INDOOR LIGHTING CALCULATION (BZ-METHOD)

PROJECT BADRA WTTP Actual Values needed


LUMINAIRE HIGH-BAY LIGHTING 150 WATT needed as as per
FACILITY LIFT PUMP STATION PR5 per design installation
1 Room Width W m 7.20
2 Room Length L m 4.00
3 Room Area Af L*W 28.80 28.80
4 Total Height Ht m 5.29
5 Suspension length Hs m 1.00
6 Mounting Height Hm Ht - Hs 4.29 4.29
L*W
7 Room Index Kr = 0.599 0.599
Hm(L+W)
8 Reflectance
Celing Rc 0.27
Walls Rw 0.27
Floor Rf 0.27
9 Number of light sources per lantern. n 1.00 1
10 Utilization Factor.
From Table
Kr1 UF1 UF2 - UF1 * Kr - Kr1
Kr 0.599 UF # UF =UF1+ 0.300 0.300
Kr2 0.6 UF2 0.3 Kr2 -Kr 1
11 Reduction Factor k 1.00 1.00
12 Depreciation Factor f 1.54 1.54
13 Type of Lamp
14 Luminous Flux per Lamp O 14500.00 14500
15 Illumination Level E 250.00 250
E*Af*f
16 Calculation of Number Luminair N= 2.552
O * n *UF*K

L*N
17 Number of Luminair Along NL= 1.2
W
NL(Rounted Figure.) 1 1
W*N
18 Number of Luminair Across NW= 2.1
L
NW (Rounted Figure.) 2 3
19 Total Number of Luminairs Nt= NL*NW 3 4

1 Af
20 Uniformity S/Hm= 0.78 0.66
Hm Nt
Nt*O*n*UF*k
21 Maintained Average Illuminance Aave = 250 348
Af*f
Note: Average Illuminance as per selection = 348