• Glass bulb
• Standard Spary Pattern
• K-factor 5.6
• Quick & Standard
Response
Paradise Industry Co. Ltd. , REP. NO.: SPH(E) 001 (REV.A) NOV , 2011
Sprinkler PI-2 Series
2of 4
Design Criteria
Note1
Note. 1. The products of UL Listed and FM Approved are not same. Please Contact us to confirm when purchasing.
Installation
The Paradise Industry sprinklers are intended
for fire protection systems designed in
accordance with the standard installation rules
of the applicable listings or approval agency.
(eg., NFPA 13 or FM’s Loss Prevention Data
Sheets)
Note.
Do not install any bulb type sprinkler if the
bulb is cracked or there is a loss of fluid
from the bulb. And with the sprinkler held
horizontally, a small air bubble should be
present.
The sprinkler joint should be obtained with
maximum torque of 28.5 Nm (21 ft-lbs)
Paradise Industry Co. Ltd. , REP. NO.: SPH(E) 001 (REV.A) NOV , 2011
Sprinkler PI-2 Series
3of 4
Spray Pattern
Paradise Industry Co. Ltd. , REP. NO.: SPH(E) 001 (REV.A) NOV , 2011
Sprinkler PI-2 Series
4of 4
Paradise Industry Co. Ltd. , REP. NO.: SPH(E) 001 (REV.A) NOV , 2011
TECHNICAL DATA Installation
Sprinkler PI-2 Series Guide
1of 4
• Glass bulb
• Standard Spary Pattern
• K-factor 5.6
• Quick & Standard Response
PI 222
Paradise Industry Co. Ltd. , REP. NO.: SPH(E) 005 (REV.A) Apr , 2013
Sprinkler PI-2 Series
2of 4
Design Criteria
Installation
The Paradise Industry sprinklers are intended
for fire protection systems designed in
accordance with the standard installation rules
of the applicable listings or approval agency.
(eg., NFPA 13 or FM’s Loss Prevention Data
Sheets)
Note.
Do not install any bulb type sprinkler if the
bulb is cracked or there is a loss of fluid from
the bulb. And with the sprinkler held
horizontally, a small air bubble should be
present.
The sprinkler joint should be obtained with
maximum torque of 28.5 Nm (21 ft-lbs)
Paradise Industry Co. Ltd. , REP. NO.: SPH(E) 005 (REV.A) Apr , 2013
Sprinkler PI-2 Series
3of 4
Spray Pattern
PI 222
Paradise Industry Co. Ltd. , REP. NO.: SPH(E) 005 (REV.A) Apr , 2013
Sprinkler PI-2 Series
4of 4
Paradise Industry Co. Ltd. , REP. NO.: SPH(E) 005 (REV.A) Apr , 2013
TECHNICAL DATA Installation
Sprinkler PI-2 Series Guide
1of 4
• Glass bulb
• Standard Spary Pattern
• K-factor 5.6
• Quick & Standard Response
PI 240 PI 241
Paradise Industry Co. Ltd. , REP. NO.: SPH(E) 002 (REV.A) Apr , 2013
Sprinkler PI-2 Series
2of 4
Design Criteria
Note1
Note1
Installation
The Paradise Industry sprinklers are intended
for fire protection systems designed in
accordance with the standard installation rules
of the applicable listings or approval agency.
(eg., NFPA 13 or FM’s Loss Prevention Data
Sheets)
Note.
Do not install any bulb type sprinkler if the
bulb is cracked or there is a loss of fluid from
the bulb. And with the sprinkler held
horizontally, a small air bubble should be
present.
The sprinkler joint should be obtained with
maximum torque of 28.5 Nm (21 ft-lbs)
Paradise Industry Co. Ltd. , REP. NO.: SPH(E) 002 (REV.A) Apr , 2013
Sprinkler PI-2 Series
3of 4
Spray Pattern
Paradise Industry Co. Ltd. , REP. NO.: SPH(E) 002 (REV.A) Apr , 2013
Sprinkler PI-2 Series
4of 4
Paradise Industry Co. Ltd. , REP. NO.: SPH(E) 002 (REV.A) Apr , 2013
TECHNICAL DATA Installation
Sprinkler PI-7 Series Guide
1of 5
• Fusible alloy
• Standard Sparay Pattern
• K-factor 5.6
• Quick & Standard Response
PI 720 PI 721
Paradise Industry Co. Ltd. , REP. NO.: SPH(E) 003 (REV.A) April , 2013
Sprinkler PI-7 Series
2of 5
Design Criteria
Note. 1. The products of UL Listed is not same. Please Contact us to confirm when purchasing.
Installation
Paradise Industry Co. Ltd. , REP. NO.: SPH(E) 003 (REV.A) April , 2013
Sprinkler PI-7 Series
3of 5
Installation
4. Using the Model PI720 Sprinkler Wrench, 6. After the ceiling finishing is complete and
tighten the Sprinkler into the fitting. the sprinkler system is ready to be put into
The Wrench is shipped over the Protective service, slide off the Protective Cap.
Cap and can be mounted to a 1/2 inch socket
drive ratchet. Align the Wrench Lugs of NOTE
all Sprinklers within a compartment to be Failure to remove the Protective Cap will
parallel to one of the compartment walls. prevent proper operation of the Sprinkler.
Paradise Industry Co. Ltd. , REP. NO.: SPH(E) 003 (REV.A) April , 2013
Sprinkler PI-7 Series
4of 5
Operation
Spray Pattern
PI 720 / PI 721
Paradise Industry Co. Ltd. , REP. NO.: SPH(E) 003 (REV.A) April , 2013
Sprinkler PI-7 Series
5of 5
Paradise Industry Co. Ltd. , REP. NO.: SPH(E) 003 (REV.A) April , 2013
TECHNICAL DATA Installation
Sprinkler PI-8 Series Guide
1of 4
• Glass bulb
• Standard Spray Pattern
• K-factor 5.6
• Quick & Standard Response
PI 820 / PI821
Paradise Industry Co. Ltd. , REP. NO.: SPH(E) 004 OCT , 2012
Sprinkler PI-8 Series
2of 4
Design Criteria
Installation
Note.
Do not install any bulb type sprinkler if the
bulb is cracked or there is a loss of fluid
from the bulb. And with the sprinkler held
horizontally, a small air bubble should be
present.
The sprinkler joint should be obtained with
maximum torque of 28.5 Nm (21 ft-lbs)
Paradise Industry Co. Ltd. , REP. NO.: SPH(E) 004 OCT , 2012
Sprinkler PI-8 Series
3of 4
Spray Pattern
Paradise Industry Co. Ltd. , REP. NO.: SPH(E) 004 OCT , 2012
Sprinkler PI-8 Series
4of 4
Paradise Industry Co. Ltd. , REP. NO.: SPH(E) 004 OCT , 2012
TECHNICAL DATA Installation
Sprinkler PI-3 Series Guide
1of 4
• Glass bulb
• Standard Spary Pattern
• K-factor 5.6
• Quick & Standard Response
Design Criteria
Footnotes
1 The sprinkler temperature rating is stamped on the deflector.
2 Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location,
and other requirements of the Authority Having Jurisdiction. Refer to specific installation
standards.
Approval Chart
PI311 1/2" 1/2" 5.6 80.7 1.84 47.8 A1, B1, C1, D1, E1
PI321 1/2" 1/2" 5.6 80.7 1.88 48.8 A1, B1, C1, D1, E1
Installation
Note.
Do not install any bulb type sprinkler if the
bulb is cracked or there is a loss of fluid
from the bulb. And with the sprinkler held
horizontally, a small air bubble should be
present.
The sprinkler joint should be obtained with
maximum torque of 28.5 Nm (21 ft-lbs)
• Glass bulb
• Standard Spary Pattern
• K-factor 5.6
• Quick & Standard Response
PI 340 PI 341
Design Criteria
Footnotes
1 The sprinkler temperature rating is stamped on the deflector.
2 Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location,
and other requirements of the Authority Having Jurisdiction. Refer to specific installation
standards.
Approval Chart
PI341 1/2" 1/2" 5.6 80.7 2.32 59 A1, B1, C1, D1, E1
Installation
Note.
Do not install any bulb type sprinkler if the
bulb is cracked or there is a loss of fluid
from the bulb. And with the sprinkler held
horizontally, a small air bubble should be
present.
The sprinkler joint should be obtained with
maximum torque of 28.5 Nm (21 ft-lbs)