U/U
≤ Ø160mm PVC-U & PVC-C 60mm EI 240 C/C, EI 240 U/C, EI 240 C/U, EI 240 U/U
Ø315x9.2mm PVC-U & PVC-C 75mm EI 120 C/C
≤ Ø50mm PE, ABS & SAN+PVC 50mm EI 240 C/C, EI 240 U/C, EI 240 C/U, EI 240 U/U
≤ Ø110mm PE, ABS & SAN+PVC 50mm EI 180 C/C, EI 180 U/C, EI 180 C/U, EI 180 U/U (E 240)
≤ Ø160mm PE, ABS & SAN+PVC 60mm EI 180 C/C, EI 180 U/C, EI 180 C/U, EI 180 U/U
Ø200x18.2mm PE, ABS & SAN+PVC 75mm EI 60 C/C
Ø250x22.7mm PE, ABS & SAN+PVC 75mm EI 90 C/C (E 120)
≤ Ø50mm PP 30mm EI 240 C/C, EI 240 U/C, EI 240 C/U, EI 240 U/U
≤ Ø110mm PP 50mm EI 240 C/C, EI 240 U/C, EI 90 C/U, EI 90 U/U (E 240)
≤ Ø140mm PP 60mm EI 180 C/C, EI 180 U/C, EI 60 C/U, EI 60 U/U (E 240)
Ø160mm PP 60mm EI 180 C/C, EI 180 U/C, EI 180 C/U, EI 180 U/U (E 240)

Polyseam Ltd, 15 St Andrews Road,


Huddersfield, West Yorkshire, HD1 6SB
ETA 18/0854
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 27/7/19
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 66
Client:
Installation Instructions
Apertures with less
1. Before fitting the collars ensure that any gaps than 8mm annular Any gaps must be sealed
between the pipe and the separating element are width around services with a bead of Protecta Job Title:
sealed with a bead of Protecta® FR Acrylic to cover FR Acrylic on both sides
the opening. Masonry screws or Products Protecta FR Collar
2. Place a suitable collar around the pipe and ensure expansion bolts Protecta FR Acrylic
that the collar shell and fixing lugs are positioned
tightly to the surface of the wall, so that the fixings Composite Application Fire stopping of composite
can be inserted fully. plastic pipe plastic pipes in rigid walls

3. Where the surface is uneven, apply a sealing bead of Construction Minimum wall thickness of 100
Protecta® FR Acrylic between the wall and the collar mm and comprise concrete,
shell. aerated concrete or masonry,
with a density of ≥ 650 kg/m3
4. Attach the collar with ≥ Ø4 x 40mm long masonry
screws or expansion bolts. Protecta FR Collar to
both sides of the wall Fire & Sound classification

Fire classifications in table on the left. For full


specifications, please refer to the Installation
Services Minimum Collar Classification Instructions.
Height
≤ Ø32mm Aquatherm Green SDR9 30mm EI 120 C/C Sound reduction (seal only)
≤ Ø50mm Aquatherm Green SDR9 50mm EI 120 C/C 58dB
≤ Ø110mm Aquatherm Green SDR9 50mm EI 60 C/C (E 120)
≤ Ø50mm BluePower 50mm EI 90 C/C, EI 90 U/C, EI 90 C/U, EI 90 U/U (E 120)
≤ Ø110mm BluePower 50mm EI 60 C/C, EI 60 U/C, EI 60 C/U (E 120)
Ø125mm BluePower 60mm EI 60 C/C, EI 60 U/C, EI 60 C/U
Ø160mm BluePower 60mm EI 90 C/C, EI 90 U/C, EI 90 C/U
≤ Ø50mm Geberit Silent-PP 50mm EI 120 C/C, EI 120 U/C, EI 120 C/U, EI 120 U/U
≤ Ø110mm Geberit Silent-PP 50mm EI 60 C/C, EI 60 U/C, EI 60 C/U, EI 60 U/U (E 120)
≤ Ø50mm Polo-Kal NG pipes 50mm EI 120 C/C, EI 120 U/C, EI 120 C/U, EI 120 U/U
≤ Ø110mm Polo-Kal NG pipes 50mm EI 90 C/C, EI 90 U/C, EI 90 C/U, EI 90 U/U (E 120)
Ø125mm Polo-Kal NG pipes 60mm EI 120 C/C, EI 120 U/C (E 120 C/U, E 120 U/U)
Ø160mm Polo-Kal NG pipes 60mm EI 120 C/C, EI 120 U/C, EI 120 C/U, EI 120 U/U
≤ Ø50mm Rehau Raupiano Plus 50mm EI 90 C/C, EI 90 U/C, EI 90 C/U, EI 90 U/U (E 120)
≤ Ø110mm Rehau Raupiano Plus 50mm EI 60 C/C, EI 60 U/C, EI 60 C/U, EI 60 U/U (E 120)
≤ Ø160mm Rehau Raupiano Plus 60mm EI 120 C/C, EI 120 U/C, EI 120 C/U, EI 120 U/U
≤ Ø50mm Wavin SiTech 50mm EI 120 C/C, EI 120 U/C, EI 120 C/U, EI 120 U/U Polyseam Ltd, 15 St Andrews Road,
≤ Ø110mm Wavin SiTech 50mm EI 60 C/C, EI 60 U/C, EI 60 C/U, EI 60 U/U (E 120) Huddersfield, West Yorkshire, HD1 6SB
ETA 18/0854
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 27/7/19
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 67
Client:
Installation Instructions

1. Before fitting the collars ensure that any gaps


between the pipes and the separating element are
Job Title:
sealed with a bead of Protecta® FR Acrylic to cover
the opening.
Products Protecta FR Collar
Apertures with less Protecta FR Acrylic
2. Place a suitable collar around the pipes and ensure
than 10mm annular
that the collar shell and fixing lugs are positioned
width around services Application Fire stopping of PEX pipe-in-
tightly to the surface of the wall, so that the fixings
can be inserted fully. pipes in rigid walls

3. Where the surface is uneven, apply a sealing bead of Any gaps must be sealed Construction Minimum wall thickness of 100
Protecta® FR Acrylic between the wall and the collar with a bead of Protecta mm and comprise concrete,
shell. FR Acrylic on both sides aerated concrete or masonry,
Masonry screws with a density of ≥ 650 kg/m3
4. Attach the collar with ≥ Ø4 x 40mm long masonry or expansion
screws or expansion bolts. bolts
Fire & Sound classification

PEX pipes PEX pipes ≤ Ø 25mm, single or in a bundle


≤ Ø55mm, with collars ≤ Ø55mm at ≥ 30mm
height
EI 90 & E 120

Sound reduction (seal only)


58dB
Protecta FR Collar to
both sides of the wall

Polyseam Ltd, 15 St Andrews Road,


Huddersfield, West Yorkshire, HD1 6SB
ETA 18/0854
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 27/7/19
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 68
Client:
Installation Instructions

1. Before installing Protecta® FR Putty Cord ensure that


the surface of all service penetrations and
Job Title:
surrounding construction is wiped clean, dry, free
from all loose contaminants, dust, oils and grease.
Products Protecta FR Putty Cord Ø15mm
2. Place the Putty Cord around the services so that it
seals the services to the wall all the way round. Apertures with less Application Fire stopping of cables in
than 10mm annular flexible walls
3. Press the Putty Cord into the wall and services with width around services
your thumbs to form a fillet or V shape joint, Construction Minimum wall thickness of 100
ensuring good contact is made all the way round the mm and comprise steel studs
services and the wall. or timber studs* lined on both
faces with minimum 2 layers of
12.5 mm thick boards

Protecta FR Putty Cord Fire & Sound classification


on both sides oversailing
Cables ≤ Ø 21mm, single or in a bundle
the aperture
≤ Ø 50mm
EI 120 & E 120

Cables ≤ Ø 80mm, single or in a bundle


≤ Ø 50mm
EI 60 & E 60
Cables

Polyseam Ltd, 15 St Andrews Road,


Huddersfield, West Yorkshire, HD1 6SB
ETA 16/0322
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 29/5/18
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 69
Client:
Installation Instructions

1. Before fitting the collars ensure that any gaps


between the cable bundle and the separating
Job Title:
element are sealed with a bead of Protecta® FR
Acrylic to cover the opening.
Products Protecta FR Collar
2. Place a suitable collar around the cable bundle and Protecta FR Acrylic
Apertures with less
ensure that the collar shell and fixing lugs are than 10mm annular
positioned tightly to the surface of the wall, so that Application Fire stopping of cable bundles
width around services in flexible walls
the fixings can be inserted fully.

3. Where the surface is uneven, apply a sealing bead of Construction Minimum wall thickness of 100
Protecta® FR Acrylic between the wall and the collar mm and comprise steel studs
shell. Any gaps must be sealed or timber studs* lined on both
with a bead of Protecta faces with minimum 2 layers of
4. Attach the collar with ≥ Ø4mm drywall, wood screws Drywall, wood FR Acrylic on both sides 12.5 mm thick boards
or anchors with a length suitable for the number of screws or Fire & Sound classification
boards that form the wall. anchors of steel
Cables ≤ Ø 21mm, in a bundle ≤ Ø110mm, with
collars ≤ Ø110mm at ≥ 30mm height
Cable bundle
EI 60 & E 120
Cables ≤ Ø 80mm, in a bundle ≤ Ø110mm, with
collars ≤ Ø110mm at ≥ 50mm height
EI 60 & E 120
Cables ≤ Ø 80mm, in a bundle ≤ Ø160mm, with
collars ≤ Ø160mm at ≥ 60mm height
EI 60 & E 120
Protecta FR Collar to
both sides of the wall Sound reduction (seal only) 58dB

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0854
Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 27/7/19
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 70
Client:
Installation Instructions

1. Before installing Protecta® FR Putty Cord ensure that


Job Title:
the surface of all service penetrations and
surrounding construction is wiped clean, dry, free
from all loose contaminants, dust, oils and grease.
Apertures with less Products Protecta FR Putty Cord Ø15mm
2. Place the Putty Cord around the services so that it than 10mm annular
seals the services to the wall all the way round. width around services Application Fire stopping of steel pipes in
flexible walls
3. Press the Putty Cord into the wall and services with
your thumbs to form a fillet or V shape joint, Construction Minimum wall thickness of 100
ensuring good contact is made all the way round the mm and comprise steel studs
services and the wall. or timber studs* lined on both
faces with minimum 2 layers of
12.5 mm thick boards

Protecta FR Putty Cord Fire & Sound classification


on both sides oversailing
Steel pipes ≤ Ø 22mm
the aperture
EI 60 C/U & E 120 C/U

Steel pipes ≤ Ø 30mm


EI 45 C/U & E 120 C/U

Steel pipes

Polyseam Ltd, 15 St Andrews Road,


Huddersfield, West Yorkshire, HD1 6SB
ETA 16/0322
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 29/5/18
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 71
Client:
Installation Instructions

1. Before installing Protecta® FR Putty Cord ensure that


Job Title:
the surface of all service penetrations and
surrounding construction is wiped clean, dry, free
from all loose contaminants, dust, oils and grease.
Apertures with less Products Protecta FR Putty Cord Ø15mm
2. Place the Putty Cord around the services so that it than 10mm annular
seals the services to the wall all the way round. width around services Application Fire stopping of steel pipes in
flexible walls
3. Press the Putty Cord into the wall and services with
your thumbs to form a fillet or V shape joint, Construction Minimum wall thickness of 100
ensuring good contact is made all the way round the mm and comprise steel studs
services and the wall. or timber studs* lined on both
faces with minimum 2 layers of
12.5 mm thick boards

Protecta FR Putty Cord Fire & Sound classification


on both sides oversailing
Steel pipes ≤ Ø40mm with 20mm thick
the aperture
continuous pipe insulation
EI 120 C/U & E 120 C/U

Steel pipes ≤ Ø324mm with 30-80mm thick


continuous pipe insulation
EI 60 C/U & E 90 C/U
Steel pipes
Pipe insulation of stone
wool ≥ 80kg/m3

Polyseam Ltd, 15 St Andrews Road,


Huddersfield, West Yorkshire, HD1 6SB
ETA 16/0322
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 29/5/18
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 72
Client:
Installation Instructions

1. Before installing Protecta® FR Putty Cord ensure that


Job Title:
the surface of all service penetrations and
surrounding construction is wiped clean, dry, free
from all loose contaminants, dust, oils and grease.
Apertures with less Products Protecta FR Putty Cord Ø15mm
2. Place the Putty Cord around the services so that it than 10mm annular
seals the services to the wall all the way round. Application Fire stopping of steel pipes in
width around services
flexible walls
3. Press the Putty Cord into the wall and services with
your thumbs to form a fillet or V shape joint, Construction Minimum wall thickness of 100
ensuring good contact is made all the way round the mm and comprise steel studs
services and the wall. or timber studs* lined on both
faces with minimum 2 layers of
12.5 mm thick boards

Protecta FR Putty Cord Fire & Sound classification


on both sides oversailing
the aperture Steel pipes ≤ Ø40mm with ≥ 20mm thick pipe
insulation
EI 120 C/U & E 120 C/U

Steel pipes ≤ Ø324mm with ≥ 30mm thick pipe


insulation
EI 120 C/U & E 120 C/U
Pipe insulation of stone
Steel pipes
wool ≥ 80kg/m3
≥ 50cm on both sides

Polyseam Ltd, 15 St Andrews Road,


Huddersfield, West Yorkshire, HD1 6SB
ETA 16/0322
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 11/11/18
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 73
Client:
Installation Instructions

1. Before installing Protecta® FR Putty Cord ensure that


Job Title:
the surface of all service penetrations and
surrounding construction is wiped clean, dry, free
from all loose contaminants, dust, oils and grease.
Apertures with less Products Protecta FR Putty Cord Ø15mm
2. Place the Putty Cord around the services so that it than 10mm annular
seals the services to the wall all the way round. width around services Application Fire stopping of copper pipes in
flexible walls
3. Press the Putty Cord into the wall and services with
your thumbs to form a fillet or V shape joint, Construction Minimum wall thickness of 100
ensuring good contact is made all the way round the mm and comprise steel studs
services and the wall. or timber studs* lined on both
faces with minimum 2 layers of
12.5 mm thick boards

Protecta FR Putty Cord Fire & Sound classification


on both sides oversailing
Copper pipes ≤ Ø 6mm
the aperture
EI 120 C/C & E 120 C/C

Copper pipes ≤ Ø 12mm


EI 60 C/C & E 120 C/C

Copper pipes

Polyseam Ltd, 15 St Andrews Road,


Huddersfield, West Yorkshire, HD1 6SB
ETA 16/0322
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 29/5/18
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 74
Client:
Installation Instructions

1. Before installing Protecta® FR Putty Cord ensure that


Job Title:
the surface of all service penetrations and
surrounding construction is wiped clean, dry, free
from all loose contaminants, dust, oils and grease.
Apertures with less Products Protecta FR Putty Cord Ø15mm
2. Place the Putty Cord around the services so that it than 10mm annular
seals the services to the wall all the way round. width around services Application Fire stopping of copper pipes in
flexible walls
3. Press the Putty Cord into the wall and services with
your thumbs to form a fillet or V shape joint, Construction Minimum wall thickness of 100
ensuring good contact is made all the way round the mm and comprise steel studs
services and the wall. or timber studs* lined on both
faces with minimum 2 layers of
12.5 mm thick boards

Protecta FR Putty Cord Fire & Sound classification


on both sides oversailing
Copper pipes ≤ Ø12mm with 20mm thick
the aperture
continuous pipe insulation
EI 60 C/C & E 90 C/C

Copper pipes ≤ Ø54mm with 30-80mm thick


continuous pipe insulation
EI 60 C/C & E 90 C/C
Copper pipes
Pipe insulation of stone
wool ≥ 80kg/m3

Polyseam Ltd, 15 St Andrews Road,


Huddersfield, West Yorkshire, HD1 6SB
ETA 16/0322
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 11/11/18
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 75
Client:
Installation Instructions

1. Before installing Protecta® FR Putty Cord ensure that


Job Title:
the surface of all service penetrations and
surrounding construction is wiped clean, dry, free
from all loose contaminants, dust, oils and grease.
Apertures with less Products Protecta FR Putty Cord Ø15mm
2. Place the Putty Cord around the services so that it than 10mm annular
seals the services to the wall all the way round. Application Fire stopping of copper pipes in
width around services
flexible walls
3. Press the Putty Cord into the wall and services with
your thumbs to form a fillet or V shape joint, Construction Minimum wall thickness of 100
ensuring good contact is made all the way round the mm and comprise steel studs
services and the wall. or timber studs* lined on both
faces with minimum 2 layers of
12.5 mm thick boards

Protecta FR Putty Cord Fire & Sound classification


on both sides oversailing
the aperture Copper pipes ≤ Ø54mm with ≥ 20mm thick pipe
insulation
EI 60 C/C & E 90 C/C

Pipe insulation of stone


Copper pipes
wool ≥ 80kg/m3
≥ 50cm on both sides

Polyseam Ltd, 15 St Andrews Road,


Huddersfield, West Yorkshire, HD1 6SB
ETA 16/0322
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 29/5/18
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 76
Client:
Installation Instructions

1. Before installing Protecta® FR Putty Cord ensure that


Job Title:
the surface of all service penetrations and
surrounding construction is wiped clean, dry, free
from all loose contaminants, dust, oils and grease.
Apertures with less Products Protecta FR Putty Cord Ø15mm
2. Place the Putty Cord around the services so that it than 10mm annular
seals the services to the wall all the way round. width around services Application Fire stopping of alupex pipes in
flexible walls
3. Press the Putty Cord into the wall and services with
your thumbs to form a fillet or V shape joint, Construction Minimum wall thickness of 100
ensuring good contact is made all the way round the mm and comprise steel studs
services and the wall. or timber studs* lined on both
faces with minimum 2 layers of
12.5 mm thick boards

Protecta FR Putty Cord Fire & Sound classification


on both sides oversailing
Alupex pipes ≤ Ø 16mm
the aperture
EI 120 C/C & E 120 C/C

Alupex pipes ≤ Ø 20mm


EI 90 C/C & E 120 C/C

Alupex pipes

Polyseam Ltd, 15 St Andrews Road,


Huddersfield, West Yorkshire, HD1 6SB
ETA 16/0322
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 11/11/18
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 77
Apertures with less
Client:
Installation Instructions
than 8mm annular
1. Before fitting the collars ensure that any gaps width around services
Any gaps must be sealed
between the pipe and the separating element are
Job Title:
with a bead of Protecta
sealed with a bead of Protecta® FR Acrylic to cover FR Acrylic on both sides
the opening. Drywall, wood screws
Products Protecta FR Collar
or anchors of steel Protecta FR Acrylic
2. Place a suitable collar around the pipe and ensure
that the collar shell and fixing lugs are positioned
Plastic pipe Application Fire stopping of plastic pipes in
tightly to the surface of the wall, so that the fixings
can be inserted fully. flexible walls

3. Where the surface is uneven, apply a sealing bead of Construction Minimum wall thickness of 100
Protecta® FR Acrylic between the wall and the collar mm and comprise steel studs
shell. or timber studs* lined on both
faces with minimum 2 layers of
4. Attach the collar with ≥ Ø4mm drywall, wood screws Protecta FR Collar to 12.5 mm thick boards
or anchors with a length suitable for the number of both sides of the wall
boards that form the wall. Fire & Sound classification

Fire classifications in table on the left. For full


specifications, please refer to the Installation
Instructions.
Services Minimum Collar Classification
Height Sound reduction (seal only)
≤ Ø50mm PVC-U & PVC-C 30mm EI 60 C/C, EI 60 U/C, EI 60 C/U, EI 60 U/U (E 90) 58dB
≤ Ø110mm PVC-U & PVC-C 30mm EI 60 C/C, EI 60 U/C
≤ Ø140mm PVC-U & PVC-C 50mm EI 60 C/C, EI 60 U/C, EI 60 C/U, EI 60 U/U (E 90)
≤ Ø160mm PVC-U & PVC-C 60mm EI 90 C/C, EI 90 U/C, EI 60 C/U, EI 60 U/U
Ø315x9.2mm PVC-U & PVC-C 75mm EI 60 C/C
≤ Ø50mm PE, ABS & SAN+PVC 30mm EI 60 C/C, EI 60 U/C (E 90)
≤ Ø50mm PE, ABS & SAN+PVC 50mm EI 90 C/C, EI 90 U/C, EI 90 C/U, EI 90 U/U (E 120)
≤ Ø110mm PE, ABS & SAN+PVC 30mm EI 60 C/C, EI 60 U/C
≤ Ø110mm PE, ABS & SAN+PVC 50mm EI 60 C/C, EI 60 U/C, EI 60 C/U, EI 60 U/U (E 90)
≤ Ø140mm PE, ABS & SAN+PVC 60mm EI 60 C/C, EI 60 U/C, EI 60 C/U, EI 60 U/U (E 90)
Ø160mm PE, ABS & SAN+PVC 60mm EI 90 C/C, EI 90 U/C, EI 90 C/U, EI 90 U/U
Ø200x18.2mm PE, ABS & SAN+PVC 75mm EI 60 C/C
Ø250x22.7mm PE, ABS & SAN+PVC 75mm EI 60 C/C
≤ Ø50mm PP 30mm EI 60 C/C, EI 60 U/C, EI 60 C/U, EI 60 U/U (E 90)
≤ Ø110mm PP 30mm EI 60 C/C, EI 60 U/C (E 90)
≤ Ø110mm PP 50mm EI 60 C/C, EI 60 U/C, EI 60 C/U, EI 60 U/U (E 90) Polyseam Ltd, 15 St Andrews Road,
≤ Ø160mm PP 60mm EI 60 C/C, EI 60 U/C, EI 60 C/U, EI 60 U/U Huddersfield, West Yorkshire, HD1 6SB
ETA 18/0854
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 15/7/19
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 78
Apertures with less
Client:
Installation Instructions
than 8mm annular
1. Before fitting the collars ensure that any gaps width around services
Any gaps must be sealed
between the pipe and the separating element are
Job Title:
with a bead of Protecta
sealed with a bead of Protecta® FR Acrylic to cover FR Acrylic on both sides
the opening. M5 drywall
Products Protecta FR Collar
anchors of steel Protecta FR Acrylic
2. Place a suitable collar around the pipe and ensure
that the collar shell and fixing lugs are positioned
Plastic pipe Application Fire stopping of plastic pipes in
tightly to the surface of the wall, so that the fixings
can be inserted fully. 2 hour fire rated flexible walls

3. Where the surface is uneven, apply a sealing bead of Construction Minimum wall thickness of 120
Protecta® FR Acrylic between the wall and the collar mm and comprise steel studs
shell. or timber studs* lined on both
faces with minimum 2 layers of
4. Attach the collar with M5 drywall anchors with a Protecta FR Collar to 12.5 mm thick boards
length suitable for the number of boards that form both sides of the wall
the wall. Fire & Sound classification

Fire classifications in table on the left. For full


specifications, please refer to the Installation
Instructions.
Services Minimum Collar Classification
Height
≤ Ø110mm PVC-U & PVC-C 50mm EI 120 C/C Sound reduction (seal only)
≤ Ø160mm PVC-U & PVC-C 60mm EI 120 C/C 58dB
≤ Ø50mm PE, ABS & SAN+PVC 50mm EI 120 C/C
≤ Ø110mm PE, ABS & SAN+PVC 50mm EI 90 C/C (E 120)
Ø110x3.4mm PE, ABS & SAN+PVC 50mm EI 120 C/C
≤ Ø160mm PE, ABS & SAN+PVC 60mm EI 90 C/C
Ø160x9.5mm PE, ABS & SAN+PVC 60mm EI 120 C/C
≤ Ø50mm PP 50mm EI 120 C/C
≤ Ø110mm PP 50mm EI 90 C/C (E 120)
≤ Ø140mm PP 60mm EI 90 C/C (E 120)
Ø160mm PP 60mm EI 120 C/C

Polyseam Ltd, 15 St Andrews Road,


Huddersfield, West Yorkshire, HD1 6SB
ETA 18/0854
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 15/7/19
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 79
Apertures with less
Client:
Installation Instructions
than 8mm annular
1. Before fitting the collars ensure that any gaps width around services
Any gaps must be sealed
between the pipe and the separating element are
Job Title:
with a bead of Protecta
sealed with a bead of Protecta® FR Acrylic to cover FR Acrylic on both sides
the opening. Drywall, wood screws
Products Protecta FR Collar
or anchors of steel Protecta FR Acrylic
2. Place a suitable collar around the pipe and ensure
that the collar shell and fixing lugs are positioned
Composite plastic pipe Application Fire stopping of composite
tightly to the surface of the wall, so that the fixings
can be inserted fully. plastic pipes in flexible walls

3. Where the surface is uneven, apply a sealing bead of Construction Minimum wall thickness of 100
Protecta® FR Acrylic between the wall and the collar mm and comprise steel studs
shell. or timber studs* lined on both
faces with minimum 2 layers of
4. Attach the collar with ≥ Ø4mm drywall, wood screws Protecta FR Collar to 12.5 mm thick boards
or anchors with a length suitable for the number of both sides of the wall
boards that form the wall. Fire & Sound classification

Fire classifications in table on the left. For full


specifications, please refer to the Installation
Services Minimum Collar Classification Instructions.
Height
≤ Ø32mm Aquatherm Green SDR9 30mm EI 120 C/C Sound reduction (seal only)
≤ Ø50mm Aquatherm Green SDR9 50mm EI 120 C/C 58dB
≤ Ø110mm Aquatherm Green SDR9 50mm EI 60 C/C (E 120)
≤ Ø50mm BluePower 50mm EI 90 C/C, EI 90 U/C, EI 90 C/U, EI 90 U/U (E 120)
≤ Ø110mm BluePower 50mm EI 60 C/C, EI 60 U/C, EI 60 C/U (E 120)
Ø125mm BluePower 60mm EI 60 C/C, EI 60 U/C, EI 60 C/U
Ø160mm BluePower 60mm EI 90 C/C, EI 90 U/C, EI 90 C/U
≤ Ø50mm Geberit Silent-PP 50mm EI 120 C/C, EI 120 U/C, EI 120 C/U, EI 120 U/U
≤ Ø110mm Geberit Silent-PP 50mm EI 60 C/C, EI 60 U/C, EI 60 C/U, EI 60 U/U (E 120)
≤ Ø50mm Polo-Kal NG pipes 50mm EI 120 C/C, EI 120 U/C, EI 120 C/U, EI 120 U/U
≤ Ø110mm Polo-Kal NG pipes 50mm EI 90 C/C, EI 90 U/C, EI 90 C/U, EI 90 U/U (E 120)
Ø125mm Polo-Kal NG pipes 60mm EI 120 C/C, EI 120 U/C (E 120 C/U, E 120 U/U)
Ø160mm Polo-Kal NG pipes 60mm EI 120 C/C, EI 120 U/C, EI 120 C/U, EI 120 U/U
≤ Ø50mm Rehau Raupiano Plus 50mm EI 90 C/C, EI 90 U/C, EI 90 C/U, EI 90 U/U (E 120)
≤ Ø110mm Rehau Raupiano Plus 50mm EI 60 C/C, EI 60 U/C, EI 60 C/U, EI 60 U/U (E 120)
≤ Ø160mm Rehau Raupiano Plus 60mm EI 120 C/C, EI 120 U/C, EI 120 C/U, EI 120 U/U
≤ Ø50mm Wavin SiTech 50mm EI 120 C/C, EI 120 U/C, EI 120 C/U, EI 120 U/U Polyseam Ltd, 15 St Andrews Road,
≤ Ø110mm Wavin SiTech 50mm EI 60 C/C, EI 60 U/C, EI 60 C/U, EI 60 U/U (E 120) Huddersfield, West Yorkshire, HD1 6SB
ETA 18/0854
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 27/7/19
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 80
Client:
Installation Instructions

1. Before fitting the collars ensure that any gaps


between the pipes and the separating element are
Job Title:
sealed with a bead of Protecta® FR Acrylic to cover
the opening.
Products Protecta FR Collar
2. Place a suitable collar around the pipes and ensure Protecta FR Acrylic
Apertures with less
that the collar shell and fixing lugs are positioned than 10mm annular
tightly to the surface of the wall, so that the fixings Application Fire stopping of PEX pipe-in-
width around services pipes in flexible walls
can be inserted fully.

3. Where the surface is uneven, apply a sealing bead of Construction Minimum wall thickness of 100
Protecta® FR Acrylic between the wall and the collar mm and comprise steel studs
shell. Any gaps must be sealed or timber studs* lined on both
with a bead of Protecta faces with minimum 2 layers of
4. Attach the collar with ≥ Ø4mm drywall, wood screws Drywall, wood FR Acrylic on both sides 12.5 mm thick boards
or anchors with a length suitable for the number of screws or
boards that form the wall. anchors of steel Fire & Sound classification

PEX pipes ≤ Ø 25mm, single or in a bundle


PEX pipes
≤ Ø55mm, with collars ≤ Ø55mm at ≥ 30mm
height
EI 90 & E 120

Sound reduction (seal only)


58dB
Protecta FR Collar to
both sides of the wall

Polyseam Ltd, 15 St Andrews Road,


Huddersfield, West Yorkshire, HD1 6SB
ETA 18/0854
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 27/7/19
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 81
Appendix III
-
Service penetration solutions with gaps ≥ 10mm and ≤ 30mm

P a g e | 82
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Protecta Mineral Fibre BIO
surfaces that cannot tolerate direct contact;
appropriate surface preparation should be made Application Fire stopping of cables in rigid
(contact Polyseam for guidance in these cases). For Protecta FR Acrylic floors
Backing with Protecta
paints sensitive to sealing compounds, priming with Minimum seal depth 25mm
Mineral Fibre BIO Maximum aperture 100x1000mm
a PVA primer is recommended. Construction Minimum floor thickness of 150
minimum 25mm deep
3. When installing Protecta® FR Acrylic in hollow floor mm and comprise aerated
slabs or boards, fire seals specified as single sided concrete or concrete with a
should be installed from the soffit side of the floor minimum density of 650kg/m3.
assuming there is sufficient thickness of concrete
below the void to follow the installation guide.
Fire & Sound classification
Where this is not the case, tubular voids should be
filled with stone wool normally the same thickness
Single sided seal top or soffit face position
as the depth of the floor slab. Alternatively, simply
EI 60 & E 120
fire seal on both sides.
4. When installing any backing material, cut this slightly Sound reduction (seal only)
oversize and insert into the gap ensuring a tight Rw 62 dB
friction fit. Ensure correct depth is achieved.
5. Fill the gap or joint with Protecta® FR Acrylic to the
required depth.
6. Apply the sealant generously to prevent air bubbles.
Finish the bead with a moist spatula, pallet knife or Single cable ≤ Ø21mm
brush.
7. Protecta® FR Acrylic can be over-painted with most
emulsion or alkyd (gloss) paints.

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904
Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 4/3/15
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 83
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Protecta Mineral Fibre BIO
surfaces that cannot tolerate direct contact;
appropriate surface preparation should be made Application Fire stopping of cables in rigid
(contact Polyseam for guidance in these cases). For Protecta FR Acrylic floors
Backing with Protecta
paints sensitive to sealing compounds, priming with Minimum seal depth 25mm
Mineral Fibre BIO Maximum aperture 300x300mm
a PVA primer is recommended. Construction Minimum floor thickness of 150
minimum 48mm deep
3. When installing Protecta® FR Acrylic in hollow floor mm and comprise aerated
slabs or boards, tubular voids should be filled with concrete or concrete with a
stone wool normally the same thickness as the minimum density of 650kg/m3.
depth of the floor slab. Alternatively, simply fire seal
on both sides.
Fire & Sound classification
4. When installing any backing material, cut this slightly
oversize and insert into the gap ensuring a tight
Cable ≤ Ø21mm single sided seal top face
friction fit. Ensure correct depth is achieved.
position
5. Fill the gap or joint with Protecta® FR Acrylic to the EI 90 & E 120
required depth.
6. Apply the sealant generously to prevent air bubbles. Cable Ø23-27mm 1x185mm2 core with PVC
Finish the bead with a moist spatula, pallet knife or sheath single sided seal top face position
brush. EI 240 & E 240
7. Protecta® FR Acrylic can be over-painted with most
emulsion or alkyd (gloss) paints. Sound reduction (seal only)
Single cable Rw 62 dB

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904 Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 4/3/15
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 84
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Stone wool
surfaces that cannot tolerate direct contact;
appropriate surface preparation should be made Application Fire stopping of cables in rigid
(contact Polyseam for guidance in these cases). For Protecta FR Acrylic floors
paints sensitive to sealing compounds, priming with Minimum seal depth 15mm
a PVA primer is recommended. Maximum aperture 300x300mm Construction Minimum floor thickness of 150
Backing with stone wool
3. When installing any backing material, cut this slightly minimum 25mm deep mm and comprise aerated
oversize and insert into the gap ensuring a tight concrete or concrete with a
friction fit. Ensure correct depth is achieved. minimum density of 650kg/m3.
4. Fill the gap or joint with Protecta® FR Acrylic to the
required depth. Fire & Sound classification
5. Apply the sealant generously to prevent air bubbles.
Cables ≤ Ø21mm single or in a bundle
Finish the bead with a moist spatula, pallet knife or
≤ Ø100mm EI 120 & E 120
brush.
6. Protecta® FR Acrylic can be over-painted with most Cables ≤ Ø50mm single or in a bundle
emulsion or alkyd (gloss) paints. ≤ Ø100mm EI 90 & E 120

Cables ≤ Ø80mm single or in a bundle


≤ Ø100mm EI 60 & E 120

Sound reduction (seal only)


Single or bundled Rw 62 dB
cables

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904 Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 9/8/19
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
Scale: Drawn by:
NTS K.B

P a g e | 85
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Stone wool
surfaces that cannot tolerate direct contact;
Protecta FR Acrylic
appropriate surface preparation should be made Application Fire stopping of steel pipes in
Single sided seal top face
(contact Polyseam for guidance in these cases). For rigid floors
Minimum seal depth 25mm
paints sensitive to sealing compounds, priming with
Maximum aperture 300x300 or Ø344mm
a PVA primer is recommended. Backing with stone wool Construction Minimum floor thickness of 150
3. As Protecta® FR Acrylic is water based, in cases minimum 48mm deep mm and comprise aerated
where corrosion protection is a problem; some concrete or concrete with a
metals may require a barrier between the sealant minimum density of 650kg/m3.
and the metal surface prior to this installation.
4. When installing any backing material, cut this slightly Fire & Sound classification
oversize and insert into the gap ensuring a tight
Steel pipe ≤ Ø16mm
friction fit. Ensure correct depth is achieved.
EI 120 C/U & E 120 C/U
5. Fill the gap or joint with Protecta® FR Acrylic to the
required depth. Steel pipe ≤ Ø324mm
6. Apply the sealant generously to prevent air bubbles. E 120 C/U
Finish the bead with a moist spatula, pallet knife or
brush. Sound reduction (seal only)
7. Protecta® FR Acrylic can be over-painted with most Rw 62 dB
emulsion or alkyd (gloss) paints.
Steel pipe

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904 Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 9/8/19
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
Scale: Drawn by:
NTS K.B

P a g e | 86
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Stone wool
surfaces that cannot tolerate direct contact;
appropriate surface preparation should be made Application Fire stopping of steel pipes in
(contact Polyseam for guidance in these cases). For Protecta FR Acrylic rigid floors
Backing with stone wool Minimum seal depth 25mm
paints sensitive to sealing compounds, priming with
density ≥ 140kg/m3 Maximum aperture 300x300mm
a PVA primer is recommended. Construction Minimum floor thickness of 150
minimum 25mm deep
3. As Protecta® FR Acrylic is water based, in cases mm and comprise aerated
where corrosion protection is a problem; some concrete or concrete with a
metals may require a barrier between the sealant minimum density of 650kg/m3.
and the metal surface prior to this installation.
4. When installing any backing material, cut this slightly Fire & Sound classification
oversize and insert into the gap ensuring a tight
Double sided seal
friction fit. Ensure correct depth is achieved.
EI 240 C/U & E 240 C/U
5. Fill the gap or joint with Protecta® FR Acrylic to the
required depth. Sound reduction (seal only)
6. Apply the sealant generously to prevent air bubbles. Rw 62 dB
Finish the bead with a moist spatula, pallet knife or
brush.
7. Protecta® FR Acrylic can be over-painted with most
emulsion or alkyd (gloss) paints.

Steel pipe
≤ Ø16mm

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904 Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 4/3/15
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
Scale: Drawn by:
NTS K.B

P a g e | 87
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
Protecta FR Acrylic
construction is free from all loose contaminants,
Minimum seal depth 25mm
dust and grease.
single sided seal top face Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Protecta Mineral Fibre BIO
surfaces that cannot tolerate direct contact;
appropriate surface preparation should be made Backing with Protecta Application Fire stopping of steel pipes in
(contact Polyseam for guidance in these cases). For Mineral Fibre BIO rigid floors
paints sensitive to sealing compounds, priming with minimum 48mm deep
a PVA primer is recommended. Construction Minimum floor thickness of 150
3. When installing any backing material, cut this slightly mm and comprise aerated
oversize and insert into the gap ensuring a tight concrete or concrete with a
friction fit. Ensure correct depth is achieved. minimum density of 650kg/m3.
4. Fill the gap or joint with Protecta® FR Acrylic to the
required depth.
5. Apply the sealant generously to prevent air bubbles. Fire & Sound classification
Finish the bead with a moist spatula, pallet knife or
brush. Steel pipe ≤ Ø324mm with 20-80mm thick
6. Protecta® FR Acrylic can be over-painted with most continuous pipe insulation in maximum
emulsion or alkyd (gloss) paints.. aperture 300x300mm or Ø504mm
EI 240 C/U & E 240 C/U

Sound reduction (seal only)


Rw 62dB

Pipe insulation of stone


Steel pipe
wool ≥ 80kg/m3

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904 Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 20/1/17
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 88
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Stone wool
surfaces that cannot tolerate direct contact; Application Fire stopping of steel pipes in
appropriate surface preparation should be made Protecta FR Acrylic rigid floors
(contact Polyseam for guidance in these cases). For Minimum seal depth 15mm Construction Minimum floor thickness of 150
paints sensitive to sealing compounds, priming with single sided seal top or soffit face mm and comprise aerated
Backing with stone wool
a PVA primer is recommended. concrete or concrete with a
minimum 20mm deep minimum density of 650kg/m3.
3. As Protecta® FR Acrylic is water based, in cases
where corrosion protection is a problem; some
metals may require a barrier between the sealant Fire & Sound classification
and the metal surface prior to this installation.
4. When installing Protecta® FR Acrylic in hollow floor Steel pipe ≤ Ø40mm with ≥ 20mm thick pipe
insulation in maximum aperture 300x300mm
slabs or boards, fire seals specified as single sided
EI 60 C/U & E 90 C/U
should be installed from the soffit side of the floor
Steel pipe ≤ Ø40mm with ≥ 20mm thick pipe
assuming there is sufficient thickness of concrete
insulation and annular ring width 10mm
below the void to follow the installation guide. EI 240 C/U & E 240 C/U
Where this is not the case, tubular voids should be Steel pipe ≤ Ø219mm with ≥ 30mm thick pipe
filled with stone wool normally the same thickness insulation in maximum aperture 300x300mm
as the depth of the floor slab. Alternatively, simply EI 60 C/U & E 90 C/U
fire seal on both sides. Steel pipe ≤ Ø219mm with ≥ 30mm thick pipe
5. When installing any backing material, cut this slightly insulation and annular ring width 10mm
oversize and insert into the gap ensuring a tight EI 90 C/U & E 240 C/U
friction fit. Ensure correct depth is achieved. Sound reduction (seal only) Rw 62dB
Steel pipe Pipe insulation of stone
6. Fill the gap or joint with Protecta® FR Acrylic to the
wool ≥ 80kg/m3
required depth.
≥ 100cm on both sides
7. Apply the sealant generously to prevent air bubbles.
Finish the bead with a moist spatula, pallet knife or
brush.
8. Protecta® FR Acrylic can be over-painted with most
emulsion or alkyd (gloss) paints.

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904 Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 4/3/15
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 89
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Stone wool
surfaces that cannot tolerate direct contact;
appropriate surface preparation should be made Protecta FR Acrylic Application Fire stopping of steel pipes in
(contact Polyseam for guidance in these cases). For Minimum seal depth 25mm rigid floors
paints sensitive to sealing compounds, priming with single sided seal top or soffit face
Backing with stone wool
a PVA primer is recommended. Construction Minimum floor thickness of 150
minimum 20mm deep mm and comprise aerated
3. As Protecta® FR Acrylic is water based, in cases
where corrosion protection is a problem; some concrete or concrete with a
metals may require a barrier between the sealant minimum density of 650kg/m3.
and the metal surface prior to this installation.
4. When installing Protecta® FR Acrylic in hollow floor Fire & Sound classification
slabs or boards, fire seals specified as single sided
Steel pipe ≤ Ø40mm with ≥ 20mm thick pipe
should be installed from the soffit side of the floor
insulation in maximum aperture 300x300mm or
assuming there is sufficient thickness of concrete
100x1000mm EI 90 C/U & E 120 C/U
below the void to follow the installation guide.
Where this is not the case, tubular voids should be Steel pipe ≤ Ø219mm with ≥ 30mm thick pipe
filled with stone wool normally the same thickness insulation in maximum aperture 300x300mm or
as the depth of the floor slab. Alternatively, simply 100x1000mm EI 90 C/U & E 120 C/U
fire seal on both sides.
5. When installing any backing material, cut this slightly Sound reduction (seal only)
oversize and insert into the gap ensuring a tight Rw 62dB
friction fit. Ensure correct depth is achieved.
Steel pipe Pipe insulation of stone
6. Fill the gap or joint with Protecta® FR Acrylic to the
wool ≥ 80kg/m3
required depth.
≥ 100cm on both sides
7. Apply the sealant generously to prevent air bubbles.
Finish the bead with a moist spatula, pallet knife or
brush.
8. Protecta® FR Acrylic can be over-painted with most
emulsion or alkyd (gloss) paints.

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904 Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 4/3/15
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 90
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Stone wool
surfaces that cannot tolerate direct contact;
Protecta FR Acrylic
appropriate surface preparation should be made Application Fire stopping of steel pipes in
Minimum seal depth 15mm
(contact Polyseam for guidance in these cases). For rigid floors
Maximum aperture 300x300mm or
paints sensitive to sealing compounds, priming with
Backing with stone wool 100x1000mm
a PVA primer is recommended. Construction Minimum floor thickness of 150
minimum 20mm deep mm and comprise aerated
3. As Protecta® FR Acrylic is water based, in cases
where corrosion protection is a problem; some concrete or concrete with a
metals may require a barrier between the sealant minimum density of 650kg/m3.
and the metal surface prior to this installation.
4. When installing any backing material, cut this slightly
Fire & Sound classification
oversize and insert into the gap ensuring a tight
friction fit. Ensure correct depth is achieved.
Double sided seal
5. Fill the gap or joint with Protecta® FR Acrylic to the
EI 120 C/U & E 240 C/U
required depth.
6. Apply the sealant generously to prevent air bubbles. Sound reduction (seal only)
Finish the bead with a moist spatula, pallet knife or Rw 62dB
brush.
7. Protecta® FR Acrylic can be over-painted with most
emulsion or alkyd (gloss) paints.

Steel pipe ≥ 30mm thick pipe insulation


≤ Ø219mm of stone wool ≥ 80kg/m3
≥ 100cm on both sides

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904
Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 4/3/15
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 91
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Stone wool
Protecta FR Acrylic
surfaces that cannot tolerate direct contact;
Minimum seal depth 25mm
appropriate surface preparation should be made Application Fire stopping of steel pipes in
Backing with stone wool Maximum annular ring width 30mm
(contact Polyseam for guidance in these cases). For rigid floors
minimum 20mm deep Double sided seal
paints sensitive to sealing compounds, priming with
a PVA primer is recommended. Construction Minimum floor thickness of 150
3. When installing any backing material, cut this slightly mm and comprise aerated
oversize and insert into the gap ensuring a tight concrete or concrete with a
friction fit. Ensure correct depth is achieved. minimum density of 650kg/m3.
4. Fill the gap or joint with Protecta® FR Acrylic to the
required depth.
Fire & Sound classification
5. Apply the sealant generously to prevent air bubbles.
Finish the bead with a moist spatula, pallet knife or
Steel pipe ≤ Ø40mm with 13 – 19mm thick pipe
brush.
insulation
6. Protecta® FR Acrylic can be over-painted with most EI 180 C/U & E 180 C/U
emulsion or alkyd (gloss) paints.
Sound reduction (seal only)
Rw 62dB

Steel pipe Continuous elastomeric


or phenolic insulation

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904
Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 10/8/19
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 92
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Protecta FR Acrylic Protecta Mineral Fibre BIO
surfaces that cannot tolerate direct contact; Minimum seal depth 25mm
appropriate surface preparation should be made Maximum annular ring width 30mm Application Fire stopping of steel pipes in
(contact Polyseam for guidance in these cases). For Backing with Protecta Double sided seal rigid floors
paints sensitive to sealing compounds, priming with Mineral Fibre BIO
a PVA primer is recommended. minimum 25mm deep Construction Minimum floor thickness of 150
3. When installing any backing material, cut this slightly mm and comprise aerated
oversize and insert into the gap ensuring a tight concrete or concrete with a
friction fit. Ensure correct depth is achieved. minimum density of 650kg/m3.
4. Fill the gap or joint with Protecta® FR Acrylic to the
required depth.
Fire & Sound classification
5. Apply the sealant generously to prevent air bubbles.
Finish the bead with a moist spatula, pallet knife or
Steel pipe ≤ Ø165mm with 13 – 19mm thick
brush.
pipe insulation
6. Protecta® FR Acrylic can be over-painted with most EI 60 C/U & E 60 C/U
emulsion or alkyd (gloss) paints.
Sound reduction (seal only)
Rw 62dB

Steel pipe Continuous elastomeric


or phenolic insulation

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904
Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 10/8/19
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 93
Client:
Installation Instructions

1. Before installing Protecta® FR Graphite ensure that


the surface of all service penetrations and
Job Title:
surrounding construction is free from all loose
contaminants, dust and grease.
Products Protecta FR Graphite
2. When installing any backing material, cut this slightly Protecta FR Graphite Protecta Mineral Fibre BIO
oversize and insert into the gap ensuring a tight Minimum seal depth 45mm
friction fit. Ensure correct depth is achieved. Seal widths between 10 and 30mm Application Fire stopping of steel pipes in
Backing with Protecta rigid floors
3. Fill the gap or joint with Protecta® FR Graphite to the Mineral Fibre BIO Double sided seal
required depth. minimum 30mm deep Construction Minimum floor thickness of 150
4. Apply the sealant generously avoiding air bubbles. mm and comprise aerated
Finish the bead with a moist spatula or pallet knife. concrete or concrete with a
Avoid excessive tooling/smoothing as this may make minimum density of 650kg/m3.
the seal surface wet and soft.
Fire & Sound classification
5. Protecta® FR Graphite can be over-painted with
most emulsion or alkyd (gloss) paints.
Steel pipe ≤ Ø324mm with 25 – 49mm thick
pipe insulation
EI 60 C/U

Steel pipe ≤ Ø324mm with 50mm thick pipe


insulation
EI 120 C/U

Sound reduction (seal only)


Rw 53dB

Steel pipe Continuous elastomeric


insulation

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0626 Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 11/11/18
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 94
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Stone wool
surfaces that cannot tolerate direct contact;
appropriate surface preparation should be made Protecta FR Acrylic Application Fire stopping of copper pipes in
(contact Polyseam for guidance in these cases). For Single sided seal top face rigid floors
paints sensitive to sealing compounds, priming with Minimum seal depth 25mm
a PVA primer is recommended. Backing with stone wool Maximum aperture 300x300mm Construction Minimum floor thickness of 150
3. As Protecta® FR Acrylic is water based, in cases minimum 48mm deep mm and comprise aerated
where corrosion protection is a problem; some concrete or concrete with a
metals may require a barrier between the sealant minimum density of 650kg/m3
and the metal surface prior to this installation.
4. When installing any backing material, cut this slightly Fire & Sound classification
oversize and insert into the gap ensuring a tight
Copper pipe ≤ Ø6mm
friction fit. Ensure correct depth is achieved.
EI 120 C/C & E 120 C/C
5. Fill the gap or joint with Protecta® FR Acrylic to the
required depth. Copper pipe ≤ Ø15mm
6. Apply the sealant generously to prevent air bubbles. EI 60 C/C & E 120 C/C
Finish the bead with a moist spatula, pallet knife or
brush. Copper pipe ≤ Ø54mm
7. Protecta® FR Acrylic can be over-painted with most E 120 C/C
emulsion or alkyd (gloss) paints.
Sound reduction (seal only)
Copper pipe
Rw 62 dB

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904 Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 10/8/19
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
Scale: Drawn by:
NTS K.B

P a g e | 95
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Stone wool
surfaces that cannot tolerate direct contact;
appropriate surface preparation should be made Application Fire stopping of copper pipes in
(contact Polyseam for guidance in these cases). For Protecta FR Acrylic rigid floors
Backing with stone wool Minimum seal depth 25mm
paints sensitive to sealing compounds, priming with
density ≥ 140kg/m3 Maximum aperture 300x300mm
a PVA primer is recommended. Construction Minimum floor thickness of 150
minimum 25mm deep
3. As Protecta® FR Acrylic is water based, in cases mm and comprise aerated
where corrosion protection is a problem; some concrete or concrete with a
metals may require a barrier between the sealant minimum density of 650kg/m3.
and the metal surface prior to this installation.
4. When installing any backing material, cut this slightly Fire & Sound classification
oversize and insert into the gap ensuring a tight
Double sided seal
friction fit. Ensure correct depth is achieved.
EI 20 C/U & E 120 C/U
5. Fill the gap or joint with Protecta® FR Acrylic to the
required depth. Sound reduction (seal only)
6. Apply the sealant generously to prevent air bubbles. Rw 62 dB
Finish the bead with a moist spatula, pallet knife or
brush.
7. Protecta® FR Acrylic can be over-painted with most
emulsion or alkyd (gloss) paints.

Copper pipe
≤ Ø54mm

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904 Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 4/3/15
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
Scale: Drawn by:
NTS K.B

P a g e | 96
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants, Protecta FR Acrylic
dust and grease. Minimum seal depth 25mm
single sided seal top face Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Stonewool
surfaces that cannot tolerate direct contact;
appropriate surface preparation should be made Backing with
Application Fire stopping of copper pipes in
(contact Polyseam for guidance in these cases). For stonewool minimum rigid floors
paints sensitive to sealing compounds, priming with 48mm deep
a PVA primer is recommended. Construction Minimum floor thickness of 150
3. When installing any backing material, cut this slightly mm and comprise aerated
oversize and insert into the gap ensuring a tight concrete or concrete with a
friction fit. Ensure correct depth is achieved. minimum density of 650kg/m3
4. Fill the gap or joint with Protecta® FR Acrylic to the Fire & Sound classification
required depth.
5. Apply the sealant generously to prevent air bubbles. Copper pipe ≤ Ø12mm with 20-80mm thick
Finish the bead with a moist spatula, pallet knife or continuous pipe insulation in maximum
brush. aperture 300x300mm
EI 240 C/C & E 240 C/C
6. Protecta® FR Acrylic can be over-painted with most
emulsion or alkyd (gloss) paints.
Copper pipe ≤ Ø54mm with 20-80mm thick
continuous pipe insulation in maximum
aperture 300x300mm
EI 180 C/C & E 240 C/C

Sound reduction (seal only)


Rw 62dB
Pipe insulation of stone
Copper pipe
wool ≥ 80kg/m3

Polyseam Ltd, 15 St Andrews Road,


Huddersfield, West Yorkshire, HD1 6SB
ETA 18/0904
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 10/8/19
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 97
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Stone wool
surfaces that cannot tolerate direct contact; Application Fire stopping of copper pipes in
appropriate surface preparation should be made Protecta FR Acrylic rigid floors
(contact Polyseam for guidance in these cases). For Minimum seal depth 15mm Construction Minimum floor thickness of 150
paints sensitive to sealing compounds, priming with single sided seal top or soffit face mm and comprise aerated
Backing with stone wool
a PVA primer is recommended. concrete or concrete with a
minimum 20mm deep minimum density of 650kg/m3
3. As Protecta® FR Acrylic is water based, in cases
where corrosion protection is a problem; some
metals may require a barrier between the sealant Fire & Sound classification
and the metal surface prior to this installation.
4. When installing Protecta® FR Acrylic in hollow floor Copper pipe ≤ Ø12mm with ≥ 20mm thick pipe
insulation and annular ring width 10mm
slabs or boards, fire seals specified as single sided
EI 240 C/U & E 240 C/U
should be installed from the soffit side of the floor
assuming there is sufficient thickness of concrete
Copper pipe ≤ Ø54mm with ≥ 20mm thick pipe
below the void to follow the installation guide. insulation in maximum aperture 300x300mm
Where this is not the case, tubular voids should be EI 60 C/U & E 90 C/U
filled with stone wool normally the same thickness
as the depth of the floor slab. Alternatively, simply Copper pipe ≤ Ø54mm with ≥ 20mm thick pipe
fire seal on both sides. insulation and annular ring width 10mm
5. When installing any backing material, cut this slightly EI 180 C/U & E 240 C/U
oversize and insert into the gap ensuring a tight
friction fit. Ensure correct depth is achieved. Sound reduction (seal only) Rw 62dB
Copper pipe Pipe insulation of stone
6. Fill the gap or joint with Protecta® FR Acrylic to the
wool ≥ 80kg/m3
required depth.
≥ 100cm on both sides
7. Apply the sealant generously to prevent air bubbles.
Finish the bead with a moist spatula, pallet knife or
brush.
8. Protecta® FR Acrylic can be over-painted with most
emulsion or alkyd (gloss) paints.

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904 Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 4/3/15
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 98
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Stone wool
surfaces that cannot tolerate direct contact;
appropriate surface preparation should be made Protecta FR Acrylic Application Fire stopping of copper pipes in
(contact Polyseam for guidance in these cases). For Minimum seal depth 25mm rigid floors
paints sensitive to sealing compounds, priming with single sided seal top or soffit face
Backing with stone wool
a PVA primer is recommended. Construction Minimum floor thickness of 150
minimum 20mm deep mm and comprise aerated
3. As Protecta® FR Acrylic is water based, in cases
where corrosion protection is a problem; some concrete or concrete with a
metals may require a barrier between the sealant minimum density of 650kg/m3
and the metal surface prior to this installation.
4. When installing Protecta® FR Acrylic in hollow floor
Fire & Sound classification
slabs or boards, fire seals specified as single sided
should be installed from the soffit side of the floor
Copper pipe ≤ Ø54mm with ≥ 20mm thick pipe
assuming there is sufficient thickness of concrete
insulation in maximum aperture 300x300mm or
below the void to follow the installation guide. 100x1000mm
Where this is not the case, tubular voids should be EI 120 C/U & E 120 C/U
filled with stone wool normally the same thickness
as the depth of the floor slab. Alternatively, simply Sound reduction (seal only)
fire seal on both sides. Rw 62dB
5. When installing any backing material, cut this slightly
oversize and insert into the gap ensuring a tight
friction fit. Ensure correct depth is achieved.
Copper pipe Pipe insulation of stone
6. Fill the gap or joint with Protecta® FR Acrylic to the
wool ≥ 80kg/m3
required depth.
≥ 100cm on both sides
7. Apply the sealant generously to prevent air bubbles.
Finish the bead with a moist spatula, pallet knife or
brush.
8. Protecta® FR Acrylic can be over-painted with most
emulsion or alkyd (gloss) paints.

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904
Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 4/3/15
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 99
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Protecta Mineral Fibre BIO
Protecta FR Acrylic
surfaces that cannot tolerate direct contact;
Minimum seal depth 25mm
appropriate surface preparation should be made Application Fire stopping of copper pipes in
Backing with Protecta Maximum annular ring width 30mm
(contact Polyseam for guidance in these cases). For rigid floors
Mineral Fibre BIO Double sided seal
paints sensitive to sealing compounds, priming with
a PVA primer is recommended. minimum 25mm deep Construction Minimum floor thickness of 150
3. When installing any backing material, cut this slightly mm and comprise aerated
oversize and insert into the gap ensuring a tight concrete or concrete with a
friction fit. Ensure correct depth is achieved. minimum density of 650kg/m3
4. Fill the gap or joint with Protecta® FR Acrylic to the
required depth. Fire & Sound classification
5. Apply the sealant generously to prevent air bubbles.
Copper pipe ≤ Ø12mm with 9mm thick pipe
Finish the bead with a moist spatula, pallet knife or
insulation EI 180 C/C & E 240 C/C
brush.
6. Protecta® FR Acrylic can be over-painted with most Copper pipe ≤ Ø54mm with 9-13mm thick pipe
emulsion or alkyd (gloss) paints. insulation EI 120 C/C & E 180 C/C

Copper pipe ≤ Ø54mm with 14-25mm thick pipe


insulation EI 60 C/C & E 90 C/C

Sound reduction (seal only) Rw 62dB

Copper pipe Continuous elastomeric


or phenolic insulation

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904 Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 10/8/19
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 100
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Stone wool
surfaces that cannot tolerate direct contact;
appropriate surface preparation should be made Protecta FR Acrylic Application Fire stopping of alupex pipes in
(contact Polyseam for guidance in these cases). For Single sided seal top face rigid floors
paints sensitive to sealing compounds, priming with Minimum seal depth 25mm
a PVA primer is recommended. Backing with stone wool Maximum aperture 300x300mm Construction Minimum floor thickness of 150
3. As Protecta® FR Acrylic is water based, in cases minimum 48mm deep mm and comprise aerated
where corrosion protection is a problem; some concrete or concrete with a
metals may require a barrier between the sealant minimum density of 650kg/m3
and the metal surface prior to this installation.
4. When installing any backing material, cut this slightly
Fire & Sound classification
oversize and insert into the gap ensuring a tight
friction fit. Ensure correct depth is achieved.
Alupex pipe ≤ Ø20mm
5. Fill the gap or joint with Protecta® FR Acrylic to the
EI 120 C/C & E 120 C/C
required depth.
6. Apply the sealant generously to prevent air bubbles. Alupex pipe ≤ Ø75mm
Finish the bead with a moist spatula, pallet knife or EI 90 C/C & E 120 C/C
brush.
7. Protecta® FR Acrylic can be over-painted with most Sound reduction (seal only)
emulsion or alkyd (gloss) paints. Rw 62 dB
Alupex pipe

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904 Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 10/8/19
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 101
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants, Protecta FR Acrylic
dust and grease. Minimum seal depth 25mm
single sided seal top face Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Stonewool
surfaces that cannot tolerate direct contact;
appropriate surface preparation should be made Backing with
Application Fire stopping of alupex pipes in
(contact Polyseam for guidance in these cases). For stonewool minimum rigid floors
paints sensitive to sealing compounds, priming with 48mm deep
a PVA primer is recommended. Construction Minimum floor thickness of 150
3. When installing any backing material, cut this slightly mm and comprise aerated
oversize and insert into the gap ensuring a tight concrete or concrete with a
friction fit. Ensure correct depth is achieved. minimum density of 650kg/m3
4. Fill the gap or joint with Protecta® FR Acrylic to the
required depth.
Fire & Sound classification
5. Apply the sealant generously to prevent air bubbles.
Finish the bead with a moist spatula, pallet knife or
Alupex pipe ≤ Ø75mm with 20-50mm thick
brush.
continuous pipe insulation in maximum
6. Protecta® FR Acrylic can be over-painted with most aperture 300x300mm
emulsion or alkyd (gloss) paints. EI 120 C/C & E 180 C/C

Sound reduction (seal only)


Rw 62dB

Pipe insulation of glass or


Alupex pipe
stone wool ≥ 75kg/m3

Polyseam Ltd, 15 St Andrews Road,


Huddersfield, West Yorkshire, HD1 6SB
ETA 18/0904
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 10/8/19
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 102
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Protecta Mineral Fibre BIO
surfaces that cannot tolerate direct contact;
appropriate surface preparation should be made Protecta FR Acrylic Application Fire stopping of alupex pipes in
(contact Polyseam for guidance in these cases). For Minimum seal depth 25mm rigid floors
paints sensitive to sealing compounds, priming with Backing with Protecta
single sided seal top or soffit face
a PVA primer is recommended. Mineral Fibre BIO Construction Minimum floor thickness of 150
3. As Protecta® FR Acrylic is water based, in cases minimum 48mm deep mm and comprise aerated
where corrosion protection is a problem; some concrete or concrete with a
metals may require a barrier between the sealant minimum density of 650kg/m3
and the metal surface prior to this installation.
4. When installing Protecta® FR Acrylic in hollow floor
Fire & Sound classification
slabs or boards, fire seals specified as single sided
should be installed from the soffit side of the floor
Alupex pipe ≤ Ø75mm with ≥ 20mm thick pipe
assuming there is sufficient thickness of concrete
insulation in maximum aperture 300x300mm
below the void to follow the installation guide. EI 240 C/C & E 240 C/C
Where this is not the case, tubular voids should be
filled with stone wool normally the same thickness Sound reduction (seal only)
as the depth of the floor slab. Alternatively, simply Rw 62dB
fire seal on both sides.
5. When installing any backing material, cut this slightly
oversize and insert into the gap ensuring a tight
friction fit. Ensure correct depth is achieved.
Alupex pipe Pipe insulation of stone
6. Fill the gap or joint with Protecta® FR Acrylic to the
wool ≥ 80kg/m3
required depth.
≥ 50cm on both sides
7. Apply the sealant generously to prevent air bubbles.
Finish the bead with a moist spatula, pallet knife or
brush.
8. Protecta® FR Acrylic can be over-painted with most
emulsion or alkyd (gloss) paints.

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904
Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 4/3/15
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 103
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Protecta Mineral Fibre BIO
Protecta FR Acrylic
surfaces that cannot tolerate direct contact;
Minimum seal depth 25mm
appropriate surface preparation should be made Application Fire stopping of alupex pipes in
Backing with Protecta Maximum annular ring width 30mm
(contact Polyseam for guidance in these cases). For rigid floors
Mineral Fibre BIO Double sided seal
paints sensitive to sealing compounds, priming with
a PVA primer is recommended. minimum 25mm deep Construction Minimum floor thickness of 150
3. When installing any backing material, cut this slightly mm and comprise aerated
oversize and insert into the gap ensuring a tight concrete or concrete with a
friction fit. Ensure correct depth is achieved. minimum density of 650kg/m3
4. Fill the gap or joint with Protecta® FR Acrylic to the
required depth. Fire & Sound classification
5. Apply the sealant generously to prevent air bubbles.
Alupex pipe ≤ Ø16mm with 9mm thick pipe
Finish the bead with a moist spatula, pallet knife or
insulation EI 180 C/C & E 180 C/C
brush.
6. Protecta® FR Acrylic can be over-painted with most Alupex pipe ≤ Ø75mm with 9-13mm thick pipe
emulsion or alkyd (gloss) paints. insulation EI 60 C/C & E 120 C/C

Alupex pipe ≤ Ø75mm with 14-25mm thick pipe


insulation EI 60 C/C & E 60 C/C

Sound reduction (seal only) Rw 62dB

Alupex pipe Continuous elastomeric


or phenolic insulation

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904 Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 10/8/19
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 104
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Stone wool
surfaces that cannot tolerate direct contact;
appropriate surface preparation should be made Protecta FR Acrylic Application Fire stopping of PEX plastic
(contact Polyseam for guidance in these cases). For Minimum seal depth 25mm pipes in rigid floors
paints sensitive to sealing compounds, priming with Backing with Protecta Single sided seal top face
a PVA primer is recommended. Mineral Fibre BIO Construction Minimum floor thickness of 150
3. When installing any backing material, cut this slightly minimum 48mm deep mm and comprise aerated
oversize and insert into the gap ensuring a tight concrete or concrete with a
friction fit. Ensure correct depth is achieved. minimum density of 650kg/m3
4. Fill the gap or joint with Protecta® FR Acrylic to the
required depth.
Fire & Sound classification
5. Apply the sealant generously to prevent air bubbles.
Finish the bead with a moist spatula, pallet knife or
PEX pipe-in-pipe ≤ Ø25mm and maximum
brush.
annular ring width 30mm
6. Protecta® FR Acrylic can be over-painted with most EI 90 C/C & E 90 C/C
emulsion or alkyd (gloss) paints.
Sound reduction (seal only)
Rw 62dB

Plastic pipe

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904
Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 4/3/15
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 105
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Stone wool
surfaces that cannot tolerate direct contact;
appropriate surface preparation should be made Protecta FR Acrylic
Application Fire stopping of plastic pipes in
(contact Polyseam for guidance in these cases). For Minimum seal depth 25mm
rigid floors
paints sensitive to sealing compounds, priming with Maximum annular ring width 30mm
Backing with stone wool
a PVA primer is recommended. Double sided seal Construction Minimum floor thickness of 150
minimum 25mm deep
3. When installing any backing material, cut this slightly mm and comprise aerated
oversize and insert into the gap ensuring a tight concrete or concrete with a
friction fit. Ensure correct depth is achieved. minimum density of 650kg/m3
4. Fill the gap or joint with Protecta® FR Acrylic to the Fire & Sound classification
required depth.
PVC-U or PVC-C pipe ≤ Ø50mm with wall
5. Apply the sealant generously to prevent air bubbles.
thickness 1.6-3.7mm EI 240 U/C & E 240 U/C
Finish the bead with a moist spatula, pallet knife or
brush.
PE, ABS or SAN+PVC pipe ≤ Ø40mm with wall
6. Protecta® FR Acrylic can be over-painted with most thickness 2.0-2.4mm EI 240 U/C & E 240 U/C
emulsion or alkyd (gloss) paints.
PP pipe ≤ Ø 12mm with wall thickness 1.2mm
EI 240 U/C & E 240 U/C

PP pipe ≤ Ø75mm with wall thickness


1.2-6.8mm EI 90 U/C & E 90 U/C

Plastic pipe Sound reduction (seal only) Rw 62dB

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904
For all technical details on the products specified Huddersfield, West Yorkshire, HD1 6SB
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Tel: +44 (0) 148 4421036
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu Email: post.uk@polyseam.com
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is Sheet size: Drawn date & no:
Signed and approved:
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability A4 10/8/19
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 106
Client:
Installation Instructions

1. Before installing Protecta® FR Graphite ensure that


the surface of all service penetrations and
Job Title:
surrounding construction is free from all loose
contaminants, dust and grease.
Protecta FR Graphite Products Protecta FR Graphite
2. When installing any backing material, cut this slightly Stone wool
Minimum seal depth 25mm
oversize and insert into the gap ensuring a tight Application Fire stopping of plastic pipes in
Backing with stone wool Seal widths between 10 and 30mm
friction fit. Ensure correct depth is achieved. rigid floors
minimum 25mm deep Double sided seal
3. Fill the gap or joint with Protecta® FR Graphite to the Construction Minimum floor thickness of 150
mm and comprise aerated
required depth.
concrete or concrete with a
4. Apply the sealant generously avoiding air bubbles. minimum density of 650kg/m3
Finish the bead with a moist spatula or pallet knife. Fire & Sound classification
Avoid excessive tooling/smoothing as this may make PVC-U or PVC-C pipe ≤ 40 mm diameter with
the seal surface wet and soft. wall thickness 1.8-3.7mm EI 240 U/U
5. Protecta® FR Graphite can be over-painted with PVC-U or PVC-C pipe ≤ 110 mm diameter with
most emulsion or alkyd (gloss) paints. wall thickness 1.8-6.6mm EI 90 C/U
PE, ABS or SAN+PVC pipe ≤ 40 mm diameter
with wall thickness 2.4-3.7mm
EI 60 U/U & EI 240 U/C
PE, ABS or SAN+PVC pipe ≤ 110 mm diameter
with wall thickness 2.4-4.2mm EI 60 U/C
PE, ABS or SAN+PVC pipe ≤ 110 mm diameter
with wall thickness 4.3-10.0mm EI 90 U/C
PE, ABS or SAN+PVC pipe ≤ 110 mm diameter
with wall thickness 10.0mm EI 60 U/U
PP pipe ≤ 40 mm diameter with wall thickness
Plastic pipe 1.8mm EI 120 C/C
PP pipe ≤ 110 mm diameter with wall thickness
1.8-6.3mm EI 30 U/C
Sound reduction (seal only) 53dB

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0626 Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can
product specifications without giving notice. All information contained in this document is given in good faith and is Email: post.uk@polyseam.com
be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is Signed and approved:
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
A4 11/11/18
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given. Scale: Drawn by:
NTS K.B

P a g e | 107
Client:
Installation Instructions

1. Before installing Protecta® FR Graphite ensure that


the surface of all service penetrations and
Job Title:
surrounding construction is free from all loose
contaminants, dust and grease.
Protecta FR Graphite Products Protecta FR Graphite
2. When installing any backing material, cut this slightly Stone wool
Backing with Protecta Minimum seal depth 35mm
oversize and insert into the gap ensuring a tight
Mineral Fibre BIO Seal widths between 10 and 30mm
friction fit. Ensure correct depth is achieved. Application Fire stopping of plastic pipes in
minimum 25mm deep Double sided seal
3. Fill the gap or joint with Protecta® FR Graphite to the rigid floors
required depth.
Construction Minimum floor thickness of 150
4. Apply the sealant generously avoiding air bubbles. mm and comprise aerated
Finish the bead with a moist spatula or pallet knife. concrete or concrete with a
Avoid excessive tooling/smoothing as this may make minimum density of 650kg/m3
the seal surface wet and soft.
Fire & Sound classification
5. Protecta® FR Graphite can be over-painted with
PVC-U or PVC-C pipe ≤ 160 mm diameter with
most emulsion or alkyd (gloss) paints.
wall thickness 4.0-9.5mm EI 60 U/C

PE, ABS or SAN+PVC pipe ≤ 160 mm diameter


with wall thickness 4.9-14.6mm EI 30 U/C

PE, ABS or SAN+PVC pipe ≤ 160 mm diameter


with wall thickness 14.6mm EI 60 U/C

Sound reduction (seal only) 53dB

Plastic pipe

Polyseam Ltd, 15 St Andrews Road,


Huddersfield, West Yorkshire, HD1 6SB
ETA 18/0626 Tel: +44 (0) 148 4421036
For all technical details on the products specified Email: post.uk@polyseam.com
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu Sheet size: Drawn date & no:
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
Signed and approved: A4 11/11/18
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 108
Client:
Installation Instructions Apertures with minimum
10mm annular width
1. Before fitting the collar ensure that the gaps around services
between the pipe and the separating element are Protecta FR Acrylic on Job Title:
sealed with minimum 10mm deep Protecta FR stonewool backing
Acrylic on 40mm deep stone wool backing. Plastic pipe from soffit side
Products Protecta FR Collar
2. Place a suitable collar around the pipe and ensure Stonewool
that the collar shell and fixing lugs are positioned
tightly to the surface of the floor, so that the fixings Application Fire stopping of plastic pipes in
can be inserted fully. rigid floors

3. Where the surface is uneven, apply a sealing bead of Construction Minimum floor thickness of 150
Protecta® FR Acrylic between the floor and the collar mm and comprise aerated
shell. concrete or concrete with a
minimum density of 650kg/m3
4. Attach the collar with ≥ Ø4 x 40mm long masonry
screws or expansion bolts. Masonry screws Protecta FR Collar
or expansion bolts on soffit side
Fire & Sound classification

Fire classifications in tables on the left. For full


Services Min. Classification Services Min. Classification specifications, please refer to the Installation
Collar Collar Instructions.
Height Height
≤ Ø50mm PVC-U & PVC-C 30mm EI 60 C/C, EI 60 U/C, EI 60 C/U, EI 60 U/U (E 90) ≤ Ø50mm PP 30mm EI 120 C/C, EI 120 U/C, EI 120 C/U, EI 120 U/U Sound reduction (seal only)
≤ Ø90mm PVC-U & PVC-C 50mm EI 120 C/C, EI 120 U/C, EI 60 C/U, EI 60 U/U ≤ Ø110mm PP 50mm EI 120 C/C, EI 120 U/C, EI 60 C/U, EI 60 U/U Rw 58dB
≤ Ø110mm PVC-U & PVC-C 30mm EI 60 C/C, EI 60 U/C, EI 60 C/U, EI 60 U/U ≤ Ø140mm PP 60mm EI 120 C/C, EI 120 U/C, EI 60 C/U, EI 60 U/U
≤ Ø110mm PVC-U & PVC-C 50mm EI 120 C/C, EI 90 U/C (E 120), EI 60 C/U ≤ Ø160mm PP 60mm EI 180 C/C, EI 180 U/C, EI 60 C/U, EI 60 U/U
≤ Ø160mm PVC-U & PVC-C 60mm EI 120 C/C, EI 120 U/C, EI 60 C/U, EI 60 U/U ≤ Ø200mm PP 60mm EI 120 C/C
≤ Ø200mm PVC-U & PVC-C 60mm EI 60 C/C (E 120) ≤ Ø250mm PP 75mm EI 60 C/C
≤ Ø315mm PVC-U & PVC-C 75mm EI 60 C/C Ø315x28.6mm PP 75mm EI 60 C/C
≤ Ø400mm PVC-U & PVC-C 100mm EI 60 C/C ≤ Ø400mm PP 100mm EI 30 C/C
≤ Ø55mm PE, ABS & SAN+PVC 30mm EI 60 C/C, EI 60 U/C, EI 60 C/U, EI 60 U/U
≤ Ø50mm PE, ABS & SAN+PVC 50mm EI 240 C/C, EI 240 U/C, EI 60 C/U, EI 60 U/U
≤ Ø110mm PE, ABS & SAN+PVC 30mm EI 60 C/C, EI 60 U/C
≤ Ø110mm PE, ABS & SAN+PVC 50mm EI 120 C/C, EI 120 U/C, EI 60 C/U, EI 60 U/U
≤ Ø160mm PE, ABS & SAN+PVC 60mm EI 120 C/C, EI 120 U/C, EI 60 C/U, EI 60 U/U
≤ Ø200mm PE, ABS & SAN+PVC 60mm EI 120 C/C (E 240)
≤ Ø250mm PE, ABS & SAN+PVC 75mm EI 240 C/C
Ø315x18.7mm PE, ABS & SAN+PVC 75mm EI 240 C/C Polyseam Ltd, 15 St Andrews Road,
Ø400x36.3mm PE, ABS & SAN+PVC 100mm EI 90 C/C Huddersfield, West Yorkshire, HD1 6SB
ETA 18/0854
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 20/8/19
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 109
Client:
Installation Instructions Apertures with minimum
10mm annular width
1. Before fitting the collar ensure that the gaps around services Protecta FR Acrylic on
between the pipe and the separating element are
Job Title:
stonewool backing
sealed with minimum 10mm deep Protecta FR from soffit side
Composite plastic pipe
Acrylic on 40mm deep stone wool backing.
Products Protecta FR Collar
2. Place a suitable collar around the pipe and ensure Stonewool
that the collar shell and fixing lugs are positioned
tightly to the surface of the floor, so that the fixings Application Fire stopping of composite
can be inserted fully. plastic pipes in rigid floors

3. Where the surface is uneven, apply a sealing bead of Construction Minimum floor thickness of 150
Protecta® FR Acrylic between the floor and the collar mm and comprise aerated
shell. concrete or concrete with a
minimum density of 650kg/m3
4. Attach the collar with ≥ Ø4 x 40mm long masonry
screws or expansion bolts. Masonry screws Protecta FR Collar
or expansion bolts on soffit side
Fire & Sound classification

Services Minimum Collar Classification Fire classifications in tables on the left. For full
Height specifications, please refer to the Installation
≤ Ø32mm Aquatherm Green SDR9 30mm EI 240 C/C Instructions.
≤ Ø50mm Aquatherm Green SDR9 50mm EI 240 C/C
≤ Ø110mm Aquatherm Green SDR9 50mm EI 120 C/C Sound reduction (seal only)
≤ Ø50mm BluePower 50mm EI 180 C/C, EI 180 U/C, EI 180 C/U, EI 180 U/U Rw 58dB
≤ Ø110mm BluePower 50mm EI 180 C/C, EI 180 U/C, EI 180 C/U
Ø125mm BluePower 60mm EI 180 C/C, EI 180 U/C, EI 180 C/U
Ø160mm BluePower 60mm EI 240 C/C, EI 240 U/C, EI 240 C/U
≤ Ø50mm Geberit Silent-PP 50mm EI 240 C/C, EI 240 U/C, EI 240 C/U, EI 240 U/U
≤ Ø110mm Geberit Silent-PP 50mm EI 180 C/C, EI 180 U/C, EI 180 C/U
≤ Ø50mm Polo-Kal NG pipes 50mm EI 240 C/C, EI 240 U/C, EI 240 C/U, EI 240 U/U
≤ Ø110mm Polo-Kal NG pipes 50mm EI 240 C/C, EI 240 U/C, EI 240 C/U
Ø125mm Polo-Kal NG pipes 60mm EI 240 C/C, EI 240 U/C
Ø160mm Polo-Kal NG pipes 60mm EI 240 C/C, EI 240 U/C (E 240 C/U)
≤ Ø50mm Rehau Raupiano Plus 50mm EI 240 C/C, EI 240 U/C, EI 240 C/U, EI 240 U/U
≤ Ø110mm Rehau Raupiano Plus 50mm EI 120 C/C, EI 120 U/C, EI 120 C/U
Ø125mm Rehau Raupiano Plus 60mm EI 180 C/C, EI 180 U/C, EI 180 C/U
Ø160mm Rehau Raupiano Plus 60mm EI 240 C/C, EI 240 U/C (E 240 C/U)
≤ Ø50mm Wavin SiTech 50mm EI 240 C/C, EI 240 U/C, EI 240 C/U, EI 240 U/U Polyseam Ltd, 15 St Andrews Road,
≤ Ø110mm Wavin SiTech 50mm EI 180 C/C, EI 180 U/C, EI 180 C/U Huddersfield, West Yorkshire, HD1 6SB
ETA 18/0854
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 20/8/19
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 110
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Protecta FR Acrylic Stone wool
surfaces that cannot tolerate direct contact; Minimum seal depth 25mm
appropriate surface preparation should be made Backing with stone wool Application Fire stopping of conduits in
Maximum annular ring width 30mm
(contact Polyseam for guidance in these cases). For minimum 25mm deep rigid floors
Double sided seal
paints sensitive to sealing compounds, priming with
a PVA primer is recommended. Construction Minimum floor thickness of 150
3. When installing any backing material, cut this slightly mm and comprise aerated
oversize and insert into the gap ensuring a tight concrete or concrete with a
friction fit. Ensure correct depth is achieved. minimum density of 650kg/m3
4. Fill the gap or joint with Protecta® FR Acrylic to the Fire & Sound classification
required depth.
PVC-U & PVC-C conduit/pipe ≤ Ø40mm with
5. Apply the sealant generously to prevent air bubbles.
wall thickness 1.6 – 3.7mm
Finish the bead with a moist spatula, pallet knife or
EI 240 U/C & E 240 U/C
brush.
6. Protecta® FR Acrylic can be over-painted with most PE, ABS & SAN+PVC conduit/pipe ≤ Ø40mm
emulsion or alkyd (gloss) paints. with wall thickness 2.0 – 2.4mm
EI 180 U/C & E 180 U/C

PP conduit/pipe ≤ Ø40mm with wall thickness


1.2 – 1.8mm EI 180 U/C & E 180 U/C
Conduit (plastic
pipe with cables) Sound reduction (seal only) Rw 62dB

Cables ≤ Ø21mm
single or in a
bundle

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904
For all technical details on the products specified Huddersfield, West Yorkshire, HD1 6SB
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Tel: +44 (0) 148 4421036
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu Email: post.uk@polyseam.com
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is Sheet size: Drawn date & no:
Signed and approved:
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability A4 9/4/18
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
Scale: Drawn by:
NTS K.B

P a g e | 111
Client:
Installation Instructions

1. Before installing Protecta® FR Graphite ensure that


the surface of all service penetrations and
Job Title:
surrounding construction is free from all loose
contaminants, dust and grease.
Protecta FR Graphite Products Protecta FR Graphite
2. When installing any backing material, cut this slightly Minimum seal depth 25mm Stone wool
oversize and insert into the gap ensuring a tight Backing with stone wool Seal widths between 10 and 30mm
friction fit. Ensure correct depth is achieved. minimum 25mm deep Double sided seal Application Fire stopping of conduits in
3. Fill the gap or joint with Protecta® FR Graphite to the rigid floors
required depth.
Construction Minimum floor thickness of 150
4. Apply the sealant generously avoiding air bubbles. mm and comprise aerated
Finish the bead with a moist spatula or pallet knife. concrete or concrete with a
Avoid excessive tooling/smoothing as this may make minimum density of 650kg/m3
the seal surface wet and soft. Fire & Sound classification
5. Protecta® FR Graphite can be over-painted with
PE, ABS or SAN+PVC conduit/pipe ≤ Ø110mm
most emulsion or alkyd (gloss) paints.
with wall thickness 2.4 - 10.0mm EI 60 U/C

PP conduit/pipe ≤ Ø110mm with wall thickness


2.7mm EI 90 U/C

PVC-U or PVC-C conduit/pipe ≤ Ø110mm with


wall thickness 1.8-6.6mm EI 90 U/C

Sound reduction (seal only) Rw 53dB


Conduit (plastic
pipe with cables)

Cables ≤ Ø20mm
single or in a
bundle

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0626
For all technical details on the products specified Huddersfield, West Yorkshire, HD1 6SB
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Tel: +44 (0) 148 4421036
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu Email: post.uk@polyseam.com
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is Sheet size: Drawn date & no:
Signed and approved:
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability A4 11/11/18
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
Scale: Drawn by:
NTS K.B

P a g e | 112
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Protecta Mineral Fibre BIO
surfaces that cannot tolerate direct contact;
appropriate surface preparation should be made Application Fire stopping of cables in rigid
(contact Polyseam for guidance in these cases). For Backing with Protecta walls
paints sensitive to sealing compounds, priming with Mineral Fibre BIO
a PVA primer is recommended. minimum 48mm deep Construction Minimum wall thickness of 150
3. When installing any backing material, cut this slightly mm and comprise concrete,
oversize and insert into the gap ensuring a tight aerated concrete or masonry,
Protecta FR Acrylic
friction fit. Ensure correct depth is achieved. with a density of ≥ 650 kg/m3
Minimum seal
4. Fill the gap or joint with Protecta® FR Acrylic to the depth 25mm
required depth.
Fire & Sound classification
5. Apply the sealant generously to prevent air bubbles.
Finish the bead with a moist spatula, pallet knife or
Cable ≤ Ø21mm single sided seal in maximum
brush.
Single cable aperture 300x300mm EI 60 & E 240
6. Protecta® FR Acrylic can be over-painted with most
emulsion or alkyd (gloss) paints. Cable ≤ Ø21mm single sided seal in maximum
aperture Ø87mm EI 90 & E 240

Cable ≤ Ø21mm single sided seal in maximum


aperture 35x35mm or Ø 36mm EI 120 & E 240

Sound reduction (seal only) Rw 62 dB

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904 Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 7/3/15
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 113
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Stone wool
surfaces that cannot tolerate direct contact;
appropriate surface preparation should be made Application Fire stopping of cables in rigid
(contact Polyseam for guidance in these cases). For walls
paints sensitive to sealing compounds, priming with Backing with stone wool
a PVA primer is recommended. minimum 25mm deep Construction Minimum wall thickness of 150
3. When installing any backing material, cut this slightly mm and comprise concrete,
oversize and insert into the gap ensuring a tight Protecta FR Acrylic aerated concrete or masonry,
friction fit. Ensure correct depth is achieved. Minimum seal depth 15mm with a density of ≥ 650 kg/m3
4. Fill the gap or joint with Protecta® FR Acrylic to the Double sided seal
required depth.
Fire & Sound classification
5. Apply the sealant generously to prevent air bubbles.
Finish the bead with a moist spatula, pallet knife or Single or Cables ≤ Ø21mm single or in a bundle
brush. bundled cables ≤ Ø100mm in maximum aperture 300x300mm
6. Protecta® FR Acrylic can be over-painted with most EI 120 & E 240
emulsion or alkyd (gloss) paints.
Cables ≤ Ø80mm single or in a bundle
≤ Ø100mm in maximum aperture 300x300mm
EI 60 & E 120

Sound reduction (seal only) Rw 62 dB

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904
Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 7/3/15
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 114
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Protecta Mineral Fibre BIO
surfaces that cannot tolerate direct contact;
appropriate surface preparation should be made Application Fire stopping of cables in rigid
(contact Polyseam for guidance in these cases). For Backing with Protecta walls
paints sensitive to sealing compounds, priming with Mineral Fibre BIO
a PVA primer is recommended. minimum 48mm deep Construction Minimum wall thickness of 150
3. When installing any backing material, cut this slightly mm and comprise concrete,
oversize and insert into the gap ensuring a tight aerated concrete or masonry,
Protecta FR Acrylic
friction fit. Ensure correct depth is achieved. with a density of ≥ 650 kg/m3
Minimum seal depth 25mm
4. Fill the gap or joint with Protecta® FR Acrylic to the Double sided seal
required depth.
Fire & Sound classification
5. Apply the sealant generously to prevent air bubbles.
Finish the bead with a moist spatula, pallet knife or
Cables ≤ Ø21mm single or in a bundle
brush. Single or ≤ Ø100mm in maximum aperture 300x300mm
6. Protecta® FR Acrylic can be over-painted with most bundled cables EI 240 & E 240
emulsion or alkyd (gloss) paints.
Cables ≤ Ø80mm single or in a bundle
≤ Ø100mm in maximum aperture 300x300mm
EI 60 & E 240

Sound reduction (seal only) Rw 62 dB

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904
Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 7/3/15
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 115
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Stone wool
surfaces that cannot tolerate direct contact;
appropriate surface preparation should be made Backing with stone wool
Application Fire stopping of steel pipes in
(contact Polyseam for guidance in these cases). For minimum 12.5mm deep
rigid walls
paints sensitive to sealing compounds, priming with
a PVA primer is recommended. Protecta FR Acrylic Construction Minimum wall thickness of 100
3. As Protecta® FR Acrylic is water based, in cases Minimum seal depth mm and comprise concrete,
where corrosion protection is a problem; some Steel 12.5mm double sided aerated concrete or masonry,
metals may require a barrier between the sealant pipe with a density of ≥ 650 kg/m3
and the metal surface prior to this installation.
4. When installing any backing material, cut this slightly Fire & Sound classification
oversize and insert into the gap ensuring a tight
Steel pipe ≤ Ø30mm without pipe insulation in
friction fit. Ensure correct depth is achieved.
maximum aperture 300x300mm
5. Fill the gap or joint with Protecta® FR Acrylic to the
required depth. EI 90 C/C & E 90 C/C
6. Apply the sealant generously to prevent air bubbles.
Finish the bead with a moist spatula, pallet knife or Sound reduction (seal only)
brush. Rw 62dB
7. Protecta® FR Acrylic can be over-painted with most
emulsion or alkyd (gloss) paints.

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904 Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 8/4/18
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 116
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Stone wool
surfaces that cannot tolerate direct contact;
appropriate surface preparation should be made Backing with stone wool
Application Fire stopping of steel pipes in
(contact Polyseam for guidance in these cases). For minimum 25mm deep
rigid walls
paints sensitive to sealing compounds, priming with
a PVA primer is recommended. Protecta FR Acrylic Construction Minimum wall thickness of 100
3. As Protecta® FR Acrylic is water based, in cases Minimum seal depth mm and comprise concrete,
where corrosion protection is a problem; some Steel 25mm double sided seal aerated concrete or masonry,
metals may require a barrier between the sealant pipe with a density of ≥ 650 kg/m3
and the metal surface prior to this installation.
4. When installing any backing material, cut this slightly Fire & Sound classification
oversize and insert into the gap ensuring a tight
Steel pipe Ø22 – Ø30mm without pipe
friction fit. Ensure correct depth is achieved.
insulation in maximum aperture 300x300mm
5. Fill the gap or joint with Protecta® FR Acrylic to the
required depth. EI 120 C/C & E 120 C/C
6. Apply the sealant generously to prevent air bubbles.
Finish the bead with a moist spatula, pallet knife or Sound reduction (seal only)
brush. Rw 62dB
7. Protecta® FR Acrylic can be over-painted with most
emulsion or alkyd (gloss) paints.

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904 Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 8/4/18
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 117
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Stone wool
surfaces that cannot tolerate direct contact;
appropriate surface preparation should be made Backing with stone wool
Application Fire stopping of steel pipes in
(contact Polyseam for guidance in these cases). For minimum 15mm deep
rigid walls
paints sensitive to sealing compounds, priming with
a PVA primer is recommended. Protecta FR Acrylic Construction Minimum wall thickness of 120
3. As Protecta® FR Acrylic is water based, in cases Minimum seal depth mm and comprise concrete,
where corrosion protection is a problem; some Steel 15mm double sided seal aerated concrete or masonry,
metals may require a barrier between the sealant pipe with a density of ≥ 650 kg/m3
and the metal surface prior to this installation.
4. When installing any backing material, cut this slightly
Fire & Sound classification
oversize and insert into the gap ensuring a tight
friction fit. Ensure correct depth is achieved.
Steel pipe ≤ Ø324mm without pipe insulation in
5. Fill the gap or joint with Protecta® FR Acrylic to the
maximum aperture 300x300mm or Ø344mm
required depth.
6. Apply the sealant generously to prevent air bubbles. E 120 C/U
Finish the bead with a moist spatula, pallet knife or
brush. Sound reduction (seal only)
7. Protecta® FR Acrylic can be over-painted with most Rw 62dB
emulsion or alkyd (gloss) paints.

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904
Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 13/8/19
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 118
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Protecta Mineral Fibre BIO
surfaces that cannot tolerate direct contact; Backing with Protecta
appropriate surface preparation should be made Mineral Fibre BIO
Application Fire stopping of steel pipes in
(contact Polyseam for guidance in these cases). For minimum 48mm deep
rigid walls
paints sensitive to sealing compounds, priming with
a PVA primer is recommended. Protecta FR Acrylic Construction Minimum wall thickness of 150
3. When installing any backing material, cut this slightly Steel Minimum seal depth mm and comprise concrete,
oversize and insert into the gap ensuring a tight pipe 25mm single sided seal aerated concrete or masonry,
friction fit. Ensure correct depth is achieved. with a density of ≥ 650 kg/m3
4. Fill the gap or joint with Protecta® FR Acrylic to the Fire & Sound classification
required depth.
Steel pipe ≤ Ø40mm with 20mm thick pipe
5. Apply the sealant generously to prevent air bubbles.
Continuous pipe insulation in maximum aperture 300x300mm or
Finish the bead with a moist spatula, pallet knife or
insulation of stone Ø504mm
brush.
EI 240 C/U & E 240 C/U
6. Protecta® FR Acrylic can be over-painted with most wool ≥ 80kg/m3
emulsion or alkyd (gloss) paints. Steel pipe ≤ Ø324mm with 30-80mm thick pipe
insulation in maximum aperture 300x300mm or
Ø504mm
EI 180 C/U & E 180 C/U

Sound reduction (seal only)


Rw 62dB

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904 Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 9/4/18
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 119
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Stone wool
surfaces that cannot tolerate direct contact;
appropriate surface preparation should be made Backing with stone wool
Application Fire stopping of steel pipes in
(contact Polyseam for guidance in these cases). For minimum 25mm deep
rigid walls
paints sensitive to sealing compounds, priming with
a PVA primer is recommended. Protecta FR Acrylic Construction Minimum wall thickness of 150
3. When installing any backing material, cut this slightly Steel Minimum seal depth mm and comprise concrete,
oversize and insert into the gap ensuring a tight pipe 15mm double sided seal aerated concrete or masonry,
friction fit. Ensure correct depth is achieved. with a density of ≥ 650 kg/m3
4. Fill the gap or joint with Protecta® FR Acrylic to the
required depth.
Fire & Sound classification
5. Apply the sealant generously to prevent air bubbles.
Finish the bead with a moist spatula, pallet knife or Continuous pipe
Steel pipe ≤ Ø324mm with 30-80mm thick pipe
brush. insulation of stone
insulation in maximum aperture 300x300mm or
6. Protecta® FR Acrylic can be over-painted with most wool ≥ 80kg/m3
Ø504mm
emulsion or alkyd (gloss) paints. EI 240 C/U & E 240 C/U

Sound reduction (seal only)


Rw 62dB

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904
Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 20/4/15
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 120
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Stone wool
surfaces that cannot tolerate direct contact; Backing with stone wool
appropriate surface preparation should be made minimum 20mm deep Application Fire stopping of steel pipes in
(contact Polyseam for guidance in these cases). For rigid walls
paints sensitive to sealing compounds, priming with
Protecta FR Acrylic
a PVA primer is recommended. Construction Minimum wall thickness of 150
Minimum seal depth
3. As Protecta® FR Acrylic is water based, in cases mm and comprise concrete,
Steel 15mm single sided seal
where corrosion protection is a problem; some aerated concrete or masonry,
metals may require a barrier between the sealant pipe with a density of ≥ 650 kg/m3
and the metal surface prior to this installation. Fire & Sound classification
4. When installing any backing material, cut this slightly
Steel pipe ≤ Ø40mm with ≥ 20mm thick pipe
oversize and insert into the gap ensuring a tight
insulation and maximum annular ring width
friction fit. Ensure correct depth is achieved.
18mm
5. Fill the gap or joint with Protecta® FR Acrylic to the
EI 240 C/U & E 240 C/U
required depth.
Pipe insulation of stone
6. Apply the sealant generously to prevent air bubbles. Steel pipe ≤ Ø219mm with ≥ 30mm thick pipe
wool ≥ 80kg/m3
Finish the bead with a moist spatula, pallet knife or insulation and maximum annular ring width
≥ 100cm on both sides
brush. 18mm
7. Protecta® FR Acrylic can be over-painted with most EI 90 C/U & E 180 C/U
emulsion or alkyd (gloss) paints.
Sound reduction (seal only)
Rw 62dB

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904 Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 7/3/15
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 121
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Stone wool
surfaces that cannot tolerate direct contact; Backing with stone wool
appropriate surface preparation should be made minimum 25mm deep Application Fire stopping of steel pipes in
(contact Polyseam for guidance in these cases). For rigid walls
paints sensitive to sealing compounds, priming with
Protecta FR Acrylic
a PVA primer is recommended. Construction Minimum wall thickness of 150
Minimum seal depth
3. As Protecta® FR Acrylic is water based, in cases mm and comprise concrete,
Steel 25mm single sided seal
where corrosion protection is a problem; some aerated concrete or masonry,
metals may require a barrier between the sealant pipe with a density of ≥ 650 kg/m3
and the metal surface prior to this installation.
4. When installing any backing material, cut this slightly Fire & Sound classification
oversize and insert into the gap ensuring a tight
Steel pipe ≤ Ø40mm with ≥ 20mm thick pipe
friction fit. Ensure correct depth is achieved.
insulation in maximum aperture 300x300mm
5. Fill the gap or joint with Protecta® FR Acrylic to the
EI 60 C/U & E 240 C/U
required depth.
Pipe insulation of stone
6. Apply the sealant generously to prevent air bubbles. Steel pipe ≤ Ø219mm with ≥ 30mm thick pipe
wool ≥ 80kg/m3
Finish the bead with a moist spatula, pallet knife or insulation in maximum aperture 300x300mm
≥ 100cm on both sides
brush. EI 60 C/U & E 240 C/U
7. Protecta® FR Acrylic can be over-painted with most
emulsion or alkyd (gloss) paints. Sound reduction (seal only)
Rw 62dB

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904 Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 13/8/19
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 122
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Stone wool
surfaces that cannot tolerate direct contact; Backing with stone wool
appropriate surface preparation should be made minimum 20mm deep Application Fire stopping of steel pipes in
(contact Polyseam for guidance in these cases). For rigid walls
paints sensitive to sealing compounds, priming with
Protecta FR Acrylic
a PVA primer is recommended. Construction Minimum wall thickness of 150
Minimum seal depth
3. As Protecta® FR Acrylic is water based, in cases mm and comprise concrete,
Steel 15mm double sided seal
where corrosion protection is a problem; some aerated concrete or masonry,
metals may require a barrier between the sealant pipe with a density of ≥ 650 kg/m3
and the metal surface prior to this installation.
4. When installing any backing material, cut this slightly Fire & Sound classification
oversize and insert into the gap ensuring a tight
Steel pipe ≤ Ø219mm with ≥ 30mm thick pipe
friction fit. Ensure correct depth is achieved.
insulation in maximum aperture 300x300mm
5. Fill the gap or joint with Protecta® FR Acrylic to the
required depth. EI 120 C/U & E 240 C/U
Pipe insulation of stone
6. Apply the sealant generously to prevent air bubbles.
wool ≥ 80kg/m3
Finish the bead with a moist spatula, pallet knife or Sound reduction (seal only)
≥ 100cm on both sides
brush. Rw 62dB
7. Protecta® FR Acrylic can be over-painted with most
emulsion or alkyd (gloss) paints.

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904 Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 7/3/15
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 123
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Stone wool
surfaces that cannot tolerate direct contact;
appropriate surface preparation should be made Application Fire stopping of steel pipes in
(contact Polyseam for guidance in these cases). For rigid walls
Backing with stone Protecta FR Acrylic
paints sensitive to sealing compounds, priming with
wool minimum Minimum seal depth 12.5mm
a PVA primer is recommended. Construction Minimum wall thickness of 100
20mm deep Maximum annular ring width 30mm
3. When installing any backing material, cut this slightly mm and comprise concrete,
oversize and insert into the gap ensuring a tight Double sided seal aerated concrete or masonry,
friction fit. Ensure correct depth is achieved. with a density of ≥ 650 kg/m3
4. Fill the gap or joint with Protecta® FR Acrylic to the
required depth.
Steel pipe Fire & Sound classification
5. Apply the sealant generously to prevent air bubbles.
Finish the bead with a moist spatula, pallet knife or
Continuous elastomeric Steel pipe ≤ Ø40mm with 13 – 19mm thick pipe
brush.
insulation insulation
6. Protecta® FR Acrylic can be over-painted with most EI 120 C/C & E 120 C/C
emulsion or alkyd (gloss) paints.
Sound reduction (seal only)
Rw 62dB

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904
Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 7/3/15
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 124
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Protecta Mineral Fibre BIO
surfaces that cannot tolerate direct contact;
appropriate surface preparation should be made Application Fire stopping of steel pipes in
(contact Polyseam for guidance in these cases). For Backing with
rigid walls
paints sensitive to sealing compounds, priming with Protecta Mineral Protecta FR Acrylic
a PVA primer is recommended. Fibre BIO minimum Minimum seal depth 25mm Construction Minimum wall thickness of 100
3. When installing any backing material, cut this slightly 25mm deep Maximum annular ring width 30mm mm and comprise concrete,
oversize and insert into the gap ensuring a tight Double sided seal aerated concrete or masonry,
friction fit. Ensure correct depth is achieved. with a density of ≥ 650 kg/m3
4. Fill the gap or joint with Protecta® FR Acrylic to the
required depth.
Steel pipe Fire & Sound classification
5. Apply the sealant generously to prevent air bubbles.
Finish the bead with a moist spatula, pallet knife or
Continuous elastomeric Steel pipe ≤ Ø165mm with 13 – 19mm thick
brush.
insulation pipe insulation
6. Protecta® FR Acrylic can be over-painted with most EI 60 C/C & E 120 C/C
emulsion or alkyd (gloss) paints.
Sound reduction (seal only)
Rw 62dB

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904
Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 7/3/15
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 125
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Protecta Mineral Fibre BIO
surfaces that cannot tolerate direct contact;
appropriate surface preparation should be made Application Fire stopping of steel pipes in
(contact Polyseam for guidance in these cases). For Backing with rigid walls
Protecta FR Acrylic
paints sensitive to sealing compounds, priming with stonewool minimum Minimum seal depth 25mm
a PVA primer is recommended. 25mm deep Construction Minimum wall thickness of 150
Maximum annular ring width 30mm mm and comprise concrete,
3. When installing any backing material, cut this slightly
Double sided seal aerated concrete or masonry,
oversize and insert into the gap ensuring a tight
friction fit. Ensure correct depth is achieved. with a density of ≥ 650 kg/m3
4. Fill the gap or joint with Protecta® FR Acrylic to the
required depth. Fire & Sound classification
Steel pipe
5. Apply the sealant generously to prevent air bubbles.
Steel pipe ≤ Ø22mm with 13mm thick pipe
Finish the bead with a moist spatula, pallet knife or
Continuous elastomeric insulation EI 180 C/U & E 240 C/U
brush.
6. Protecta® FR Acrylic can be over-painted with most insulation
Steel pipe ≤ Ø114mm with 13 – 25mm thick
emulsion or alkyd (gloss) paints. pipe insulation EI 90 C/U & E 120 C/U

Steel pipe ≤ Ø114mm with 26 – 50mm thick


pipe insulation EI 60 C/U & E 60 C/U

Sound reduction (seal only)


Rw 62dB

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904 Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 9/4/18
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 126
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Stone wool
surfaces that cannot tolerate direct contact;
appropriate surface preparation should be made Backing with stone wool
Application Fire stopping of copper pipes in
(contact Polyseam for guidance in these cases). For minimum 12.5mm deep
rigid walls
paints sensitive to sealing compounds, priming with
a PVA primer is recommended. Protecta FR Acrylic Construction Minimum wall thickness of 100
3. As Protecta® FR Acrylic is water based, in cases Minimum seal depth mm and comprise concrete,
where corrosion protection is a problem; some Copper 12.5mm double sided aerated concrete or masonry,
metals may require a barrier between the sealant pipe with a density of ≥ 650 kg/m3
and the metal surface prior to this installation.
4. When installing any backing material, cut this slightly Fire & Sound classification
oversize and insert into the gap ensuring a tight
Copper pipe ≤ Ø12mm without pipe insulation
friction fit. Ensure correct depth is achieved.
in maximum aperture 300x300mm
5. Fill the gap or joint with Protecta® FR Acrylic to the
EI 60 C/C & E 90 C/C
required depth.
6. Apply the sealant generously to prevent air bubbles. Copper pipe Ø13-Ø22mm without pipe
Finish the bead with a moist spatula, pallet knife or insulation in maximum aperture 300x300mm
brush. EI 30 C/C & E 90 C/C
7. Protecta® FR Acrylic can be over-painted with most
emulsion or alkyd (gloss) paints. Sound reduction (seal only) Rw 62dB

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904 Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 14/8/19
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 127
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Stone wool
surfaces that cannot tolerate direct contact;
appropriate surface preparation should be made Backing with stone wool
Application Fire stopping of copper pipes in
(contact Polyseam for guidance in these cases). For minimum 15mm deep
rigid walls
paints sensitive to sealing compounds, priming with
a PVA primer is recommended. Protecta FR Acrylic Construction Minimum wall thickness of 120
3. As Protecta® FR Acrylic is water based, in cases Minimum seal depth mm and comprise concrete,
where corrosion protection is a problem; some Copper 15mm double sided aerated concrete or masonry,
metals may require a barrier between the sealant pipe with a density of ≥ 650 kg/m3
and the metal surface prior to this installation.
4. When installing any backing material, cut this slightly
Fire & Sound classification
oversize and insert into the gap ensuring a tight
friction fit. Ensure correct depth is achieved.
Copper pipe ≤ Ø54mm without pipe insulation
5. Fill the gap or joint with Protecta® FR Acrylic to the
in maximum aperture 300x300mm
required depth. E 120 C/C
6. Apply the sealant generously to prevent air bubbles.
Finish the bead with a moist spatula, pallet knife or Sound reduction (seal only)
brush. Rw 62dB
7. Protecta® FR Acrylic can be over-painted with most
emulsion or alkyd (gloss) paints.

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904
Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 14/8/19
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 128
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Stone wool
surfaces that cannot tolerate direct contact;
appropriate surface preparation should be made Backing with stone wool Application Fire stopping of copper pipes in
(contact Polyseam for guidance in these cases). For minimum 12.5mm deep rigid walls
paints sensitive to sealing compounds, priming with
a PVA primer is recommended. Protecta FR Acrylic Construction Minimum wall thickness of 100
3. When installing any backing material, cut this slightly Minimum seal depth mm and comprise concrete,
oversize and insert into the gap ensuring a tight Copper 12.5mm double sided seal aerated concrete or masonry,
friction fit. Ensure correct depth is achieved. pipe with a density of ≥ 650 kg/m3
4. Fill the gap or joint with Protecta® FR Acrylic to the
required depth.
Fire & Sound classification
5. Apply the sealant generously to prevent air bubbles.
Finish the bead with a moist spatula, pallet knife or
Copper pipe ≤ Ø54mm with 20-80mm thick pipe
brush. Continuous pipe
insulation in maximum aperture 300x300mm or
6. Protecta® FR Acrylic can be over-painted with most insulation of stone
Ø504mm
emulsion or alkyd (gloss) paints. wool ≥ 80kg/m3
EI 60 C/C & E 120 C/C

Sound reduction (seal only)


Rw 62dB

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904
Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 14/8/19
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 129
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Stone wool
surfaces that cannot tolerate direct contact; Backing with stone wool
appropriate surface preparation should be made minimum 20mm deep Application Fire stopping of copper pipes in
(contact Polyseam for guidance in these cases). For rigid walls
paints sensitive to sealing compounds, priming with
Protecta FR Acrylic
a PVA primer is recommended. Construction Minimum wall thickness of 150
Minimum seal depth
3. As Protecta® FR Acrylic is water based, in cases mm and comprise concrete,
Copper 15mm single sided seal
where corrosion protection is a problem; some aerated concrete or masonry,
metals may require a barrier between the sealant pipe with a density of ≥ 650 kg/m3
and the metal surface prior to this installation.
4. When installing any backing material, cut this slightly Fire & Sound classification
oversize and insert into the gap ensuring a tight
Copper pipe ≤ Ø12mm with ≥ 20mm thick pipe
friction fit. Ensure correct depth is achieved.
insulation and annular ring width 10mm
5. Fill the gap or joint with Protecta® FR Acrylic to the
EI 240 C/U & E 240 C/U
required depth.
Pipe insulation of stone
6. Apply the sealant generously to prevent air bubbles. Copper pipe ≤ Ø54mm with ≥ 20mm thick pipe
wool ≥ 80kg/m3
Finish the bead with a moist spatula, pallet knife or insulation and annular ring width 10mm
≥ 100cm on both sides
brush. EI 180 C/U & E 240 C/U
7. Protecta® FR Acrylic can be over-painted with most
emulsion or alkyd (gloss) paints. Sound reduction (seal only)
Rw 62dB

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904 Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 9/3/15
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 130
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Stone wool
surfaces that cannot tolerate direct contact; Backing with stone wool
appropriate surface preparation should be made minimum 25mm deep Application Fire stopping of copper pipes in
(contact Polyseam for guidance in these cases). For rigid walls
paints sensitive to sealing compounds, priming with
Protecta FR Acrylic
a PVA primer is recommended. Construction Minimum wall thickness of 150
Minimum seal depth
3. As Protecta® FR Acrylic is water based, in cases mm and comprise concrete,
Copper 25mm single sided seal
where corrosion protection is a problem; some aerated concrete or masonry,
metals may require a barrier between the sealant pipe with a density of ≥ 650 kg/m3
and the metal surface prior to this installation.
4. When installing any backing material, cut this slightly
Fire & Sound classification
oversize and insert into the gap ensuring a tight
friction fit. Ensure correct depth is achieved.
Copper pipe ≤ Ø54mm with ≥ 20mm thick pipe
5. Fill the gap or joint with Protecta® FR Acrylic to the
insulation in maximum aperture 300x300mm
required depth. EI 60 C/U & E 240 C/U
Pipe insulation of stone
6. Apply the sealant generously to prevent air bubbles.
wool ≥ 80kg/m3
Finish the bead with a moist spatula, pallet knife or Sound reduction (seal only)
≥ 100cm on both sides
brush. Rw 62dB
7. Protecta® FR Acrylic can be over-painted with most
emulsion or alkyd (gloss) paints.

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904
Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 13/8/19
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 131
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Stone wool
surfaces that cannot tolerate direct contact; Backing with stone wool
appropriate surface preparation should be made minimum 20mm deep Application Fire stopping of copper pipes in
(contact Polyseam for guidance in these cases). For rigid walls
paints sensitive to sealing compounds, priming with
Protecta FR Acrylic
a PVA primer is recommended. Construction Minimum wall thickness of 100
Minimum seal depth
3. As Protecta® FR Acrylic is water based, in cases mm and comprise concrete,
Copper 12.5mm double sided seal
where corrosion protection is a problem; some aerated concrete or masonry,
metals may require a barrier between the sealant pipe with a density of ≥ 650 kg/m3
and the metal surface prior to this installation.
4. When installing any backing material, cut this slightly Fire & Sound classification
oversize and insert into the gap ensuring a tight
Copper pipe ≤ Ø54mm with ≥ 20mm thick pipe
friction fit. Ensure correct depth is achieved.
insulation in maximum aperture 300x300mm
5. Fill the gap or joint with Protecta® FR Acrylic to the
required depth. EI 120 C/U & E 120 C/U
Pipe insulation of stone
6. Apply the sealant generously to prevent air bubbles.
wool ≥ 80kg/m3
Finish the bead with a moist spatula, pallet knife or Sound reduction (seal only)
≥ 50cm on both sides
brush. Rw 62dB
7. Protecta® FR Acrylic can be over-painted with most
emulsion or alkyd (gloss) paints.

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904 Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 9/3/15
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 132
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Protecta Mineral Fibre BIO
surfaces that cannot tolerate direct contact;
appropriate surface preparation should be made Application Fire stopping of copper pipes in
(contact Polyseam for guidance in these cases). For Backing with
rigid walls
paints sensitive to sealing compounds, priming with Protecta Mineral Protecta FR Acrylic
a PVA primer is recommended. Fibre BIO minimum Minimum seal depth 25mm Construction Minimum wall thickness of 100
3. When installing any backing material, cut this slightly 25mm deep Maximum annular ring width 30mm mm and comprise concrete,
oversize and insert into the gap ensuring a tight Double sided seal aerated concrete or masonry,
friction fit. Ensure correct depth is achieved. with a density of ≥ 650 kg/m3
4. Fill the gap or joint with Protecta® FR Acrylic to the
required depth. Fire & Sound classification
Copper pipe
5. Apply the sealant generously to prevent air bubbles.
Copper pipe ≤ Ø12mm with 9mm thick pipe
Finish the bead with a moist spatula, pallet knife or
Continuous elastomeric insulation EI 120 C/C & E 120 C/C
brush.
6. Protecta® FR Acrylic can be over-painted with most insulation
Copper pipe ≤ Ø54mm with 9-13mm thick pipe
emulsion or alkyd (gloss) paints. insulation EI 60 C/C & E 120 C/C

Copper pipe ≤ Ø54mm with 14-25mm thick pipe


insulation EI 60 C/C & E 60 C/C

Sound reduction (seal only) Rw 62dB

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904 Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 9/3/15
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 133
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Stone wool
surfaces that cannot tolerate direct contact;
appropriate surface preparation should be made Backing with stone wool
Application Fire stopping of alupex pipes in
(contact Polyseam for guidance in these cases). For minimum 12.5mm deep
rigid walls
paints sensitive to sealing compounds, priming with
a PVA primer is recommended. Protecta FR Acrylic Construction Minimum wall thickness of 100
3. As Protecta® FR Acrylic is water based, in cases Minimum seal depth mm and comprise concrete,
where corrosion protection is a problem; some Alupex 12.5mm double sided aerated concrete or masonry,
metals may require a barrier between the sealant pipe with a density of ≥ 650 kg/m3
and the metal surface prior to this installation.
4. When installing any backing material, cut this slightly Fire & Sound classification
oversize and insert into the gap ensuring a tight
Alupex pipe ≤ Ø20mm without pipe insulation
friction fit. Ensure correct depth is achieved.
in maximum aperture 300x300mm
5. Fill the gap or joint with Protecta® FR Acrylic to the
required depth. EI 120 C/C & E 120 C/C
6. Apply the sealant generously to prevent air bubbles.
Finish the bead with a moist spatula, pallet knife or Sound reduction (seal only)
brush. Rw 62dB
7. Protecta® FR Acrylic can be over-painted with most
emulsion or alkyd (gloss) paints.

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904 Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 8/4/18
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 134
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Stone wool
surfaces that cannot tolerate direct contact;
appropriate surface preparation should be made Backing with stone wool
Application Fire stopping of alupex pipes in
(contact Polyseam for guidance in these cases). For minimum 15mm deep
rigid walls
paints sensitive to sealing compounds, priming with
a PVA primer is recommended. Protecta FR Acrylic Construction Minimum wall thickness of 120
3. As Protecta® FR Acrylic is water based, in cases Minimum seal depth mm and comprise concrete,
where corrosion protection is a problem; some Alupex 15mm double sided aerated concrete or masonry,
metals may require a barrier between the sealant pipe with a density of ≥ 650 kg/m3
and the metal surface prior to this installation.
4. When installing any backing material, cut this slightly Fire & Sound classification
oversize and insert into the gap ensuring a tight
Alupex pipe ≤ Ø75mm without pipe insulation
friction fit. Ensure correct depth is achieved.
in maximum aperture 300x300mm
5. Fill the gap or joint with Protecta® FR Acrylic to the
required depth. EI 30 C/C & E 120 C/C
6. Apply the sealant generously to prevent air bubbles.
Finish the bead with a moist spatula, pallet knife or Sound reduction (seal only)
brush. Rw 62dB
7. Protecta® FR Acrylic can be over-painted with most
emulsion or alkyd (gloss) paints.

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904 Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 14/8/19
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 135
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Stone wool
surfaces that cannot tolerate direct contact;
Backing with stone wool
appropriate surface preparation should be made Application Fire stopping of alupex pipes in
minimum 12.5mm deep
(contact Polyseam for guidance in these cases). For rigid walls
paints sensitive to sealing compounds, priming with Protecta FR Acrylic
a PVA primer is recommended. Minimum seal depth Construction Minimum wall thickness of 100
3. When installing any backing material, cut this slightly Alupex 12.5mm double sided seal mm and comprise concrete,
oversize and insert into the gap ensuring a tight pipe aerated concrete or masonry,
friction fit. Ensure correct depth is achieved. with a density of ≥ 650 kg/m3
4. Fill the gap or joint with Protecta® FR Acrylic to the
required depth.
Fire & Sound classification
5. Apply the sealant generously to prevent air bubbles.
Finish the bead with a moist spatula, pallet knife or Continuous pipe
Alupex pipe ≤ Ø75mm with 20-50mm thick pipe
brush. insulation of glass or
insulation in maximum aperture 300x300mm or
6. Protecta® FR Acrylic can be over-painted with most stone wool ≥ 75kg/m3 Ø504mm
emulsion or alkyd (gloss) paints. EI 120 C/C & E 120 C/C

Sound reduction (seal only)


Rw 62dB

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904
Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 14/8/19
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 136
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Stone wool
surfaces that cannot tolerate direct contact; Backing with stone wool
appropriate surface preparation should be made minimum 20mm deep Application Fire stopping of alupex pipes in
(contact Polyseam for guidance in these cases). For rigid walls
paints sensitive to sealing compounds, priming with
Protecta FR Acrylic
a PVA primer is recommended. Construction Minimum wall thickness of 150
Minimum seal depth
3. As Protecta® FR Acrylic is water based, in cases mm and comprise concrete,
Alupex 15mm single sided seal
where corrosion protection is a problem; some aerated concrete or masonry,
metals may require a barrier between the sealant pipe with a density of ≥ 650 kg/m3
and the metal surface prior to this installation.
4. When installing any backing material, cut this slightly
Fire & Sound classification
oversize and insert into the gap ensuring a tight
friction fit. Ensure correct depth is achieved.
Alupex pipe ≤ Ø75mm with ≥ 25mm thick pipe
5. Fill the gap or joint with Protecta® FR Acrylic to the
insulation and maximum annular ring width
required depth. Pipe insulation of
30mm
6. Apply the sealant generously to prevent air bubbles. Protecta Mineral Fibre EI 120 C/U & E 120 C/U
Finish the bead with a moist spatula, pallet knife or BIO ≥ 60cm on both
brush. sides Sound reduction (seal only)
7. Protecta® FR Acrylic can be over-painted with most Rw 62dB
emulsion or alkyd (gloss) paints.

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904
Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 23/4/15
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 137
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Stone wool
surfaces that cannot tolerate direct contact; Backing with stone wool
appropriate surface preparation should be made minimum 25mm deep Application Fire stopping of alupex pipes in
(contact Polyseam for guidance in these cases). For rigid walls
paints sensitive to sealing compounds, priming with
Protecta FR Acrylic
a PVA primer is recommended. Construction Minimum wall thickness of 150
Minimum seal depth
3. As Protecta® FR Acrylic is water based, in cases mm and comprise concrete,
Alupex 25mm single sided seal
where corrosion protection is a problem; some aerated concrete or masonry,
metals may require a barrier between the sealant pipe with a density of ≥ 650 kg/m3
and the metal surface prior to this installation.
4. When installing any backing material, cut this slightly
Fire & Sound classification
oversize and insert into the gap ensuring a tight
friction fit. Ensure correct depth is achieved.
Alupex pipe ≤ Ø75mm with ≥ 25mm thick pipe
5. Fill the gap or joint with Protecta® FR Acrylic to the
insulation in maximum aperture 300x300mm
required depth. Pipe insulation of
6. Apply the sealant generously to prevent air bubbles. Protecta Mineral Fibre EI 60 C/U & E 240 C/U
Finish the bead with a moist spatula, pallet knife or BIO ≥ 60cm on both
brush. sides Sound reduction (seal only)
7. Protecta® FR Acrylic can be over-painted with most Rw 62dB
emulsion or alkyd (gloss) paints.

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904
Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 13/8/19
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 138
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Stone wool
surfaces that cannot tolerate direct contact; Backing with stone wool
appropriate surface preparation should be made minimum 12.5mm deep Application Fire stopping of alupex pipes in
(contact Polyseam for guidance in these cases). For rigid walls
paints sensitive to sealing compounds, priming with
Protecta FR Acrylic
a PVA primer is recommended. Construction Minimum wall thickness of 100
Minimum seal depth
3. As Protecta® FR Acrylic is water based, in cases mm and comprise concrete,
Alupex 12.5mm double sided seal
where corrosion protection is a problem; some aerated concrete or masonry,
metals may require a barrier between the sealant pipe with a density of ≥ 650 kg/m3
and the metal surface prior to this installation.
4. When installing any backing material, cut this slightly Fire & Sound classification
oversize and insert into the gap ensuring a tight
Alupex pipe ≤ Ø75mm with ≥ 20mm thick pipe
friction fit. Ensure correct depth is achieved.
insulation in maximum aperture 300x300mm
5. Fill the gap or joint with Protecta® FR Acrylic to the
required depth. EI 120 C/C & E 120 C/C
Pipe insulation of stone
6. Apply the sealant generously to prevent air bubbles.
wool ≥ 80kg/m3
Finish the bead with a moist spatula, pallet knife or Sound reduction (seal only)
≥ 50cm on both sides
brush. Rw 62dB
7. Protecta® FR Acrylic can be over-painted with most
emulsion or alkyd (gloss) paints.

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904 Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 23/4/15
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 139
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Protecta Mineral Fibre BIO
surfaces that cannot tolerate direct contact;
appropriate surface preparation should be made Application Fire stopping of alupex pipes in
(contact Polyseam for guidance in these cases). For Backing with
rigid walls
paints sensitive to sealing compounds, priming with Protecta Mineral Protecta FR Acrylic
a PVA primer is recommended. Fibre BIO minimum Minimum seal depth 25mm Construction Minimum wall thickness of 100
3. When installing any backing material, cut this slightly 25mm deep Maximum annular ring width 30mm mm and comprise concrete,
oversize and insert into the gap ensuring a tight Double sided seal aerated concrete or masonry,
friction fit. Ensure correct depth is achieved. with a density of ≥ 650 kg/m3
4. Fill the gap or joint with Protecta® FR Acrylic to the
required depth.
Alupex pipe Fire & Sound classification
5. Apply the sealant generously to prevent air bubbles.
Finish the bead with a moist spatula, pallet knife or
Continuous elastomeric Alupex pipe ≤ Ø16mm with 9mm thick pipe
brush.
insulation insulation EI 120 C/C & E 120 C/C
6. Protecta® FR Acrylic can be over-painted with most
emulsion or alkyd (gloss) paints. Alupex pipe ≤ Ø75mm with 9 – 25mm thick pipe
insulation EI 60 C/C & E 60 C/C

Sound reduction (seal only) Rw 62dB

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904
Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 23/4/15
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 140
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Stonewool
surfaces that cannot tolerate direct contact; Backing with stone wool
appropriate surface preparation should be made minimum 12.5mm deep Application Fire stopping of PEX plastic
(contact Polyseam for guidance in these cases). For pipes in rigid walls
paints sensitive to sealing compounds, priming with
Protecta FR Acrylic
a PVA primer is recommended. Construction Minimum wall thickness of 100
Minimum seal depth 12.5mm
3. When installing any backing material, cut this slightly mm and comprise concrete,
Double sided seal
oversize and insert into the gap ensuring a tight aerated concrete or masonry,
friction fit. Ensure correct depth is achieved. with a density of ≥ 650 kg/m3
4. Fill the gap or joint with Protecta® FR Acrylic to the
required depth. Fire & Sound classification
5. Apply the sealant generously to prevent air bubbles.
Plastic pipe PEX pipe-in-pipe ≤ Ø25mm and maximum
Finish the bead with a moist spatula, pallet knife or
annular ring width 30mm
brush.
EI 120 C/C & E 120 C/C
6. Protecta® FR Acrylic can be over-painted with most
emulsion or alkyd (gloss) paints. Sound reduction (seal only)
Rw 62dB

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904 Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 9/4/18
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 141
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Application Fire stopping of plastic pipes in
surfaces that cannot tolerate direct contact; rigid walls
appropriate surface preparation should be made Construction Minimum wall thickness of 100
(contact Polyseam for guidance in these cases). For Protecta FR Acrylic mm and comprise concrete,
paints sensitive to sealing compounds, priming with Minimum seal depth 25mm aerated concrete or masonry,
a PVA primer is recommended. Maximum annular ring width 30mm with a density of ≥ 650 kg/m3
3. When installing any backing material, cut this slightly Double sided seal Fire & Sound classification
oversize and insert into the gap ensuring a tight PVC-U or PVC-C pipe ≤ Ø32mm with wall
friction fit. Ensure correct depth is achieved. thickness 1.0-1.6mm EI 120 C/C & E 120 C/C
4. Fill the gap or joint with Protecta® FR Acrylic to the
required depth. PVC-U or PVC-C pipe ≤ Ø32mm with wall
thickness 1.0-2.4mm EI 90 U/C & E 120 U/C
5. Apply the sealant generously to prevent air bubbles.
Finish the bead with a moist spatula, pallet knife or Plastic pipe
PE, ABS or SAN+PVC pipe Ø20mm with wall
brush.
thickness 2.0mm EI 120 U/C & E 120 U/C
6. Protecta® FR Acrylic can be over-painted with most
emulsion or alkyd (gloss) paints. PE, ABS or SAN+PVC pipe ≤ Ø32mm with wall
thickness 2.0-3.0mm EI 90 C/C & E 90 C/C

PP pipe Ø20mm with wall thickness 2.2mm


EI 120 U/C & E 120 U/C

PP pipe ≤ Ø32mm with wall thickness


1.8-4.4mm EI 60 C/C & E 60 C/C

Sound reduction (seal only) Rw 62dB

Polyseam Ltd, 15 St Andrews Road,


Huddersfield, West Yorkshire, HD1 6SB
ETA 18/0904 Tel: +44 (0) 148 4421036
For all technical details on the products specified
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can
Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu Sheet size: Drawn date & no:
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
Signed and approved: A4 14/8/19
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 142
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Stonewool
surfaces that cannot tolerate direct contact; Backing with stone wool
appropriate surface preparation should be made minimum 25mm deep Application Fire stopping of plastic pipes in
(contact Polyseam for guidance in these cases). For rigid walls
paints sensitive to sealing compounds, priming with Protecta FR Acrylic
a PVA primer is recommended. Minimum seal depth 25mm Construction Minimum wall thickness of 150
3. When installing any backing material, cut this slightly Maximum annular ring width 30mm mm and comprise concrete,
oversize and insert into the gap ensuring a tight aerated concrete or masonry,
Double sided seal
friction fit. Ensure correct depth is achieved. with a density of ≥ 650 kg/m3
4. Fill the gap or joint with Protecta® FR Acrylic to the Fire & Sound classification
required depth.
PVC-U or PVC-C pipe ≤ Ø32mm with wall
5. Apply the sealant generously to prevent air bubbles. Plastic pipe
thickness 1.0-1.6mm
Finish the bead with a moist spatula, pallet knife or
EI 240 U/C & E 240 U/C
brush.
6. Protecta® FR Acrylic can be over-painted with most PE, ABS or SAN+PVC pipe ≤ Ø32mm with wall
emulsion or alkyd (gloss) paints. thickness 2.0mm
EI 240 C/U & E 240 C/U

PP pipe Ø32mm with wall thickness 2.0-4.4mm


EI 180 C/U & E 180 C/U

Sound reduction (seal only) Rw 62dB

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904 Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 13/8/19
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 143
Client:
Installation Instructions

1. Before installing Protecta® FR Graphite ensure that


the surface of all service penetrations and
Job Title:
surrounding construction is free from all loose
contaminants, dust and grease.
Products Protecta FR Graphite
2. When installing any backing material, cut this slightly Stone wool
oversize and insert into the gap ensuring a tight Application Fire stopping of plastic pipes in
friction fit. Ensure correct depth is achieved. rigid walls
3. Fill the gap or joint with Protecta® FR Graphite to the Construction Minimum wall thickness of 100
Backing with stone wool mm and comprise concrete,
required depth. minimum 25mm deep aerated concrete or masonry,
4. Apply the sealant generously avoiding air bubbles. with a density of ≥ 650 kg/m3
Finish the bead with a moist spatula or pallet knife. Fire & Sound classification
Avoid excessive tooling/smoothing as this may make
the seal surface wet and soft. PVC-U or PVC-C pipe ≤ 110 mm diameter with
wall thickness 1.9-6.6mm in seal widths between
5. Protecta® FR Graphite can be over-painted with
Plastic pipe 10 and 30mm EI 120 U/C
most emulsion or alkyd (gloss) paints.
Protecta FR Graphite
Minimum seal depth 25mm PE, ABS or SAN+PVC pipe ≤ 40 mm diameter
with wall thickness 2.4-3.7mm in seal widths
Double sided seal
between 10 and 30mm EI 120 U/C

PE, ABS or SAN+PVC pipe ≤ 110 mm diameter


with wall thickness 2.4-4.2mm in seal widths
between 10 and 30mm EI 60 U/C

PE, ABS or SAN+PVC pipe ≤ 110 mm diameter


with wall thickness 4.3-10.0mm in seal widths
between 10 and 30mm EI 90 U/C & E 120 U/C

Sound reduction (seal only) Rw 53dB

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0626 Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 11/11/18
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
Scale: Drawn by:
NTS K.B

P a g e | 144
Client:
Installation Instructions

1. Before installing Protecta® FR Graphite ensure that


the surface of all service penetrations and
Job Title:
surrounding construction is free from all loose
contaminants, dust and grease.
Products Protecta FR Graphite
2. When installing any backing material, cut this slightly
oversize and insert into the gap ensuring a tight Application Fire stopping of plastic pipes in
friction fit. Ensure correct depth is achieved. rigid walls
3. Fill the gap or joint with Protecta® FR Graphite to the
Construction Minimum wall thickness of 100
required depth.
mm and comprise concrete,
4. Apply the sealant generously avoiding air bubbles. aerated concrete or masonry,
Finish the bead with a moist spatula or pallet knife. with a density of ≥ 650 kg/m3
Avoid excessive tooling/smoothing as this may make
the seal surface wet and soft. Fire & Sound classification
5. Protecta® FR Graphite can be over-painted with
Plastic pipe PVC-U or PVC-C pipe ≤ 160 mm diameter with
most emulsion or alkyd (gloss) paints.
Protecta FR Graphite wall thickness 3.2-9.5mm in seal widths between
Minimum seal depth 25mm 10 and 30mm EI 30 U/C
Double sided seal
PVC-U or PVC-C pipe ≤ 160 mm diameter with
wall thickness 9.5mm in seal widths between 10
and 30mm EI 90 U/C

PP pipe ≤ 110 mm diameter with wall thickness


1.8-6.3mm in seal widths between 10 and 30mm
EI 60 U/C

Sound reduction (seal only)


Rw 53dB

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0626 Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 11/11/18
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
Scale: Drawn by:
NTS K.B

P a g e | 145
Client:
Installation Instructions

1. Before installing Protecta® FR Graphite ensure that


the surface of all service penetrations and
Job Title:
surrounding construction is free from all loose
contaminants, dust and grease.
Products Protecta FR Graphite
2. When installing any backing material, cut this slightly
oversize and insert into the gap ensuring a tight Application Fire stopping of plastic pipes in
friction fit. Ensure correct depth is achieved. rigid walls
3. Fill the gap or joint with Protecta® FR Graphite to the Backing with Protecta Construction Minimum wall thickness of 150
required depth. Mineral Fibre BIO mm and comprise concrete,
4. Apply the sealant generously avoiding air bubbles. minimum 25mm deep aerated concrete or masonry,
Finish the bead with a moist spatula or pallet knife. with a density of ≥ 650 kg/m3
Avoid excessive tooling/smoothing as this may make
the seal surface wet and soft. Fire & Sound classification
5. Protecta® FR Graphite can be over-painted with
Plastic pipe PVC-U or PVC-C pipe ≤ 160 mm diameter with
most emulsion or alkyd (gloss) paints.
Protecta FR Graphite wall thickness 4.0-9.5mm in seal widths between
Minimum seal depth 35mm 10 and 30mm
EI 90 U/C
Double sided seal
PVC-U or PVC-C pipe ≤ 160 mm diameter with
wall thickness 9.5mm in seal widths between 10
and 30mm
EI 180 U/C & E 240 U/C

Sound reduction (seal only)


Rw 53dB

Polyseam Ltd, 15 St Andrews Road,


Huddersfield, West Yorkshire, HD1 6SB
Tel: +44 (0) 148 4421036
ETA 18/0626 Email: post.uk@polyseam.com
For all technical details on the products specified
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Sheet size: Drawn date & no:
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over A4 11/11/18
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 146
Client:
Installation Instructions Apertures with
minimum 8mm annular
1. Before fitting the collars ensure that the gaps
between the pipe and the separating element are
width around services Job Title:
sealed with minimum 25mm deep Protecta FR Any gaps must be sealed
Acrylic to cover the opening. Masonry screws or with Protecta FR Acrylic
on both sides Products Protecta FR Collar
expansion bolts
2. Place a suitable collar around the pipe and ensure Protecta FR Acrylic
that the collar shell and fixing lugs are positioned
Plastic pipe Application Fire stopping of plastic pipes in
tightly to the surface of the wall, so that the fixings
can be inserted fully. rigid walls

3. Where the surface is uneven, apply a sealing bead of Construction Minimum wall thickness of 100
Protecta® FR Acrylic between the wall and the collar mm and comprise concrete,
shell. aerated concrete or masonry,
with a density of ≥ 650 kg/m3
4. Attach the collar with ≥ Ø4 x 40mm long masonry
Protecta FR Collar to
screws or expansion bolts.
both sides of the wall
Fire & Sound classification

Fire classifications in table on the left. For full


specifications, please refer to the Installation
Instructions.
Services Minimum Collar Classification
Height Sound reduction (seal only)
≤ Ø50mm PVC-U & PVC-C 30mm EI 60 C/C, EI 60 U/C, EI 60 C/U, EI 60 U/U (E 90) Rw 58dB
≤ Ø110mm PVC-U & PVC-C 30mm EI 60 C/C, EI 60 U/C
≤ Ø140mm PVC-U & PVC-C 50mm EI 60 C/C, EI 60 U/C, EI 60 C/U, EI 60 U/U (E 90)
≤ Ø160mm PVC-U & PVC-C 60mm EI 90 C/C, EI 90 U/C, EI 60 C/U, EI 60 U/U
Ø315x9.2mm PVC-U & PVC-C 75mm EI 60 C/C
≤ Ø50mm PE, ABS & SAN+PVC 30mm EI 60 C/C, EI 60 U/C (E 90)
≤ Ø50mm PE, ABS & SAN+PVC 50mm EI 90 C/C, EI 90 U/C, EI 90 C/U, EI 90 U/U (E 120)
≤ Ø110mm PE, ABS & SAN+PVC 30mm EI 60 C/C, EI 60 U/C
≤ Ø110mm PE, ABS & SAN+PVC 50mm EI 60 C/C, EI 60 U/C, EI 60 C/U, EI 60 U/U (E 90)
≤ Ø140mm PE, ABS & SAN+PVC 60mm EI 60 C/C, EI 60 U/C, EI 60 C/U, EI 60 U/U (E 90)
Ø160mm PE, ABS & SAN+PVC 60mm EI 90 C/C, EI 90 U/C, EI 90 C/U, EI 90 U/U
Ø200x18.2mm PE, ABS & SAN+PVC 75mm EI 60 C/C
Ø250x22.7mm PE, ABS & SAN+PVC 75mm EI 60 C/C
≤ Ø50mm PP 30mm EI 60 C/C, EI 60 U/C, EI 60 C/U, EI 60 U/U (E 90)
≤ Ø110mm PP 30mm EI 60 C/C, EI 60 U/C (E 90)
≤ Ø110mm PP 50mm EI 60 C/C, EI 60 U/C, EI 60 C/U, EI 60 U/U (E 90) Polyseam Ltd, 15 St Andrews Road,
≤ Ø160mm PP 60mm EI 60 C/C, EI 60 U/C, EI 60 C/U, EI 60 U/U Huddersfield, West Yorkshire, HD1 6SB
ETA 18/0854
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 20/8/19
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 147
Client:
Installation Instructions Apertures with
minimum 8mm annular
1. Before fitting the collars ensure that the gaps
between the pipe and the separating element are
width around services Job Title:
sealed with minimum 25mm deep Protecta FR Any gaps must be sealed
Acrylic to cover the opening. Masonry screws or with Protecta FR Acrylic
on both sides Products Protecta FR Collar
expansion bolts
2. Place a suitable collar around the pipe and ensure Protecta FR Acrylic
that the collar shell and fixing lugs are positioned Plastic pipe
tightly to the surface of the wall, so that the fixings Application Fire stopping of plastic pipes in
can be inserted fully. rigid walls

3. Where the surface is uneven, apply a sealing bead of Construction Minimum wall thickness of 120
Protecta® FR Acrylic between the wall and the collar mm and comprise concrete,
shell. aerated concrete or masonry,
with a density of ≥ 650 kg/m3
4. Attach the collar with ≥ Ø4 x 40mm long masonry
Protecta FR Collar to
screws or expansion bolts.
both sides of the wall
Fire & Sound classification

Fire classifications in table on the left. For full


specifications, please refer to the Installation
Instructions.
Services Minimum Collar Classification
Height
≤ Ø110mm PVC-U & PVC-C 50mm EI 120 C/C Sound reduction (seal only)
≤ Ø160mm PVC-U & PVC-C 60mm EI 120 C/C Rw 58dB
≤ Ø50mm PE, ABS & SAN+PVC 50mm EI 120 C/C
≤ Ø110mm PE, ABS & SAN+PVC 50mm EI 90 C/C (E 120)
Ø110x3.4mm PE, ABS & SAN+PVC 50mm EI 120 C/C
≤ Ø160mm PE, ABS & SAN+PVC 60mm EI 90 C/C
Ø160x9.5mm PE, ABS & SAN+PVC 60mm EI 120 C/C
≤ Ø50mm PP 50mm EI 120 C/C
≤ Ø110mm PP 50mm EI 90 C/C (E 120)
≤ Ø140mm PP 60mm EI 90 C/C (E 120)
Ø160mm PP 60mm EI 120 C/C

Polyseam Ltd, 15 St Andrews Road,


Huddersfield, West Yorkshire, HD1 6SB
ETA 18/0854
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 20/8/19
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 148
Client:
Installation Instructions Apertures with
1. Before fitting the collars ensure that the gaps minimum 8mm annular
between the pipe and the separating element are
width around services Job Title:
sealed with minimum 20mm deep Protecta FR Any gaps must be sealed
Acrylic on 20mm deep stone wool to cover the Masonry screws or with Protecta FR Acrylic Products Protecta FR Collar
opening. expansion bolts on a stonewool backing Protecta FR Acrylic
2. Place a suitable collar around the pipe and ensure on both sides
that the collar shell and fixing lugs are positioned Plastic pipe Application Fire stopping of plastic pipes in
tightly to the surface of the wall, so that the fixings rigid walls
can be inserted fully.
Construction Minimum wall thickness of 150
3. Where the surface is uneven, apply a sealing bead of mm and comprise concrete,
Protecta® FR Acrylic between the wall and the collar aerated concrete or masonry,
shell. with a density of ≥ 650 kg/m3

4. Attach the collar with ≥ Ø4 x 40mm long masonry Protecta FR Collar to


screws or expansion bolts. both sides of the wall Fire & Sound classification

Fire classifications in table on the left. For full


specifications, please refer to the Installation
Instructions.

Services Minimum Collar Classification Sound reduction (seal only)


Height Rw 58dB
≤ Ø50mm PVC-U & PVC-C 50mm EI 180 C/C, EI 180 U/C, EI 180 C/U, EI 180 U/U (E 240)
≤ Ø110mm PVC-U & PVC-C 50mm EI 180 C/C, EI 180 U/C, EI 180 C/U, EI 180 U/U
≤ Ø160mm PVC-U & PVC-C 60mm EI 240 C/C, EI 240 U/C, EI 240 C/U, EI 240 U/U
Ø315x9.2mm PVC-U & PVC-C 75mm EI 120 C/C
≤ Ø50mm PE, ABS & SAN+PVC 50mm EI 240 C/C, EI 240 U/C, EI 240 C/U, EI 240 U/U
≤ Ø110mm PE, ABS & SAN+PVC 50mm EI 180 C/C, EI 180 U/C, EI 180 C/U, EI 180 U/U (E 240)
≤ Ø160mm PE, ABS & SAN+PVC 60mm EI 180 C/C, EI 180 U/C, EI 180 C/U, EI 180 U/U
Ø200x18.2mm PE, ABS & SAN+PVC 75mm EI 60 C/C
Ø250x22.7mm PE, ABS & SAN+PVC 75mm EI 90 C/C (E 120)
≤ Ø50mm PP 30mm EI 240 C/C, EI 240 U/C, EI 240 C/U, EI 240 U/U
≤ Ø110mm PP 50mm EI 240 C/C, EI 240 U/C, EI 90 C/U, EI 90 U/U (E 240)
≤ Ø140mm PP 60mm EI 180 C/C, EI 180 U/C, EI 60 C/U, EI 60 U/U (E 240)
Ø160mm PP 60mm EI 180 C/C, EI 180 U/C, EI 180 C/U, EI 180 U/U (E 240)

Polyseam Ltd, 15 St Andrews Road,


Huddersfield, West Yorkshire, HD1 6SB
ETA 18/0854
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 20/8/19
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 149
Client:
Installation Instructions
Apertures with
1. Before fitting the collars ensure that the gaps minimum 8mm annular
between the pipe and the separating element are width around services Job Title:
sealed with minimum 25mm deep Protecta FR Any gaps must be sealed
Acrylic to cover the opening. Masonry screws or with Protecta FR Acrylic Products Protecta FR Collar
expansion bolts on both sides Protecta FR Acrylic
2. Place a suitable collar around the pipe and ensure
that the collar shell and fixing lugs are positioned
tightly to the surface of the wall, so that the fixings Composite Application Fire stopping of composite
can be inserted fully. plastic pipe plastic pipes in rigid walls

3. Where the surface is uneven, apply a sealing bead of Construction Minimum wall thickness of 100
Protecta® FR Acrylic between the wall and the collar mm and comprise concrete,
shell. aerated concrete or masonry,
with a density of ≥ 650 kg/m3
4. Attach the collar with ≥ Ø4 x 40mm long masonry
screws or expansion bolts. Protecta FR Collar to
both sides of the wall Fire & Sound classification

Fire classifications in table on the left. For full


specifications, please refer to the Installation
Services Minimum Collar Classification Instructions.
Height
≤ Ø32mm Aquatherm Green SDR9 30mm EI 120 C/C Sound reduction (seal only)
≤ Ø50mm Aquatherm Green SDR9 50mm EI 120 C/C Rw 58dB
≤ Ø110mm Aquatherm Green SDR9 50mm EI 60 C/C (E 120)
≤ Ø50mm BluePower 50mm EI 90 C/C, EI 90 U/C, EI 90 C/U, EI 90 U/U (E 120)
≤ Ø110mm BluePower 50mm EI 60 C/C, EI 60 U/C, EI 60 C/U (E 120)
Ø125mm BluePower 60mm EI 60 C/C, EI 60 U/C, EI 60 C/U
Ø160mm BluePower 60mm EI 90 C/C, EI 90 U/C, EI 90 C/U
≤ Ø50mm Geberit Silent-PP 50mm EI 120 C/C, EI 120 U/C, EI 120 C/U, EI 120 U/U
≤ Ø110mm Geberit Silent-PP 50mm EI 60 C/C, EI 60 U/C, EI 60 C/U, EI 60 U/U (E 120)
≤ Ø50mm Polo-Kal NG pipes 50mm EI 120 C/C, EI 120 U/C, EI 120 C/U, EI 120 U/U
≤ Ø110mm Polo-Kal NG pipes 50mm EI 90 C/C, EI 90 U/C, EI 90 C/U, EI 90 U/U (E 120)
Ø125mm Polo-Kal NG pipes 60mm EI 120 C/C, EI 120 U/C (E 120 C/U, E 120 U/U)
Ø160mm Polo-Kal NG pipes 60mm EI 120 C/C, EI 120 U/C, EI 120 C/U, EI 120 U/U
≤ Ø50mm Rehau Raupiano Plus 50mm EI 90 C/C, EI 90 U/C, EI 90 C/U, EI 90 U/U (E 120)
≤ Ø110mm Rehau Raupiano Plus 50mm EI 60 C/C, EI 60 U/C, EI 60 C/U, EI 60 U/U (E 120)
≤ Ø160mm Rehau Raupiano Plus 60mm EI 120 C/C, EI 120 U/C, EI 120 C/U, EI 120 U/U
≤ Ø50mm Wavin SiTech 50mm EI 120 C/C, EI 120 U/C, EI 120 C/U, EI 120 U/U Polyseam Ltd, 15 St Andrews Road,
≤ Ø110mm Wavin SiTech 50mm EI 60 C/C, EI 60 U/C, EI 60 C/U, EI 60 U/U (E 120) Huddersfield, West Yorkshire, HD1 6SB
ETA 18/0854
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 20/8/19
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 150
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against
surfaces that cannot tolerate direct contact; Application Fire stopping of conduits in
appropriate surface preparation should be made rigid walls
(contact Polyseam for guidance in these cases). For
paints sensitive to sealing compounds, priming with Construction Minimum wall thickness of 100
Protecta FR Acrylic
a PVA primer is recommended. mm and comprise concrete,
Minimum seal depth 25mm
3. When installing any backing material, cut this slightly aerated concrete or masonry,
Maximum annular ring width 30mm
oversize and insert into the gap ensuring a tight with a density of ≥ 650 kg/m3
Double sided seal
friction fit. Ensure correct depth is achieved. Conduit (plastic
4. Fill the gap or joint with Protecta® FR Acrylic to the pipe with cables) Fire & Sound classification
required depth.
PVC-U or PVC-C conduit/pipe ≤ Ø40mm with
5. Apply the sealant generously to prevent air bubbles. Cables ≤ Ø21mm wall thickness 1.0 – 1.9mm
Finish the bead with a moist spatula, pallet knife or single or in a EI 120 U/C & E 120 U/C
brush. bundle
6. Protecta® FR Acrylic can be over-painted with most PE, ABS or SAN+PVC conduit/pipe ≤ Ø40mm
emulsion or alkyd (gloss) paints. with wall thickness 2.0 – 3.0mm
EI 90 U/C & E 90 U/C

PP conduit/pipe ≤ Ø40mm with wall thickness


1.8 – 2.2mm EI 90 U/C & E 90 U/C

Sound reduction (seal only) Rw 62dB

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904 Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 14/8/19
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 151
Client:
Installation Instructions

1. Before installing Protecta® FR Graphite ensure that


the surface of all service penetrations and
Job Title:
surrounding construction is free from all loose
contaminants, dust and grease.
Products Protecta FR Graphite
2. When installing any backing material, cut this slightly
oversize and insert into the gap ensuring a tight Application Fire stopping of conduits in
friction fit. Ensure correct depth is achieved. rigid walls
Protecta FR Graphite
3. Fill the gap or joint with Protecta® FR Graphite to the Minimum seal depth 25mm
Construction Minimum wall thickness of 100
required depth. Seal widths between 10 and 30mm
mm and comprise concrete,
4. Apply the sealant generously avoiding air bubbles. Double sided seal aerated concrete or masonry,
Conduit (plastic
Finish the bead with a moist spatula or pallet knife. pipe with cables) with a density of ≥ 650 kg/m3
Avoid excessive tooling/smoothing as this may make
the seal surface wet and soft.
Cables ≤ Ø20mm
Fire & Sound classification
5. Protecta® FR Graphite can be over-painted with single or in a
most emulsion or alkyd (gloss) paints. bundle PE, ABS or SAN+PVC conduit/pipe ≤ Ø110mm
with wall thickness 2.4 - 10.0mm EI 60 U/C

PP conduit/pipe ≤ Ø110mm with wall thickness


2.7 - 6.6mm EI 90 U/C

PVC-U or PVC-C conduit/pipe ≤ Ø110mm with


wall thickness 1.9 - 6.6mm EI 90 U/C

Sound reduction (seal only) Rw 53dB

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0626 Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 11/11/18
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 152
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against
surfaces that cannot tolerate direct contact; Application Fire stopping of cables in
appropriate surface preparation should be made flexible walls
(contact Polyseam for guidance in these cases). For
paints sensitive to sealing compounds, priming with Construction Minimum wall thickness of 75
a PVA primer is recommended. mm and comprise steel studs
3. When installing the sealant in gypsum boards, the or timber studs* lined on both
exposed edges of the board can be wetted with Protecta FR Acrylic faces with minimum 1 layer of
water, or Protecta® FR Acrylic diluted with water to Minimum seal 12.5 mm thick boards
prime the surfaces helping adhesion and preventing depth 12.5mm
excessive joint shrinkage. Fire & Sound classification
4. When installing any backing material, cut this slightly
oversize and insert into the gap ensuring a tight Cable ≤ Ø21mm in double sided seal in
friction fit. Ensure correct depth is achieved. Single cable maximum aperture 150x150mm
5. Fill the gap or joint with Protecta® FR Acrylic to the EI 45 & E 60
required depth.
6. Apply the sealant generously to prevent air bubbles. Sound reduction (seal only)
Finish the bead with a moist spatula, pallet knife or Rw 62 dB
brush.
7. Protecta® FR Acrylic can be over-painted with most
emulsion or alkyd (gloss) paints.

Polyseam Ltd, 15 St Andrews Road,


Huddersfield, West Yorkshire, HD1 6SB
ETA 18/0904
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 8/4/18
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 153
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against
surfaces that cannot tolerate direct contact; Application Fire stopping of cables in
appropriate surface preparation should be made flexible walls
(contact Polyseam for guidance in these cases). For
paints sensitive to sealing compounds, priming with Construction Minimum wall thickness of 75
a PVA primer is recommended. mm and comprise steel studs
3. When installing the sealant in gypsum boards, the Protecta FR Acrylic or timber studs* lined on both
exposed edges of the board can be wetted with Minimum seal faces with minimum 1 layer of
water, or Protecta® FR Acrylic diluted with water to depth 12.5mm 12.5 mm thick boards
prime the surfaces helping adhesion and preventing
excessive joint shrinkage. Fire & Sound classification
4. When installing any backing material, cut this slightly
oversize and insert into the gap ensuring a tight Bundled cables Cables ≤ Ø21mm in a bundle ≤ Ø 100mm in
friction fit. Ensure correct depth is achieved. double sided seal in maximum aperture
5. Fill the gap or joint with Protecta® FR Acrylic to the 150x150mm
required depth. EI 30 & E 45
6. Apply the sealant generously to prevent air bubbles.
Finish the bead with a moist spatula, pallet knife or Sound reduction (seal only)
brush. Rw 62 dB
7. Protecta® FR Acrylic can be over-painted with most
emulsion or alkyd (gloss) paints.

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904 Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 8/4/18
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 154
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Stone wool
surfaces that cannot tolerate direct contact;
appropriate surface preparation should be made Application Fire stopping of cables in
(contact Polyseam for guidance in these cases). For flexible walls
paints sensitive to sealing compounds, priming with Backing with stone wool
a PVA primer is recommended. minimum 12.5mm deep Construction Minimum wall thickness of 100
3. When installing the sealant in gypsum boards, the mm and comprise steel studs
exposed edges of the board can be wetted with or timber studs* lined on both
Protecta FR Acrylic
water, or Protecta® FR Acrylic diluted with water to faces with minimum 2 layers of
Minimum seal
prime the surfaces helping adhesion and preventing 12.5 mm thick boards
depth 12.5mm
excessive joint shrinkage.
Fire & Sound classification
4. When installing any backing material, cut this slightly
oversize and insert into the gap ensuring a tight Single or
bundled cables Cables ≤ Ø21mm single or in a bundle ≤ Ø50mm
friction fit. Ensure correct depth is achieved.
in double sided seal in maximum aperture
5. Fill the gap or joint with Protecta® FR Acrylic to the 300x300mm
required depth. EI 90 & E 120
6. Apply the sealant generously to prevent air bubbles.
Finish the bead with a moist spatula, pallet knife or Sound reduction (seal only)
brush. Rw 62 dB
7. Protecta® FR Acrylic can be over-painted with most
emulsion or alkyd (gloss) paints.

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904
Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 13/8/19
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 155
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Stone wool
surfaces that cannot tolerate direct contact;
appropriate surface preparation should be made Application Fire stopping of cables in
(contact Polyseam for guidance in these cases). For flexible walls
paints sensitive to sealing compounds, priming with Backing with stone wool
a PVA primer is recommended. minimum 20mm deep Construction Minimum wall thickness of 100
3. When installing the sealant in gypsum boards, the mm and comprise steel studs
exposed edges of the board can be wetted with or timber studs* lined on both
Protecta FR Acrylic
water, or Protecta® FR Acrylic diluted with water to faces with minimum 2 layers of
Minimum seal
prime the surfaces helping adhesion and preventing 12.5 mm thick boards
depth 25mm
excessive joint shrinkage.
Fire & Sound classification
4. When installing any backing material, cut this slightly
oversize and insert into the gap ensuring a tight Single or
bundled cables Cables ≤ Ø21mm single or in a bundle
friction fit. Ensure correct depth is achieved.
≤ Ø100mm in double sided seal in maximum
5. Fill the gap or joint with Protecta® FR Acrylic to the aperture 300x300mm
required depth. EI 120 & E 120
6. Apply the sealant generously to prevent air bubbles.
Finish the bead with a moist spatula, pallet knife or Sound reduction (seal only)
brush. Rw 62 dB
7. Protecta® FR Acrylic can be over-painted with most
emulsion or alkyd (gloss) paints.

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904
Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 20/4/15
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 156
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Protecta Mineral Fibre BIO
surfaces that cannot tolerate direct contact;
appropriate surface preparation should be made Application Fire stopping of cables in
(contact Polyseam for guidance in these cases). For Backing with Protecta flexible walls
paints sensitive to sealing compounds, priming with Mineral Fibre BIO
a PVA primer is recommended. minimum 25mm deep Construction Minimum wall thickness of 100
3. When installing the sealant in gypsum boards, the mm and comprise steel studs
exposed edges of the board can be wetted with or timber studs* lined on both
Protecta FR Acrylic
water, or Protecta® FR Acrylic diluted with water to faces with minimum 2 layers of
Minimum seal
prime the surfaces helping adhesion and preventing 12.5 mm thick boards.
depth 25mm
excessive joint shrinkage.
Fire & Sound classification
4. When installing any backing material, cut this slightly
oversize and insert into the gap ensuring a tight Single or
bundled cables Cables ≤ Ø80mm single or in a bundle
friction fit. Ensure correct depth is achieved.
≤ Ø100mm in double sided seal in maximum
5. Fill the gap or joint with Protecta® FR Acrylic to the aperture 300x300mm
required depth. EI 60 & E 120
6. Apply the sealant generously to prevent air bubbles.
Finish the bead with a moist spatula, pallet knife or Sound reduction (seal only)
brush. Rw 62 dB
7. Protecta® FR Acrylic can be over-painted with most
emulsion or alkyd (gloss) paints.

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904
Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 20/4/15
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 157
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against
surfaces that cannot tolerate direct contact; Application Fire stopping of steel pipes in
appropriate surface preparation should be made flexible walls
(contact Polyseam for guidance in these cases). For
paints sensitive to sealing compounds, priming with Construction Minimum wall thickness of 75
Protecta FR Acrylic
a PVA primer is recommended. mm and comprise steel studs
Minimum seal depth
3. As Protecta® FR Acrylic is water based, in cases Steel or timber studs* lined on both
12.5mm double sided
where corrosion protection is a problem; some pipe faces with minimum 1 layer of
metals may require a barrier between the sealant 12.5 mm thick boards
and the metal surface prior to this installation.
4. When installing the sealant in gypsum boards, the
Fire & Sound classification
exposed edges of the board can be wetted with
water, or Protecta® FR Acrylic diluted with water to
Steel pipe ≤ Ø22mm without pipe insulation in
prime the surfaces helping adhesion and preventing
maximum aperture 150x150mm
excessive joint shrinkage.
5. When installing any backing material, cut this slightly EI 30 C/U & E 60 C/U
oversize and insert into the gap ensuring a tight
friction fit. Ensure correct depth is achieved. Sound reduction (seal only)
6. Fill the gap or joint with Protecta® FR Acrylic to the Rw 62dB
required depth.
7. Apply the sealant generously to prevent air bubbles.
Finish the bead with a moist spatula, pallet knife or
brush.
8. Protecta® FR Acrylic can be over-painted with most
emulsion or alkyd (gloss) paints.

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904 Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 8/4/18
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 158
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Stone wool
surfaces that cannot tolerate direct contact; Backing with stone wool
appropriate surface preparation should be made minimum 12.5mm deep Application Fire stopping of steel pipes in
(contact Polyseam for guidance in these cases). For flexible walls
paints sensitive to sealing compounds, priming with
Protecta FR Acrylic
a PVA primer is recommended. Construction Minimum wall thickness of 100
Minimum seal depth
3. As Protecta® FR Acrylic is water based, in cases Steel mm and comprise steel studs
12.5mm double sided
where corrosion protection is a problem; some pipe or timber studs* lined on both
metals may require a barrier between the sealant faces with minimum 2 layers of
and the metal surface prior to this installation. 12.5 mm thick boards
4. When installing the sealant in gypsum boards, the
Fire & Sound classification
exposed edges of the board can be wetted with
water, or Protecta® FR Acrylic diluted with water to
Steel pipe ≤ Ø30mm without pipe insulation in
prime the surfaces helping adhesion and preventing
maximum aperture 300x300mm
excessive joint shrinkage.
5. When installing any backing material, cut this slightly EI 90 C/C & E 90 C/C
oversize and insert into the gap ensuring a tight
friction fit. Ensure correct depth is achieved. Sound reduction (seal only)
6. Fill the gap or joint with Protecta® FR Acrylic to the Rw 62dB
required depth.
7. Apply the sealant generously to prevent air bubbles.
Finish the bead with a moist spatula, pallet knife or
brush.
8. Protecta® FR Acrylic can be over-painted with most
emulsion or alkyd (gloss) paints.

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904 Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 8/4/18
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 159
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Stone wool
surfaces that cannot tolerate direct contact; Backing with stone wool
appropriate surface preparation should be made minimum 25mm deep Application Fire stopping of steel pipes in
(contact Polyseam for guidance in these cases). For flexible walls
paints sensitive to sealing compounds, priming with
Protecta FR Acrylic
a PVA primer is recommended. Construction Minimum wall thickness of 100
Minimum seal depth
3. As Protecta® FR Acrylic is water based, in cases Steel mm and comprise steel studs
25mm double sided seal
where corrosion protection is a problem; some pipe or timber studs* lined on both
metals may require a barrier between the sealant faces with minimum 2 layers of
and the metal surface prior to this installation. 12.5 mm thick boards
4. When installing the sealant in gypsum boards, the
Fire & Sound classification
exposed edges of the board can be wetted with
water, or Protecta® FR Acrylic diluted with water to
Steel pipe Ø22 - Ø30mm without pipe insulation
prime the surfaces helping adhesion and preventing
in maximum aperture 300x300mm
excessive joint shrinkage.
5. When installing any backing material, cut this slightly EI 120 C/C & E 120 C/C
oversize and insert into the gap ensuring a tight
friction fit. Ensure correct depth is achieved. Sound reduction (seal only)
6. Fill the gap or joint with Protecta® FR Acrylic to the Rw 62dB
required depth.
7. Apply the sealant generously to prevent air bubbles.
Finish the bead with a moist spatula, pallet knife or
brush.
8. Protecta® FR Acrylic can be over-painted with most
emulsion or alkyd (gloss) paints.

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904 Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 8/4/18
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 160
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Stone wool
surfaces that cannot tolerate direct contact; Backing with stone wool
appropriate surface preparation should be made minimum 15mm deep Application Fire stopping of steel pipes in
(contact Polyseam for guidance in these cases). For flexible walls
paints sensitive to sealing compounds, priming with
Protecta FR Acrylic
a PVA primer is recommended. Construction Minimum wall thickness of 120
Minimum seal depth
3. As Protecta® FR Acrylic is water based, in cases Steel mm and comprise steel studs
15mm double sided seal
where corrosion protection is a problem; some pipe or timber studs* lined on both
metals may require a barrier between the sealant faces with minimum 2 layers of
and the metal surface prior to this installation. 12.5 mm thick boards
4. When installing the sealant in gypsum boards, the
Fire & Sound classification
exposed edges of the board can be wetted with
water, or Protecta® FR Acrylic diluted with water to
Steel pipe ≤ Ø324mm without pipe insulation in
prime the surfaces helping adhesion and preventing
maximum aperture 300x300mm or Ø344mm
excessive joint shrinkage.
5. When installing any backing material, cut this slightly E 120 C/U
oversize and insert into the gap ensuring a tight
friction fit. Ensure correct depth is achieved. Sound reduction (seal only)
6. Fill the gap or joint with Protecta® FR Acrylic to the Rw 62dB
required depth.
7. Apply the sealant generously to prevent air bubbles.
Finish the bead with a moist spatula, pallet knife or
brush.
8. Protecta® FR Acrylic can be over-painted with most
emulsion or alkyd (gloss) paints.

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904 Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 13/8/19
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 161
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against
surfaces that cannot tolerate direct contact; Application Fire stopping of steel pipes in
appropriate surface preparation should be made flexible walls
(contact Polyseam for guidance in these cases). For
Protecta FR Acrylic
paints sensitive to sealing compounds, priming with Construction Minimum wall thickness of 75
Minimum seal depth
a PVA primer is recommended. Steel mm and comprise steel studs
12.5mm double sided
3. When installing the sealant in gypsum boards, the or timber studs* lined on both
pipe
exposed edges of the board can be wetted with faces with minimum 1 layer of
water, or Protecta® FR Acrylic diluted with water to 12.5 mm thick boards.
prime the surfaces helping adhesion and preventing
excessive joint shrinkage. Continuous pipe
Fire & Sound classification
4. When installing any backing material, cut this slightly insulation of stone
oversize and insert into the gap ensuring a tight wool ≥ 80kg/m3 Steel pipe ≤ Ø324mm with 20-30mm thick pipe
friction fit. Ensure correct depth is achieved.
insulation in maximum aperture 150x150mm or
5. Fill the gap or joint with Protecta® FR Acrylic to the Ø344mm
required depth. EI 45 C/U & E 60 C/U
6. Apply the sealant generously to prevent air bubbles.
Finish the bead with a moist spatula, pallet knife or Sound reduction (seal only)
brush. Rw 62dB
7. Protecta® FR Acrylic can be over-painted with most
emulsion or alkyd (gloss) paints.

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904
Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 8/4/18
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 162
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Stone wool
surfaces that cannot tolerate direct contact;
Backing with stone wool
appropriate surface preparation should be made Application Fire stopping of steel pipes in
minimum 12.5mm deep
(contact Polyseam for guidance in these cases). For flexible walls
paints sensitive to sealing compounds, priming with Protecta FR Acrylic
a PVA primer is recommended. Minimum seal depth Construction Minimum wall thickness of 100
3. When installing the sealant in gypsum boards, the Steel mm and comprise steel studs
12.5mm double sided seal
exposed edges of the board can be wetted with pipe or timber studs* lined on both
water, or Protecta® FR Acrylic diluted with water to faces with minimum 2 layers of
prime the surfaces helping adhesion and preventing 12.5 mm thick boards.
excessive joint shrinkage.
Fire & Sound classification
4. When installing any backing material, cut this slightly Continuous pipe
oversize and insert into the gap ensuring a tight insulation of stone Steel pipe ≤ Ø324mm with 20-80mm thick pipe
friction fit. Ensure correct depth is achieved. wool ≥ 80kg/m3 insulation in maximum aperture 300x300mm or
5. Fill the gap or joint with Protecta® FR Acrylic to the Ø504mm
required depth. EI 90 C/U & E 120 C/U
6. Apply the sealant generously to prevent air bubbles.
Finish the bead with a moist spatula, pallet knife or Sound reduction (seal only)
brush. Rw 62dB
7. Protecta® FR Acrylic can be over-painted with most
emulsion or alkyd (gloss) paints.

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904
Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 20/4/15
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 163
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Stone wool
surfaces that cannot tolerate direct contact;
appropriate surface preparation should be made Backing with stone wool
Application Fire stopping of steel pipes in
(contact Polyseam for guidance in these cases). For minimum 20mm deep
flexible walls
paints sensitive to sealing compounds, priming with
a PVA primer is recommended. Protecta FR Acrylic Construction Minimum wall thickness of 100
3. As Protecta® FR Acrylic is water based, in cases Minimum seal depth mm and comprise steel studs
where corrosion protection is a problem; some Steel 12.5mm double sided seal or timber studs* lined on both
metals may require a barrier between the sealant pipe faces with minimum 2 layers of
and the metal surface prior to this installation. 12.5 mm thick boards
4. When installing the sealant in gypsum boards, the
Fire & Sound classification
exposed edges of the board can be wetted with Pipe insulation of stone
water, or Protecta® FR Acrylic diluted with water to wool ≥ 80kg/m3 Steel pipe ≤ Ø54mm with ≥ 20mm thick pipe
prime the surfaces helping adhesion and preventing ≥ 50cm on both sides insulation in maximum aperture 300x300mm
excessive joint shrinkage. EI 120 C/U & E 120 C/U
5. When installing any backing material, cut this slightly
oversize and insert into the gap ensuring a tight Steel pipe ≤ Ø219mm with ≥ 30mm thick pipe
friction fit. Ensure correct depth is achieved. insulation in maximum aperture 300x300mm
6. Fill the gap or joint with Protecta® FR Acrylic to the EI 90 C/U & E 120 C/U
required depth.
7. Apply the sealant generously to prevent air bubbles. Sound reduction (seal only) Rw 62dB
Finish the bead with a moist spatula, pallet knife or
brush.
8. Protecta® FR Acrylic can be over-painted with most
emulsion or alkyd (gloss) paints.

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904 Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 20/4/15
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 164
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Stone wool
surfaces that cannot tolerate direct contact;
appropriate surface preparation should be made Application Fire stopping of steel pipes in
(contact Polyseam for guidance in these cases). For flexible walls
Backing with stone Protecta FR Acrylic
paints sensitive to sealing compounds, priming with
wool minimum Minimum seal depth 12.5mm
a PVA primer is recommended. Construction Minimum wall thickness of 100
20mm deep Maximum annular ring width 30mm
3. When installing the sealant in gypsum boards, the mm and comprise steel studs
exposed edges of the board can be wetted with Double sided seal or timber studs* lined on both
water, or Protecta® FR Acrylic diluted with water to faces with minimum 2 layers of
prime the surfaces helping adhesion and preventing 12.5 mm thick boards
excessive joint shrinkage. Steel pipe
Fire & Sound classification
4. When installing any backing material, cut this slightly
oversize and insert into the gap ensuring a tight Continuous elastomeric Steel pipe ≤ Ø40mm with 13 – 19mm thick pipe
friction fit. Ensure correct depth is achieved. insulation insulation
5. Fill the gap or joint with Protecta® FR Acrylic to the EI 120 C/C & E 120 C/C
required depth.
6. Apply the sealant generously to prevent air bubbles. Sound reduction (seal only)
Finish the bead with a moist spatula, pallet knife or Rw 62dB
brush.
7. Protecta® FR Acrylic can be over-painted with most
emulsion or alkyd (gloss) paints.

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904
Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 23/4/15
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 165
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Protecta Mineral Fibre BIO
surfaces that cannot tolerate direct contact;
appropriate surface preparation should be made Application Fire stopping of steel pipes in
(contact Polyseam for guidance in these cases). For flexible walls
Backing with Protecta Protecta FR Acrylic
paints sensitive to sealing compounds, priming with
Mineral Fibre BIO Minimum seal depth 25mm
a PVA primer is recommended. Construction Minimum wall thickness of 100
minimum 25mm deep Maximum annular ring width 30mm
3. When installing the sealant in gypsum boards, the mm and comprise steel studs
exposed edges of the board can be wetted with Double sided seal or timber studs* lined on both
water, or Protecta® FR Acrylic diluted with water to faces with minimum 2 layers of
prime the surfaces helping adhesion and preventing 12.5 mm thick boards
excessive joint shrinkage. Steel pipe
Fire & Sound classification
4. When installing any backing material, cut this slightly
oversize and insert into the gap ensuring a tight Continuous elastomeric Steel pipe ≤ Ø165mm with 13 – 19mm thick
friction fit. Ensure correct depth is achieved. insulation pipe insulation
5. Fill the gap or joint with Protecta® FR Acrylic to the EI 60 C/C & E 120 C/C
required depth.
6. Apply the sealant generously to prevent air bubbles. Sound reduction (seal only)
Finish the bead with a moist spatula, pallet knife or Rw 62dB
brush.
7. Protecta® FR Acrylic can be over-painted with most
emulsion or alkyd (gloss) paints.

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904
Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 23/4/15
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 166
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Stone wool
surfaces that cannot tolerate direct contact; Backing with stone wool
appropriate surface preparation should be made minimum 12.5mm deep Application Fire stopping of copper pipes in
(contact Polyseam for guidance in these cases). For flexible walls
paints sensitive to sealing compounds, priming with
Protecta FR Acrylic
a PVA primer is recommended. Construction Minimum wall thickness of 100
Minimum seal depth
3. As Protecta® FR Acrylic is water based, in cases Copper mm and comprise steel studs
12.5mm double sided
where corrosion protection is a problem; some pipe or timber studs* lined on both
metals may require a barrier between the sealant faces with minimum 2 layers of
and the metal surface prior to this installation. 12.5 mm thick boards
4. When installing the sealant in gypsum boards, the
Fire & Sound classification
exposed edges of the board can be wetted with
water, or Protecta® FR Acrylic diluted with water to
Copper pipe ≤ Ø12mm without pipe insulation
prime the surfaces helping adhesion and preventing
in maximum aperture 300x300mm
excessive joint shrinkage. EI 60 C/C & E 90 C/C
5. When installing any backing material, cut this slightly
oversize and insert into the gap ensuring a tight Copper pipe Ø13-Ø22mm without pipe
friction fit. Ensure correct depth is achieved. insulation in maximum aperture 300x300mm
6. Fill the gap or joint with Protecta® FR Acrylic to the EI 30 C/C & E 90 C/C
required depth.
7. Apply the sealant generously to prevent air bubbles.
Finish the bead with a moist spatula, pallet knife or Sound reduction (seal only) Rw 62dB
brush.
8. Protecta® FR Acrylic can be over-painted with most
emulsion or alkyd (gloss) paints.

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904 Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 14/8/19
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 167
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Stone wool
surfaces that cannot tolerate direct contact; Backing with stone wool
appropriate surface preparation should be made minimum 15mm deep Application Fire stopping of copper pipes in
(contact Polyseam for guidance in these cases). For flexible walls
paints sensitive to sealing compounds, priming with
Protecta FR Acrylic
a PVA primer is recommended. Construction Minimum wall thickness of 120
Minimum seal depth
3. As Protecta® FR Acrylic is water based, in cases Copper mm and comprise steel studs
15mm double sided
where corrosion protection is a problem; some pipe or timber studs* lined on both
metals may require a barrier between the sealant faces with minimum 2 layers of
and the metal surface prior to this installation. 12.5 mm thick boards
4. When installing the sealant in gypsum boards, the
Fire & Sound classification
exposed edges of the board can be wetted with
water, or Protecta® FR Acrylic diluted with water to
Copper pipe ≤ Ø54mm without pipe insulation
prime the surfaces helping adhesion and preventing
in maximum aperture 300x300mm
excessive joint shrinkage. E 120 C/C
5. When installing any backing material, cut this slightly
oversize and insert into the gap ensuring a tight
friction fit. Ensure correct depth is achieved. Sound reduction (seal only)
6. Fill the gap or joint with Protecta® FR Acrylic to the Rw 62dB
required depth.
7. Apply the sealant generously to prevent air bubbles.
Finish the bead with a moist spatula, pallet knife or
brush.
8. Protecta® FR Acrylic can be over-painted with most
emulsion or alkyd (gloss) paints.

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904
Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 14/8/19
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 168
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Stone wool
surfaces that cannot tolerate direct contact;
Backing with stone wool
appropriate surface preparation should be made Application Fire stopping of copper pipes in
minimum 12.5mm deep
(contact Polyseam for guidance in these cases). For flexible walls
paints sensitive to sealing compounds, priming with Protecta FR Acrylic
a PVA primer is recommended. Minimum seal depth Construction Minimum wall thickness of 100
3. When installing the sealant in gypsum boards, the Copper mm and comprise steel studs
12.5mm double sided seal
exposed edges of the board can be wetted with pipe or timber studs* lined on both
water, or Protecta® FR Acrylic diluted with water to faces with minimum 2 layers of
prime the surfaces helping adhesion and preventing 12.5 mm thick boards
excessive joint shrinkage.
Fire & Sound classification
4. When installing any backing material, cut this slightly Continuous pipe
oversize and insert into the gap ensuring a tight insulation of stone Copper pipe ≤ Ø54mm with 20-80mm thick pipe
friction fit. Ensure correct depth is achieved. wool ≥ 80kg/m3 insulation in maximum aperture 300x300mm or
5. Fill the gap or joint with Protecta® FR Acrylic to the Ø504mm
required depth. EI 60 C/C & E 120 C/C
6. Apply the sealant generously to prevent air bubbles.
Finish the bead with a moist spatula, pallet knife or Sound reduction (seal only)
brush. Rw 62dB
7. Protecta® FR Acrylic can be over-painted with most
emulsion or alkyd (gloss) paints.

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904
Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 14/8/19
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 169
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Stone wool
surfaces that cannot tolerate direct contact;
appropriate surface preparation should be made Backing with stone wool
Application Fire stopping of copper pipes in
(contact Polyseam for guidance in these cases). For minimum 20mm deep
flexible walls
paints sensitive to sealing compounds, priming with
a PVA primer is recommended. Protecta FR Acrylic Construction Minimum wall thickness of 100
3. As Protecta® FR Acrylic is water based, in cases Minimum seal depth mm and comprise steel studs
where corrosion protection is a problem; some Copper 12.5mm double sided seal or timber studs* lined on both
metals may require a barrier between the sealant pipe faces with minimum 2 layers of
and the metal surface prior to this installation. 12.5 mm thick boards
4. When installing the sealant in gypsum boards, the
Fire & Sound classification
exposed edges of the board can be wetted with Pipe insulation of stone
water, or Protecta® FR Acrylic diluted with water to wool ≥ 80kg/m3 Copper pipe ≤ Ø54mm with ≥ 20mm thick pipe
prime the surfaces helping adhesion and preventing ≥ 50cm on both sides insulation in maximum aperture 300x300mm
excessive joint shrinkage.
5. When installing any backing material, cut this slightly EI 120 C/U & E 120 C/U
oversize and insert into the gap ensuring a tight
friction fit. Ensure correct depth is achieved. Sound reduction (seal only)
6. Fill the gap or joint with Protecta® FR Acrylic to the Rw 62dB
required depth.
7. Apply the sealant generously to prevent air bubbles.
Finish the bead with a moist spatula, pallet knife or
brush.
8. Protecta® FR Acrylic can be over-painted with most
emulsion or alkyd (gloss) paints.

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904
Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 23/4/15
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 170
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Protecta Mineral Fibre BIO
surfaces that cannot tolerate direct contact;
appropriate surface preparation should be made Application Fire stopping of copper pipes in
(contact Polyseam for guidance in these cases). For flexible walls
Backing with Protecta Protecta FR Acrylic
paints sensitive to sealing compounds, priming with
Mineral Fibre BIO Minimum seal depth 25mm
a PVA primer is recommended. Construction Minimum wall thickness of 100
minimum 25mm deep Maximum annular ring width 30mm
3. When installing the sealant in gypsum boards, the mm and comprise steel studs
exposed edges of the board can be wetted with Double sided seal or timber studs* lined on both
water, or Protecta® FR Acrylic diluted with water to faces with minimum 2 layers of
prime the surfaces helping adhesion and preventing 12.5 mm thick boards
excessive joint shrinkage. Copper pipe
Fire & Sound classification
4. When installing any backing material, cut this slightly
oversize and insert into the gap ensuring a tight Continuous elastomeric Copper pipe ≤ Ø12mm with 9mm thick pipe
friction fit. Ensure correct depth is achieved. insulation insulation EI 120 C/C & E 120 C/C
5. Fill the gap or joint with Protecta® FR Acrylic to the
required depth. Copper pipe ≤ Ø54mm with 9 – 13mm thick
6. Apply the sealant generously to prevent air bubbles. pipe insulation EI 60 C/C & E 120 C/C
Finish the bead with a moist spatula, pallet knife or
brush. Copper pipe ≤ Ø54mm with 14 – 25mm thick
7. Protecta® FR Acrylic can be over-painted with most pipe insulation EI 60 C/C & E 60 C/C
emulsion or alkyd (gloss) paints.
Sound reduction (seal only) Rw 62dB

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904 Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 23/4/15
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 171
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Stone wool
surfaces that cannot tolerate direct contact; Backing with stone wool
appropriate surface preparation should be made minimum 12.5mm deep Application Fire stopping of alupex pipes in
(contact Polyseam for guidance in these cases). For flexible walls
paints sensitive to sealing compounds, priming with
Protecta FR Acrylic
a PVA primer is recommended. Construction Minimum wall thickness of 100
Minimum seal depth
3. As Protecta® FR Acrylic is water based, in cases Alupex mm and comprise steel studs
12.5mm double sided
where corrosion protection is a problem; some pipe or timber studs* lined on both
metals may require a barrier between the sealant faces with minimum 2 layers of
and the metal surface prior to this installation. 12.5 mm thick boards
4. When installing the sealant in gypsum boards, the
Fire & Sound classification
exposed edges of the board can be wetted with
water, or Protecta® FR Acrylic diluted with water to
Alupex pipe ≤ Ø20mm without pipe insulation
prime the surfaces helping adhesion and preventing
in maximum aperture 300x300mm
excessive joint shrinkage.
5. When installing any backing material, cut this slightly EI 120 C/C & E 120 C/C
oversize and insert into the gap ensuring a tight
friction fit. Ensure correct depth is achieved. Sound reduction (seal only)
6. Fill the gap or joint with Protecta® FR Acrylic to the Rw 62dB
required depth.
7. Apply the sealant generously to prevent air bubbles.
Finish the bead with a moist spatula, pallet knife or
brush.
8. Protecta® FR Acrylic can be over-painted with most
emulsion or alkyd (gloss) paints.

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904 Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 8/4/18
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 172
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Stone wool
surfaces that cannot tolerate direct contact; Backing with stone wool
appropriate surface preparation should be made minimum 15mm deep Application Fire stopping of alupex pipes in
(contact Polyseam for guidance in these cases). For flexible walls
paints sensitive to sealing compounds, priming with
Protecta FR Acrylic
a PVA primer is recommended. Construction Minimum wall thickness of 120
Minimum seal depth
3. As Protecta® FR Acrylic is water based, in cases Alupex mm and comprise steel studs
15mm double sided
where corrosion protection is a problem; some pipe or timber studs* lined on both
metals may require a barrier between the sealant faces with minimum 2 layers of
and the metal surface prior to this installation. 12.5 mm thick boards
4. When installing the sealant in gypsum boards, the
Fire & Sound classification
exposed edges of the board can be wetted with
water, or Protecta® FR Acrylic diluted with water to
Alupex pipe ≤ Ø75mm without pipe insulation
prime the surfaces helping adhesion and preventing
in maximum aperture 300x300mm
excessive joint shrinkage.
5. When installing any backing material, cut this slightly EI 30 C/C & E 120 C/C
oversize and insert into the gap ensuring a tight
friction fit. Ensure correct depth is achieved. Sound reduction (seal only)
6. Fill the gap or joint with Protecta® FR Acrylic to the Rw 62dB
required depth.
7. Apply the sealant generously to prevent air bubbles.
Finish the bead with a moist spatula, pallet knife or
brush.
8. Protecta® FR Acrylic can be over-painted with most
emulsion or alkyd (gloss) paints.

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904 Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 14/8/19
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 173
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Stone wool
surfaces that cannot tolerate direct contact;
Backing with stone wool
appropriate surface preparation should be made Application Fire stopping of alupex pipes in
minimum 12.5mm deep
(contact Polyseam for guidance in these cases). For flexible walls
paints sensitive to sealing compounds, priming with Protecta FR Acrylic
a PVA primer is recommended. Minimum seal depth Construction Minimum wall thickness of 100
3. When installing the sealant in gypsum boards, the Alupex mm and comprise steel studs
12.5mm double sided seal
exposed edges of the board can be wetted with pipe or timber studs* lined on both
water, or Protecta® FR Acrylic diluted with water to faces with minimum 2 layers of
prime the surfaces helping adhesion and preventing 12.5 mm thick boards
excessive joint shrinkage.
Fire & Sound classification
4. When installing any backing material, cut this slightly Continuous pipe
oversize and insert into the gap ensuring a tight insulation of glass or Alupex pipe ≤ Ø75mm with 20-50mm thick pipe
friction fit. Ensure correct depth is achieved. stone wool ≥ 75kg/m3 insulation in maximum aperture 300x300mm or
5. Fill the gap or joint with Protecta® FR Acrylic to the Ø504mm
required depth. EI 120 C/C & E 120 C/C
6. Apply the sealant generously to prevent air bubbles.
Finish the bead with a moist spatula, pallet knife or Sound reduction (seal only)
brush. Rw 62dB
7. Protecta® FR Acrylic can be over-painted with most
emulsion or alkyd (gloss) paints.

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904
Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 14/8/19
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 174
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Stone wool
surfaces that cannot tolerate direct contact;
appropriate surface preparation should be made Backing with stone wool
Application Fire stopping of alupex pipes in
(contact Polyseam for guidance in these cases). For minimum 12.5mm deep
flexible walls
paints sensitive to sealing compounds, priming with
a PVA primer is recommended. Protecta FR Acrylic Construction Minimum wall thickness of 100
3. As Protecta® FR Acrylic is water based, in cases Minimum seal depth mm and comprise steel studs
where corrosion protection is a problem; some Alupex 12.5mm double sided seal or timber studs* lined on both
metals may require a barrier between the sealant pipe faces with minimum 2 layers of
and the metal surface prior to this installation. 12.5 mm thick boards
4. When installing the sealant in gypsum boards, the
Fire & Sound classification
exposed edges of the board can be wetted with Pipe insulation of stone
water, or Protecta® FR Acrylic diluted with water to wool ≥ 80kg/m3 Alupex pipe ≤ Ø75mm with ≥ 20mm thick pipe
prime the surfaces helping adhesion and preventing ≥ 50cm on both sides insulation in maximum aperture 300x300mm
excessive joint shrinkage.
5. When installing any backing material, cut this slightly EI 120 C/C & E 120 C/C
oversize and insert into the gap ensuring a tight
friction fit. Ensure correct depth is achieved. Sound reduction (seal only)
6. Fill the gap or joint with Protecta® FR Acrylic to the Rw 62dB
required depth.
7. Apply the sealant generously to prevent air bubbles.
Finish the bead with a moist spatula, pallet knife or
brush.
8. Protecta® FR Acrylic can be over-painted with most
emulsion or alkyd (gloss) paints.

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904
Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 23/4/15
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 175
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Protecta Mineral Fibre BIO
surfaces that cannot tolerate direct contact;
appropriate surface preparation should be made Application Fire stopping of alupex pipes in
(contact Polyseam for guidance in these cases). For flexible walls
Backing with Protecta Protecta FR Acrylic
paints sensitive to sealing compounds, priming with
Mineral Fibre BIO Minimum seal depth 25mm
a PVA primer is recommended. Construction Minimum wall thickness of 100
minimum 25mm deep Maximum annular ring width 30mm
3. When installing the sealant in gypsum boards, the mm and comprise steel studs
exposed edges of the board can be wetted with Double sided seal or timber studs* lined on both
water, or Protecta® FR Acrylic diluted with water to faces with minimum 2 layers of
prime the surfaces helping adhesion and preventing 12.5 mm thick boards
excessive joint shrinkage. Alupex pipe
Fire & Sound classification
4. When installing any backing material, cut this slightly
oversize and insert into the gap ensuring a tight Continuous elastomeric Alupex pipe ≤ Ø16mm with 9mm thick pipe
friction fit. Ensure correct depth is achieved. insulation insulation EI 120 C/C & E 120 C/C
5. Fill the gap or joint with Protecta® FR Acrylic to the
required depth. Alupex pipe ≤ Ø75mm with 9 – 25mm thick pipe
6. Apply the sealant generously to prevent air bubbles. insulation EI 60 C/C & E 60 C/C
Finish the bead with a moist spatula, pallet knife or
brush. Sound reduction (seal only) Rw 62dB
7. Protecta® FR Acrylic can be over-painted with most
emulsion or alkyd (gloss) paints.

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904
Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 23/4/15
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 176
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against
surfaces that cannot tolerate direct contact; Application Fire stopping of PEX plastic
appropriate surface preparation should be made Backing with stone wool
pipes in flexible walls
(contact Polyseam for guidance in these cases). For minimum 12.5mm deep
paints sensitive to sealing compounds, priming with Construction Minimum wall thickness of 100
a PVA primer is recommended. Protecta FR Acrylic mm and comprise steel studs
3. When installing the sealant in gypsum boards, the Minimum seal depth 12.5mm or timber studs* lined on both
exposed edges of the board can be wetted with Double sided seal faces with minimum 2 layers of
water, or Protecta® FR Acrylic diluted with water to 12.5 mm thick boards.
prime the surfaces helping adhesion and preventing
excessive joint shrinkage.
Fire & Sound classification
4. When installing any backing material, cut this slightly
oversize and insert into the gap ensuring a tight
PEX pipe-in-pipe ≤ Ø25mm and maximum
friction fit. Ensure correct depth is achieved. Plastic pipe annular ring width 30mm
5. Fill the gap or joint with Protecta® FR Acrylic to the EI 120 C/C & E 120 C/C
required depth.
6. Apply the sealant generously to prevent air bubbles. Sound reduction (seal only)
Finish the bead with a moist spatula, pallet knife or Rw 62dB
brush.
7. Protecta® FR Acrylic can be over-painted with most
emulsion or alkyd (gloss) paints.

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904
Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 23/4/15
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 177
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against
surfaces that cannot tolerate direct contact; Application Fire stopping of PEX plastic
appropriate surface preparation should be made pipes in flexible walls
(contact Polyseam for guidance in these cases). For
paints sensitive to sealing compounds, priming with Construction Minimum wall thickness of 100
a PVA primer is recommended. Protecta FR Acrylic mm and comprise steel studs
3. When installing the sealant in gypsum boards, the Minimum seal depth 25mm or timber studs* lined on both
exposed edges of the board can be wetted with Double sided seal faces with minimum 2 layers of
water, or Protecta® FR Acrylic diluted with water to 12.5 mm thick boards.
prime the surfaces helping adhesion and preventing
excessive joint shrinkage.
Fire & Sound classification
4. When installing any backing material, cut this slightly
oversize and insert into the gap ensuring a tight
PEX pipe-in-pipe ≤ Ø54mm and maximum
friction fit. Ensure correct depth is achieved. Plastic pipe annular ring width 30mm
5. Fill the gap or joint with Protecta® FR Acrylic to the EI 45 C/C & E 60 C/C
required depth.
6. Apply the sealant generously to prevent air bubbles. Sound reduction (seal only)
Finish the bead with a moist spatula, pallet knife or Rw 62dB
brush.
7. Protecta® FR Acrylic can be over-painted with most
emulsion or alkyd (gloss) paints.

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904
Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 14/8/19
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 178
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against
surfaces that cannot tolerate direct contact; Application Fire stopping of plastic pipes in
appropriate surface preparation should be made flexible walls
(contact Polyseam for guidance in these cases). For Protecta FR Acrylic
paints sensitive to sealing compounds, priming with Minimum seal depth 12.5mm
Construction Minimum wall thickness of 75
a PVA primer is recommended. Maximum annular ring width 30mm mm and comprise steel studs
Double sided seal or timber studs* lined on both
3. When installing the sealant in gypsum boards, the
exposed edges of the board can be wetted with faces with minimum 1 layer of
water, or Protecta® FR Acrylic diluted with water to 12.5 mm thick boards
prime the surfaces helping adhesion and preventing
excessive joint shrinkage. Fire & Sound classification
4. When installing any backing material, cut this slightly Plastic pipe
PE, ABS or SAN+PVC pipe ≤ Ø32mm with wall
oversize and insert into the gap ensuring a tight
thickness 2.0 – 3.0mm
friction fit. Ensure correct depth is achieved.
EI 30 U/C & E 30 U/C
5. Fill the gap or joint with Protecta® FR Acrylic to the
required depth. PP pipe ≤ Ø32mm with wall thickness
6. Apply the sealant generously to prevent air bubbles. 2.3 – 4.4mm
Finish the bead with a moist spatula, pallet knife or EI 30 U/C & E 30 U/C
brush.
7. Protecta® FR Acrylic can be over-painted with most Sound reduction (seal only)
emulsion or alkyd (gloss) paints. Rw 62dB

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904 Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 14/8/19
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 179
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against Application Fire stopping of plastic pipes in
surfaces that cannot tolerate direct contact; flexible walls
appropriate surface preparation should be made Construction Minimum wall thickness of 100
(contact Polyseam for guidance in these cases). For Protecta FR Acrylic mm and comprise steel studs
paints sensitive to sealing compounds, priming with Minimum seal depth 25mm or timber studs* lined on both
a PVA primer is recommended. Maximum annular ring width 30mm faces with minimum 2 layers of
3. When installing the sealant in gypsum boards, the Double sided seal 12.5 mm thick boards
exposed edges of the board can be wetted with Fire & Sound classification
water, or Protecta® FR Acrylic diluted with water to PVC-U or PVC-C pipe ≤ Ø32mm with wall
prime the surfaces helping adhesion and preventing thickness 1.0-1.6mm EI 120 C/C & E 120 C/C
excessive joint shrinkage.
PVC-U or PVC-C pipe ≤ Ø32mm with wall
4. When installing any backing material, cut this slightly Plastic pipe
thickness 1.0-2.4mm EI 90 U/C & E 120 U/C
oversize and insert into the gap ensuring a tight
friction fit. Ensure correct depth is achieved.
PE, ABS or SAN+PVC pipe Ø20mm with wall
5. Fill the gap or joint with Protecta® FR Acrylic to the thickness 2.0mm EI 120 U/C & E 120 U/C
required depth.
6. Apply the sealant generously to prevent air bubbles. PE, ABS or SAN+PVC pipe ≤ Ø32mm with wall
Finish the bead with a moist spatula, pallet knife or thickness 2.0-3.0mm EI 90 C/C & E 90 C/C
brush.
7. Protecta® FR Acrylic can be over-painted with most PP pipe Ø20mm with wall thickness 2.2mm
emulsion or alkyd (gloss) paints. EI 120 U/C & E 120 U/C

PP pipe ≤ Ø32mm with wall thickness


1.8-4.4mm EI 60 C/C & E 60 C/C

Sound reduction (seal only) Rw 62dB

Polyseam Ltd, 15 St Andrews Road,


Huddersfield, West Yorkshire, HD1 6SB
ETA 18/0904
For all technical details on the products specified
Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu Sheet size: Drawn date & no:
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
Signed and approved: A4 14/8/19
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability NTS KB
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.

P a g e | 180
Client:
Installation Instructions

1. Before installing Protecta® FR Graphite ensure that


the surface of all service penetrations and
Job Title:
surrounding construction is free from all loose
contaminants, dust and grease.
Products Protecta FR Graphite
2. When installing any backing material, cut this slightly Stone wool
oversize and insert into the gap ensuring a tight Application Fire stopping of plastic pipes in
friction fit. Ensure correct depth is achieved. insulated flexible walls
3. Fill the gap or joint with Protecta® FR Graphite to the Construction Minimum wall thickness of 100
Backing with stone wool mm and comprise steel studs
required depth. minimum 25mm deep or timber studs* lined on both
4. Apply the sealant generously avoiding air bubbles. faces with minimum 2 layers of
Finish the bead with a moist spatula or pallet knife. 12.5 mm thick boards
Avoid excessive tooling/smoothing as this may make Fire & Sound classification
the seal surface wet and soft. PVC-U or PVC-C pipe ≤ 110 mm diameter with
wall thickness 1.9-6.6mm in seal widths between
5. Protecta® FR Graphite can be over-painted with
Plastic pipe 10 and 30mm EI 120 U/C
most emulsion or alkyd (gloss) paints.
Protecta FR Graphite
Minimum seal depth 25mm PE, ABS or SAN+PVC pipe ≤ 40 mm diameter
with wall thickness 2.4-3.7mm in seal widths
Double sided seal
between 10 and 30mm EI 120 U/C

PE, ABS or SAN+PVC pipe ≤ 110 mm diameter


with wall thickness 2.4-4.2mm in seal widths
between 10 and 30mm EI 60 U/C

PE, ABS or SAN+PVC pipe ≤ 110 mm diameter


with wall thickness 4.3-10.0mm in seal widths
between 10 and 30mm EI 90 U/C & E 120 U/C

Sound reduction (seal only) Rw 53dB

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0626 Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 11/11/18
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
Scale: Drawn by:
NTS K.B

P a g e | 181
Client:
Installation Instructions

1. Before installing Protecta® FR Graphite ensure that


the surface of all service penetrations and
Job Title:
surrounding construction is free from all loose
contaminants, dust and grease.
Products Protecta FR Graphite
2. When installing any backing material, cut this slightly Stone wool
oversize and insert into the gap ensuring a tight Application Fire stopping of plastic pipes in
friction fit. Ensure correct depth is achieved. flexible walls
3. Fill the gap or joint with Protecta® FR Graphite to the Construction Minimum wall thickness of 100
mm and comprise steel studs
required depth.
or timber studs* lined on both
4. Apply the sealant generously avoiding air bubbles. faces with minimum 2 layers of
Finish the bead with a moist spatula or pallet knife. 12.5 mm thick boards
Avoid excessive tooling/smoothing as this may make
the seal surface wet and soft. Fire & Sound classification
5. Protecta® FR Graphite can be over-painted with
Plastic pipe PVC-U or PVC-C pipe ≤ 160 mm diameter with
most emulsion or alkyd (gloss) paints.
Protecta FR Graphite wall thickness 3.2-9.5mm in seal widths between
Minimum seal depth 25mm 10 and 30mm EI 30 U/C
Double sided seal
PVC-U or PVC-C pipe ≤ 160 mm diameter with
wall thickness 9.5mm in seal widths between 10
and 30mm EI 90 U/C

PP pipe ≤ 110 mm diameter with wall thickness


1.8-6.3mm in seal widths between 10 and 30mm
EI 60 U/C

Sound reduction (seal only)


Rw 53dB

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0626 Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 11/11/18
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
Scale: Drawn by:
NTS K.B

P a g e | 182
Apertures with Client:
Installation Instructions
minimum 8mm annular
1. Before fitting the collars ensure that the gaps width around services
between the pipe and the separating element are
Job Title:
sealed with minimum 25mm deep Protecta FR
Any gaps must be sealed
Acrylic to cover the opening. Drywall, wood screws
with Protecta FR Acrylic Products Protecta FR Collar
or anchors of steel Protecta FR Acrylic
2. Place a suitable collar around the pipe and ensure on both sides
that the collar shell and fixing lugs are positioned
Plastic pipe Application Fire stopping of plastic pipes in
tightly to the surface of the wall, so that the fixings
can be inserted fully. flexible walls

3. Where the surface is uneven, apply a sealing bead of Construction Minimum wall thickness of 100
Protecta® FR Acrylic between the wall and the collar mm and comprise steel studs
shell. or timber studs* lined on both
faces with minimum 2 layers of
4. Attach the collar with ≥ Ø4mm drywall, wood screws Protecta FR Collar to 12.5 mm thick boards
or anchors with a length suitable for the number of both sides of the wall
boards that form the wall. Fire & Sound classification

Fire classifications in table on the left. For full


specifications, please refer to the Installation
Instructions.
Services Minimum Collar Classification
Height Sound reduction (seal only)
≤ Ø50mm PVC-U & PVC-C 30mm EI 60 C/C, EI 60 U/C, EI 60 C/U, EI 60 U/U (E 90) Rw 58dB
≤ Ø110mm PVC-U & PVC-C 30mm EI 60 C/C, EI 60 U/C
≤ Ø140mm PVC-U & PVC-C 50mm EI 60 C/C, EI 60 U/C, EI 60 C/U, EI 60 U/U (E 90)
≤ Ø160mm PVC-U & PVC-C 60mm EI 90 C/C, EI 90 U/C, EI 60 C/U, EI 60 U/U
Ø315x9.2mm PVC-U & PVC-C 75mm EI 60 C/C
≤ Ø50mm PE, ABS & SAN+PVC 30mm EI 60 C/C, EI 60 U/C (E 90)
≤ Ø50mm PE, ABS & SAN+PVC 50mm EI 90 C/C, EI 90 U/C, EI 90 C/U, EI 90 U/U (E 120)
≤ Ø110mm PE, ABS & SAN+PVC 30mm EI 60 C/C, EI 60 U/C
≤ Ø110mm PE, ABS & SAN+PVC 50mm EI 60 C/C, EI 60 U/C, EI 60 C/U, EI 60 U/U (E 90)
≤ Ø140mm PE, ABS & SAN+PVC 60mm EI 60 C/C, EI 60 U/C, EI 60 C/U, EI 60 U/U (E 90)
Ø160mm PE, ABS & SAN+PVC 60mm EI 90 C/C, EI 90 U/C, EI 90 C/U, EI 90 U/U
Ø200x18.2mm PE, ABS & SAN+PVC 75mm EI 60 C/C
Ø250x22.7mm PE, ABS & SAN+PVC 75mm EI 60 C/C
≤ Ø50mm PP 30mm EI 60 C/C, EI 60 U/C, EI 60 C/U, EI 60 U/U (E 90)
≤ Ø110mm PP 30mm EI 60 C/C, EI 60 U/C (E 90)
≤ Ø110mm PP 50mm EI 60 C/C, EI 60 U/C, EI 60 C/U, EI 60 U/U (E 90) Polyseam Ltd, 15 St Andrews Road,
≤ Ø160mm PP 60mm EI 60 C/C, EI 60 U/C, EI 60 C/U, EI 60 U/U Huddersfield, West Yorkshire, HD1 6SB
ETA 18/0854
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 20/8/19
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 183
Apertures with Client:
Installation Instructions
minimum 8mm annular
1. Before fitting the collars ensure that the gaps width around services
between the pipe and the separating element are
Job Title:
sealed with minimum 25mm deep Protecta FR
Any gaps must be sealed
Acrylic to cover the opening. M5 drywall with Protecta FR Acrylic Products Protecta FR Collar
anchors of steel on both sides Protecta FR Acrylic
2. Place a suitable collar around the pipe and ensure
that the collar shell and fixing lugs are positioned
Plastic pipe Application Fire stopping of plastic pipes in
tightly to the surface of the wall, so that the fixings
can be inserted fully. 2 hour fire rated flexible walls

3. Where the surface is uneven, apply a sealing bead of Construction Minimum wall thickness of 120
Protecta® FR Acrylic between the wall and the collar mm and comprise steel studs
shell. or timber studs* lined on both
faces with minimum 2 layers of
4. Attach the collar with M5 drywall anchors with a Protecta FR Collar to 12.5 mm thick boards
length suitable for the number of boards that form both sides of the wall
the wall. Fire & Sound classification

Fire classifications in table on the left. For full


specifications, please refer to the Installation
Instructions.
Services Minimum Collar Classification
Height
≤ Ø110mm PVC-U & PVC-C 50mm EI 120 C/C Sound reduction (seal only)
≤ Ø160mm PVC-U & PVC-C 60mm EI 120 C/C Rw 58dB
≤ Ø50mm PE, ABS & SAN+PVC 50mm EI 120 C/C
≤ Ø110mm PE, ABS & SAN+PVC 50mm EI 90 C/C (E 120)
Ø110x3.4mm PE, ABS & SAN+PVC 50mm EI 120 C/C
≤ Ø160mm PE, ABS & SAN+PVC 60mm EI 90 C/C
Ø160x9.5mm PE, ABS & SAN+PVC 60mm EI 120 C/C
≤ Ø50mm PP 50mm EI 120 C/C
≤ Ø110mm PP 50mm EI 90 C/C (E 120)
≤ Ø140mm PP 60mm EI 90 C/C (E 120)
Ø160mm PP 60mm EI 120 C/C

Polyseam Ltd, 15 St Andrews Road,


Huddersfield, West Yorkshire, HD1 6SB
ETA 18/0854
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 20/8/19
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 184
Apertures with Client:
Installation Instructions
minimum 8mm annular
1. Before fitting the collars ensure that the gaps width around services
between the pipe and the separating element are
Job Title:
sealed with minimum 25mm deep Protecta FR
Any gaps must be sealed
Acrylic to cover the opening. Drywall, wood screws with Protecta FR Acrylic Products Protecta FR Collar
or anchors of steel on both sides Protecta FR Acrylic
2. Place a suitable collar around the pipe and ensure
that the collar shell and fixing lugs are positioned
Composite plastic pipe Application Fire stopping of composite
tightly to the surface of the wall, so that the fixings
can be inserted fully. plastic pipes in flexible walls

3. Where the surface is uneven, apply a sealing bead of Construction Minimum wall thickness of 100
Protecta® FR Acrylic between the wall and the collar mm and comprise steel studs
shell. or timber studs* lined on both
faces with minimum 2 layers of
4. Attach the collar with ≥ Ø4mm drywall, wood screws Protecta FR Collar to 12.5 mm thick boards
or anchors with a length suitable for the number of both sides of the wall
boards that form the wall. Fire & Sound classification

Fire classifications in table on the left. For full


specifications, please refer to the Installation
Services Minimum Collar Classification Instructions.
Height
≤ Ø32mm Aquatherm Green SDR9 30mm EI 120 C/C Sound reduction (seal only)
≤ Ø50mm Aquatherm Green SDR9 50mm EI 120 C/C Rw 58dB
≤ Ø110mm Aquatherm Green SDR9 50mm EI 60 C/C (E 120)
≤ Ø50mm BluePower 50mm EI 90 C/C, EI 90 U/C, EI 90 C/U, EI 90 U/U (E 120)
≤ Ø110mm BluePower 50mm EI 60 C/C, EI 60 U/C, EI 60 C/U (E 120)
Ø125mm BluePower 60mm EI 60 C/C, EI 60 U/C, EI 60 C/U
Ø160mm BluePower 60mm EI 90 C/C, EI 90 U/C, EI 90 C/U
≤ Ø50mm Geberit Silent-PP 50mm EI 120 C/C, EI 120 U/C, EI 120 C/U, EI 120 U/U
≤ Ø110mm Geberit Silent-PP 50mm EI 60 C/C, EI 60 U/C, EI 60 C/U, EI 60 U/U (E 120)
≤ Ø50mm Polo-Kal NG pipes 50mm EI 120 C/C, EI 120 U/C, EI 120 C/U, EI 120 U/U
≤ Ø110mm Polo-Kal NG pipes 50mm EI 90 C/C, EI 90 U/C, EI 90 C/U, EI 90 U/U (E 120)
Ø125mm Polo-Kal NG pipes 60mm EI 120 C/C, EI 120 U/C (E 120 C/U, E 120 U/U)
Ø160mm Polo-Kal NG pipes 60mm EI 120 C/C, EI 120 U/C, EI 120 C/U, EI 120 U/U
≤ Ø50mm Rehau Raupiano Plus 50mm EI 90 C/C, EI 90 U/C, EI 90 C/U, EI 90 U/U (E 120)
≤ Ø110mm Rehau Raupiano Plus 50mm EI 60 C/C, EI 60 U/C, EI 60 C/U, EI 60 U/U (E 120)
≤ Ø160mm Rehau Raupiano Plus 60mm EI 120 C/C, EI 120 U/C, EI 120 C/U, EI 120 U/U
≤ Ø50mm Wavin SiTech 50mm EI 120 C/C, EI 120 U/C, EI 120 C/U, EI 120 U/U Polyseam Ltd, 15 St Andrews Road,
≤ Ø110mm Wavin SiTech 50mm EI 60 C/C, EI 60 U/C, EI 60 C/U, EI 60 U/U (E 120) Huddersfield, West Yorkshire, HD1 6SB
ETA 18/0854
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 20/8/19
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 185
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against
surfaces that cannot tolerate direct contact; Application Fire stopping of conduits in
appropriate surface preparation should be made flexible walls
(contact Polyseam for guidance in these cases). For Protecta FR Acrylic
paints sensitive to sealing compounds, priming with Minimum seal depth 12.5mm
Construction Minimum wall thickness of 75
a PVA primer is recommended. Maximum annular ring width 30mm mm and comprise steel studs
Conduit (plastic Double sided seal or timber studs* lined on both
3. When installing the sealant in gypsum boards, the
exposed edges of the board can be wetted with pipe with cables) faces with minimum 1 layer of
water, or Protecta® FR Acrylic diluted with water to 12.5 mm thick boards
prime the surfaces helping adhesion and preventing Fire & Sound classification
Cables ≤ Ø21mm
excessive joint shrinkage. single or in a
PVC-U or PVC-C conduit/pipe ≤ Ø32mm with
4. When installing any backing material, cut this slightly bundle wall thickness 1.0 – 1.8mm
oversize and insert into the gap ensuring a tight
EI 45 U/C & E 60 U/C
friction fit. Ensure correct depth is achieved.
5. Fill the gap or joint with Protecta® FR Acrylic to the PE, ABS or SAN+PVC conduit/pipe ≤ Ø32mm
required depth. with wall thickness 2.0 – 3.0mm
6. Apply the sealant generously to prevent air bubbles. EI 30 U/C & E 45 U/C
Finish the bead with a moist spatula, pallet knife or
brush. PP conduit/pipe ≤ Ø32mm with wall thickness
7. Protecta® FR Acrylic can be over-painted with most 2.3 – 4.4mm EI 30 U/C & E 45 U/C
emulsion or alkyd (gloss) paints.
Sound reduction (seal only) Rw 62dB

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904 Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 8/4/18
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 186
Client:
Installation Instructions

1. Before installing Protecta® FR Acrylic ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Acrylic
2. Where Protecta® FR Acrylic is to be installed against
surfaces that cannot tolerate direct contact; Application Fire stopping of conduits in
appropriate surface preparation should be made flexible walls
(contact Polyseam for guidance in these cases). For Protecta FR Acrylic
paints sensitive to sealing compounds, priming with Minimum seal depth 25mm
Construction Minimum wall thickness of 100
a PVA primer is recommended. Maximum annular ring width 30mm mm and comprise steel studs
Conduit (plastic Double sided seal or timber studs* lined on both
3. When installing the sealant in gypsum boards, the
exposed edges of the board can be wetted with pipe with cables) faces with minimum 2 layers of
water, or Protecta® FR Acrylic diluted with water to 12.5 mm thick boards
prime the surfaces helping adhesion and preventing Fire & Sound classification
Cables ≤ Ø21mm
excessive joint shrinkage. single or in a
PVC-U or PVC-C conduit/pipe ≤ Ø40mm with
4. When installing any backing material, cut this slightly bundle wall thickness 1.0 – 1.9mm
oversize and insert into the gap ensuring a tight
EI 120 U/C & E 120 U/C
friction fit. Ensure correct depth is achieved.
5. Fill the gap or joint with Protecta® FR Acrylic to the PE, ABS or SAN+PVC conduit/pipe ≤ Ø40mm
required depth. with wall thickness 2.0 – 3.0mm
6. Apply the sealant generously to prevent air bubbles. EI 90 U/C & E 90 U/C
Finish the bead with a moist spatula, pallet knife or
brush. PP conduit/pipe ≤ Ø40mm with wall thickness
7. Protecta® FR Acrylic can be over-painted with most 1.8 – 2.2mm EI 90 U/C & E 90 U/C
emulsion or alkyd (gloss) paints.
Sound reduction (seal only) Rw 62dB

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0904 Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 14/8/19
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 187
Client:
Installation Instructions

1. Before installing Protecta® FR Graphite ensure that


the surface of all service penetrations and
Job Title:
surrounding construction is free from all loose
contaminants, dust and grease.
Products Protecta FR Graphite
2. When installing any backing material, cut this slightly
oversize and insert into the gap ensuring a tight Application Fire stopping of conduits in
friction fit. Ensure correct depth is achieved. flexible walls
Protecta FR Graphite
3. Fill the gap or joint with Protecta® FR Graphite to the Minimum seal depth 25mm
Construction Minimum wall thickness of 100
required depth. Seal widths between 10 and 30mm
mm and comprise steel studs
4. Apply the sealant generously avoiding air bubbles. Double sided seal or timber studs* lined on both
Conduit (plastic
Finish the bead with a moist spatula or pallet knife. pipe with cables) faces with minimum 2 layers of
Avoid excessive tooling/smoothing as this may make 12.5 mm thick boards
the seal surface wet and soft.
Cables ≤ Ø20mm
Fire & Sound classification
5. Protecta® FR Graphite can be over-painted with single or in a
most emulsion or alkyd (gloss) paints. bundle PE, ABS or SAN+PVC conduit/pipe ≤ Ø110mm
with wall thickness 2.4 - 10.0mm EI 60 U/C

PP conduit/pipe ≤ Ø110mm with wall thickness


2.7 - 6.6mm EI 90 U/C

PVC-U or PVC-C conduit/pipe ≤ Ø110mm with


wall thickness 1.9 - 6.6mm EI 90 U/C

Sound reduction (seal only) Rw 53dB

Polyseam Ltd, 15 St Andrews Road,


ETA 18/0626 Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over Sheet size: Drawn date & no:
Signed and approved:
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is A4 11/11/18
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability
Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 188
Appendix IV
-
Service penetration solutions in larger apertures

P a g e | 189
Client:
Installation Instructions

1. Before installing Protecta® FR Board ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants, Maximum aperture
dust and grease. unlimited width by
1200mm high Products Protecta FR Board
2. The coated side of the board should be flush with the Protecta FR Acrylic
surface of the drywall on both sides. 2 layers 50mm
3. Cut the required board(s) to suit the aperture FR Board 1-S
Application Fire stopping of cables in
dimensions and type and size of service flexible walls
penetration(s). All exposed and cut edges of the
board can be sealed with Protecta® FR Coating or Construction Minimum wall thickness of 100
Protecta® FR Acrylic prior to fitting which will act as mm and comprise steel studs
an adhesive and ensure a smoke tight seal. or timber studs* lined on both
4. All joints, gaps or imperfections in the installed seal faces with minimum 2 layers of
must be filled with Protecta® FR Acrylic on both 12.5 mm thick boards.
sides.
Fire & Sound classification
5. Protecta® FR Board can be over-painted with most All services and openings
emulsion or alkyd (gloss) paints. Cables must be sealed with FR Cables ≤ Ø21mm
Acrylic both sides EI 60 & E 120

Sound reduction (seal only)


52 dB

Minimum separations and limitations

An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 25mm
from seal edges. Services within the system Protecta® FR Board seal do not require a minimum
separation, except pipes where pipe insulation penetrates the seal and plastic pipe penetrations
which should be a minimum of 30 mm from other services in the aperture. The total amount of cross Polyseam Ltd, 15 St Andrews Road,
sections of services (including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
ETA 13/0673 & 18/0855
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 20/4/15
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 190
Client:
Installation Instructions

1. Before installing Protecta® FR Board ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants, Maximum aperture
dust and grease. 1200mm wide by
600mm high Products Protecta FR Board
2. The coated side of the board should be flush with the Protecta FR Acrylic
surface of the drywall on both sides. 2 layers 30mm
3. Cut the required board(s) to suit the aperture FR Board 1-S
Application Fire stopping of cables on cable
dimensions and type and size of service trays in flexible walls
penetration(s). All exposed and cut edges of the
board can be sealed with Protecta® FR Coating or Construction Minimum wall thickness of 75
Protecta® FR Acrylic prior to fitting which will act as mm and comprise steel studs
an adhesive and ensure a smoke tight seal. or timber studs* lined on both
4. All joints, gaps or imperfections in the installed seal faces with minimum 1 layer of
must be filled with Protecta® FR Acrylic on both 12.5 mm thick boards
sides.
5. Protecta® FR Board can be over-painted with most Cables on All services and openings Fire & Sound classification
emulsion or alkyd (gloss) paints. cable trays must be sealed with FR
Acrylic both sides Cables ≤ Ø21mm single or bundled on trays
EI 45 & E 45

Cables ≤ Ø80mm single or bundled on trays


EI 30 & E 45

Sound reduction (seal only)


52 dB

Minimum separations and limitations

An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 25mm
from seal edges. Services within the system Protecta® FR Board seal do not require a minimum
separation, except pipes where pipe insulation penetrates the seal and plastic pipe penetrations
which should be a minimum of 30 mm from other services in the aperture. The total amount of cross Polyseam Ltd, 15 St Andrews Road,
sections of services (including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
ETA 13/0673 & 18/0855
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 26/7/17
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 191
Client:
Installation Instructions

1. Before installing Protecta® FR Board ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants, Maximum aperture
1 layer 50mm
dust and grease. 1200mm wide by
FR Board 2-S Products Protecta FR Board
2. The board can be positioned to either side of the 600mm high
Protecta FR Acrylic
construction or anywhere in between. Protecta FR ServiceCoat FR-1
3. Cut the required board(s) to suit the aperture
dimensions and type and size of service Framed aperture with Application Fire stopping of cables on cable
penetration(s). All exposed and cut edges of the 2 layers of 12.5mm All services must trays in flexible walls
board can be sealed with Protecta® FR Coating or gypsum boards be coated with
Protecta® FR Acrylic prior to fitting which will act as Service Coat FR-1 Construction Minimum wall thickness of 100
an adhesive and ensure a smoke tight seal. both sides mm and comprise steel studs
4. All joints, gaps or imperfections in the installed seal or timber studs* lined on both
must be filled with Protecta® FR Acrylic on both faces with minimum 2 layers of
sides. 12.5 mm thick boards
5. All cables and cable trays must be coated 150mm Cables on Fire & Sound classification
each side with 300μ WFT Protecta Service Coat FR-1. perforated cable
6. Protecta® FR Board can be over-painted with most trays and ladders
All services and openings Cables ≤ Ø80mm single or bundled on
emulsion or alkyd (gloss) paints. perforated cable trays and ladders
must be sealed with FR
Acrylic both sides EI 60 & E 60

Sound reduction (seal only)


29 dB

Minimum separations and limitations

An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 25mm
from seal edges. Services within the system Protecta® FR Board seal do not require a minimum
separation, except pipes where pipe insulation penetrates the seal and plastic pipe penetrations
which should be a minimum of 30 mm from other services in the aperture. The total amount of cross Polyseam Ltd, 15 St Andrews Road,
sections of services (including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
ETA 13/0673 & 18/0855
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 26/7/17
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 192
Client:
Installation Instructions

1. Before installing Protecta® FR Board ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants, Maximum aperture
dust and grease. unlimited width by
1200mm high Products Protecta FR Board
2. The coated side of the board should be flush with the Protecta FR Acrylic
surface of the drywall on both sides. 2 layers 50mm
3. Cut the required board(s) to suit the aperture FR Board 1-S
Application Fire stopping of cables, wires
dimensions and type and size of service and conduits on cable trays in
penetration(s). All exposed and cut edges of the flexible walls
board can be sealed with Protecta® FR Coating or
Protecta® FR Acrylic prior to fitting which will act as Construction Minimum wall thickness of 100
an adhesive and ensure a smoke tight seal. mm and comprise steel studs
4. All joints, gaps or imperfections in the installed seal or timber studs* lined on both
must be filled with Protecta® FR Acrylic on both faces with minimum 2 layers of
sides. 12.5 mm thick boards.
5. Protecta® FR Board can be over-painted with most Cables, wires All services and openings Fire & Sound classification
emulsion or alkyd (gloss) paints. and conduits must be sealed with FR
on cable trays Acrylic both sides Cables ≤ Ø80mm single or bundled, wires
185mm2 and steel or PVC conduits ≤ Ø16mm on
trays
EI 60 & E 60

Sound reduction (seal only)


52 dB

Minimum separations and limitations

An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 25mm
from seal edges. Services within the system Protecta® FR Board seal do not require a minimum
separation, except pipes where pipe insulation penetrates the seal and plastic pipe penetrations
which should be a minimum of 30 mm from other services in the aperture. The total amount of cross Polyseam Ltd, 15 St Andrews Road,
sections of services (including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
ETA 13/0673 & 18/0855
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 20/4/15
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 193
Client:
Installation Instructions

1. Before installing Protecta® FR Board ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants, Maximum aperture
dust and grease. 1200mm wide by
600mm high Products Protecta FR Board
2. Protecta® FR Coating and Protecta® FR Acrylic are Protecta FR Acrylic
water based, so in cases where corrosion protection 2 layers 30mm
is a problem, some metals may require a barrier FR Board 1-S
Application Fire stopping of un-insulated
between the seal and the surface prior to this steel pipes in flexible walls
installation.
3. The coated side of the board should be flush with the Construction Minimum wall thickness of 75
surface of the drywall on both sides. mm and comprise steel studs
4. Cut the required board(s) to suit the aperture or timber studs* lined on both
dimensions and type and size of service faces with minimum 1 layer of
penetration(s). All exposed and cut edges of the 12.5 mm thick boards.
board can be sealed with Protecta® FR Coating or
Protecta® FR Acrylic prior to fitting which will act as
All services and openings Fire & Sound classification
an adhesive and ensure a smoke tight seal. Steel pipes
5. All joints, gaps or imperfections in the installed seal must be sealed with FR
Acrylic both sides Steel pipes ≤ Ø22mm
must be filled with Protecta® FR Acrylic on both EI 30 C/U & E 45 C/U
sides.
6. Protecta® FR Board can be over-painted with most Sound reduction (seal only)
emulsion or alkyd (gloss) paints. 52 dB

Minimum separations and limitations

An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 25mm
from seal edges. Services within the system Protecta® FR Board seal do not require a minimum
separation, except pipes where pipe insulation penetrates the seal and plastic pipe penetrations
which should be a minimum of 30 mm from other services in the aperture. The total amount of cross Polyseam Ltd, 15 St Andrews Road,
sections of services (including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
ETA 13/0673 & 18/0855
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 26/7/17
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 194
Client:
Installation Instructions

1. Before installing Protecta® FR Board ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants, Maximum aperture
dust and grease. unlimited width by
1200mm high Products Protecta FR Board
2. Protecta® FR Coating and Protecta® FR Acrylic are Protecta FR Acrylic
water based, so in cases where corrosion protection 2 layers 50mm
is a problem, some metals may require a barrier FR Board 1-S
Application Fire stopping of un-insulated
between the seal and the surface prior to this steel pipes in flexible walls
installation.
3. The coated side of the board should be flush with the Construction Minimum wall thickness of 100
surface of the drywall on both sides. mm and comprise steel studs
4. Cut the required board(s) to suit the aperture or timber studs* lined on both
dimensions and type and size of service faces with minimum 2 layers of
penetration(s). All exposed and cut edges of the 12.5 mm thick boards.
board can be sealed with Protecta® FR Coating or
Protecta® FR Acrylic prior to fitting which will act as
All services and openings Fire & Sound classification
an adhesive and ensure a smoke tight seal. Steel pipes
5. All joints, gaps or imperfections in the installed seal must be sealed with FR
Acrylic both sides Steel pipes ≤ Ø22mm
must be filled with Protecta® FR Acrylic on both EI 60 C/U & E 120 C/U
sides.
6. Protecta® FR Board can be over-painted with most Steel pipes ≤ Ø114mm
emulsion or alkyd (gloss) paints. EI 20 C/U & E 90 C/U

Sound reduction (seal only)


52 dB

Minimum separations and limitations

An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 25mm
from seal edges. Services within the system Protecta® FR Board seal do not require a minimum
separation, except pipes where pipe insulation penetrates the seal and plastic pipe penetrations
which should be a minimum of 30 mm from other services in the aperture. The total amount of cross Polyseam Ltd, 15 St Andrews Road,
sections of services (including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
ETA 13/0673 & 18/0855
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 26/7/17
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 195
Client:
Installation Instructions

1. Before installing Protecta® FR Board ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants, Maximum aperture
dust and grease. unlimited width by
1200mm high Products Protecta FR Board
2. The coated side of the board should be flush with the Protecta FR Acrylic
surface of the drywall on both sides. 2 layers 50mm
Protecta FR Pipe Wrap 25m
3. Cut the required board(s) to suit the aperture FR Board 1-S
Application Fire stopping of insulated steel
dimensions and type and size of service pipes in flexible walls
penetration(s). All exposed and cut edges of the Continuous Protecta Pipe Wrap Construction Minimum wall thickness of 100
board can be sealed with Protecta® FR Coating or elastomeric or PE 50mm wide fitted both mm and comprise steel studs
Protecta® FR Acrylic prior to fitting which will act as foam insulation sides or timber studs* lined on both
an adhesive and ensure a smoke tight seal. faces with minimum 2 layers of
4. All joints, gaps or imperfections in the installed seal 12.5 mm thick boards.
must be filled with Protecta® FR Acrylic on both Fire & Sound classification
sides. Steel pipes ≤ Ø40mm with 13mm continuous
foam insulation and 2 layers of pipe wrap
5. Protecta® FR Board can be over-painted with most
Steel pipes EI 120 U/U & E 120 U/U
emulsion or alkyd (gloss) paints. All services and openings
must be sealed with FR Steel pipes ≤ Ø165mm with 13 - 32mm contin-
Acrylic both sides uous foam insulation and 2 layers of pipe wrap
EI 60 U/U & E 120 U/U

Steel pipes ≤ Ø324mm with 32 - 50mm contin-


uous foam insulation and 3 layers of pipe wrap
EI 90 C/U & E 90 C/U

Sound reduction (seal only) 52 dB

Minimum separations and limitations

An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 25mm
from seal edges. Services within the system Protecta® FR Board seal do not require a minimum
separation, except pipes where pipe insulation penetrates the seal and plastic pipe penetrations
which should be a minimum of 30 mm from other services in the aperture. The total amount of cross Polyseam Ltd, 15 St Andrews Road,
ETA 13/0673 & 18/0855 sections of services (including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 5/3/19
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 196
Client:
Installation Instructions

1. Before installing Protecta® FR Board ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants, Maximum aperture
1200mm wide by 2 layers 30mm
dust and grease.
600mm high FR Board 1-S Products Protecta FR Board
2. The coated side of the board should be flush with the Protecta FR Acrylic
surface of the drywall on both sides.
3. Cut the required board(s) to suit the aperture Application Fire stopping of insulated steel
Continuous stone
dimensions and type and size of service pipes in flexible walls
wool insulation
penetration(s). All exposed and cut edges of the
≥ 80 kg/m3
board can be sealed with Protecta® FR Coating or Construction Minimum wall thickness of 75
Protecta® FR Acrylic prior to fitting which will act as mm and comprise steel studs
an adhesive and ensure a smoke tight seal. or timber studs* lined on both
4. All joints, gaps or imperfections in the installed seal faces with minimum 1 layer of
must be filled with Protecta® FR Acrylic on both 12.5 mm thick boards.
sides. Steel pipes
5. Protecta® FR Board can be over-painted with most
Fire & Sound classification
emulsion or alkyd (gloss) paints.
All services and openings
must be sealed with FR Steel pipes ≤ Ø324mm with 20-30mm
Acrylic both sides continuous stone wool insulation
EI 45 C/U & E 45 C/U

Sound reduction (seal only)


52 dB

Minimum separations and limitations

An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 25mm
from seal edges. Services within the system Protecta® FR Board seal do not require a minimum
separation, except pipes where pipe insulation penetrates the seal and plastic pipe penetrations
which should be a minimum of 30 mm from other services in the aperture. The total amount of cross Polyseam Ltd, 15 St Andrews Road,
sections of services (including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
ETA 13/0673 & 18/0855
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 26/7/17
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 197
Client:
Installation Instructions

1. Before installing Protecta® FR Board ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants, Maximum aperture
1200mm wide by 1 layer 50mm
dust and grease.
600mm high FR Board 2-S Products Protecta FR Board
2. The board can be positioned to either side of the Protecta FR Acrylic
construction or anywhere in between.
3. Cut the required board(s) to suit the aperture Framed aperture with Application Fire stopping of insulated steel
dimensions and type and size of service 2 layers of 12.5mm pipes in flexible walls
penetration(s). All exposed and cut edges of the gypsum boards
board can be sealed with Protecta® FR Coating or Construction Minimum wall thickness of 100
Protecta® FR Acrylic prior to fitting which will act as mm and comprise steel studs
an adhesive and ensure a smoke tight seal. or timber studs* lined on both
4. All joints, gaps or imperfections in the installed seal faces with minimum 2 layers of
must be filled with Protecta® FR Acrylic on both 12.5 mm thick boards.
sides. Steel pipes
5. Protecta® FR Board can be over-painted with most
Fire & Sound classification
emulsion or alkyd (gloss) paints. Continuous stone
All services and openings
wool insulation Steel pipes ≤ Ø324mm with 20-30mm
must be sealed with FR
≥ 80 kg/m3 continuous stone wool insulation
Acrylic both sides
EI 60 C/U & E 90 C/U

Sound reduction (seal only)


29 dB

Minimum separations and limitations

An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 25mm
from seal edges. Services within the system Protecta® FR Board seal do not require a minimum
separation, except pipes where pipe insulation penetrates the seal and plastic pipe penetrations
which should be a minimum of 30 mm from other services in the aperture. The total amount of cross Polyseam Ltd, 15 St Andrews Road,
sections of services (including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
ETA 13/0673 & 18/0855
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 26/7/17
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 198
Client:
Installation Instructions

1. Before installing Protecta® FR Board ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants, Maximum aperture
unlimited width by 2 layers 50mm
dust and grease.
1200mm high FR Board 1-S Products Protecta FR Board
2. The coated side of the board should be flush with the Protecta FR Acrylic
surface of the drywall on both sides.
3. Cut the required board(s) to suit the aperture Application Fire stopping of insulated steel
Continuous stone
dimensions and type and size of service pipes in flexible walls
wool insulation
penetration(s). All exposed and cut edges of the
≥ 80 kg/m3
board can be sealed with Protecta® FR Coating or Construction Minimum wall thickness of 100
Protecta® FR Acrylic prior to fitting which will act as mm and comprise steel studs
an adhesive and ensure a smoke tight seal. or timber studs* lined on both
4. All joints, gaps or imperfections in the installed seal faces with minimum 2 layers of
must be filled with Protecta® FR Acrylic on both 12.5 mm thick boards.
sides. Steel pipes
5. Protecta® FR Board can be over-painted with most
Fire & Sound classification
emulsion or alkyd (gloss) paints.
All services and openings
must be sealed with FR Steel pipes ≤ Ø324mm with 20-80mm
Acrylic both sides continuous stone wool insulation
EI 120 C/U & E 120 C/U

Sound reduction (seal only)


52 dB

Minimum separations and limitations

An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 25mm
from seal edges. Services within the system Protecta® FR Board seal do not require a minimum
separation, except pipes where pipe insulation penetrates the seal and plastic pipe penetrations
which should be a minimum of 30 mm from other services in the aperture. The total amount of cross Polyseam Ltd, 15 St Andrews Road,
sections of services (including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
ETA 13/0673 & 18/0855
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 10/1/17
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 199
Client:
Installation Instructions

1. Before installing Protecta® FR Board ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants, Maximum aperture
dust and grease. unlimited width by
1200mm high Products Protecta FR Board
2. Protecta® FR Coating and Protecta® FR Acrylic are Protecta FR Acrylic
water based, so in cases where corrosion protection 2 layers 50mm
is a problem, some metals may require a barrier FR Board 1-S
Application Fire stopping of insulated steel
between the seal and the surface prior to this pipes in flexible walls
installation. Stone wool ≥ 80 kg/m3
3. The coated side of the board should be flush with the to be installed ≥ 50cm Construction Minimum wall thickness of 100
surface of the drywall on both sides. on both sides mm and comprise steel studs
4. Cut the required board(s) to suit the aperture or timber studs* lined on both
dimensions and type and size of service faces with minimum 2 layers of
penetration(s). All exposed and cut edges of the 12.5 mm thick boards.
board can be sealed with Protecta® FR Coating or
Fire & Sound classification
Protecta® FR Acrylic prior to fitting which will act as
an adhesive and ensure a smoke tight seal. Steel pipes
All services and openings Steel pipes ≤ Ø40mm with ≥ 20mm stone wool
5. All joints, gaps or imperfections in the installed seal must be sealed with FR insulation
must be filled with Protecta® FR Acrylic on both Acrylic both sides EI 120 C/U & E 120 C/U
sides.
6. Protecta® FR Board can be over-painted with most Steel pipes ≤ Ø219mm with ≥ 30mm stone wool
emulsion or alkyd (gloss) paints. insulation
EI 90 C/U & E 120 C/U

Sound reduction (seal only)


52 dB

Minimum separations and limitations

An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 25mm
from seal edges. Services within the system Protecta® FR Board seal do not require a minimum
separation, except pipes where pipe insulation penetrates the seal and plastic pipe penetrations
which should be a minimum of 30 mm from other services in the aperture. The total amount of cross Polyseam Ltd, 15 St Andrews Road,
ETA 13/0673 & 18/0855 sections of services (including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 20/4/15
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 200
Client:
Installation Instructions

1. Before installing Protecta® FR Board ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants, Maximum aperture
dust and grease. unlimited width by
1200mm high Products Protecta FR Board
2. Protecta® FR Coating and Protecta® FR Acrylic are Protecta FR Acrylic
water based, so in cases where corrosion protection 2 layers 50mm
is a problem, some metals may require a barrier FR Board 1-S
Application Fire stopping of un-insulated
between the seal and the surface prior to this copper pipes in flexible walls
installation.
3. The coated side of the board should be flush with the Construction Minimum wall thickness of 100
surface of the drywall on both sides. mm and comprise steel studs
4. Cut the required board(s) to suit the aperture or timber studs* lined on both
dimensions and type and size of service faces with minimum 2 layers of
penetration(s). All exposed and cut edges of the 12.5 mm thick boards.
board can be sealed with Protecta® FR Coating or
Protecta® FR Acrylic prior to fitting which will act as
All services and openings Fire & Sound classification
an adhesive and ensure a smoke tight seal. Copper pipes
5. All joints, gaps or imperfections in the installed seal must be sealed with FR
Acrylic both sides Copper pipes ≤ Ø6mm
must be filled with Protecta® FR Acrylic on both EI 60 C/C & E 120 C/C
sides.
6. Protecta® FR Board can be over-painted with most Sound reduction (seal only)
emulsion or alkyd (gloss) paints. 52 dB

Minimum separations and limitations

An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 25mm
from seal edges. Services within the system Protecta® FR Board seal do not require a minimum
separation, except pipes where pipe insulation penetrates the seal and plastic pipe penetrations
which should be a minimum of 30 mm from other services in the aperture. The total amount of cross Polyseam Ltd, 15 St Andrews Road,
sections of services (including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
ETA 13/0673 & 18/0855
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 26/7/17
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 201
Client:
Installation Instructions

1. Before installing Protecta® FR Board ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants, Maximum aperture
dust and grease. unlimited width by
1200mm high Products Protecta FR Board
2. The coated side of the board should be flush with the Protecta FR Acrylic
surface of the drywall on both sides. 2 layers 50mm
Protecta FR Pipe Wrap 25m
3. Cut the required board(s) to suit the aperture FR Board 1-S
Application Fire stopping of insulated
dimensions and type and size of service copper pipes in flexible walls
penetration(s). All exposed and cut edges of the Continuous Protecta Pipe Wrap 2 Construction Minimum wall thickness of 100
board can be sealed with Protecta® FR Coating or elastomeric or PE layers of 50mm wide mm and comprise steel studs
Protecta® FR Acrylic prior to fitting which will act as foam insulation fitted both sides or timber studs* lined on both
an adhesive and ensure a smoke tight seal. faces with minimum 2 layers of
4. All joints, gaps or imperfections in the installed seal 12.5 mm thick boards.
must be filled with Protecta® FR Acrylic on both Fire & Sound classification
sides.
Copper pipes ≤ Ø12mm with 9mm continuous
5. Protecta® FR Board can be over-painted with most
Copper pipes foam insulation EI 120 C/C & E 120 C/C
emulsion or alkyd (gloss) paints. All services and openings
must be sealed with FR Copper pipes ≤ Ø54mm with 9 - 13mm
Acrylic both sides continuous foam insulation
EI 90 C/C & E 120 C/C

Copper pipes ≤ Ø54mm with 14 - 25mm


continuous foam insulation
EI 60 C/C & E 120 C/C

Sound reduction (seal only) 52 dB

Minimum separations and limitations

An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 25mm
from seal edges. Services within the system Protecta® FR Board seal do not require a minimum
separation, except pipes where pipe insulation penetrates the seal and plastic pipe penetrations
which should be a minimum of 30 mm from other services in the aperture. The total amount of cross Polyseam Ltd, 15 St Andrews Road,
ETA 13/0673 & 18/0855 sections of services (including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 5/3/19
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 202
Client:
Installation Instructions

1. Before installing Protecta® FR Board ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants, Maximum aperture
dust and grease. unlimited width by
1200mm high Products Protecta FR Board
2. Protecta® FR Coating and Protecta® FR Acrylic are Protecta FR Acrylic
water based, so in cases where corrosion protection 2 layers 50mm
is a problem, some metals may require a barrier FR Board 1-S
Application Fire stopping of insulated
between the seal and the surface prior to this copper pipes in flexible walls
installation. Stone wool ≥ 80 kg/m3
3. The coated side of the board should be flush with the to be installed ≥ 50cm Construction Minimum wall thickness of 100
surface of the drywall on both sides. on both sides mm and comprise steel studs
4. Cut the required board(s) to suit the aperture or timber studs* lined on both
dimensions and type and size of service faces with minimum 2 layers of
penetration(s). All exposed and cut edges of the 12.5 mm thick boards.
board can be sealed with Protecta® FR Coating or
Protecta® FR Acrylic prior to fitting which will act as
Copper pipes Fire & Sound classification
an adhesive and ensure a smoke tight seal. All services and openings
5. All joints, gaps or imperfections in the installed seal must be sealed with FR Copper pipes ≤ Ø54mm with ≥ 20mm stone
must be filled with Protecta® FR Acrylic on both Acrylic both sides wool insulation
sides. EI 120 C/C & E 120 C/C
6. Protecta® FR Board can be over-painted with most
emulsion or alkyd (gloss) paints.
Sound reduction (seal only)
52 dB

Minimum separations and limitations

An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 25mm
from seal edges. Services within the system Protecta® FR Board seal do not require a minimum
separation, except pipes where pipe insulation penetrates the seal and plastic pipe penetrations
which should be a minimum of 30 mm from other services in the aperture. The total amount of cross Polyseam Ltd, 15 St Andrews Road,
sections of services (including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
ETA 13/0673 & 18/0855
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 20/4/15
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 203
Client:
Installation Instructions

1. Before installing Protecta® FR Board ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants, Maximum aperture
dust and grease. unlimited width by
1200mm high Products Protecta FR Board
2. Protecta® FR Coating and Protecta® FR Acrylic are Protecta FR Acrylic
water based, so in cases where corrosion protection 2 layers 50mm
is a problem, some metals may require a barrier FR Board 1-S
Application Fire stopping of un-insulated
between the seal and the surface prior to this alupex pipes in flexible walls
installation.
3. The coated side of the board should be flush with the Construction Minimum wall thickness of 100
surface of the drywall on both sides. mm and comprise steel studs
4. Cut the required board(s) to suit the aperture or timber studs* lined on both
dimensions and type and size of service faces with minimum 2 layers of
penetration(s). All exposed and cut edges of the 12.5 mm thick boards.
board can be sealed with Protecta® FR Coating or
Protecta® FR Acrylic prior to fitting which will act as
All services and openings Fire & Sound classification
an adhesive and ensure a smoke tight seal. Alupex pipes
5. All joints, gaps or imperfections in the installed seal must be sealed with FR
Acrylic both sides Alupex pipes ≤ Ø20mm
must be filled with Protecta® FR Acrylic on both EI 120 C/C & E 120 C/C
sides.
6. Protecta® FR Board can be over-painted with most Sound reduction (seal only)
emulsion or alkyd (gloss) paints. 52 dB

Minimum separations and limitations

An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 25mm
from seal edges. Services within the system Protecta® FR Board seal do not require a minimum
separation, except pipes where pipe insulation penetrates the seal and plastic pipe penetrations
which should be a minimum of 30 mm from other services in the aperture. The total amount of cross Polyseam Ltd, 15 St Andrews Road,
sections of services (including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
ETA 13/0673 & 18/0855
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 26/7/17
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 204
Client:
Installation Instructions

1. Before installing Protecta® FR Board ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants, Maximum aperture
dust and grease. unlimited width by
1200mm high Products Protecta FR Board
2. The coated side of the board should be flush with the Protecta FR Acrylic
surface of the drywall on both sides. 2 layers 50mm
Protecta FR Pipe Wrap 25m
3. Cut the required board(s) to suit the aperture FR Board 1-S
dimensions and type and size of service Application Fire stopping of insulated
penetration(s). All exposed and cut edges of the Continuous Protecta Pipe Wrap 2 alupex pipes in flexible walls
board can be sealed with Protecta® FR Coating or elastomeric or PE layers of 50mm wide
Protecta® FR Acrylic prior to fitting which will act as foam insulation fitted both sides Construction Minimum wall thickness of 100
an adhesive and ensure a smoke tight seal. mm and comprise steel studs
4. All joints, gaps or imperfections in the installed seal or timber studs* lined on both
must be filled with Protecta® FR Acrylic on both faces with minimum 2 layers of
sides. 12.5 mm thick boards.
5. Protecta® FR Board can be over-painted with most
Alupex pipes Fire & Sound classification
emulsion or alkyd (gloss) paints. All services and openings
must be sealed with FR Alupex pipes ≤ Ø75mm with 9 - 25mm
Acrylic both sides continuous foam insulation
EI 120 C/C & E 120 C/C

Sound reduction (seal only)


52 dB

Minimum separations and limitations

An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 25mm
from seal edges. Services within the system Protecta® FR Board seal do not require a minimum
separation, except pipes where pipe insulation penetrates the seal and plastic pipe penetrations
which should be a minimum of 30 mm from other services in the aperture. The total amount of cross Polyseam Ltd, 15 St Andrews Road,
sections of services (including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
ETA 13/0673 & 18/0855
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 5/3/19
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 205
Client:
Installation Instructions

1. Before installing Protecta® FR Board ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants, Maximum aperture
dust and grease. unlimited width by
1200mm high Products Protecta FR Board
2. Protecta® FR Coating and Protecta® FR Acrylic are Protecta FR Acrylic
water based, so in cases where corrosion protection 2 layers 50mm
is a problem, some metals may require a barrier FR Board 1-S
Application Fire stopping of insulated
between the seal and the surface prior to this alupex pipes in flexible walls
installation. Stone wool ≥ 80 kg/m3
3. The coated side of the board should be flush with the to be installed ≥ 50cm Construction Minimum wall thickness of 100
surface of the drywall on both sides. on both sides mm and comprise steel studs
4. Cut the required board(s) to suit the aperture or timber studs* lined on both
dimensions and type and size of service faces with minimum 2 layers of
penetration(s). All exposed and cut edges of the 12.5 mm thick boards.
board can be sealed with Protecta® FR Coating or
Fire & Sound classification
Protecta® FR Acrylic prior to fitting which will act as
an adhesive and ensure a smoke tight seal. Alupex pipes
All services and openings Alupex pipes ≤ Ø16mm with ≥ 20mm stone
5. All joints, gaps or imperfections in the installed seal must be sealed with FR wool insulation
must be filled with Protecta® FR Acrylic on both Acrylic both sides EI 120 C/C & E 120 C/C
sides.
6. Protecta® FR Board can be over-painted with most Alupex pipes ≤ Ø75mm with ≥ 20mm stone
emulsion or alkyd (gloss) paints. wool insulation
EI 60 C/C & E 60 C/C

Sound reduction (seal only)


52 dB

Minimum separations and limitations

An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 25mm
from seal edges. Services within the system Protecta® FR Board seal do not require a minimum
separation, except pipes where pipe insulation penetrates the seal and plastic pipe penetrations
which should be a minimum of 30 mm from other services in the aperture. The total amount of cross Polyseam Ltd, 15 St Andrews Road,
ETA 13/0673 & 18/0855 sections of services (including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 20/4/15
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 206
Client:
Installation Instructions

1. Before installing Protecta® FR Board ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants, Maximum aperture
dust and grease. 1200mm wide by
600mm high Products Protecta FR Board
2. The coated side of the board should be flush with the Protecta FR Acrylic
surface of the drywall on both sides. 2 layers 30mm
3. Cut the required board(s) to suit the aperture FR Board 1-S
Application Fire stopping of plastic pipes in
dimensions and type and size of service flexible walls
penetration(s). All exposed and cut edges of the
board can be sealed with Protecta® FR Coating or Construction Minimum wall thickness of 75
Protecta® FR Acrylic prior to fitting which will act as mm and comprise steel studs
an adhesive and ensure a smoke tight seal. or timber studs* lined on both
4. All joints, gaps or imperfections in the installed seal faces with minimum 1 layer of
must be filled with Protecta® FR Acrylic on both 12.5 mm thick boards
sides.
5. Protecta® FR Board can be over-painted with most
Fire & Sound classification
emulsion or alkyd (gloss) paints. Plastic pipes
All services and openings
PVC-U and PVC-C pipes ≤ Ø32mm with wall
must be sealed with FR thickness 1.0-1.8mm
Acrylic both sides EI 45 U/C & E 45 U/C

Sound reduction (seal only)


52 dB

Minimum separations and limitations

An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 25mm
from seal edges. Services within the system Protecta® FR Board seal do not require a minimum
separation, except pipes where pipe insulation penetrates the seal and plastic pipe penetrations
which should be a minimum of 30 mm from other services in the aperture. The total amount of cross Polyseam Ltd, 15 St Andrews Road,
sections of services (including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
ETA 13/0673 & 18/0855
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 5/3/19
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 207
Client:
Installation Instructions

1. Before installing Protecta® FR Board ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants, Maximum aperture
dust and grease. 1200mm wide by 1 layer 50mm
600mm high Products Protecta FR Board
2. The board can be positioned to either side of the FR Board 2-S
Protecta FR Acrylic
construction or anywhere in between. Protecta FR Collar
3. Cut the required board(s) to suit the aperture All services and openings
dimensions and type and size of service must be sealed with FR Application Fire stopping of plastic pipes in
penetration(s). All exposed and cut edges of the Framed aperture with
Acrylic both sides flexible walls
2 layers of 12.5mm
board can be sealed with Protecta® FR Coating or
gypsum boards Construction Minimum wall thickness of 100
Protecta® FR Acrylic prior to fitting which will act as
an adhesive and ensure a smoke tight seal. mm and comprise steel studs
4. All joints, gaps or imperfections in the installed seal or timber studs* lined on both
must be filled with Protecta® FR Acrylic on both faces with minimum 2 layers of
sides. 12.5 mm thick boards.
5. Plastic pipes must be secured with Protecta® FR
Fire & Sound classification
Collars Ø110mm fixed with penetrating threaded Plastic pipes Protecta FR Collar
rod and nuts on both sides. Ø110mm
PVC-U and PVC-C pipes ≤ Ø110mm
6. Protecta® FR Board can be over-painted with most EI 60 U/C & E 90 U/C
emulsion or alkyd (gloss) paints.
Sound reduction (seal only)
29 dB

Minimum separations and limitations

An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 25mm
from seal edges. Services within the system Protecta® FR Board seal do not require a minimum
separation, except pipes where pipe insulation penetrates the seal and plastic pipe penetrations
which should be a minimum of 30 mm from other services in the aperture. The total amount of cross Polyseam Ltd, 15 St Andrews Road,
sections of services (including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
ETA 13/0673 & 18/0855
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 26/7/17
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 208
Client:
Installation Instructions

1. Before installing Protecta® FR Board ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants, Maximum aperture
dust and grease. unlimited width by
1200mm high Products Protecta FR Board
2. The coated side of the board should be flush with the Protecta FR Acrylic
surface of the drywall on both sides. 2 layers 50mm
Application Fire stopping of plastic pipes in
3. Cut the required board(s) to suit the aperture FR Board 1-S
flexible walls
dimensions and type and size of service Construction Minimum wall thickness of 100
penetration(s). All exposed and cut edges of the mm and comprise steel studs
board can be sealed with Protecta® FR Coating or or timber studs* lined on both
Protecta® FR Acrylic prior to fitting which will act as faces with minimum 2 layers of
an adhesive and ensure a smoke tight seal. 12.5 mm thick boards.
4. All joints, gaps or imperfections in the installed seal Fire & Sound classification
must be filled with Protecta® FR Acrylic on both
sides. PEX pipe-in-pipe ≤ Ø25mm
EI 90 C/C & E 90 C/C
5. Protecta® FR Board can be over-painted with most
emulsion or alkyd (gloss) paints. Plastic pipes PVC-U and PVC-C pipes ≤ Ø32mm with wall
All services and openings thickness 1.0-2.4mm EI 60 U/C & E 90 U/C
must be sealed with FR
Acrylic both sides PE, ABS and SAN+PVC pipes ≤ Ø32mm with wall
thickness 2.0-3.0mm EI 60 U/C & E 60 U/C

PP pipes ≤ Ø32mm with wall thickness 1.8-


2.2mm EI 60 U/C & E 120 U/C

Sound reduction (seal only) 52 dB

Minimum separations and limitations

An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 25mm
from seal edges. Services within the system Protecta® FR Board seal do not require a minimum
separation, except pipes where pipe insulation penetrates the seal and plastic pipe penetrations
which should be a minimum of 30 mm from other services in the aperture. The total amount of cross Polyseam Ltd, 15 St Andrews Road,
sections of services (including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
ETA 13/0673 & 18/0855
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 5/3/19
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 209
Client:
Installation Instructions

1. Before installing Protecta® FR Board ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants, Maximum aperture
dust and grease. unlimited width by Products Protecta FR Board
2. The coated side of the board should be flush with the 1200mm high Protecta FR Acrylic
surface of the drywall on both sides. Protecta FR Pipe Wrap
2 layers 50mm
3. Cut the required board(s) to suit the aperture FR Board 1-S
dimensions and type and size of service Application Fire stopping of PEX pipe-in-
penetration(s). All exposed and cut edges of the pipes in flexible walls
board can be sealed with Protecta® FR Coating or Protecta Pipe Wrap 2
Protecta® FR Acrylic prior to fitting which will act as layers of 50mm wide Construction Minimum wall thickness of 100
an adhesive and ensure a smoke tight seal. fitted both sides mm and comprise steel studs
4. All joints, gaps or imperfections in the installed seal or timber studs* lined on both
must be filled with Protecta® FR Acrylic on both faces with minimum 2 layers of
sides. 12.5 mm thick boards.
5. Protecta® FR Board can be over-painted with most
Fire & Sound classification
emulsion or alkyd (gloss) paints. All services and openings
PEX pipe-
in-pipes must be sealed with FR PEX pipe-in-pipes ≤ Ø54mm
Acrylic both sides EI 120 C/C & E 120 C/C

PEX pipe-in-pipes ≤ Ø25mm in bundles


≤ Ø50mm
EI 90 C/C & E 90 C/C

Sound reduction (seal only) 52 dB

Minimum separations and limitations

An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 25mm
from seal edges. Services within the system Protecta® FR Board seal do not require a minimum
separation, except pipes where pipe insulation penetrates the seal and plastic pipe penetrations Polyseam Ltd, 15 St Andrews Road,
which should be a minimum of 30 mm from other services in the aperture. The total amount of cross
Huddersfield, West Yorkshire, HD1 6SB
sections of services (including insulation) should not exceed 60% of the penetration area.
ETA 13/0673 & 18/0855 Tel: +44 (0) 148 4421036
For all technical details on the products specified Email: post.uk@polyseam.com
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu Sheet size: Drawn date & no:
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
Signed and approved: A4 5/3/19
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 210
Client:
Installation Instructions Maximum aperture 2 layers 50mm
unlimited width by FR Board 1-S
1. Before installing Protecta® FR Board ensure that the
surface of all service penetrations and surrounding
1200mm high Job Title:
construction is free from all loose contaminants, Protecta Pipe Wrap
dust and grease. fitted both sides
Products Protecta FR Board
2. The coated side of the board should be flush with the Protecta FR Acrylic
surface of the drywall on both sides. Protecta FR Pipe Wrap 25m
3. Cut the required board(s) to suit the aperture
dimensions and type and size of service Application Fire stopping of plastic pipes in
penetration(s). All exposed and cut edges of the flexible walls
Plastic pipes All services and openings
board can be sealed with Protecta® FR Coating or
Protecta® FR Acrylic prior to fitting which will act as must be sealed with FR Construction Minimum wall thickness of 100
an adhesive and ensure a smoke tight seal. Acrylic both sides mm and comprise steel studs
4. All joints, gaps or imperfections in the installed seal or timber studs* lined on both
must be filled with Protecta® FR Acrylic on both faces with minimum 2 layers of
sides. 12.5 mm thick boards
Services Pipe Wall Thickness FR Pipe Wrap Classification
5. Protecta® FR Board can be over-painted with most ≤ Ø 40mm PVC-U & PVC-C 1.9 – 3.0mm 50 x 1.8mm (1 layer) EI 120 U/U (E 120 U/U)
Fire & Sound classification
emulsion or alkyd (gloss) paints. ≤ Ø 40mm PE, ABS & SAN+PVC 2.4 – 3.7mm 50 x 1.8mm (1 layer) EI 120 U/U (E 120 U/U)
≤ Ø 40mm PP 1.8 – 5.5mm 50 x 1.8mm (1 layer) EI 120 U/U (E 120 U/U)
≤ Ø 110mm PVC-U & PVC-C 2.7 – 6.6mm 50 x 3.6mm (2 layers) EI 90 U/C (E 120 U/C) For fire classifications please see the table on
≤ Ø 110mm PE, ABS & SAN+PVC 4.2 – 10.0mm 50 x 3.6mm (2 layers) EI 90 U/C (E 120 U/C) the left.
≤ Ø 110mm PP 2.7 – 15.1mm 50 x 3.6mm (2 layers) EI 90 U/U (E 90 U/U)
≤ Ø 125mm PVC-U & PVC-C 3.7 – 7.4mm 50 x 5.4mm (3 layers) EI 90 U/C (E 120 U/C) Sound reduction (seal only)
≤ Ø 125mm PE, ABS & SAN+PVC 4.8 – 12.0mm 50 x 5.4mm (3 layers) EI 90 U/C (E 120 U/C) 52 dB
≤ Ø 125mm PP 3.1 – 17.1mm 50 x 5.4mm (3 layers) EI 90 U/C (E 120 U/C)
≤ Ø 160mm PVC-U & PVC-C 9.5mm 50 x 7.2mm (4 layers) EI 90 U/C (E 120 U/C)
≤ Ø 160mm PE, ABS & SAN+PVC 14.6mm 50 x 7.2mm (4 layers) EI 90 U/C (E 120 U/C)
≤ Ø 160mm PP 21.9mm 50 x 7.2mm (4 layers) EI 90 U/C (E 120 U/C)
≤ Ø 200mm PVC-U & PVC-C 9.0 – 10.2mm 50 x 18.0mm (10 layers) EI 90 C/C (E 90 C/C)
≤ Ø 250mm PVC-U & PVC-C 8.5 – 11.0mm 50 x 18.0mm (10 layers) EI 90 C/C (E 90 C/C)
≤ Ø 315mm PVC-U & PVC-C 7.7 – 12.1mm 50 x 18.0mm (10 layers) EI 90 C/C (E 90 C/C)
≤ Ø 400mm PVC-U & PVC-C 9.8 – 15.3mm 50 x 28.8mm (16 layers) EI 90 C/C (E 90 C/C)

Minimum separations and limitations An aperture can include several services, and they may also be
different. The minimum permitted separation between adjacent seals/apertures is 200mm. Services
should be a minimum of 25mm from seal edges. Services within the system Protecta® FR Board seal
do not require a minimum separation, except pipes where pipe insulation penetrates the seal and
plastic pipe penetrations which should be a minimum of 30 mm from other services in the aperture. Polyseam Ltd, 15 St Andrews Road,
ETA 13/0673 & 18/0855 The total amount of cross sections of services should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 5/3/19
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 211
Client:
Installation Instructions Maximum aperture 2 layers 50mm
unlimited width by FR Board 1-S
1. Before installing Protecta® FR Board ensure that the
surface of all service penetrations and surrounding
1200mm high Job Title:
construction is free from all loose contaminants, Protecta Pipe Wrap
dust and grease. fitted both sides
Products Protecta FR Board
2. The coated side of the board should be flush with the Protecta FR Acrylic
surface of the drywall on both sides. Protecta FR Pipe Wrap 25m
3. Cut the required board(s) to suit the aperture
dimensions and type and size of service Application Fire stopping of composite
penetration(s). All exposed and cut edges of the plastic pipes in flexible walls
board can be sealed with Protecta® FR Coating or Composite All services and openings
Protecta® FR Acrylic prior to fitting which will act as plastic pipes must be sealed with FR Construction Minimum wall thickness of 100
an adhesive and ensure a smoke tight seal. Acrylic both sides mm and comprise steel studs
4. All joints, gaps or imperfections in the installed seal or timber studs* lined on both
must be filled with Protecta® FR Acrylic on both faces with minimum 2 layers of
sides. 12.5 mm thick boards
Services FR Pipe Wrap Classification
5. Protecta® FR Board can be over-painted with most Ø 32mm Aquatherm Green SDR9 pipes 50 x 1.8mm (1 layer) EI 90 C/C (E 120 C/C)
Fire & Sound classification
emulsion or alkyd (gloss) paints. ≤ Ø 110mm Aquatherm Green SDR9 pipes 50 x 3.6mm (2 layers) EI 90 C/C (E 120 C/C)
≤ Ø 50mm BluePower pipes 50 x 3.6mm (2 layers) EI 90 U/U (E 90 U/U)
≤ Ø 110mm BluePower pipes 50 x 3.6mm (2 layers) EI 90 C/U (E 90 C/U) For fire classifications please see the table on
≤ Ø 50mm Geberit Silent-PP pipes 50 x 3.6mm (2 layers) EI 120 U/U (E 120 U/U) the left.
≤ Ø 110mm Geberit Silent-PP pipes 50 x 3.6mm (2 layers) EI 120 U/C (E 120 U/C)
≤ Ø 50mm Polo-Kal NG pipes 50 x 3.6mm (2 layers) EI 120 U/U (E 120 U/U) Sound reduction (seal only)
≤ Ø 110mm Polo-Kal NG pipes 50 x 3.6mm (2 layers) EI 120 U/C (E 120 U/C) 52 dB
Ø 125mm Polo-Kal NG pipes 50 x 7.2mm (4 layers) EI 120 U/C (E 120 U/C)
Ø 160mm Polo-Kal NG pipes 50 x 10.8mm (6 layers) EI 120 U/C (E 120 U/C)
≤ Ø 50mm Rehau Raupiano Plus pipes 50 x 3.6mm (2 layers) EI 120 U/U (E 120 U/U)
≤ Ø 110mm Rehau Raupiano Plus pipes 50 x 3.6mm (2 layers) EI 120 U/C (E 120 U/C)
Ø 125mm Rehau Raupiano Plus pipes 50 x 7.2mm (4 layers) EI 120 U/C (E 120 U/C)
Ø 160mm Rehau Raupiano Plus pipes 50 x 10.8mm (6 layers) EI 120 U/C (E 120 U/C)
≤ Ø 50mm Wavin SiTech pipes 50 x 3.6mm (2 layers) EI 90 U/U (E 120 U/U)
≤ Ø 110mm Wavin SiTech pipes 50 x 3.6mm (2 layers) EI 60 U/C (E 120 U/C)

Minimum separations and limitations An aperture can include several services, and they may also be
different. The minimum permitted separation between adjacent seals/apertures is 200mm. Services
should be a minimum of 25mm from seal edges. Services within the system Protecta® FR Board seal
do not require a minimum separation, except pipes where pipe insulation penetrates the seal and
plastic pipe penetrations which should be a minimum of 30 mm from other services in the aperture. Polyseam Ltd, 15 St Andrews Road,
ETA 13/0673 & 18/0855 The total amount of cross sections of services should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 5/3/19
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 212
Client:
Installation Instructions

1. Before installing Protecta® FR Board ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants, Maximum aperture
dust and grease. unlimited width by Products Protecta FR Board
2. The coated side of the board should be flush with the 1200mm high Protecta FR Acrylic
surface of the drywall on both sides. Protecta FR Pipe Wrap
2 layers 50mm
3. Cut the required board(s) to suit the aperture FR Board 1-S Application Fire stopping of conduits in
dimensions and type and size of service flexible walls
penetration(s). All exposed and cut edges of the Construction Minimum wall thickness of 100
board can be sealed with Protecta® FR Coating or Protecta Pipe Wrap 2 mm and comprise steel studs
Protecta® FR Acrylic prior to fitting which will act as Cables layers of 50mm wide or timber studs* lined on both
an adhesive and ensure a smoke tight seal. ≤ Ø14mm fitted both sides faces with minimum 2 layers of
4. All joints, gaps or imperfections in the installed seal single or in 12.5 mm thick boards.
must be filled with Protecta® FR Acrylic on both a bundle Fire & Sound classification
sides.
Conduits of PVC-U & PVC-C pipe ≤ Ø110mm
5. Protecta® FR Board can be over-painted with most
with wall thickness 2.7-6.6mm
emulsion or alkyd (gloss) paints. All services and openings
Plastic pipes EI 90 U/C & E 120 U/C
must be sealed with FR
Acrylic both sides Conduits of PE, ABS & SAN+PVC pipes
≤ Ø110mm with wall thickness 4.2-10.0mm
EI 90 U/C & E 120 U/C

Conduits of PP pipe ≤ Ø110mm with wall


thickness 2.7-15.1mm EI 90 U/C & E 120 U/C

Sound reduction (seal only) 52 dB

Minimum separations and limitations

An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 25mm
from seal edges. Services within the system Protecta® FR Board seal do not require a minimum
separation, except pipes where pipe insulation penetrates the seal and plastic pipe penetrations Polyseam Ltd, 15 St Andrews Road,
which should be a minimum of 30 mm from other services in the aperture. The total amount of cross
Huddersfield, West Yorkshire, HD1 6SB
sections of services (including insulation) should not exceed 60% of the penetration area.
ETA 13/0673 & 18/0855 Tel: +44 (0) 148 4421036
For all technical details on the products specified Email: post.uk@polyseam.com
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu Sheet size: Drawn date & no:
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
Signed and approved: A4 5/3/19
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 213
Client:
Installation Instructions

1. Before installing Protecta® FR Board ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants, Maximum aperture
dust and grease. unlimited width by
1200mm high Products Protecta FR Board
2. Protecta® FR Coating and Protecta® FR Acrylic are Protecta FR Acrylic
water based, so in cases where corrosion protection 2 layers 50mm
Protecta FR Damper
is a problem, some metals may require a barrier FR Board 1-S
Application Fire stopping of ventilation
between the seal and the surface prior to this Protecta FR ducts in flexible walls
installation. Damper 30mm stone wool Construction Minimum wall thickness of 100
3. The coated side of the board should be flush with the matt mm and comprise steel studs
surface of the drywall on both sides. Ventilation or timber studs* lined on both
4. Cut the required board(s) to suit the aperture duct faces with minimum 2 layers of
dimensions and type and size of service 12.5 mm thick boards
penetration(s). All exposed and cut edges of the Fire & Sound classification
board can be sealed with Protecta® FR Coating or
Protecta® FR Acrylic prior to fitting which will act as ≤ Ø 400mm damper/duct with ≥ 200mm stone
an adhesive and ensure a smoke tight seal. wool matt on both sides EI 120 & E 120
5. All joints, gaps or imperfections in the installed seal ≤ Ø 1250mm damper/duct with ≥ 500mm stone
wool matt on both sides EI 60 & E 90
must be filled with Protecta® FR Acrylic on both
≤ 600mm high x 1000mm wide damper/duct
sides.
All services and openings with ≥ 500mm stone wool matt on both sides
6. Insulate the ventilation duct towards the fire seal on EI 120 & E 120
must be sealed with FR
both sides with 30mm thick stone wool matting to ≤ 1200mm high x 1700mm wide damper/duct
Acrylic both sides
the length given on this page. Insulate on one side with ≥ 500mm stone wool matt on both sides
only if the duct terminates in the wall. EI 90 & E 90
7. Protecta® FR Board can be over-painted with most
emulsion or alkyd (gloss) paints. Sound reduction (seal only) 52 dB

Minimum separations and limitations

An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 25mm
from seal edges. Services within the system Protecta® FR Board seal do not require a minimum
separation, except pipes where pipe insulation penetrates the seal and plastic pipe penetrations
which should be a minimum of 30 mm from other services in the aperture. The total amount of cross Polyseam Ltd, 15 St Andrews Road,
This product is certified to applicable European (EN)
standards and UL-EU Mark service requirements.
sections of services (including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 27/7/17
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 214
Client:
Installation Instructions

1. Before installing Protecta® FR Board ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants, Maximum aperture
dust and grease. 1200mm wide by
600mm high Products Protecta FR Board
2. The board can be positioned to either side of the Protecta FR Acrylic
construction or anywhere in between. Protecta FR ServiceCoat FR-1
3. Cut the required board(s) to suit the aperture
dimensions and type and size of service 1 layer 50mm Application Fire stopping of cables on cable
penetration(s). All exposed and cut edges of the Cables on FR Board 2-S trays in rigid walls
board can be sealed with Protecta® FR Coating or perforated cable
Protecta® FR Acrylic prior to fitting which will act as trays and ladders Construction Minimum wall thickness of 100
an adhesive and ensure a smoke tight seal. mm and comprise concrete,
4. All joints, gaps or imperfections in the installed seal aerated concrete or masonry,
must be filled with Protecta® FR Acrylic on both with a density of ≥ 650 kg/m3
sides.
5. All cables and cable trays must be coated 150mm All services and openings
Fire & Sound classification
each side with 300μ WFT Protecta Service Coat FR-1. must be sealed with FR All services must
6. Protecta® FR Board can be over-painted with most Acrylic both sides be coated with Cables ≤ Ø80mm single or bundled on
emulsion or alkyd (gloss) paints. Service Coat FR-1 perforated cable trays and ladders
both sides EI 60 & E 60

Sound reduction (seal only)


29 dB

Minimum separations and limitations

An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 25mm
from seal edges. Services within the system Protecta® FR Board seal do not require a minimum
separation, except pipes where pipe insulation penetrates the seal and plastic pipe penetrations
which should be a minimum of 30 mm from other services in the aperture. The total amount of cross Polyseam Ltd, 15 St Andrews Road,
sections of services (including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
ETA 13/0673 & 18/0855
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 26/7/17
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 215
Client:
Installation Instructions

1. Before installing Protecta® FR Board ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants, Maximum aperture
dust and grease. unlimited width by
1200mm high Products Protecta FR Board
2. The board can be positioned to either side of the Protecta FR Acrylic
construction or anywhere in between.
3. Cut the required board(s) to suit the aperture Application Fire stopping of cables in rigid
dimensions and type and size of service walls
penetration(s). All exposed and cut edges of the
1 layer 60mm
board can be sealed with Protecta® FR Coating or Construction Minimum wall thickness of 150
FR Board 2-S
Protecta® FR Acrylic prior to fitting which will act as mm and comprise concrete,
Cables
an adhesive and ensure a smoke tight seal. aerated concrete or masonry,
4. All joints, gaps or imperfections in the installed seal All services and with a density of ≥ 650 kg/m3
must be filled with Protecta® FR Acrylic on both openings must
sides. be sealed with
FR Acrylic both Fire & Sound classification
5. Protecta® FR Board can be over-painted with most
emulsion or alkyd (gloss) paints. sides
Cables ≤ Ø21mm
EI 90 & E 240

Sound reduction (seal only)


29 dB

Minimum separations and limitations

An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 25mm
from seal edges. Services within the system Protecta® FR Board seal do not require a minimum
separation, except pipes where pipe insulation penetrates the seal and plastic pipe penetrations
which should be a minimum of 30 mm from other services in the aperture. The total amount of cross Polyseam Ltd, 15 St Andrews Road,
sections of services (including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
ETA 13/0673 & 18/0855
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 20/4/15
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 216
Client:
Installation Instructions

1. Before installing Protecta® FR Board ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants, Maximum aperture
dust and grease. unlimited width by
1200mm high Products Protecta FR Board
2. The boards should be flush with the surface of the Protecta FR Acrylic
construction on both sides to maximize the fire
resistance. If this is not possible, there should be an 2 layers 60mm
Application Fire stopping of cables and
air gap of at least 30mm between the boards. FR Board 2-S
conduits in rigid walls
3. Cut the required board(s) to suit the aperture
dimensions and type and size of service Construction Minimum wall thickness of 150
penetration(s). All exposed and cut edges of the mm and comprise concrete,
board can be sealed with Protecta® FR Coating or aerated concrete or masonry,
Protecta® FR Acrylic prior to fitting which will act as with a density of ≥ 650 kg/m3
an adhesive and ensure a smoke tight seal.
4. All joints, gaps or imperfections in the installed seal
Cables and Fire & Sound classification
must be filled with Protecta® FR Acrylic on both
conduits All services and
sides.
openings must Cables ≤ Ø21mm, single or in a bundle and PVC
5. Protecta® FR Board can be over-painted with most
conduits ≤ Ø16mm
emulsion or alkyd (gloss) paints. be sealed with
EI 120 & E 240
FR Acrylic both
sides
Cables ≤ Ø21mm and PVC conduits ≤ Ø16mm
EI 180 & E 240

Sound reduction (seal only)


52 dB

Minimum separations and limitations

An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 25mm
from seal edges. Services within the system Protecta® FR Board seal do not require a minimum
separation, except pipes where pipe insulation penetrates the seal and plastic pipe penetrations
which should be a minimum of 30 mm from other services in the aperture. The total amount of cross Polyseam Ltd, 15 St Andrews Road,
sections of services (including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
ETA 13/0673 & 18/0855
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 20/4/15
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 217
Client:
Installation Instructions

1. Before installing Protecta® FR Board ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants, Maximum aperture
dust and grease. unlimited width by
1200mm high Products Protecta FR Board
2. The boards should be flush with the surface of the Protecta FR Acrylic
construction on both sides to maximize the fire 2 layers 50mm
resistance. FR Board 1-S Application Fire stopping of cables, wires
3. Cut the required board(s) to suit the aperture and conduits on cable trays in
dimensions and type and size of service rigid walls
penetration(s). All exposed and cut edges of the
board can be sealed with Protecta® FR Coating or Construction Minimum wall thickness of 100
Protecta® FR Acrylic prior to fitting which will act as mm and comprise concrete,
an adhesive and ensure a smoke tight seal. aerated concrete or masonry,
4. All joints, gaps or imperfections in the installed seal with a density of ≥ 650 kg/m3
must be filled with Protecta® FR Acrylic on both
Cables, wires and Fire & Sound classification
sides.
5. Protecta® FR Board can be over-painted with most conduits on cable All services and
trays openings must Cables ≤ Ø80mm single or bundled, wires
emulsion or alkyd (gloss) paints.
185mm2 and steel or PVC conduits ≤ Ø16mm on
be sealed with
trays
FR Acrylic both
EI 60 & E 60
sides
Sound reduction (seal only)
52 dB

Minimum separations and limitations

An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 25mm
from seal edges. Services within the system Protecta® FR Board seal do not require a minimum
separation, except pipes where pipe insulation penetrates the seal and plastic pipe penetrations
which should be a minimum of 30 mm from other services in the aperture. The total amount of cross Polyseam Ltd, 15 St Andrews Road,
sections of services (including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
ETA 13/0673 & 18/0855
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 6/3/19
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 218
Client:
Installation Instructions

1. Before installing Protecta® FR Board ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants, Maximum aperture
dust and grease. unlimited width by
1200mm high Products Protecta FR Board
2. The boards should be flush with the surface of the Protecta FR Acrylic
construction on both sides to maximize the fire 2 layers 60mm
resistance. If this is not possible, there should be an FR Board 2-S Application Fire stopping of cables and
air gap of at least 30mm between the boards. conduits on cable trays in rigid
3. Cut the required board(s) to suit the aperture walls
dimensions and type and size of service
penetration(s). All exposed and cut edges of the Construction Minimum wall thickness of 150
board can be sealed with Protecta® FR Coating or mm and comprise concrete,
Protecta® FR Acrylic prior to fitting which will act as aerated concrete or masonry,
an adhesive and ensure a smoke tight seal. with a density of ≥ 650 kg/m3
4. All joints, gaps or imperfections in the installed seal
Cables and conduits Fire & Sound classification
must be filled with Protecta® FR Acrylic on both
on cable trays All services and
sides.
openings must Cables ≤ Ø21mm in tied bundles ≤ Ø100mm and
5. Protecta® FR Board can be over-painted with most
PVC conduits ≤ Ø16mm on ≤ 200 mm ladders or
emulsion or alkyd (gloss) paints. be sealed with
≤ 500 mm non-perforated trays
FR Acrylic both
EI 120 & E 180
sides
Cables ≤ Ø80mm, single, bundled and on trays
EI 60 & E 180

Sound reduction (seal only)


52 dB

Minimum separations and limitations

An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 25mm
from seal edges. Services within the system Protecta® FR Board seal do not require a minimum
separation, except pipes where pipe insulation penetrates the seal and plastic pipe penetrations
which should be a minimum of 30 mm from other services in the aperture. The total amount of cross Polyseam Ltd, 15 St Andrews Road,
ETA 13/0673 & 18/0855 sections of services (including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 20/4/15
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 219
Client:
Installation Instructions

1. Before installing Protecta® FR Board ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants, Maximum aperture
dust and grease. 600mm wide and 60mm FR Board
600mm high 2-S installed 30mm Products Protecta FR Board
2. Cut the required board(s) to suit the aperture Protecta FR Acrylic
dimensions and type and size of service into aperture both
Protecta FR Coating
penetration(s). All exposed and cut edges of the sides to achieve
board can be sealed with Protecta® FR Coating or total seal width of
Application Fire stopping of cables, wires
Protecta® FR Acrylic prior to fitting which will act as at least 210mm and conduits on cable trays in
an adhesive and ensure a smoke tight seal. rigid walls
3. All joints, gaps or imperfections in the installed seal
must be filled with Protecta® FR Acrylic on both Construction Minimum wall thickness of 150
sides. mm and comprise concrete,
4. Protecta® FR Board can be over-painted with most aerated concrete or masonry,
emulsion or alkyd (gloss) paints. with a density of ≥ 650 kg/m3
Cables, wires Fire & Sound classification
and conduits All services and
on cable trays openings must Cables ≤ Ø21mm in tied bundles ≤ Ø100mm on
be sealed with trays EI 240 & E 240

Board edges must FR Acrylic both


Cables ≤ Ø21mm, single, bundled and wires
be coated with FR sides
≤ 95mm2 on trays EI 120 & E 240
Coating both sides
Cables ≤ Ø80mm, single, bundled and wires
≤ 185mm2 on trays EI 60 & E 240

Sound reduction (seal only) 53 dB

Minimum separations and limitations

An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 25mm
from seal edges. Services within the system Protecta® FR Board seal do not require a minimum
separation, except pipes where pipe insulation penetrates the seal and plastic pipe penetrations
which should be a minimum of 30 mm from other services in the aperture. The total amount of cross Polyseam Ltd, 15 St Andrews Road,
ETA 13/0673 & 18/0855 sections of services (including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 20/4/15
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 220
Client:
Installation Instructions

1. Before installing Protecta® FR Board ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants, Maximum aperture
dust and grease. 600mm wide and
600mm high Products Protecta FR Board
2. Cut the required board(s) to suit the aperture Protecta FR Acrylic
dimensions and type and size of service 60mm FR Board 2-S Protecta FR Coating
penetration(s). All exposed and cut edges of the oversailing aperture
board can be sealed with Protecta® FR Coating or by 50mm on both Application Fire stopping of cables, wires
Protecta® FR Acrylic prior to fitting which will act as sides and conduits on cable trays in
an adhesive and ensure a smoke tight seal. rigid walls
3. All joints, gaps or imperfections in the installed seal
must be filled with Protecta® FR Acrylic on both Construction Minimum wall thickness of 150
sides. mm and comprise concrete,
4. Protecta® FR Board can be over-painted with most aerated concrete or masonry,
emulsion or alkyd (gloss) paints. with a density of ≥ 650 kg/m3
Cables, wires Fire & Sound classification
and conduits All services and
on cable trays openings must Cables ≤ Ø21mm in tied bundles ≤ Ø100mm on
be sealed with trays EI 240 & E 240
FR Acrylic both
Cables ≤ Ø50mm, single, bundled and wires
Board edges must sides
≤ 185mm2 on trays EI 90 & E 240
be coated with FR
Coating both sides Fixed with 100mm Cables ≤ Ø80mm, single, bundled and on trays
long screws and EI 60 & E 240
penny washers at
350mm centres Sound reduction (seal only) 53 dB

Minimum separations and limitations

An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 25mm
from seal edges. Services within the system Protecta® FR Board seal do not require a minimum
separation, except pipes where pipe insulation penetrates the seal and plastic pipe penetrations
which should be a minimum of 30 mm from other services in the aperture. The total amount of cross Polyseam Ltd, 15 St Andrews Road,
ETA 13/0673 & 18/0855 sections of services (including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 20/4/15
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 221
Client:
Installation Instructions

1. Before installing Protecta® FR Board ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants, Maximum aperture
dust and grease. unlimited width by
1200mm high Products Protecta FR Board
2. Protecta® FR Coating and Protecta® FR Acrylic are Protecta FR Acrylic
water based, so in cases where corrosion protection
is a problem, some metals may require a barrier Application Fire stopping of un-insulated
between the seal and the surface prior to this 2 layers 50mm
steel pipes in rigid walls
installation. FR Board 1-S
3. The boards should be flush with the surface of the Construction Minimum wall thickness of 100
construction on both sides to maximize the fire mm and comprise concrete,
resistance. aerated concrete or masonry,
4. Cut the required board(s) to suit the aperture with a density of ≥ 650 kg/m3
dimensions and type and size of service
penetration(s). All exposed and cut edges of the All services and openings
board can be sealed with Protecta® FR Coating or Steel pipes must be sealed with FR Fire & Sound classification
Protecta® FR Acrylic prior to fitting which will act as Acrylic both sides
an adhesive and ensure a smoke tight seal.
Steel pipes ≤ Ø22mm
5. All joints, gaps or imperfections in the installed seal EI 60 C/U & E 120 C/U
must be filled with Protecta® FR Acrylic on both
sides. Steel pipes ≤ Ø114mm
6. Protecta® FR Board can be over-painted with most EI 20 C/U & E 90 C/U
emulsion or alkyd (gloss) paints.
Sound reduction (seal only)
52 dB

Minimum separations and limitations

An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 25mm
from seal edges. Services within the system Protecta® FR Board seal do not require a minimum
separation, except pipes where pipe insulation penetrates the seal and plastic pipe penetrations
which should be a minimum of 30 mm from other services in the aperture. The total amount of cross Polyseam Ltd, 15 St Andrews Road,
sections of services (including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
ETA 13/0673 & 18/0855
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 26/7/17
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 222
Client:
Installation Instructions

1. Before installing Protecta® FR Board ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants, Maximum aperture
dust and grease. unlimited width by
1200mm high Products Protecta FR Board
2. The board can be positioned to either side of the Protecta FR Acrylic
construction or anywhere in between. Protecta FR Pipe Wrap 25m
3. Cut the required board(s) to suit the aperture
dimensions and type and size of service Application Fire stopping of insulated steel
penetration(s). All exposed and cut edges of the Continuous pipes in rigid walls
Protecta Pipe Wrap 1
board can be sealed with Protecta® FR Coating or elastomeric or PE layer of 50mm wide
Protecta® FR Acrylic prior to fitting which will act as foam insulation Construction Minimum wall thickness of 150
an adhesive and ensure a smoke tight seal. mm and comprise concrete,
4. All joints, gaps or imperfections in the installed seal aerated concrete or masonry,
must be filled with Protecta® FR Acrylic on both with a density of ≥ 650 kg/m3
sides.
5. Protecta® FR Board can be over-painted with most Steel pipes
All services and openings Fire & Sound classification
emulsion or alkyd (gloss) paints.
must be sealed with FR
Acrylic both sides Steel pipes ≤ Ø165mm with 9 - 25mm
1 layer 60mm
continuous foam insulation
FR Board 2-S
EI 45 U/C & E 120 U/C

Sound reduction (seal only)


29 dB

Minimum separations and limitations

An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 25mm
from seal edges. Services within the system Protecta® FR Board seal do not require a minimum
separation, except pipes where pipe insulation penetrates the seal and plastic pipe penetrations
which should be a minimum of 30 mm from other services in the aperture. The total amount of cross Polyseam Ltd, 15 St Andrews Road,
sections of services (including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
ETA 13/0673 & 18/0855
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 5/3/19
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 223
Client:
Installation Instructions

1. Before installing Protecta® FR Board ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants, Maximum aperture
dust and grease. unlimited width by
1200mm high Products Protecta FR Board
2. The boards should be flush with the surface of the 2 layers 50mm Protecta FR Acrylic
construction on both sides to maximize the fire FR Board 1-S Protecta FR Pipe Wrap 25m
resistance. Application Fire stopping of insulated steel
3. Cut the required board(s) to suit the aperture pipes in rigid walls
Protecta Pipe Wrap of
dimensions and type and size of service Construction Minimum wall thickness of 100
Continuous 50mm wide fitted both
penetration(s). All exposed and cut edges of the mm and comprise concrete,
elastomeric or PE sides
board can be sealed with Protecta® FR Coating or aerated concrete or masonry,
foam insulation with a density of ≥ 650 kg/m3
Protecta® FR Acrylic prior to fitting which will act as
an adhesive and ensure a smoke tight seal. Fire & Sound classification
4. All joints, gaps or imperfections in the installed seal
must be filled with Protecta® FR Acrylic on both Steel pipes ≤ Ø40mm with 13mm continuous
foam insulation and 2 layers of pipe wrap
sides.
Steel pipes EI 120 U/U & E 120 U/U
5. Protecta® FR Board can be over-painted with most All services and openings
emulsion or alkyd (gloss) paints. must be sealed with FR Steel pipes ≤ Ø165mm with 13 - 32mm contin-
Acrylic both sides uous foam insulation and 2 layers of pipe wrap
EI 60 U/U & E 120 U/U

Steel pipes ≤ Ø324mm with 32 - 50mm contin-


uous foam insulation and 3 layers of pipe wrap
EI 90 C/U & E 90 C/U

Sound reduction (seal only) 52 dB

Minimum separations and limitations

An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 25mm
from seal edges. Services within the system Protecta® FR Board seal do not require a minimum
separation, except pipes where pipe insulation penetrates the seal and plastic pipe penetrations
which should be a minimum of 30 mm from other services in the aperture. The total amount of cross Polyseam Ltd, 15 St Andrews Road,
ETA 13/0673 & 18/0855 sections of services (including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 18/3/19
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 224
Client:
Installation Instructions

1. Before installing Protecta® FR Board ensure that the


surface of all service penetrations and surrounding
Job Title:
1 layer 50mm
construction is free from all loose contaminants, Maximum aperture FR Board 2-S
dust and grease. 1200mm wide by
600mm high Products Protecta FR Board
2. The board can be positioned to either side of the Protecta FR Acrylic
construction or anywhere in between.
3. Cut the required board(s) to suit the aperture Application Fire stopping of insulated steel
Continuous stone
dimensions and type and size of service pipes in rigid walls
wool insulation
penetration(s). All exposed and cut edges of the
≥ 80 kg/m3
board can be sealed with Protecta® FR Coating or Construction Minimum wall thickness of 100
Protecta® FR Acrylic prior to fitting which will act as mm and comprise concrete,
an adhesive and ensure a smoke tight seal. aerated concrete or masonry,
4. All joints, gaps or imperfections in the installed seal with a density of ≥ 650 kg/m3
must be filled with Protecta® FR Acrylic on both
sides. Steel pipes
5. Protecta® FR Board can be over-painted with most
Fire & Sound classification
emulsion or alkyd (gloss) paints.

All services and openings Steel pipes ≤ Ø324mm with 20-30mm


must be sealed with FR continuous stone wool insulation
Acrylic both sides EI 60 C/U & E 90 C/U

Sound reduction (seal only)


29 dB

Minimum separations and limitations

An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 25mm
from seal edges. Services within the system Protecta® FR Board seal do not require a minimum
separation, except pipes where pipe insulation penetrates the seal and plastic pipe penetrations
which should be a minimum of 30 mm from other services in the aperture. The total amount of cross Polyseam Ltd, 15 St Andrews Road,
sections of services (including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
ETA 13/0673 & 18/0855
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 20/4/15
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 225
Client:
Installation Instructions

1. Before installing Protecta® FR Board ensure that the


surface of all service penetrations and surrounding
Job Title:
1 layer 60mm
construction is free from all loose contaminants, Maximum aperture FR Board 2-S
dust and grease. unlimited width by
1200mm high Products Protecta FR Board
2. The board can be positioned to either side of the Protecta FR Acrylic
construction or anywhere in between.
3. Cut the required board(s) to suit the aperture Application Fire stopping of insulated steel
Continuous stone
dimensions and type and size of service pipes in rigid walls
wool insulation
penetration(s). All exposed and cut edges of the
≥ 80 kg/m3
board can be sealed with Protecta® FR Coating or Construction Minimum wall thickness of 150
Protecta® FR Acrylic prior to fitting which will act as mm and comprise concrete,
an adhesive and ensure a smoke tight seal. aerated concrete or masonry,
4. All joints, gaps or imperfections in the installed seal with a density of ≥ 650 kg/m3
must be filled with Protecta® FR Acrylic on both
sides. Steel pipes
Fire & Sound classification
5. Protecta® FR Board can be over-painted with most
emulsion or alkyd (gloss) paints.
Steel pipes ≤ Ø219mm with 30mm continuous
All services and openings stone wool insulation
must be sealed with FR EI 60 C/U & E 240 C/U
Acrylic both sides
Steel pipes Ø325mm with 30mm continuous
stone wool insulation
EI 90 C/U & E 120 C/U

Sound reduction (seal only)


29 dB

Minimum separations and limitations

An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 25mm
from seal edges. Services within the system Protecta® FR Board seal do not require a minimum
separation, except pipes where pipe insulation penetrates the seal and plastic pipe penetrations
which should be a minimum of 30 mm from other services in the aperture. The total amount of cross Polyseam Ltd, 15 St Andrews Road,
ETA 13/0673 & 18/0855 sections of services (including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 26/7/17
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 226
Client:
Installation Instructions

1. Before installing Protecta® FR Board ensure that the


surface of all service penetrations and surrounding
Job Title:
2 layers 50mm
construction is free from all loose contaminants, Maximum aperture FR Board 1-S
dust and grease. unlimited width by
1200mm high Products Protecta FR Board
2. Protecta® FR Coating and Protecta® FR Acrylic are Protecta FR Acrylic
water based, so in cases where corrosion protection
is a problem, some metals may require a barrier Application Fire stopping of insulated steel
Continuous stone
between the seal and the surface prior to this pipes in rigid walls
wool insulation
installation.
≥ 80 kg/m3
3. The boards should be flush with the surface of the Construction Minimum wall thickness of 100
construction on both sides to maximize the fire mm and comprise concrete,
resistance. aerated concrete or masonry,
4. Cut the required board(s) to suit the aperture with a density of ≥ 650 kg/m3
dimensions and type and size of service
penetration(s). All exposed and cut edges of the Steel pipes
board can be sealed with Protecta® FR Coating or
Fire & Sound classification
Protecta® FR Acrylic prior to fitting which will act as
an adhesive and ensure a smoke tight seal.
All services and openings Steel pipes ≤ Ø324mm with 20-80mm
5. All joints, gaps or imperfections in the installed seal continuous stone wool insulation
must be sealed with FR
must be filled with Protecta® FR Acrylic on both EI 120 C/U & E 120 C/U
Acrylic both sides
sides.
6. Protecta® FR Board can be over-painted with most Sound reduction (seal only)
emulsion or alkyd (gloss) paints. 52 dB

Minimum separations and limitations

An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 25mm
from seal edges. Services within the system Protecta® FR Board seal do not require a minimum
separation, except pipes where pipe insulation penetrates the seal and plastic pipe penetrations
which should be a minimum of 30 mm from other services in the aperture. The total amount of cross Polyseam Ltd, 15 St Andrews Road,
sections of services (including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
ETA 13/0673 & 18/0855
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 16/1/17
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 227
Client:
Installation Instructions

1. Before installing Protecta® FR Board ensure that the


surface of all service penetrations and surrounding
Job Title:
2 layers 60mm
construction is free from all loose contaminants, Maximum aperture FR Board 2-S
dust and grease. unlimited width by
1200mm high Products Protecta FR Board
2. Protecta® FR Coating and Protecta® FR Acrylic are Protecta FR Acrylic
water based, so in cases where corrosion protection
is a problem, some metals may require a barrier Application Fire stopping of insulated steel
Continuous stone
between the seal and the surface prior to this pipes in rigid walls
wool insulation
installation.
≥ 80 kg/m3
3. The boards should be flush with the surface of the Construction Minimum wall thickness of 150
construction on both sides to maximize the fire mm and comprise concrete,
resistance. If this is not possible, there should be an aerated concrete or masonry,
air gap of at least 30mm between the boards. with a density of ≥ 650 kg/m3
4. Cut the required board(s) to suit the aperture
dimensions and type and size of service Steel pipes
penetration(s). All exposed and cut edges of the
Fire & Sound classification
board can be sealed with Protecta® FR Coating or
Protecta® FR Acrylic prior to fitting which will act as
All services and openings Steel pipes ≤ Ø324mm with 20-80mm
an adhesive and ensure a smoke tight seal. continuous stone wool insulation
must be sealed with FR
5. All joints, gaps or imperfections in the installed seal EI 180 C/U & E 240 C/U
Acrylic both sides
must be filled with Protecta® FR Acrylic on both
sides. Sound reduction (seal only)
6. Protecta® FR Board can be over-painted with most 52 dB
emulsion or alkyd (gloss) paints.

Minimum separations and limitations

An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 25mm
from seal edges. Services within the system Protecta® FR Board seal do not require a minimum
separation, except pipes where pipe insulation penetrates the seal and plastic pipe penetrations
which should be a minimum of 30 mm from other services in the aperture. The total amount of cross Polyseam Ltd, 15 St Andrews Road,
sections of services (including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
ETA 13/0673 & 18/0855
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 9/1/17
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 228
Client:
Installation Instructions

1. Before installing Protecta® FR Board ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Board
2. Protecta® FR Coating and Protecta® FR Acrylic are Protecta FR Acrylic
water based, so in cases where corrosion protection Application Fire stopping of insulated steel
is a problem, some metals may require a barrier Stone wool ≥ 80 kg/m3 pipes in rigid walls
between the seal and the surface prior to this to be installed Construction Minimum wall thickness of 150
installation. ≥ 100cm on both sides mm and comprise concrete,
3. The board can be positioned to either side of the aerated concrete or masonry,
construction or anywhere in between. with a density of ≥ 650 kg/m3
4. Cut the required board(s) to suit the aperture Fire & Sound classification
dimensions and type and size of service
penetration(s). All exposed and cut edges of the Steel pipes ≤ Ø40mm with ≥ 20mm stone wool
board can be sealed with Protecta® FR Coating or Steel pipes insulation in maximum aperture 280mm wide
Protecta® FR Acrylic prior to fitting which will act as and 280mm high EI 240 C/U & E 240 C/U
an adhesive and ensure a smoke tight seal. Steel pipes ≤ Ø40mm with ≥ 20mm stone wool
All services and openings
5. All joints, gaps or imperfections in the installed seal insulation in maximum aperture unlimited
must be sealed with FR
1 layer 60mm width by 1200mm high EI 90 C/U & E 240 C/U
must be filled with Protecta® FR Acrylic on both Acrylic both sides
FR Board 2-S Steel pipes ≤ Ø219mm with ≥ 30mm stone wool
sides.
insulation in maximum aperture 280mm wide
6. Protecta® FR Board can be over-painted with most and 280mm high EI 240 C/U & E 240 C/U
emulsion or alkyd (gloss) paints. Steel pipes ≤ Ø219mm with ≥ 30mm stone wool
insulation in maximum aperture unlimited
width by 1200mm high EI 90 C/U & E 240 C/U

Sound reduction (seal only) 29 dB

Minimum separations and limitations

An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 25mm
from seal edges. Services within the system Protecta® FR Board seal do not require a minimum
separation, except pipes where pipe insulation penetrates the seal and plastic pipe penetrations
which should be a minimum of 30 mm from other services in the aperture. The total amount of cross Polyseam Ltd, 15 St Andrews Road,
ETA 13/0673 & 18/0855 sections of services (including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 20/4/15
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 229
Client:
Installation Instructions

1. Before installing Protecta® FR Board ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants, Maximum aperture
dust and grease. unlimited width by
2 layers 60mm Products Protecta FR Board
2. Protecta® FR Coating and Protecta® FR Acrylic are 1200mm high
FR Board 2-S Protecta FR Acrylic
water based, so in cases where corrosion protection
is a problem, some metals may require a barrier Application Fire stopping of insulated steel
between the seal and the surface prior to this Stone wool ≥ 80 kg/m3
pipes in rigid walls
installation. to be installed
≥ 100cm on both sides
3. The boards should be flush with the surface of the Construction Minimum wall thickness of 150
construction on both sides to maximize the fire mm and comprise concrete,
resistance. If this is not possible, there should be an aerated concrete or masonry,
air gap of at least 30mm between the boards. with a density of ≥ 650 kg/m3
4. Cut the required board(s) to suit the aperture
dimensions and type and size of service Fire & Sound classification
penetration(s). All exposed and cut edges of the Steel pipes
Steel pipes ≤ Ø40mm with ≥ 20mm stone wool
board can be sealed with Protecta® FR Coating or All services and openings insulation
Protecta® FR Acrylic prior to fitting which will act as must be sealed with FR EI 180 C/U & E 240 C/U
an adhesive and ensure a smoke tight seal. Acrylic both sides
5. All joints, gaps or imperfections in the installed seal Steel pipes ≤ Ø219mm with ≥ 30mm stone wool
must be filled with Protecta® FR Acrylic on both insulation
sides. EI 180 C/U & E 240 C/U
6. Protecta® FR Board can be over-painted with most
emulsion or alkyd (gloss) paints. Sound reduction (seal only)
52 dB

Minimum separations and limitations

An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 25mm
from seal edges. Services within the system Protecta® FR Board seal do not require a minimum
separation, except pipes where pipe insulation penetrates the seal and plastic pipe penetrations
which should be a minimum of 30 mm from other services in the aperture. The total amount of cross Polyseam Ltd, 15 St Andrews Road,
ETA 13/0673 & 18/0855 sections of services (including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 20/4/15
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 230
Client:
Installation Instructions

1. Before installing Protecta® FR Board ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants, Maximum aperture
dust and grease. unlimited width by
1200mm high Products Protecta FR Board
2. Protecta® FR Coating and Protecta® FR Acrylic are Protecta FR Acrylic
water based, so in cases where corrosion protection
is a problem, some metals may require a barrier Application Fire stopping of un-insulated
between the seal and the surface prior to this 2 layers 50mm
copper pipes in rigid walls
installation. FR Board 1-S
3. The boards should be flush with the surface of the Construction Minimum wall thickness of 100
construction on both sides to maximize the fire mm and comprise concrete,
resistance. aerated concrete or masonry,
4. Cut the required board(s) to suit the aperture with a density of ≥ 650 kg/m3
dimensions and type and size of service
penetration(s). All exposed and cut edges of the All services and openings
board can be sealed with Protecta® FR Coating or Copper pipes must be sealed with FR Fire & Sound classification
Protecta® FR Acrylic prior to fitting which will act as Acrylic both sides
an adhesive and ensure a smoke tight seal.
Copper pipes ≤ Ø6mm
5. All joints, gaps or imperfections in the installed seal EI 60 C/C & E 120 C/C
must be filled with Protecta® FR Acrylic on both
sides. Sound reduction (seal only)
6. Protecta® FR Board can be over-painted with most 52 dB
emulsion or alkyd (gloss) paints.

Minimum separations and limitations

An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 25mm
from seal edges. Services within the system Protecta® FR Board seal do not require a minimum
separation, except pipes where pipe insulation penetrates the seal and plastic pipe penetrations
which should be a minimum of 30 mm from other services in the aperture. The total amount of cross Polyseam Ltd, 15 St Andrews Road,
sections of services (including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
ETA 13/0673 & 18/0855
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 26/7/17
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 231
Client:
Installation Instructions

1. Before installing Protecta® FR Board ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants, Maximum aperture
dust and grease. unlimited width by
2 layers 50mm Products Protecta FR Board
2. The boards should be flush with the surface of the 1200mm high
FR Board 1-S Protecta FR Acrylic
construction on both sides to maximize the fire Protecta FR Pipe Wrap 25m
resistance. Application Fire stopping of insulated
3. Cut the required board(s) to suit the aperture Protecta Pipe Wrap 2
copper pipes in rigid walls
dimensions and type and size of service Continuous layers of 50mm wide
Construction Minimum wall thickness of 100
elastomeric or PE fitted both sides
penetration(s). All exposed and cut edges of the mm and comprise concrete,
board can be sealed with Protecta® FR Coating or foam insulation aerated concrete or masonry,
Protecta® FR Acrylic prior to fitting which will act as with a density of ≥ 650 kg/m3
an adhesive and ensure a smoke tight seal. Fire & Sound classification
4. All joints, gaps or imperfections in the installed seal
must be filled with Protecta® FR Acrylic on both Copper pipes ≤ Ø12mm with 9mm continuous
foam insulation EI 120 C/C & E 120 C/C
sides. Copper pipes
5. Protecta® FR Board can be over-painted with most All services and openings
must be sealed with FR Copper pipes ≤ Ø54mm with 9 - 13mm
emulsion or alkyd (gloss) paints.
Acrylic both sides continuous foam insulation
EI 90 C/C & E 120 C/C

Copper pipes ≤ Ø54mm with 14 - 25mm


continuous foam insulation
EI 60 C/C & E 120 C/C

Sound reduction (seal only) 52 dB

Minimum separations and limitations

An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 25mm
from seal edges. Services within the system Protecta® FR Board seal do not require a minimum
separation, except pipes where pipe insulation penetrates the seal and plastic pipe penetrations
which should be a minimum of 30 mm from other services in the aperture. The total amount of cross Polyseam Ltd, 15 St Andrews Road,
ETA 13/0673 & 18/0855 sections of services (including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 5/3/19
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 232
Client:
Installation Instructions

1. Before installing Protecta® FR Board ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Board
2. Protecta® FR Coating and Protecta® FR Acrylic are Protecta FR Acrylic
water based, so in cases where corrosion protection Application Fire stopping of insulated
is a problem, some metals may require a barrier Stone wool ≥ 80 kg/m3 copper pipes in rigid walls
between the seal and the surface prior to this to be installed Construction Minimum wall thickness of 150
installation. ≥ 100cm on both sides mm and comprise concrete,
3. The board can be positioned to either side of the aerated concrete or masonry,
construction or anywhere in between. with a density of ≥ 650 kg/m3
4. Cut the required board(s) to suit the aperture Fire & Sound classification
dimensions and type and size of service
penetration(s). All exposed and cut edges of the Copper pipes ≤ Ø12mm with ≥ 20mm stone
board can be sealed with Protecta® FR Coating or Copper pipes wool insulation in maximum aperture 70mm
Protecta® FR Acrylic prior to fitting which will act as wide and 70mm high EI 240 C/U & E 240 C/U
an adhesive and ensure a smoke tight seal. All services and openings
5. All joints, gaps or imperfections in the installed seal Copper pipes ≤ Ø54mm with ≥ 20mm stone
must be sealed with FR
1 layer 60mm wool insulation in maximum aperture 115mm
must be filled with Protecta® FR Acrylic on both Acrylic both sides
FR Board 2-S wide and 115mm high EI 120 C/U & E 240 C/U
sides.
6. Protecta® FR Board can be over-painted with most Copper pipes ≤ Ø54mm with ≥ 20mm stone
emulsion or alkyd (gloss) paints. wool insulation in maximum aperture unlimited
width by 1200mm high EI 90 C/U & E 240 C/U

Sound reduction (seal only) 29 dB

Minimum separations and limitations

An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 25mm
from seal edges. Services within the system Protecta® FR Board seal do not require a minimum
separation, except pipes where pipe insulation penetrates the seal and plastic pipe penetrations
which should be a minimum of 30 mm from other services in the aperture. The total amount of cross Polyseam Ltd, 15 St Andrews Road,
ETA 13/0673 & 18/0855 sections of services (including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 20/4/15
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 233
Client:
Installation Instructions

1. Before installing Protecta® FR Board ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants, Maximum aperture
dust and grease. unlimited width by
2 layers 60mm Products Protecta FR Board
2. Protecta® FR Coating and Protecta® FR Acrylic are 1200mm high
FR Board 2-S Protecta FR Acrylic
water based, so in cases where corrosion protection
is a problem, some metals may require a barrier Application Fire stopping of insulated
between the seal and the surface prior to this Stone wool ≥ 80 kg/m3
copper pipes in rigid walls
installation. to be installed
≥ 100cm on both sides
3. The boards should be flush with the surface of the Construction Minimum wall thickness of 150
construction on both sides to maximize the fire mm and comprise concrete,
resistance. If this is not possible, there should be an aerated concrete or masonry,
air gap of at least 30mm between the boards. with a density of ≥ 650 kg/m3
4. Cut the required board(s) to suit the aperture
dimensions and type and size of service
penetration(s). All exposed and cut edges of the Copper pipes
Fire & Sound classification
board can be sealed with Protecta® FR Coating or All services and openings
Protecta® FR Acrylic prior to fitting which will act as must be sealed with FR Copper pipes ≤ Ø54mm with ≥ 20mm stone
an adhesive and ensure a smoke tight seal. Acrylic both sides wool insulation
5. All joints, gaps or imperfections in the installed seal EI 120 C/U & E 240 C/U
must be filled with Protecta® FR Acrylic on both
sides. Sound reduction (seal only)
6. Protecta® FR Board can be over-painted with most 52 dB
emulsion or alkyd (gloss) paints.

Minimum separations and limitations

An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 25mm
from seal edges. Services within the system Protecta® FR Board seal do not require a minimum
separation, except pipes where pipe insulation penetrates the seal and plastic pipe penetrations
which should be a minimum of 30 mm from other services in the aperture. The total amount of cross Polyseam Ltd, 15 St Andrews Road,
sections of services (including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
ETA 13/0673 & 18/0855
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 20/4/15
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 234
Client:
Installation Instructions

1. Before installing Protecta® FR Board ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants, Maximum aperture
dust and grease. unlimited width by
1200mm high Products Protecta FR Board
2. Protecta® FR Coating and Protecta® FR Acrylic are Protecta FR Acrylic
water based, so in cases where corrosion protection
is a problem, some metals may require a barrier Application Fire stopping of un-insulated
between the seal and the surface prior to this 2 layers 50mm
alupex pipes in rigid walls
installation. FR Board 1-S
3. The boards should be flush with the surface of the Construction Minimum wall thickness of 100
construction on both sides to maximize the fire mm and comprise concrete,
resistance. aerated concrete or masonry,
4. Cut the required board(s) to suit the aperture with a density of ≥ 650 kg/m3
dimensions and type and size of service
penetration(s). All exposed and cut edges of the All services and openings
board can be sealed with Protecta® FR Coating or Alupex pipes
must be sealed with FR Fire & Sound classification
Protecta® FR Acrylic prior to fitting which will act as Acrylic both sides
an adhesive and ensure a smoke tight seal.
Alupex pipes ≤ Ø20mm
5. All joints, gaps or imperfections in the installed seal EI 120 C/C & E 120 C/C
must be filled with Protecta® FR Acrylic on both
sides. Sound reduction (seal only)
6. Protecta® FR Board can be over-painted with most 52 dB
emulsion or alkyd (gloss) paints.

Minimum separations and limitations

An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 25mm
from seal edges. Services within the system Protecta® FR Board seal do not require a minimum
separation, except pipes where pipe insulation penetrates the seal and plastic pipe penetrations
which should be a minimum of 30 mm from other services in the aperture. The total amount of cross Polyseam Ltd, 15 St Andrews Road,
sections of services (including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
ETA 13/0673 & 18/0855
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 26/7/17
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 235
Client:
Installation Instructions

1. Before installing Protecta® FR Board ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants, Maximum aperture
dust and grease. unlimited width by
1200mm high 2 layers 50mm Products Protecta FR Board
2. The boards should be flush with the surface of the Protecta FR Acrylic
construction on both sides to maximize the fire FR Board 1-S
Protecta FR Pipe Wrap 25m
resistance.
3. Cut the required board(s) to suit the aperture Protecta Pipe Wrap 2 Application Fire stopping of insulated
dimensions and type and size of service Continuous layers of 50mm wide alupex pipes in rigid walls
penetration(s). All exposed and cut edges of the elastomeric or PE fitted both sides
board can be sealed with Protecta® FR Coating or foam insulation Construction Minimum wall thickness of 100
Protecta® FR Acrylic prior to fitting which will act as mm and comprise concrete,
an adhesive and ensure a smoke tight seal. aerated concrete or masonry,
4. All joints, gaps or imperfections in the installed seal with a density of ≥ 650 kg/m3
must be filled with Protecta® FR Acrylic on both
sides.
Alupex pipes All services and openings Fire & Sound classification
5. Protecta® FR Board can be over-painted with most
emulsion or alkyd (gloss) paints. must be sealed with FR
Acrylic both sides Alupex pipes ≤ Ø75mm with 9 - 25mm
continuous foam insulation
EI 120 C/C & E 120 C/C

Sound reduction (seal only)


52 dB

Minimum separations and limitations

An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 25mm
from seal edges. Services within the system Protecta® FR Board seal do not require a minimum
separation, except pipes where pipe insulation penetrates the seal and plastic pipe penetrations
which should be a minimum of 30 mm from other services in the aperture. The total amount of cross Polyseam Ltd, 15 St Andrews Road,
sections of services (including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
ETA 13/0673 & 18/0855
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 5/3/19
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 236
Client:
Installation Instructions

1. Before installing Protecta® FR Board ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease.
Products Protecta FR Board
2. Protecta® FR Coating and Protecta® FR Acrylic are Protecta FR Acrylic
water based, so in cases where corrosion protection
is a problem, some metals may require a barrier Stone wool ≥ 80 kg/m3 Application Fire stopping of insulated
between the seal and the surface prior to this to be installed ≥ 60cm alupex pipes in rigid walls
installation. on both sides
3. The board can be positioned to either side of the Construction Minimum wall thickness of 150
construction or anywhere in between. mm and comprise concrete,
4. Cut the required board(s) to suit the aperture aerated concrete or masonry,
dimensions and type and size of service with a density of ≥ 650 kg/m3
penetration(s). All exposed and cut edges of the
board can be sealed with Protecta® FR Coating or Alupex pipes
Fire & Sound classification
Protecta® FR Acrylic prior to fitting which will act as
an adhesive and ensure a smoke tight seal. All services and openings Alupex pipes ≤ Ø75mm with ≥ 30mm stone
5. All joints, gaps or imperfections in the installed seal must be sealed with FR wool insulation in maximum aperture 200mm
must be filled with Protecta® FR Acrylic on both 1 layer 60mm Acrylic both sides wide and 200mm high EI 120 C/C & E 120 C/C
sides. FR Board 2-S
6. Protecta® FR Board can be over-painted with most Alupex pipes ≤ Ø75mm with ≥ 30mm stone
emulsion or alkyd (gloss) paints. wool insulation in maximum aperture unlimited
width by 1200mm high EI 90 C/C & E 120 C/C

Sound reduction (seal only) 29 dB

Minimum separations and limitations

An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 25mm
from seal edges. Services within the system Protecta® FR Board seal do not require a minimum
separation, except pipes where pipe insulation penetrates the seal and plastic pipe penetrations
which should be a minimum of 30 mm from other services in the aperture. The total amount of cross Polyseam Ltd, 15 St Andrews Road,
ETA 13/0673 & 18/0855 sections of services (including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 20/4/15
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 237
Client:
Installation Instructions

1. Before installing Protecta® FR Board ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants,
dust and grease. 2 layers 60mm Products Protecta FR Board
2. Protecta® FR Coating and Protecta® FR Acrylic are FR Board 2-S Protecta FR Acrylic
water based, so in cases where corrosion protection Application Fire stopping of insulated
is a problem, some metals may require a barrier alupex pipes in rigid walls
between the seal and the surface prior to this Stone wool ≥ 80 kg/m3
Construction Minimum wall thickness of 150
installation. to be installed ≥ 60cm
mm and comprise concrete,
on both sides
3. The boards should be flush with the surface of the aerated concrete or masonry,
construction on both sides to maximize the fire with a density of ≥ 650 kg/m3
resistance. If this is not possible, there should be an
air gap of at least 30mm between the boards. Fire & Sound classification
4. Cut the required board(s) to suit the aperture
Alupex pipes ≤ Ø16mm with ≥ 30mm stone
dimensions and type and size of service
Alupex pipes wool insulation in maximum aperture 1200mm
penetration(s). All exposed and cut edges of the
wide and 1200mm high EI 240 U/C & E 240 U/C
board can be sealed with Protecta® FR Coating or All services and openings
Protecta® FR Acrylic prior to fitting which will act as must be sealed with FR Alupex pipes ≤ Ø16mm with ≥ 30mm stone
an adhesive and ensure a smoke tight seal. Acrylic both sides wool insulation in maximum aperture unlimited
5. All joints, gaps or imperfections in the installed seal width by 1200mm high EI 180 U/C & E 240 U/C
must be filled with Protecta® FR Acrylic on both
sides. Alupex pipes ≤ Ø75mm with ≥ 30mm stone
6. Protecta® FR Board can be over-painted with most wool insulation in maximum aperture unlimited
emulsion or alkyd (gloss) paints. width by 1200mm high EI 120 C/C & E 120 C/C

Sound reduction (seal only) 52 dB

Minimum separations and limitations

An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 25mm
from seal edges. Services within the system Protecta® FR Board seal do not require a minimum
separation, except pipes where pipe insulation penetrates the seal and plastic pipe penetrations
which should be a minimum of 30 mm from other services in the aperture. The total amount of cross Polyseam Ltd, 15 St Andrews Road,
sections of services (including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
ETA 13/0673 & 18/0855
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 20/4/15
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 238
Client:
Installation Instructions

1. Before installing Protecta® FR Board ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants, Maximum aperture
dust and grease. unlimited width by
1200mm high Products Protecta FR Board
2. The boards should be flush with the surface of the Protecta FR Acrylic
construction on both sides to maximize the fire Application Fire stopping of plastic pipes in
resistance. 2 layers 50mm rigid walls
3. Cut the required board(s) to suit the aperture FR Board 1-S Construction Minimum wall thickness of 100
dimensions and type and size of service mm and comprise concrete,
penetration(s). All exposed and cut edges of the aerated concrete or masonry,
board can be sealed with Protecta® FR Coating or with a density of ≥ 650 kg/m3
Protecta® FR Acrylic prior to fitting which will act as
an adhesive and ensure a smoke tight seal. Fire & Sound classification
4. All joints, gaps or imperfections in the installed seal
must be filled with Protecta® FR Acrylic on both PEX pipe-in-pipe ≤ Ø25mm
Plastic pipes EI 90 C/C & E 90 C/C
sides.
5. Protecta® FR Board can be over-painted with most
PVC-U and PVC-C pipes ≤ Ø32mm with wall
emulsion or alkyd (gloss) paints.
thickness 1.0-2.4mm EI 60 U/C & E 90 U/C
All services and openings
must be sealed with FR PE, ABS and SAN+PVC pipes ≤ Ø32mm with wall
Acrylic both sides thickness 2.0-3.0mm EI 60 U/C & E 60 U/C

PP pipes ≤ Ø32mm with wall thickness 1.8-


2.2mm EI 60 U/C & E 120 U/C

Sound reduction (seal only) 52 dB

Minimum separations and limitations

An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 25mm
from seal edges. Services within the system Protecta® FR Board seal do not require a minimum
separation, except pipes where pipe insulation penetrates the seal and plastic pipe penetrations
which should be a minimum of 30 mm from other services in the aperture. The total amount of cross Polyseam Ltd, 15 St Andrews Road,
ETA 13/0673 & 18/0855 sections of services (including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 5/3/19
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 239
Client:
Installation Instructions

1. Before installing Protecta® FR Board ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants, Maximum aperture
dust and grease. unlimited width by Products Protecta FR Board
2. The boards should be flush with the surface of the 1200mm high Protecta FR Acrylic
construction on both sides to maximize the fire 2 layers 50mm
Protecta FR Pipe Wrap
resistance. FR Board 1-S
3. Cut the required board(s) to suit the aperture Application Fire stopping of PEX pipe-in-
dimensions and type and size of service Protecta Pipe Wrap 2 pipes in rigid walls
penetration(s). All exposed and cut edges of the layers of 50mm wide
board can be sealed with Protecta® FR Coating or fitted both sides Construction Minimum wall thickness of 100
Protecta® FR Acrylic prior to fitting which will act as mm and comprise concrete,
an adhesive and ensure a smoke tight seal. aerated concrete or masonry,
4. All joints, gaps or imperfections in the installed seal with a density of ≥ 650 kg/m3
must be filled with Protecta® FR Acrylic on both
Fire & Sound classification
sides.
5. Protecta® FR Board can be over-painted with most
PEX pipe- PEX pipe-in-pipes ≤ Ø54mm
emulsion or alkyd (gloss) paints. All services and openings EI 120 C/C & E 120 C/C
in-pipes
must be sealed with FR
Acrylic both sides PEX pipe-in-pipes ≤ Ø25mm in bundles
≤ Ø50mm
EI 90 C/C & E 90 C/C

Sound reduction (seal only)


52 dB

Minimum separations and limitations

An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 25mm
from seal edges. Services within the system Protecta® FR Board seal do not require a minimum
separation, except pipes where pipe insulation penetrates the seal and plastic pipe penetrations Polyseam Ltd, 15 St Andrews Road,
which should be a minimum of 30 mm from other services in the aperture. The total amount of cross
Huddersfield, West Yorkshire, HD1 6SB
sections of services (including insulation) should not exceed 60% of the penetration area.
ETA 13/0673 & 18/0855 Tel: +44 (0) 148 4421036
For all technical details on the products specified Email: post.uk@polyseam.com
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu Sheet size: Drawn date & no:
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
Signed and approved: A4 5/3/19
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 240
Client:
Installation Instructions Maximum aperture 2 layers 50mm
unlimited width by FR Board 1-S
1. Before installing Protecta® FR Board ensure that the
surface of all service penetrations and surrounding
1200mm high Job Title:
construction is free from all loose contaminants, Protecta Pipe Wrap
dust and grease. fitted both sides
Products Protecta FR Board
2. The boards should be flush with the surface of the Protecta FR Acrylic
construction on both sides to maximize the fire Protecta FR Pipe Wrap 25m
resistance.
3. Cut the required board(s) to suit the aperture Application Fire stopping of plastic pipes in
dimensions and type and size of service rigid walls
Plastic pipes All services and openings
penetration(s). All exposed and cut edges of the
board can be sealed with Protecta® FR Coating or must be sealed with FR Construction Minimum wall thickness of 100
Protecta® FR Acrylic prior to fitting which will act as Acrylic both sides mm and comprise concrete,
an adhesive and ensure a smoke tight seal. aerated concrete or masonry,
4. All joints, gaps or imperfections in the installed seal with a density of ≥ 650 kg/m3
must be filled with Protecta® FR Acrylic on both Services Pipe Wall Thickness FR Pipe Wrap Classification
sides. ≤ Ø 40mm PVC-U & PVC-C 1.9 – 3.0mm 50 x 1.8mm (1 layer) EI 120 U/U (E 120 U/U)
Fire & Sound classification
5. Protecta® FR Board can be over-painted with most ≤ Ø 40mm PE, ABS & SAN+PVC 2.4 – 3.7mm 50 x 1.8mm (1 layer) EI 120 U/U (E 120 U/U)
emulsion or alkyd (gloss) paints. ≤ Ø 40mm PP 1.8 – 5.5mm 50 x 1.8mm (1 layer) EI 120 U/U (E 120 U/U)
≤ Ø 110mm PVC-U & PVC-C 2.7 – 6.6mm 50 x 3.6mm (2 layers) EI 90 U/C (E 120 U/C) For fire classifications please see the table on
≤ Ø 110mm PE, ABS & SAN+PVC 4.2 – 10.0mm 50 x 3.6mm (2 layers) EI 90 U/C (E 120 U/C) the left.
≤ Ø 110mm PP 2.7 – 15.1mm 50 x 3.6mm (2 layers) EI 90 U/U (E 90 U/U)
≤ Ø 125mm PVC-U & PVC-C 3.7 – 7.4mm 50 x 5.4mm (3 layers) EI 90 U/C (E 120 U/C) Sound reduction (seal only)
≤ Ø 125mm PE, ABS & SAN+PVC 4.8 – 12.0mm 50 x 5.4mm (3 layers) EI 90 U/C (E 120 U/C) 52 dB
≤ Ø 125mm PP 3.1 – 17.1mm 50 x 5.4mm (3 layers) EI 90 U/C (E 120 U/C)
≤ Ø 160mm PVC-U & PVC-C 9.5mm 50 x 7.2mm (4 layers) EI 90 U/C (E 120 U/C)
≤ Ø 160mm PE, ABS & SAN+PVC 14.6mm 50 x 7.2mm (4 layers) EI 90 U/C (E 120 U/C)
≤ Ø 160mm PP 21.9mm 50 x 7.2mm (4 layers) EI 90 U/C (E 120 U/C)
≤ Ø 200mm PVC-U & PVC-C 9.0 – 10.2mm 50 x 18.0mm (10 layers) EI 90 C/C (E 90 C/C)
≤ Ø 250mm PVC-U & PVC-C 8.5 – 11.0mm 50 x 18.0mm (10 layers) EI 90 C/C (E 90 C/C)
≤ Ø 315mm PVC-U & PVC-C 7.7 – 12.1mm 50 x 18.0mm (10 layers) EI 90 C/C (E 90 C/C)
≤ Ø 400mm PVC-U & PVC-C 9.8 – 15.3mm 50 x 28.8mm (16 layers) EI 90 C/C (E 90 C/C)

Minimum separations and limitations An aperture can include several services, and they may also be
different. The minimum permitted separation between adjacent seals/apertures is 200mm. Services
should be a minimum of 25mm from seal edges. Services within the system Protecta® FR Board seal
do not require a minimum separation, except pipes where pipe insulation penetrates the seal and
plastic pipe penetrations which should be a minimum of 30 mm from other services in the aperture. Polyseam Ltd, 15 St Andrews Road,
ETA 13/0673 & 18/0855 The total amount of cross sections of services should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 5/3/19
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 241
2 layers 60mm Client:
Installation Instructions Maximum aperture FR Board 2-S
unlimited width by
1. Before installing Protecta® FR Board ensure that the
surface of all service penetrations and surrounding
1200mm high Job Title:
construction is free from all loose contaminants, Protecta Pipe Wrap
dust and grease. fitted both sides
Products Protecta FR Board
2. The boards should be flush with the surface of the Protecta FR Acrylic
construction on both sides to maximize the fire Protecta FR Pipe Wrap 25m
resistance. If this is not possible, there should be an
air gap of at least 30mm between the boards. Application Fire stopping of plastic pipes in
3. Cut the required board(s) to suit the aperture All services and openings rigid walls
dimensions and type and size of service Plastic pipes
must be sealed with FR
penetration(s). All exposed and cut edges of the Acrylic both sides Construction Minimum wall thickness of 150
board can be sealed with Protecta® FR Coating or mm and comprise concrete,
Protecta® FR Acrylic prior to fitting which will act as aerated concrete or masonry,
an adhesive and ensure a smoke tight seal. with a density of ≥ 650 kg/m3
4. All joints, gaps or imperfections in the installed seal Services Pipe Wall Thickness FR Pipe Wrap Classification
must be filled with Protecta® FR Acrylic on both ≤ Ø 40mm PVC-U & PVC-C 1.9 – 3.0mm 50 x 1.8mm (1 layer) EI 240 U/C (E 240 U/C)
Fire & Sound classification
sides. ≤ Ø 40mm PE, ABS & SAN+PVC 2.4 – 4.6mm 50 x 1.8mm (1 layer) EI 240 U/C (E 240 U/C)
5. Protecta® FR Board can be over-painted with most ≤ Ø 40mm PP 1.8 – 5.5mm 50 x 1.8mm (1 layer) EI 240 U/C (E 240 U/C)
≤ Ø 110mm PVC-U & PVC-C 2.7 – 6.6mm 50 x 3.6mm (2 layers) EI 240 U/C (E 240 U/C) For fire classifications please see the table on
emulsion or alkyd (gloss) paints. the left.
≤ Ø 110mm PE, ABS & SAN+PVC 3.4 – 10.0mm 50 x 3.6mm (2 layers) EI 240 U/C (E 240 U/C)
≤ Ø 110mm PP 2.7 – 10.0mm 50 x 3.6mm (2 layers) EI 240 C/C (E 240 C/C)
≤ Ø 125mm PVC-U & PVC-C 4.7 – 7.4mm 50 x 7.2mm (4 layers) EI 240 U/C (E 240 U/C) Sound reduction (seal only)
≤ Ø 125mm PE, ABS & SAN+PVC 3.9 – 7.4mm 50 x 7.2mm (4 layers) EI 240 U/C (E 240 U/C) 52 dB
≤ Ø 125mm PP 3.1 – 11.4mm 50 x 7.2mm (4 layers) EI 240 C/C (E 240 C/C)
≤ Ø 160mm PVC-U & PVC-C 4.0 – 9.5mm 50 x 10.8mm (6 layers) EI 240 U/C (E 240 U/C)
≤ Ø 160mm PE, ABS & SAN+PVC 4.9 – 9.5mm 50 x 10.8mm (6 layers) EI 240 U/C (E 240 U/C)
≤ Ø 160mm PP 4.9 – 14.6mm 50 x 10.8mm (6 layers) EI 240 C/C (E 240 C/C)
≤ Ø 200mm PVC-U & PVC-C 5.0 – 10.2mm 75 x 18.0mm (10 layers) EI 120 C/C (E 120 C/C)
≤ Ø 250mm PVC-U & PVC-C 6.0 – 11.0mm 75 x 18.0mm (10 layers) EI 120 C/C (E 120 C/C)
≤ Ø 315mm PVC-U & PVC-C 7.7 – 12.1mm 75 x 18.0mm (10 layers) EI 120 C/C (E 120 C/C)
≤ Ø 400mm PVC-U & PVC-C 9.8 – 15.3mm 75 x 28.8mm (16 layers) EI 120 C/C (E 120 C/C)

Minimum separations and limitations An aperture can include several services, and they may also be
different. The minimum permitted separation between adjacent seals/apertures is 200mm. Services
should be a minimum of 25mm from seal edges. Services within the system Protecta® FR Board seal
do not require a minimum separation, except pipes where pipe insulation penetrates the seal and
Polyseam Ltd, 15 St Andrews Road,
plastic pipe penetrations which should be a minimum of 30 mm from other services in the aperture.
ETA 13/0673 & 18/0855 The total amount of cross sections of services should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 6/3/19
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 242
Client:
Installation Instructions Maximum aperture 2 layers 50mm
unlimited width by FR Board 1-S
1. Before installing Protecta® FR Board ensure that the
surface of all service penetrations and surrounding
1200mm high Job Title:
Protecta Pipe Wrap
construction is free from all loose contaminants, fitted both sides
dust and grease.
Products Protecta FR Board
2. The boards should be flush with the surface of the Protecta FR Acrylic
construction on both sides to maximize the fire Protecta FR Pipe Wrap 25m
resistance.
3. Cut the required board(s) to suit the aperture Application Fire stopping of composite
dimensions and type and size of service plastic pipes in rigid walls
penetration(s). All exposed and cut edges of the Composite All services and openings
board can be sealed with Protecta® FR Coating or plastic pipes must be sealed with FR Construction Minimum wall thickness of 100
Protecta® FR Acrylic prior to fitting which will act as Acrylic both sides mm and comprise concrete,
an adhesive and ensure a smoke tight seal. aerated concrete or masonry,
4. All joints, gaps or imperfections in the installed seal with a density of ≥ 650 kg/m3
must be filled with Protecta® FR Acrylic on both Services FR Pipe Wrap Classification
sides. Ø 32mm Aquatherm Green SDR9 pipes 50 x 1.8mm (1 layer) EI 90 C/C (E 120 C/C)
Fire & Sound classification
5. Protecta® FR Board can be over-painted with most ≤ Ø 110mm Aquatherm Green SDR9 pipes 50 x 3.6mm (2 layers) EI 90 C/C (E 120 C/C)
emulsion or alkyd (gloss) paints. ≤ Ø 50mm BluePower pipes 50 x 3.6mm (2 layers) EI 90 U/U (E 90 U/U)
≤ Ø 110mm BluePower pipes 50 x 3.6mm (2 layers) EI 90 C/U (E 90 C/U) For fire classifications please see the table on
≤ Ø 50mm Geberit Silent-PP pipes 50 x 3.6mm (2 layers) EI 120 U/U (E 120 U/U) the left.
≤ Ø 110mm Geberit Silent-PP pipes 50 x 3.6mm (2 layers) EI 120 U/C (E 120 U/C)
≤ Ø 50mm Polo-Kal NG pipes 50 x 3.6mm (2 layers) EI 120 U/U (E 120 U/U) Sound reduction (seal only)
≤ Ø 110mm Polo-Kal NG pipes 50 x 3.6mm (2 layers) EI 120 U/C (E 120 U/C) 52 dB
Ø 125mm Polo-Kal NG pipes 50 x 7.2mm (4 layers) EI 120 U/C (E 120 U/C)
Ø 160mm Polo-Kal NG pipes 50 x 10.8mm (6 layers) EI 120 U/C (E 120 U/C)
≤ Ø 50mm Rehau Raupiano Plus pipes 50 x 3.6mm (2 layers) EI 120 U/U (E 120 U/U)
≤ Ø 110mm Rehau Raupiano Plus pipes 50 x 3.6mm (2 layers) EI 120 U/C (E 120 U/C)
Ø 125mm Rehau Raupiano Plus pipes 50 x 7.2mm (4 layers) EI 120 U/C (E 120 U/C)
Ø 160mm Rehau Raupiano Plus pipes 50 x 10.8mm (6 layers) EI 120 U/C (E 120 U/C)
≤ Ø 50mm Wavin SiTech pipes 50 x 3.6mm (2 layers) EI 90 U/U (E 120 U/U)
≤ Ø 110mm Wavin SiTech pipes 50 x 3.6mm (2 layers) EI 60 U/C (E 120 U/C)

Minimum separations and limitations An aperture can include several services, and they may also be
different. The minimum permitted separation between adjacent seals/apertures is 200mm. Services
should be a minimum of 25mm from seal edges. Services within the system Protecta® FR Board seal
do not require a minimum separation, except pipes where pipe insulation penetrates the seal and
plastic pipe penetrations which should be a minimum of 30 mm from other services in the aperture. Polyseam Ltd, 15 St Andrews Road,
ETA 13/0673 & 18/0855 The total amount of cross sections of services should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 5/3/19
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 243
Client:
Installation Instructions

1. Before installing Protecta® FR Board ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants, Maximum aperture
dust and grease. unlimited width by Products Protecta FR Board
2. The boards should be flush with the surface of the 2 layers 50mm
1200mm high Protecta FR Acrylic
construction on both sides to maximize the fire FR Board 1-S Protecta FR Pipe Wrap
resistance. Application Fire stopping of conduits in
3. Cut the required board(s) to suit the aperture Protecta Pipe Wrap 2 rigid walls
dimensions and type and size of service layers of 50mm wide Construction Minimum wall thickness of 100
penetration(s). All exposed and cut edges of the fitted both sides mm and comprise concrete,
board can be sealed with Protecta® FR Coating or Cables aerated concrete or masonry,
Protecta® FR Acrylic prior to fitting which will act as ≤ Ø14mm with a density of ≥ 650 kg/m3
an adhesive and ensure a smoke tight seal. single or in Fire & Sound classification
4. All joints, gaps or imperfections in the installed seal a bundle
must be filled with Protecta® FR Acrylic on both Conduits of PVC-U & PVC-C pipes ≤ Ø110mm
with wall thickness 2.7-6.6mm
sides.
EI 90 U/C & E 120 U/C
5. Protecta® FR Board can be over-painted with most All services and openings
emulsion or alkyd (gloss) paints. Plastic pipes
must be sealed with FR Conduits of PE, ABS & SAN+PVC pipes
Acrylic both sides ≤ Ø110mm with wall thickness 4.2-10.0mm
EI 90 U/C & E 120 U/C

Conduits of PP pipes ≤ Ø110mm with wall


thickness 2.7-15.1mm EI 90 U/C & E 120 U/C

Sound reduction (seal only) 52 dB

Minimum separations and limitations

An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 25mm
from seal edges. Services within the system Protecta® FR Board seal do not require a minimum
separation, except pipes where pipe insulation penetrates the seal and plastic pipe penetrations Polyseam Ltd, 15 St Andrews Road,
which should be a minimum of 30 mm from other services in the aperture. The total amount of cross
Huddersfield, West Yorkshire, HD1 6SB
sections of services (including insulation) should not exceed 60% of the penetration area.
ETA 13/0673 & 18/0855 Tel: +44 (0) 148 4421036
For all technical details on the products specified Email: post.uk@polyseam.com
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu Sheet size: Drawn date & no:
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
Signed and approved: A4 5/3/19
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 244
Client:
Installation Instructions

1. Before installing Protecta® FR Board ensure that the


surface of all service penetrations and surrounding
Job Title:
construction is free from all loose contaminants, Maximum aperture
dust and grease. unlimited width by
1200mm high Products Protecta FR Board
2. Protecta® FR Coating and Protecta® FR Acrylic are 2 layers 50mm
Protecta FR Acrylic
water based, so in cases where corrosion protection FR Board 1-S
Protecta FR Damper
is a problem, some metals may require a barrier Application Fire stopping of ventilation
between the seal and the surface prior to this Protecta FR ducts in rigid walls
30mm stone wool
installation. Damper Construction Minimum wall thickness of 100
matt
3. The boards should be flush with the surface of the mm and comprise concrete,
construction on both sides to maximize the fire Ventilation aerated concrete or masonry,
resistance. duct with a density of ≥ 650 kg/m3
4. Cut the required board(s) to suit the aperture Fire & Sound classification
dimensions and type and size of service
penetration(s). All exposed and cut edges of the ≤ Ø 400mm damper/duct with ≥ 200mm stone
wool matt on both sides
board can be sealed with Protecta® FR Coating or
EI 120 & E 120
Protecta® FR Acrylic prior to fitting which will act as
≤ Ø 1250mm damper/duct with ≥ 500mm stone
an adhesive and ensure a smoke tight seal.
All services and openings wool matt on both sides
5. All joints, gaps or imperfections in the installed seal EI 60 & E 90
must be sealed with FR
must be filled with Protecta® FR Acrylic on both ≤ 600mm high x 1000mm wide damper/duct
Acrylic both sides
sides. with ≥ 500mm stone wool matt on both sides
6. Insulate the ventilation duct towards the fire seal on EI 120 & E 120
both sides with 30mm thick stone wool matting to ≤ 1200mm high x 1700mm wide damper/duct
the length given on this page. Insulate on one side with ≥ 500mm stone wool matt on both sides
only if the duct terminates in the wall. EI 90 & E 90
7. Protecta® FR Board can be over-painted with most Sound reduction (seal only) 52 dB
emulsion or alkyd (gloss) paints.

Minimum separations and limitations

An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 25mm
from seal edges. Services within the system Protecta® FR Board seal do not require a minimum
separation, except pipes where pipe insulation penetrates the seal and plastic pipe penetrations
which should be a minimum of 30 mm from other services in the aperture. The total amount of cross Polyseam Ltd, 15 St Andrews Road,
This product is certified to applicable European (EN)
standards and UL-EU Mark service requirements. sections of services (including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 27/7/17
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 245
Client:
Installation Instructions

1. Ensure the faces of the aperture opening are free of


dust and any other contaminants. The faces may be
Job Title:
moistened for better adhesion.
2. The seal can be positioned to either side of the
Protecta EX Mortar Products Protecta EX Mortar
construction or anywhere in between. Stone wool shutter
3. When installing Protecta® EX Mortar in hollow floor Minimum seal depth 50mm
slabs or boards, level the fire seal with the soffit side. Maximum aperture 1200x2400mm
Application Fire stopping of cables and
Ensure there is sufficient thickness of concrete conduits in rigid floors
below the void for the depth of mortar. Where this
is not the case, tubular voids should be filled with Construction Minimum floor thickness of 150
stone wool normally the same thickness as the mm and comprise aerated
depth of the floor slab. Alternatively, simply fire seal concrete or concrete with a
on both sides. minimum density of 650kg/m3.
4. Install a stone wool shutter board to achieve the
required thickness of mortar. Make sure that this Fire & Sound classification
achieves a very tight seal – any small openings
Cables ≤ Ø21mm EI 90 & E 180
should be sealed with Protecta® FR Acrylic
5. Pour clean water into a suitable mixing vessel and
Cables ≤ Ø21mm in tied bundles ≤ Ø100mm and
add the mortar to obtain the required consistency. Cables and PVC conduits 50mm stone wool PVC conduits (C/U) ≤ Ø16mm EI 180 & E 180
Mix steadily at low speed and ensure that any lumps shutter ≥ 150kg/m3
of powder are fully dispersed. Always add the mortar Non-sheathed cables/wires ≤ Ø17mm
to the water, do not reverse this mixing process EI 60 & E 180
6. Once the desired consistency is achieved pour or
trowel the mortar onto the shutter board making Sound reduction (seal only) 48dB
sure that it flows into all corners and around
services. Apply a firm pressure to the mortar to
eliminate any trapped air bubbles. Build up to the
required depth.

Minimum separations and limitations


An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 30mm
from seal edges. Services within the seal do not require a minimum separation, except pipes where
combustible pipe insulation penetrates the seal and plastic pipe penetrations which should be a
minimum of 30mm from other services in the aperture. The total amount of cross sections of services Polyseam Ltd, 15 St Andrews Road,
ETA 13/0672 & 18/0855
(including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 6/3/19
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 246
Client:
Installation Instructions

1. Ensure the faces of the aperture opening are free of


dust and any other contaminants. The faces may be
Job Title:
moistened for better adhesion.
2. The seal can be positioned to either side of the
Protecta EX Mortar Products Protecta EX Mortar
construction or anywhere in between. Application Fire stopping of cables and
3. When installing Protecta® EX Mortar in hollow floor Minimum seal depth 100mm
conduits in rigid floors
slabs or boards, level the fire seal with the soffit side. Maximum aperture 1200x2400mm
Construction Minimum floor thickness of 150
Ensure there is sufficient thickness of concrete mm and comprise aerated
below the void for the depth of mortar. Where this concrete or concrete with a
is not the case, tubular voids should be filled with minimum density of 650kg/m3
stone wool normally the same thickness as the
Fire & Sound classification
depth of the floor slab. Alternatively, simply fire seal
on both sides. Cables ≤ Ø21mm EI 90 & E 180
4. Install a shutter board to achieve the required
thickness of mortar. Make sure that this achieves a Cables ≤ Ø21mm in tied bundles ≤ Ø100mm and
very tight seal. PVC conduits (C/U) ≤ Ø16mm EI 180 & E 180
5. Pour clean water into a suitable mixing vessel and
add the mortar to obtain the required consistency. Cables ≤ Ø50mm, single or bundled
Mix steadily at low speed and ensure that any lumps Cables and PVC conduits EI 60 & E 180
of powder are fully dispersed. Always add the mortar
to the water, do not reverse this mixing process Cables ≤ Ø80mm, single or bundled
6. Once the desired consistency is achieved pour or EI 60 & E 120
trowel the mortar onto the shutter board making
Non-sheathed cables/wires ≤ Ø17mm
sure that it flows into all corners and around
EI 60 & E 180
services. Apply a firm pressure to the mortar to Loadbearing Properties
eliminate any trapped air bubbles. Build up to the Sound reduction (seal only) 48dB
required depth. Soft body impact, serviceability 500Nm. Soft body impact, safety in use 700Nm. Hard body impact
serviceability 6Nm. Hard body impact, safety in use 10Nm. Concentrated load to 15kN on size up to
1500mm x1000mm (no failure), 4.85kN on sizes up to 1200mm x 2400mm.
Minimum separations and limitations
An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 30mm
from seal edges. Services within the seal do not require a minimum separation, except pipes where
combustible pipe insulation penetrates the seal and plastic pipe penetrations which should be a
Polyseam Ltd, 15 St Andrews Road,
minimum of 30mm from other services in the aperture. The total amount of cross sections of services
Huddersfield, West Yorkshire, HD1 6SB
ETA 13/0672 & 18/0855 (including insulation) should not exceed 60% of the penetration area.
Tel: +44 (0) 148 4421036
For all technical details on the products specified
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu Sheet size: Drawn date & no:
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
Signed and approved: A4 6/3/19
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 247
Client:
Installation Instructions

1. Ensure the faces of the aperture opening are free of


dust and any other contaminants. The faces may be
Job Title:
moistened for better adhesion.
2. The seal can be positioned to either side of the
Protecta EX Mortar Products Protecta EX Mortar
construction or anywhere in between. Application Fire stopping of cables and
Minimum seal depth 150mm
3. When installing Protecta® EX Mortar in hollow floor conduits in rigid floors
Maximum aperture 1200x2400mm
slabs or boards, level the fire seal with the soffit side. Construction Minimum floor thickness of 150
Ensure there is sufficient thickness of concrete mm and comprise aerated
below the void for the depth of mortar. Where this concrete or concrete with a
is not the case, tubular voids should be filled with minimum density of 650kg/m3
stone wool normally the same thickness as the
Fire & Sound classification
depth of the floor slab. Alternatively, simply fire seal
on both sides. Cables ≤ Ø21mm, single EI 120 & E 240
4. Install a shutter board to achieve the required
thickness of mortar. Make sure that this achieves a Cables ≤ Ø21mm in tied bundles ≤ Ø100mm and
very tight seal. PVC conduits (C/U) ≤ Ø16mm EI 180 & E 180
5. Pour clean water into a suitable mixing vessel and
add the mortar to obtain the required consistency. Cables ≤ Ø50mm, single or bundled
Mix steadily at low speed and ensure that any lumps Cables and PVC conduits EI 90 & E 240
of powder are fully dispersed. Always add the mortar
to the water, do not reverse this mixing process Cables ≤ Ø80mm, single or bundled
6. Once the desired consistency is achieved pour or EI 60 & E 120
trowel the mortar onto the shutter board making
Unsheathed wires/cables ≤ Ø24 mm
sure that it flows into all corners and around
EI 120 & E 120
services. Apply a firm pressure to the mortar to Loadbearing Properties
eliminate any trapped air bubbles. Build up to the Sound reduction (seal only) 48dB
required depth. Soft body impact, serviceability 500Nm. Soft body impact, safety in use 700Nm. Hard body impact
serviceability 6Nm. Hard body impact, safety in use 10Nm. Concentrated load to 15kN on size up to
1500mm x1000mm (no failure), 4.85kN on sizes up to 1200mm x 2400mm.
Minimum separations and limitations
An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 30mm
from seal edges. Services within the seal do not require a minimum separation, except pipes where
combustible pipe insulation penetrates the seal and plastic pipe penetrations which should be a
minimum of 30mm from other services in the aperture. The total amount of cross sections of services
Polyseam Ltd, 15 St Andrews Road,
(including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
ETA 13/0672 & 18/0855
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 6/3/19
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 248
Client:
Installation Instructions

1. Ensure the faces of the aperture opening are free of


dust and any other contaminants. The faces may be
Job Title:
moistened for better adhesion.
2. Bare metal passing through the seal must be
Products Protecta EX Mortar
protected against corrosion using a suitable Protecta EX Mortar Stone wool shutter
primer/protection system. Minimum seal depth 50mm
3. The seal can be positioned to either side of the Maximum aperture 1200x2400mm Application Fire stopping of cables, wires
construction or anywhere in between. and conduits on cable trays in
4. When installing Protecta® EX Mortar in hollow floor rigid floors
slabs or boards, level the fire seal with the soffit side.
Ensure there is sufficient thickness of concrete Construction Minimum floor thickness of 150
below the void for the depth of mortar. Where this mm and comprise aerated
is not the case, tubular voids should be filled with concrete or concrete with a
stone wool normally the same thickness as the minimum density of 650kg/m3.
depth of the floor slab. Alternatively, simply fire seal
Fire & Sound classification
on both sides.
5. Install a stone wool shutter board to achieve the
Cables ≤ Ø21mm, single or bundled on trays
required thickness of mortar. Make sure that this
EI 60 & E 180
achieves a very tight seal – any small openings Cables, wires and PVC 50mm stone wool
should be sealed with Protecta® FR Acrylic conduits on cable trays shutter ≥ 150kg/m3 Cables ≤ Ø21mm, single or bundled, non-
6. Pour clean water into a suitable mixing vessel and sheathed cables/wires ≤ Ø17mm and PVC
add the mortar to obtain the required consistency. conduits (C/U) ≤ Ø16mm on trays or ladders
Mix steadily at low speed and ensure that any lumps EI 60 & E 90
of powder are fully dispersed. Always add the mortar
to the water, do not reverse this mixing process Sound reduction (seal only)
7. Once the desired consistency is achieved pour or 48dB
trowel the mortar onto the shutter board making
sure that it flows into all corners and around
services. Apply a firm pressure to the mortar to
eliminate any trapped air bubbles. Build up to the Minimum separations and limitations
required depth. An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 30mm
from seal edges. Services within the seal do not require a minimum separation, except pipes where
combustible pipe insulation penetrates the seal and plastic pipe penetrations which should be a
minimum of 30mm from other services in the aperture. The total amount of cross sections of services Polyseam Ltd, 15 St Andrews Road,
ETA 13/0672 & 18/0855
(including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 6/3/19
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 249
Client:
Installation Instructions

1. Ensure the faces of the aperture opening are free of


dust and any other contaminants. The faces may be
Job Title:
moistened for better adhesion.
2. Bare metal passing through the seal must be
Protecta EX Mortar Products Protecta EX Mortar
protected against corrosion using a suitable
primer/protection system. Minimum seal depth 100mm
Application Fire stopping of cables, wires
3. The seal can be positioned to either side of the Maximum aperture 1200x2400mm
and conduits on cable trays in
construction or anywhere in between. rigid floors
4. When installing Protecta® EX Mortar in hollow floor
slabs or boards, level the fire seal with the soffit side. Construction Minimum floor thickness of 150
Ensure there is sufficient thickness of concrete mm and comprise aerated
below the void for the depth of mortar. Where this concrete or concrete with a
is not the case, tubular voids should be filled with minimum density of 650kg/m3
stone wool normally the same thickness as the Fire & Sound classification
depth of the floor slab. Alternatively, simply fire seal
Cables ≤ Ø50mm, single or bundled, non-
on both sides.
sheathed cables/wires ≤ Ø17mm and PVC
5. Install a shutter board to achieve the required
conduits ≤ Ø16mm (C/U) on trays
thickness of mortar. Make sure that this achieves a
Cables, wires and PVC EI 60 & E 180
very tight seal.
6. Pour clean water into a suitable mixing vessel and conduits on cable trays
Cables ≤ Ø80mm, single or bundled, non-
add the mortar to obtain the required consistency. sheathed cables/wires ≤ Ø17mm and PVC
Mix steadily at low speed and ensure that any lumps conduits ≤ Ø16mm (C/U) on trays or ladders
of powder are fully dispersed. Always add the mortar EI 60 & E 120
to the water, do not reverse this mixing process
7. Once the desired consistency is achieved pour or Sound reduction (seal only)
Loadbearing Properties 48dB
trowel the mortar onto the shutter board making
sure that it flows into all corners and around Soft body impact, serviceability 500Nm. Soft body impact, safety in use 700Nm. Hard body impact
services. Apply a firm pressure to the mortar to serviceability 6Nm. Hard body impact, safety in use 10Nm. Concentrated load to 15kN on size up to
eliminate any trapped air bubbles. Build up to the 1500mm x1000mm (no failure), 4.85kN on sizes up to 1200mm x 2400mm.
required depth. Minimum separations and limitations
An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 30mm
from seal edges. Services within the seal do not require a minimum separation, except pipes where
combustible pipe insulation penetrates the seal and plastic pipe penetrations which should be a
minimum of 30mm from other services in the aperture. The total amount of cross sections of services
Polyseam Ltd, 15 St Andrews Road,
ETA 13/0672 & 18/0855 (including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 6/3/19
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 250
Client:
Installation Instructions

1. Ensure the faces of the aperture opening are free of


dust and any other contaminants. The faces may be
Job Title:
moistened for better adhesion.
2. Bare metal passing through the seal must be Protecta EX Mortar Products Protecta EX Mortar
protected against corrosion using a suitable Minimum seal depth 150mm Application Fire stopping of cables, wires
primer/protection system. Maximum aperture 1200x2400mm and conduits on cable trays in
3. The seal can be positioned to either side of the rigid floors
construction or anywhere in between. Construction Minimum floor thickness of 150
4. When installing Protecta® EX Mortar in hollow floor mm and comprise aerated
slabs or boards, level the fire seal with the soffit side. concrete or concrete with a
Ensure there is sufficient thickness of concrete minimum density of 650kg/m3
below the void for the depth of mortar. Where this
is not the case, tubular voids should be filled with Fire & Sound classification
stone wool normally the same thickness as the
depth of the floor slab. Alternatively, simply fire seal Cables ≤ Ø21mm, single or bundled on trays or
ladders ≤ 500mm wide EI 120 & E 240
on both sides.
5. Install a shutter board to achieve the required
Cables ≤ Ø80mm, single or bundled on trays or
thickness of mortar. Make sure that this achieves a
Cables, wires and PVC ladders EI 60 & E 120
very tight seal.
6. Pour clean water into a suitable mixing vessel and conduits on cable trays
PVC conduits ≤ Ø16mm (C/U) on trays or
add the mortar to obtain the required consistency. ladders ≤ 500mm wide EI 120 & E 180
Mix steadily at low speed and ensure that any lumps
of powder are fully dispersed. Always add the mortar Unsheathed wires/cables ≤ Ø24 mm on trays or
to the water, do not reverse this mixing process ladders ≤ 500mm wide EI 120 & E 120
7. Once the desired consistency is achieved pour or
Loadbearing Properties Sound reduction (seal only) 48dB
trowel the mortar onto the shutter board making
sure that it flows into all corners and around Soft body impact, serviceability 500Nm. Soft body impact, safety in use 700Nm. Hard body impact
services. Apply a firm pressure to the mortar to serviceability 6Nm. Hard body impact, safety in use 10Nm. Concentrated load to 15kN on size up to
eliminate any trapped air bubbles. Build up to the 1500mm x1000mm (no failure), 4.85kN on sizes up to 1200mm x 2400mm.
required depth.
Minimum separations and limitations
An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 30mm
from seal edges. Services within the seal do not require a minimum separation, except pipes where
combustible pipe insulation penetrates the seal and plastic pipe penetrations which should be a
minimum of 30mm from other services in the aperture. The total amount of cross sections of services
Polyseam Ltd, 15 St Andrews Road,
ETA 13/0672 & 18/0855 (including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 6/3/19
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 251
Client:
Installation Instructions

1. Ensure the faces of the aperture opening are free of


dust and any other contaminants. The faces may be
Job Title:
Protecta EX Mortar
moistened for better adhesion.
Minimum seal depth 50mm
2. Bare metal pipes passing through the seal must be
Maximum aperture 1200x2400mm Products Protecta EX Mortar
protected against corrosion using a suitable Stone wool shutter
primer/protection system.
3. The seal can be positioned to either side of the Application Fire stopping of un-insulated
construction or anywhere in between. steel pipes in rigid floors
4. When installing Protecta® EX Mortar in hollow floor
slabs or boards, level the fire seal with the soffit side. Construction Minimum floor thickness of 150
Ensure there is sufficient thickness of concrete mm and comprise aerated
below the void for the depth of mortar. Where this concrete or concrete with a
is not the case, tubular voids should be filled with minimum density of 650kg/m3.
stone wool normally the same thickness as the
depth of the floor slab. Alternatively, simply fire seal
on both sides.
Fire & Sound classification
5. Install a stone wool shutter board to achieve the 50mm stone wool
required thickness of mortar. Make sure that this shutter ≥ 150kg/m3
Steel pipes Steel pipes ≤ Ø16mm
achieves a very tight seal – any small openings EI 180 C/U & E 180 C/U
should be sealed with Protecta® FR Acrylic.
6. Pour clean water into a suitable mixing vessel and Sound reduction (seal only)
add the mortar to obtain the required consistency. 48dB
Mix steadily at low speed and ensure that any lumps
of powder are fully dispersed. Always add the mortar
to the water, do not reverse this mixing process
7. Once the desired consistency is achieved pour or
trowel the mortar onto the shutter board making
sure that it flows into all corners and around
services. Apply a firm pressure to the mortar to
eliminate any trapped air bubbles. Build up to the Minimum separations and limitations
required depth. An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 30mm
from seal edges. Services within the seal do not require a minimum separation, except pipes where
combustible pipe insulation penetrates the seal and plastic pipe penetrations which should be a
minimum of 30mm from other services in the aperture. The total amount of cross sections of services
Polyseam Ltd, 15 St Andrews Road,
(including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
ETA 13/0672 & 18/0855
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 23/5/18
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 252
Client:
Installation Instructions

1. Ensure the faces of the aperture opening are free of


dust and any other contaminants. The faces may be
Job Title:
moistened for better adhesion.
2. Bare metal pipes passing through the seal must be
Protecta EX Mortar Products Protecta EX Mortar
protected against corrosion using a suitable
Minimum seal depth 100mm
primer/protection system. Application Fire stopping of un-insulated
Maximum aperture 1200x2400mm
3. The seal can be positioned to either side of the steel pipes in rigid floors
construction or anywhere in between.
4. When installing Protecta® EX Mortar in hollow floor Construction Minimum floor thickness of 150
slabs or boards, level the fire seal with the soffit side. mm and comprise aerated
Ensure there is sufficient thickness of concrete concrete or concrete with a
below the void for the depth of mortar. Where this minimum density of 650kg/m3.
is not the case, tubular voids should be filled with
stone wool normally the same thickness as the
depth of the floor slab. Alternatively, simply fire seal
Fire & Sound classification
on both sides.
5. Install a shutter board to achieve the required
Steel pipes ≤ Ø16mm
thickness of mortar. Make sure that this achieves a
Steel pipes EI 240 C/U & E 240 C/U
very tight seal.
6. Pour clean water into a suitable mixing vessel and Sound reduction (seal only)
add the mortar to obtain the required consistency. 48dB
Mix steadily at low speed and ensure that any lumps
of powder are fully dispersed. Always add the mortar
to the water, do not reverse this mixing process
7. Once the desired consistency is achieved pour or
Loadbearing Properties
trowel the mortar onto the shutter board making
sure that it flows into all corners and around Soft body impact, serviceability 500Nm. Soft body impact, safety in use 700Nm. Hard body impact
services. Apply a firm pressure to the mortar to serviceability 6Nm. Hard body impact, safety in use 10Nm. Concentrated load to 15kN on size up to
eliminate any trapped air bubbles. Build up to the 1500mm x1000mm (no failure), 4.85kN on sizes up to 1200mm x 2400mm.
required depth. Minimum separations and limitations
An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 30mm
from seal edges. Services within the seal do not require a minimum separation, except pipes where
combustible pipe insulation penetrates the seal and plastic pipe penetrations which should be a
minimum of 30mm from other services in the aperture. The total amount of cross sections of services
Polyseam Ltd, 15 St Andrews Road,
(including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
ETA 13/0672 & 18/0855
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 23/5/18
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 253
Client:
Installation Instructions

1. Ensure the faces of the aperture opening are free of


dust and any other contaminants. The faces may be
Job Title:
Continuous elastomeric
moistened for better adhesion. or phenolic foam Protecta EX Mortar
2. The seal can be positioned to either side of the insulation Minimum seal depth 100mm
Products Protecta EX Mortar
construction or anywhere in between. Maximum aperture 1200x2400mm Protecta FR Pipe Wrap 25m
3. When installing Protecta® EX Mortar in hollow floor Application Fire stopping of insulated steel
slabs or boards, level the fire seal with the soffit side. pipes in rigid floors
Ensure there is sufficient thickness of concrete Construction Minimum floor thickness of 150
below the void for the depth of mortar. Where this mm and comprise aerated
is not the case, tubular voids should be filled with concrete or concrete with a
stone wool normally the same thickness as the minimum density of 650kg/m3.
depth of the floor slab. Alternatively, simply fire seal Fire & Sound classification
on both sides. Steel pipes ≤ Ø40mm with 13mm continuous
4. Install a shutter board to achieve the required foam insulation and 1 layer of pipe wrap
thickness of mortar. Make sure that this achieves a EI 180 C/U & E 180 C/U
Steel pipes ≤ Ø40mm with 14-25mm continuous
very tight seal.
Protecta Pipe Wrap foam insulation and 2 layers of pipe wrap
5. Pour clean water into a suitable mixing vessel and
50mm wide fitted at soffit EI 180 C/U & E 180 C/U
add the mortar to obtain the required consistency.
Steel pipes Steel pipes ≤ Ø165mm with 14 - 19mm
Mix steadily at low speed and ensure that any lumps continuous foam insulation and 1 layer of pipe
of powder are fully dispersed. Always add the mortar wrap EI 120 C/U & E 180 C/U
to the water, do not reverse this mixing process Steel pipes ≤ Ø324mm with 25mm continuous
6. Once the desired consistency is achieved pour or foam insulation and 2 layers of pipe wrap
trowel the mortar onto the shutter board making EI 120 C/U & E 180 C/U
sure that it flows into all corners and around Steel pipes ≤ Ø324mm with 26 - 50mm
services. Apply a firm pressure to the mortar to continuous foam insulation and 3 layers of pipe
Loadbearing Properties
eliminate any trapped air bubbles. Build up to the wrap EI 120 C/U & E 120 C/U
required depth. Sound reduction (seal only) 48dB
Soft body impact, serviceability 500Nm. Soft body impact, safety in use 700Nm. Hard body impact
serviceability 6Nm. Hard body impact, safety in use 10Nm. Concentrated load to 15kN on size up to
1500mm x1000mm (no failure), 4.85kN on sizes up to 1200mm x 2400mm.
Minimum separations and limitations
An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 30mm
from seal edges. Services within the seal do not require a minimum separation, except pipes where
combustible pipe insulation penetrates the seal and plastic pipe penetrations which should be a
Polyseam Ltd, 15 St Andrews Road,
minimum of 30mm from other services in the aperture. The total amount of cross sections of services
Huddersfield, West Yorkshire, HD1 6SB
ETA 13/0672 & 18/0855 (including insulation) should not exceed 60% of the penetration area.
Tel: +44 (0) 148 4421036
For all technical details on the products specified
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is be found on www.protecta.eu Sheet size: Drawn date & no:
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
Signed and approved: A4 4/3/19
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 254
Client:
Installation Instructions

1. Ensure the faces of the aperture opening are free of


dust and any other contaminants. The faces may be
Job Title:
moistened for better adhesion.
2. The seal can be positioned to either side of the
Products Protecta EX Mortar
construction or anywhere in between. Continuous stone wool Stone wool shutter
3. When installing Protecta® EX Mortar in hollow floor Protecta EX Mortar
≥ 80 kg/m3 Minimum seal depth 50mm
slabs or boards, level the fire seal with the soffit side. Application Fire stopping of insulated steel
Ensure there is sufficient thickness of concrete pipes in rigid floors
below the void for the depth of mortar. Where this
is not the case, tubular voids should be filled with Construction Minimum floor thickness of 150
stone wool normally the same thickness as the mm and comprise aerated
depth of the floor slab. Alternatively, simply fire seal concrete or concrete with a
on both sides. minimum density of 650kg/m3
4. Install a stone wool shutter board to achieve the
required thickness of mortar. Make sure that this Fire & Sound classification
achieves a very tight seal – any small openings
Steel pipes ≤ Ø324mm with 20-80mm thick
should be sealed with Protecta® FR Acrylic
stone wool insulation in maximum apertures
5. Pour clean water into a suitable mixing vessel and
50mm stone wool 1200 x 2400mm EI 180 C/U & E 180 C/U
add the mortar to obtain the required consistency.
Mix steadily at low speed and ensure that any lumps shutter ≥ 150kg/m3
Steel pipes ≤ Ø324mm with 20-80mm thick
of powder are fully dispersed. Always add the mortar Steel pipes stone wool insulation in maximum apertures
to the water, do not reverse this mixing process 550 x 1100mm EI 240 C/U & E 240 C/U
6. Once the desired consistency is achieved pour or
trowel the mortar onto the shutter board making Sound reduction (seal only) 48dB
sure that it flows into all corners and around
services. Apply a firm pressure to the mortar to
eliminate any trapped air bubbles. Build up to the
required depth.

Minimum separations and limitations


An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 30mm
from seal edges. Services within the seal do not require a minimum separation, except pipes where
combustible pipe insulation penetrates the seal and plastic pipe penetrations which should be a
minimum of 30mm from other services in the aperture. The total amount of cross sections of services Polyseam Ltd, 15 St Andrews Road,
ETA 13/0672 & 18/0855
(including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 16/1/17
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 255
Client:
Installation Instructions

1. Ensure the faces of the aperture opening are free of


dust and any other contaminants. The faces may be
Job Title:
moistened for better adhesion.
2. The seal can be positioned to either side of the
Products Protecta EX Mortar
construction or anywhere in between. Continuous stone wool
3. When installing Protecta® EX Mortar in hollow floor Protecta EX Mortar
≥ 80 kg/m3 Minimum seal depth 100mm Application Fire stopping of insulated steel
slabs or boards, level the fire seal with the soffit side. pipes in rigid floors
Ensure there is sufficient thickness of concrete
below the void for the depth of mortar. Where this Construction Minimum floor thickness of 150
is not the case, tubular voids should be filled with mm and comprise aerated
stone wool normally the same thickness as the concrete or concrete with a
depth of the floor slab. Alternatively, simply fire seal minimum density of 650kg/m3
on both sides.
4. Install a shutter board to achieve the required
thickness of mortar. Make sure that this achieves a
Fire & Sound classification
very tight seal.
5. Pour clean water into a suitable mixing vessel and
Steel pipes ≤ Ø324mm with 20-80mm thick
add the mortar to obtain the required consistency.
stone wool insulation in maximum apertures
Mix steadily at low speed and ensure that any lumps 1200 x 2400mm
of powder are fully dispersed. Always add the mortar EI 240 C/U & E 240 C/U
to the water, do not reverse this mixing process Steel pipes
6. Once the desired consistency is achieved pour or Sound reduction (seal only)
trowel the mortar onto the shutter board making 48dB
sure that it flows into all corners and around
services. Apply a firm pressure to the mortar to Loadbearing Properties
eliminate any trapped air bubbles. Build up to the
Soft body impact, serviceability 500Nm. Soft body impact, safety in use 700Nm. Hard body impact
required depth.
serviceability 6Nm. Hard body impact, safety in use 10Nm. Concentrated load to 15kN on size up to
1500mm x1000mm (no failure), 4.85kN on sizes up to 1200mm x 2400mm.
Minimum separations and limitations
An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 30mm
from seal edges. Services within the seal do not require a minimum separation, except pipes where
combustible pipe insulation penetrates the seal and plastic pipe penetrations which should be a
minimum of 30mm from other services in the aperture. The total amount of cross sections of services Polyseam Ltd, 15 St Andrews Road,
(including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
ETA 13/0672 & 18/0855
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 23/5/18
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 256
Client:
Installation Instructions

1. Ensure the faces of the aperture opening are free of


dust and any other contaminants. The faces may be
Job Title:
moistened for better adhesion.
2. Bare metal pipes passing through the seal must be Stone wool ≥ 80 kg/m3
to be installed ≥ 100cm Products Protecta EX Mortar
protected against corrosion using a suitable Stone wool shutter
primer/protection system. on both sides Protecta EX Mortar
Minimum seal depth 50mm Application Fire stopping of insulated steel
3. The seal can be positioned to either side of the pipes in rigid floors
construction or anywhere in between. Construction Minimum floor thickness of 150
4. When installing Protecta® EX Mortar in hollow floor mm and comprise aerated
slabs or boards, level the fire seal with the soffit side. concrete or concrete with a
Ensure there is sufficient thickness of concrete minimum density of 650kg/m3.
below the void for the depth of mortar. Where this Fire & Sound classification
is not the case, tubular voids should be filled with
stone wool normally the same thickness as the Steel pipes ≤ Ø40mm with ≥ 20mm stone wool
depth of the floor slab. Alternatively, simply fire seal insulation in maximum apertures
1200 x 2400mm EI 180 C/U & E 180 C/U
on both sides.
Steel pipes ≤ Ø40mm with ≥ 20mm stone wool
5. Install a stone wool shutter board to achieve the
insulation in maximum apertures
required thickness of mortar. Make sure that this
50mm stone wool 280 x 280mm EI 240 C/U & E 240 C/U
achieves a very tight seal – any small openings Steel pipes ≤ Ø219mm with ≥ 30mm stone wool
should be sealed with Protecta® FR Acrylic shutter ≥ 150kg/m3
insulation in maximum apertures
6. Pour clean water into a suitable mixing vessel and Steel pipes 1200 x 2400mm EI 90 C/U & E 180 C/U
add the mortar to obtain the required consistency. Steel pipes ≤ Ø219mm with ≥ 30mm stone wool
Mix steadily at low speed and ensure that any lumps insulation in maximum apertures
of powder are fully dispersed. Always add the mortar 280 x 280mm EI 90 C/U & E 240 C/U
to the water, do not reverse this mixing process
7. Once the desired consistency is achieved pour or Sound reduction (seal only) 48dB
trowel the mortar onto the shutter board making
sure that it flows into all corners and around
services. Apply a firm pressure to the mortar to
eliminate any trapped air bubbles. Build up to the Minimum separations and limitations
required depth. An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 30mm
from seal edges. Services within the seal do not require a minimum separation, except pipes where
combustible pipe insulation penetrates the seal and plastic pipe penetrations which should be a
minimum of 30mm from other services in the aperture. The total amount of cross sections of services Polyseam Ltd, 15 St Andrews Road,
ETA 13/0672 & 18/0855
(including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 19/8/15
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 257
Client:
Installation Instructions

1. Ensure the faces of the aperture opening are free of


dust and any other contaminants. The faces may be
Job Title:
moistened for better adhesion. Stone wool ≥ 80 kg/m3
2. Bare metal pipes passing through the seal must be to be installed ≥ 100cm Products Protecta EX Mortar
protected against corrosion using a suitable on both sides Protecta EX Mortar
primer/protection system. Minimum seal depth 100mm Application Fire stopping of insulated steel
3. The seal can be positioned to either side of the pipes in rigid floors
construction or anywhere in between.
4. When installing Protecta® EX Mortar in hollow floor Construction Minimum floor thickness of 150
slabs or boards, level the fire seal with the soffit side. mm and comprise aerated
Ensure there is sufficient thickness of concrete concrete or concrete with a
below the void for the depth of mortar. Where this minimum density of 650kg/m3.
is not the case, tubular voids should be filled with
stone wool normally the same thickness as the
depth of the floor slab. Alternatively, simply fire seal
Fire & Sound classification
on both sides.
5. Install a shutter board to achieve the required
Steel pipes ≤ Ø40mm with ≥ 20mm stone wool
thickness of mortar. Make sure that this achieves a
insulation in maximum apertures
very tight seal. 1200 x 2400mm EI 240 C/U & E 240 C/U
6. Pour clean water into a suitable mixing vessel and Steel pipes
add the mortar to obtain the required consistency. Steel pipes ≤ Ø219mm with ≥ 30mm stone wool
Mix steadily at low speed and ensure that any lumps insulation in maximum apertures
of powder are fully dispersed. Always add the mortar 1200 x 2400mm EI 120 C/U & E 240 C/U
to the water, do not reverse this mixing process
7. Once the desired consistency is achieved pour or Sound reduction (seal only)
Loadbearing Properties
trowel the mortar onto the shutter board making 48dB
sure that it flows into all corners and around Soft body impact, serviceability 500Nm. Soft body impact, safety in use 700Nm. Hard body impact
services. Apply a firm pressure to the mortar to serviceability 6Nm. Hard body impact, safety in use 10Nm. Concentrated load to 15kN on size up to
eliminate any trapped air bubbles. Build up to the 1500mm x1000mm (no failure), 4.85kN on sizes up to 1200mm x 2400mm.
required depth. Minimum separations and limitations
An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 30mm
from seal edges. Services within the seal do not require a minimum separation, except pipes where
combustible pipe insulation penetrates the seal and plastic pipe penetrations which should be a
minimum of 30mm from other services in the aperture. The total amount of cross sections of services
Polyseam Ltd, 15 St Andrews Road,
ETA 13/0672 & 18/0855 (including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 23/5/18
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 258
Client:
Installation Instructions

1. Ensure the faces of the aperture opening are free of


dust and any other contaminants. The faces may be
Job Title:
Protecta EX Mortar
moistened for better adhesion.
Minimum seal depth 50mm
2. Bare metal pipes passing through the seal must be
Maximum aperture 1200x2400mm Products Protecta EX Mortar
protected against corrosion using a suitable Stone wool shutter
primer/protection system.
3. The seal can be positioned to either side of the Application Fire stopping of un-insulated
construction or anywhere in between. copper pipes in rigid floors
4. When installing Protecta® EX Mortar in hollow floor
slabs or boards, level the fire seal with the soffit side. Construction Minimum floor thickness of 150
Ensure there is sufficient thickness of concrete mm and comprise aerated
below the void for the depth of mortar. Where this concrete or concrete with a
is not the case, tubular voids should be filled with minimum density of 650kg/m3.
stone wool normally the same thickness as the
depth of the floor slab. Alternatively, simply fire seal
on both sides.
Fire & Sound classification
5. Install a stone wool shutter board to achieve the 50mm stone wool
required thickness of mortar. Make sure that this shutter ≥ 150kg/m3
Copper pipes Copper pipes Ø6mm
achieves a very tight seal – any small openings EI 120 C/C & E 180 C/C
should be sealed with Protecta® FR Acrylic.
6. Pour clean water into a suitable mixing vessel and Copper pipes ≤ Ø15mm
add the mortar to obtain the required consistency. EI 30 C/C & E 180 C/C
Mix steadily at low speed and ensure that any lumps
of powder are fully dispersed. Always add the mortar Sound reduction (seal only)
to the water, do not reverse this mixing process 48dB
7. Once the desired consistency is achieved pour or
trowel the mortar onto the shutter board making
sure that it flows into all corners and around
services. Apply a firm pressure to the mortar to
eliminate any trapped air bubbles. Build up to the Minimum separations and limitations
required depth. An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 30mm
from seal edges. Services within the seal do not require a minimum separation, except pipes where
combustible pipe insulation penetrates the seal and plastic pipe penetrations which should be a
minimum of 30mm from other services in the aperture. The total amount of cross sections of services
Polyseam Ltd, 15 St Andrews Road,
(including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
ETA 13/0672 & 18/0855
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 23/5/18
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 259
Client:
Installation Instructions

1. Ensure the faces of the aperture opening are free of


dust and any other contaminants. The faces may be
Job Title:
moistened for better adhesion.
2. Bare metal pipes passing through the seal must be Protecta EX Mortar Products Protecta EX Mortar
protected against corrosion using a suitable Minimum seal depth 100mm
primer/protection system. Maximum aperture 1200x2400mm Application Fire stopping of un-insulated
3. The seal can be positioned to either side of the copper pipes in rigid floors
construction or anywhere in between.
4. When installing Protecta® EX Mortar in hollow floor Construction Minimum floor thickness of 150
slabs or boards, level the fire seal with the soffit side. mm and comprise aerated
Ensure there is sufficient thickness of concrete concrete or concrete with a
below the void for the depth of mortar. Where this minimum density of 650kg/m3.
is not the case, tubular voids should be filled with
stone wool normally the same thickness as the
depth of the floor slab. Alternatively, simply fire seal Fire & Sound classification
on both sides.
Copper pipes Ø6mm
5. Install a shutter board to achieve the required
EI 120 C/C & E 180 C/C
thickness of mortar. Make sure that this achieves a
very tight seal. Copper pipes
Copper pipes ≤ Ø15mm
6. Pour clean water into a suitable mixing vessel and EI 30 C/C & E 180 C/C
add the mortar to obtain the required consistency.
Mix steadily at low speed and ensure that any lumps Copper pipes ≤ Ø54mm
of powder are fully dispersed. Always add the mortar EI 20 C/C & E 120 C/C
to the water, do not reverse this mixing process
7. Once the desired consistency is achieved pour or Sound reduction (seal only)
Loadbearing Properties
trowel the mortar onto the shutter board making 48dB
sure that it flows into all corners and around Soft body impact, serviceability 500Nm. Soft body impact, safety in use 700Nm. Hard body impact
services. Apply a firm pressure to the mortar to serviceability 6Nm. Hard body impact, safety in use 10Nm. Concentrated load to 15kN on size up to
eliminate any trapped air bubbles. Build up to the 1500mm x1000mm (no failure), 4.85kN on sizes up to 1200mm x 2400mm.
required depth. Minimum separations and limitations
An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 30mm
from seal edges. Services within the seal do not require a minimum separation, except pipes where
combustible pipe insulation penetrates the seal and plastic pipe penetrations which should be a
minimum of 30mm from other services in the aperture. The total amount of cross sections of services Polyseam Ltd, 15 St Andrews Road,
ETA 13/0672 & 18/0855 (including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 23/5/18
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 260
Client:
Installation Instructions

1. Ensure the faces of the aperture opening are free of


dust and any other contaminants. The faces may be
Job Title:
Continuous elastomeric
moistened for better adhesion. or phenolic foam
2. The seal can be positioned to either side of the insulation Protecta EX Mortar
Products Protecta EX Mortar
construction or anywhere in between. Minimum seal depth 100mm
Protecta FR Pipe Wrap 25m
3. When installing Protecta® EX Mortar in hollow floor Application Fire stopping of insulated
slabs or boards, level the fire seal with the soffit side. copper pipes in rigid floors
Ensure there is sufficient thickness of concrete Construction Minimum floor thickness of 150
below the void for the depth of mortar. Where this mm and comprise aerated
is not the case, tubular voids should be filled with concrete or concrete with a
stone wool normally the same thickness as the minimum density of 650kg/m3
depth of the floor slab. Alternatively, simply fire seal
on both sides. Fire & Sound classification
4. Install a shutter board to achieve the required
thickness of mortar. Make sure that this achieves a Copper pipes ≤ Ø12mm with 9mm foam
insulation in maximum apertures
very tight seal. Protecta Pipe Wrap
1200 x 2400mm
5. Pour clean water into a suitable mixing vessel and 2 layers of 50mm wide fitted at soffit
EI 240 C/C & E 240 C/C
add the mortar to obtain the required consistency.
Mix steadily at low speed and ensure that any lumps Copper pipes
Copper pipes ≤ Ø54mm with 13 - 25mm foam
of powder are fully dispersed. Always add the mortar insulation in maximum apertures
to the water, do not reverse this mixing process 1200 x 2400mm
6. Once the desired consistency is achieved pour or EI 60 C/C & E 240 C/C
trowel the mortar onto the shutter board making
sure that it flows into all corners and around Sound reduction (seal only)
services. Apply a firm pressure to the mortar to 48dB
Loadbearing Properties
eliminate any trapped air bubbles. Build up to the
required depth. Soft body impact, serviceability 500Nm. Soft body impact, safety in use 700Nm. Hard body impact
serviceability 6Nm. Hard body impact, safety in use 10Nm. Concentrated load to 15kN on size up to
1500mm x1000mm (no failure), 4.85kN on sizes up to 1200mm x 2400mm.
Minimum separations and limitations
An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 30mm
from seal edges. Services within the seal do not require a minimum separation, except pipes where
combustible pipe insulation penetrates the seal and plastic pipe penetrations which should be a
minimum of 30mm from other services in the aperture. The total amount of cross sections of services
Polyseam Ltd, 15 St Andrews Road,
ETA 13/0672 & 18/0855 (including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 4/3/19
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 261
Client:
Installation Instructions

1. Ensure the faces of the aperture opening are free of


dust and any other contaminants. The faces may be
Job Title:
moistened for better adhesion.
2. The seal can be positioned to either side of the
Products Protecta EX Mortar
construction or anywhere in between. Continuous stone wool Stone wool shutter
3. When installing Protecta® EX Mortar in hollow floor Protecta EX Mortar
≥ 80 kg/m3 Minimum seal depth 50mm
slabs or boards, level the fire seal with the soffit side. Application Fire stopping of insulated
Ensure there is sufficient thickness of concrete copper pipes in rigid floors
below the void for the depth of mortar. Where this
is not the case, tubular voids should be filled with Construction Minimum floor thickness of 150
stone wool normally the same thickness as the mm and comprise aerated
depth of the floor slab. Alternatively, simply fire seal concrete or concrete with a
on both sides. minimum density of 650kg/m3
4. Install a stone wool shutter board to achieve the
required thickness of mortar. Make sure that this
Fire & Sound classification
achieves a very tight seal – any small openings
should be sealed with Protecta® FR Acrylic
Copper pipes ≤ Ø54mm with 20-80mm thick
5. Pour clean water into a suitable mixing vessel and
50mm stone wool stone wool insulation in maximum apertures
add the mortar to obtain the required consistency. 1200 x 2400mm
Mix steadily at low speed and ensure that any lumps shutter ≥ 150kg/m3
EI 120 C/C & E 180 C/C
of powder are fully dispersed. Always add the mortar Copper pipes
to the water, do not reverse this mixing process Sound reduction (seal only)
6. Once the desired consistency is achieved pour or 48dB
trowel the mortar onto the shutter board making
sure that it flows into all corners and around
services. Apply a firm pressure to the mortar to
eliminate any trapped air bubbles. Build up to the
required depth.

Minimum separations and limitations


An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 30mm
from seal edges. Services within the seal do not require a minimum separation, except pipes where
combustible pipe insulation penetrates the seal and plastic pipe penetrations which should be a
minimum of 30mm from other services in the aperture. The total amount of cross sections of services Polyseam Ltd, 15 St Andrews Road,
(including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
ETA 13/0672 & 18/0855
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 23/5/18
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 262
Client:
Installation Instructions

1. Ensure the faces of the aperture opening are free of


dust and any other contaminants. The faces may be
Job Title:
moistened for better adhesion.
2. The seal can be positioned to either side of the
Products Protecta EX Mortar
construction or anywhere in between. Continuous stone wool
3. When installing Protecta® EX Mortar in hollow floor Protecta EX Mortar
≥ 80 kg/m3 Minimum seal depth 100mm Application Fire stopping of insulated
slabs or boards, level the fire seal with the soffit side. copper pipes in rigid floors
Ensure there is sufficient thickness of concrete
below the void for the depth of mortar. Where this Construction Minimum floor thickness of 150
is not the case, tubular voids should be filled with mm and comprise aerated
stone wool normally the same thickness as the concrete or concrete with a
depth of the floor slab. Alternatively, simply fire seal minimum density of 650kg/m3
on both sides.
4. Install a shutter board to achieve the required
thickness of mortar. Make sure that this achieves a
Fire & Sound classification
very tight seal.
5. Pour clean water into a suitable mixing vessel and
Copper pipes ≤ Ø54mm with 20-80mm thick
add the mortar to obtain the required consistency.
stone wool insulation in maximum apertures
Mix steadily at low speed and ensure that any lumps 1200 x 2400mm
of powder are fully dispersed. Always add the mortar EI 120 C/C & E 180 C/C
to the water, do not reverse this mixing process Copper pipes
6. Once the desired consistency is achieved pour or Sound reduction (seal only)
trowel the mortar onto the shutter board making 48dB
sure that it flows into all corners and around
services. Apply a firm pressure to the mortar to Loadbearing Properties
eliminate any trapped air bubbles. Build up to the
Soft body impact, serviceability 500Nm. Soft body impact, safety in use 700Nm. Hard body impact
required depth.
serviceability 6Nm. Hard body impact, safety in use 10Nm. Concentrated load to 15kN on size up to
1500mm x1000mm (no failure), 4.85kN on sizes up to 1200mm x 2400mm.
Minimum separations and limitations
An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 30mm
from seal edges. Services within the seal do not require a minimum separation, except pipes where
combustible pipe insulation penetrates the seal and plastic pipe penetrations which should be a
minimum of 30mm from other services in the aperture. The total amount of cross sections of services Polyseam Ltd, 15 St Andrews Road,
(including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
ETA 13/0672 & 18/0855
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 23/5/18
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 263
Client:
Installation Instructions

1. Ensure the faces of the aperture opening are free of


dust and any other contaminants. The faces may be
Job Title:
moistened for better adhesion.
2. Bare metal pipes passing through the seal must be Stone wool ≥ 80 kg/m3
to be installed ≥ 100cm Products Protecta EX Mortar
protected against corrosion using a suitable Stone wool shutter
primer/protection system. on both sides Protecta EX Mortar
Minimum seal depth 50mm Application Fire stopping of insulated
3. The seal can be positioned to either side of the copper pipes in rigid floors
construction or anywhere in between. Construction Minimum floor thickness of 150
4. When installing Protecta® EX Mortar in hollow floor mm and comprise aerated
slabs or boards, level the fire seal with the soffit side. concrete or concrete with a
Ensure there is sufficient thickness of concrete minimum density of 650kg/m3.
below the void for the depth of mortar. Where this Fire & Sound classification
is not the case, tubular voids should be filled with
stone wool normally the same thickness as the Copper pipes ≤ Ø12mm with ≥ 20mm stone
depth of the floor slab. Alternatively, simply fire seal wool insulation in maximum apertures
70 x 70mm EI 240 C/C & E 240 C/C
on both sides.
5. Install a stone wool shutter board to achieve the
Copper pipes ≤ Ø54mm with ≥ 20mm stone
required thickness of mortar. Make sure that this
50mm stone wool wool insulation in maximum apertures
achieves a very tight seal – any small openings 1200 x 2400mm EI 180 C/C & E 180 C/C
should be sealed with Protecta® FR Acrylic shutter ≥ 150kg/m3
6. Pour clean water into a suitable mixing vessel and Copper pipes Copper pipes ≤ Ø54mm with ≥ 20mm stone
add the mortar to obtain the required consistency. wool insulation in maximum apertures
Mix steadily at low speed and ensure that any lumps 115 x 115mm EI 180 C/C & E 240 C/C
of powder are fully dispersed. Always add the mortar
to the water, do not reverse this mixing process Sound reduction (seal only) 48dB
7. Once the desired consistency is achieved pour or
trowel the mortar onto the shutter board making
sure that it flows into all corners and around
services. Apply a firm pressure to the mortar to
eliminate any trapped air bubbles. Build up to the Minimum separations and limitations
required depth. An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 30mm
from seal edges. Services within the seal do not require a minimum separation, except pipes where
combustible pipe insulation penetrates the seal and plastic pipe penetrations which should be a
minimum of 30mm from other services in the aperture. The total amount of cross sections of services Polyseam Ltd, 15 St Andrews Road,
ETA 13/0672 & 18/0855
(including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 20/8/15
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 264
Client:
Installation Instructions

1. Ensure the faces of the aperture opening are free of


dust and any other contaminants. The faces may be
Job Title:
moistened for better adhesion. Stone wool ≥ 80 kg/m3
2. Bare metal pipes passing through the seal must be to be installed ≥ 100cm Products Protecta EX Mortar
protected against corrosion using a suitable on both sides Protecta EX Mortar
primer/protection system. Minimum seal depth 100mm Application Fire stopping of insulated
3. The seal can be positioned to either side of the copper pipes in rigid floors
construction or anywhere in between.
4. When installing Protecta® EX Mortar in hollow floor Construction Minimum floor thickness of 150
slabs or boards, level the fire seal with the soffit side. mm and comprise aerated
Ensure there is sufficient thickness of concrete concrete or concrete with a
below the void for the depth of mortar. Where this minimum density of 650kg/m3.
is not the case, tubular voids should be filled with
stone wool normally the same thickness as the Fire & Sound classification
depth of the floor slab. Alternatively, simply fire seal
Copper pipes ≤ Ø12mm with ≥ 20mm stone
on both sides.
wool insulation in maximum apertures
5. Install a shutter board to achieve the required
1200 x 2400mm
thickness of mortar. Make sure that this achieves a
EI 240 C/C & E 240 C/C
very tight seal.
6. Pour clean water into a suitable mixing vessel and Copper pipes Copper pipes ≤ Ø54mm with ≥ 20mm stone
add the mortar to obtain the required consistency. wool insulation in maximum apertures
Mix steadily at low speed and ensure that any lumps 1200 x 2400mm
of powder are fully dispersed. Always add the mortar EI 180 C/C & E 240 C/C
to the water, do not reverse this mixing process
7. Once the desired consistency is achieved pour or Sound reduction (seal only)
Loadbearing Properties
trowel the mortar onto the shutter board making 48dB
sure that it flows into all corners and around Soft body impact, serviceability 500Nm. Soft body impact, safety in use 700Nm. Hard body impact
services. Apply a firm pressure to the mortar to serviceability 6Nm. Hard body impact, safety in use 10Nm. Concentrated load to 15kN on size up to
eliminate any trapped air bubbles. Build up to the 1500mm x1000mm (no failure), 4.85kN on sizes up to 1200mm x 2400mm.
required depth.
Minimum separations and limitations
An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 30mm
from seal edges. Services within the seal do not require a minimum separation, except pipes where
combustible pipe insulation penetrates the seal and plastic pipe penetrations which should be a
minimum of 30mm from other services in the aperture. The total amount of cross sections of services
Polyseam Ltd, 15 St Andrews Road,
ETA 13/0672 & 18/0855 (including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 23/5/18
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 265
Client:
Installation Instructions

1. Ensure the faces of the aperture opening are free of


dust and any other contaminants. The faces may be
Job Title:
Protecta EX Mortar
moistened for better adhesion.
Minimum seal depth 50mm
2. Bare metal pipes passing through the seal must be
Maximum aperture 1200x2400mm Products Protecta EX Mortar
protected against corrosion using a suitable Stone wool shutter
primer/protection system.
3. The seal can be positioned to either side of the Application Fire stopping of un-insulated
construction or anywhere in between. alupex pipes in rigid floors
4. When installing Protecta® EX Mortar in hollow floor
slabs or boards, level the fire seal with the soffit side. Construction Minimum floor thickness of 150
Ensure there is sufficient thickness of concrete mm and comprise aerated
below the void for the depth of mortar. Where this concrete or concrete with a
is not the case, tubular voids should be filled with minimum density of 650kg/m3.
stone wool normally the same thickness as the
depth of the floor slab. Alternatively, simply fire seal
on both sides.
Fire & Sound classification
5. Install a stone wool shutter board to achieve the 50mm stone wool
required thickness of mortar. Make sure that this shutter ≥ 150kg/m3
Alupex pipes Alupex pipes ≤ Ø20mm
achieves a very tight seal – any small openings EI 180 C/C & E 180 C/C
should be sealed with Protecta® FR Acrylic.
6. Pour clean water into a suitable mixing vessel and Sound reduction (seal only)
add the mortar to obtain the required consistency. 48dB
Mix steadily at low speed and ensure that any lumps
of powder are fully dispersed. Always add the mortar
to the water, do not reverse this mixing process
7. Once the desired consistency is achieved pour or
trowel the mortar onto the shutter board making
sure that it flows into all corners and around
services. Apply a firm pressure to the mortar to
eliminate any trapped air bubbles. Build up to the Minimum separations and limitations
required depth. An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 30mm
from seal edges. Services within the seal do not require a minimum separation, except pipes where
combustible pipe insulation penetrates the seal and plastic pipe penetrations which should be a
minimum of 30mm from other services in the aperture. The total amount of cross sections of services
Polyseam Ltd, 15 St Andrews Road,
(including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
ETA 13/0672 & 18/0855
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 23/5/18
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 266
Client:
Installation Instructions

1. Ensure the faces of the aperture opening are free of


dust and any other contaminants. The faces may be
Job Title:
moistened for better adhesion.
2. The seal can be positioned to either side of the
Products Protecta EX Mortar
construction or anywhere in between.
Protecta EX Mortar
3. When installing Protecta® EX Mortar in hollow floor Application Fire stopping of un-insulated
Minimum seal depth 100mm
slabs or boards, level the fire seal with the soffit side. alupex pipes in rigid floors
Ensure there is sufficient thickness of concrete
below the void for the depth of mortar. Where this Construction Minimum floor thickness of 150
is not the case, tubular voids should be filled with mm and comprise aerated
stone wool normally the same thickness as the concrete or concrete with a
depth of the floor slab. Alternatively, simply fire seal minimum density of 650kg/m3.
on both sides.
4. Install a shutter board to achieve the required
thickness of mortar. Make sure that this achieves a
Fire & Sound classification
very tight seal.
5. Pour clean water into a suitable mixing vessel and
Alupex pipes ≤ Ø20mm in maximum apertures
add the mortar to obtain the required consistency.
Alupex pipes 1200 x 2400mm
Mix steadily at low speed and ensure that any lumps EI 180 C/C & E 180 C/C
of powder are fully dispersed. Always add the mortar
to the water, do not reverse this mixing process Alupex pipes ≤ Ø75mm in maximum apertures
6. Once the desired consistency is achieved pour or 1200 x 2400mm
trowel the mortar onto the shutter board making EI 20 U/C & E 240 U/C
sure that it flows into all corners and around
services. Apply a firm pressure to the mortar to Sound reduction (seal only)
Loadbearing Properties
eliminate any trapped air bubbles. Build up to the 48dB
required depth. Soft body impact, serviceability 500Nm. Soft body impact, safety in use 700Nm. Hard body impact
serviceability 6Nm. Hard body impact, safety in use 10Nm. Concentrated load to 15kN on size up to
1500mm x1000mm (no failure), 4.85kN on sizes up to 1200mm x 2400mm.
Minimum separations and limitations
An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 30mm
from seal edges. Services within the seal do not require a minimum separation, except pipes where
combustible pipe insulation penetrates the seal and plastic pipe penetrations which should be a
minimum of 30mm from other services in the aperture. The total amount of cross sections of services Polyseam Ltd, 15 St Andrews Road,
ETA 13/0672 & 18/0855 (including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 23/5/18
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 267
Client:
Installation Instructions

1. Ensure the faces of the aperture opening are free of


dust and any other contaminants. The faces may be
Job Title:
Continuous elastomeric
moistened for better adhesion. or phenolic foam
2. The seal can be positioned to either side of the insulation Protecta EX Mortar
Products Protecta EX Mortar
construction or anywhere in between. Minimum seal depth 100mm
Protecta FR Pipe Wrap 25m
3. When installing Protecta® EX Mortar in hollow floor Application Fire stopping of insulated
slabs or boards, level the fire seal with the soffit side. alupex pipes in rigid floors
Ensure there is sufficient thickness of concrete Construction Minimum floor thickness of 150
below the void for the depth of mortar. Where this mm and comprise aerated
is not the case, tubular voids should be filled with concrete or concrete with a
stone wool normally the same thickness as the minimum density of 650kg/m3
depth of the floor slab. Alternatively, simply fire seal
on both sides. Fire & Sound classification
4. Install a shutter board to achieve the required
thickness of mortar. Make sure that this achieves a Alupex pipes ≤ Ø16mm with 9mm foam
insulation in maximum apertures
very tight seal. Protecta Pipe Wrap
1200 x 2400mm EI 240 C/C & E 240 C/C
5. Pour clean water into a suitable mixing vessel and 2 layers of 50mm wide fitted at soffit
add the mortar to obtain the required consistency.
Alupex pipes Alupex pipes ≤ Ø75mm with 13 - 25mm foam
Mix steadily at low speed and ensure that any lumps insulation in maximum apertures
of powder are fully dispersed. Always add the mortar 1200 x 2400mm EI 90 C/C & E 180 C/C
to the water, do not reverse this mixing process
6. Once the desired consistency is achieved pour or Alupex pipes ≤ Ø75mm with 9 - 13mm foam
trowel the mortar onto the shutter board making insulation in maximum apertures
sure that it flows into all corners and around 1200 x 2400mm EI 90 C/C & E 240 C/C
services. Apply a firm pressure to the mortar to
Loadbearing Properties
eliminate any trapped air bubbles. Build up to the Sound reduction (seal only) 48dB
required depth. Soft body impact, serviceability 500Nm. Soft body impact, safety in use 700Nm. Hard body impact
serviceability 6Nm. Hard body impact, safety in use 10Nm. Concentrated load to 15kN on size up to
1500mm x1000mm (no failure), 4.85kN on sizes up to 1200mm x 2400mm.
Minimum separations and limitations
An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 30mm
from seal edges. Services within the seal do not require a minimum separation, except pipes where
combustible pipe insulation penetrates the seal and plastic pipe penetrations which should be a
minimum of 30mm from other services in the aperture. The total amount of cross sections of services Polyseam Ltd, 15 St Andrews Road,
ETA 13/0672 & 18/0855 (including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 4/3/19
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 268
Client:
Installation Instructions

1. Ensure the faces of the aperture opening are free of


dust and any other contaminants. The faces may be
Job Title:
moistened for better adhesion.
2. The seal can be positioned to either side of the Stone wool ≥ 80 kg/m3
to be installed ≥ 50cm Products Protecta EX Mortar
construction or anywhere in between. Stone wool shutter
3. When installing Protecta® EX Mortar in hollow floor on both sides Protecta EX Mortar
Minimum seal depth 50mm Application Fire stopping of insulated
slabs or boards, level the fire seal with the soffit side. alupex pipes in rigid floors
Ensure there is sufficient thickness of concrete Construction Minimum floor thickness of 150
below the void for the depth of mortar. Where this mm and comprise aerated
is not the case, tubular voids should be filled with concrete or concrete with a
stone wool normally the same thickness as the minimum density of 650kg/m3.
depth of the floor slab. Alternatively, simply fire seal Fire & Sound classification
on both sides.
4. Install a stone wool shutter board to achieve the Alupex pipes ≤ Ø16mm with ≥ 20mm stone
required thickness of mortar. Make sure that this wool insulation in maximum apertures
135 x 135mm EI 240 C/C & E 240 C/C
achieves a very tight seal – any small openings
should be sealed with Protecta® FR Acrylic
Alupex pipes ≤ Ø75mm with ≥ 20mm stone
5. Pour clean water into a suitable mixing vessel and
50mm stone wool wool insulation in maximum apertures
add the mortar to obtain the required consistency. 1200 x 2400mm EI 180 C/C & E 180 C/C
Mix steadily at low speed and ensure that any lumps shutter ≥ 150kg/m3
of powder are fully dispersed. Always add the mortar Alupex pipes Alupex pipes ≤ Ø75mm with ≥ 20mm stone
to the water, do not reverse this mixing process wool insulation in maximum apertures
6. Once the desired consistency is achieved pour or 135 x 135mm EI 180 C/C & E 240 C/C
trowel the mortar onto the shutter board making
sure that it flows into all corners and around Sound reduction (seal only) 48dB
services. Apply a firm pressure to the mortar to
eliminate any trapped air bubbles. Build up to the
required depth.

Minimum separations and limitations


An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 30mm
from seal edges. Services within the seal do not require a minimum separation, except pipes where
combustible pipe insulation penetrates the seal and plastic pipe penetrations which should be a
minimum of 30mm from other services in the aperture. The total amount of cross sections of services Polyseam Ltd, 15 St Andrews Road,
ETA 13/0672 & 18/0855
(including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 20/8/15
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 269
Client:
Installation Instructions

1. Ensure the faces of the aperture opening are free of


dust and any other contaminants. The faces may be
Job Title:
moistened for better adhesion. Stone wool ≥ 80 kg/m3
2. The seal can be positioned to either side of the to be installed ≥ 50cm Products Protecta EX Mortar
construction or anywhere in between. on both sides Protecta EX Mortar
3. When installing Protecta® EX Mortar in hollow floor Minimum seal depth 100mm Application Fire stopping of insulated
slabs or boards, level the fire seal with the soffit side. alupex pipes in rigid floors
Ensure there is sufficient thickness of concrete
below the void for the depth of mortar. Where this Construction Minimum floor thickness of 150
is not the case, tubular voids should be filled with mm and comprise aerated
stone wool normally the same thickness as the concrete or concrete with a
depth of the floor slab. Alternatively, simply fire seal minimum density of 650kg/m3.
on both sides.
4. Install a shutter board to achieve the required
thickness of mortar. Make sure that this achieves a Fire & Sound classification
very tight seal.
Alupex pipes ≤ Ø16mm with ≥ 20mm stone
5. Pour clean water into a suitable mixing vessel and
wool insulation in maximum apertures
add the mortar to obtain the required consistency.
1200 x 2400mm EI 240 C/C & E 240 C/C
Mix steadily at low speed and ensure that any lumps
of powder are fully dispersed. Always add the mortar Alupex pipes Alupex pipes ≤ Ø75mm with ≥ 20mm stone
to the water, do not reverse this mixing process wool insulation in maximum apertures
6. Once the desired consistency is achieved pour or 1200 x 2400mm EI 180 C/C & E 240 C/C
trowel the mortar onto the shutter board making
sure that it flows into all corners and around Sound reduction (seal only) 48dB
services. Apply a firm pressure to the mortar to
Loadbearing Properties
eliminate any trapped air bubbles. Build up to the
required depth. Soft body impact, serviceability 500Nm. Soft body impact, safety in use 700Nm. Hard body impact
serviceability 6Nm. Hard body impact, safety in use 10Nm. Concentrated load to 15kN on size up to
1500mm x1000mm (no failure), 4.85kN on sizes up to 1200mm x 2400mm.
Minimum separations and limitations
An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 30mm
from seal edges. Services within the seal do not require a minimum separation, except pipes where
combustible pipe insulation penetrates the seal and plastic pipe penetrations which should be a
minimum of 30mm from other services in the aperture. The total amount of cross sections of services
Polyseam Ltd, 15 St Andrews Road,
ETA 13/0672 & 18/0855 (including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 23/5/18
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 270
Client:
Installation Instructions

1. Ensure the faces of the aperture opening are free of


dust and any other contaminants. The faces may be
Job Title:
moistened for better adhesion.
2. The seal can be positioned to either side of the
Products Protecta EX Mortar
construction or anywhere in between. Stone wool shutter
Protecta EX Mortar
3. When installing Protecta® EX Mortar in hollow floor Minimum seal depth 50mm Application Fire stopping of plastic pipes in
slabs or boards, level the fire seal with the soffit side. rigid floors
Ensure there is sufficient thickness of concrete Construction Minimum floor thickness of 150
below the void for the depth of mortar. Where this mm and comprise aerated
is not the case, tubular voids should be filled with concrete or concrete with a
stone wool normally the same thickness as the minimum density of 650kg/m3.
depth of the floor slab. Alternatively, simply fire seal Fire & Sound classification
on both sides.
4. Install a stone wool shutter board to achieve the PVC-U & PVC-C plastic pipes ≤ Ø40mm in
required thickness of mortar. Make sure that this maximum apertures 1200 x 2400mm
EI 120 U/C & E 120 U/C
achieves a very tight seal – any small openings
should be sealed with Protecta® FR Acrylic
PEX pipe-in-pipes ≤ Ø25mm in maximum
5. Pour clean water into a suitable mixing vessel and
50mm stone wool apertures 1200 x 2400mm
add the mortar to obtain the required consistency. EI 180 C/C & E 180 C/C
Mix steadily at low speed and ensure that any lumps shutter ≥ 150kg/m3
of powder are fully dispersed. Always add the mortar Plastic pipes PEX pipe-in-pipes ≤ Ø25mm in maximum
to the water, do not reverse this mixing process apertures 550 x 1100mm
6. Once the desired consistency is achieved pour or EI 240 C/C & E 240 C/C
trowel the mortar onto the shutter board making
sure that it flows into all corners and around Sound reduction (seal only)
services. Apply a firm pressure to the mortar to 48dB
eliminate any trapped air bubbles. Build up to the
required depth.

Minimum separations and limitations


An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 30mm
from seal edges. Services within the seal do not require a minimum separation, except pipes where
combustible pipe insulation penetrates the seal and plastic pipe penetrations which should be a
minimum of 30mm from other services in the aperture. The total amount of cross sections of services Polyseam Ltd, 15 St Andrews Road,
ETA 13/0672 & 18/0855
(including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 23/5/18
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 271
Client:
Installation Instructions

1. Ensure the faces of the aperture opening are free of


dust and any other contaminants. The faces may be
Job Title:
moistened for better adhesion.
2. The seal can be positioned to either side of the
Protecta EX Mortar Products Protecta EX Mortar
construction or anywhere in between.
3. When installing Protecta® EX Mortar in hollow floor Minimum seal depth 100mm
Maximum aperture 1200x2400mm Application Fire stopping of plastic pipes in
slabs or boards, level the fire seal with the soffit side. rigid floors
Ensure there is sufficient thickness of concrete
below the void for the depth of mortar. Where this Construction Minimum floor thickness of 150
is not the case, tubular voids should be filled with mm and comprise aerated
stone wool normally the same thickness as the concrete or concrete with a
depth of the floor slab. Alternatively, simply fire seal minimum density of 650kg/m3.
on both sides.
4. Install a shutter board to achieve the required
thickness of mortar. Make sure that this achieves a Fire & Sound classification
very tight seal.
PE, ABS, SAN+PVC & PP plastic pipes ≤ Ø40mm
5. Pour clean water into a suitable mixing vessel and
EI 120 U/C & E 120 U/C
add the mortar to obtain the required consistency.
Mix steadily at low speed and ensure that any lumps Plastic pipes
PVC-U & PVC-C plastic pipes ≤ Ø40mm
of powder are fully dispersed. Always add the mortar EI 120 U/C & E 120 U/C
to the water, do not reverse this mixing process
6. Once the desired consistency is achieved pour or PEX pipe-in-pipes ≤ Ø25mm
trowel the mortar onto the shutter board making EI 240 C/C & E 240 C/C
sure that it flows into all corners and around
services. Apply a firm pressure to the mortar to Sound reduction (seal only)
Loadbearing Properties 48dB
eliminate any trapped air bubbles. Build up to the
required depth. Soft body impact, serviceability 500Nm. Soft body impact, safety in use 700Nm. Hard body impact
serviceability 6Nm. Hard body impact, safety in use 10Nm. Concentrated load to 15kN on size up to
1500mm x1000mm (no failure), 4.85kN on sizes up to 1200mm x 2400mm.
Minimum separations and limitations
An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 30mm
from seal edges. Services within the seal do not require a minimum separation, except pipes where
combustible pipe insulation penetrates the seal and plastic pipe penetrations which should be a
minimum of 30mm from other services in the aperture. The total amount of cross sections of services
Polyseam Ltd, 15 St Andrews Road,
ETA 13/0672 & 18/0855 (including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 23/5/18
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 272
Client:
Installation Instructions

1. Ensure the faces of the aperture opening are free of


dust and any other contaminants. The faces may be
Job Title:
moistened for better adhesion.
2. The seal can be positioned to either side of the Protecta EX Mortar
Products Protecta EX Mortar
construction or anywhere in between. Minimum seal depth 100mm
Protecta FR Pipe Wrap 25m
3. When installing Protecta® EX Mortar in hollow floor Maximum aperture 1200x2400mm
slabs or boards, level the fire seal with the soffit side. Application Fire stopping of plastic pipes in
Ensure there is sufficient thickness of concrete rigid floors
below the void for the depth of mortar. Where this
is not the case, tubular voids should be filled with Construction Minimum floor thickness of 150
stone wool normally the same thickness as the mm and comprise aerated
depth of the floor slab. Alternatively, simply fire seal concrete or concrete with a
on both sides. minimum density of 650kg/m3.
4. Install a shutter board to achieve the required
thickness of mortar. Make sure that this achieves a
Fire & Sound classification
very tight seal.
5. Pour clean water into a suitable mixing vessel and
PEX pipe-in-pipes ≤ Ø54mm
add the mortar to obtain the required consistency. Protecta Pipe Wrap
Plastic pipes EI 120 C/C & E 120 C/C
Mix steadily at low speed and ensure that any lumps 2 layers of 50mm wide fitted at soffit
of powder are fully dispersed. Always add the mortar Sound reduction (seal only)
to the water, do not reverse this mixing process 48dB
6. Once the desired consistency is achieved pour or
trowel the mortar onto the shutter board making
sure that it flows into all corners and around
services. Apply a firm pressure to the mortar to Loadbearing Properties
eliminate any trapped air bubbles. Build up to the
required depth. Soft body impact, serviceability 500Nm. Soft body impact, safety in use 700Nm. Hard body impact
serviceability 6Nm. Hard body impact, safety in use 10Nm. Concentrated load to 15kN on size up to
1500mm x1000mm (no failure), 4.85kN on sizes up to 1200mm x 2400mm.
Minimum separations and limitations
An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 30mm
from seal edges. Services within the seal do not require a minimum separation, except pipes where
combustible pipe insulation penetrates the seal and plastic pipe penetrations which should be a
minimum of 30mm from other services in the aperture. The total amount of cross sections of services
Polyseam Ltd, 15 St Andrews Road,
(including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
ETA 13/0672 & 18/0855
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 4/3/19
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 273
Protecta EX Mortar Client:
Installation Instructions
Minimum seal depth 100mm
1. Ensure the faces of the aperture opening are free of Maximum aperture 1200x2400mm
dust and any other contaminants. The faces may be
Job Title:
moistened for better adhesion.
2. The seal can be positioned to either side of the
Products Protecta EX Mortar
construction or anywhere in between. Protecta FR Pipe Wrap 25m
3. When installing Protecta® EX Mortar in hollow floor
slabs or boards, level the fire seal with the soffit side. Application Fire stopping of plastic pipes in
Ensure there is sufficient thickness of concrete Protecta FR Pipe Wrap to
Plastic pipes rigid floors
below the void for the depth of mortar. Where this the bottom of the seal
is not the case, tubular voids should be filled with Construction Minimum floor thickness of 150
Services Pipe Wall Pipe Wrap Classification
stone wool normally the same thickness as the mm and comprise aerated
Thickness
depth of the floor slab. Alternatively, simply fire seal concrete or concrete with a
≤ Ø40mm PVC-U & PVC-C 1.8 – 3.7mm 50 x 1.8mm (1 layer) EI 120 U/U (E 180 U/U)
on both sides. ≤ Ø40mm PE, ABS & SAN+PVC 2.4 – 3.7mm 50 x 1.8mm (1 layer) EI 240 U/U (E 240 U/U) minimum density of 650kg/m3
4. Install a shutter board to achieve the required ≤ Ø40mm PP 1.8 – 5.5mm 50 x 1.8mm (1 layer) EI 120 U/U (E 120 U/U)
thickness of mortar. Make sure that this achieves a ≤ Ø110mm PVC-U & PVC-C 1.9 – 6.6mm 50 x 3.6mm (2 layers) EI 240 U/C (E 240 U/C)
≤ Ø110mm PE, ABS & SAN+PVC 2.5 – 10.0mm 50 x 3.6mm (2 layers) EI 120 U/C (E 120 U/C) Fire & Sound classification
very tight seal.
≤ Ø110mm PP 1.9 – 6.3mm 50 x 3.6mm (2 layers) EI 240 U/C (E 240 U/C)
5. Pour clean water into a suitable mixing vessel and
≤ Ø125mm PVC-U & PVC-C 3.5 – 7.4mm 50 x 7.2mm (4 layers) EI 120 U/C (E 120 U/C) Fire classifications in table on the left.
add the mortar to obtain the required consistency. ≤ Ø125mm PE, ABS & SAN+PVC 3.9 – 11.4mm 50 x 7.2mm (4 layers) EI 240 U/C (E 240 U/C)
Mix steadily at low speed and ensure that any lumps ≤ Ø125mm PP 3.4 – 11.4mm 50 x 7.2mm (4 layers) EI 240 U/C (E 240 U/C) Sound reduction (seal only)
of powder are fully dispersed. Always add the mortar ≤ Ø160mm PVC-U & PVC-C 4.5 – 9.5mm 50 x 10.8mm (6 layers) EI 90 C/C (E 90 C/C) 48dB
to the water, do not reverse this mixing process ≤ Ø160mm PVC-U & PVC-C 4.5mm 50 x 10.8mm (6 layers) EI 240 C/C (E 240 C/C)
6. Once the desired consistency is achieved pour or ≤ Ø160mm PVC-U & PVC-C 9.5mm 50 x 10.8mm (6 layers) EI 90 U/C (E 90 U/C)
≤ Ø160mm PE, ABS & SAN+PVC 4.9 – 14.6mm 50 x 10.8mm (6 layers) EI 120 U/C (E 120 U/C)
trowel the mortar onto the shutter board making
≤ Ø160mm PP 4.9 – 14.6mm 50 x 10.8mm (6 layers) EI 240 U/C (E 240 U/C)
sure that it flows into all corners and around ≤ Ø250mm PE, ABS & SAN+PVC 7.8mm 75 x 12.6mm (7 layers) EI 180 C/C (E 180 C/C)
services. Apply a firm pressure to the mortar to
eliminate any trapped air bubbles. Build up to the Loadbearing Properties
required depth. Soft body impact, serviceability 500Nm. Soft body impact, safety in use 700Nm. Hard body impact
serviceability 6Nm. Hard body impact, safety in use 10Nm. Concentrated load to 15kN on size up to
1500mm x1000mm (no failure), 4.85kN on sizes up to 1200mm x 2400mm.
Minimum separations and limitations
An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 30mm
from seal edges. Services within the seal do not require a minimum separation, except pipes where
combustible pipe insulation penetrates the seal and plastic pipe penetrations which should be a
minimum of 30mm from other services in the aperture. The total amount of cross sections of services
Polyseam Ltd, 15 St Andrews Road,
(including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
ETA 13/0672 & 18/0855
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 4/3/19
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 274
Protecta EX Mortar Client:
Installation Instructions
Minimum seal depth 120mm
1. Ensure the faces of the aperture opening are free of Maximum aperture 1200x2400mm
dust and any other contaminants. The faces may be
Job Title:
moistened for better adhesion.
2. The seal can be positioned to either side of the
Products Protecta EX Mortar
construction or anywhere in between. Protecta FR Pipe Wrap 25m
3. When installing Protecta® EX Mortar in hollow floor
slabs or boards, level the fire seal with the soffit side. Application Fire stopping of plastic pipes in
Ensure there is sufficient thickness of concrete Protecta FR Pipe Wrap to
Plastic pipes rigid floors
below the void for the depth of mortar. Where this the bottom of the seal
is not the case, tubular voids should be filled with Construction Minimum floor thickness of 150
Services Pipe Wall Pipe Wrap Classification
stone wool normally the same thickness as the mm and comprise aerated
Thickness
depth of the floor slab. Alternatively, simply fire seal concrete or concrete with a
Ø160mm PVC-U & PVC-C 4.5 – 9.5mm 50 x 10.8mm (6 layers) EI 120 U/C (E 120 U/C)
on both sides. ≤ Ø200mm PP 4.9 – 18.2mm 75 x 10.8mm (6 layers) EI 240 C/C (E 240 C/C) minimum density of 650kg/m3
4. Install a shutter board to achieve the required ≤ Ø315mm PVC-U & PVC-C 4.5 – 12.1mm 75 x 18.0mm (10 layers) EI 90 C/C (E 90 C/C)
thickness of mortar. Make sure that this achieves a Ø315mm PVC-U & PVC-C 7.7mm 75 x 18.0mm (10 layers) EI 120 C/C (E 120 C/C)
Fire & Sound classification
very tight seal.
5. Pour clean water into a suitable mixing vessel and
Fire classifications in table on the left.
add the mortar to obtain the required consistency.
Mix steadily at low speed and ensure that any lumps Sound reduction (seal only)
of powder are fully dispersed. Always add the mortar 48dB
to the water, do not reverse this mixing process
6. Once the desired consistency is achieved pour or
trowel the mortar onto the shutter board making
sure that it flows into all corners and around
services. Apply a firm pressure to the mortar to
eliminate any trapped air bubbles. Build up to the Loadbearing Properties
required depth. Soft body impact, serviceability 500Nm. Soft body impact, safety in use 700Nm. Hard body impact
serviceability 6Nm. Hard body impact, safety in use 10Nm. Concentrated load to 15kN on size up to
1500mm x1000mm (no failure), 4.85kN on sizes up to 1200mm x 2400mm.
Minimum separations and limitations
An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 30mm
from seal edges. Services within the seal do not require a minimum separation, except pipes where
combustible pipe insulation penetrates the seal and plastic pipe penetrations which should be a
minimum of 30mm from other services in the aperture. The total amount of cross sections of services
Polyseam Ltd, 15 St Andrews Road,
(including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
ETA 13/0672 & 18/0855
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 4/3/19
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 275
Protecta EX Mortar Client:
Installation Instructions
Minimum seal depth 150mm
1. Ensure the faces of the aperture opening are free of Maximum aperture 1200x2400mm
dust and any other contaminants. The faces may be
Job Title:
moistened for better adhesion.
2. The seal can be positioned to either side of the
Products Protecta EX Mortar
construction or anywhere in between. Protecta FR Pipe Wrap 25m
3. When installing Protecta® EX Mortar in hollow floor
slabs or boards, level the fire seal with the soffit side. Application Fire stopping of plastic pipes in
Ensure there is sufficient thickness of concrete Protecta FR Pipe Wrap to
Plastic pipes rigid floors
below the void for the depth of mortar. Where this the bottom of the seal
is not the case, tubular voids should be filled with Construction Minimum floor thickness of 150
Services Pipe Wall Pipe Wrap Classification
stone wool normally the same thickness as the mm and comprise aerated
Thickness
depth of the floor slab. Alternatively, simply fire seal concrete or concrete with a
≤ Ø40mm PVC-U & PVC-C 1.8 – 3.7mm 50 x 1.8mm (1 layer) EI 120 U/U (E 180 U/U)
on both sides. ≤ Ø40mm PE, ABS & SAN+PVC 2.4 – 3.7mm 50 x 1.8mm (1 layer) EI 240 U/U (E 240 U/U) minimum density of 650kg/m3
4. Install a shutter board to achieve the required ≤ Ø40mm PP 1.8 – 5.5mm 50 x 1.8mm (1 layer) EI 120 U/U (E 120 U/U)
thickness of mortar. Make sure that this achieves a ≤ Ø110mm PVC-U & PVC-C 1.9 – 6.8mm 50 x 7.2mm (4 layers) EI 60 U/U (E 60 U/U)
≤ Ø110mm PE, ABS & SAN+PVC 3.4 – 10.0mm 75 x 5.4mm (3 layers) EI 240 U/U (E 240 U/U) Fire & Sound classification
very tight seal.
≤ Ø110mm PP 3.7 – 10.5mm 50 x 7.2mm (4 layers) EI 240 U/U (E 240 U/U)
5. Pour clean water into a suitable mixing vessel and
≤ Ø125mm PVC-U & PVC-C 1.9 – 7.4mm 50 x 7.2mm (4 layers) EI 60 U/U (E 60 U/U) Fire classifications in table on the left.
add the mortar to obtain the required consistency. Ø125mm PVC-U & PVC-C 7.4mm 50 x 7.2mm (4 layers) EI 120 U/U (E 120 U/U)
Mix steadily at low speed and ensure that any lumps Ø125mm PE, ABS & SAN+PVC 11.4mm 50 x 7.2mm (4 layers) EI 240 U/U (E 240 U/U) Sound reduction (seal only)
of powder are fully dispersed. Always add the mortar Ø125mm PP 11.4mm 50 x 7.2mm (4 layers) EI 240 U/U (E 240 U/U) 48dB
to the water, do not reverse this mixing process Ø140mm PVC-U & PVC-C 6.5 – 8.3mm 75 x 10.8mm (6 layers) EI 30 U/U (E 120 U/U)
6. Once the desired consistency is achieved pour or Ø140mm PE, ABS & SAN+PVC 8.0 – 12.4mm 75 x 10.8mm (6 layers) EI 120 U/U (E 240 U/U)
Ø140mm PP 12.8mm 75 x 7.2mm (4 layers) EI 240 U/U (E 240 U/U)
trowel the mortar onto the shutter board making
Ø160mm PVC-U & PVC-C 9.5mm 75 x 7.2mm (4 layers) EI 30 U/U (E 120 U/U)
sure that it flows into all corners and around ≤ Ø160mm PE, ABS & SAN+PVC 4.9 – 14.6mm 75 x 7.2mm (4 layers) EI 120 U/U (E 120 U/U)
services. Apply a firm pressure to the mortar to ≤ Ø160mm PE, ABS & SAN+PVC 3.9 – 14.6mm 75 x 18.0mm (10 layers) EI 120 U/U (E 240 U/U)
eliminate any trapped air bubbles. Build up to the Ø160mm PP 14.6mm 75 x 7.2mm (4 layers) EI 240 U/U (E 240 U/U)
required depth. ≤ Ø315mm PE, ABS & SAN+PVC 4.9 – 18.7mm 75 x 18.0mm (10 layers) EI 60 C/C (E 60 C/C)
≤ Ø315mm PP 4.9 – 28.6mm 75 x 18.0mm (10 layers) EI 60 C/C (E 60 C/C)
Ø315mm PP 7.7mm 75 x 18.0mm (10 layers) EI 180 C/C (E 180 C/C)

Minimum separations and limitations


An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 30mm
from seal edges. Services within the seal do not require a minimum separation, except pipes where
combustible pipe insulation penetrates the seal and plastic pipe penetrations which should be a
minimum of 30mm from other services in the aperture. The total amount of cross sections of services
Polyseam Ltd, 15 St Andrews Road,
(including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
ETA 13/0672 & 18/0855
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 4/3/19
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 276
Protecta EX Mortar Client:
Installation Instructions
Minimum seal depth 100mm
1. Ensure the faces of the aperture opening are free of Maximum aperture 1200x2400mm
dust and any other contaminants. The faces may be
Job Title:
moistened for better adhesion.
2. The seal can be positioned to either side of the
Products Protecta EX Mortar
construction or anywhere in between. Protecta FR Pipe Wrap 25m
3. When installing Protecta® EX Mortar in hollow floor
slabs or boards, level the fire seal with the soffit side. Application Fire stopping of composite
Ensure there is sufficient thickness of concrete Protecta FR Pipe Wrap to
Composite plastic pipes plastic pipes in rigid floors
below the void for the depth of mortar. Where this the bottom of the seal
is not the case, tubular voids should be filled with Construction Minimum floor thickness of 150
Services Pipe Wrap Classification
stone wool normally the same thickness as the mm and comprise aerated
Ø 32mm Aquatherm Green SDR9 pipes 50 x 1.8mm (1 layer) EI 240 C/C (E 240 C/C)
depth of the floor slab. Alternatively, simply fire seal concrete or concrete with a
≤ Ø 110mm Aquatherm Green SDR9 pipes 50 x 3.6mm (2 layers) EI 240 C/C (E 240 C/C)
on both sides. ≤ Ø 50mm Geberit Silent-PP pipes 50 x 3.6mm (2 layers) EI 120 U/U (E 120 U/U)
minimum density of 650kg/m3
4. Install a shutter board to achieve the required ≤ Ø 110mm Geberit Silent-PP pipes 50 x 3.6mm (2 layers) EI 120 U/C (E 120 U/C)
thickness of mortar. Make sure that this achieves a ≤ Ø 110mm Polo-Kal NG pipes 50 x 3.6mm (2 layers) EI 180 U/C (E 180 U/C)
Ø 125mm Polo-Kal NG pipes 50 x 7.2mm (4 layers) EI 240 U/C (E 240 U/C) Fire & Sound classification
very tight seal.
Ø 160mm Polo-Kal NG pipes 50 x 10.8mm (6 layers) EI 240 U/C (E 240 U/C)
5. Pour clean water into a suitable mixing vessel and
≤ Ø 50mm Rehau Raupiano Plus pipes 50 x 3.6mm (2 layers) EI 120 U/U (E 120 U/U) Fire classifications in table on the left.
add the mortar to obtain the required consistency. ≤ Ø 110mm Rehau Raupiano Plus pipes 50 x 3.6mm (2 layers) EI 120 U/C (E 120 U/C)
Mix steadily at low speed and ensure that any lumps Ø 125mm Rehau Raupiano Plus pipes 50 x 7.2mm (4 layers) EI 120 U/C (E 240 U/C) Sound reduction (seal only)
of powder are fully dispersed. Always add the mortar Ø 160mm Rehau Raupiano Plus pipes 50 x 10.8mm (6 layers) EI 120 U/C (E 120 U/C) 48dB
to the water, do not reverse this mixing process ≤ Ø 50mm Wavin SiTech pipes 50 x 3.6mm (2 layers) EI 120 U/U (E 120 U/U)
6. Once the desired consistency is achieved pour or ≤ Ø 110mm Wavin SiTech pipes 50 x 3.6mm (2 layers) EI 120 U/C (E 120 U/C)
trowel the mortar onto the shutter board making
sure that it flows into all corners and around
services. Apply a firm pressure to the mortar to
eliminate any trapped air bubbles. Build up to the Loadbearing Properties
required depth. Soft body impact, serviceability 500Nm. Soft body impact, safety in use 700Nm. Hard body impact
serviceability 6Nm. Hard body impact, safety in use 10Nm. Concentrated load to 15kN on size up to
1500mm x1000mm (no failure), 4.85kN on sizes up to 1200mm x 2400mm.
Minimum separations and limitations
An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 30mm
from seal edges. Services within the seal do not require a minimum separation, except pipes where
combustible pipe insulation penetrates the seal and plastic pipe penetrations which should be a
minimum of 30mm from other services in the aperture. The total amount of cross sections of services
Polyseam Ltd, 15 St Andrews Road,
(including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
ETA 13/0672 & 18/0855
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 4/3/19
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 277
Client:
Installation Instructions
Protecta EX Mortar
1. Ensure the faces of the aperture opening are free of
dust and any other contaminants. The faces may be
Minimum seal depth 100mm Job Title:
Maximum aperture 1200x2400mm
moistened for better adhesion.
2. The seal can be positioned to either side of the
Products Protecta EX Mortar
construction or anywhere in between. Protecta FR Pipe Wrap 25m
3. When installing Protecta® EX Mortar in hollow floor
slabs or boards, level the fire seal with the soffit side. Application Fire stopping of conduits in
Ensure there is sufficient thickness of concrete rigid floors
below the void for the depth of mortar. Where this
is not the case, tubular voids should be filled with Construction Minimum floor thickness of 150
stone wool normally the same thickness as the mm and comprise aerated
depth of the floor slab. Alternatively, simply fire seal concrete or concrete with a
on both sides. minimum density of 650kg/m3
4. Install a shutter board to achieve the required
thickness of mortar. Make sure that this achieves a
Fire & Sound classification
very tight seal.
5. Pour clean water into a suitable mixing vessel and Protecta Pipe Wrap
Conduits (closed circuit 2 layers of 50mm wide fitted at soffit Conduits of PE, ABS & SAN+PVC plastic pipes
add the mortar to obtain the required consistency.
plastic pipes with cables) ≤ Ø110mm EI 60 U/C & E 120 U/C
Mix steadily at low speed and ensure that any lumps
of powder are fully dispersed. Always add the mortar Cables ≤ Ø14mm in Conduits of PVC-U & PVC-C plastic pipes
to the water, do not reverse this mixing process bundle ≤ Ø90mm ≤ Ø110mm EI 120 U/C & E 120 U/C
6. Once the desired consistency is achieved pour or
trowel the mortar onto the shutter board making Conduits of PP plastic pipes ≤ Ø110mm
sure that it flows into all corners and around EI 60 U/C & E 60 U/C
services. Apply a firm pressure to the mortar to
Loadbearing Properties Sound reduction (seal only) 48dB
eliminate any trapped air bubbles. Build up to the
required depth. Soft body impact, serviceability 500Nm. Soft body impact, safety in use 700Nm. Hard body impact
serviceability 6Nm. Hard body impact, safety in use 10Nm. Concentrated load to 15kN on size up to
1500mm x1000mm (no failure), 4.85kN on sizes up to 1200mm x 2400mm.
Minimum separations and limitations
An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 30mm
from seal edges. Services within the seal do not require a minimum separation, except pipes where
combustible pipe insulation penetrates the seal and plastic pipe penetrations which should be a
minimum of 30mm from other services in the aperture. The total amount of cross sections of services
Polyseam Ltd, 15 St Andrews Road,
ETA 13/0672 & 18/0855 (including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 4/3/19
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 278
Client:
Installation Instructions

1. Ensure the faces of the aperture opening are free of


dust and any other contaminants. The faces may be
Job Title:
Protecta FR 30mm stone wool
moistened for better adhesion. matt
Damper
2. Bare metal passing through the seal must be
Products Protecta EX Mortar
protected against corrosion using a suitable Protecta FR Damper
primer/protection system.
3. The seal can be positioned to either side of the Application Fire stopping of ventilation
construction or anywhere in between. ducts in rigid floors
4. When installing Protecta® EX Mortar in hollow floor
slabs or boards, level the fire seal with the soffit side. Construction Minimum floor thickness of 150
Ensure there is sufficient thickness of concrete mm and comprise aerated
below the void for the depth of mortar. Where this concrete or concrete with a
is not the case, tubular voids should be filled with minimum density of 650kg/m3.
stone wool normally the same thickness as the
Protecta EX Mortar Fire & Sound classification
depth of the floor slab.
Minimum seal depth 100mm
5. Install a shutter board to achieve the required
Maximum aperture 1200x2400mm ≤ Ø 400mm damper/duct with ≥ 150mm stone
thickness of mortar. Make sure that this achieves a Ventilation wool matt on the top side EI 120 & E 180
very tight seal. duct ≤ Ø 1000mm damper/duct with ≥ 500mm stone
6. Pour clean water into a suitable mixing vessel and wool matt on the top side EI 90 & E 90
add the mortar to obtain the required consistency. ≤ 600 x 1000mm damper/duct with ≥ 500mm
Mix steadily at low speed and ensure that any lumps stone wool matt on the top side EI 60 & E 90
of powder are fully dispersed. Always add the mortar ≤ 1000 x 1000mm damper/duct with ≥ 500mm
to the water, do not reverse this mixing process. stone wool matt on the top side EI 90 & E 90
7. Once the desired consistency is achieved pour or
trowel the mortar onto the shutter board making Sound reduction (seal only) 48dB
Loadbearing Properties
sure that it flows into all corners and around
Soft body impact, serviceability 500Nm. Soft body impact, safety in use 700Nm. Hard body impact
services. Apply a firm pressure to the mortar to
serviceability 6Nm. Hard body impact, safety in use 10Nm. Concentrated load to 15kN on size up to
eliminate any trapped air bubbles. Build up to the
1500mm x1000mm (no failure), 4.85kN on sizes up to 1200mm x 2400mm.
required depth.
8. Insulate the ventilation duct towards the fire seal on Minimum separations and limitations
the top side with 30mm thick stone wool matting to An aperture can include several services, and they may also be different. The minimum permitted
the length given on this page. separation between adjacent seals/apertures is 200mm. Services should be a minimum of 30mm
from seal edges. Services within the seal do not require a minimum separation, except pipes where
combustible pipe insulation penetrates the seal and plastic pipe penetrations which should be a
minimum of 30mm from other services in the aperture. The total amount of cross sections of services Polyseam Ltd, 15 St Andrews Road,
This product is certified to applicable European (EN)
standards and UL-EU Mark service requirements.
(including insulation) should not exceed 60% of the penetration area. Huddersfield, West Yorkshire, HD1 6SB
For all technical details on the products specified Tel: +44 (0) 148 4421036
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Email: post.uk@polyseam.com
product specifications without giving notice. All information contained in this document is given in good faith and is
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
be found on www.protecta.eu Sheet size: Drawn date & no:
Signed and approved: A4 27/7/17
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability Scale: Drawn by:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.
NTS K.B

P a g e | 279
Appendix V
-
Apertures with mixed services

P a g e | 280
MIXED SERVICE APERTURE
Installation Instructions Fire Classification EI 30
1. Before installing Protecta® FR Board ensure that the Sound Reduction 29 dB
surface of all service penetrations and surrounding Maximum aperture Installation details - Page 1 of 2
construction is free from all loose contaminants, 1200mm wide by
dust and grease. 600mm high Products Protecta FR Board
2. Protecta® FR Coating and Protecta® FR Acrylic are
Protecta FR Acrylic
water based, so in cases where corrosion protection 2 layers 30mm
is a problem, some metals may require a barrier FR Board 1-S Construction Minimum wall thickness of 75
between the seal and the surface prior to this mm and comprise steel studs
installation. or timber studs* lined on both
3. The coated side of the board should be flush with the faces with minimum 1 layer of
surface of the gypsum on both sides. 12.5 mm thick boards
4. When fire sealing shaft walls consisting of gypsum
only on one side, subject to authority approval,
install Protecta® FR Board on the exposed side. The Services
board should be facing the (fire) exposed side.
5. Cut the required board(s) to suit the aperture 1. Cables and cable trays
dimensions and type and size of service 2. Steel pipes
penetration(s). All exposed and cut edges of the 3. Plastic pipes
board can be sealed with Protecta® FR Coating or For full specification see page 2.
Protecta® FR Acrylic prior to fitting which will act as
an adhesive and ensure a smoke tight seal. Indoor air comfort test results
6. All joints, gaps or imperfections in the installed seal
All services and openings
must be filled with Protecta® FR Acrylic on both  French A+ – Complies
must be sealed with FR
sides.  BREEAM-NOR – Complies
Acrylic both sides
7. Protecta® FR Board can be over-painted with most  DIBt – Complies
emulsion or alkyd (gloss) paints.  M1 Protocol – Complies

Durability
Minimum separations and limitations
Y1 - Intended for use at temperatures below 0°C
An aperture can include several services, and they may also be different. The minimum permitted
with exposure to UV and humidity but no
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 25mm
exposure to rain. Includes lower classes Y2, Z1 and
from seal edges. Services within the system Protecta® FR Board seal do not require a minimum Z2.
separation, except pipes where pipe insulation penetrates the seal and plastic pipe penetrations
which should be a minimum of 30mm from other services in the aperture. The total amount of cross
sections of services (including insulation) should not exceed 60% of the penetration area.
ETA 13/0673 & 18/0855
For all technical details on the products specified
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can
product specifications without giving notice. All information contained in this document is given in good faith and is be found on http://www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is Polyseam Ltd, 15 St Andrews Road, Huddersfield,
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability West Yorkshire, HD1 6SB, United Kingdom Scale: Drawn by & date:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given. Tel: +44 (0) 1484 421 036 NTS K.B. 16/3/19

P a g e | 281
MIXED SERVICE APERTURE
Fire Classification EI 30
Sound Reduction 29 dB
List of services - Page 2 of 2
Pipe wall
Type of Services Size of Services Pipe Insulation Pipe Wraps or Coat Back
thicknesses
Cables, single or bundled, with or without cable trays ≤ Ø80mm per cable - - -

≤ Ø22mm per pipe - None -


Steel pipes C/U
≤ Ø324mm per pipe - 20-30mm thick continuous stone wool ≥ 80kg/m3 -

PVC-U and PVC-C pipes ≤ Ø32mm per pipe 1.0 – 1.8mm None None

P a g e | 282
MIXED SERVICE APERTURE
Installation Instructions Fire Classification EI 60
1. Before installing Protecta® FR Board ensure that the Sound Reduction 29 dB
surface of all service penetrations and surrounding Maximum aperture Installation details - Page 1 of 2
construction is free from all loose contaminants, 1200mm wide by
dust and grease. 600mm high
2. The board can be positioned to either side of the Products Protecta FR Board
construction or anywhere in between. Protecta FR Acrylic
3. When fire sealing shaft walls consisting of gypsum 1 layer 50mm Protecta FR Collar
FR Board 2-S Protecta ServiceCoat FR-1
only on one side, subject to authority approval,
install Protecta® FR Board on the (fire) exposed side.
Construction Minimum wall thickness of 100
4. Cut the required board(s) to suit the aperture Cables and cable trays mm and comprise steel studs
dimensions and type and size of service must be coated with or timber studs* lined on both
penetration(s). All exposed and cut edges of the Protecta Service Coat FR-1 faces with minimum 2 layers of
board can be sealed with Protecta® FR Coating or Framed aperture with 12.5 mm thick boards.
Protecta® FR Acrylic prior to fitting which will act as 2 layers of 12.5mm
an adhesive and ensure a smoke tight seal. gypsum boards
5. All joints, gaps or imperfections in the installed seal Services
must be filled with Protecta® FR Acrylic on both
Plastic pipes must be 1. Cables, cable trays and ladders
sides.
secured with Protecta 2. Steel pipes
6. Protecta® FR Board can be over-painted with most
FR Collar both sides 3. Plastic pipes
emulsion or alkyd (gloss) paints.

For full specification see page 2.


All services and openings
must be sealed with FR Indoor air comfort test results
Acrylic both sides
 French A+ – Complies
 BREEAM-NOR – Complies
 DIBt – Complies
Minimum separations and limitations  M1 Protocol – Complies

An aperture can include several services, and they may also be different. The minimum permitted Durability
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 25mm
Y1 - Intended for use at temperatures below 0°C
from seal edges. Services within the system Protecta® FR Board seal do not require a minimum
with exposure to UV and humidity but no
separation, except pipes where pipe insulation penetrates the seal and plastic pipe penetrations
exposure to rain. Includes lower classes Y2, Z1 and
which should be a minimum of 30mm from other services in the aperture. The total amount of cross Z2.
sections of services (including insulation) should not exceed 60% of the penetration area.
ETA 13/0673 & 18/0855
For all technical details on the products specified
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can
product specifications without giving notice. All information contained in this document is given in good faith and is be found on http://www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is Polyseam Ltd, 15 St Andrews Road, Huddersfield,
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability West Yorkshire, HD1 6SB, United Kingdom Scale: Drawn by & date:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given. Tel: +44 (0) 1484 421 036 NTS K.B. 16/3/19

P a g e | 283
MIXED SERVICE APERTURE
Fire Classification EI 60
Sound Reduction 29 dB
List of services - Page 2 of 2
Pipe wall
Type of Services Size of Services Pipe Insulation Pipe Collars or Coat Back
thicknesses
150mm each side with 300μ WFT Protecta
Cables, single or bundled, with or without perforated cable trays and ladders ≤ Ø80mm per cable - -
Service Coat FR-1
Steel pipes C/U ≤ Ø324mm per pipe - 20-30mm thick continuous stone wool ≥ 80kg/m3 -

PVC-U and PVC-C pipes U/C ≤ Ø110mm per pipe 1.9 – 6.6mm Protecta FR Collar 50mm high ≤ Ø110mm
None
PE, ABS and SAN+PVC pipes C/C ≤ Ø110mm per pipe 3.0 – 10.0mm with pig tail fixings on both sides

P a g e | 284
MIXED SERVICE APERTURE
Installation Instructions Fire Classification EI 60
1. Before installing Protecta® FR Board ensure that the Sound Reduction 52 dB
surface of all service penetrations and surrounding Maximum aperture Installation details - Page 1 of 4
construction is free from all loose contaminants, unlimited width by
dust and grease. 1200mm high
2. Protecta® FR Coating and Protecta® FR Acrylic are Products Protecta FR Board
water based, so in cases where corrosion protection Protecta FR Acrylic
Protecta FR Pipe Wrap 2 layers 50mm
is a problem, some metals may require a barrier Protecta FR Pipe Wrap
50mm wide fitted both FR Board 1-S
between the seal and the surface prior to this sides within the board Construction Minimum wall thickness of 100
installation. sealed off with FR Acrylic mm and comprise steel studs
3. The coated side of the board should be flush with the or timber studs* lined on both
surface of the gypsum on both sides. faces with minimum 2 layers of
4. When fire sealing shaft walls consisting of gypsum 12.5 mm thick boards.
only on one side, subject to authority approval,
install Protecta® FR Board on the exposed side. The
board should be facing the (fire) exposed side. Services
5. Cut the required board(s) to suit the aperture
dimensions and type and size of service All services and openings 1. Cables, with or without cable trays
penetration(s). All exposed and cut edges of the 2. Steel pipes
must be sealed with FR
board can be sealed with Protecta® FR Coating or 3. Copper pipes
Acrylic both sides
Protecta® FR Acrylic prior to fitting which will act as 4. Alupex pipes
5. Plastic pipes
an adhesive and ensure a smoke tight seal.
6. Composite pipes
6. All joints, gaps or imperfections in the installed seal
7. Conduits
must be filled with Protecta® FR Acrylic on both
8. Ventilation ducts
sides.
7. Protecta® FR Board can be over-painted with most For full specification see pages 2 - 4.
emulsion or alkyd (gloss) paints.
Indoor air comfort test results
Minimum separations and limitations
 French A+ – Complies
An aperture can include several services, and they may also be different. The minimum permitted  BREEAM-NOR – Complies
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 25mm  DIBt – Complies
 M1 Protocol – Complies
from seal edges. Services within the system Protecta® FR Board seal do not require a minimum
separation, except pipes where pipe insulation penetrates the seal and plastic pipe penetrations
Durability
which should be a minimum of 30mm from other services in the aperture. The total amount of cross
sections of services (including insulation) should not exceed 60% of the penetration area. Y1 - Intended for use at temperatures below 0°C
ETA 13/0673 & 18/0855
For all technical details on the products specified with exposure to UV and humidity but no
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can exposure to rain. Includes lower classes Y2, Z1 and
product specifications without giving notice. All information contained in this document is given in good faith and is be found on http://www.protecta.eu Z2.
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is Polyseam Ltd, 15 St Andrews Road, Huddersfield,
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability West Yorkshire, HD1 6SB, United Kingdom Scale: Drawn by & date:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given. Tel: +44 (0) 1484 421 036 NTS K.B. 16/3/19

P a g e | 285
MIXED SERVICE APERTURE
Fire Classification EI 60
Sound Reduction 52 dB
List of services - Page 2 of 4
Pipe wall Pipe
Type of Services Size of Services Pipe Insulation Pipe Wraps
thicknesses config
Cables, single or bundled, with or w/o trays ≤ Ø80mm per cable - - - -

Unsheathed cables/wires, with or w/o trays ≤ 185mm2 per wire - - - -

Steel or PVC conduits, with or w/o trays ≤ Ø16mm per conduit - - C/U -

≤ Ø22mm per pipe - None C/U -

≤ Ø40mm per pipe - 13mm thick continuous elastomeric or PE U/U 1 layer of 50mm wide both sides

≤ Ø165mm per pipe - 13 - 32mm thick continuous elastomeric or PE U/U 2 layers of 50mm wide both sides

Steel pipes ≤ Ø324mm per pipe - 32 - 50mm thick continuous elastomeric or PE C/U 3 layers of 50mm wide both sides

≤ Ø324mm per pipe - 20 - 80mm thick continuous stone wool ≥ 80kg/m3 C/U -

≤ Ø40mm per pipe - ≥ 20mm thick x 500mm long stone wool ≥ 80 kg/m3 both sides C/U -

≤ Ø219mm per pipe - ≥ 30mm thick x 500mm long stone wool ≥ 80 kg/m3 both sides C/U -

≤ Ø6mm per pipe - None C/C -

Copper pipes ≤ Ø54mm per pipe - 9 - 25mm thick continuous elastomeric or PE C/C 2 layers of 50mm wide both sides

≤ Ø54mm per pipe - ≥ 20mm thick x 500mm long stone wool ≥ 80 kg/m3 both sides C/C -

≤ Ø20mm per pipe - None C/C -

Alupex pipes ≤ Ø75mm per pipe - 9 - 25mm thick continuous elastomeric or PE C/C 2 layers of 50mm wide both sides

≤ Ø75mm per pipe - ≥ 20mm thick x 500mm long stone wool ≥ 80 kg/m3 both sides C/C -

≤ Ø32mm per pipe 1.0-2.4mm - U/C None

≤ Ø40mm per pipe 1.9-3.0mm - U/U 1 layer of 50mm wide both sides

≤ Ø110mm per pipe 2.7-6.6mm - U/C 2 layers of 50mm wide both sides

PVC-U & PVC-C pipes ≤ Ø125mm per pipe 3.7-7.4mm - U/C 3 layers of 50mm wide both sides

≤ Ø160mm per pipe 9.5mm - U/C 4 layers of 50mm wide both sides

≤ Ø315mm per pipe 7.7-12.1mm - C/C 10 layers of 50mm wide both sides

≤ Ø400mm per pipe 9.8-15.3mm - C/C 16 layers of 50mm wide both sides

P a g e | 286
MIXED SERVICE APERTURE
Fire Classification EI 60
Sound Reduction 52 dB
List of services - Page 3 of 4
Pipe wall Pipe
Type of Services Size of Services Pipe Insulation Pipe Wraps
thicknesses config
≤ Ø32mm per pipe 2.0-3.0mm - U/C None

≤ Ø40mm per pipe 2.4-3.7mm - U/U 1 layer of 50mm wide both sides

PE, ABS and SAN+PVC pipes ≤ Ø110mm per pipe 4.2-10.0mm - U/C 2 layers of 50mm wide both sides

≤ Ø125mm per pipe 4.8-12.0mm - U/C 3 layers of 50mm wide both sides

≤ Ø160mm per pipe 14.6mm - U/C 4 layers of 50mm wide both sides

≤ Ø32mm per pipe 1.8-2.2mm - U/C None

≤ Ø40mm per pipe 1.8-5.5mm - U/U 1 layer of 50mm wide both sides

PP pipes ≤ Ø110mm per pipe 2.7-15.1mm - U/U 2 layers of 50mm wide both sides

≤ Ø125mm per pipe 3.1-17.1mm - U/C 3 layers of 50mm wide both sides

≤ Ø160mm per pipe 21.9mm - U/C 4 layers of 50mm wide both sides

≤ Ø25mm per pipe - - C/C None

PEX pipe-in-pipes ≤ Ø54mm per pipe - - C/C 2 layers of 50mm wide both sides

≤ Ø25mm in bundles ≤ Ø50mm - - C/C 2 layers of 50mm wide both sides

Ø32mm per pipe - - C/C 1 layer of 50mm wide both sides


Aquatherm Green SDR9 pipes
≤ Ø110mm per pipe - - C/C 2 layers of 50mm wide both sides

≤ Ø50mm per pipe - - U/U 2 layers of 50mm wide both sides


BluePower pipes
≤ Ø110mm per pipe - - C/U 2 layers of 50mm wide both sides

≤ Ø50mm per pipe - - U/U 2 layers of 50mm wide both sides


Geberit Silent-PP pipes
≤ Ø110mm per pipe - - U/C 2 layers of 50mm wide both sides

≤ Ø50mm per pipe - - U/U 2 layers of 50mm wide both sides

≤ Ø110mm per pipe - - U/C 2 layers of 50mm wide both sides


Polo-Kal NG pipes
Ø125mm per pipe - - U/C 4 layers of 50mm wide both sides

Ø160mm per pipe - - U/C 6 layers of 50mm wide both sides

P a g e | 287
MIXED SERVICE APERTURE
Fire Classification EI 60
Sound Reduction 52 dB
List of services - Page 4 of 4
Pipe wall Pipe
Type of Services Size of Services Pipe Insulation Pipe Wraps
thicknesses config
≤ Ø50mm per pipe - - U/U 2 layers of 50mm wide both sides

≤ Ø110mm per pipe - - U/C 2 layers of 50mm wide both sides


Rehau Raupiano Plus pipes
Ø125mm per pipe - - U/C 4 layers of 50mm wide both sides

Ø160mm per pipe - - U/C 6 layers of 50mm wide both sides

≤ Ø50mm per pipe - - U/U 2 layers of 50mm wide both sides


Wavin SiTech pipes
≤ Ø110mm per pipe - - U/C 2 layers of 50mm wide both sides

Conduits of PVC-U & PVC-C pipes ≤ Ø110mm w/cables ≤ Ø14mm 2.7-6.6mm - U/C 2 layers of 50mm wide both sides

Conduits of PE, ABS & SAN+PVC pipes ≤ Ø110mm w/cables ≤ Ø14mm 4.2-10.0mm - U/C 2 layers of 50mm wide both sides

Conduits of PP pipe ≤ Ø110mm w/cables ≤ Ø14mm 2.7-15.1mm - U/C 2 layers of 50mm wide both sides

≤ Ø400mm - ≥ 30mm thick x 20cm long stonewool mat ≥80kg/m3 both sides - Protecta FR Damper

Ventilation ducts ≤ Ø1250mm - ≥ 30mm thick x 50cm long stonewool mat ≥80kg/m3 both sides - Protecta FR Damper

≤ 1200mm high x 1700mm w - ≥ 30mm thick x 50cm long stonewool mat ≥80kg/m3 both sides - Protecta FR Damper

P a g e | 288
MIXED SERVICE APERTURE
Installation Instructions Fire Classification EI 60
1. Before installing Protecta® FR Board ensure that the Sound Reduction 29 dB
surface of all service penetrations and surrounding Installation details - Page 1 of 2
construction is free from all loose contaminants, Maximum aperture
dust and grease. unlimited width by
1200mm high 1 layer 60mm Products Protecta FR Board
2. Protecta® FR Coating and Protecta® FR Acrylic are
FR Board 2-S Protecta FR Acrylic
water based, so in cases where corrosion protection Protecta FR Collar
is a problem, some metals may require a barrier Protecta ServiceCoat FR-1
between the seal and the surface prior to this Cables and cable trays
installation. coated with Protecta Construction Minimum wall thickness of 100
3. The board can be positioned to either side of the Service Coat FR-1 mm and comprise concrete,
construction or anywhere in between. aerated concrete or masonry,
4. Cut the required board(s) to suit the aperture with a density of ≥ 650 kg/m3
dimensions and type and size of service
penetration(s). All exposed and cut edges of the
board can be sealed with Protecta® FR Coating or Services
Protecta® FR Acrylic prior to fitting which will act as
1. Cables, cable trays and ladders
an adhesive and ensure a smoke tight seal.
5. All joints, gaps or imperfections in the installed seal Plastic pipes secured 2. Steel pipes
must be filled with Protecta® FR Acrylic on both with Protecta FR
Collar both sides 3. Copper pipes
sides.
6. Protecta® FR Board can be over-painted with most 4. Alupex pipes
emulsion or alkyd (gloss) paints.
5. Plastic pipes
All services and openings
For full specification see page 2.
must be sealed with FR
Acrylic both sides
Indoor air comfort test results

 French A+ – Complies
 BREEAM-NOR – Complies
 DIBt – Complies
Minimum separations and limitations
 M1 Protocol – Complies
An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 25mm Durability
from seal edges. Services within the system Protecta® FR Board seal do not require a minimum
Y1 - Intended for use at temperatures below 0°C
separation, except pipes where pipe insulation penetrates the seal and plastic pipe penetrations
with exposure to UV and humidity but no
which should be a minimum of 30mm from other services in the aperture. The total amount of cross exposure to rain. Includes lower classes Y2, Z1 and
ETA 13/0673 & 18/0855 sections of services (including insulation) should not exceed 60% of the penetration area. Z2.
For all technical details on the products specified
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can
product specifications without giving notice. All information contained in this document is given in good faith and is be found on http://www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is Polyseam Ltd, 15 St Andrews Road, Huddersfield,
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability West Yorkshire, HD1 6SB, United Kingdom Scale: Drawn by & date:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given. Tel: +44 (0) 1484 421 036 NTS K.B. 16/3/19

P a g e | 289
MIXED SERVICE APERTURE
Fire Classification EI 60
Sound Reduction 29 dB
List of services - Page 2 of 2
Pipe wall Pipe
Type of Services Size of Services Pipe Insulation Collars or Coat Back
thicknesses config
Cables ≤ Ø21mm per cable - - - None
Cables single or bundled, with or without 150mm each side with 300μ WFT
≤ Ø80mm per cable - - -
perforated cable trays and ladders Protecta Service Coat FR-1
≤ Ø324mm per pipe - 20 - 30mm thick continuous stone wool ≥ 80kg/m3 C/U -

Steel pipes ≤ Ø40mm per pipe - ≥ 20mm thick x 100cm long stone wool ≥ 80 kg/m3 both sides C/U -

≤ Ø219mm per pipe - ≥ 30mm thick x 100cm long stone wool ≥ 80 kg/m3 both sides C/U -

Copper pipes ≤ Ø54mm per pipe - ≥ 20mm thick x 100cm long stone wool ≥ 80 kg/m3 both sides C/U -

Alupex pipes ≤ Ø75mm per pipe - ≥ 30mm thick x 60cm long stone wool ≥ 80 kg/m3 both sides C/C -

PVC-U and PVC-C pipes ≤ Ø110mm per pipe 1.9 – 6.6mm - U/C Protecta FR Collar 50mm high
PE, ABS and SAN+PVC pipes ≤ Ø110mm per pipe 3.0 – 10.0mm - C/C ≤ Ø110mm with pig tail fixings

P a g e | 290
MIXED SERVICE APERTURE
Installation Instructions Fire Classification E 120
1. Before installing Protecta® FR Board ensure that the Sound Reduction 29 dB
surface of all service penetrations and surrounding Installation details - Page 1 of 2
construction is free from all loose contaminants, Maximum aperture
dust and grease. unlimited width by
1 layer 60mm Products Protecta FR Board
2. Protecta® FR Coating and Protecta® FR Acrylic are 1200mm high
FR Board 2-S Protecta FR Acrylic
water based, so in cases where corrosion protection Protecta FR Pipe Wrap
is a problem, some metals may require a barrier
Protecta FR Pipe Wrap
between the seal and the surface prior to this Construction Minimum wall thickness of 150
50mm wide fitted
installation. mm and comprise concrete,
within the board sealed
3. The board can be positioned to either side of the aerated concrete or masonry,
off with FR Acrylic both
construction or anywhere in between. with a density of ≥ 650 kg/m3
sides
4. Cut the required board(s) to suit the aperture
dimensions and type and size of service
penetration(s). All exposed and cut edges of the
board can be sealed with Protecta® FR Coating or Services
Protecta® FR Acrylic prior to fitting which will act as
1. Cables
an adhesive and ensure a smoke tight seal.
5. All joints, gaps or imperfections in the installed seal 2. Steel pipes
must be filled with Protecta® FR Acrylic on both
3. Copper pipes
sides.
6. Protecta® FR Board can be over-painted with most 4. Alupex pipes
All services and openings
emulsion or alkyd (gloss) paints.
must be sealed with FR For full specification see page 2.
Acrylic both sides
Indoor air comfort test results

 French A+ – Complies
 BREEAM-NOR – Complies
 DIBt – Complies
 M1 Protocol – Complies
Minimum separations and limitations
Durability
An aperture can include several services, and they may also be different. The minimum permitted
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 25mm Y1 - Intended for use at temperatures below 0°C
from seal edges. Services within the system Protecta® FR Board seal do not require a minimum with exposure to UV and humidity but no
separation, except pipes where pipe insulation penetrates the seal and plastic pipe penetrations exposure to rain. Includes lower classes Y2, Z1 and
which should be a minimum of 30mm from other services in the aperture. The total amount of cross Z2.
ETA 13/0673 & 18/0855 sections of services (including insulation) should not exceed 60% of the penetration area.
For all technical details on the products specified
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can
product specifications without giving notice. All information contained in this document is given in good faith and is be found on http://www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is Polyseam Ltd, 15 St Andrews Road, Huddersfield,
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability West Yorkshire, HD1 6SB, United Kingdom Scale: Drawn by & date:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given. Tel: +44 (0) 1484 421 036 NTS K.B. 7/4/19

P a g e | 291
MIXED SERVICE APERTURE
Fire Classification E 120
Sound Reduction 29 dB
List of services - Page 2 of 2
Pipe wall Pipe
Type of Services Size of Services Pipe Insulation Pipe Wraps
thicknesses config
Cables ≤ Ø21mm per cable - - - None

≤ Ø165mm per pipe - 9 - 25mm thick continuous elastomeric or PE C/U 1 layer of 50mm wide

≤ Ø324mm per pipe - 30mm thick continuous stone wool ≥ 80kg/m3 C/U -
Steel pipes
≤ Ø40mm per pipe - ≥ 20mm thick x 100cm long stone wool ≥ 80 kg/m3 both sides C/U -

≤ Ø219mm per pipe - ≥ 30mm thick x 100cm long stone wool ≥ 80 kg/m3 both sides C/U -

Copper pipes ≤ Ø54mm per pipe - ≥ 20mm thick x 100cm long stone wool ≥ 80 kg/m3 both sides C/U -

Alupex pipes ≤ Ø75mm per pipe - ≥ 30mm thick x 60cm long stone wool ≥ 80 kg/m3 both sides C/C -

P a g e | 292
MIXED SERVICE APERTURE
Installation Instructions Fire Classification EI 60
1. Before installing Protecta® FR Board ensure that the Sound Reduction 52 dB
surface of all service penetrations and surrounding Maximum aperture
unlimited width by
Installation details - Page 1 of 4
construction is free from all loose contaminants,
dust and grease. 1200mm high
2 layers 50mm Products Protecta FR Board
2. Protecta® FR Coating and Protecta® FR Acrylic are
FR Board 1-S Protecta FR Acrylic
water based, so in cases where corrosion protection Protecta FR Pipe Wrap
Protecta FR Pipe Wrap
is a problem, some metals may require a barrier 50mm wide fitted both
between the seal and the surface prior to this sides within the board Construction Minimum wall thickness of 100
installation. sealed off with FR Acrylic mm and comprise concrete,
3. The boards should be flush with the surface of the aerated concrete or masonry,
construction on both sides to maximize the fire with a density of ≥ 650 kg/m3
resistance.
4. Cut the required board(s) to suit the aperture
dimensions and type and size of service Services
penetration(s). All exposed and cut edges of the
board can be sealed with Protecta® FR Coating or 1. Cables, with or without cable trays
Protecta® FR Acrylic prior to fitting which will act as 2. Steel pipes
an adhesive and ensure a smoke tight seal. 3. Copper pipes
4. Alupex pipes
5. All joints, gaps or imperfections in the installed seal
5. Plastic pipes
must be filled with Protecta® FR Acrylic on both
6. Composite pipes
sides.
7. Conduits
6. Protecta® FR Board can be over-painted with most 8. Ventilation ducts
All services and openings
emulsion or alkyd (gloss) paints.
must be sealed with FR
Acrylic both sides For full specification see pages 2 - 4.

Indoor air comfort test results

Minimum separations and limitations  French A+ – Complies


 BREEAM-NOR – Complies
An aperture can include several services, and they may also be different. The minimum permitted  DIBt – Complies
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 25mm  M1 Protocol – Complies
from seal edges. Services within the system Protecta® FR Board seal do not require a minimum
separation, except pipes where pipe insulation penetrates the seal and plastic pipe penetrations Durability
which should be a minimum of 30mm from other services in the aperture. The total amount of cross
sections of services (including insulation) should not exceed 60% of the penetration area. Y1 - Intended for use at temperatures below 0°C
ETA 13/0673 & 18/0855 with exposure to UV and humidity but no
For all technical details on the products specified exposure to rain. Includes lower classes Y2, Z1 and
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can Z2.
product specifications without giving notice. All information contained in this document is given in good faith and is be found on http://www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is Polyseam Ltd, 15 St Andrews Road, Huddersfield,
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability West Yorkshire, HD1 6SB, United Kingdom Scale: Drawn by & date:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given. Tel: +44 (0) 1484 421 036 NTS K.B. 16/3/19

P a g e | 293
MIXED SERVICE APERTURE
Fire Classification EI 60
Sound Reduction 52 dB
List of services - Page 2 of 4
Pipe wall Pipe
Type of Services Size of Services Pipe Insulation Pipe Wraps
thicknesses config
Cables, single or bundled, with or w/o trays ≤ Ø80mm per cable - - - -

Unsheathed cables/wires, with or w/o trays ≤ 185mm2 per wire - - - -

Steel or PVC conduits, with or w/o trays ≤ Ø16mm per conduit - - C/U -

≤ Ø22mm per pipe - None C/U -

≤ Ø40mm per pipe - 13mm thick continuous elastomeric or PE U/U 1 layer of 50mm wide both sides

≤ Ø165mm per pipe - 13 - 32mm thick continuous elastomeric or PE U/U 2 layers of 50mm wide both sides

Steel pipes ≤ Ø324mm per pipe - 32 - 50mm thick continuous elastomeric or PE C/U 3 layers of 50mm wide both sides

≤ Ø324mm per pipe - 20 - 80mm thick continuous stone wool ≥ 80kg/m3 C/U -

≤ Ø40mm per pipe - ≥ 20mm thick x 500mm long stone wool ≥ 80 kg/m3 both sides C/U -

≤ Ø219mm per pipe - ≥ 30mm thick x 500mm long stone wool ≥ 80 kg/m3 both sides C/U -

≤ Ø6mm per pipe - None C/C -

Copper pipes ≤ Ø54mm per pipe - 9 - 25mm thick continuous elastomeric or PE C/C 2 layers of 50mm wide both sides

≤ Ø54mm per pipe - ≥ 20mm thick x 500mm long stone wool ≥ 80 kg/m3 both sides C/C -

≤ Ø20mm per pipe - None C/C -

Alupex pipes ≤ Ø75mm per pipe - 9 - 25mm thick continuous elastomeric or PE C/C 2 layers of 50mm wide both sides

≤ Ø75mm per pipe - ≥ 20mm thick x 500mm long stone wool ≥ 80 kg/m3 both sides C/C -

≤ Ø32mm per pipe 1.0-2.4mm - U/C None

≤ Ø40mm per pipe 1.9-3.0mm - U/U 1 layer of 50mm wide both sides

≤ Ø110mm per pipe 2.7-6.6mm - U/C 2 layers of 50mm wide both sides

PVC-U & PVC-C pipes ≤ Ø125mm per pipe 3.7-7.4mm - U/C 3 layers of 50mm wide both sides

≤ Ø160mm per pipe 9.5mm - U/C 4 layers of 50mm wide both sides

≤ Ø315mm per pipe 7.7-12.1mm - C/C 10 layers of 50mm wide both sides

≤ Ø400mm per pipe 9.8-15.3mm - C/C 16 layers of 50mm wide both sides

P a g e | 294
MIXED SERVICE APERTURE
Fire Classification EI 60
Sound Reduction 52 dB
List of services - Page 3 of 4
Pipe wall Pipe
Type of Services Size of Services Pipe Insulation Pipe Wraps
thicknesses config
≤ Ø32mm per pipe 2.0-3.0mm - U/C None

≤ Ø40mm per pipe 2.4-3.7mm - U/U 1 layer of 50mm wide both sides

PE, ABS and SAN+PVC pipes ≤ Ø110mm per pipe 4.2-10.0mm - U/C 2 layers of 50mm wide both sides

≤ Ø125mm per pipe 4.8-12.0mm - U/C 3 layers of 50mm wide both sides

≤ Ø160mm per pipe 14.6mm - U/C 4 layers of 50mm wide both sides

≤ Ø32mm per pipe 1.8-2.2mm - U/C None

≤ Ø40mm per pipe 1.8-5.5mm - U/U 1 layer of 50mm wide both sides

PP pipes ≤ Ø110mm per pipe 2.7-15.1mm - U/U 2 layers of 50mm wide both sides

≤ Ø125mm per pipe 3.1-17.1mm - U/C 3 layers of 50mm wide both sides

≤ Ø160mm per pipe 21.9mm - U/C 4 layers of 50mm wide both sides

≤ Ø25mm per pipe - - C/C None

PEX pipe-in-pipes ≤ Ø54mm per pipe - - C/C 2 layers of 50mm wide both sides

≤ Ø25mm in bundles ≤ Ø50mm - - C/C 2 layers of 50mm wide both sides

Ø32mm per pipe - - C/C 1 layer of 50mm wide both sides


Aquatherm Green SDR9 pipes
≤ Ø110mm per pipe - - C/C 2 layers of 50mm wide both sides

≤ Ø50mm per pipe - - U/U 2 layers of 50mm wide both sides


BluePower pipes
≤ Ø110mm per pipe - - C/U 2 layers of 50mm wide both sides

≤ Ø50mm per pipe - - U/U 2 layers of 50mm wide both sides


Geberit Silent-PP pipes
≤ Ø110mm per pipe - - U/C 2 layers of 50mm wide both sides

≤ Ø50mm per pipe - - U/U 2 layers of 50mm wide both sides

≤ Ø110mm per pipe - - U/C 2 layers of 50mm wide both sides


Polo-Kal NG pipes
Ø125mm per pipe - - U/C 4 layers of 50mm wide both sides

Ø160mm per pipe - - U/C 6 layers of 50mm wide both sides

P a g e | 295
MIXED SERVICE APERTURE
Fire Classification EI 60
Sound Reduction 52 dB
List of services - Page 4 of 4
Pipe wall Pipe
Type of Services Size of Services Pipe Insulation Pipe Wraps
thicknesses config
≤ Ø50mm per pipe - - U/U 2 layers of 50mm wide both sides

≤ Ø110mm per pipe - - U/C 2 layers of 50mm wide both sides


Rehau Raupiano Plus pipes
Ø125mm per pipe - - U/C 4 layers of 50mm wide both sides

Ø160mm per pipe - - U/C 6 layers of 50mm wide both sides

≤ Ø50mm per pipe - - U/U 2 layers of 50mm wide both sides


Wavin SiTech pipes
≤ Ø110mm per pipe - - U/C 2 layers of 50mm wide both sides

Conduits of PVC-U & PVC-C pipes ≤ Ø110mm w/cables ≤ Ø14mm 2.7-6.6mm - U/C 2 layers of 50mm wide both sides

Conduits of PE, ABS & SAN+PVC pipes ≤ Ø110mm w/cables ≤ Ø14mm 4.2-10.0mm - U/C 2 layers of 50mm wide both sides

Conduits of PP pipe ≤ Ø110mm w/cables ≤ Ø14mm 2.7-15.1mm - U/C 2 layers of 50mm wide both sides

≤ Ø400mm - ≥ 30mm thick x 20cm long stonewool mat ≥80kg/m3 both sides - Protecta FR Damper

Ventilation ducts ≤ Ø1250mm - ≥ 30mm thick x 50cm long stonewool mat ≥80kg/m3 both sides - Protecta FR Damper

≤ 1200mm high x 1700mm w - ≥ 30mm thick x 50cm long stonewool mat ≥80kg/m3 both sides - Protecta FR Damper

P a g e | 296
MIXED SERVICE APERTURE
Installation Instructions Fire Classification EI 120
1. Before installing Protecta® FR Board ensure that the Maximum aperture Sound Reduction 52 dB
surface of all service penetrations and surrounding unlimited width by Installation details - Page 1 of 3
construction is free from all loose contaminants, 1200mm high
dust and grease. 2 layers 60mm
Products Protecta FR Board
2. Protecta® FR Coating and Protecta® FR Acrylic are Protecta FR Pipe Wrap FR Board 2-S
Protecta FR Acrylic
water based, so in cases where corrosion protection 50mm wide fitted both Protecta FR Pipe Wrap
is a problem, some metals may require a barrier sides within the board
between the seal and the surface prior to this sealed off with FR Acrylic Construction Minimum wall thickness of 150
installation. mm and comprise concrete,
3. The boards should be flush with the surface of the aerated concrete or masonry,
construction on both sides to maximize the fire with a density of ≥ 650 kg/m3
resistance. If this is not possible, there should be an
air gap of at least 30mm between the boards. Services
4. Cut the required board(s) to suit the aperture
dimensions and type and size of service 1. Cables, with or without cable trays
penetration(s). All exposed and cut edges of the 2. Steel pipes
board can be sealed with Protecta® FR Coating or 3. Copper pipes
Protecta® FR Acrylic prior to fitting which will act as 4. Alupex pipes
an adhesive and ensure a smoke tight seal. 5. Plastic pipes
5. All joints, gaps or imperfections in the installed seal 6. Composite pipes
must be filled with Protecta® FR Acrylic on both 7. Conduits
sides. All services and openings 8. Ventilation ducts
6. Protecta® FR Board can be over-painted with most must be sealed with FR
For full specification see pages 2 - 3.
emulsion or alkyd (gloss) paints. Acrylic both sides
Indoor air comfort test results

 French A+ – Complies
 BREEAM-NOR – Complies
 DIBt – Complies
Minimum separations and limitations  M1 Protocol – Complies
An aperture can include several services, and they may also be different. The minimum permitted
Durability
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 25mm
from seal edges. Services within the system Protecta® FR Board seal do not require a minimum Y1 - Intended for use at temperatures below 0°C
separation, except pipes where pipe insulation penetrates the seal and plastic pipe penetrations with exposure to UV and humidity but no
which should be a minimum of 30mm from other services in the aperture. The total amount of cross exposure to rain. Includes lower classes Y2, Z1 and
ETA 13/0673 & 18/0855 sections of services (including insulation) should not exceed 60% of the penetration area. Z2.
For all technical details on the products specified
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can
product specifications without giving notice. All information contained in this document is given in good faith and is be found on http://www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is Polyseam Ltd, 15 St Andrews Road, Huddersfield,
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability West Yorkshire, HD1 6SB, United Kingdom Scale: Drawn by & date:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given. Tel: +44 (0) 1484 421 036 NTS K.B. 16/3/19

P a g e | 297
MIXED SERVICE APERTURE
Fire Classification EI 120
Sound Reduction 52 dB
List of services - Page 2 of 3
Pipe wall Pipe
Type of Services Size of Services Pipe Insulation Pipe Wraps
thicknesses config
Cables, single or bundled ≤ Ø21mm per cable - - - -

≤ Ø21mm cables in bundles ≤ Ø100mm - - - -

≤ Ø16mm PVC conduits - - C/U -


Cables in tied bundles and conduits on trays
≤ 200 mm ladders - - - -

≤ 500 mm non perforated trays - - - -

≤ Ø40mm per pipe - 13mm thick continuous elastomeric or PE U/U 1 layer of 50mm wide both sides

≤ Ø324mm per pipe - 20 - 80mm thick continuous stone wool ≥ 80kg/m3 C/U -
Steel pipes
≤ Ø40mm per pipe - ≥ 20mm thick x 50cm long stone wool ≥ 80 kg/m3 both sides C/U -

≤ Ø219mm per pipe - ≥ 30mm thick x 100cm long stone wool ≥ 80 kg/m3 both sides C/U -

≤ Ø12mm per pipe - 9mm thick continuous elastomeric or PE C/C 2 layers of 50mm wide both sides

Copper pipes ≤ Ø54mm per pipe - ≥ 20mm thick x 50cm long stone wool ≥ 80 kg/m3 both sides C/C -

≤ Ø54mm per pipe - ≥ 20mm thick x 100cm long stone wool ≥ 80 kg/m3 both sides C/U -

≤ Ø20mm per pipe - None C/C -

≤ Ø75mm per pipe - 9 - 25mm thick continuous elastomeric or PE C/C 2 layers of 50mm wide both sides
Alupex pipes
≤ Ø16mm per pipe - ≥ 20mm thick x 60cm long stone wool ≥ 80 kg/m3 both sides U/C -

≤ Ø75mm per pipe - ≥ 30mm thick x 60cm long stone wool ≥ 80 kg/m3 both sides C/C -

≤ Ø40mm per pipe 1.9-3.0mm - U/U 1 layer of 50mm wide both sides

≤ Ø110mm per pipe 2.7-6.6mm - U/C 2 layers of 50mm wide both sides

≤ Ø125mm per pipe 4.7-7.4mm - U/C 4 layers of 50mm wide both sides

≤ Ø160mm per pipe 4.0-9.5mm - U/C 6 layers of 50mm wide both sides
PVC-U & PVC-C pipes
≤ Ø200mm per pipe 5.0-10.2mm - C/C 10 layers of 75mm wide both sides

≤ Ø250mm per pipe 6.0-11.0mm - C/C 10 layers of 75mm wide both sides

≤ Ø315mm per pipe 7.7-12.1mm - C/C 10 layers of 75mm wide both sides

≤ Ø400mm per pipe 9.8-15.3mm - C/C 16 layers of 75mm wide both sides

P a g e | 298
MIXED SERVICE APERTURE
Fire Classification EI 120
Sound Reduction 52 dB
List of services - Page 3 of 3
Pipe wall Pipe
Type of Services Size of Services Pipe Insulation Pipe Wraps
thicknesses config
≤ Ø40mm per pipe 2.4-3.7mm - U/U 1 layer of 50mm wide both sides

≤ Ø40mm per pipe 3.8-4.6mm - U/C 1 layer of 50mm wide both sides

PE, ABS and SAN+PVC pipes ≤ Ø110mm per pipe 3.4-10.0mm - U/C 2 layers of 50mm wide both sides

≤ Ø125mm per pipe 3.9-7.4mm - U/C 4 layers of 50mm wide both sides

≤ Ø160mm per pipe 4.9-9.5mm - U/C 6 layers of 50mm wide both sides

≤ Ø40mm per pipe 1.8-5.5mm - U/U 1 layer of 50mm wide both sides

≤ Ø110mm per pipe 2.7-10.0mm - C/C 2 layers of 50mm wide both sides
PP pipes
≤ Ø125mm per pipe 3.1-11.4mm - C/C 4 layers of 50mm wide both sides

≤ Ø160mm per pipe 4.9-14.6mm - C/C 6 layers of 50mm wide both sides

PEX pipe-in-pipes ≤ Ø54mm per pipe - - C/C 2 layers of 50mm wide both sides

≤ Ø50mm per pipe - - U/U 2 layers of 50mm wide both sides


Geberit Silent-PP pipes
≤ Ø110mm per pipe - - U/C 2 layers of 50mm wide both sides

≤ Ø50mm per pipe - - U/U 2 layers of 50mm wide both sides

≤ Ø110mm per pipe - - U/C 2 layers of 50mm wide both sides


Polo-Kal NG pipes
Ø125mm per pipe - - U/C 4 layers of 50mm wide both sides

Ø160mm per pipe - - U/C 6 layers of 50mm wide both sides

≤ Ø50mm per pipe - - U/U 2 layers of 50mm wide both sides

≤ Ø110mm per pipe - - U/C 2 layers of 50mm wide both sides


Rehau Raupiano Plus pipes
Ø125mm per pipe - - U/C 4 layers of 50mm wide both sides

Ø160mm per pipe - - U/C 6 layers of 50mm wide both sides

≤ Ø400mm - ≥ 30mm thick x 20cm long stonewool mat ≥80kg/m3 both sides - Protecta FR Damper
Ventilation ducts
≤ 600mm high x 1000mm wide - ≥ 30mm thick x 50cm long stonewool mat ≥80kg/m3 both sides - Protecta FR Damper

P a g e | 299
MIXED SERVICE APERTURE
Installation Instructions Fire Classification EI 60
1. Ensure the faces of the aperture opening are free of Sound Reduction 48 dB
Maximum aperture
dust and any other contaminants. The faces may be
1200 x 2400mm Installation details - Page 1 of 2
moistened for better adhesion.
2. Bare metal passing through the seal must be
protected against corrosion using a suitable Products Protecta EX Mortar
Protecta EX Mortar Stone wool shutter
primer/protection system.
3. The seal can be positioned to either side of the Minimum seal depth 50mm
Construction Minimum floor thickness of 150
construction or anywhere in between. mm and comprise aerated
4. When installing Protecta® EX Mortar in hollow floor concrete or concrete with a
slabs or boards, level the fire seal with the soffit side. minimum density of 650kg/m3
Ensure there is sufficient thickness of concrete
below the void for the depth of mortar. Where this
is not the case, tubular voids should be filled with
Services
stone wool normally the same thickness as the
depth of the floor slab. Alternatively, simply fire seal
1. Cables and cable trays
on both sides.
5. Install a stone wool shutter board to achieve the 2. Steel pipes
required thickness of mortar. Make sure that this 3. Copper pipes
achieves a very tight seal – any small openings
should be sealed with Protecta® FR Acrylic 4. Alupex pipes
6. Pour clean water into a suitable mixing vessel and 5. Plastic pipes
pour enough mortar to obtain the required
consistency. Mix well to avoid lumps. Always add the 50mm stone wool
mortar to the water, do not reverse this mixing shutter ≥ 150kg/m3 For full specification see page 2.
process.
7. Once the desired consistency is achieved pour or
trowel the mortar onto the shutter board making Indoor air comfort test results
sure that it flows into all corners and around
services. Apply a firm pressure to the mortar to  EMICODE EC 1PLUS – Complies
eliminate any trapped air bubbles. Build up to the  BREEAM-NOR – Complies
required depth. Minimum separations and limitations  DIBt – Complies
An aperture can include several services, and they may also be different. The minimum permitted  LEED – Complies
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 30mm
from seal edges. Services within the seal do not require a minimum separation, except pipes where Durability
combustible pipe insulation penetrates the seal and plastic pipe penetrations which should be a
minimum of 30mm from other services in the aperture. The total amount of cross sections of services Z2 - Intended for use in internal conditions with
(including insulation) should not exceed 60% of the penetration area. humidity classes other than Z1, excluding
ETA 13/0672 & 18/0855
temperatures below 0 °C.
For all technical details on the products specified
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can
product specifications without giving notice. All information contained in this document is given in good faith and is be found on http://www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is Polyseam Ltd, 15 St Andrews Road, Huddersfield,
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability West Yorkshire, HD1 6SB, United Kingdom Scale: Drawn by & date:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given. Tel: +44 (0) 1484 421 036 NTS K.B. 17/3/19

P a g e | 300
MIXED SERVICE APERTURE
Fire Classification EI 60
Sound Reduction 48 dB
List of services - Page 2 of 2
Pipe wall Pipe
Type of Services Size of Services Pipe Insulation Pipe Wraps
thicknesses config
≤ Ø21mm cables single or bundled - - - -

Cables, with or without trays or ladders ≤ Ø16mm PVC conduits - - C/U -

≤ Ø17mm unsheathed cables/wires - - - -

≤ Ø16mm per pipe - None C/U -

≤ Ø324mm per pipe - 20 - 80mm thick continuous stone wool ≥ 80kg/m3 C/U -
Steel pipes
≤ Ø40mm per pipe - ≥ 20mm thick x 100cm long stone wool ≥ 80 kg/m3 both sides C/U -

≤ Ø219mm per pipe - ≥ 30mm thick x 100cm long stone wool ≥ 80 kg/m3 both sides C/U -

Ø6mm per pipe - None C/C -

Copper pipes ≤ Ø54mm per pipe - 20 - 80mm thick continuous stone wool ≥ 80kg/m3 C/C -

≤ Ø54mm per pipe - ≥ 20mm thick x 100cm long stone wool ≥ 80 kg/m3 both sides C/C -

≤ Ø20mm per pipe - None C/C -


Alupex pipes
≤ Ø75mm per pipe - ≥ 20mm thick x 50cm long stone wool ≥ 80 kg/m3 both sides C/C -

PVC-U and PVC-C pipes ≤ Ø40mm per pipe 1.6-3.0mm - U/C None

PEX pipe-in-pipes ≤ Ø25mm per pipe - - C/C None

P a g e | 301
MIXED SERVICE APERTURE
Installation Instructions Fire Classification E 120
1. Ensure the faces of the aperture opening are free of Sound Reduction 48 dB
Maximum aperture
dust and any other contaminants. The faces may be
1200 x 2400mm Installation details - Page 1 of 2
moistened for better adhesion.
2. Bare metal passing through the seal must be
protected against corrosion using a suitable Products Protecta EX Mortar
Protecta EX Mortar Stone wool shutter
primer/protection system.
3. The seal can be positioned to either side of the Minimum seal depth 50mm
Construction Minimum floor thickness of 150
construction or anywhere in between. mm and comprise aerated
4. When installing Protecta® EX Mortar in hollow floor concrete or concrete with a
slabs or boards, level the fire seal with the soffit side. minimum density of 650kg/m3
Ensure there is sufficient thickness of concrete
below the void for the depth of mortar. Where this
is not the case, tubular voids should be filled with
Services
stone wool normally the same thickness as the
depth of the floor slab. Alternatively, simply fire seal
1. Cables and cable trays
on both sides.
5. Install a stone wool shutter board to achieve the 2. Steel pipes
required thickness of mortar. Make sure that this 3. Copper pipes
achieves a very tight seal – any small openings
should be sealed with Protecta® FR Acrylic 4. Alupex pipes
6. Pour clean water into a suitable mixing vessel and 5. Plastic pipes
pour enough mortar to obtain the required
consistency. Mix well to avoid lumps. Always add the 50mm stone wool
mortar to the water, do not reverse this mixing shutter ≥ 150kg/m3 For full specification see page 2.
process.
7. Once the desired consistency is achieved pour or
trowel the mortar onto the shutter board making Indoor air comfort test results
sure that it flows into all corners and around
services. Apply a firm pressure to the mortar to  EMICODE EC 1PLUS – Complies
eliminate any trapped air bubbles. Build up to the  BREEAM-NOR – Complies
required depth. Minimum separations and limitations  DIBt – Complies
An aperture can include several services, and they may also be different. The minimum permitted  LEED – Complies
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 30mm
from seal edges. Services within the seal do not require a minimum separation, except pipes where Durability
combustible pipe insulation penetrates the seal and plastic pipe penetrations which should be a
minimum of 30mm from other services in the aperture. The total amount of cross sections of services Z2 - Intended for use in internal conditions with
(including insulation) should not exceed 60% of the penetration area. humidity classes other than Z1, excluding
ETA 13/0672 & 18/0855
temperatures below 0 °C.
For all technical details on the products specified
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change please refer to the technical data sheets that can
product specifications without giving notice. All information contained in this document is given in good faith and is be found on http://www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is Polyseam Ltd, 15 St Andrews Road, Huddersfield,
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability West Yorkshire, HD1 6SB, United Kingdom Scale: Drawn by & date:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given. Tel: +44 (0) 1484 421 036 NTS K.B. 17/3/19

P a g e | 302
MIXED SERVICE APERTURE
Fire Classification E 120
Sound Reduction 48 dB
List of services - Page 2 of 2
Pipe wall Pipe
Type of Services Size of Services Pipe Insulation Pipe Wraps
thicknesses config
≤ Ø21mm cables single or bundled - - - -

Cables, with or without trays ≤ Ø16mm PVC conduits - - C/U -

≤ Ø24mm unsheathed cables/wires - - - -

≤ Ø16mm per pipe - None C/U -

≤ Ø324mm per pipe - 20 - 80mm thick continuous stone wool ≥ 80kg/m3 C/U -
Steel pipes
≤ Ø40mm per pipe - ≥ 20mm thick x 100cm long stone wool ≥ 80 kg/m3 both sides C/U -

≤ Ø219mm per pipe - ≥ 30mm thick x 100cm long stone wool ≥ 80 kg/m3 both sides C/U -

≤ Ø15mm per pipe - None C/C -

Copper pipes ≤ Ø54mm per pipe - 20 - 80mm thick continuous stone wool ≥ 80kg/m3 C/C -

≤ Ø54mm per pipe - ≥ 20mm thick x 100cm long stone wool ≥ 80 kg/m3 both sides C/C -

≤ Ø20mm per pipe - None C/C -


Alupex pipes
≤ Ø75mm per pipe - ≥ 20mm thick x 50cm long stone wool ≥ 80 kg/m3 both sides C/C -

PVC-U and PVC-C pipes ≤ Ø40mm per pipe 1.6-3.0mm - U/C None

PEX pipe-in-pipes ≤ Ø25mm per pipe - - C/C None

P a g e | 303
MIXED SERVICE APERTURE
Installation Instructions Fire Classification EI 60
1. Ensure the faces of the aperture opening are free of Protecta EX Mortar Sound Reduction 48 dB
Maximum aperture
dust and any other contaminants. The faces may be Minimum seal depth 100mm
1200 x 2400mm Installation details - Page 1 of 4
moistened for better adhesion.
2. Bare metal passing through the seal must be
Products Protecta EX Mortar
protected against corrosion using a suitable
Protecta FR Pipe Wrap
primer/protection system.
3. The seal can be positioned to either side of the Construction Minimum floor thickness of 150
construction or anywhere in between. mm and comprise aerated
4. When installing Protecta® EX Mortar in hollow floor concrete or concrete with a
slabs or boards, level the fire seal with the soffit side. minimum density of 650kg/m3
Ensure there is sufficient thickness of concrete
below the void for the depth of mortar. Where this
is not the case, tubular voids should be filled with Services
stone wool normally the same thickness as the
depth of the floor slab. Alternatively, simply fire seal 1. Cables, with or without cable trays
on both sides. 2. Steel pipes
5. Install a shutter board to achieve the required 3. Copper pipes
4. Alupex pipes
thickness of mortar. Make sure that this achieves a
Protecta Pipe Wrap 5. Plastic pipes
very tight seal.
50mm wide fitted at 6. Composite pipes
6. Pour clean water into a suitable mixing vessel and 7. Conduits
pour enough mortar to obtain the required soffit
8. Ventilation ducts
consistency. Mix well to avoid lumps. Always add the
mortar to the water, do not reverse this mixing Loadbearing Properties
For full specification see pages 2 - 4.
process.
Soft body impact, serviceability 500Nm. Soft body impact, safety in use 700Nm. Hard body impact
7. Once the desired consistency is achieved pour or Indoor air comfort test results
serviceability 6Nm. Hard body impact, safety in use 10Nm. Concentrated load to 15kN on size up to
trowel the mortar onto the shutter board making
1500mm x1000mm (no failure), 4.85kN on sizes up to 1200mm x 2400mm.
sure that it flows into all corners and around  EMICODE EC 1PLUS – Complies
Minimum separations and limitations  BREEAM-NOR – Complies
services. Apply a firm pressure to the mortar to
An aperture can include several services, and they may also be different. The minimum permitted  DIBt – Complies
eliminate any trapped air bubbles. Build up to the
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 30mm  LEED – Complies
required depth.
from seal edges. Services within the seal do not require a minimum separation, except pipes where
combustible pipe insulation penetrates the seal and plastic pipe penetrations which should be a Durability
minimum of 30mm from other services in the aperture. The total amount of cross sections of services
(including insulation) should not exceed 60% of the penetration area. Z2 - Intended for use in internal conditions with
ETA 13/0672 & 18/0855 humidity classes other than Z , excluding
1
For all technical details on the products specified
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change temperatures below 0 °C.
please refer to the technical data sheets that can
product specifications without giving notice. All information contained in this document is given in good faith and is be found on http://www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is Polyseam Ltd, 15 St Andrews Road, Huddersfield,
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability West Yorkshire, HD1 6SB, United Kingdom NTS K.B. 17/3/19
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given. Tel: +44 (0) 1484 421 036

P a g e | 304
MIXED SERVICE APERTURE
Fire Classification EI 60
Sound Reduction 48 dB
List of services - Page 2 of 4
Pipe wall Pipe
Type of Services Size of Services Pipe Insulation Pipe Wraps
thicknesses config
≤ Ø80mm cables single or bundled - - - -

Cables, with or without trays or ladders ≤ Ø16mm PVC conduits - - C/U -

≤ Ø17mm unsheathed cables/wires - - - -

≤ Ø16mm per pipe - None C/U -

≤ Ø40mm per pipe - 13mm thick continuous elastomeric or phenolic C/U 1 layer of 50mm wide soffit side

≤ Ø40mm per pipe - 14 - 25mm thick continuous elastomeric or phenolic C/U 2 layers of 50mm wide soffit side

≤ Ø165mm per pipe - 14 - 19mm thick continuous elastomeric or phenolic C/U 1 layer of 50mm wide soffit side

Steel pipes ≤ Ø324mm per pipe - 25mm thick continuous elastomeric or phenolic C/U 2 layers of 50mm wide soffit side

≤ Ø324mm per pipe - 26 - 50mm thick continuous elastomeric or phenolic C/U 3 layers of 50mm wide soffit side

≤ Ø324mm per pipe - 20 - 80mm thick continuous stone wool ≥ 80kg/m3 C/U -

≤ Ø40mm per pipe - ≥ 20mm thick x 100cm long stone wool ≥ 80 kg/m3 both sides C/U -

≤ Ø219mm per pipe - ≥ 30mm thick x 100cm long stone wool ≥ 80 kg/m3 both sides C/U -

Ø6mm per pipe - None C/C -

≤ Ø12mm per pipe - 9mm thick continuous elastomeric or phenolic C/C 2 layers of 50mm wide soffit side

Copper pipes ≤ Ø54mm per pipe - 13 - 25mm thick continuous elastomeric or phenolic C/C 2 layers of 50mm wide soffit side

≤ Ø54mm per pipe - 20 - 80mm thick continuous stone wool ≥ 80kg/m3 C/C -

≤ Ø54mm per pipe - ≥ 20mm thick x 100cm long stone wool ≥ 80 kg/m3 both sides C/C -

≤ Ø20mm per pipe - None C/C -

Alupex pipes ≤ Ø75mm per pipe - 9 - 25mm thick continuous elastomeric or phenolic C/C 2 layers of 50mm wide soffit side

≤ Ø75mm per pipe - ≥ 20mm thick x 50cm long stone wool ≥ 80 kg/m3 both sides C/C -

P a g e | 305
MIXED SERVICE APERTURE
Fire Classification EI 60
Sound Reduction 48 dB
List of services - Page 3 of 4
Pipe wall Pipe
Type of Services Size of Services Pipe Insulation Pipe Wraps
thicknesses config
≤ Ø40mm per pipe 1.6-3.0mm - U/C None

≤ Ø40mm per pipe 1.8-3.7mm - U/U 1 layer of 50mm wide soffit side

≤ Ø110mm per pipe 1.9-6.6mm - U/C 2 layers of 50mm wide soffit side
PVC-U and PVC-C pipes
≤ Ø125mm per pipe 3.5-7.4mm - U/C 4 layers of 50mm wide soffit side

≤ Ø160mm per pipe 4.5-9.5mm - C/C 6 layers of 50mm wide soffit side

≤ Ø160mm per pipe 9.5mm - U/C 6 layers of 50mm wide soffit side

≤ Ø40mm per pipe 1.8-4.4mm - U/C None

≤ Ø40mm per pipe 2.4-3.7mm - U/U 1 layer of 50mm wide soffit side

≤ Ø110mm per pipe 2.5-10.0mm - U/C 2 layers of 50mm wide soffit side
PE, ABS and SAN+PVC pipes
≤ Ø125mm per pipe 3.9-11.4mm - U/C 4 layers of 50mm wide soffit side

≤ Ø160mm per pipe 4.9-14.6mm - U/C 6 layers of 50mm wide soffit side

≤ Ø250mm per pipe 7.8mm - C/C 7 layers of 75mm wide soffit side

≤ Ø40mm per pipe 1.8-4.4mm - U/C None

≤ Ø40mm per pipe 1.8-5.5mm - U/U 1 layer of 50mm wide soffit side

PP pipes ≤ Ø110mm per pipe 1.9-6.3mm - U/C 2 layers of 50mm wide soffit side

≤ Ø125mm per pipe 3.4-11.4mm - U/C 4 layers of 50mm wide soffit side

≤ Ø160mm per pipe 4.9-14.6mm - U/C 6 layers of 50mm wide soffit side

≤ Ø25mm per pipe - - C/C None


PEX pipe-in-pipes
≤ Ø54mm per pipe - - C/C 2 layers of 50mm wide soffit side

Ø32mm per pipe - - C/C 1 layer of 50mm wide soffit side


Aquatherm Green SDR9 pipes
≤ Ø110mm per pipe - - C/C 2 layers of 50mm wide soffit side

≤ Ø50mm per pipe - - U/U 2 layers of 50mm wide soffit side


Geberit Silent-PP pipes
≤ Ø110mm per pipe - - U/C 2 layers of 50mm wide soffit side

P a g e | 306
MIXED SERVICE APERTURE
Fire Classification EI 60
Sound Reduction 48 dB
List of services - Page 4 of 4
Pipe wall Pipe
Type of Services Size of Services Pipe Insulation Pipe Wraps
thicknesses config
≤ Ø110mm per pipe - - U/C 2 layers of 50mm wide soffit side

Polo-Kal NG pipes Ø125mm per pipe - - U/C 4 layers of 50mm wide soffit side

Ø160mm per pipe - - U/C 6 layers of 50mm wide soffit side

≤ Ø50mm per pipe - - U/U 2 layers of 50mm wide soffit side

≤ Ø110mm per pipe - - U/C 2 layers of 50mm wide soffit side


Rehau Raupiano Plus pipes
Ø125mm per pipe - - U/C 4 layers of 50mm wide soffit side

Ø160mm per pipe - - U/C 6 layers of 50mm wide soffit side

≤ Ø50mm per pipe - - U/U 2 layers of 50mm wide soffit side


Wavin SiTech pipes
≤ Ø110mm per pipe - - U/C 2 layers of 50mm wide soffit side

Conduits of PVC-U & PVC-C pipes ≤ Ø110mm w/cables ≤ Ø14mm 2.7-6.6mm - U/C 2 layers of 50mm wide soffit side

Conduits of PE, ABS & SAN+PVC pipes ≤ Ø110mm w/cables ≤ Ø14mm 2.7-10.0mm - U/C 2 layers of 50mm wide soffit side

Conduits of PP pipe ≤ Ø110mm w/cables ≤ Ø14mm 3.4-6.3mm - U/C 2 layers of 50mm wide soffit side

≤ Ø400mm - ≥ 30mm thick x 15cm long stonewool mat ≥80kg/m3 top side - Protecta FR Damper

Ventilation ducts ≤ Ø1000mm - ≥ 30mm thick x 50cm long stonewool mat ≥80kg/m3 top side - Protecta FR Damper

≤ 1000 x 1000mm - ≥ 30mm thick x 50cm long stonewool mat ≥80kg/m3 top side - Protecta FR Damper

P a g e | 307
Protecta EX Mortar
MIXED SERVICE APERTURE
Installation Instructions Fire Classification EI 120
Minimum seal depth 100mm
1. Ensure the faces of the aperture opening are free of Sound Reduction 48 dB
Maximum aperture
dust and any other contaminants. The faces may be 1200 x 2400mm Installation details - Page 1 of 4
moistened for better adhesion.
2. Bare metal passing through the seal must be
Products Protecta EX Mortar
protected against corrosion using a suitable
Protecta FR Pipe Wrap
primer/protection system.
3. The seal can be positioned to either side of the Construction Minimum floor thickness of 150
construction or anywhere in between. mm and comprise aerated
4. When installing Protecta® EX Mortar in hollow floor concrete or concrete with a
slabs or boards, level the fire seal with the soffit side. minimum density of 650kg/m3
Ensure there is sufficient thickness of concrete
below the void for the depth of mortar. Where this
is not the case, tubular voids should be filled with Services
stone wool normally the same thickness as the
depth of the floor slab. Alternatively, simply fire seal 1. Cables
on both sides. 2. Steel pipes
3. Copper pipes
5. Install a shutter board to achieve the required
4. Alupex pipes
thickness of mortar. Make sure that this achieves a
Protecta Pipe Wrap 5. Plastic pipes
very tight seal. 6. Composite pipes
50mm wide fitted at
6. Pour clean water into a suitable mixing vessel and 7. Conduits
soffit
pour enough mortar to obtain the required 8. Ventilation ducts
consistency. Mix well to avoid lumps. Always add the
mortar to the water, do not reverse this mixing Loadbearing Properties For full specification see pages 2 - 4.
process.
Soft body impact, serviceability 500Nm. Soft body impact, safety in use 700Nm. Hard body impact
7. Once the desired consistency is achieved pour or Indoor air comfort test results
serviceability 6Nm. Hard body impact, safety in use 10Nm. Concentrated load to 15kN on size up to
trowel the mortar onto the shutter board making
1500mm x1000mm (no failure), 4.85kN on sizes up to 1200mm x 2400mm.  EMICODE EC 1PLUS – Complies
sure that it flows into all corners and around
Minimum separations and limitations  BREEAM-NOR – Complies
services. Apply a firm pressure to the mortar to
An aperture can include several services, and they may also be different. The minimum permitted  DIBt – Complies
eliminate any trapped air bubbles. Build up to the
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 30mm  LEED – Complies
required depth.
from seal edges. Services within the seal do not require a minimum separation, except pipes where
combustible pipe insulation penetrates the seal and plastic pipe penetrations which should be a Durability
minimum of 30mm from other services in the aperture. The total amount of cross sections of services
(including insulation) should not exceed 60% of the penetration area. Z2 - Intended for use in internal conditions with
ETA 13/0672 & 18/0855 humidity classes other than Z1, excluding
For all technical details on the products specified
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change
temperatures below 0 °C.
please refer to the technical data sheets that can
product specifications without giving notice. All information contained in this document is given in good faith and is be found on http://www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is Polyseam Ltd, 15 St Andrews Road, Huddersfield,
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability West Yorkshire, HD1 6SB, United Kingdom Scale: Drawn by & date:
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given. Tel: +44 (0) 1484 421 036 NTS K.B. 17/3/19

P a g e | 308
MIXED SERVICE APERTURE
Fire Classification EI 120
Sound Reduction 48 dB
List of services - Page 2 of 4
Pipe wall Pipe
Type of Services Size of Services Pipe Insulation Pipe Wraps
thicknesses config
≤ Ø21mm cables in bundles ≤ Ø100mm - - - -
Cables in tied bundles
≤ Ø16mm PVC conduits - - C/U -

≤ Ø16mm per pipe - None C/U -

≤ Ø40mm per pipe - 13mm thick continuous elastomeric or phenolic C/U 1 layer of 50mm wide soffit side

≤ Ø40mm per pipe - 14 - 25mm thick continuous elastomeric or phenolic C/U 2 layers of 50mm wide soffit side

≤ Ø165mm per pipe - 14 - 19mm thick continuous elastomeric or phenolic C/U 1 layer of 50mm wide soffit side

Steel pipes ≤ Ø324mm per pipe - 25mm thick continuous elastomeric or phenolic C/U 2 layers of 50mm wide soffit side

≤ Ø324mm per pipe - 26 - 50mm thick continuous elastomeric or phenolic C/U 3 layers of 50mm wide soffit side

≤ Ø324mm per pipe - 20 - 80mm thick continuous stone wool ≥ 80kg/m3 C/U -

≤ Ø40mm per pipe - ≥ 20mm thick x 100cm long stone wool ≥ 80 kg/m3 both sides C/U -

≤ Ø219mm per pipe - ≥ 30mm thick x 100cm long stone wool ≥ 80 kg/m3 both sides C/U -

Ø6mm per pipe - None C/C -

≤ Ø12mm per pipe - 9mm thick continuous elastomeric or phenolic C/C 2 layers of 50mm wide soffit side
Copper pipes
≤ Ø54mm per pipe - 20 - 80mm thick continuous stone wool ≥ 80kg/m3 C/C -

≤ Ø54mm per pipe - ≥ 20mm thick x 100cm long stone wool ≥ 80 kg/m3 both sides C/C -

≤ Ø20mm per pipe - None C/C -

Alupex pipes ≤ Ø16mm per pipe - 9mm thick continuous elastomeric or phenolic C/C 2 layers of 50mm wide soffit side

≤ Ø75mm per pipe - ≥ 20mm thick x 50cm long stone wool ≥ 80 kg/m3 both sides C/C -

P a g e | 309
MIXED SERVICE APERTURE
Fire Classification EI 120
Sound Reduction 48 dB
List of services - Page 3 of 4
Pipe wall Pipe
Type of Services Size of Services Pipe Insulation Pipe Wraps
thicknesses config
≤ Ø40mm per pipe 1.6-3.0mm - U/C None

≤ Ø40mm per pipe 1.8-3.7mm - U/U 1 layer of 50mm wide soffit side

PVC-U and PVC-C pipes ≤ Ø110mm per pipe 1.9-6.6mm - U/C 2 layers of 50mm wide soffit side

≤ Ø125mm per pipe 3.5-7.4mm - U/C 4 layers of 50mm wide soffit side

≤ Ø160mm per pipe 4.5mm - C/C 6 layers of 50mm wide soffit side

≤ Ø40mm per pipe 1.8-4.4mm - U/C None

≤ Ø40mm per pipe 2.4-3.7mm - U/U 1 layer of 50mm wide soffit side

≤ Ø110mm per pipe 2.5-10.0mm - U/C 2 layers of 50mm wide soffit side
PE, ABS and SAN+PVC pipes
≤ Ø125mm per pipe 3.9-11.4mm - U/C 4 layers of 50mm wide soffit side

≤ Ø160mm per pipe 4.9-14.6mm - U/C 6 layers of 50mm wide soffit side

≤ Ø250mm per pipe 7.8mm - C/C 7 layers of 75mm wide soffit side

≤ Ø40mm per pipe 1.8-4.4mm - U/C None

≤ Ø40mm per pipe 1.8-5.5mm - U/U 1 layer of 50mm wide soffit side

PP pipes ≤ Ø110mm per pipe 1.9-6.3mm - U/C 2 layers of 50mm wide soffit side

≤ Ø125mm per pipe 3.4-11.4mm - U/C 4 layers of 50mm wide soffit side

≤ Ø160mm per pipe 4.9-14.6mm - U/C 6 layers of 50mm wide soffit side

≤ Ø25mm per pipe - - C/C None


PEX pipe-in-pipes
≤ Ø54mm per pipe - - C/C 2 layers of 50mm wide soffit side

Ø32mm per pipe - - C/C 1 layer of 50mm wide soffit side


Aquatherm Green SDR9 pipes
≤ Ø110mm per pipe - - C/C 2 layers of 50mm wide soffit side

≤ Ø50mm per pipe - - U/U 2 layers of 50mm wide soffit side


Geberit Silent-PP pipes
≤ Ø110mm per pipe - - U/C 2 layers of 50mm wide soffit side

P a g e | 310
MIXED SERVICE APERTURE
Fire Classification EI 120
Sound Reduction 48 dB
List of services - Page 4 of 4
Pipe wall Pipe
Type of Services Size of Services Pipe Insulation Pipe Wraps
thicknesses config
≤ Ø110mm per pipe - - U/C 2 layers of 50mm wide soffit side

Polo-Kal NG pipes Ø125mm per pipe - - U/C 4 layers of 50mm wide soffit side

Ø160mm per pipe - - U/C 6 layers of 50mm wide soffit side

≤ Ø50mm per pipe - - U/U 2 layers of 50mm wide soffit side

≤ Ø110mm per pipe - - U/C 2 layers of 50mm wide soffit side


Rehau Raupiano Plus pipes
Ø125mm per pipe - - U/C 4 layers of 50mm wide soffit side

Ø160mm per pipe - - U/C 6 layers of 50mm wide soffit side

≤ Ø50mm per pipe - - U/U 2 layers of 50mm wide soffit side


Wavin SiTech pipes
≤ Ø110mm per pipe - - U/C 2 layers of 50mm wide soffit side

Conduits of PVC-U & PVC-C pipes ≤ Ø110mm w/cables ≤ Ø14mm 2.7-6.6mm - U/C 2 layers of 50mm wide soffit side

Ventilation ducts ≤ Ø400mm - ≥ 30mm thick x 15cm long stonewool mat ≥80kg/m3 top side - Protecta FR Damper

P a g e | 311
MIXED SERVICE APERTURE
Installation Instructions Fire Classification EI 120
1. Ensure the faces of the aperture opening are free of Protecta EX Mortar Sound Reduction 48 dB
Maximum aperture
dust and any other contaminants. The faces may be Minimum seal depth 150mm
1200 x 2400mm Installation details - Page 1 of 5
moistened for better adhesion.
2. Bare metal passing through the seal must be
Products Protecta EX Mortar
protected against corrosion using a suitable
Protecta FR Pipe Wrap
primer/protection system.
3. The seal can be positioned to either side of the Construction Minimum floor thickness of 150
construction or anywhere in between. mm and comprise aerated
4. When installing Protecta® EX Mortar in hollow floor concrete or concrete with a
slabs or boards, level the fire seal with the soffit side. minimum density of 650kg/m3
Ensure there is sufficient thickness of concrete
below the void for the depth of mortar. Where this
is not the case, tubular voids should be filled with Services
stone wool normally the same thickness as the
depth of the floor slab. Alternatively, simply fire seal 1. Cables, with or without cable trays
on both sides. 2. Steel pipes
3. Copper pipes
5. Install a shutter board to achieve the required
4. Alupex pipes
thickness of mortar. Make sure that this achieves a
Protecta Pipe Wrap 5. Plastic pipes
very tight seal. 6. Composite pipes
6. Pour clean water into a suitable mixing vessel and 50mm wide fitted at
soffit 7. Conduits
pour enough mortar to obtain the required 8. Ventilation ducts
consistency. Mix well to avoid lumps. Always add the
mortar to the water, do not reverse this mixing Loadbearing Properties For full specification see pages 2 - 5.
process.
Soft body impact, serviceability 500Nm. Soft body impact, safety in use 700Nm. Hard body impact
7. Once the desired consistency is achieved pour or Indoor air comfort test results
serviceability 6Nm. Hard body impact, safety in use 10Nm. Concentrated load to 15kN on size up to
trowel the mortar onto the shutter board making
1500mm x1000mm (no failure), 4.85kN on sizes up to 1200mm x 2400mm.  EMICODE EC 1PLUS – Complies
sure that it flows into all corners and around
Minimum separations and limitations  BREEAM-NOR – Complies
services. Apply a firm pressure to the mortar to
An aperture can include several services, and they may also be different. The minimum permitted  DIBt – Complies
eliminate any trapped air bubbles. Build up to the
separation between adjacent seals/apertures is 200mm. Services should be a minimum of 30mm  LEED – Complies
required depth.
from seal edges. Services within the seal do not require a minimum separation, except pipes where
combustible pipe insulation penetrates the seal and plastic pipe penetrations which should be a Durability
minimum of 30mm from other services in the aperture. The total amount of cross sections of services
(including insulation) should not exceed 60% of the penetration area. Z2 - Intended for use in internal conditions with
ETA 13/0672 & 18/0855 humidity classes other than Z1, excluding
For all technical details on the products specified
As a part of our policy of on-going product development and testing, we reserve the right to modify, alter or change
temperatures below 0 °C.
please refer to the technical data sheets that can
product specifications without giving notice. All information contained in this document is given in good faith and is be found on http://www.protecta.eu
provided for guidance only. Any drawings provided are for illustrative purposes only. As Polyseam has no control over
the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is Polyseam Ltd, 15 St Andrews Road, Huddersfield,
intended to be given as to the actual performance of the product mentioned or referred to herein and no liability West Yorkshire, HD1 6SB, United Kingdom NTS K.B. 17/3/19
whatsoever will be accepted for any loss, damage or injury arising from the use of the information given. Tel: +44 (0) 1484 421 036

P a g e | 312
MIXED SERVICE APERTURE
Fire Classification EI 120
Sound Reduction 48 dB
List of services - Page 2 of 5
Pipe wall Pipe
Type of Services Size of Services Pipe Insulation Pipe Wraps
thicknesses config
≤ Ø21mm cables single or bundled - - - -

≤ Ø16mm PVC conduits - - C/U -


Cables, with or without trays or ladders
≤ Ø24mm unsheathed cables/wires - - - -

≤ 500mm wide trays or ladders - - - -

≤ Ø16mm per pipe - None C/U -

≤ Ø40mm per pipe - 13mm thick continuous elastomeric or phenolic C/U 1 layer of 50mm wide soffit side

≤ Ø40mm per pipe - 14 - 25mm thick continuous elastomeric or phenolic C/U 2 layers of 50mm wide soffit side

≤ Ø165mm per pipe - 14 - 19mm thick continuous elastomeric or phenolic C/U 1 layer of 50mm wide soffit side

Steel pipes ≤ Ø324mm per pipe - 25mm thick continuous elastomeric or phenolic C/U 2 layers of 50mm wide soffit side

≤ Ø324mm per pipe - 26 - 50mm thick continuous elastomeric or phenolic C/U 3 layers of 50mm wide soffit side

≤ Ø324mm per pipe - 20 - 80mm thick continuous stone wool ≥ 80kg/m3 C/U -

≤ Ø40mm per pipe - ≥ 20mm thick x 100cm long stone wool ≥ 80 kg/m3 both sides C/U -

≤ Ø219mm per pipe - ≥ 30mm thick x 100cm long stone wool ≥ 80 kg/m3 both sides C/U -

Ø6mm per pipe - None C/C -

≤ Ø12mm per pipe - 9mm thick continuous elastomeric or phenolic C/C 2 layers of 50mm wide soffit side
Copper pipes
≤ Ø54mm per pipe - 20 - 80mm thick continuous stone wool ≥ 80kg/m3 C/C -

≤ Ø54mm per pipe - ≥ 20mm thick x 100cm long stone wool ≥ 80 kg/m3 both sides C/C -

≤ Ø20mm per pipe - None C/C -

Alupex pipes ≤ Ø16mm per pipe - 9mm thick continuous elastomeric or phenolic C/C 2 layers of 50mm wide soffit side

≤ Ø75mm per pipe - ≥ 20mm thick x 50cm long stone wool ≥ 80 kg/m3 both sides C/C -

P a g e | 313
MIXED SERVICE APERTURE
Fire Classification EI 120
Sound Reduction 48 dB
List of services - Page 3 of 5
Pipe wall Pipe
Type of Services Size of Services Pipe Insulation Pipe Wraps
thicknesses config
≤ Ø40mm per pipe 1.6-3.0mm - U/C None

≤ Ø40mm per pipe 1.8-3.7mm - U/U 1 layer of 50mm wide soffit side

≤ Ø110mm per pipe 1.9-6.6mm - U/C 2 layers of 50mm wide soffit side
PVC-U and PVC-C pipes
≤ Ø125mm per pipe 3.5-7.4mm - U/C 4 layers of 50mm wide soffit side

≤ Ø160mm per pipe 4.5-9.5mm - U/C 6 layers of 50mm wide soffit side

Ø 315mm per pipe 7.7mm C/C 10 layers of 75mm wide soffit side

≤ Ø40mm per pipe 1.8-4.4mm - U/C None

≤ Ø40mm per pipe 2.4-3.7mm - U/U 1 layer of 50mm wide soffit side

≤ Ø110mm per pipe 2.5-10.0mm - U/C 2 layers of 50mm wide soffit side

≤ Ø110mm per pipe 3.4-10.0mm - U/U 3 layers of 75mm wide soffit side

≤ Ø125mm per pipe 3.9-11.4mm - U/C 4 layers of 50mm wide soffit side
PE, ABS and SAN+PVC pipes
Ø 125mm per pipe 11.4mm - U/U 4 layers of 50mm wide soffit side

Ø 140mm per pipe 8.0-12.4mm - U/U 6 layers of 75mm wide soffit side

≤ Ø160mm per pipe 4.9-14.6mm - U/U 4 layers of 75mm wide soffit side

≤ Ø160mm per pipe 3.9-4.8mm - U/U 10 layers of 75mm wide soffit side

≤ Ø250mm per pipe 7.8mm - C/C 7 layers of 75mm wide soffit side

P a g e | 314
MIXED SERVICE APERTURE
Fire Classification EI 120
Sound Reduction 48 dB
List of services - Page 4 of 5
Pipe wall Pipe
Type of Services Size of Services Pipe Insulation Pipe Wraps
thicknesses config
≤ Ø40mm per pipe 1.8-4.4mm - U/C None

≤ Ø40mm per pipe 1.8-5.5mm - U/U 1 layer of 50mm wide soffit side

≤ Ø110mm per pipe 1.9-6.3mm - U/C 2 layers of 50mm wide soffit side

≤ Ø110mm per pipe 3.7-10.5mm - U/U 4 layers of 50mm wide soffit side

≤ Ø125mm per pipe 3.4-11.4mm - U/C 4 layers of 50mm wide soffit side

PP pipes Ø125mm per pipe 11.4mm - U/U 4 layers of 50mm wide soffit side

Ø140mm per pipe 12.8mm - U/U 4 layers of 75mm wide soffit side

≤ Ø160mm per pipe 4.9-14.6mm - U/C 6 layers of 50mm wide soffit side

Ø160mm per pipe 14.6mm U/U 4 layers of 75mm wide soffit side

≤ Ø200mm per pipe 4.9-18.2mm C/C 6 layers of 75mm wide soffit side

Ø315mm per pipe 7.7mm C/C 10 layers of 75mm wide soffit side

≤ Ø25mm per pipe - - C/C None


PEX pipe-in-pipes
≤ Ø54mm per pipe - - C/C 2 layers of 50mm wide soffit side

Ø32mm per pipe - - C/C 1 layer of 50mm wide soffit side


Aquatherm Green SDR9 pipes
≤ Ø110mm per pipe - - C/C 2 layers of 50mm wide soffit side

≤ Ø50mm per pipe - - U/U 2 layers of 50mm wide soffit side


Geberit Silent-PP pipes
≤ Ø110mm per pipe - - U/C 2 layers of 50mm wide soffit side

≤ Ø110mm per pipe - - U/C 2 layers of 50mm wide soffit side

Polo-Kal NG pipes Ø125mm per pipe - - U/C 4 layers of 50mm wide soffit side

Ø160mm per pipe - - U/C 6 layers of 50mm wide soffit side

≤ Ø50mm per pipe - - U/U 2 layers of 50mm wide soffit side

≤ Ø110mm per pipe - - U/C 2 layers of 50mm wide soffit side


Rehau Raupiano Plus pipes
Ø125mm per pipe - - U/C 4 layers of 50mm wide soffit side

Ø160mm per pipe - - U/C 6 layers of 50mm wide soffit side

P a g e | 315
MIXED SERVICE APERTURE
Fire Classification EI 120
Sound Reduction 48 dB
List of services - Page 5 of 5
Pipe wall Pipe
Type of Services Size of Services Pipe Insulation Pipe Wraps
thicknesses config
≤ Ø50mm per pipe - - U/U 2 layers of 50mm wide soffit side
Wavin SiTech pipes
≤ Ø110mm per pipe - - U/C 2 layers of 50mm wide soffit side

Conduits of PVC-U & PVC-C pipes ≤ Ø110mm w/cables ≤ Ø14mm 2.7-6.6mm - U/C 2 layers of 50mm wide soffit side

Ventilation ducts ≤ Ø400mm - ≥ 30mm thick x 15cm long stonewool mat ≥80kg/m3 top side - Protecta FR Damper

P a g e | 316
INDEX
Appendix I – Linear seal solutions in floors Seals in 100mm walls, movement & waterproof to EI 120 41
Top side seals to EI 180 18 Extra wide seals with FR Board to EI 120 42
Top side seals to EI 240 19
Appendix II – Services with gaps ≤ 10mm in floors
Soffit side seals to EI 60 & E 120 20
Single cables and medium bundles to EI 120 44
Double sided seals to EI 240 21
Large cable bundles to EI 180 45
Top side seals, movement & waterproof to EI 180 22
Steel pipes without insulation to EI 120 46
Double sided seals, movement & waterproof to EI 240 23
Steel pipes with continuous insulation to EI 240 47
Extra wide seals with FR Board to EI 120 24
Steel pipes with interrupted insulation to EI 240 48
Extra wide seals with EX Mortar to EI 180 25
Copper pipes without insulation to EI 120 49
Extra wide loadbearing seals with EX Mortar to EI 240 26
Copper pipes with continuous insulation to EI 240 50
Appendix I – Linear seal solutions in rigid walls Copper pipes with interrupted insulation to EI 240 51
Single sided seals to EI 60 – 120 27 Plastic pipes with soffit side seals 52
Single sided seals to EI 120 28 Plastic pipes with top side seals 53
Double sided seals to EI 240 29 Composite plastic pipes 54
Single sided movement & waterproof seals to EI 60 30
Appendix II – Services with gaps ≤ 10mm in rigid walls
Double sided movement & waterproof seals to EI 120 31
Single cables and medium bundles to EI 120 55
Extra wide seals with FR Board to EI 90 & E 240 32
Large cable bundles to EI 60 & E 120 56
Extra wide seals with FR Board to EI 120 33
Steel pipes without insulation to EI 60 & E 120 57
Extra wide seals with FR Board to EI 180 34
Steel pipes with continuous insulation to EI 120 58
Appendix I – Linear seal solutions in drywalls Steel pipes with interrupted insulation to EI 120 59
Seals in 75mm walls to EI 45 & E 60 35 Copper pipes without insulation to EI 120 60
Seals in 75mm walls, movement & waterproof seals 36 Copper pipes with continuous insulation to EI 60 61
Seals in 100mm walls without backing to EI 90 37 Copper pipes with interrupted insulation to EI 60 62
Seals in 100mm walls to EI 120 38 Alupex pipes without insulation to EI 120 63
Seals in 100mm walls without backing to EI 120 39 Plastic pipes to EI 60 64
Seals in 100mm walls w/o backing, movement & waterproof 40 Plastic pipes to EI 120 65
P a g e | 317
INDEX
Plastic pipes to EI 240 66 Steel pipes with interrupted stone wool insulation to EI 120 91
Composite plastic pipes 67 Steel pipes (small) with combustible insulation to EI 180 92
PEX pipe-in-pipes to EI 90 & E 120 68 Steel pipes (medium) with combustible insulation to EI 60 93
Steel pipes (large) with combustible insulation to EI 60 - 120 94
Appendix II – Services with gaps ≤ 10mm in drywalls
Copper pipes in single sided seal with no insulation 95
Single cables and medium bundles to EI 120 69
Copper pipes in double sided seal with no insulation 96
Large cable bundles to EI 60 & E 120 70
Copper pipes with continuous stone wool insulation to EI 180 97
Steel pipes without insulation to EI 60 & E 120 71
Copper pipes with interrupted insulation to EI 60 - 240 98
Steel pipes with continuous insulation to EI 120 72
Copper pipes with interrupted insulation to EI 120 99
Steel pipes with interrupted insulation to EI 120 73
Copper pipes with combustible insulation to EI 60 - 180 100
Copper pipes without insulation to EI 120 74
Alupex pipes with no insulation to EI 120 101
Copper pipes with continuous insulation to EI 60 75
Alupex pipes with continuous stone wool insulation 102
Copper pipes with interrupted insulation to EI 60 76
Alupex pipes with interrupted stone wool insulation 103
Alupex pipes without insulation to EI 120 77
Alupex pipes with combustible insulation to EI 60 - 180 104
Plastic pipes to EI 60 78
PEX pipe-in-pipe to EI 90 105
Plastic pipes to EI 120 79
Plastic pipes (small) to EI 90 - 240 106
Composite plastic pipes 80
Plastic pipes (medium) to EI 30 - 240 107
PEX pipe-in-pipes to EI 90 & E 120 81
Plastic pipes (large) to EI 30 - 60 108
Appendix III – Services with gaps 10-30mm in floors Plastic pipes (full range) up to EI 240 109
Cables in single sided seal to EI 60 & E 120 83 Composite plastic pipes 110
Cables in single sided seal to EI 90 & E 120 84 Conduits (medium pipes with cables) to EI 180 - 240 111
Cables in double sided seal to EI 120 85 Conduits (large pipes with cables) to EI 60 - 90 112
Steel pipes with no insulation in single sided seal to EI 120 86
Appendix III – Services with gaps 10-30mm in rigid walls
Steel pipes with no insulation in double sided seal to EI 240 87
Cables in single sided seal to EI 60 - 120 113
Steel pipes with continuous stone wool insulation to EI 240 88
Cables in double sided seal to EI 60 - 120 114
Steel pipes with interrupted stone wool insulation to EI 60 89
Cables in double sided seal to EI 60 - 240 115
Steel pipes with interrupted insulation to EI 90 & E 120 90
P a g e | 318
INDEX
Steel pipes (small) with no insulation to EI 90 116 Plastic pipes (small) to EI 180 - 240 143
Steel pipes (small) with no insulation to EI 120 117 PVC & PE pipes (medium) to EI 60 - 120 144
Steel pipes (large) with no insulation to E 120 118 PVC (large) & PP pipes (medium) to EI 30 - 90 145
Steel pipes with continuous stone wool insulation to EI 180 119 PVC pipes (large) to EI 90 - 180 146
Steel pipes with continuous stone wool insulation to EI 240 120 Plastic pipes (full range) with pipe collars up to EI 90 147
Steel pipes with interrupted insulation in small annular size 121 Plastic pipes (full range) with pipe collars up to EI 120 148
Steel pipes with interrupted insulation in large annular size 122 Plastic pipes (full range) with pipe collars up to EI 240 149
Steel pipes with interrupted insulation to EI 120 & E 240 123 Composite plastic pipes 150
Steel pipes (small) with combustible insulation to EI 120 124 Conduits (medium pipes with cables) to EI 90 - 120 151
Steel pipes with combustible insulation to EI 60 & E 120 125 Conduits (large pipes with cables) to EI 60 - 90 152
Steel pipes with thick combustible insulation to EI 60 126
Appendix III – Services with gaps 10-30mm in drywalls
Copper pipes (small) with no insulation to EI 60 127
Cables in 75mm walls to EI 45 & E 60 153
Copper pipes (large) with no insulation to E 120 128
Cable bundles in 75mm walls to EI 30 154
Copper pipes with continuous stone wool insulation 129
Cables in 100mm walls to EI 90 & E 120 155
Copper pipes w/ interrupted insulation in small annular size 130
Cables in 100mm walls to EI 120 156
Copper pipes w/ interrupted insulation in large annular size 131
Cables (large) in 100mm walls to EI 60 & E 120 157
Copper pipes with interrupted insulation to EI 120 132
Steel pipes in 75mm walls with no insulation to EI 30 & E 60 158
Copper pipes with combustible insulation to EI 60 - 120 133
Steel pipes in 100mm walls with no insulation to EI 90 159
Alupex pipes (small) with no insulation to EI 120 134
Steel pipes in 100mm walls with no insulation to EI 120 160
Alupex pipes (large) with no insulation to E 120 135
Steel pipes (large) in 100mm walls with no insulation 161
Alupex pipes with continuous mineral wool insulation 136
Steel pipes in 75mm walls with continuous insul. to EI 45 162
Alupex pipes w/interrupted insulation, medium annular size 137
Steel pipes in 100mm walls with continuous insulation 163
Alupex pipes w/ interrupted insulation in large annular size 138
Steel pipes with interrupted insulation to EI 90 - 120 164
Alupex pipes with interrupted insulation to EI 120 139
Steel pipes (small) with combustible insulation to EI 120 165
Alupex pipes with combustible insulation to EI 60 - 120 140
Steel pipes with combustible insulation to EI 60 & E 120 166
PEX pipe-in-pipe to EI 120 141
Copper pipes with no insulation to EI 30 - 60 167
Plastic pipes (small) to EI 60 - 120 142
P a g e | 319
INDEX
Copper pipes (large) with no insulation to E 120 168 Steel pipes with no insulation in 75mm walls to EI 30 194
Copper pipes with continuous stone wool insulation 169 Steel pipes with no insulation to EI 20 – 60 & E 120 195
Copper pipes with interrupted stone wool insulation 170 Steel pipes with combustible insulation to EI 60 - 120 196
Copper pipes with combustible insulation to EI 60 - 120 171 Steel pipes with stone wool insulation in 75mm walls 197
Alupex pipes with no insulation to EI 120 172 Steel pipes with stone wool insulation in framed aperture 198
Alupex pipes (large) with no insulation to EI 30 & E 120 173 Steel pipes with continuous stone wool insulation to EI 120 199
Alupex pipes with continuous mineral wool insulation 174 Steel pipes with interrupted stone wool insulation to EI 90 200
Alupex pipes with interrupted stone wool insulation 175 Copper pipes with no insulation to EI 60 & E 120 201
Alupex pipes with combustible insulation to EI 60 - 120 176 Copper pipes with combustible insulation to EI 60 - 120 202
PEX pipe-in-pipe (medium) to EI 120 177 Copper pipes with stone wool insulation to EI 120 203
PEX pipe-in-pipe (large) to EI 45 & E 60 178 Alupex pipes with no insulation to EI 120 204
Plastic pipes (small) in 75mm walls to EI 45 & E 60 179 Alupex pipes with combustible insulation to EI 120 205
Plastic pipes (small) in 100mm walls to EI 60 - 120 180 Alupex pipes with stone wool insulation to EI 60 - 120 206
PVC & PE pipes (medium) to EI 60 - 120 181 Plastic pipes in 75mm walls to EI 45 207
PVC (large) & PP pipes (medium) to EI 30 - 90 182 Plastic pipes in framed aperture to EI 60 208
Plastic pipes (full range) with pipe collars up to EI 90 183 Plastic pipes (small) to EI 60 - 90 209
Plastic pipes (full range) with pipe collars up to EI 120 184 PEX pipe-in pipes to EI 90 - 120 210
Composite plastic pipes 185 Plastic pipes (full range) to EI 90 - 120 211
Conduits (medium pipes with cables) in 75mm walls 186 Composite plastic pipes to EI 60 - 120 212
Conduits (medium pipes with cables) in 100mm walls 187 Plastic conduits to EI 90 & E 120 213
Conduits (large pipes with cables) in 100mm walls 188 Ventilation ducts to EI 60 - 120 214
Appendix IV – Larger apertures in drywalls Appendix IV – Larger apertures in rigid walls
Cables to EI 60 & E 120 190 Cables on cable trays with single 50mm boards to EI 60 215
Cables on cable trays in 75mm walls to EI 30 191 Cables to EI 90 & E 240 216
Cables on cable trays in framed aperture to EI 60 192 Cables and conduits to EI 120 - 180 217
Cables, wires and conduits on cable trays to EI 60 193 Cables and conduits on cable trays to EI 60 218

P a g e | 320
INDEX
Cables and conduits on cable trays to EI 60 - 120 219 Appendix IV – Larger apertures in floors
Cables, wires and conduits on cable trays to EI 60 - 240 220 Cables and conduits to EI 60 - 180 246
Cables and conduits on cable trays w/oversailing boards 221 Cables (large) and conduits to EI 60 - 180 247
Steel pipes with no insulation to EI 20 – 60 & E 120 222 Cables (large) and conduits to EI 60 - 180 & E 240 248
Steel pipes with combustible insulation to EI 45 & E 120 223 Cables, wires and conduits on cable trays to EI 60 & E 180 249
Steel pipes with combustible insulation to EI 60 - 120 224 Cables (large), wires and conduits on trays to EI 60 & E 120 250
Steel pipes with continuous stone wool insulation to EI 60 225 Cables, wires and conduits on cable trays to EI 120 251
Steel pipes with continuous insulation to EI 90 & E 240 226 Steel pipes (small) with no insulation to EI 180 252
Steel pipes with continuous stone wool insulation to EI 120 227 Steel pipes (small) with no insulation to EI 240 253
Steel pipes with continuous stone wool insulation to EI 180 228 Steel pipes with combustible insulation to EI 120 - 180 254
Steel pipes with interrupted insulation to EI 90 & E 240 229 Steel pipes with continuous stone wool insulation to EI 180 255
Steel pipes with interrupted stone wool insulation to EI 180 230 Steel pipes with continuous stone wool insulation to EI 240 256
Copper pipes with no insulation to EI 60 & E 120 231 Steel pipes with interrupted insulation to EI 90 - 240 257
Copper pipes with combustible insulation to EI 60 - 120 232 Steel pipes with interrupted stone wool insulation to EI 120 258
Copper pipes with stone wool insulation to EI 90 - 240 233 Copper pipes with no insulation to EI 30 - 120 259
Copper pipes with stone wool insulation to EI 120 234 Copper pipes (large) with no insulation to EI 20 - 120 260
Alupex pipes with no insulation to EI 120 235 Copper pipes with combustible insulation to EI 60 - 240 261
Alupex pipes with combustible insulation to EI 120 236 Copper pipes with continuous insulation to EI 120 262
Alupex pipes with stone wool insulation to EI 90 - 120 237 Copper pipes with continuous insulation, loadbearing 263
Alupex pipes with stone wool insulation to EI 120 - 240 238 Copper pipes with stone wool insulation to EI 180 - 240 264
Plastic pipes (small) to EI 60 – 90 & E 120 239 Copper pipes with stone wool insulation, loadbearing 265
PEX pipe-in pipes to EI 90 - 120 240 Alupex pipes with no insulation to EI 180 266
Plastic pipes (full range) to EI 90 - 120 241 Alupex pipes (large) with no insulation to EI 20 & E 240 267
Plastic pipes (full range) to EI 120 - 240 242 Alupex pipes with combustible insulation to EI 90 - 240 268
Composite plastic pipes to EI 60 - 120 243 Alupex pipes with stone wool insulation to EI 180 - 240 269
Plastic conduits to EI 90 & E 120 244 Alupex pipes with stone wool insulation, loadbearing 270
Ventilation ducts to EI 60 - 120 245 Plastic pipes (small) to EI 120 - 240 271
P a g e | 321
INDEX
Plastic pipes (small) to EI 120 - 240, loadbearing 272 Masonry and concrete walls to EI 60 (single board) 289-290
PEX pipe-in pipes to EI 120 273 Masonry and concrete walls to E 120 (single board) 291-292
Plastic pipes (full range) to EI 90 - 240 274 Masonry and concrete walls to EI 60 (double boards) 293-296
Plastic pipes, additional approvals in 120mm cast 275 Masonry and concrete walls to EI 120 297-299
Plastic pipes, additional approvals in 150mm cast 276 Concrete floors to EI 60 (with 50mm cast depth) 300-301
Composite plastic pipes to EI 120 - 240 277 Concrete floors to E 120 (with 50mm cast depth) 302-303
Conduits (pipes with cables) to EI 60 - 120 278 Concrete floors to EI 60 (with 100mm cast depth) 304-307
Ventilation ducts to EI 60 - 120 279 Concrete floors to EI 120 (with 100mm cast depth) 308-311
Concrete floors to EI 120 (with 150mm cast depth) 312-316
Appendix V – Apertures with mixed services
Drywalls (75mm) to EI 30 281-282
Drywalls with framed apertures to EI 60 283-284
Drywalls to EI 60 285-288

P a g e | 322
Contact us
United Kingdom
Head Office and Factory
Polyseam Ltd,
15 St Andrews Road,
Huddersfield, HD1 6SB.
United Kingdom.
T: +44 (0) 1484 421036
E: post.uk@polyseam.com

Norway
Polyseam AS,
Ravneveien 7,
N-3174 Revetal, Norway.
T: +47 3330 6700
E: post.no@polyseam.com

Sweden
Polyseam AB,
Frukthandlarvägen 7
120 44 Årsta, Sweden.
T: +46 (0) 8 124 563 00
E: post.se@polyseam.com

www.protecta.eu