Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500

Model B-1 — 3.0 K-factor


Upright and Pendent
Foam-Water Sprinklers
tection Association, in addition to the
General standards of any other authorities hav-
ing jurisdiction. Failure to do so may
Description impair the performance of these de-
vices.
The Model B-1 Upright and Pendent
Foam-Water Sprinklers are air-aspi- The owner is responsible for maintain-
rating foam discharge outlets de- ing their fire protection system and de-
signed for use in foam-water deluge vices in proper operating condition.
systems. They are designed for flam- The installing contractor or sprinkler
mable liquid risks where it is desired to manufacturer should be contacted
apply foam from overhead sprinklers with any questions.
(either upright or pendent) and where
follow-up with plain water in a standard
spray sprinkler pattern is necessary as
in the case of NFPA 16, “Standard for
the Installation of Foam-Water Sprin-
Technical
kler and Foam-Water Spray Systems”. Data
It is recommended that the end user be Approvals
consulted with respect to the suitability The Model B-1 Upright and Pendent
of the materials of construction for any Foam-Water Sprinklers are UL and
given corrosive environment. The ef- ULC Listed. (Discharge outlets and
fects of ambient temperature, concen- foam concentrates are Listed for use
tration of chemicals, and gas/chemical
velocity, should be considered, at a
together. Refer to the individual foam
concentrate Listing for operating limi-
Operation
minimum, along with the corrosive na- tations and compatibility with the B-1
ture to which the sprinklers may be The Model B-1 Foam-Water Sprinklers
Foam-Water Sprinklers as provided in are designed with a unique venturi
exposed. the UL Fire Protection Equipment Di- style body. As foam solution (water
The Model B-1 Foam-Water Sprinkler rectory.) and foam concentrate mixture) flows
is a redesignation for the Gem Issue The Model B-1 Upright and Pendent through the inlet of the body, air is
B-1 and Star Model B-1. Foam-Water Sprinklers meet the re- drawn into the body through the open-
quirements of MIL-S-901C for light- ings adjacent to the wrenching area.
WARNINGS weight Grade A shock proof equip- The foam solution and air mix is then
The Model B-1 Foam-Water Sprinklers ment. agitated to create an air-aspirated
described herein must be installed and foam.
maintained in compliance with this The Model B-1 Pendent Foam-Water
document, as well as with the applica- Sprinklers meet the requirements of The B-1 Foam-Water Sprinklers are
ble standards of the National Fire Pro- MIL-H-24146. designed to discharge foam in a pre-
determined discharge pattern, as well
Maximum Working Pressure as to discharge water similar to stand-
175 psi (12,1 bar) ard spray sprinklers. To meet the in-
IMPORTANT
Always refer to Technical Data Discharge Coefficient tent of NFPA 16, foam-water sprin-
Sheet TFP700 for the “INSTALLER K = 3.0 GPM/psi1/2 (43,2 LPG/bar1/2) klers must be able to sufficiently
WARNING” that provides cautions distribute water after depletion of the
Thread Connection foam concentrate.
with respect to handling and instal- 1/2 inch NPT
lation of sprinkler systems and com-
ponents. Improper handling and in- Finishes
stallation can permanently damage Natural Bronze
a sprinkler system or its compo- Physical Characteristics
nents and cause the sprinkler to fail Body . . . . . . . . . . . . . . Bronze
to operate in a fire situation or cause Deflector . . . . . . . . . . . . Brass
it to operate prematurely. Agitator . . . . . . . . . . . . Brass

Page 1 of 4 MARCH, 2006 TFP840


Page 2 of 4 TFP840

1" (25,4 mm)


2-1/8" DIA. WRENCHING ACROSS
(54,0 mm) AREA WRENCH
DEFLECTOR 1/2"
FLATS
NPT
3/8" DIA.
(9,5 mm)

7/16"
(11,1 mm)
5-13/16" NOMINAL BODY
(147,6 mm) MAKE-IN

AGITATOR
AGITATOR

7/16" 5-15/16"
(11,1 mm) BODY (150,8 mm)
NOMINAL
MAKE-IN

3/8" DIA.
(9,5 mm)
1/2"
1" (25,4 mm)
NPT DEFLECTOR
WRENCHING ACROSS 2-1/8" DIA.
AREA WRENCH (54,0 mm)
FLATS

UPRIGHT PENDENT

FIGURE 1
MODEL B-1 UPRIGHT AND PENDENT FOAM-WATER SPRINKLERS
NOMINAL DIMENSIONS

area with a resulting minimum dis-


Design charge pressure of not less than 30 psi
(2,1 bar).
Installation
Criteria Foam-water sprinkler spacing must
The Model B-1 Foam-Water Sprinklers
must be installed in accordance with
The Model B-1 Upright and Pendent not exceed the requirements of NFPA the following instructions:
Foam-Water Sprinklers are intended 13 for extra hazard occupancies and
for fire protection systems designed in the system must be hydraulically cal- NOTE
accordance with the standard installa- culated to obtain the required density A leak tight 1/2 inch NPT sprinkler joint
tion rules for foam-water sprinklers and discharge pressure. should be obtained with a torque of 7
systems recognized by the applicable to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi-
Listing agency (e.g., UL Listing is NOTE mum of 21 ft. lbs. (28,5 Nm) of torque
based on the requirements of NFPA 13 Discharge outlets and foam concen- may be used to install sprinklers with
and 16). trates are Listed for use together. Re- 1/2 NPT connections. Higher levels of
fer to the individual foam concentrate torque may distort the sprinkler inlet
Figure 2 provides the nominal dis- Listing for operating limitations and and cause impairment of the sprinkler.
charge patterns for reference use. compatibility with the B-1 Foam-Water
Sprinklers as provided in the UL Fire Step 1. Pendent sprinklers are to be
NOTE Protection Equipment Directory. installed in the pendent position, and
The discharge patterns shown in Fig- upright sprinklers are to be installed in
ure 2 are not to be used for design the upright position.
purposes or to disregard standard in-
Step 2. With pipe thread sealant ap-
stallation rules.
plied to the pipe threads, hand tighten
Not less than two foam-water sprin- the sprinkler into the sprinkler fitting.
klers are to be installed in any area,
Step 3. Tighten the sprinkler into the
regardless of size, in order to obtain
sprinkler fitting using an 8 or 10 inch
pattern overlap.
adjustable Crescent wrench. With ref-
The applied density (flow per unit of erence to Figures 1 and 3, the adjust-
area) of foam solution must meet the able Crescent wrench is only to be
requirements of the Authority Having applied to the wrench flats of the
Jurisdiction for the type flammable liq- wrenching area.
uid and occupancy. Per NFPA 16, cov-
erage density must not be less than
0.16 GPM/ft2 (6,52 mm/min) of floor
TFP840 Page 3 of 4

DATA KEY
WATER DISCHARGE FOAM DISCHARGE
8 OR 10 INCH
RADIUS, METRES RADIUS, FEET ADJUSTABLE
3,0 2,0 1,0 0 2 4 6 8 10 WRENCH
0 0

DISTANCE BELOW
DISTANCE BELOW
CEILING, METRES

0,5

CEILING, FEET
2
1,0
4 APPLY TO
1,5 WRENCH
FLATS
6 ONLY
2,0

2,5 8
UPRIGHT FIGURE 3
WRENCH FLATS
RADIUS, METRES RADIUS, FEET
3,0 2,0 1,0 0 2 4 6 8 10
0 0

DISTANCE BELOW
DISTANCE BELOW
CEILING, METRES

0,5

CEILING, FEET
2
1,0
4
1,5
6
2,0

2,5 8
PENDENT

FIGURE 2
NOMINAL DISCHARGE PATTERNS
(Shown for reference only — Not suitable for design purposes)

Frequent visual inspections are rec-


Care and ommended to be initially performed for
sprinklers installed in potentially corro-
Maintenance sive atmospheres to verify the integrity
of the materials of construction as they
The Model B-1 Foam-Water Sprinklers may be affected by the corrosive con-
must be maintained and serviced in ditions present for a given installation.
accordance with the following instruc- Thereafter, annual inspections per
tions: NFPA 25 are required.
NOTE The owner is responsible for the in-
Before closing a fire protection system spection, testing, and maintenance of
main control valve for maintenance their fire protection system and de-
work on the fire protection system that vices in compliance with this docu-
it controls, permission to shut down the ment, as well as with the applicable
affected fire protection system must be standards of the National Fire Protec-
obtained from the proper authorities tion Association (e.g., NFPA 25), in
and all personnel who may be affected addition to the standards of any other
by this action must be notified. authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
Model B-1 Foam-Water Sprinklers facturer should be contacted relative
must never be painted, plated, coated to any questions.
or altered in any way after leaving the
factory; otherwise, the spray perform- It is recommended that foam-water
ance may be impaired. sprinkler systems be inspected,
tested, and maintained by a qualified
Care must be exercised to avoid dam- Inspection Service in accordance with
age to the sprinklers - before, during, local requirements and/or national
and after installation. Sprinklers dam- codes.
aged by dropping, striking, wrench
twist/slippage, or the like, must be re-
placed.
Page 4 of 4 TFP840

Limited Ordering
Warranty Procedure
Products manufactured by Tyco Fire & When placing an order, indicate the full
Building Products (TFBP) are war- product name. Refer to the Price List
ranted solely to the original Buyer for for complete listing of Part Numbers.
ten (10) years against defects in mate-
Contact your local distributor for avail-
rial and workmanship when paid for
ability.
and properly installed and maintained
under normal use and service. This
Upright Foam-Water Sprinklers:
warranty will expire ten (10) years
Specify: Model B-1 Upright Foam-
from date of shipment by TFBP. No
Water Sprinkler, P/N 49-210-1-001.
warranty is given for products or com-
ponents manufactured by companies
Pendent Foam-Water Sprinklers:
not affiliated by ownership with TFBP
Specify: Model B-1 Pendent Foam-
or for products and components which
Water Sprinkler, P/N 49-211-1-001.
have been subject to misuse, improper
installation, corrosion, or which have
not been installed, maintained, modi-
fied or repaired in accordance with ap-
plicable Standards of the National Fire
Protection Association, and/or the
standards of any other Authorities
Having Jurisdiction. Materials found
by TFBP to be defective shall be either
repaired or replaced, at TFBP’s sole
option. TFBP neither assumes, nor
authorizes any person to assume for it,
any other obligation in connection with
the sale of products or parts of prod-
ucts. TFBP shall not be responsible for
sprinkler system design errors or inac-
curate or incomplete information sup-
plied by Buyer or Buyer’s repre-
sentatives.
In no event shall TFBP be liable, in
contract, tort, strict liability or under
any other legal theory, for incidental,
indirect, special or consequential dam-
ages, including but not limited to labor
charges, regardless of whether TFBP
was informed about the possibility of
such damages, and in no event shall
TFBP’s liability exceed an amount
equal to the sales price.
The foregoing warranty is made in lieu
of any and all other warranties, ex-
press or implied, including warranties
of merchantability and fitness for a par-
ticular purpose.
This limited warranty sets forth the ex-
clusive remedy for claims based on
failure of or defect in products, materi-
als or components, whether the claim
is made in contract, tort, strict liability
or any other legal theory.
This warranty will apply to the full ex-
tent permitted by law. The invalidity, in
whole or part, of any portion of this
warranty will not affect the remainder.

TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446