TEST CERTIFICATE FOR CURRENT TRANSFORMER

AS PER INDIAN STANDARD SPECIFICATION NO.: 2705 - 1992


Office : 13, Gouranga Mandir road,
Serial No. : 72397 - 72399 RESIN CAST Kusumkanan, Kolkata-700086, India.
Phone: (033) 24258509/24250079
Client : CONTROL BLUE AUTOMATION & SOFTWARE (I) PVT. LTD. Factory:
Order No. : CBA/IN/PO/025/2020-21 Unit I : 130, Nath Para, Manikpur,
Date : 24.08.2020 P.O.: Harinavi, Kolkata-700148, India.
Material No. :
Ref. Drg. No.:

CT TYPE : RING TYPE VA Burden : 5 VA ID : 30 mm


Class of CT : METERING System Voltage : 415 V Quantity : 3 Nos
Ratio : 160/1 A H.S.V : 1.1 KV
Frequency : 50 Hz Accuracy Class : 1

This is to certify that the Current Transformer bearing serial nos. given above have been manufactured in accordance
with Indian Standard Specification IS 2705 - 1992 to which they confirm and following are the routine tests performed.

FACTORY TEST RESULT

Polarity Test: Checked as per terminal marking.

High Voltage Power Frequency one Minute withstand Test:


Withstood : 3 KV between Primary to Secondary and Earth.
Withstood : 3 KV between Secondary to Primary and Earth.

Inter-turn Insulation Test : Conducted as per ISS and test was satisfactory.

Composite Error Test for Protection Class Current Transformer : Conducted as per ISS and test was
satisfactory.
Ratio & Phase Angle Error and Class of Accuracy Test : The test was carried out at 5 VA Burden.

Date of Test: 02.09.2020 Prepared By: Tested By: Certified by