Model ESFR-34
33.6 K-factor Pendent Sprinklers
Early Suppression, Fast Response
General NOTICE
The Model ESFR-34 Sprinklers
Description described herein must be installed
and maintained in compliance with this
TYCO Model ESFR-34 Pendent Sprin- document, as well as with the applica-
klers are Early Suppression, Fast ble standards of FM Global, in addi-
Response Sprinklers having a nominal tion to the standards of any authorities
K-factor of 33.6 (See Figure 1). They are having jurisdiction. Failure to do so
suppression-mode sprinklers that are may impair the performance of these
especially advantageous as a means of devices.
eliminating the use of in-rack sprinklers
when protecting high-piled storage. The owner is responsible for main-
taining their fire protection system
The Model ESFR-34 Sprinklers are pri- and devices in proper operating con-
marily used for ceiling-only sprinkler dition. Contact the installing contrac-
protection of (but not limited to) the tor or product manufacturer with any
following storage applications: questions.
• most encapsulated or non-encap-
sulated common materials including
In all cases, the appropriate FM instal-
lation standard, or other applicable Technical
cartoned, unexpanded plastics
• uncartoned (exposed) expanded
standard, must be referenced to ensure
applicability and to obtain complete Data
plastics in accordance with FM installation guidelines. The general Approvals
Global standards guidelines in this technical data sheet FM Approved
are not intended to provide complete
For more specific criteria, refer to Table installation criteria. Finish
B as well as the applicable design Natural Brass
standard.
The Model ESFR-34 can protect a
Sprinkler Physical Characteristics
Frame ���������������������������������������������������������Brass
storage arrangement of 50 ft (15,2 m)
with a ceiling height of 55 ft (16,8 m)
Identification Deflector ���������������������������������������������������Bronze
Compression Screw �������������������� Stainless Steel
Operation
The fusible link assembly is com-
prised of two link halves that are joined
IMPORTANT together by a thin layer of solder. When
Refer to Technical Data Sheet the rated temperature is reached, the
TFP2300 for warnings pertaining to solder melts and the two link halves
regulatory and health information. separate, activating the sprinkler and
flowing water.
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
1-1/4" NPT
1
Components:
8
1 - Frame
2 - Deflector 2-1/16"
3 - Compression 7 5/8" (52,4 mm)
Screw (15,9 mm)
4 - Hook 6 NOMINAL
5 - Strut 4-3/16" MAKE-IN
6 - Link (106,4 mm)
Assembly 5
CENTERLINE
7 - Button OF THERMAL
Assembly WRENCH
4 ELEMENT
8 - Sealing FLATS
Assembly
3
2
TEMPERATURE 2-1/4"
RATING (57,2 mm)
FIGURE 1
MODEL ESFR-34 (TY9286) EARLY SUPPRESSION, FAST RESPONSE
PENDENT SPRINKLER 33.6 K-FACTOR
The following general guidelines pro- K-factor, gpm/psi½ (lpm/bar½) 33.6 gpm/psi½ (480 lpm/bar½)
vided for the TYCO Model ESFR-34
Pendent Sprinklers can be used for a Thread Size 1 1/4 in. NPT or ISO 7-R 1 1/4
quick reference.
Sprinkler Orientation Pendent
FM Global Property Loss Prevention
Data Sheet 2-0, “Installation Guide- Maximum Working Pressure, psi (bar) 175 psi (12,1 bar)
lines for Automatic Sprinklers”, pro-
vides the installation guidelines for TABLE A
the TYCO K33.6 sprinkler under the MODEL ESFR-34 PENDENT SPRINKLER
heading of Storage Sprinkler, whereas TECHNICAL DATA
FM Global Property Loss Prevention
Data Sheet 8-9, “Storage of Class 1, Roof Construction Minimum Spacing
2, 3, 4 and Plastic Commodities”, pro- Refer to FM 2-0, Section 2.2 8 ft (2,4 m)
vides its design guidelines. In all cases,
the appropriate FM Global installation Ceiling Slope Minimum Deflector to Top of
standard must be referenced to ensure Up to 10° Storage
applicability and cannot be substituted Maximum Coverage Area 36 in. (914 mm)
by other codes or standards. Table B 100 ft² (9,3 m²) Minimum Aisle Width
provides a summary of the design 6 ft (1,8 m)
and installation guidelines provided in Minimum Coverage Area
Data Sheets 2-0 and 8-9; they are not 64 ft² (5,8 m²) Centerline of Thermal Sensing
intended to provide complete installa- Maximum Spacing Element-to-Ceiling Distance
tion criteria. • 12 ft (3,7 m) for building heights up • Max. Distance: 17 in. (432 mm)
to 30 ft (9,1 m) • Min. Distance: Refer to FM 2-0,
• 10 ft (3,0 m) for building heights Section 2.2
greater than 30 ft (9,1 m)
TFP338
Page 3 of 4
Description Specification
Response Type QR
Open Frame (i.e., no solid shelves) Single, Double, Multiple Row, Refer to FM 2-0 and 8-9
or Portable Rack Storage of Class I-IV and Group A or B Plastics
Solid Pile or Palletized Storage of Class I-IV and Group A or B Refer to FM 2-0 and 8-9
Plastics
TABLE B
MODEL ESFR-34 PENDENT SPRINKLERS
COMMODITY SELECTION AND DESIGN CRITERIA