Series ELO-231B – 11.2 K-factor


Upright and Pendent Sprinklers
Standard Response, Standard Coverage
General for any given corrosive environment.
The effects of ambient temperature,
Description concentration of chemicals, and gas/
chemical velocity, should be consid-
TYCO Series ELO-231B 11.2K Standard ered, as a minimum, along with the cor-
Response, Standard Coverage Upright rosive nature of the chemical to which
and Pendent Sprinklers (Ref. Figure 1) the sprinklers will be exposed.
are automatic sprinklers of the frangible An upright intermediate level version
bulb type. They are standard response, of the Series ELO-231B Sprinklers for
spray sprinklers that produce a hemi- in-rack applications can be obtained by
spherical water distribution pattern utilizing the Series ELO-231B Upright
below the deflector. Sprinkler with the WSG-2 Guard &
The 11.2 K-factor, ELO-231B Sprinklers Shield, and a pendent intermediate
were subjected to full-scale, high-piled level version of the Series ELO-231B
storage fire tests to qualify their use Sprinklers can be obtained by utilizing
in lieu of 5.6 or 8.0 K-factor standard the Series ELO-231B Pendent Sprinkler
spray sprinklers for the protection of with the WS-2 Shield. If there is a pos-
high-piled storage. sibility of the pendent intermediate level
version being exposed to mechanical
Higher flow rates can be achieved at damage, a G-2 Guard can be added.
much lower pressures with the 11.2
K-factor, ELO-231B Sprinklers, making NOTICE
their use highly advantageous in high
density applications, such as the pro- The 11.2 K-factor, Series ELO-231B
tection of high-piled storage. Upright and Pendent Sprinklers
described herein must be installed
Wax or lead coatings can be used and maintained in compliance with this
to extend the life of the copper alloy document, as well as with the applica-
components used in Series ELO-231B ble standards of the National Fire Pro-
Sprinklers beyond that which would tection Association (NFPA), in addition
otherwise be obtained when exposed to the standards of any other authori-
to corrosive atmospheres. Although ties having jurisdiction. Failure to do so
wax, lead, and polyester coated sprin- may impair the performance of these
klers have passed the standard corro- devices.
sion tests of the applicable approval
Sprinkler
agencies, the testing is not repre- The owner is responsible for main-
sentative of all possible corrosive taining their fire protection system
and devices in proper operating con-
atmospheres. Consequently, it is rec-
ommended that the end-user be con- dition. Contact the installing contrac- Identification
tor or product manufacturer with any
sulted with respect to the suitability
of these corrosion resistant coatings questions. Numbers (SINs)
Installation of Series ELO-231B Pendent Refer to Table A for sprinkler identifica-
IMPORTANT Sprinklers in recessed escutcheons will tion numbers.
Refer to Technical Data Sheet void all sprinkler warranties, as well as
TFP2300 for warnings pertaining to possibly void the sprinkler’s Approvals
regulatory and health information. and/or Listings.
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.

Page 1 of 6 AUGUST 2018 TFP342


TFP342
Page 2 of 6

1/2" (12,7 mm) Components:


NOMINAL MAKE-IN
1 - Frame
3/4" 2 - Seal
NPT 1 Assembly
3 - Cap
2-13/16" 2 4 - Bulb
(71,4 mm) WRENCH THREAD 5 - Compression
TYP. FLATS RELIEF 3 Screw
6 - Deflector *
4

1/2" 3/4" 5 * Temperature


NPT NPT rating is
indicated on
6
7/16" (11,1 mm) 1/2" (12,7 mm) deflector.
NOMINAL MAKE-IN NOMINAL MAKE-IN
UPRIGHT UPRIGHT PENDENT CROSS
TY5851 TY5151 TY5251 SECTION
FIGURE 1
SERIES ELO-231B 11.2K UPRIGHT 3/4 INCH NPT (TY5151), UPRIGHT 1/2 INCH NPT (TY5851), AND
PENDENT 3/4 INCH NPT (TY5251) SPRINKLERS, STANDARD RESPONSE

Technical Item Description

Data TY5151 - Upright 3/4 in. NPT


TY5251 -Pendent 3/4 in. NPT
Approvals TY5851 - Upright 1/2 in. NPT
Sprinkler Identification Number (SIN)
UL and C-UL Listed TY5151 is a re-designation for Central SIN C5151.
TY5251 is a re-designation for Central, Gem, and
FM Approved Star SINs C5251, G1871, and S2531, respectively.
NYC Approved TY5851 is a re-designation for Central SIN C5851.

Refer to Table C for specific details on K-factor, (gpm/psi) (lpm/bar) 11.2 GPM/psi½ (161,4 LPM/bar½)
laboratory and approvals, including
corrosion-resistant status. The approv- 155 ºF (68 ºC)1
als apply to the service conditions indi- Temperature Rating °F (°C)1 200 ºF (93 ºC)
cated in the Design Criteria section.) 286 ºF (141 ºC)
Finishes Thread Size 3/4 in. NPT or 1/2 in. NPT
Refer to Table C
Physical Characteristics Sprinkler Orientation Upright/Pendent
Frame �������������������������������������������������������Bronze
Cap �����������������������������������������������������������Bronze Maximum Working Pressure, psi (bar) 175 psi (12,1 bar)
Sealing Assembly. . Beryllium Nickel w/TEFLON Note:
Bulb (5 mm dia.) ����������������������������������������� Glass 1. Refer to Table C for laboratory listings and approvals.
Compression Screw ���������������������������������Bronze
Deflector ���������������������������������������������������Bronze TABLE A
Additional Technical Data SERIES ELO-231B 11.2K UPRIGHT AND PENDENT SPRINKLERS
Refer to Table A for additional techni- TECHNICAL DATA
cal data.

Operation Design and Group A plastics) with a minimum


residual (flowing) pressure of 7 psi (0,5

The glass bulb contains a fluid that


Criteria bar) for wet or dry pipe systems. Refer
to Table B for additional information.
expands when exposed to heat. When UL and C-UL FM Approval Requirements
the rated temperature is reached, the Listing Requirements The 11.2 K-factor, Model ELO-231B
fluid expands sufficiently to shatter the TYCO Series ELO-231B 11.2K Standard Sprinklers are to be installed in accor-
glass bulb, allowing the sprinkler to Response, Standard Coverage Upright dance with the applicable control mode
activate and water to flow. and Pendent Sprinklers are to be density/area guidelines provided by FM
installed in accordance with NFPA 13 Global.
standard sprinkler position and area/ Note: FM Approval guidelines may
density flow calculation requirements differ from UL and C-UL Listing criteria.
for light, ordinary, or extra hazard occu-
pancies, as well as high-piled storage
occupancies (solid-piled, palletized,
rack storage, bin box, and shelf storage
including but not limited to Class I-IV
TFP342
Page 3 of 6

Storage Type NFPA FM Global

Sprinkler Type Standard Coverage Storage

Response Type SR SR

System Type Wet, Dry Wet, Dry

155 ºF (68 ºC)1 155 ºF (68 ºC)1


Temperature Rating °F (°C)1 200 ºF (93 ºC) 200 ºF (93 ºC)
286 ºF (141 ºC) 286 ºF (141 ºC)
Open Frame (that is, no solid shelves) Single, Double, Multiple-
Row, or Portable Rack Storage of Class I-IV and Group A or B Refer to NFPA 13 Refer to FM 2-0 and 8-9
Plastics

Solid Pile or Palletized Storage of Class I-IV and Group A or B Refer to NFPA 13 Refer to FM 2-0 and 8-9
Plastics

Idle Pallet Storage Refer to NFPA 13 Refer to FM 2-0, 8-9, and 8-24

Rubber Tire Storage Refer to NFPA 13 Refer to FM 2-0 and 8-3

Rolled Paper Storage (Refer to the standard.) Refer to NFPA 13 Refer to FM 8-21

Flammable Liquid Storage (Refer to the standard.) Refer to NFPA 30 Refer to FM 7-29

Aerosol Storage (Refer to the standard.) Refer to NFPA 30B Refer to FM 7-31

Automotive Components in Portable Racks (Control mode only, Refer to NFPA 13 N/A
refer to the standard.)

Note:
1. Refer to Table C for laboratory listings and approvals.
N/A - Not Applicable

TABLE B
SERIES ELO-231B 11.2K UPRIGHT AND PENDENT SPRINKLERS
COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW

SPRINKLER FINISH
SPRINKLER TEMPERATURE BULB
TYPE RATING LIQUID NATURAL CHROME LEAD WAX WAX-OVER-LEAD
BRASS PLATED COATED COATED COATED
155°F (68°C) Red
UPRIGHT 3
200°F (93°C) Green 1, 2, 3, 4
(TY5151 & TY5851)
286°F (141°C) Blue 3 3a
155°F (68°C) Red
PENDENT 3
200°F (93°C) Green 1, 2, 3, 4
(TY5251)
286°F (141°C) Blue 3 3a
Notes:
1. Listed by Underwriters Laboratories, Inc. (UL)
2. Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL)
3. Approved by FM Global (FM Approvals)
4. Approved by the City of New York (NYC) under MEA 291-04-E
a. Listed/Approved for a maximum ceiling temperature of 150°F (66°C).
TABLE C
SERIES ELO-231B 11.2K UPRIGHT AND PENDENT SPRINKLERS, STANDARD RESPONSE
LABORATORY LISTINGS AND APPROVALS
TFP342
Page 4 of 6

"FITTING SIDE"
TOWARDS SPRINKLER
that an 8 in. or 10 in. adjustable wrench
is to be used for wax-coated sprinklers. Care and
FITTING With reference to Figure 1, the W-Type
3 Sprinkler Wrench or the adjustable Maintenance
wrench, as applicable, is to be applied TYCO Series ELO-231B 11.2K Standard
to the wrench flats. Response, Standard Coverage Upright
When installing wax-coated sprinklers and Pendent Sprinklers must be main-
with the adjustable wrench, additional tained and serviced in accordance with
WRENCH care needs to be exercised to prevent this section.
RECESS damage to the wax coating on the
(END "A") Before closing a fire protection system
sprinkler wrench flats or frame arms control valve for maintenance work on
and, consequently, exposure of bare the fire protection system that it con-
FIGURE 2 metal to the corrosive environment. trols, permission to shut down the
W-TYPE 3 The jaws of the wrench should be affected fire protection system must
SPRINKLER WRENCH opened sufficiently wide to pass over be obtained from the proper authorities
the wrench flats without damaging the and all personnel who may be affected
Installation wax coating. Before wrench-tightening
the sprinkler, the jaws of the wrench are
by this action must be notified.
to be adjusted to just contact the sprin- Sprinklers that are found to be leaking
TYCO Series ELO-231B 11.2K Stan- kler wrench flats. After wrench-tight- or exhibiting visible signs of corrosion
dard Response, Standard Coverage ening the sprinkler, loosen the wrench must be replaced.
Upright and Pendent Sprinklers must jaws before removing the wrench.
be installed in accordance with this Automatic sprinklers must never be
section. After installation, the sprinkler painted, plated, coated or other-
wrench flats and frame arms must wise altered after leaving the factory.
A leak-tight 3/4 in. NPT sprinkler joint be inspected and the wax coating Modified sprinklers must be replaced.
should be obtained by applying a min- retouched (repaired) whenever the Sprinklers that have been exposed to
imum-to-maximum torque of 10 to 20 coating has been damaged and bare corrosive products of combustion, but
lb-ft (13,4 to 26,8 N∙m). A leak-tight metal is exposed. The wax coating on have not operated, should be replaced
1/2 in. NPT sprinkler joint should be the wrench flats can be retouched by if they cannot be completely cleaned
obtained by applying a minimum-to- gently applying a heated 1/8 in. diam- by wiping the sprinkler with a cloth or
maximum torque of 7 to 14 lb-ft (9,5 eter steel rod to the areas of wax that by brushing it with a soft bristle brush.
to 19,0 N∙m). Higher levels of torque have been damaged, to smooth it
can distort the sprinkler inlet with con- Care must be exercised to avoid
back over areas where bare metal is damage to the sprinklers before,
sequent leakage or impairment of the exposed.
sprinkler. during, and after installation. Sprin-
Notes: Only retouching of the wax klers damaged by dropping, striking,
Notes: Do not install any bulb type coating applied to the wrench flats wrench twist/slippage, or the like, must
sprinkler if the bulb is cracked or there and frame arms is permitted, and be replaced. Also, replace any sprin-
is a loss of liquid from the bulb. With the retouching is to be performed kler that has a cracked bulb or that has
the sprinkler held horizontally, a small only at the time of the initial sprinkler lost liquid from its bulb. For additional
air bubble should be present. The installation. information, refer to Installation section.
diameter of the air bubble is approxi-
mately 1/16 in. (1,6 mm) for the 155°F The steel rod should be heated only Frequent visual inspections are rec-
(68°C) to 3/32 in. (2,4 mm) for the to the point at which it can begin to ommended to be initially performed
286°F (141°C) temperature ratings. melt the wax, and appropriate precau- for corrosion resistant sprinklers, after
tions need to be taken, when handling the installation has been completed, to
Do not attempt to make up for insuf- the heated rod, in order to prevent the verify the long term potential integrity
ficient adjustment in the escutcheon installer from being burned. of the sprinkler coatings. Thereafter,
plate by under- or over-tightening the annual inspections per NFPA 25 should
sprinkler. Re-adjust the position of the If attempts to retouch the wax coating suffice; however, instead of inspecting
sprinkler fitting to suit. with complete coverage are unsuc- from the floor level, a random sampling
cessful, additional wax can be ordered of close-up visual inspections should
The Series ELO-231B Upright and in the form of a wax stick (the end
Pendent Sprinklers must be installed be made, so as to better determine the
of which is color-coded). Only the exact sprinkler condition and the long
in accordance with the following correct color-coded wax is to be
instructions. term integrity of the corrosion resistant
used, and retouching of wrench flats coating, as it may be affected by the
Note: Pendent sprinklers are to be and frame arms is only permitted at corrosive conditions present.
installed in the pendent position; the time of initial sprinkler installation.
upright sprinklers are to be installed in With the steel rod heated as previ- The owner is responsible for the
the upright position. ously described, touch the rod to the inspection, testing, and maintenance of
area requiring additional wax with the their fire protection system and devices
Step 1. With pipe thread sealant in compliance with this document, as
rod angled downward, and then touch
applied to the pipe threads, hand- well as with the applicable standards
the wax stick to the rod approximately
tighten the sprinkler into the sprinkler of the National Fire Protection Associ-
1/2 in. away from the area requiring
fitting. ation, such as NFPA 25, in addition to
retouching. The wax will melt and run
Step 2. Tighten the sprinkler into the down onto the sprinkler. the standards of any other authorities
sprinkler fitting using only the W-Type 3 having jurisdiction. Contact the install-
Sprinkler Wrench (Ref. Figure 2), except ing contractor or product manufacturer
with any questions.
TFP342
Page 5 of 6

P/N  50 — XXX — X — XXX

SIN SPRINKLER TEMPERATURE


FINISH RATING

501 11.2K UPRIGHT (1/2 in. NPT) TY5851 NATURAL


1 155 155°F (68°C)
BRASS

510 11.2K UPRIGHT (3/4 in. NPT) TY5151 WAX


6 200 200°F (93°C)
COATED

512 11.2K PENDENT (3/4 in. NPT) TY5251 LEAD


7 286 286°F (141°C)
COATED
WAX-OVER-LEAD
8 COATED
CHROME
9 PLATED

TABLE D
SERIES ELO-231B 11.2K UPRIGHT AND PENDENT SPRINKLERS, STANDARD RESPONSE
PART NUMBER SELECTION

It is recommended that automatic


sprinkler systems be inspected, tested, Ordering Wax Sticks
(for retouching wrench-damaged wax
and maintained by a qualified Inspec-
tion Service in accordance with local Procedure coating)
Specify: (specify Color) color-coded
requirements and/or national codes. Wax Stick for retouching (specify tem-
Sprinkler Assemblies with
perature rating) temperature rated
Limited NPT Thread Connection
Specify: Series ELO-231B 11.2K Stan- Series ELO-231B Sprinklers, P/N
(specify):
Warranty
dard Response (specify Pendent
or Upright) Sprinkler, SIN (specify), Red for 155°F (68°C) . . . . . . . . . . . 56-065-1-155
(specify temperature rating), with Blue for 200°F (93°C)
For warranty terms and conditions, visit (specify) finish, P/N (specify from Table and 286°F (141°C) . . . . . . . . . . . . . 56-065-1-286
www.tyco-fire.com. D) Notes: Each wax stick is suitable for
Sprinkler Wrench retouching up to twenty-five sprinklers.
Specify: W-Type 3 Sprinkler Wrench, The wax used for 286°F (141°C) sprin-
P/N 56-895-1-001 klers is the same as for 200°F (93°C)
sprinklers, and, therefore, the 286°F
(141°C) sprinkler is limited to the same
maximum ceiling temperature as the
200°F (93°C)sprinkler, such as 150°F
(66°C).
TFP342
Page 6 of 6

1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700


© 2018 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.

NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;
TEFLON is a registered trademark of DuPont
VNIV.EX5985 - Sprinklers, Automatic and Open | UL Product iQ https://iq.ulprospector.com/en/profile?e=160281

VNIV.EX5985 - Sprinklers, Automatic and Open

Sprinklers, Automatic and Open


TYCO FIRE & BUILDING PRODUCTS EX5985
1400 PENNBROOK PKWY
LANSDALE, PA 19446-3840 United States

Sprinkler Identification Numbers (SIN) TY1121, TY1221, TY1281, TY1282, TY1381, TY1382, TY3101, TY3103, TY3121, TY3123, TY3210, TY3221,
TY3281, TY3282, TY3290, TY3301, TY3321, TY3322, TY3381, TY3382, TY3390, TY4101, TY4103, TY4121, TY4123, TY4210, TY4321, TY4322,
TY4801, TY4910, TY9128 Fusible Element Type.

Sprinkler Identification Numbers (SIN) TY313, TY315, TY323, TY325, TY363, TY365, TY1131, TY1151, TY1231, TY1251, TY1331, TY2131, TY2231,
TY3104, TY3131, TY3133, TY3151, TY3153, TY3187, TY3191, TY3201, TY3230, TY3231, TY3250, TY3251, TY3291,TY3296, TY3331, TY3332,
TY3351, TY3391, TY3431, TY3451, TY3530, TY3535, TY3539, TY3532, TY3537, TY3550, TY3555, TY3631, TY3651, TY3582, TY4131, TY4133,
TY4151, TY4153, TY4191, TY4231, TY4251, TY4292, TY4232, TY4282, TY4332, TY4631, TY4651, TY4831, TY4851, TY4931, TY4951, TY5131,
TY5137, TY5151, TY5153, TY5231, TY5237, TY5251, TY5332, TY5337, TY5339, TY5831, TY5851, TY6137, TY6237, TY7103, TY7153, TY8131,
TY8151, TY8181, TY8191, TY8231, TY8151, TY8281, TY8291, TY8331, TY8351, TY9131, TY9151, TY9181, TY9191, TY9231, TY9251, TY9281,
TY9291 glass bulb type.

Sprinkler Identification Numbers (SIN) TY3111, TY3113, TY3211, TY3311, TY4113, TY4211, TY4811 and TY4911 are center strut type sprinklers.
Chrome plated sprinklers are identified by an unplated area where the deflector is staked to the frame and/or unplated ends of the center
strut. Telfon coated sprinklers are identified by the chrome plated operating mechanism.

Sprinkler Identification Numbers (SIN) TY3135, TY3155, TY3230, TY3235, TY3250, TY3255, TY3335, TY3337, TY3339, TY3355, TY3338, TY3357,
TY3358, TY3735, TY3835, TY3935, TY4235, TY4255, TY5255, TY5235, TY5238, dry sprinkler glass bulb type.

Sprinkler Identification Numbers (SIN) TY3187, TY4180, TY4181, TY4182, TY2180, TY2181, TY2182 are plain brass glass bulb type attic
sprinklers.

Sprinkler Identification Numbers (SIN) TY3180, TY3181, TY3182, TY3183, TY3184, TY3185, TY3521, TY4522, TY5521, TY5522, TY9128 are fusible
link type sprinklers.

Sprinkler Identification Numbers (SIN) TY1189, TY2189, TY2190, TY3189, TY3190, TY2199, TY3199 are plain brass glass bulb type quick
response sprinklers for concealed spaces.

Sprinkler Identification Numbers (SIN) TY5111, TY5211, TY5811 are center strut type sprinklers.

Sprinkler Identification Numbers (SIN) SA1131, SA1132, SA1151, SA1152 glass bulb type.

UPRIGHT AND PENDENT STANDARD SPRAY SPRINKLERS


NOMINAL 5.6 K-FACTOR
Response System Working
SIN Type Type Pressure, psig Temp Rating, °F

TY313 QR Upright 250 135, 155, 175, 200, 286

TY315 SR Upright 250 135, 155, 175, 200, 286, 360

TY323 QR Pendent 250 135, 155, 175, 200, 286

TY325 SR Pendent 250 135, 155, 175, 200, 286, 360

TY3231 QR Pendent 250 135, 155, 175, 200, 286

1 of 21 09/11/21, 4:19 PM
VNIV.EX5985 - Sprinklers, Automatic and Open | UL Product iQ https://iq.ulprospector.com/en/profile?e=160281

TY3201 QR Pendent 175 135, 155, 175, 200, 286

TY3221 QR Pendent, Rec. Pendent 175 165, 212

TY3131 QR Upright 250 135, 155, 175, 200, 286

TY3121 QR Upright 175 165, 212

TY3211 SR Pendent 175 135, 165, 212, 280, 360, 500

TY3251 SR Pendent 250 135, 155, 175, 200, 286, 360, 500

TY3111 SR Upright 175 135, 165, 212, 286, 360

TY3151 SR Upright 250 135, 155, 175, 200, 286, 360, 500

TY3101 SR Upright 175 135,165,212,280,360

TY3210 SR Pendent 175 135,165,212,280,360

SA1131 QR Pendent 175 155, 175, 200, 286

SA1132 QR Upright 175 155, 175, 200, 286

SA1151 SR Pendent 175 155, 175, 200, 286

SA1152 SR Upright 175 155, 175, 200, 286

TY3296 SR Pendent 175 400, 500

TY3191 SR Upright 175 400, 500

TY8131 QR Upright 250 135, 155, 175, 200, 286, 360

TY8151 SR Upright 250 135, 155, 175, 200, 286, 360

TY8231 QR Pendent 250 135, 155, 175, 200, 286, 360

TY8251 SR Pendent 250 135, 155, 175, 200, 286, 360

TY8331 QR HSW 250 135, 155, 175, 200, 286, 360

TY8351 SR HSW 250 135, 155, 175, 200, 286, 360

TY9131 QR Upright 250 135, 155, 175, 200, 286, 360

TY9151 SR Upright 250 135, 155, 175, 200, 286, 360

TY9231 QR Pendent 250 135, 155, 175, 200, 286, 360

TY9251 SR Pendent 250 135, 155, 175, 200, 286, 360

NOMINAL 1.4 TO 4.2 K-FACTOR


Response Nom System Working
SIN Type Type K-Factor Pressure, psig Temp Rating, °F

TY1231 QR Pendent 2.8 175 135, 155, 175, 200, 286

TY2231 QR Pendent 4.2 175 135, 155, 175, 200, 286

2 of 21 09/11/21, 4:19 PM
VNIV.EX5985 - Sprinklers, Automatic and Open | UL Product iQ https://iq.ulprospector.com/en/profile?e=160281

TY1221 QR Pendent, Rec. Pendent 2.8 175 165, 212

TY1131 QR Upright 2.8 175 135, 155, 175, 200, 286

TY1121 QR Upright 2.8 175 165, 212

TY2131 QR Upright 4.2 175 135, 155, 175, 200, 286

TY1251 SR Pendent 2.8 175 135, 155, 175, 200, 286, 360

TY1151 SR Upright 2.8 175 135, 155, 175, 200, 286, 360

NOMINAL 8.0 K-FACTOR


Response Inlet System Working
SIN Type Type Thread NPT Pressure, psig Temp Rating, °F

TY4231 QR Pendent 3/4 175 135, 155, 175, 200, 286

TY4131 QR Upright 3/4 175 135, 155, 175, 200, 286

TY4121 QR Upright 3/4 175 165, 212

TY4221 QR Pendent 3/4 175 165, 212

TY4911 SR Pendent 1/2 175 135, 165, 212, 286, 360

TY4211 SR Pendent 3/4 175 135, 165, 212, 280, 286

TY4251 SR Pendent 3/4 175 135, 155, 175, 200, 286, 360

TY4951 SR Pendent 1/2, 3/4 175 135, 155, 175, 200, 286, 360

TY4811 SR Upright 1/2 175 135, 165, 212, 280, 360

TY4111 SR Upright 3/4 175 135, 165, 212, 280, 360

TY4151 SR Upright 3/4 175 135, 155, 175, 200, 286, 360

TY4831 QR Upright 1/2 175 135, 155, 175, 200, 286

TY4851 SR Upright 1/2, 3/4 175 135, 155, 175, 200, 286, 360

TY4931 QR Pendent 1/2 175 135, 155, 175, 200, 286

TY4101 SR Upright 3/4 175 135, 165, 212, 280, 360

TY4801 SR Upright 1/2 175 135, 165, 212, 280, 360

TY4210 SR Upright 3/4 175 135, 165, 212, 280, 360

TY4910 SR Upright 1/2 175 135, 165, 212, 280, 360

TY4292 SR Pendent 3/4 175 400, 500

TY4191 SR Upright 3/4 175 400, 500

STANDARD SIDEWALL SPRAY SPRINKLERS

3 of 21 09/11/21, 4:19 PM
VNIV.EX5985 - Sprinklers, Automatic and Open | UL Product iQ https://iq.ulprospector.com/en/profile?e=160281

Response Nom System Working


SIN Type Type K-Factor Pressure, psig Temp Rating, °F

TY1381+, ++ QR Flush HSW 5.6 175 165

TY3331+, ++ QR HSW 5.6 250 135, 155, 175, 200, 286

TY3321 QR HSW 5.6 175 165, 212

TY3331+, ++ QR Rec. HSW 5.6 250 135, 155, 175, 200

TY3431 QR VSW 5.6 175 135, 155, 175, 200, 286

TY3311 SR HSW 5.6 175 135, 165, 212, 280, 360

TY3351+, ++ SR HSW 5.6 250 135, 155, 175, 200, 286, 360

TY3351+, ++ SR Rec. HSW 5.6 250 135, 155, 175, 200

TY3381+, ++ QR Flush HSW 5.6 175 165

TY3390+, ++ SR Flush HSW 5.6 175 140

TY3390 SR Flush HSW 5.6 175 165

TY3391+, ++ QR Flush HSW 5.6 175 135, 155, 175, 200

TY3451 SR VSW 5.6 175 135, 155, 175, 200, 286, 360

TY3301 SR HSW 5.6 175 135, 165, 212, 280, 360

+ Ordinary hazard occupancies.

++ Installation 4 to 12 in. below the ceiling.

FLUSH, RECESSED AND CONCEALED SPRINKLERS

Temp Rating, °F
Response Nom System Working
SIN Type Type K-Factor Pressure, psig Cover Sprinkler

TY1281 QR Flush Pendent 5.6 175 — 165

TY323 QR Rec. Pendent 5.6 250 — 135, 155, 175, 200

TY325 SR Rec. Pendent 5.6 250 — 135, 155, 175, 200

TY3531 QR Concealed 5.6 250 139, 165 155, 200

TY3281 QR Flush Pendent 5.6 175 — 165

TY3291 QR Flush Pendent 5.6 175 — 135, 155, 175, 200

TY1231 QR Rec. Pendent 2.8 175 — 135, 155, 175, 200

TY3201 QR Rec. Pendent 5.6 175 — 135, 155, 175, 200

TY3231 QR Rec. Pendent 5.6 250 — 135, 155, 175, 200, 286

TY4231 QR Rec. Pendent 8.0 175 — 135, 155, 175, 200, 286

4 of 21 09/11/21, 4:19 PM
VNIV.EX5985 - Sprinklers, Automatic and Open | UL Product iQ https://iq.ulprospector.com/en/profile?e=160281

TY3290 SR Flush Pendent 5.6 175 — 140, 165, 212

TY3390 SR Flush HSW 5.6 175 — 140, 165

TY1251 SR Rec. Pendent 2.8 175 — 135, 155, 175, 200

TY3211 SR Rec. Pendent 5.6 175 — 135, 165, 212, 280, 360

TY3251 SR Rec. Pendent 5.6 250 — 135, 155, 175, 200, 286

TY4211 SR Rec. Pendent 8.0 175 — 135, 165, 212, 280, 360

TY4951 SR Rec. Pendent 8.0 175 — 135, 155, 175, 200

TY4251 SR Rec. Pendent 8.0 175 — 135, 155, 175, 200, 286

TY3551 SR Concealed 5.6 250 139, 165 155, 200

TY5521 QR Concealed Pendent 11.2 175 139, 165 160, 212

TY3530 QR Concealed Pendent 5.6 175 139, 165 155, 200

TY3550 SR Concealed Pendent 5.6 175 139, 165 155, 200

TY3521 QR Concealed HSW 5.6 250 139, 165 160, 212

DRY SPRINKLERS
System
Working
Response Max Pressure, Temp Rating,
SIN Type Type Length, in. psig Nom K-Factor F

TY3535# QR Concealed 48 175 5.6 155, 200

TY3335* QR HSW 48 175 5.6 135, 155, 175, 200, 286

TY3235 QR Pendent 48 175 5.6 135, 155, 175, 200, 286

TY5235 QR Pendent 48 175 11.2 135, 155, 175, 200, 286

TY3235 QR Rec. Pendent 48 175 5.6 135, 155, 175, 200, 286

TY5235 QR Rec. Pendent 48 175 11.2 135, 155, 175, 200, 286

TY3135# QR Upright 48 175 5.6 135, 155, 175, 200, 286

TY3555 SR Concealed 48 175 5.6 155, 200

TY3355* SR HSW 48 175 5.6 135, 155, 175, 200, 286, 360

TY3255 SR Pendent 48 175 5.6 135, 155, 175, 200, 286, 360

TY5255 SR Pendent 48 175 11.2 135, 155, 175, 200, 286, 360

TY3255 SR Rec. Pendent 48 175 5.6 135, 155, 175, 200, 286

TY5255 SR Rec. Pendent 48 175 11.2 135, 155, 175, 200, 286

TY3155 SR Upright 48 175 5.6 135, 155, 175, 200, 286, 360

5 of 21 09/11/21, 4:19 PM
VNIV.EX5985 - Sprinklers, Automatic and Open | UL Product iQ https://iq.ulprospector.com/en/profile?e=160281

TY3230 QR Pendent, Rec. Pendent 48 175 5.6 135, 155, 175, 200, 286

TY3250 SR Pendent 48 175 5.6 135, 155, 175, 200, 286, 360

TY3250 SR Rec. Pendent 48 175 5.6 135, 155, 175, 200, 286

TY3337 QR Pendent, Rec. Pendent 48 175 5.6 135, 155, 175, 200, 286

TY3357* SR HSW 48 175 5.6 135, 155, 175, 200, 286, 360

TY3357* SR Rec. HSW 48 175 5.6 135, 155, 175, 200, 286

TY3735+ QR HSW 48 175 5.6 135, 155, 175, 200, 286

TY3835+ QR Upright 48 175 5.6 135, 155, 175, 200, 286

TY3935+ QR Pendent 48 175 5.6 135, 155, 175, 200, 286

TY3935+ QR Rec. Pendent 48 175 5.6 135, 155, 175, 200, 286

TY4235 QR Pendent 48 175 8.0 135, 155, 175, 200, 286

TY4235 QR Rec. Pendent 48 175 8.0 135, 155, 175, 200, 286

TY4255 SR Pendent 48 175 8.0 135, 155, 175, 200, 286, 360

TY4255 SR Rec. Pendent 48 175 8.0 135, 155, 175, 200, 286

* For ordinary hazard occupancies when installed 4 to 12 in. below ceiling.

# The 155°F sprinkler utilizes a 135°F coverplate and the 200°F sprinkler utilizes a 155°F coverplate

+ 3/4 in. NPT

CONVENTIONAL (OLD STYLE) SPRINKLERS


Response Nom
SIN Type K-Factor Temp Rating, °F

TY363 QR 5.6 135, 155, 175, 200, 286

TY365 SR 5.6 135, 155, 175, 200, 286

TY3631 QR 5.6 135, 155, 175, 200, 286

TY4631 QR 8.0 135, 155, 175, 200, 286

TY3651 SR 5.6 135, 155, 175, 200, 286, 360, 500

TY4651 SR 8.0 135, 155, 175, 200, 286, 360

STANDARD RESPONSE - (SR) - EXTENDED COVERAGE SPRINKLER - LIGHT HAZARD


Max Max Min Distance
Width Length Flow Nom Below
SIN Type (A) Ft (B) Ft GPM K-Factor Ceiling In. Temp Rating, °F

TY3302 HSW, Rec. HSW 16 18 29 5.6 4 to 12 155, 200

TY3302 HSW, Rec. HSW 16 20 32 5.6 4 to 12 155, 200

6 of 21 09/11/21, 4:19 PM
VNIV.EX5985 - Sprinklers, Automatic and Open | UL Product iQ https://iq.ulprospector.com/en/profile?e=160281

TY3302 HSW 16 24 39 5.6 4 to 18 135

TY3332 HSW, Rec. HSW 16 20 32 5.6 4 to 6 155

TY3332 HSW, Rec. HSW 16 22 35 5.6 4 to 6 155, 175

TY4322 HSW 16 22 37 8.0 4 to 6 165

TY4322 HSW 16 24 44 8.0 4 to 6 165

TY4322 HSW 16 20 45 8.0 4 to 18 165

TY4332 HSW, Rec. HSW 16 20 33 8.0 4 to 12 135

TY4332 HSW, Rec. HSW 16 22 35 8.0 4 to 6 155, 175

TY4332 HSW, Rec. HSW 16 22 36 8.0 4 to 12 155, 175

TY4332 HSW, Rec. HSW 16 24 39 8.0 4 to 6 155, 175

TY4332 HSW, Rec. HSW 16 24 40 8.0 4 to 12 155, 175

TY3232 Pendent, Rec. pendent 20 20 40 5.6 — 155

TY5522* Concealed Pendent 20 20 40 11.2 — 160, 212

Dimension of wall on which a sidewall sprinkler is installed.

(B) Dimension perpendicular to wall on which a sidewall sprinkler is installed.

* Utilizes A 135 or 165°F Coverplate.

QUICK RESPONSE - (QR) - EXTENDED COVERAGE SPRINKLERS - LIGHT HAZARD

System Distance
Max Max Min Working Below
Width Length Flow Pressure, Nom Ceiling
SIN Type (A) Ft (B) Ft GPM psig K-Factor In. Temp Rating, °F

TY1282 Flush Pendent 16 16 26 175 5.6 — 165

TY1382 Flush HSW 16 16 26 175 5.6 4 to 12 165

TY3232 Pendent, Rec. 16 16 26 175 5.6 — 135, 155


pendent

TY3232 Pendent, Rec. 18 18 33 175 5.6 — 135, 155


pendent

TY3232 Pendent, Rec. 20 20 40 175 5.6 — 135


pendent

TY3282 Flush Pendent 16 16 26 175 5.6 — 165

TY3382 Flush HSW 16 16 26 175 5.6 4 to 12 165

TY6237 Pendent 18 18 37 175 14.0 — 135, 155, 175,


200, 286

7 of 21 09/11/21, 4:19 PM
VNIV.EX5985 - Sprinklers, Automatic and Open | UL Product iQ https://iq.ulprospector.com/en/profile?e=160281

TY6237 Pendent 20 20 40 175 14.0 — 135, 155, 175,


200, 286

TY6237 Rec. Pendent 18 18 37 175 14.0 — 135, 155, 175,


200

TY6237 Rec. Pendent 20 20 40 175 14.0 — 135, 155, 175,


200

TY5237 Pendent, Rec. 16 16 30 175 11.2 — 135, 155, 175,


pendent 200, 286

TY5237 Pendent, Rec. 18 18 33 175 11.2 — 135, 155, 175,


pendent 200, 286

TY5237 Pendent 20 20 40 175 11.2 — 135, 155, 175

TY5237 Rec. pendent 20 20 40 175 11.2 — 135, 175

TY3532* Concealed 16 16 26 175 5.6 — 155, 200

TY3532* Concealed 20 20 40 175 5.6 — 155, 200

TY3532* Concealed 18 18 33 175 5.6 — 155, 200

TY3537* Concealed 16 16 26 175 5.6 — 155, 200

TY3537* Concealed 20 20 40 175 5.6 — 155, 200

TY3537* Concealed 18 18 33 175 5.6 — 155, 200

TY4232 Pendent, Rec. 16 16 26 175 8.0 — 135


Pendent

TY4232 Pendent 16 16 26 175 8.0 — 155

TY4232 Pendent, Rec. 18 18 33 175 8.0 — 135


Pendent

TY4232 Pendent 18 18 33 175 8.0 — 155

TY4232 Pendent, Rec. 20 20 40 175 8.0 — 135


Pendent

TY4232 Pendent 20 20 40 175 8.0 — 155

TY4332+ Concealed HSW 16 16 26 250 8.0 4 to12 155

TY3539* Dry Concealed 16 16 26 175 175 — 155, 200

TY3539* Dry Concealed 18 18 33 175 175 — 155, 200

TY3302 HSW, Rec. HSW 16 16 26 175 5.6 4 to 12 200

TY3302 HSW, Rec. HSW 16 16 26 175 5.6 4 to 18 135, 155

TY3302 HSW, Rec. HSW 16 18 29 175 5.6 4 to 18 135, 155

TY3302 HSW, Rec. HSW 16 20 32 175 5.6 4 to 18 135, 155

8 of 21 09/11/21, 4:19 PM
VNIV.EX5985 - Sprinklers, Automatic and Open | UL Product iQ https://iq.ulprospector.com/en/profile?e=160281

TY3302 HSW 16 22 36 175 5.6 4 to 18 135

TY3338, Dry HSW 16 16 26 175 5.6 4 to 12 135, 155


TY3339

TY3338, Dry HSW 16 18 29 175 5.6 4 to 12 135, 155


TY3339

TY3338, Dry HSW 18 16 29 175 5.6 4 to 12 135, 155


TY3339

TY3338, Dry HSW 16 20 32 175 5.6 4 to 12 135, 155


TY3339

TY3358 Dry HSW 16 16 26 175 5.6 4 to 12 135, 155

TY3358 Dry HSW 16 18 29 175 5.6 4 to 12 135, 155

TY3358 Dry HSW 16 20 32 175 5.6 4 to 12 135, 155

TY3358 Dry HSW 18 16 29 175 5.6 4 to 12 135, 155

TY5238 Dry Pendent 18 18 33 175 11.2 — 135, 155, 175,


200

TY5238 Dry Pendent, Rec. 16 16 30 175 11.2 — 135, 155, 175,


Pendent 200

TY3322 HSW 16 16 29 175 5.6 4 to 12 165

TY3322 HSW 18 16 29 175 5.6 4 to 12 165

TY3322 HSW 16 20 33 175 5.6 4 to 12 165

TY4322 HSW 16 16 26 175 8.0 4 to 6 165

TY4322 HSW 16 18 29 175 8.0 4 to 6 165

TY4322 HSW 18 16 31 175 8.0 4 to 6 165

TY4322 HSW 18 18 33 175 8.0 4 to 6 165

TY4322 HSW 16 20 34 175 8.0 4 to 6 165

TY4322 HSW 20 16 35 175 8.0 4 to 6 165

TY4322 HSW 16 22 37 175 8.0 4 to 6 165

TY4322 HSW 16 18 38 175 8.0 4 to 18 165

TY3332 HSW, Rec. HSW 16 16 26 250 5.6 4 to 12 135, 155, 175

TY3332 HSW, Rec. HSW 16 18 29 250 5.6 4 to 12 135, 155, 175

TY3332 HSW, Rec. HSW 16 20 32 250 5.6 4 to 6 135, 155, 175

TY3332 HSW, Rec. HSW 16 22 35 250 5.6 4 to 6 135

TY4332 HSW, Rec. HSW 16 16 26 250 8.0 4 to 12 135, 155, 175

9 of 21 09/11/21, 4:19 PM
VNIV.EX5985 - Sprinklers, Automatic and Open | UL Product iQ https://iq.ulprospector.com/en/profile?e=160281

TY4332 HSW, Rec. HSW 16 18 29 250 8.0 4 to 12 135, 155, 175

TY4332 HSW, Rec. HSW 16 20 32 250 8.0 4 to 6 135

TY4332 HSW, Rec. HSW 16 20 33 250 8.0 4 to 12 135

TY4332 HSW, Rec. HSW 16 22 35 250 8.0 4 to 6 135

TY4332 HSW, Rec. HSW 16 22 36 250 8.0 4 to 12 135

TY4332 HSW, Rec. HSW 16 24 39 250 8.0 4 to 6 135

TY4332 HSW, Rec. HSW 16 24 40 250 8.0 4 to 12 135

TY4522+ Concealed HSW 14 22 31 175 8.0 4 to 6 160

TY4522+ Concealed HSW 14 22 36 175 8.0 6 to 12 160

TY4522+ Concealed HSW 14 24 34 175 8.0 4 to 6 160

TY4522+ Concealed HSW 14 24 38 175 8.0 6 to 12 160

TY4522+ Concealed HSW 16 16 26 175 8.0 4 to 6 160

TY4522+ Concealed HSW 16 16 27 175 8.0 6 to 12 160

TY4522+ Concealed HSW 16 18 29 175 8.0 4 to 12 160

TY4522+ Concealed HSW 16 20 32 175 8.0 4 to 12 160

TY4522+ Concealed HSW 16 22 36 175 8.0 4 to 12 160

TY4522+ Concealed HSW 16 24 39 175 8.0 4 to 12 160

TY4522+ Concealed HSW 18 18 33 175 8.0 4 to 12 160

TY4522+ Concealed HSW 18 20 36 175 8.0 4 to 12 160

TY4522+ Concealed HSW 18 22 40 175 8.0 4 to 12 160

TY5522* Concealed Pendent 16 16 30 175 11.2 — 160, 212

TY5522* Concealed Pendent 18 18 33 175 11.2 — 160, 212

* The 155 or 160°F sprinkler utilizes a 135°F coverplate and the 200 or 212°F sprinkler utilizes a 165°F coverplate.

+ Utilizes a 135°F coverplate.

Dimension of wall on which a sidewall sprinkler is installed.

(B) Dimension perpendicular to wall on which a sidewall sprinkler is installed.

STANDARD RESPONSE - (SR) - EXTENDED COVERAGE SPRINKLERS - ORDINARY HAZARD


Max Width x Ordinary Min Sprinkler Flow Nom Temp Rating
SIN Type Length FtxFt Hazard Group Rate GPM K-Factor °F

TY5332 HSW 16x16 1 38 11.2 155, 200

TY5332 HSW 16x16 2 51 11.2 155, 200

10 of 21 09/11/21, 4:19 PM
VNIV.EX5985 - Sprinklers, Automatic and Open | UL Product iQ https://iq.ulprospector.com/en/profile?e=160281

TY5332 HSW 16x18 1 43 11.2 155, 200

TY5332 HSW 16x18 2 58 11.2 155, 200

TY5332 HSW 16x20 1 48 11.2 155, 200

TY5332 HSW 16x20 2 64 11.2 155, 200

TY5337 HSW 16x22 1 53 11.2 200

TY5337 HSW 16x22 2 71 11.2 200

TY5337 HSW 16x24 1 58 11.2 200

TY5337 HSW 16x24 2 77 11.2 200

TY5339 Dry HSW 16x16 1 38 11.2 155, 200

TY5339 Dry HSW 16x16 2 51 11.2 155, 200

TY5339 Dry HSW 16x18 1 43 11.2 155, 200

TY5339 Dry HSW 16x18 2 58 11.2 155, 200

TY5339 Dry HSW 16x20 1 48 11.2 155, 200

TY5339 Dry HSW 16x20 2 64 11.2 155, 200

TY5237+ Pendent, Rec. 16x16 1 39 11.2 135, 155, 175,


Pendent 200, 286

TY5237+ Pendent, Rec. 16x16 2 51 11.2 135, 155, 175,


Pendent 200, 286

TY5238 Pendent, Rec. 16x16 1 39 11.2 155, 175, 200,


Pendent 286

TY5238+ Pendent, Rec. 16x16 2 51 11.2 155, 175, 200,


Pendent 286

TY5237+ Pendent, Rec. 18x18 1 49 11.2 135, 155, 175,


Pendent 200, 286

TY5237+ Pendent, Rec. 18x18 2 65 11.2 135, 155, 175,


Pendent 200, 286

TY5237+ Pendent, Rec. 20x20 1 60 11.2 135, 155, 175,


Pendent 200, 286

TY5237+ Pendent, Rec. 20x20 2 80 11.2 135, 155, 175,


Pendent 200, 286

TY6237+ Pendent, Rec. 16x16 1 39 14.5 135, 155, 175,


Pendent 200, 286

TY6237+ Pendent, Rec. 16x16 2 51 14.0 135, 155, 175,


Pendent 200, 286

11 of 21 09/11/21, 4:19 PM
VNIV.EX5985 - Sprinklers, Automatic and Open | UL Product iQ https://iq.ulprospector.com/en/profile?e=160281

TY6237+ Pendent, Rec. 18x18 1 49 14.0 135, 155, 175,


Pendent 200, 286

TY6237+ Pendent, Rec. 18x18 2 65 14.0 135, 155, 175,


Pendent 200, 286

TY6237+ Pendent, Rec. 20x20 1 60 14.0 135, 155, 175,


Pendent 200, 286

TY6237+ Pendent, Rec. 20x20 2 80 14.0 135, 155, 175,


Pendent 200, 286

TY5137+ Upright 16x16 1 39 11.2 135, 155, 175,


200, 286

TY5137+ Upright 16x16 2 51 11.2 135, 155, 175,


200, 286

TY5137+ Upright 18x18 1 49 11.2 135, 155, 175,


200, 286

TY5137+ Upright 18x18 2 65 11.2 135, 155, 175,


200, 286

TY5137+ Upright 20x20 1 60 11.2 135, 155, 175,


200, 286

TY5137+ Upright 20x20 2 80 11.2 135, 155, 175,


200, 286

TY6137+ Upright 16x16 1 39 14.5 135, 155, 175,


200, 286

TY6137+ Upright 16x16 2 51 14.5 135, 155, 175,


200, 286

TY6137+ Upright 18x18 1 49 14.5 135, 155, 175,


200, 286

TY6137+ Upright 18x18 2 65 14.5 135, 155, 175,


200, 286

TY6137+ Upright 20x20 1 60 14.5 135, 155, 175,


200, 286

TY6137+ Upright 20x20 2 80 14.5 135, 155, 175,


200, 286

+ Sprinklers are suitable for installation below noncombustible obstructed construction as described in NFPA 13.

QUICK RESPONSE (QR) - EXTENDED COVERAGE SPRINKLERS - ORDINARY HAZARD


Min
Max Sprinkler
Width x Ordinary Flow Temp
Length Hazard Rate Nom Rating,
SIN Type Ft x Ft Group GPM K-Factor °F

12 of 21 09/11/21, 4:19 PM
VNIV.EX5985 - Sprinklers, Automatic and Open | UL Product iQ https://iq.ulprospector.com/en/profile?e=160281

TY5137 Upright 14 x 14 1 30 11.2 135, 155, 175, 200, 286

TY5137 Upright 14 x 14 2 39 11.2 135, 155, 175, 200, 286

TY5237+ Pendent, Rec. Pendent 14 x 14 1 30 11.2 135, 155, 175, 200, 286

TY5237+ Pendent, Rec. Pendent 14 x 14 2 39 11.2 135, 155, 175, 200, 286

TY5238 Pendent, Rec. Pendent 14 x 14 1 30 11.2 135, 155, 175, 200, 286

TY5238 Pendent, Rec. Pendent 14 x 14 2 39 11.2 135, 155, 175, 200, 286

TY6137 Upright 14 x 14 1 39 14.0 135, 155, 175, 200, 286

TY6137 Upright 14 x 14 2 51 14.0 135, 155, 175, 200, 286

TY6237 Pendent 14 x 14 1 39 14.0 135, 155, 175, 200, 286

TY6237 Pendent 14 x 14 2 51 14.0 135, 155, 175, 200, 286

TY6237 Rec. Pendent 14 x 14 1 39 14.0 135, 155, 175, 200

TY6237 Rec. Pendent 14 x 14 2 51 14.0 135, 155, 175, 200

+ Sprinklers are suitable for installation below noncombustible obstructed construction as described in NFPA 13-1999.

CORROSION RESISTANT SPRINKLERS


Nom Coating
SIN Type K-Factor Type Temp Rating, °F

TY313 Upright 5.6 Polyester 135, 155, 175, 200, 286

TY323 Pendent 5.6 Polyester 135, 155, 175, 200, 286

TY315 Upright 5.6 Polyester 135, 155, 175, 200, 286

TY325 Pendent 5.6 Polyester 135, 155, 175, 200, 286

TY363 Conventional 5.6 Polyester 135, 155, 175, 200, 286

TY365 Conventional 5.6 Polyester 135, 155, 175, 200, 286

TY3631 Conventional 5.6 Polyester 135, 155, 175, 200 ,286

TY4631 Conventional 8.0 Polyester 135, 155, 175, 200, 286

TY3311 HSW 5.6 Lead 165, 212

TY3332 HSW 5.6 Polyester 135, 155, 175

TY4332 HSW 8.0 Polyester 135, 155, 175

TY3351 HSW 5.6 Polyester, lead 135, 155, 175, 200, 286, 360

TY3331 HSW 5.6 Polyester, lead 135, 155, 175, 200, 286

TY3311 HSW 5.6 Wax 165, 212

TY3311 HSW 5.6 Wax over lead 165, 212

13 of 21 09/11/21, 4:19 PM
VNIV.EX5985 - Sprinklers, Automatic and Open | UL Product iQ https://iq.ulprospector.com/en/profile?e=160281

TY3351 HSW 5.6 Wax, Wax over lead 135, 155, 175, 200

TY5332 HSW 11.2 Polyester 155, 200

TY5337 HSW 11.2 Polyester 155, 200

TY5131 Upright 11.2 Polyester 155, 200, 250, 286

TY5231 Pendent 11.2 Polyester 155, 200, 250, 286

TY3211 Pendent 5.6 Lead 165, 212

TY3251 Pendent 5.6 Polyester, lead 135, 155, 175, 200, 286, 360

TY3231 Pendent 5.6 Polyester, lead 135, 155, 175, 200, 286

TY3211 Pendent 5.6 Wax 165, 212

TY3211 Pendent 5.6 Wax over lead 165, 212

TY3251 Pendent 5.6 Wax, Wax over lead 135, 155, 175, 200

TY4911 Pendent 8.0 Lead 165, 212

TY4211 Pendent 8.0 Lead 165, 212

TY4251 Pendent 8.0 Polyester, lead 135, 155, 175, 200, 286, 360

TY4231 Pendent 8.0 Polyester, lead 135, 155, 175, 200, 286

TY4911 Pendent 8.0 Wax 165, 212

TY4211 Pendent 8.0 Wax 165, 212

TY4911 Pendent 8.0 Wax over lead 165, 212

TY4211 Pendent 8.0 Wax over lead 165, 212

TY4251 Pendent 8.0 Wax, Wax over lead 135, 155, 175, 200

TY5237 Pendent 11.2 Lead 135, 155, 175, 200, 286

TY5237 Pendent 11.2 Polyester 135, 155, 175, 200, 286

TY6237 Pendent 14 Lead 135, 155, 175, 200, 286

TY6237 Pendent 14 Polyester 135, 155, 175, 200, 286

TY7251 Pendent 16.8 Polyester 155, 200, 286

TY3111 Upright 5.6 Lead 165, 212

TY3133 Upright 5.6 Lead 135, 155, 175, 200, 286

TY3153 Upright 5.6 Lead 135, 155, 175, 200, 286, 360

TY3151 Upright 5.6 Polyester, lead 135, 155, 175, 200, 286, 360

TY3131 Upright 5.6 Polyester, lead 135, 155, 175, 200, 286

14 of 21 09/11/21, 4:19 PM
VNIV.EX5985 - Sprinklers, Automatic and Open | UL Product iQ https://iq.ulprospector.com/en/profile?e=160281

TY3111 Upright 5.6 Wax 165, 212

TY3111 Upright 5.6 Wax over lead 165, 212

TY3151 Upright 5.6 Wax, Wax over lead 135, 155, 175, 200

TY4811 Upright 8.0 Lead 165, 212

TY4111 Upright 8.0 Lead 165, 212

TY4133 Upright 8.0 Lead 135, 155, 175, 200, 286

TY4153 Upright 8.0 Lead 135, 155, 175, 200, 286, 360

TY4151 Upright 8.0 Polyester, lead 135, 155, 175, 200, 286, 360

TY4131 Upright 8.0 Polyester, lead 135, 155, 175, 200, 286

TY4811 Upright 8.0 Wax 165, 212

TY4111 Upright 8.0 Wax 165, 212

TY4811 Upright 8.0 Wax over lead 165, 212

TY4111 Upright 8.0 Wax over lead 165, 212

TY4151 Upright 8.0 Wax, Wax over lead 135, 155, 175, 200

TY5137 Upright 11.2 Lead 135, 155, 175, 200, 286

TY5137 Upright 11.2 Polyester 135, 155, 175, 200, 286

TY6137 Upright 14 Lead 135, 155, 175, 200, 286

TY6137 Upright 14 Polyester 135, 155, 175, 200, 286

TY7151 Upright 16.8 Polyester 155, 200, 286

TY3431 VSW 5.6 Polyester, lead 135, 155, 175, 200, 286

TY3451 VSW 5.6 Polyester, lead 135, 155, 175, 200, 286, 360

TY3451 VSW 5.6 Wax, Wax over lead 135, 155, 175, 200

TY9281 Pendent 8.0 Stainless Steel 135, 155, 175, 200, 286

TY8181 Upright 5.6 Stainless Steel 135, 155, 175, 200, 286

TY8281 Pendent 5.6 Stainless Steel 135, 155, 175, 200, 286

TY9181 Upright 8.0 Stainless Steel 135, 155, 175, 200, 286

TY8291 Pendent 5.6 Stainless Steel 135, 155, 175, 200, 286, 360, 500

TY8191 Upright 5.6 Stainless Steel 135, 155, 175, 200, 286, 360, 500

TY9291 Pendent 8.0 Stainless Steel 135, 155, 175, 200, 286, 360, 500

TY9191 Upright 8.0 Stainless Steel 135, 155, 175, 200, 286, 360, 500

15 of 21 09/11/21, 4:19 PM
VNIV.EX5985 - Sprinklers, Automatic and Open | UL Product iQ https://iq.ulprospector.com/en/profile?e=160281

TY3230 Pendent 5.6 Stainless Steel 135, 155, 175, 200, 286

TY3250 Pendent 5.6 Stainless Steel 135, 155, 175, 200, 286, 360

TY3337 HSW 5.6 Stainless Steel 135, 155, 175, 200, 286

TY3357 HSW 5.6 Stainless Steel 135, 155, 175, 200, 286, 360

TY3339 HSW 5.6 Stainless Steel 135, 155, 175, 200, 286

TY3296 Pendent 5.6 Lead 400, 500

TY4292 Pendent 8.0 Lead 400, 500

TY3191 Upright 5.6 Lead 400, 500

TY4191 Upright 8.0 Lead 400, 500

TY8131 Upright 5.6 Polyester 135, 155, 175, 200, 286, 360

TY8151 Upright 5.6 Polyester 135, 155, 175, 200, 286, 360

TY8231 Pendent 5.6 Polyester 135, 155, 175, 200, 286, 360

TY8251 Pendent 5.6 Polyester 135, 155, 175, 200, 286, 360

TY8331 HSW 5.6 Polyester 135, 155, 175, 200, 286, 360

TY8351 HSW 5.6 Polyester 135, 155, 175, 200, 286, 360

TY9131 Upright 8.0 Polyester 135, 155, 175, 200, 286, 360

TY9151 Upright 8.0 Polyester 135, 155, 175, 200, 286, 360

TY9231 Pendent 8.0 Polyester 135, 155, 175, 200, 286, 360

TY9251 Pendent 8.0 Polyester 135, 155, 175, 200, 286, 360

HIGH TEMPERATURE, WAX COATED SPRINKLERS


Max Sprinkler
Nom Ambient Temp
SIN Type K-Factor Temp, F Rating, F

TY3351 HSW 8.0 150 286

TY4251 Pendent 8.0 150 286

TY3251 Pendent 8.0 150 286

TY4151 Upright 8.0 150 286

TY3151 Upright 8.0 150 286

TY3451 VSW 8.0 150 286

TY9281 Pendent 8.0 150 286

TY8181 Upright 5.6 150 286

16 of 21 09/11/21, 4:19 PM
VNIV.EX5985 - Sprinklers, Automatic and Open | UL Product iQ https://iq.ulprospector.com/en/profile?e=160281

TY8281 Pendent 5.6 150 286

TY9181 Upright 8.0 150 286

TY8291 Pendent 5.6 150 286

TY8191 Upright 5.6 150 286

TY9291 Pendent 8.0 150 286

TY9191 Upright 8.0 150 286

INTERMEDIATE LEVEL SPRINKLERS


Response Nom
SIN* Type Type K-Factor Temp Rating, °F

TY313 QR Upright 5.6 135, 155, 175, 200, 286

TY315 SR Upright 5.6 135, 155, 175, 200, 286

TY323 QR Pendent 5.6 135, 155, 175, 200, 286

TY325 SR Pendent 5.6 135, 155, 175, 200, 286

TY3231 QR Pendent 5.6 135, 155, 175, 200, 286

TY3221 QR Pendent 5.6 165

TY4231 QR Pendent 8.0 135, 155, 175, 200, 286

TY4221 QR Pendent 8.0 165

TY3133 QR Upright 5.6 135, 155, 175, 200, 286

TY3123 QR Upright 5.6 165

TY4133 QR Upright 8.0 135, 155, 175, 200, 286

TY4123 QR Upright 8.0 165

TY3251 SR Pendent 5.6 135, 155, 175, 200, 286, 360

TY4251 SR Pendent 8.0 135, 155, 175, 200, 286, 360

TY3113 SR Upright 5.6 135, 165, 212, 280, 360

TY3153 SR Upright 5.6 135, 155, 175, 200, 286, 360

TY4111 SR Upright 8.0 135, 165, 212, 280, 360

TY4113 SR Upright 8.0 135, 165, 212, 280, 360

TY4153 SR Upright 8.0 135, 155, 175, 200, 286, 360

TY4211 SR Upright 8.0 135, 165, 212, 280, 360

TY4210 SR Pendent 8.0 135, 165, 212, 280, 360

TY3210 SR Pendent 5.6 135, 165, 212, 280, 360

17 of 21 09/11/21, 4:19 PM
VNIV.EX5985 - Sprinklers, Automatic and Open | UL Product iQ https://iq.ulprospector.com/en/profile?e=160281

TY3211 SR Pendent 5.6 135, 165, 212, 280, 360

TY3103 SR Upright 5.6 135, 165, 212, 280, 360

TY4103 SR Upright 8.0 135, 165, 212, 280, 360

* These sprinklers are available with or without sprinkler guards Models G1 and G4 as covered under File MS26602.

SPRINKLERS FOR STORAGE PROTECTION (CONTROL MODE DENSITY AREA)


Response Nom
SIN Type Type K-Factor Temp Rating, °F

TY5231 QR Pendent 11.2 155, 200, 286

TY5131 QR Upright 11.2 155, 200, 286

TY5111 SR Upright 11.2 165, 212, 286

TY5211 SR Pendent 11.2 165, 212, 286

TY5151 SR Upright 11.2 155, 200, 286

TY5831A QR Upright 11.2 155, 200

TY5851 SR Upright 11.2 155, 200, 286

TY5251 SR Rec. Pendent, Pendent 11.2 155, 200, 286

TY7151 SR Upright 16.8 155, 200, 286

TY7251 SR Pendent 16.8 155, 200, 286

A- For retrofit only, not to be installed in new systems.

EXTENDED COVERAGE SPRINKLERS FOR STORAGE PROTECTION (CONTROL MODE DENSITY AREA)
Max
Response Width x Length Nom
SIN Type Ft x Ft Type K-Factor Temp Rating, F

TY9128 SR 14 x 14 Upright 25.2 165, 212

These sprinklers have not been investigated for use as a Control Mode Specific Application (CMSA) sprinkler in accordance with NFPA 13.

SPRINKLERS FOR STORAGE PROTECTION (CONTROL MODE SPECIFIC APPLICATION)


Response Nom Temp
SIN Type Type K-Factor Rating, °F

TY5153 SR Upright 11.2 155, 200, 286

TY7103 SR Upright 16.8 286

TY7153 SR Upright 16.8 200

SPECIFIC APPLICATION SPRINKLERS


Attic Sprinklers

18 of 21 09/11/21, 4:19 PM
VNIV.EX5985 - Sprinklers, Automatic and Open | UL Product iQ https://iq.ulprospector.com/en/profile?e=160281

Min
Roof Flow
Response Fire Pitch Max Max Rate Nom Temp
SIN Type Risk (In./In.) Width Ft Length Ft GPM K-Factor Rating, F

TY2180 QR ++ 3/12 to 7/12 6 20 13 4.2 155

TY2180 QR ++ 3/12 to 7/12 6 20 13 4.2 200

TY2181 QR ++ 7/12 to 12/12 6 20 13 4.2 155

TY2181 QR ++ 7/12 to 12/12 6 20 13 4.2 200

TY2182 QR ++ 10/12 to 12/12 6 20 13 4.2 155

TY2182 QR ++ 10/12 to 12/12 6 20 13 4.2 200

TY3180 QR ++ 4/12 to 6/12 6 60 38 5.6 212

TY3180 QR ++ 4/12 to 6/12 6 40 25 5.6 212

TY3181 QR ++ 7/12 to 9/12 6 60 38 5.6 212

TY3181 QR ++ 7/12 to 9/12 6 40 25 5.6 212

TY3182 QR ++ 10/12 to 12/12 6 60 38 5.6 212

TY3182 QR ++ 10/12 to 12/12 6 40 25 5.6 212

TY3183 QR ++ 4/12 to 6/12 6 40 35 5.6 212

TY3183 QR ++ 4/12 to 6/12 6 30 25 5.6 212

TY3184 QR ++ 7/12 to 9/12 6 40 35 5.6 212

TY3184 QR ++ 7/12 to 9/12 6 30 25 5.6 212

TY3185 QR ++ 10/12 to 12/12 6 40 35 5.6 212

TY3185 QR ++ 10/12 to 12/12 6 30 25 5.6 212

TY3187 QR ++ 4/12 to 12/12 6 28 34 5.6 200

TY3187 QR ++ 4/12 to 12/12 6 20 25 5.6 200

TY3183 QR ++ 4/12 to 6/12 6 10 19 5.6 212

TY3184 QR ++ 7/12 to 9/12 6 10 19 5.6 212

TY3185 QR ++ 10/12 to 12/12 6 10 19 5.6 212

TY4180 QR ++ 4/12 to 6/12 6 60 38 8.0 200

TY4181 QR ++ 7/12 to 9/12 6 60 38 8.0 200

TY4182 QR ++ 10/12 to 12/12 6 60 38 8.0 200

++ For protection of Light Hazard attic spaces of wood truss or open wood joist construction with saddle type roofs in buildings 20 to 60 ft in
width and not exceeding a protection area of 400 sq ft per sprinkler when installed in accordance with the manufacturer' s installation and
design parameter instructions.

19 of 21 09/11/21, 4:19 PM
VNIV.EX5985 - Sprinklers, Automatic and Open | UL Product iQ https://iq.ulprospector.com/en/profile?e=160281

Window Sprinklers
Min
Distance Flow
Response Fire Nom Between Rate Temp
SIN Type Risk Type K-Factor Sprinklers, Ft GPM Rating, F

TY3388 QR *, % HSW 5.6 6 to 8 20 155, 200

TY3388 QR *, % HSW 5.6 + 15 155, 200

TY3488 QR *, % VSW 5.6 6 to 8 20 155, 200

TY3488 QR *, % VSW 5.6 + 15 155, 200

TY3498 QR *,% Concealed VSW 5.6 6 to 8 20 160, 212

TY3498 QR *,% Concealed VSW 5.6 ++ 20 160, 212

+ Located between Mullions and not greater than 6 ft apart.

++ Located between Mullions and not greater that 8 ft apart.

* For use on heat-strengthened or tempered glass windows without horizontal mullions having a maximum height of 13 ft. Combustibles must
be maintained at a minimum distance of 2 in. from the glass. This may be accomplished by use of a 3 ft. pony wall or any other method
acceptable to the authority having jurisdiction when installed in accordance with the manufacturer's installation and design parameter
instructions.

% For use on UL certified FireLite Plus ceramic glass (by Technical Glass Products) without horizontal mullions having a maximum height of 8
ft. Combustibles are not required to be maintained at any minimum distance from the glass when the sprinklers are installed in accordance
with the manufacturer's installation and design parameter instructions.

Authorities having jurisdiction shall be consulted to determine the hydraulic requirements for each installation.

Concealed Space Sprinklers

Max
Response Height of Space, In. Coverage Nom Temp
SIN Type Type Min Max Area, Ft2 K-Factor Rating, F

TY1189+ QR Upright 12 36 100 2.8 175

TY1189++ QR Upright 6* 54 100 2.8 175

TY2189+ ** QR Upright 12 36 144 4.2 175

TY2189++ ** QR Upright 6* 54 144 4.2 175

TY3189+ ** QR Upright 12 36 144 5.6 175

TY3189++ ** QR Upright 6* 54 144 5.6 175

TY2190% QR Upright 6 480 120 4.2 200

TY3190% QR Upright 6 480 120 5.6 200

TY2199+ ** QR Upright 6* 84 196 4.2 200

TY2199++ ** QR Upright 6* 84 196 4.2 200

TY3199+ ** a QR Upright 6* 84 256 5.6 200

20 of 21 09/11/21, 4:19 PM
VNIV.EX5985 - Sprinklers, Automatic and Open | UL Product iQ https://iq.ulprospector.com/en/profile?e=160281

TY3199++ ** QR Upright 6* 84 256 5.6 200

* Minimum distance between upper and lower joists.

** Wet or Dry pipe systems using steel pipe.

+ For use in light hazard flat concealed spaces incorporating noncombustible or wood truss construction. The Manufacturers Installation and
Design Parameter Instructions should be consulted for specific installation parameters, obstruction criteria and hydraulic design requirements.

++ For use in combustible solid wood and composite wood joist construction.

% For use in attic areas outside the scope of application for the BB, SD or HIP sprinklers.

a - For use in combustible solid wood joists with baffle spaced at 2000 Ft2. The Manufacturers Installation and Design Parameter Instructions
should be consulted for specific installation parameters, obstruction criteria and hydraulic design requirements. 

Corridor/Hallway Sprinklers
Max Width, Max Length, Min Flow, System Working Nom Temp
SIN Type ft (A) ft (B) gpm Pressure, psig K-Factor Rating, °F

TY4282+ Pendent, 28 8 23 250 8.0 155,200


Recessed
Pendent

TY4282+ Pendent, 28 10 28 250 8.0 155,200


Recessed
Pendent

TY3582+# Concealed 28 8 23 250 5.6 155,200


Pendent

TY3582+# Concealed 28 10 28 250 5.6 155,200


Pendent

+ For use in corridors and hallways of light hazard occupancies. The Manufacturer's Installation and Design Parameter Instructions should be
consulted for specific installation parameters, obstruction criteria, and hydraulic design requirements.

# The 155°F rated sprinkler uses a 139°F cover plate assembly and the 200°F rated sprinkler uses a 165°F rated cover plate assembly.

Trademark and/or Tradename: "CSC"

Last Updated on 2021-04-30

The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow-
Up Service. Always look for the Mark on the product.

UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non-
misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory
with permission from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice
in the following format: "© 2021 UL LLC"

21 of 21 09/11/21, 4:19 PM

You might also like