1-19/32" ( 40.9mm )
2
3
2-5/16" ( 58.2mm )
2-1/4" ( 56.9mm )
4
1-11/16" ( 42.5mm )
5
6
CENTERLINE OF
WATERWAY
NANJING FIRE PROTECTION TECHNOLOGY CO., LTD. IS AN ISO9001 CERTIFIED COMPANY. TD01511-2- 5/ 1
Tel: 0086-25-84279156, Fax: 0086-25-84279101, Email: nfef@tuna.com.cn ©Copyright 2008 NFPT.
TUNA® Automatic Sprinklers TD01511
NANJING FIRE PROTECTION PIN: NX003-NX006
TECHNICAL DATA
TECHNOLOGY CO., LTD. 200808.2nd Edition
Footnotes:
1
Sprinkler I.D. Nos. and nominal U.S. K-factors provided in accordance with the 2002 edition of NFPA 13.
2
The pipe thread connections accord with ISO7/1.
3
This table shows the listings and approvals available at the time of printing. Check with the manufacturer for any
additional approvals.
4
UL and ULC Listed for both Light-Hazard and Ordinary-Hazard occupancies. FM for Upright type only.
5
Based on National Fire Prevention and Control Administration Contract No. 7-34860.
6
Based on NFPA 13. Other limits may apply depending on fire loading, sprinkler location, and other requirements
of the Authority Having Jurisdiction. Refer to specific installation standards.
7
The temperature rating is stamped on the deflector or adjacent to orifice seat on frame.
65
240
Set Screw Brass UNS-28000 60
220
20 80
ACCESSORIES 15 60
Standard Escutcheon 10 40
PARTIAL CURVE ONLY
5 20
Type E-1 MAX. PRESSURE 1.2 MPA
NANJING FIRE PROTECTION TECHNOLOGY CO., LTD. IS AN ISO9001 CERTIFIED COMPANY. TD01511-2- 5/ 2
Tel: 0086-25-84279156, Fax: 0086-25-84279101, Email: nfef@tuna.com.cn ©Copyright 2008 NFPT.
TUNA® Automatic Sprinklers TD01511
NANJING FIRE PROTECTION PIN: NX003-NX006
TECHNICAL DATA
TECHNOLOGY CO., LTD. 200808.2nd Edition
INSTALLATION
NOTES
Do not install any bulb type sprinkler if the bulb
is cracked or there is a loss of liquid from the
TYPICAL INSTALLATION
bulb. With the sprinkler held horizontal, a small
air bubble should be present. The diameter of FIGURE C : MODEL NX005/NX006 PENDENT
the air bubble is approximately 1/16" (1.6 mm) SPRINKLER INSTALLED WITH A STANDARD
for the 135°F/57°C to 3/32" (2.4 mm) for the ESCUTCHEON
286°F/141°C rating. (At higher ambient
temperatures, the bubble may be barely
perceptible for the lower temperature ratings.)
3. Refer to Figure D and select the appropriate Carefully remove the Sprinkler Wrench by
Sprinkler Wrench for tightening the sprinkler disengaging it from the sprinkler wrench flats,
into the sprinkler fitting. and then lowering it down over the sprinkler
deflector.
NOTES
Sprinkler Assemblies:
CARE AND MAINTENANCE Specify: 1/2" orifice, (specify temperature
rating), Model NX003/NX004 Upright Sprinklers
Automatic sprinklers must never be shipped or with (specify type of finish), PSN (specify as
stored where their temperatures will exceed follows).
100°F/38°C and they must never be painted,
plated, coated or otherwise altered after leaving
the factory. Modified sprinklers must be NX003/NX004 Upright Sprinkler:
replaced. Sprinklers that have been exposed to
corrosive products of combustion, but have not
operated, should be replaced if they cannot be PSN 0151 13 X1 X2 − X3
completely cleaned by wiping the sprinkler with
a cloth or by brushing it with a soft bristle brush. Sprinkler Response and
X1
Nominal Temperature Rating
Care must be exercised to avoid damage to 1 135°F∕57°C Standard Response
the sprinklers — both before and after
2 135°F∕57°C Quick Response
installation. Sprinklers damaged by dropping,
striking, wrench twist/slippage, or the like, must 3 155°F∕68°C Standard Response
be replaced. Also, replace any sprinkler that 4 155°F∕68°C Quick Response
has a cracked bulb or that has lost liquid from 5 175°F∕79°C Standard Response
its bulb (ref. Installation Section Note). 6 175°F∕79°C Quick Response
NOTES 7 200°F∕93°C Standard Response
Absence of an escutcheon, which is used to 8 200°F∕93°C Quick Response
cover a clearance hole, may delay the time to X2 Thread Size and Sprinkler Finish
sprinkler operation in a fire situation. 1 NPT1/2 Natural Brass
Before closing a fire protection system control 2 NPT1/2 Chrome Plated
valve for maintenance work on the fire 3 R1/2 per ISO 7/1 Natural Brass
protection system, which it controls, permission 4 R1/2 per ISO 7/1 Chrome Plated
to shut down the affected fire protection system
X3 Listings and Approvals
must be obtained from the proper authorities
and all personnel who may be affected by this 1 CCC
action must be notified. 2 UL∕ULC
It is recommended that automatic sprinkler 3 FM
systems be inspected quarterly by a qualified 4 FM & UL
Inspection Service.
Please refer to LIST PRICE BOOK for available
PSN.
ORDERING PROCEDURE
NANJING FIRE PROTECTION TECHNOLOGY CO., LTD. IS AN ISO9001 CERTIFIED COMPANY. TD01511-2- 5/ 4
Tel: 0086-25-84279156, Fax: 0086-25-84279101, Email: nfef@tuna.com.cn ©Copyright 2008 NFPT.
TUNA® Automatic Sprinklers TD01511
NANJING FIRE PROTECTION PIN: NX003-NX006
TECHNICAL DATA
TECHNOLOGY CO., LTD. 200808.2nd Edition
! WARNING
This product must be installed by an experienced, trained installer, in accordance with the instructions provided
1
with each valve. These instructions contain important information.
Failure to follow these instructions may result in serious personal injury, property damage, or valve leakage.
We reserve the right to change product specifications, designs and standard equipment without notice and
without incurring obligations.
If you have any questions about the safe installation and use of this device, contact Nanjing Fire Protection
Technology Co., Ltd. P.C.210007, 12 Shiyang Road, Baixia District, Nanjing, R. P.China