You are on page 1of 29

TECHNICAL DATA Installation

Sprinkler PI-2 Series Guide


1of 4

Automatic Sprinkler PI-2 Series ( Glass bulb type )

• Glass bulb
• Standard Spary Pattern
• K-factor 5.6
• Quick & Standard
Response

PI 221 PI 220 PI 211 PI 210

General Description Technical Data


Paradise Industry Standard and Quick res- Minimum Operating Pressure :
ponse sprinklers are thermo sensitive glass 7 psi (0.5 bar)
bulb sprinklers available in different finishes
Maximum Working Pressure :
and temperature ratings to meet design
requirements. These sprinklers are standard 175 psi (12 bar)
spray pattern to meet approval agencies Discharge Coefficient :
requirement. Especially, the Nickel-Chrome K = 5.6 GPM/psi1/2 (80.7 LPM/bar1/2)
plated sprinklers are decorative and attractive, Temperature Rating:
so it is well matched to customer interior
135 / 155 / 200 F (57 / 68 / 93 ℃)
decoration. In addition, Nickel-Chrome
plating might be utilized to extend the life of Leakage Test at Factory:
copper alloy sprinkler, although it has passed 30 Kgf/㎠ (0.3Mpa, 29.4bar, 426.7 psi)
the standard corrosion test.
Material
Frame Forging ..Brass AS1568 Alloy486
Sprinkler Identification Numbers Deflector . . . . . . . . . . . . Copper C2200
PI210 : Spring Seat . . . . . …. . . . . . Ni-Be alloy,
Standard response, Upright, 5.6K, 1/2”(N)PT coated on both sides with Teflon Tape.
PI211 : Bulb . . . . . . . . . . . . . .Glass
Quick response, Upright, 5.6K, 1/2”(N)PT
Bulb Cap . . . .. Phosphor Bronze C5191
PI220 :
Standard response,Pendent,5.6K, 1/2”(N)PT Screw . . . . . . . . . . . . . . . .. Brass C3604
PI221 :
Quick response, Pendent, 5.6K, 1/2”(N)PT

Paradise Industry Co. Ltd. , REP. NO.: SPH(E) 001 (REV.A) NOV , 2011
Sprinkler PI-2 Series
2of 4

Design Criteria

Note1

Note. 1. The spring is applied only PI210/PI220/PI221

SIN No Spray Response Thread Size Nominal Sprinkler Approval


Pattern K Factor Height
(N)PT BSP

PI 210 Upright SR ½” 15mm K 5.6 (US) 55.9mm CULUS, FM Note1

PI 211 Upright QR ½” 15mm K 5.6 (US) 55.9mm CULUS, FM

PI 220 Pendent SR ½” 15mm K 5.6 (US) 56.8mm CULUS, FM Note1

PI 221 Pendent QR ½” 15mm K 5.6 (US) 56.8mm CULUS, FM Note1

Note. 1. The products of UL Listed and FM Approved are not same. Please Contact us to confirm when purchasing.

Installation
The Paradise Industry sprinklers are intended
for fire protection systems designed in
accordance with the standard installation rules
of the applicable listings or approval agency.
(eg., NFPA 13 or FM’s Loss Prevention Data
Sheets)

Note.
Do not install any bulb type sprinkler if the
bulb is cracked or there is a loss of fluid
from the bulb. And with the sprinkler held
horizontally, a small air bubble should be
present.
The sprinkler joint should be obtained with
maximum torque of 28.5 Nm (21 ft-lbs)

Paradise Industry Co. Ltd. , REP. NO.: SPH(E) 001 (REV.A) NOV , 2011
Sprinkler PI-2 Series
3of 4

Operation Inspections, Tests and Maintenance

When the rated temperature is reached, the


fluid which is contained in the glass bulb Automatic Sprinklers must never be shipped
expands sufficiently to shatter the glass bulb, or stored where their temperature will
releasing the bulb cap and spring seat exceed 39℃ and they must never be
assembly. Water flowing through the sprinkler painted, plated, coated or otherwise altered
orifice and strikes the deflector forming a after leaving factory. Modified sprinklers
intended spray pattern to extinguish or control must be replaced. Sprinklers that have been
the fire. exposed to corrosive products of
combustion, but have not operated, should
be replaced if they cannot be completely
cleaned by wiping the sprinkler with a cloth
or by brushing it with a soft bristle brush.

Care must be exercised to avoid damage to


the sprinklers both before and after
installation. Sprinklers damaged by
dropping, striking, wrench twist/slippage, or
the like, must be replaced. Also, replace any
sprinkler that has a cracked bulb or that has
lost liquid from its bulb.

Spray Pattern

Upright (PI 210 / 211) Pendent (PI 220 / 221)

Paradise Industry Co. Ltd. , REP. NO.: SPH(E) 001 (REV.A) NOV , 2011
Sprinkler PI-2 Series
4of 4

THIS PAGE INTENTONALLY LEFT BLANK

Paradise Industry Co. Ltd. , REP. NO.: SPH(E) 001 (REV.A) NOV , 2011
TECHNICAL DATA Installation
Sprinkler PI-2 Series Guide
1of 4

Automatic Sprinkler PI-2 Series ( Glass bulb type )

• Glass bulb
• Standard Spary Pattern
• K-factor 5.6
• Quick & Standard Response

PI 222

General Description Technical Data


Paradise Clean room type sprinkler is used Minimum Operating Pressure :
through combination with flexible sprinkler
hose in the clean room of semi-conductor 7 psi (0.5 bar)
manufacturing facility (TFT-LCD, PDP and etc.) Maximum Working Pressure :
and designed to fit through mould bar hole 175 psi (12 bar)
installed in the clean room. These sprinklers are Discharge Coefficient :
standard spray pattern to meet approval
agencies requirement. Especially, the Nickel- K = 5.6 GPM/psi1/2 (80.7 LPM/bar1/2)
Chrome plated sprinklers are decorative and Temperature Rating:
attractive, so it is well matched to customer 135 / 155 / 200 F (57 / 68 / 93 ℃)
interior decoration. In addition, Nickel-Chrome Leakage Test at Factory:
plating might be utilized to extend the life of
copper alloy sprinkler, although it has passed 30 Kgf/㎠ (0.3Mpa, 29.4bar, 426.7 psi)
the standard corrosion test.
Material
Frame Forging ..Brass AS1568 Alloy486
Sprinkler Identification Numbers Deflector . . . . . . . . . . . . Copper C2200
Spring Seat . . . . . …. . . . . . Ni-Be alloy,
PI222 :
coated on both sides with Teflon Tape.
Quick response, Pendent, 5.6K, 1/2”(N)PT
Bulb . . . . . . . . . . . . . .Glass
Bulb Cap . . . .. Phosphor Bronze C5191
Screw . . . . . . . . . . . . . . . .. Brass C3604

Paradise Industry Co. Ltd. , REP. NO.: SPH(E) 005 (REV.A) Apr , 2013
Sprinkler PI-2 Series
2of 4

Design Criteria

SIN No Spray Response Thread Size Nominal Sprinkler Approval


Pattern K Factor Height
(N)PT BSP

PI 222 Pendent QR ½” 15mm K 5.6 (US) 54mm CULUS, FM

Installation
The Paradise Industry sprinklers are intended
for fire protection systems designed in
accordance with the standard installation rules
of the applicable listings or approval agency.
(eg., NFPA 13 or FM’s Loss Prevention Data
Sheets)

Note.
Do not install any bulb type sprinkler if the
bulb is cracked or there is a loss of fluid from
the bulb. And with the sprinkler held
horizontally, a small air bubble should be
present.
The sprinkler joint should be obtained with
maximum torque of 28.5 Nm (21 ft-lbs)

Paradise Industry Co. Ltd. , REP. NO.: SPH(E) 005 (REV.A) Apr , 2013
Sprinkler PI-2 Series
3of 4

Operation Inspections, Tests and Maintenance

When the rated temperature is reached, the


fluid which is contained in the glass bulb Automatic Sprinklers must never be shipped
expands sufficiently to shatter the glass bulb, or stored where their temperature will
releasing the bulb cap and spring seat exceed 39℃ and they must never be
assembly. Water flowing through the sprinkler painted, plated, coated or otherwise altered
orifice and strikes the deflector forming a after leaving factory. Modified sprinklers
intended spray pattern to extinguish or control must be replaced. Sprinklers that have been
the fire. exposed to corrosive products of
combustion, but have not operated, should
be replaced if they cannot be completely
cleaned by wiping the sprinkler with a cloth
or by brushing it with a soft bristle brush.

Care must be exercised to avoid damage to


the sprinklers both before and after
installation. Sprinklers damaged by
dropping, striking, wrench twist/slippage, or
the like, must be replaced. Also, replace any
sprinkler that has a cracked bulb or that has
lost liquid from its bulb.

Spray Pattern

PI 222

Paradise Industry Co. Ltd. , REP. NO.: SPH(E) 005 (REV.A) Apr , 2013
Sprinkler PI-2 Series
4of 4

THIS PAGE INTENTONALLY LEFT BLANK

Paradise Industry Co. Ltd. , REP. NO.: SPH(E) 005 (REV.A) Apr , 2013
TECHNICAL DATA Installation
Sprinkler PI-2 Series Guide
1of 4

Automatic Sprinkler PI-2 Series ( Glass bulb type )

• Glass bulb
• Standard Spary Pattern
• K-factor 5.6
• Quick & Standard Response

PI 240 PI 241

General Description Technical Data

Paradise Industry Standard and Quick res-ponse Minimum Operating Pressure :


sprinklers are thermo sensitive glass bulb 7 psi (0.5 bar)
sprinklers available in different finishes and Maximum Working Pressure :
temperature ratings to meet design
requirements. These sprinklers are standard 175 psi (12 bar)
spray pattern to meet approval agencies Discharge Coefficient :
requirement. Especially, the Nickel-Chrome K = 5.6 GPM/psi1/2 (80.7 LPM/bar1/2)
plated sprinklers are decorative and attractive, Temperature Rating:
so it is well matched to customer interior
decoration. In addition, Nickel-Chrome plating 135 / 155 / 200 F (57 / 68 / 93 ℃)
might be utilized to extend the life of copper Leakage Test at Factory:
alloy sprinkler, although it has passed the 30 Kgf/㎠ (0.3Mpa, 29.4bar, 426.7 psi)
standard corrosion test.
Material
Frame Forging ..Brass AS1568 Alloy486
Sprinkler Identification Numbers Deflector . . . . . . . . . . . . Copper C2200
Spring Seat . . . . . …. . . . . . Ni-Be alloy,
PI240 :
coated on both sides with Teflon Tape.
Standard response, Sidewall, 5.6K, 1/2”(N)PT
Bulb . . . . . . . . . . . . . .Glass
PI241 : Bulb Cap . . . .. Phosphor Bronze C5191
Quick response, Sidewall, 5.6K, 1/2”(N)PT Screw . . . . . . . . . . . . . . . .. Brass C3604

Paradise Industry Co. Ltd. , REP. NO.: SPH(E) 002 (REV.A) Apr , 2013
Sprinkler PI-2 Series
2of 4

Design Criteria

SIN No Spray Response Thread Size Nominal Sprinkler Approval


Pattern K Factor Height
(N)PT BSP

PI 240 Sidewall SR ½” 15mm K 5.6 (US) 55.9mm CULUS


Note1

PI 241 Sidewall QR ½” 15mm K 5.6 (US) 55.9mm CULUS

Note1

Note1

Installation
The Paradise Industry sprinklers are intended
for fire protection systems designed in
accordance with the standard installation rules
of the applicable listings or approval agency.
(eg., NFPA 13 or FM’s Loss Prevention Data
Sheets)

Note.
Do not install any bulb type sprinkler if the
bulb is cracked or there is a loss of fluid from
the bulb. And with the sprinkler held
horizontally, a small air bubble should be
present.
The sprinkler joint should be obtained with
maximum torque of 28.5 Nm (21 ft-lbs)

Paradise Industry Co. Ltd. , REP. NO.: SPH(E) 002 (REV.A) Apr , 2013
Sprinkler PI-2 Series
3of 4

Operation Inspections, Tests and Maintenance

When the rated temperature is reached, the


fluid which is contained in the glass bulb Automatic Sprinklers must never be shipped
expands sufficiently to shatter the glass bulb, or stored where their temperature will
releasing the bulb cap and spring seat exceed 39℃ and they must never be
assembly. Water flowing through the sprinkler painted, plated, coated or otherwise altered
orifice and strikes the deflector forming a after leaving factory. Modified sprinklers
intended spray pattern to extinguish or control must be replaced. Sprinklers that have been
the fire. exposed to corrosive products of
combustion, but have not operated, should
be replaced if they cannot be completely
cleaned by wiping the sprinkler with a cloth
or by brushing it with a soft bristle brush.

Care must be exercised to avoid damage to


the sprinklers both before and after
installation. Sprinklers damaged by
dropping, striking, wrench twist/slippage, or
the like, must be replaced. Also, replace any
sprinkler that has a cracked bulb or that has
lost liquid from its bulb.

Spray Pattern

Paradise Industry Co. Ltd. , REP. NO.: SPH(E) 002 (REV.A) Apr , 2013
Sprinkler PI-2 Series
4of 4

THIS PAGE INTENTONALLY LEFT BLANK

Paradise Industry Co. Ltd. , REP. NO.: SPH(E) 002 (REV.A) Apr , 2013
TECHNICAL DATA Installation
Sprinkler PI-7 Series Guide
1of 5

Automatic Sprinkler PI-7 Series ( Fusible Alloy Type )

• Fusible alloy
• Standard Sparay Pattern
• K-factor 5.6
• Quick & Standard Response

PI 720 PI 721

General Description Sprinkler Identification Numbers


Paradise Industry Standard and Quick res-ponse PI720 :
flush type sprinkler has the protective cap Standard response, Pendent, 5.6K, 1/2”(N)PT
protecting the sprinkler head from any external PI721 :
impact during transport and installation. It uses Quick response, Pendent, 5.6K, 1/2”(N)PT
teflon sheet that has greater sealing and
elasticity instead of copper plate gasket.
compact in size and aesthetically pleasing, it is Material
widely used for apartment, hotel, theater,
department store, hospital and multi-purpose
Frame Forging ..Brass AS1568 Alloy486
building
Inner Loading Plate. . . . . . Copper C3604
Out Loading Plate. . .. . . . . Copper C3604
Technical Data
Heat Collector #1 #2 #3 . . Copper C1221P
Minimum Operating Pressure : Bulb Cap . . . . . . . Phosphor Bronze C5191
7 psi (0.5 bar) Locking Screw . . . . . . . . . . . . . . . .. STS304
Maximum Working Pressure : Impress Screw . . . . . . . . . . . . . . . .. STS304
175 psi (12 bar) Retaining Ring . . . . . . . . . . . . . . . . TW
Discharge Coefficient : Spring Seat . . . . . . . . . . . . . . . . . . Ni-Be alloy
K = 5.6 GPM/psi1/2 (80.7 LPM/bar1/2) Fuse Metal . . . . . . . . . Low-melting-point alloy
Temperature Rating: Deflector . . . . . . . . . . . . . . . . . . Copper C1100
162 F (72 ℃) Deflector Ring. . . . . . . . .. . . . . . Copper C3604
Leakage Test at Factory: Plug. . . . . . . . . . . . . . . . . . . . . . . . .STS304
30 Kgf/㎠ (0.3Mpa, 29.4bar, 426.7 psi) Cap and Cork . . . . . . . . . . . . . . . . PE or PP
Washer . . . . . . . . . . . . . . .. . . . Cold Roll Steel

Paradise Industry Co. Ltd. , REP. NO.: SPH(E) 003 (REV.A) April , 2013
Sprinkler PI-7 Series
2of 5

Design Criteria

Note. 1. The spring is applied only PI720/PI721

SIN No Spray Response Thread Size Nominal Sprinkler Approval


Pattern K Factor Height
(N)PT BSP

PI 720 Pendent SR ½” 15mm K 5.6 (US) 51.0mm CULUS,

PI 721 Pendentt QR ½” 15mm K 5.6 (US) 51.0mm CULUS,

Note. 1. The products of UL Listed is not same. Please Contact us to confirm when purchasing.

Installation

The model PI720/721 Flush Sprinklers must be


installed in accordance with the following
instructions.

1. The Sprinkler must only be installed in the


pendent, flush mounted position and with
the threaded end perpendicular to the
mounting surface.

2. Use only a non-hardening type of Teflon


based pipe joint sealant and apply it
TECHNICAL NOTES & INSTALLATION
DESCRIPTION

Paradise Industry Co. Ltd. , REP. NO.: SPH(E) 003 (REV.A) April , 2013
Sprinkler PI-7 Series
3of 5

Installation

<Flush sprinklers-Fusible alloy type> NOTE


sparingly to the male threads only. Failure to use the Protective Cap, while the
ceiling installation is being completed, can
3. Hand tighten the Sprinkler with the result in the accidental damage or painting of a
attached Protective Cap (as shipped), sprinkler. Damage or painted sprinkler must be
into the sprinkler fitting. replaced.

4. Using the Model PI720 Sprinkler Wrench, 6. After the ceiling finishing is complete and
tighten the Sprinkler into the fitting. the sprinkler system is ready to be put into
The Wrench is shipped over the Protective service, slide off the Protective Cap.
Cap and can be mounted to a 1/2 inch socket
drive ratchet. Align the Wrench Lugs of NOTE
all Sprinklers within a compartment to be Failure to remove the Protective Cap will
parallel to one of the compartment walls. prevent proper operation of the Sprinkler.

Care and Maintenance


NOTE
A leak tight 1/2 inch PT sprinkler joint should Automatic Sprinklers must never be shipped,
be obtained with a torque of 9.5 to 19.0 Nm (7 stored, or used where their temperature will
to 14ft.lbs.). A maximum of 28.5 Nm (21 ft.lbs.) exceed 39℃ and they must never be painted,
of torque is to be used to install the sprinkler. plated, coated, or otherwise altered after
Higher levels of torque may distort the leaving the factory. Modified or over-heated
sprinkler orifice seat with consequent leakage. sprinklers must be replace.
Care must be exercised to avoid damage to the
5. Do not remove the Protective Cap at this model PI720 Flush Sprinklers⎯both before and
time. The Protective Cap is intended to after installation. Sprinklers damaged by
help protect the sprinkler until the dropping, striking, wrench twist/slippage, or
ceiling finish is complete and the the like, must be replaced
sprinkler system is ready to be put into
service.

Paradise Industry Co. Ltd. , REP. NO.: SPH(E) 003 (REV.A) April , 2013
Sprinkler PI-7 Series
4of 5

Operation

When the rated temperature is reached,


mounted around the head temperature rises by
sensing heat collector temperature is reached,
The fuse metal starts to dissolve the initial load
took the inner loading plate and out loading
plate retaining ring. And discharged by spring
seat, heat collector, inner loading plate, out
loading plate frame for contraction and at the
same time until it is pass down. Water flowing
through the sprinkler orifice and strikes the
deflector forming a intended spray pattern to
extinguish or control the fire.

Spray Pattern

PI 720 / PI 721

Paradise Industry Co. Ltd. , REP. NO.: SPH(E) 003 (REV.A) April , 2013
Sprinkler PI-7 Series
5of 5

THIS PAGE INTENTONALLY LEFT BLANK

Paradise Industry Co. Ltd. , REP. NO.: SPH(E) 003 (REV.A) April , 2013
TECHNICAL DATA Installation
Sprinkler PI-8 Series Guide
1of 4

Automatic Sprinkler PI-8 Series(CONCEALED TYPE SPRINKLER)

• Glass bulb
• Standard Spray Pattern
• K-factor 5.6
• Quick & Standard Response

PI 820 / PI821

General Description Technical Data


Paradise Industry Standard and Quick Response
Concealed Pendent Sprinkler PI820 and PI821 Minimum Operating Pressure :
are thermosensitive glass-bulb spray sprinklers 7 psi (0.5 bar)
with the cover plate. The sprinkler is pre- Maximum Working Pressure :
assembled with a threaded adapter for
175 psi (12 bar)
installation with a low-profile cover assembly
that provides up to 10mm of vertical Discharge Coefficient :
adjustment.. K = 5.6 GPM/psi1/2 (80.7 LPM/bar1/2)
The two-piece design allows installation and Temperature Rating:
testing of the sprinkler prior to installation of
Sprinkler : 155 / 200 ℉ (68 / 93 ℃)
the cover plate. The “thread-on”, “thread-off”
design of the concealed cover plate assembly Cover Assembly : 135 / 165 ℉(57 / 74℃)
allows easy installation of the cover plate after Leakage Test at Factory (Air):
the system has been tested and the ceiling 30 Kgf/㎠ (0.3Mpa, 29.4bar, 426.7 psi)
finish has been applied. The cover assembly can
be removed and reinstalled, allowing temporary
removal of ceiling panels without taking the Material
sprinkler system out of service or removing the Frame Forging ..Brass AS1568 Alloy486
sprinkler. Deflector . . . . . . . . . . . . Copper C2680S
Spring Seat . . . . . …. . . . . . Ni-Be alloy,
Sprinkler Identification Numbers
coated on both sides with Teflon Tape.
PI820 :
Bulb . . . . . . . . . . . . . .Glass
Standard response,Pendent,5.6K, 1/2”(N)PT
PI821 : Bulb Cap . . . .. Phosphor Bronze C5191
Quick response, Pendent, 5.6K, 1/2”(N)PT Screw . . . . . . . . . . . . . . . .. Brass C3604

Paradise Industry Co. Ltd. , REP. NO.: SPH(E) 004 OCT , 2012
Sprinkler PI-8 Series
2of 4

Design Criteria

SIN No Spray Response Thread Size Nominal Vertical Approval


Pattern K Factor adjustment
(N)PT BSP

PI 820 Pendent SR ½” 15mm K 5.6 (US) 10mm CULUS,

PI 821 Pendent QR ½” 15mm K 5.6 (US) 10mm CULUS,

Installation

The Paradise Industry sprinklers are intended


for fire protection systems designed in
accordance with the standard installation rules
of the applicable listings or approval agency.
(eg., NFPA 13 or UL 199 Standard)

Note.
Do not install any bulb type sprinkler if the
bulb is cracked or there is a loss of fluid
from the bulb. And with the sprinkler held
horizontally, a small air bubble should be
present.
The sprinkler joint should be obtained with
maximum torque of 28.5 Nm (21 ft-lbs)

Paradise Industry Co. Ltd. , REP. NO.: SPH(E) 004 OCT , 2012
Sprinkler PI-8 Series
3of 4

Operation Inspections, Tests and Maintenance


During fire conditions, when the temperature Automatic Sprinklers must never be shipped
around the sprinkler approaches its operating or stored where their temperature will
temperature, the cover plate detaches. exceed 39℃ and they must never be
Continued heating of the exposed sprinkler painted, plated, coated or otherwise altered
causes the heat-sensitive liquid in the glass after leaving factory. Modified sprinklers
bulb to expand and the bulb to shatter, must be replaced. Sprinklers that have been
releasing the bulb cap and sealing spring exposed to corrosive products of
assembly. Water flowing through the sprinkler combustion, but have not operated, should
orifice strikes the sprinkler deflector, forming a be replaced if they cannot be completely
uniform spray pattern to extinguish or control cleaned by wiping the sprinkler with a cloth
the fire. or by brushing it with a soft bristle brush.

Care must be exercised to avoid damage to


the sprinklers both before and after
installation. Sprinklers damaged by
dropping, striking, wrench twist/slippage, or
the like, must be replaced. Also, replace any
sprinkler that has a cracked bulb or that has
lost liquid from its bulb.

Spray Pattern

Paradise Industry Co. Ltd. , REP. NO.: SPH(E) 004 OCT , 2012
Sprinkler PI-8 Series
4of 4

THIS PAGE INTENTONALLY LEFT BLANK

Paradise Industry Co. Ltd. , REP. NO.: SPH(E) 004 OCT , 2012
TECHNICAL DATA Installation
Sprinkler PI-3 Series Guide
1of 4

Automatic Sprinkler PI-3 Series ( Glass bulb type )

• Glass bulb
• Standard Spary Pattern
• K-factor 5.6
• Quick & Standard Response

PI 310 PI 311 PI 320 PI 321

General Description Technical Data


Minimum Operating Pressure :
Paratech Standard and Quick Response 7 psi (0.5 bar)
Sprinklers are thermo sensitive glass bulb
Maximum Working Pressure :
sprinklers available in different finishes and
temperature ratings to meet design 175 psi (12 bar)
requirements. These sprinklers are standard Discharge Coefficient :
spray pattern to meet approval agencies K = 5.6 GPM/psi1/2 (80.7 LPM/bar1/2)
requirement. Especially, the Nickel-Chrome Temperature Rating:
plated sprinklers are decorative and attractive,
135℉ / 155℉ / 175℉ / 200℉ / 286℉
so it is well matched to customer interior
decoration. In addition, Nickel-Chrome (57℃ / 68℃ / 79℃ / 93℃ / 141℃)
plating might be utilized to extend the life of Leakage Test at Factory:
copper alloy sprinkler, although it has passed 30 Kgf/㎠ (0.3Mpa, 29.4bar, 426.7 psi)
the standard corrosion test.
Material
Sprinkler Identification Numbers Frame Forging ..Brass AS1568 Alloy486
Deflector . . . . . . . . . . . . Copper C2200
PI310 :
Standard response, Upright, K5.6, ½”(N)PT Spring Seat . . . . . . . . . . . . Ni-Be alloy,
PI311 : coated on both sides with Teflon Tape.
Quick response, Upright, K5.6, ½”(N)PT Bulb . . . . . . . . . . . . . . . . . . . . . . . . Glass
PI320 :
Bulb Cap . . . . . . . . . . . . . . . . . . . C3533
Standard response, Pendent, K5.6, ½”(N)PT
PI321 : Screw . . . . . . . . . . . . . . . . . . . . . STS304
Quick response, Pendent, K5.6, ½”(N)PT Spring . . . . . . . . . . . . . . . . . . . . . STS304

Paratech Co., Ltd REP. NO.: SBI004104 MARCH , 2016


Sprinkler PI-3 Series
2of 4

Design Criteria

AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES


Sprinkler Temperature Sprinkler Nominal Maximum Ambient
Bulb Color
Classification Temperature Rating1 Ceiling Temperature2

Ordinary 135℉(57℃) 100℉(38℃) Orange

Ordinary 155℉(68℃) 100℉(38℃) Red

Intermediate 175℉(79℃) 150℉(65℃) Yellow

Intermediate 200℉(93℃) 150℉(65℃) Green

High 286℉(141℃) 225℉(107℃) Blue

Sprinkler Finishes : Brass, Nickel-Chrome, White Polyester, Black Teflon Coating

Footnotes
1 The sprinkler temperature rating is stamped on the deflector.
2 Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location,
and other requirements of the Authority Having Jurisdiction. Refer to specific installation
standards.

Paratech Co., Ltd REP. NO.: SBI004104 MARCH , 2016


Sprinkler PI-3 Series
3of 4

Approval Chart

Nominal Listings and


Thread Size Overall Length
K-Factor Approvals
SIN
PT NPT U.S. Metric Inches mm cULus

PI310 1/2" 1/2" 5.6 80.7 1.84 47.8 A1, B1, D1

PI311 1/2" 1/2" 5.6 80.7 1.84 47.8 A1, B1, C1, D1, E1

PI320 1/2" 1/2" 5.6 80.7 1.88 48.8 A1, B1, D1

PI321 1/2" 1/2" 5.6 80.7 1.88 48.8 A1, B1, C1, D1, E1

Approved Temperature Ratings Approved Finishes


A - 135℉ (57℃) 1- Brass, Nickel-Chrome, White Polyester, and
B - 155℉ (68℃) Black Teflon coating
C - 175℉ (79℃)
D - 200℉ (93℃)
E - 286℉ (141℃)

Installation

The Paratech Sprinklers are intended for fire


protection systems designed in accordance
with the standard installation rules of the
applicable listings or approval agency. (eg.,
NFPA 13 or FM’s Loss Prevention Data Sheets)

Note.
Do not install any bulb type sprinkler if the
bulb is cracked or there is a loss of fluid
from the bulb. And with the sprinkler held
horizontally, a small air bubble should be
present.
The sprinkler joint should be obtained with
maximum torque of 28.5 Nm (21 ft-lbs)

Paratech Co., Ltd REP. NO.: SBI004104 MARCH , 2016


Sprinkler PI-3 Series
4of 4

Operation Inspections, Tests and Maintenance


When the rated temperature is reached, the Automatic Sprinklers must never be shipped
fluid which is contained in the glass bulb or stored where their temperature will
expands sufficiently to shatter the glass bulb, exceed 39℃ and they must not be painted,
releasing the bulb cap and spring seat plated, coated or otherwise altered after
assembly. Water flowing through the sprinkler leaving factory. Modified sprinklers must be
orifice and strikes the deflector forming a replaced. Sprinklers that have been exposed
intended spray pattern to extinguish or control to corrosive products of combustion, but
the fire. have not operated, should be replaced if
they cannot be completely cleaned by
wiping the sprinkler with a cloth or by
brushing it with a soft bristle brush.

Care must be exercised to avoid damage to


the sprinklers both before and after
installation. Sprinklers damaged by
dropping, striking, wrench twist/slippage, or
the like, must be replaced. Also, replace any
sprinkler that has a cracked bulb or that has
lost liquid from its bulb.
Spray Pattern

Paratech Co., Ltd REP. NO.: SBI004104 MARCH , 2016


TECHNICAL DATA Installation
Sprinkler PI-3 Series Guide
1of 4

Automatic Sprinkler PI-3 Series ( Glass bulb type )

• Glass bulb
• Standard Spary Pattern
• K-factor 5.6
• Quick & Standard Response

PI 340 PI 341

General Description Technical Data


Minimum Operating Pressure :
Paratech Standard and Quick Response 7 psi (0.5 bar)
Sprinklers are thermo sensitive glass bulb
Maximum Working Pressure :
sprinklers available in different finishes and
temperature ratings to meet design 175 psi (12 bar)
requirements. These sprinklers are sidewall Discharge Coefficient :
standard spray pattern to meet approval K = 5.6 GPM/psi1/2 (80.7 LPM/bar1/2)
agencies requirement. Especially, the Nickel- Temperature Rating:
Chrome plated sprinklers are decorative and
135℉ / 155℉ / 175℉ / 200℉ / 286℉
attractive, so it is well matched to customer
interior decoration. In addition, Nickel- (57℃ / 68℃ / 79℃ / 93℃ / 141℃)
Chrome plating might be utilized to extend Leakage Test at Factory:
the life of copper alloy sprinkler, although it 30 Kgf/㎠ (0.3Mpa, 29.4bar, 426.7 psi)
has passed the standard corrosion test.
Material
Frame Forging ..Brass AS1568 Alloy486
Sprinkler Identification Numbers Deflector . . . . . . . . . . . . Copper C2200
Spring Seat . . . . . . . . . . . . Ni-Be alloy,
PI340 :
coated on both sides with Teflon Tape.
Standard response, Sidewall, 5.6K, ½”(N)PT
Bulb . . . . . . . . . . . . . . . . . . . . . . . . Glass
PI341 : Bulb Cap . . . . . . . . . . . . . . . . . . . C3533
Quick response, Sidewall, 5.6K, ½”(N)PT Screw . . . . . . . . . . . . . . . . . . . . . STS304
Spring . . . . . . . . . . . . . . . . . . . . . STS304

Paratech Co., Ltd REP. NO.: SBI004204 (REV.A) MARCH , 2016


Sprinkler PI-3 Series
2of 4

Design Criteria

AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES


Sprinkler Temperature Sprinkler Nominal Maximum Ambient
Bulb Color
Classification Temperature Rating1 Ceiling Temperature2

Ordinary 135℉(57℃) 100℉(38℃) Orange

Ordinary 155℉(68℃) 100℉(38℃) Red

Intermediate 175℉(79℃) 150℉(65℃) Yellow

Intermediate 200℉(93℃) 150℉(65℃) Green

High 286℉(141℃) 225℉(107℃) Blue

Sprinkler Finishes : Brass, Nickel-Chrome, White Polyester, Black Teflon Coating

Footnotes
1 The sprinkler temperature rating is stamped on the deflector.
2 Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location,
and other requirements of the Authority Having Jurisdiction. Refer to specific installation
standards.

Paratech Co., Ltd REP. NO.: SBI004204 (REV.A) MARCH , 2016


Sprinkler PI-3 Series
3of 4

Approval Chart

Nominal Listings and


Thread Size Overall Length
K-Factor Approvals
SIN
PT NPT U.S. Metric Inches mm cULus

PI340 1/2" 1/2" 5.6 80.7 2.32 59 A1, B1, D1

PI341 1/2" 1/2" 5.6 80.7 2.32 59 A1, B1, C1, D1, E1

Approved Temperature Ratings Approved Finishes


A - 135℉ (57℃) 1- Brass, Nickel-Chrome, White Polyester, and
B - 155℉ (68℃) Black Teflon coating
C - 175℉ (79℃)
D - 200℉ (93℃)
E - 286℉ (141℃)

Installation

The Paratech sprinklers are intended for fire


protection systems designed in accordance
with the standard installation rules of the
applicable listings or approval agency. (eg.,
NFPA 13 or FM’s Loss Prevention Data Sheets)

Note.
Do not install any bulb type sprinkler if the
bulb is cracked or there is a loss of fluid
from the bulb. And with the sprinkler held
horizontally, a small air bubble should be
present.
The sprinkler joint should be obtained with
maximum torque of 28.5 Nm (21 ft-lbs)

Paratech Co., Ltd. REP. NO.: SBI004204 (REV.A) MARCH , 2016


Sprinkler PI-3 Series
4of 4

Operation Inspections, Tests and Maintenance


When the rated temperature is reached, the Automatic Sprinklers must never be shipped
fluid which is contained in the glass bulb or stored where their temperature will
expands sufficiently to shatter the glass bulb, exceed 39℃ and they must not be painted,
releasing the bulb cap and spring seat plated, coated or otherwise altered after
assembly. Water flowing through the sprinkler leaving factory. Modified sprinklers must be
orifice and strikes the deflector forming a replaced. Sprinklers that have been exposed
intended spray pattern to extinguish or control to corrosive products of combustion, but
the fire. have not operated, should be replaced if
they cannot be completely cleaned by
wiping the sprinkler with a cloth or by
brushing it with a soft bristle brush.

Care must be exercised to avoid damage to


the sprinklers both before and after
installation. Sprinklers damaged by
dropping, striking, wrench twist/slippage, or
the like, must be replaced. Also, replace any
sprinkler that has a cracked bulb or that has
lost liquid from its bulb.
Spray Pattern

Paratech Co., Ltd REP. NO.: SBI004204 (REV.A) MARCH , 2016