CLAUSE NO.
TECHNICAL REQUIREMENTS
13
[Type
18
16.
17.
‘The isolation transformer shall be fed from two different bus sections of MCC and
fault level restricted to 3 KA at Lighting Panels.
Atleast one 6/184, 240V AC universal socket outlet with switch shall be provided
in offices, cabins, etc. Further 20A, 240V AC industrial receptacle with switch
shall be provided strategically in all industrial areas.
Suitable number of 63A, 3p7, 415V AC industrial receptacles shall be provided
‘for entire plant for welding purposes, particularly near all major equipment and at
2an average distance of 50m Atleast one 63A, 3ph, 415V AC receptacle shall be
provided in each floor of of-site buildings! structures.
Receptacles boxes shall be fabricated out of 2 mm thick MS steel hot dip
galvanized or of not less than 2.5 mm thick die-cast aluminium alloy or fabricated
Cut of 2 mm thick CRCA sheet with electro static powder coating. IP-degree of
protection shall be applicable to receptacles Type ‘RA &RC’ only
Receptacles shal be of flloving types :
‘Switch rang Sockst Slug Type & make of plug & Terminal Block size
rating Socket
20A,sP240V 20K, 3pm240VAC NTPC apd make 1A way, suitable Fr lop.
Ac(indsstid) troop ut of 109 en.
‘AL Conductor
16a, SP24v AC 61606 Pin NTPC apd make 14 way, stab forloop-
eceratvo Piano. inoop- cut of upto 10
oy Type Sich ‘samm. Al. Conductor
ASP24V 20K, 39N24VAC_—NIPCappd make 1-4 way, stable for lop
Ac(indsstid) inoop- out of 2co10-16
sqm Al Cable
In the hazardous areas like Hydrogen generation plant, fuel oil handling areas or
any other gas! liquid fuel storage! handling areas in bidder's scope, lighting shall
be flame proof.
The type of fixtures, LP, JB. and receptacle used in Hydrogen generation plant
building shall be suitable for group II C as per IS: 2148 or class I, Division Il as
per NEC 70-428,
Al flouresent lamps shall be have "Cool day light” colour designation. The mirror
cptics type flouresent fixtures shall have no irridescence effect. Fixtures with
better efficiency and upgraded proven system may also be considered
Incandescent lamps may be used only with DC Lighting.
Aviation warning lights shall be provided as per the recommendations of ICAO
and Director general of civil aviation, india. The arrangement of light should be
marked such that the object is indicated from every angle in azimuth. The
LOTAA PROVECTS. TECHNICAL SPECIFICATION “SUBSECTIONALEIS
Page
FLUE GAS FLUE GAS DESULPHURISATION SECTION- Vi, PART-B evesathioet da Be
(FD) SYSTEM PACKAGE Bip DOC NO : €8-0011-109(1A)-2