www.tyco-fire.com
Contacts
Refer to Table C for specific details on K-factor, (gpm/psi) (lpm/bar) 11.2 GPM/psi½ (161,4 LPM/bar½)
laboratory and approvals, including
corrosion-resistant status. The approv- 155 ºF (68 ºC)1
als apply to the service conditions indi- Temperature Rating °F (°C)1 200 ºF (93 ºC)
cated in the Design Criteria section.) 286 ºF (141 ºC)
Finishes Thread Size 3/4 in. NPT or 1/2 in. NPT
Refer to Table C
Physical Characteristics Sprinkler Orientation Upright/Pendent
Frame �������������������������������������������������������Bronze
Cap �����������������������������������������������������������Bronze Maximum Working Pressure, psi (bar) 175 psi (12,1 bar)
Sealing Assembly. . Beryllium Nickel w/TEFLON Note:
Bulb (5 mm dia.) ����������������������������������������� Glass 1. Refer to Table C for laboratory listings and approvals.
Compression Screw ���������������������������������Bronze
Deflector ���������������������������������������������������Bronze TABLE A
Additional Technical Data SERIES ELO-231B 11.2K UPRIGHT AND PENDENT SPRINKLERS
Refer to Table A for additional techni- TECHNICAL DATA
cal data.
Response Type SR SR
Solid Pile or Palletized Storage of Class I-IV and Group A or B Refer to NFPA 13 Refer to FM 2-0 and 8-9
Plastics
Idle Pallet Storage Refer to NFPA 13 Refer to FM 2-0, 8-9, and 8-24
Rolled Paper Storage (Refer to the standard.) Refer to NFPA 13 Refer to FM 8-21
Flammable Liquid Storage (Refer to the standard.) Refer to NFPA 30 Refer to FM 7-29
Aerosol Storage (Refer to the standard.) Refer to NFPA 30B Refer to FM 7-31
Automotive Components in Portable Racks (Control mode only, Refer to NFPA 13 N/A
refer to the standard.)
Note:
1. Refer to Table C for laboratory listings and approvals.
N/A - Not Applicable
TABLE B
SERIES ELO-231B 11.2K UPRIGHT AND PENDENT SPRINKLERS
COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW
SPRINKLER FINISH
SPRINKLER TEMPERATURE BULB
TYPE RATING LIQUID NATURAL CHROME LEAD WAX WAX-OVER-LEAD
BRASS PLATED COATED COATED COATED
155°F (68°C) Red
UPRIGHT 3
200°F (93°C) Green 1, 2, 3, 4
(TY5151 & TY5851)
286°F (141°C) Blue 3 3a
155°F (68°C) Red
PENDENT 3
200°F (93°C) Green 1, 2, 3, 4
(TY5251)
286°F (141°C) Blue 3 3a
Notes:
1. Listed by Underwriters Laboratories, Inc. (UL)
2. Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL)
3. Approved by FM Global (FM Approvals)
4. Approved by the City of New York (NYC) under MEA 291-04-E
a. Listed/Approved for a maximum ceiling temperature of 150°F (66°C).
TABLE C
SERIES ELO-231B 11.2K UPRIGHT AND PENDENT SPRINKLERS, STANDARD RESPONSE
LABORATORY LISTINGS AND APPROVALS
TFP342
Page 4 of 6
"FITTING SIDE"
TOWARDS SPRINKLER
that an 8 in. or 10 in. adjustable wrench
is to be used for wax-coated sprinklers. Care and
FITTING With reference to Figure 1, the W-Type
3 Sprinkler Wrench or the adjustable Maintenance
wrench, as applicable, is to be applied TYCO Series ELO-231B 11.2K Standard
to the wrench flats. Response, Standard Coverage Upright
When installing wax-coated sprinklers and Pendent Sprinklers must be main-
with the adjustable wrench, additional tained and serviced in accordance with
WRENCH care needs to be exercised to prevent this section.
RECESS damage to the wax coating on the
(END "A") Before closing a fire protection system
sprinkler wrench flats or frame arms control valve for maintenance work on
and, consequently, exposure of bare the fire protection system that it con-
FIGURE 2 metal to the corrosive environment. trols, permission to shut down the
W-TYPE 3 The jaws of the wrench should be affected fire protection system must
SPRINKLER WRENCH opened sufficiently wide to pass over be obtained from the proper authorities
the wrench flats without damaging the and all personnel who may be affected
Installation wax coating. Before wrench-tightening
the sprinkler, the jaws of the wrench are
by this action must be notified.
to be adjusted to just contact the sprin- Sprinklers that are found to be leaking
TYCO Series ELO-231B 11.2K Stan- kler wrench flats. After wrench-tight- or exhibiting visible signs of corrosion
dard Response, Standard Coverage ening the sprinkler, loosen the wrench must be replaced.
Upright and Pendent Sprinklers must jaws before removing the wrench.
be installed in accordance with this Automatic sprinklers must never be
section. After installation, the sprinkler painted, plated, coated or other-
wrench flats and frame arms must wise altered after leaving the factory.
A leak-tight 3/4 in. NPT sprinkler joint be inspected and the wax coating Modified sprinklers must be replaced.
should be obtained by applying a min- retouched (repaired) whenever the Sprinklers that have been exposed to
imum-to-maximum torque of 10 to 20 coating has been damaged and bare corrosive products of combustion, but
lb-ft (13,4 to 26,8 N∙m). A leak-tight metal is exposed. The wax coating on have not operated, should be replaced
1/2 in. NPT sprinkler joint should be the wrench flats can be retouched by if they cannot be completely cleaned
obtained by applying a minimum-to- gently applying a heated 1/8 in. diam- by wiping the sprinkler with a cloth or
maximum torque of 7 to 14 lb-ft (9,5 eter steel rod to the areas of wax that by brushing it with a soft bristle brush.
to 19,0 N∙m). Higher levels of torque have been damaged, to smooth it
can distort the sprinkler inlet with con- Care must be exercised to avoid
back over areas where bare metal is damage to the sprinklers before,
sequent leakage or impairment of the exposed.
sprinkler. during, and after installation. Sprin-
Notes: Only retouching of the wax klers damaged by dropping, striking,
Notes: Do not install any bulb type coating applied to the wrench flats wrench twist/slippage, or the like, must
sprinkler if the bulb is cracked or there and frame arms is permitted, and be replaced. Also, replace any sprin-
is a loss of liquid from the bulb. With the retouching is to be performed kler that has a cracked bulb or that has
the sprinkler held horizontally, a small only at the time of the initial sprinkler lost liquid from its bulb. For additional
air bubble should be present. The installation. information, refer to Installation section.
diameter of the air bubble is approxi-
mately 1/16 in. (1,6 mm) for the 155°F The steel rod should be heated only Frequent visual inspections are rec-
(68°C) to 3/32 in. (2,4 mm) for the to the point at which it can begin to ommended to be initially performed
286°F (141°C) temperature ratings. melt the wax, and appropriate precau- for corrosion resistant sprinklers, after
tions need to be taken, when handling the installation has been completed, to
Do not attempt to make up for insuf- the heated rod, in order to prevent the verify the long term potential integrity
ficient adjustment in the escutcheon installer from being burned. of the sprinkler coatings. Thereafter,
plate by under- or over-tightening the annual inspections per NFPA 25 should
sprinkler. Re-adjust the position of the If attempts to retouch the wax coating suffice; however, instead of inspecting
sprinkler fitting to suit. with complete coverage are unsuc- from the floor level, a random sampling
cessful, additional wax can be ordered of close-up visual inspections should
The Series ELO-231B Upright and in the form of a wax stick (the end
Pendent Sprinklers must be installed be made, so as to better determine the
of which is color-coded). Only the exact sprinkler condition and the long
in accordance with the following correct color-coded wax is to be
instructions. term integrity of the corrosion resistant
used, and retouching of wrench flats coating, as it may be affected by the
Note: Pendent sprinklers are to be and frame arms is only permitted at corrosive conditions present.
installed in the pendent position; the time of initial sprinkler installation.
upright sprinklers are to be installed in With the steel rod heated as previ- The owner is responsible for the
the upright position. ously described, touch the rod to the inspection, testing, and maintenance of
area requiring additional wax with the their fire protection system and devices
Step 1. With pipe thread sealant in compliance with this document, as
rod angled downward, and then touch
applied to the pipe threads, hand- well as with the applicable standards
the wax stick to the rod approximately
tighten the sprinkler into the sprinkler of the National Fire Protection Associ-
1/2 in. away from the area requiring
fitting. ation, such as NFPA 25, in addition to
retouching. The wax will melt and run
Step 2. Tighten the sprinkler into the down onto the sprinkler. the standards of any other authorities
sprinkler fitting using only the W-Type 3 having jurisdiction. Contact the install-
Sprinkler Wrench (Ref. Figure 2), except ing contractor or product manufacturer
with any questions.
TFP342
Page 5 of 6
P/N 50 — XXX — X — XXX
TABLE D
SERIES ELO-231B 11.2K UPRIGHT AND PENDENT SPRINKLERS, STANDARD RESPONSE
PART NUMBER SELECTION
NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;
TEFLON is a registered trademark of DuPont
VNIV.EX5985 - Sprinklers, Automatic and Open | UL Product iQ https://iq.ulprospector.com/en/profile?e=160281
Sprinkler Identification Numbers (SIN) TY1121, TY1221, TY1281, TY1282, TY1381, TY1382, TY3101, TY3103, TY3121, TY3123, TY3210, TY3221,
TY3281, TY3282, TY3290, TY3301, TY3321, TY3322, TY3381, TY3382, TY3390, TY4101, TY4103, TY4121, TY4123, TY4210, TY4321, TY4322,
TY4801, TY4910, TY9128 Fusible Element Type.
Sprinkler Identification Numbers (SIN) TY313, TY315, TY323, TY325, TY363, TY365, TY1131, TY1151, TY1231, TY1251, TY1331, TY2131, TY2231,
TY3104, TY3131, TY3133, TY3151, TY3153, TY3187, TY3191, TY3201, TY3230, TY3231, TY3250, TY3251, TY3291,TY3296, TY3331, TY3332,
TY3351, TY3391, TY3431, TY3451, TY3530, TY3535, TY3539, TY3532, TY3537, TY3550, TY3555, TY3631, TY3651, TY3582, TY4131, TY4133,
TY4151, TY4153, TY4191, TY4231, TY4251, TY4292, TY4232, TY4282, TY4332, TY4631, TY4651, TY4831, TY4851, TY4931, TY4951, TY5131,
TY5137, TY5151, TY5153, TY5231, TY5237, TY5251, TY5332, TY5337, TY5339, TY5831, TY5851, TY6137, TY6237, TY7103, TY7153, TY8131,
TY8151, TY8181, TY8191, TY8231, TY8151, TY8281, TY8291, TY8331, TY8351, TY9131, TY9151, TY9181, TY9191, TY9231, TY9251, TY9281,
TY9291 glass bulb type.
Sprinkler Identification Numbers (SIN) TY3111, TY3113, TY3211, TY3311, TY4113, TY4211, TY4811 and TY4911 are center strut type sprinklers.
Chrome plated sprinklers are identified by an unplated area where the deflector is staked to the frame and/or unplated ends of the center
strut. Telfon coated sprinklers are identified by the chrome plated operating mechanism.
Sprinkler Identification Numbers (SIN) TY3135, TY3155, TY3230, TY3235, TY3250, TY3255, TY3335, TY3337, TY3339, TY3355, TY3338, TY3357,
TY3358, TY3735, TY3835, TY3935, TY4235, TY4255, TY5255, TY5235, TY5238, dry sprinkler glass bulb type.
Sprinkler Identification Numbers (SIN) TY3187, TY4180, TY4181, TY4182, TY2180, TY2181, TY2182 are plain brass glass bulb type attic
sprinklers.
Sprinkler Identification Numbers (SIN) TY3180, TY3181, TY3182, TY3183, TY3184, TY3185, TY3521, TY4522, TY5521, TY5522, TY9128 are fusible
link type sprinklers.
Sprinkler Identification Numbers (SIN) TY1189, TY2189, TY2190, TY3189, TY3190, TY2199, TY3199 are plain brass glass bulb type quick
response sprinklers for concealed spaces.
Sprinkler Identification Numbers (SIN) TY5111, TY5211, TY5811 are center strut type sprinklers.
Sprinkler Identification Numbers (SIN) SA1131, SA1132, SA1151, SA1152 glass bulb type.
1 of 21 09/11/21, 4:19 PM
VNIV.EX5985 - Sprinklers, Automatic and Open | UL Product iQ https://iq.ulprospector.com/en/profile?e=160281
TY3251 SR Pendent 250 135, 155, 175, 200, 286, 360, 500
TY3151 SR Upright 250 135, 155, 175, 200, 286, 360, 500
2 of 21 09/11/21, 4:19 PM
VNIV.EX5985 - Sprinklers, Automatic and Open | UL Product iQ https://iq.ulprospector.com/en/profile?e=160281
TY1251 SR Pendent 2.8 175 135, 155, 175, 200, 286, 360
TY1151 SR Upright 2.8 175 135, 155, 175, 200, 286, 360
TY4251 SR Pendent 3/4 175 135, 155, 175, 200, 286, 360
TY4951 SR Pendent 1/2, 3/4 175 135, 155, 175, 200, 286, 360
TY4151 SR Upright 3/4 175 135, 155, 175, 200, 286, 360
TY4851 SR Upright 1/2, 3/4 175 135, 155, 175, 200, 286, 360
3 of 21 09/11/21, 4:19 PM
VNIV.EX5985 - Sprinklers, Automatic and Open | UL Product iQ https://iq.ulprospector.com/en/profile?e=160281
TY3351+, ++ SR HSW 5.6 250 135, 155, 175, 200, 286, 360
TY3451 SR VSW 5.6 175 135, 155, 175, 200, 286, 360
Temp Rating, °F
Response Nom System Working
SIN Type Type K-Factor Pressure, psig Cover Sprinkler
TY3231 QR Rec. Pendent 5.6 250 — 135, 155, 175, 200, 286
TY4231 QR Rec. Pendent 8.0 175 — 135, 155, 175, 200, 286
4 of 21 09/11/21, 4:19 PM
VNIV.EX5985 - Sprinklers, Automatic and Open | UL Product iQ https://iq.ulprospector.com/en/profile?e=160281
TY3211 SR Rec. Pendent 5.6 175 — 135, 165, 212, 280, 360
TY3251 SR Rec. Pendent 5.6 250 — 135, 155, 175, 200, 286
TY4211 SR Rec. Pendent 8.0 175 — 135, 165, 212, 280, 360
TY4251 SR Rec. Pendent 8.0 175 — 135, 155, 175, 200, 286
DRY SPRINKLERS
System
Working
Response Max Pressure, Temp Rating,
SIN Type Type Length, in. psig Nom K-Factor F
TY3235 QR Rec. Pendent 48 175 5.6 135, 155, 175, 200, 286
TY5235 QR Rec. Pendent 48 175 11.2 135, 155, 175, 200, 286
TY3355* SR HSW 48 175 5.6 135, 155, 175, 200, 286, 360
TY3255 SR Pendent 48 175 5.6 135, 155, 175, 200, 286, 360
TY5255 SR Pendent 48 175 11.2 135, 155, 175, 200, 286, 360
TY3255 SR Rec. Pendent 48 175 5.6 135, 155, 175, 200, 286
TY5255 SR Rec. Pendent 48 175 11.2 135, 155, 175, 200, 286
TY3155 SR Upright 48 175 5.6 135, 155, 175, 200, 286, 360
5 of 21 09/11/21, 4:19 PM
VNIV.EX5985 - Sprinklers, Automatic and Open | UL Product iQ https://iq.ulprospector.com/en/profile?e=160281
TY3230 QR Pendent, Rec. Pendent 48 175 5.6 135, 155, 175, 200, 286
TY3250 SR Pendent 48 175 5.6 135, 155, 175, 200, 286, 360
TY3250 SR Rec. Pendent 48 175 5.6 135, 155, 175, 200, 286
TY3337 QR Pendent, Rec. Pendent 48 175 5.6 135, 155, 175, 200, 286
TY3357* SR HSW 48 175 5.6 135, 155, 175, 200, 286, 360
TY3357* SR Rec. HSW 48 175 5.6 135, 155, 175, 200, 286
TY3935+ QR Rec. Pendent 48 175 5.6 135, 155, 175, 200, 286
TY4235 QR Rec. Pendent 48 175 8.0 135, 155, 175, 200, 286
TY4255 SR Pendent 48 175 8.0 135, 155, 175, 200, 286, 360
TY4255 SR Rec. Pendent 48 175 8.0 135, 155, 175, 200, 286
# The 155°F sprinkler utilizes a 135°F coverplate and the 200°F sprinkler utilizes a 155°F coverplate
6 of 21 09/11/21, 4:19 PM
VNIV.EX5985 - Sprinklers, Automatic and Open | UL Product iQ https://iq.ulprospector.com/en/profile?e=160281
System Distance
Max Max Min Working Below
Width Length Flow Pressure, Nom Ceiling
SIN Type (A) Ft (B) Ft GPM psig K-Factor In. Temp Rating, °F
7 of 21 09/11/21, 4:19 PM
VNIV.EX5985 - Sprinklers, Automatic and Open | UL Product iQ https://iq.ulprospector.com/en/profile?e=160281
8 of 21 09/11/21, 4:19 PM
VNIV.EX5985 - Sprinklers, Automatic and Open | UL Product iQ https://iq.ulprospector.com/en/profile?e=160281
9 of 21 09/11/21, 4:19 PM
VNIV.EX5985 - Sprinklers, Automatic and Open | UL Product iQ https://iq.ulprospector.com/en/profile?e=160281
* The 155 or 160°F sprinkler utilizes a 135°F coverplate and the 200 or 212°F sprinkler utilizes a 165°F coverplate.
10 of 21 09/11/21, 4:19 PM
VNIV.EX5985 - Sprinklers, Automatic and Open | UL Product iQ https://iq.ulprospector.com/en/profile?e=160281
11 of 21 09/11/21, 4:19 PM
VNIV.EX5985 - Sprinklers, Automatic and Open | UL Product iQ https://iq.ulprospector.com/en/profile?e=160281
+ Sprinklers are suitable for installation below noncombustible obstructed construction as described in NFPA 13.
12 of 21 09/11/21, 4:19 PM
VNIV.EX5985 - Sprinklers, Automatic and Open | UL Product iQ https://iq.ulprospector.com/en/profile?e=160281
TY5237+ Pendent, Rec. Pendent 14 x 14 1 30 11.2 135, 155, 175, 200, 286
TY5237+ Pendent, Rec. Pendent 14 x 14 2 39 11.2 135, 155, 175, 200, 286
TY5238 Pendent, Rec. Pendent 14 x 14 1 30 11.2 135, 155, 175, 200, 286
TY5238 Pendent, Rec. Pendent 14 x 14 2 39 11.2 135, 155, 175, 200, 286
+ Sprinklers are suitable for installation below noncombustible obstructed construction as described in NFPA 13-1999.
TY3351 HSW 5.6 Polyester, lead 135, 155, 175, 200, 286, 360
TY3331 HSW 5.6 Polyester, lead 135, 155, 175, 200, 286
13 of 21 09/11/21, 4:19 PM
VNIV.EX5985 - Sprinklers, Automatic and Open | UL Product iQ https://iq.ulprospector.com/en/profile?e=160281
TY3351 HSW 5.6 Wax, Wax over lead 135, 155, 175, 200
TY3251 Pendent 5.6 Polyester, lead 135, 155, 175, 200, 286, 360
TY3231 Pendent 5.6 Polyester, lead 135, 155, 175, 200, 286
TY3251 Pendent 5.6 Wax, Wax over lead 135, 155, 175, 200
TY4251 Pendent 8.0 Polyester, lead 135, 155, 175, 200, 286, 360
TY4231 Pendent 8.0 Polyester, lead 135, 155, 175, 200, 286
TY4251 Pendent 8.0 Wax, Wax over lead 135, 155, 175, 200
TY3153 Upright 5.6 Lead 135, 155, 175, 200, 286, 360
TY3151 Upright 5.6 Polyester, lead 135, 155, 175, 200, 286, 360
TY3131 Upright 5.6 Polyester, lead 135, 155, 175, 200, 286
14 of 21 09/11/21, 4:19 PM
VNIV.EX5985 - Sprinklers, Automatic and Open | UL Product iQ https://iq.ulprospector.com/en/profile?e=160281
TY3151 Upright 5.6 Wax, Wax over lead 135, 155, 175, 200
TY4153 Upright 8.0 Lead 135, 155, 175, 200, 286, 360
TY4151 Upright 8.0 Polyester, lead 135, 155, 175, 200, 286, 360
TY4131 Upright 8.0 Polyester, lead 135, 155, 175, 200, 286
TY4151 Upright 8.0 Wax, Wax over lead 135, 155, 175, 200
TY3431 VSW 5.6 Polyester, lead 135, 155, 175, 200, 286
TY3451 VSW 5.6 Polyester, lead 135, 155, 175, 200, 286, 360
TY3451 VSW 5.6 Wax, Wax over lead 135, 155, 175, 200
TY9281 Pendent 8.0 Stainless Steel 135, 155, 175, 200, 286
TY8181 Upright 5.6 Stainless Steel 135, 155, 175, 200, 286
TY8281 Pendent 5.6 Stainless Steel 135, 155, 175, 200, 286
TY9181 Upright 8.0 Stainless Steel 135, 155, 175, 200, 286
TY8291 Pendent 5.6 Stainless Steel 135, 155, 175, 200, 286, 360, 500
TY8191 Upright 5.6 Stainless Steel 135, 155, 175, 200, 286, 360, 500
TY9291 Pendent 8.0 Stainless Steel 135, 155, 175, 200, 286, 360, 500
TY9191 Upright 8.0 Stainless Steel 135, 155, 175, 200, 286, 360, 500
15 of 21 09/11/21, 4:19 PM
VNIV.EX5985 - Sprinklers, Automatic and Open | UL Product iQ https://iq.ulprospector.com/en/profile?e=160281
TY3230 Pendent 5.6 Stainless Steel 135, 155, 175, 200, 286
TY3250 Pendent 5.6 Stainless Steel 135, 155, 175, 200, 286, 360
TY3337 HSW 5.6 Stainless Steel 135, 155, 175, 200, 286
TY3357 HSW 5.6 Stainless Steel 135, 155, 175, 200, 286, 360
TY3339 HSW 5.6 Stainless Steel 135, 155, 175, 200, 286
TY8131 Upright 5.6 Polyester 135, 155, 175, 200, 286, 360
TY8151 Upright 5.6 Polyester 135, 155, 175, 200, 286, 360
TY8231 Pendent 5.6 Polyester 135, 155, 175, 200, 286, 360
TY8251 Pendent 5.6 Polyester 135, 155, 175, 200, 286, 360
TY8331 HSW 5.6 Polyester 135, 155, 175, 200, 286, 360
TY8351 HSW 5.6 Polyester 135, 155, 175, 200, 286, 360
TY9131 Upright 8.0 Polyester 135, 155, 175, 200, 286, 360
TY9151 Upright 8.0 Polyester 135, 155, 175, 200, 286, 360
TY9231 Pendent 8.0 Polyester 135, 155, 175, 200, 286, 360
TY9251 Pendent 8.0 Polyester 135, 155, 175, 200, 286, 360
16 of 21 09/11/21, 4:19 PM
VNIV.EX5985 - Sprinklers, Automatic and Open | UL Product iQ https://iq.ulprospector.com/en/profile?e=160281
17 of 21 09/11/21, 4:19 PM
VNIV.EX5985 - Sprinklers, Automatic and Open | UL Product iQ https://iq.ulprospector.com/en/profile?e=160281
* These sprinklers are available with or without sprinkler guards Models G1 and G4 as covered under File MS26602.
EXTENDED COVERAGE SPRINKLERS FOR STORAGE PROTECTION (CONTROL MODE DENSITY AREA)
Max
Response Width x Length Nom
SIN Type Ft x Ft Type K-Factor Temp Rating, F
These sprinklers have not been investigated for use as a Control Mode Specific Application (CMSA) sprinkler in accordance with NFPA 13.
18 of 21 09/11/21, 4:19 PM
VNIV.EX5985 - Sprinklers, Automatic and Open | UL Product iQ https://iq.ulprospector.com/en/profile?e=160281
Min
Roof Flow
Response Fire Pitch Max Max Rate Nom Temp
SIN Type Risk (In./In.) Width Ft Length Ft GPM K-Factor Rating, F
++ For protection of Light Hazard attic spaces of wood truss or open wood joist construction with saddle type roofs in buildings 20 to 60 ft in
width and not exceeding a protection area of 400 sq ft per sprinkler when installed in accordance with the manufacturer' s installation and
design parameter instructions.
19 of 21 09/11/21, 4:19 PM
VNIV.EX5985 - Sprinklers, Automatic and Open | UL Product iQ https://iq.ulprospector.com/en/profile?e=160281
Window Sprinklers
Min
Distance Flow
Response Fire Nom Between Rate Temp
SIN Type Risk Type K-Factor Sprinklers, Ft GPM Rating, F
* For use on heat-strengthened or tempered glass windows without horizontal mullions having a maximum height of 13 ft. Combustibles must
be maintained at a minimum distance of 2 in. from the glass. This may be accomplished by use of a 3 ft. pony wall or any other method
acceptable to the authority having jurisdiction when installed in accordance with the manufacturer's installation and design parameter
instructions.
% For use on UL certified FireLite Plus ceramic glass (by Technical Glass Products) without horizontal mullions having a maximum height of 8
ft. Combustibles are not required to be maintained at any minimum distance from the glass when the sprinklers are installed in accordance
with the manufacturer's installation and design parameter instructions.
Authorities having jurisdiction shall be consulted to determine the hydraulic requirements for each installation.
Max
Response Height of Space, In. Coverage Nom Temp
SIN Type Type Min Max Area, Ft2 K-Factor Rating, F
20 of 21 09/11/21, 4:19 PM
VNIV.EX5985 - Sprinklers, Automatic and Open | UL Product iQ https://iq.ulprospector.com/en/profile?e=160281
+ For use in light hazard flat concealed spaces incorporating noncombustible or wood truss construction. The Manufacturers Installation and
Design Parameter Instructions should be consulted for specific installation parameters, obstruction criteria and hydraulic design requirements.
++ For use in combustible solid wood and composite wood joist construction.
% For use in attic areas outside the scope of application for the BB, SD or HIP sprinklers.
a - For use in combustible solid wood joists with baffle spaced at 2000 Ft2. The Manufacturers Installation and Design Parameter Instructions
should be consulted for specific installation parameters, obstruction criteria and hydraulic design requirements.
Corridor/Hallway Sprinklers
Max Width, Max Length, Min Flow, System Working Nom Temp
SIN Type ft (A) ft (B) gpm Pressure, psig K-Factor Rating, °F
+ For use in corridors and hallways of light hazard occupancies. The Manufacturer's Installation and Design Parameter Instructions should be
consulted for specific installation parameters, obstruction criteria, and hydraulic design requirements.
# The 155°F rated sprinkler uses a 139°F cover plate assembly and the 200°F rated sprinkler uses a 165°F rated cover plate assembly.
The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow-
Up Service. Always look for the Mark on the product.
UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non-
misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory
with permission from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice
in the following format: "© 2021 UL LLC"
21 of 21 09/11/21, 4:19 PM