Job Code 0-7723

Owner's Doc. No. 17546Z-UN2-FM-MR-43PA401

SONATRACH
Contractor's Doc. No. S-43-1358-101
Hassi Messaoud Upside North Project Sheet 1 of 14

SONATRACH
HASSI MESSAOUD UPSIDE NORTH PROJECT

REALISATION D’UN CENTRE DE SEPARATION ET DE COMPRESSION (CSC)


A L’UN2-1(UPSIDE NORD) HASSI-MESSAOUD ALGERIE

CONTRACT No. ENC 17 546Z

MECHANICAL DATA SHEET FOR COMMON FLARE KO DRUM


PUMPS UN21-PA-43-401A/B

REV. DATE PAGE RESON FOR ISSUE PREP'D CHK'D APP'D

A 31-Aug-17 ALL FOR APPROVAL G. Ronquillo H. Nakazawa K. Fujii

1 22-Dec-17 ALL FOR CONSTRUCTION G. Ronquillo H. Nakazawa K. Fujii

2 25-Jul-18 ALL FOR CONSTRUCTION Milind H. Nakazawa K. Fujii

D R A
N
I 25-JUL 8
- 2 0 1
D
RINTE
HEN P
T ROLL
ED W 1 / 14
NCON
Job Code 0-7723
Owner's
17546Z-UN2-FM-MR-43PA401
Doc. No.
SONATRACH Contractor's
S-43-1358-101
Hassi Messaoud Upside North Project Doc. No.
MECHANICAL DATA SHEET FOR COMMON FLARE
KO DRUM PUMPS UN21-PA-43-401A/B
Sheet 2 of 14 Rev. 2

Item Revision Description Remarks


Sheet 5, One (1) vibration sensor per bearing housing is added. Vib. Sensor is added
Line 4,6 as agreed

D R A
N
I 25-JUL 8
- 2 0 1
D
RINTE
HEN P
T ROLL
ED W 2 / 14
NCON
Job Code 0-7723
Owner's
17546Z-UN2-FM-MR-43PA401
Doc. No.
SONATRACH Contractor's
S-43-1358-101
Hassi Messaoud Upside North Project Doc. No.
MECHANICAL DATA SHEET FOR COMMON FLARE
KO DRUM PUMPS UN21-PA-43-401A/B
Sheet 3 of 14 Rev. 2
1 Note APPLICABLE TO: PROPOSAL APPLICABLE NTL/INTNTL STANDARD: API-610 Rev
2 FOR SONATRACH UNIT COMMON FLARE KNOCK OUT
3 SITE LOT 4 PERIPHERY UPSIDE NORTH (UN) SERVICE COMMON FLARE KNOCK OUT DRUM PUMPS
4 NO. REQ 2 PUMP SIZE TYPE No. STAGES
5 MANUFACTURER MODEL SERIAL NO.

6 LIQUID CHARACTERISTICS
7 1 Units Maximum Rated Normal Rated SERVICE : (Note 1) INTERMITTENT
8 LIQUID TYPE OR NAME : WATER / HYDROCARBON • IF INTERMITTENT NO. OF STARTS :
9 VAPOR PRESSURE : bar a 1.2 1.2 - 1.2 PUMPS OPERATE IN: PARALLEL
10 4 RELATIVE DENSITY : 1.10 0.43 - 0.43 CORROSION DUE TO : (6.12.1.9) (Note 4)
11 4 SPECIFIC HEAT : kJ/(kg-K) - - - - EROSION DUE TO : (6.12.1.9) (Note 4)
12 VISCOSITY : cP 0.65 0.54 - 0.54 H2S CONCENTRATION (ppm) : (6.12.1.12) N/A

13 4 OPERATING CONDITIONS (6.1.2) CHLORIDE CONCENTRATION (ppm) : (Note 4)


14 Units Maximum Rated Normal Minimum PARTICULATE SIZE (DIA IN MICRONS)

15 6 NPSHa Datum: CL OF IMPELLER (Note 6) PARTICULATE CONCENTRATION (PPM)

16 PUMPING TEMPERATURE : °C 60.0 40 40 25


17 FLOW : m³/h 114 104 31.2
18 DISCHARGE PRESSURE : (6.3.2) bar g 9.23
19 SUCTION PRESSURE : bar g 4.08 0.21
20 DIFFERENTIAL PRESSURE : bar 9.02
21 DIFFERENTIAL HEAD : m 213.9
22 6 NPSHA (Note 6): m 0.4
23 HYDRAULIC POWER (Note 15) : kW 72.7 1

24 SITE AND UTILITY DATA


25 3 LOCATION: (Note 3) COOLING WATER : Not Available
26 OUTDOOR UNHEATED INLET RETURN DESIGN

27 MOUNTED AT : GRADE  TROPICALISATION REQD TEMP °C MAX


28 ELECTRIC AREA CLASSIFICATION: 6.1.22 ZONE 2 PRESS. bar g MIN
29 GROUP Group IIA TEMP CLASS T3 SOURCE
30 2 SITE DATA : (Note 2) COOLING WATER CHLORIDE CONCENTRATION: ppm
31 ELEVATION (MSL) +169.15 m BAROMETER : mmHg INSTRUMENT AIR : MAX 9 bar g MIN 4 bar g 1
32 RANGE OF AMBIENT TEMPS:MIN / MAX -5 / 55 °C STEAM Not Available
33 RELATIVE HUMIDITY: MIN / MAX @40°C 20 / 50 % DRIVERS HEATING
34 UNUSUAL CONDITIONS: DUST TEMP °C Max

35 • SPECIFY OTHER : High potential of sandstorm. Min


36 2 UTILITY CONDITIONS : (Note 2) PRESS. bar g Max
37 ELECTRICITY : DRIVERS HEATING CONTROL SHUTDOWN Min
38 VOLTAGE 400
39 PHASE 3
40 HERTZ 50

41 PERFORMANCE DRIVER (7.1.5)


42 PROPOSAL CURVE NO. RPM Driver Type MOTOR
43 As Tested Curve No. GEAR NO
44 IMPELLER DIA.: RATED MAX. MIN. mm VARIABLE SPEED REQUIRED NO
45 RATED POWER kW EFFICIENCY (%) SOURCE OF VARIABLE SPEED N/A
46 RATED CURVE BEP FLOW (at rated impeller dia) m³/h OTHER
47 MIN FLOW : THERMAL m³/h STABLE m³/h MANUFACTURER
48 PREFERRED OPERATING REGION (6.1.11) to m³/h NAMEPLATE POWER kW
49 ALLOWABLE OPERATING REGION to m³/h NOMINAL RPM
50 7 MAX HEAD @ RATED IMPELLER (Note 7) m RATED LOAD RPM
51 MAX POWER @ RATED IMPELLER (6.8.9) kW FRAME OR MODEL
52 NPSH3 AT RATED FLOW : m ORIENTATION
53 CL PUMP TO U/S BASEPLATE m LUBE Grease
54 NPSH MARGIN AT RATED FLOW : m BEARING TYPE:
55 SPECIFIC SPEED (6.1.9) (gpm, ft, rpm) RADIAL
56 SUCTION SPECIFIC SPEED LIMIT (gpm, ft, rpm) <10,000 THRUST
57 SUCTION SPECIFIC SPEED (gpm, ft, rpm) STARTING METHOD
58 8 MAX. ALLOW. SOUND PRESS. LEVEL REQD (6.1.14) (Note 8) (dBA) SEE DRIVER DATA SHEET See Sht 12~14
59 EST MAX SOUND PRESS. LEVEL (dBA)
60 MAX. SOUND POWER LEVEL REQ'D (6.1.14)
61 EST MAX SOUND POWER LEVEL

D R A
N
I 25-JUL 8
- 2 0 1
D
RINTE
HEN P
T ROLL
ED W 3 / 14
NCON
Job Code 0-7723
Owner's
17546Z-UN2-FM-MR-43PA401
Doc. No.
SONATRACH Contractor's
S-43-1358-101
Hassi Messaoud Upside North Project Doc. No.
MECHANICAL DATA SHEET FOR COMMON FLARE
KO DRUM PUMPS UN21-PA-43-401A/B
Sheet 4 of 14 Rev. 2
1 Note CONSTRUCTION Rev
2 API PUMP TYPE: VS6 [Based on API 610 definitions] CASING MOUNTING: VERTICAL
3 CASING TYPE: (6.3.10)
4 NOZZLE CONNECTIONS: (6.5.5) OH3 BACKPULLOUT LIFTING DEVICE REQD. (9.1.2.6)
5 Size Facing Rating Position CASE PRESSURE RATING:
6 SUCTION RF 300 END MAWP : (6.3.6) bar g @ °C
7 DISCHARGE RF 300 TOP HYDROTEST : bar g @ °C
8 PRESSURE CASING AUX. CONNECTIONS: (6.4.3.2)
9 No. Size Type Facing Rating Posn. HYDROTEST OH PUMP AS ASSEMBLY
10 BALANCE/LEAK OFF SUCT'N PRESS. REGIONS DESIGNED FOR MAWP YES
11 DRAIN RF 300 ROTATION: (VIEWED FROM COUPLING END)
12 VENT if required RF 300 • IMPELLERS INDIVIDUALLY SECURED :
13 PRESSURE GAGE • BOLT OH 3/4/5 PUMP TO PAD / FOUNDATION :
14 TEMP GAGE • PROVIDE SOLEPLATE FOR OH 3/4/5 PUMPS
15 WARM-UP LINE ROTOR:
16 SHAFT FLEXIBILITY INDEX (SFI) (9.1.1.3)
17 Drain Valve Supplied By SUPPLIER First Critical Speed Wet (Multi stage pumps only)
18 DRAINS MANIFOLDED YES COMPONENT BALANCE TO ISO 1940 G1.0
19 VENT Valve Supplied By SUPPLIER SHRINK FIT -LIMITED MOVEMENT IMPELLERS (9.2.2.3)
20 VENTS MANIFOLDED YES
21 THREADED CONS FOR PIPELINE SERVICE & < 50°C (6.4.3.2) COUPLING:(7.2.3) (7.2.13.f)
22 SPECIAL FITTINGS FOR TRANSITIONING (6.4.3.3) MANUFACTURER
23 CYLINDRICAL THREADS REQUIRED (6.4.3.8) MODEL
24 GUSSET SUPPORT REQUIRED RATING (POWER/100 RPM)
25 MACHINED AND STUDDED CONNECTIONS (6.4.3.12) YES SPACER LENGTH mm
26 VS 6 DRAIN Internal SERVICE FACTOR
27 DRAIN TO SKID EDGE YES RIGID NO
28 COUPLING WITH HYDRAULIC FIT (7.2.10)
29 MATERIAL (6.12.1.1) COUPLING BALANCED TO ISO 1940-1 G2.5 YES
30 9 APPENDIX H CLASS D-1 (Note 9) COUPLING WITH PROPRIETARY CLAMPING DEVICE (7.2.11) 1
31 MIN DESIGN METAL TEMP (6.12.4.1) -5 °C
32 REDUCED-HARDNESS MATERIALS REQ'D (6.12.1.12.1) COUPLING IN COMPLIANCE WITH (7.2.4) API 610 compliant
33 Applicable Hardness Standard (6.12.1.12.3) COUPLING GUARD STANDARD PER (7.2.13.a)
34 BARREL : Window on Coupling Guard N/A
35 BOWL :
36 DIFFUSERS BASEPLATE
37 IMPELLER : DUPLEX SS API BASEPLATE NUMBER : 1
38 IMPELLER WEAR RING : BASEPLATE CONSTRUCTION (7.3.14)
39 CASE WEAR RING : BASEPLATE DRAINAGE (7.3.1)
40 SHAFT: DUPLEX SS MOUNTING : 1
41 Bowl (if VS-type) DUPLEX SS NON-GROUT CONSTRUCTION : (7.3.13) 1
42 Inspection Class VERTICAL LEVELING SCREWS :

43 BEARINGS AND LUBRICATION (6.10.1.1) LONGITUDINAL DRIVER POSITIONING SCREWS :


44 BEARING (TYPE / NUMBER): (6.11.4) SUPPLIED WITH :  GROUT AND VENT HOLES
45 RADIAL /  DRAIN CONNECTION
46 THRUST / MOUNTING PADS SIZED FOR BASEPLATE LEVELING (7.3.5)
47 REVIEW AND APPROVE THRUST BEARING SIZE : (9.2.5.2.4) MOUNTING PADS TO BE MACHINED (7.3.6)
48 PROVIDE SPACER PLATE UNDER ALL EQUIPMENT FEET
49 LUBRICATION : (6.10.2.2) (6.11.3) (9.6.1) OTHER
50 PRESSURE LUBE SYSTEM TO ISO 10438- (9.2.6.5)
50 ISO 10438 DATA SHEETS ATTACHED
51 Pressurized Lube Oil System mtd on pump baseplate REMARKS :
52 Location of Pressurized Lube Oil System mounted on baseplate :
53
54 INTERCONNECTING PIPING PROVIDED BY Supplier
55
56 OIL VISC. ISO GRADE VG
57 CONSTANT LEVEL OILER : REQUIRED

D R A
N
I 25-JUL 8
- 2 0 1
D
RINTE
HEN P
T ROLL
ED W 4 / 14
NCON
Job Code 0-7723
Owner's
17546Z-UN2-FM-MR-43PA401
Doc. No.
SONATRACH Contractor's
S-43-1358-101
Hassi Messaoud Upside North Project Doc. No.
MECHANICAL DATA SHEET FOR COMMON FLARE
KO DRUM PUMPS UN21-PA-43-401A/B
Sheet 5 of 14 Rev. 2
1 Note INSTRUMENTATION SEAL SUPPORT SYSTEM MOUNTING Rev
2 SEE ATTACHED API-670 DATA SHEET N/A SEAL SUPPORT SYSTEM MOUNTED ON PUMP SOLEPLATE
3 ACCELEROMETER (7.4.2.1) (7.5.1.4) YES
4 Number of Accelerometers 1 per Bearing IDENTIFY LOCATION ON BASEPLATE 2
5 Mounting Location of Accelerometers
6 Bearing Housing INTERCONNECTING PIPING BY Supplier 2
7 PROVISION FOR MTG ONLY (6.10.2.10)
8 Number of Accelerometers MECHANICAL SEAL (6.8.1)

9 Mounting Location of Accelerometers SEE ATTACHED ISO 21049/API 682 DATA SHEET YES
10 ADDITIONAL CENTRAL FLUSH PORT (6.8.9)
11 FLAT SURFACE REQUIRED (6.10.2.11) YES HEATING JACKET REQ'D. (6.8.11)
12 Number of Accelerometers
13 Mounting Location of Accelerometers HEATING AND COOLING (6.1.17)
14 COOLING REQ'D N/A
15 VIBRATION PROBES (7.4.2.2) COOLING WATER PIPING PLAN
16 PROVISIONS FOR VIB. PROBES COOLING WATER PIPING
17 NUMBER PER RADIAL BEARING FITTINGS
18 NUMBER PER AXIAL BEARING COOLING WATER PIPING MATERIALS
COOLING WATER REQUIREMENTS:
19 MONITORS AND CABLES SUPPLIED BY (7.4.2.4) BEARING HOUSING m³/h
20 HEAT EXCHANGER m³/h
21 TEMPERATURE (7.4.2.3) TOTAL COOLING WATER m³/h
22 PROVISIONS FOR TEMP PROBES HEATING MEDIUM
23 RADIAL BEARING TEMP. OTHER
24 NUMBER PER RADIAL BEARING HEATING PIPING
25 THRUST BEARING TEMP.
26 NUMBER PER THRUST BEARING ACTIVE SIDE PIPING & APPURTENANCES
27 NUMBER PER THRUST BEARING INACTIVE SIDE MANIFOLD PIPING FOR PURCHASER CONNECTION (7.5.1.6)
28 TEMP. GAUGES (WITH THERMOWELLS) (9.1.3.6) VENT YES
29 PRESSURE GAUGE TYPE DRAIN YES
30 Remarks COOLING WATER N/A
31 TAG ALL ORIFICES (7.5.2.4) YES
32 SOCKET WELD CONN ON SEAL GLAND (7.5.2.8)
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65

D R A
N
I 25-JUL 8
- 2 0 1
D
RINTE
HEN P
T ROLL
ED W 5 / 14
NCON
Job Code 0-7723
Owner's
17546Z-UN2-FM-MR-43PA401
Doc. No.
SONATRACH Contractor's
S-43-1358-101
Hassi Messaoud Upside North Project Doc. No.
MECHANICAL DATA SHEET FOR COMMON FLARE
KO DRUM PUMPS UN21-PA-43-401A/B
Sheet 6 of 14 Rev. 2
1 Note SURFACE PREPARATION AND PAINT TEST Rev
2 MANUFACTURER'S STANDARD SHOP INSPECTION (8.1.1)
3 OTHER (SEE BELOW) YES PERFORMANCE CURVE
4 SPECIFICATION NO. As per S-00-13A0-001 & DATA APPROVAL PRIOR TO SHIPMENT. YES
5 TEST WITH SUBSTITUTE SEAL (8.3.3.2.b)
6 PUMP: MATERIAL CERTIFICATION REQUIRED CASING YES
7 PUMP SURFACE PREPARATION *Refer to S-00-1358-003 IMPELLER YES
8 PRIMER SHAFT YES
9 FINISH COAT OTHER YES
10 CASTING REPAIR WELD PROCEDURE APPR REQD
BASEPLATE: (6.12.2.5) (6.12.3.1)
11 BASEPLATE SURFACE PREPARATION INSPECTION REQUIRED FOR CONNECTION WELDS (6.12.3.4.d)
12 PRIMER: (6.12.3.4.e) MAG PARTICLE
13 FINISH COAT RADIOGRAPHY
14 DETAILS OF LIFTING DEVICES LIQUID PENETRANT
15 ULTRASONIC
16 SHIPMENT: (8.4.1) EXPORT INSPECTION REQUIRED FOR CASTINGS
17 EXPORT BOXING REQUIRED YES MAG PARTICLE
18 OUTDOOR STORAGE MORE THAN 6 MONTHS YES RADIOGRAPHY
LIQUID PENETRANT
19 SPARE ROTOR ASSEMBLY PACKAGED FOR: ULTRASONIC
20 ROTOR STORAGE ORIENTATION (9.2.8.2) HARDNESS TEST REQUIRED (8.2.2.7)
21 SHIPPING & STORAGE CONTAINER FOR VERT STORAGE (9.2.8.3) ADDNL SUBSURFACE EXAMINATION (6.12.1.5) (8.2.1.3)
22 FOR
23 N2 PURGE (9.2.8.4) METHOD
24 SPARE PARTS PMI TESTING REQUIRED (8.2.2.8) As per S-00-1520-103
25 START-UP YES COMPONENTS TO BE TESTED
26 NORMAL MAINTENANCE
27 WEIGHTS kg RESIDUAL UNBALANCE TEST (J.4.1.2)

28 ITEM No PUMP DRIVER GEAR BASE TOTAL NOTIFICATION OF SUCCESSFUL SHOP


29 PERFORMANCE TEST (8.1.1.c) (8.3.3.5) YES
30 BASEPLATE TEST (7.3.21)
31 HYDROSTATIC WIT
32 HYDROSTATIC TEST OF BOWLS & COLUMN (9.3.13.2)
33 OTHER PURCHASER REQUIREMENTS PERFORMANCE TEST 8.3.3.1 of S-00-1358-003 WIT
34 COORDINATION MEETING REQUIRED (10.1.3) YES TEST IN COMPLIANCE WITH (8.3.3.2)
35 MAXIMUM DISCHARGE PRESSURE TO INCLUDE TEST DATA POINTS TO (8.3.3.3)
36 MAX RELATIVE DENSITY YES TEST TOLERANCES TO (8.3.3.4)
37 OPERATION TO TRIP SPEED NPSH (8.3.4.3.1) (8.3.4.3.4) WIT
38 MAX DIA. IMPELLERS AND/OR NO OF STAGES NPSH-1ST STG ONLY (8.3.4.3.2)
39 CONNECTION DESIGN APPROVAL (9.2.1.4) NPSH TESTING TO HI 1.6 OR ISO 9906 (8.3.4.3.3)
40 TORSIONAL ANALYSIS / REPORT (6.9.2.10) TEST NPSHA LIMITED TO 110% SITE NPSHA (8.3.3.6)
41 PROGRESS REPORTS YES RETEST ON SEAL LEAKAGE (8.3.3.2.d)
42 OUTLINE OF PROC FOR OPTIONAL TESTS (10.2.5) RETEST REQUIRED AFTER FINAL HEAD ADJ (8.3.3.7.b)
43 ADDITIONNAL DATA REQUIRING 20 YEARS RETENTION (8.2.1.1) COMPLETE UNIT TEST (8.3.4.4.1)
44 SOUND LEVEL TEST (8.3.4.5)
45 LATERAL ANALYSIS REQUIRED (9.1.3.4) (9.2.4.1.3) CLEANLINESS PRIOR TO FINAL ASSEMBLY (8.2.2.6)
46 MODAL ANALYSIS REQUIRED (9.3.9.2) LOCATION OF CLEANLINESS INSPECTION
47 DYNAMIC BALANCE ROTOR (6.9.4.4) NOZZLE LOAD TEST
48 INSTALLATION LIST IN PROPOSAL (10.2.3.l) CHECK FOR CO-PLANAR MOUNTING PAD SURFACES
49 VFD STEADY STATE DAMPED RESPONSE ANALYSIS (6.9.2.3) MECHANICAL RUN TEST UNTIL OIL TEMP STABLE (*) WIT
50 4 HR. MECH RUN AFTER OIL TEMP STABLE (8.3.4.2.1)
51 TRANSIENT TORSIONAL RESPONSE (6.9.2.4) 4 HR. MECH RUN TEST (8.3.4.2.2)
52 BEARING LIFE CALCULATIONS REQUIRED (6.10.1.6) (*) 8.3.4.2.2 of S-00-1358-003
IGNITION HAZARD ASSMT TO EN 13463-1 (7.2.13.e) BRG HSG RESONANCE TEST (8.3.4.7)
53 CASING RETIREMENT THICKNESS DRAWING (10.3.2.3) STRUCTURAL RESONANCE TEST (9.3.9.2)
54 FLANGES RQD IN PLACE OF SKT WELD UNIONS (7.5.2.8) REMOVE / INSPECT HYDRODYNAMIC BEARINGS AFTER TEST
55 INCLUDE PLOTTED VIBRATION SPECTRA (6.9.3.3) YES (9.2.7.5)
56 CONNECTION BOLTING (7.5.1.7) AUXILIARY EQUIPMENT TEST (8.3.4.6)
57 CADMIUM PLATED BOLTS PROHIBITED EQUIPMENT TO BE INCLUDED IN AUXILLIARY TESTS
58 VENDOR TO KEEP REPAIR AND HT RCDS (8.2.1.1.c)
59 VENDOR SUBMIT TEST PROCEDURES (8.3.1.1) YES LOCATION OF AUXILIARY EQUIPENT TEST
60 SUBMIT INSPECTION CHECK LIST (8.1.5) YES
61 IMPACT TEST (6.12.4.3) PER EN 13445
62 PER ASME SECTION VIII
REMOVE CASING AFTER TEST

D R A
N
I 25-JUL 8
- 2 0 1
D
RINTE
HEN P
T ROLL
ED W 6 / 14
NCON
Job Code 0-7723
Owner's
17546Z-UN2-FM-MR-43PA401
Doc. No.
SONATRACH Contractor's
S-43-1358-101
Hassi Messaoud Upside North Project Doc. No.
MECHANICAL DATA SHEET FOR COMMON
FLARE KO DRUM PUMPS UN21-PA-43-401A/B
Sheet 7 of 14 Rev. 2
1 Note VERTICAL TYPE (FIG 1.1) VS6 Rev
2
3
4
5
6 VERTICAL PUMPS VERTICAL PUMPS (CONT'D)
7 PUMP THRUST: (+) UP (-) DOWN LINE SHAFT:
8 STATIC THRUST N N LINE SHAFT DIAMETER mm
9 AT MIN FLOW N N TUBE DIAMETER mm
10 AT RATED FLOW N N LINE SHAFT COUPLING:
11 AT MAX FLOW N N LINESHAFT CONNECTION
12 MAX THRUST N N
13 SOLEPLATE REQUIRED YES • SUCTION STRAINER TYPE
14 SOLEPLATE Length x Width m X m • LEVEL CONTROL
15 SOLEPLATE THICKNESS mm IMPELLER COLLETS ACCEPTABLE
16 MOUNTING FLANGE REQUIRED HARDENED SLEEVES UNDER BEARINGS (9.3.10.5) YES
17 COLUMN PIPE: RESONANCE TEST YES
18 DIAMETER mm STRUCTURAL ANALYSIS (9.3.5)
19 LENGTH m
20 NUMBER DRIVER ALIGNMENT SCREWS
21 SPACING m SUCTION CAN
22 GUIDE BUSHINGS: SUCTION CAN THICKNESS mm
23 NUMBER LENGTH m
24 LINE SHAFT BEARING SPACING mm DIAMETER mm
25 GUIDE BUSHING LUBE: SEPARATE MOUNTING PLATE (9.3.8.3.1)
26 PROVIDE SEPARATE SOLEPLATE (9.3.8.3.3) YES
27 DRAIN PIPED TO SURFACE (9.3.13.5) YES
28 BOWL HEAD CALCULATION REQUIRED

29 MATERIALS (additional) (Note 9)


30 SUCTION CAN / BARREL: LINESHAFT SLEEVES :
31 DISCHARGE HEAD : • BEARING RETAINER :
32 BOWL SHAFT : SHAFT ENCLOSING TUBE :
33 LINESHAFT : DISCHARGE COLUMN :
34 LINESHAFT HARDFACING : PRESSURE RATING: MAWP HYDRO
35 BELLMOUTH : HEAD
36 BOWL BEARING : COLUMN PIPE
37 LINESHAFT BEARING : BOWL

38 19 SUMP ARRANGEMENT
39 SUMP DIMENSIONS :
40 GRADE ELEVATION 1 +0 m
41 LOW LIQUID LEVEL 2 +0 m
42 C.L. OF DISCHARGE 3 m
43 SUMP DEPTH l1 m
44 PUMP LENGTH l2 m
45 WALL TOP TO DISCH. l3 m
46 WALL TOP TO LOW LIQUID LVL l 4 m
47 GRADE TO 1ST STG IMPL'R. l5 m
48 SUBMERGENCE REQ'D l6 m
49 SUMP DIAMETER DIMENSION d m
50
51 Remarks:
52
53
54
55
56
57

D R A
N
I 25-JUL 8
- 2 0 1
D
RINTE
HEN P
T ROLL
ED W 7 / 14
NCON
Job Code 0-7723
Owner's
17546Z-UN2-FM-MR-43PA401
Doc. No.
SONATRACH Contractor's
S-43-1358-101
Hassi Messaoud Upside North Project Doc. No.
MECHANICAL DATA SHEET FOR COMMON FLARE
KO DRUM PUMPS UN21-PA-43-401A/B
Sheet 8 of 14 Rev. 2
1 Note PRESSURE VESSEL DESIGN CODE REFERENCES Rev
2 THESE REFERENCES MUST BE LISTED BY THE MANUFACTURER
3 CASTING FACTORS USED IN DESIGN ( TABLE 4)
4 SOURCE OF MATERIAL PROPERTIES
5
6 WELDING AND REPAIRS
7 THESE REFERENCES MUST BE LISTED BY THE PURCHASER. (DEFAULT TO TABLE 11 IF NO PURCHASER PREFERENCE IS STATED)
8 ALTERNATE WELDING CODES AND STANDARDS
9 WELDING REQUIREMENT (APPLICABLE CODE OR STANDARD)
10 WELDER/OPERATOR QUALIFICATION
11 WELDING PROCEDURE QUALIFICATION
12 NON-PRESSURE RETAINING STRUCTURAL WELDING SUCH AS BASEPLATES OR SUPPORTS
13 MAGNETIC PARTICLE OR LIQUID PENETRANT EXAMINATION OF PLATE EDGES
14 POSTWELD HEAT TREATMENT
15 POSTWELD HEAT TREATMENT OF CASING FABRICATION WELDS
16
17 MATERIAL INSPECTION
18 THESE REFERENCES MUST BE LISTED BY THE PURCHASER DEFAULT TO TABLE 15
ALTERNATIVE MATERIAL INSPECTIONS AND ACCEPTANCE CRITERIA (SEE TABLE 15) (8.2.2.5)
19 TYPE OF INSPECTION METHOD FOR FABRICATIONS FOR CASTINGS
20 RADIOGRAPHY
21 ULTRASONIC INSPECTION
22 MAGNETIC PARTICLE INSPECTION
23 LIQUID PENETRANT INSPECTION
24 VISUAL INSPECTION (all surfaces)
25
26 REMARKS :
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63

D R A 64

N
I L 8
-
25-JU
2 0 1
D
RINTE
HEN P
T ROLL
ED W 8 / 14
NCON
Job Code 0-7723
Owner's
17546Z-UN2-FM-MR-43PA401
Doc. No.
SONATRACH Contractor's
S-43-1358-101
Hassi Messaoud Upside North Project Doc. No.
MECHANICAL DATA SHEET FOR COMMON FLARE
KO DRUM PUMPS UN21-PA-43-401A/B
Sheet 9 of 14 Rev. 2

1 Note 1. Pumps are both normally "off". Pumps should be able to operate simultaneously in parallel. Rev
2 One pump shall be on duty and start on 1st set point. Second pump starts when 2nd set point is reached.
3
4 2. For site data and utilities conditions, refer to S-00-1220-001, Basic Engineering Design Data.
5 Cooling water is not available at site.
6
7 3. Desert environment.
8
9 4. Pump fluid contains produced water with: Chlorides = 90,168 mg/L, dissolved O2 < 0.1 mg/L, HCO3 = 44 mg/L, dissolved CO2 = 304 mg/L.
10
11 5. Operating case:
12 Turndown is 30% of normal capacity
13 Normal capacity considers draining of liquid hold-up (HLL to LLL) in the Common Flare KO Drum (UN21-VD-43-401) within 30 min by 2 pumps
14 operating in parallel.
15 For rated flow, a margin of 10% over normal operating flow has been considered.
16
17 6. NPSHA has been calculated considering a height of 2.1 m from Common Flare KO Drum bottom TL at 3 m to pump suction nozzle elevation at 0.9 m.
18 NPSHA must exceed NPSHR by at least 1m from min. flow rate to rated flow rate.
19 NPSHA shall exceed NPSHR by 20% at the rated flow rate.
20 NPSHa shall be equal or higher than NPSHr throughout the entire curve.
21
22 7. Pump shut off pressure is estimated to be 120% of the rated differential head at maximum density.
23 Vendor to confirm maximum discharge pressure, based on maximum suction pressure, including test tolerances shall not exceed 33 barg.
24
25 8. Noise level shall comply with S-00-1244-001, Noise Control Philosophy
26
27 9. Vendor to reconfirm suitability of the material based on past experiences of similar application.
28 If higher grade material is required, vendor to explan reason for such selection.
29
30 10. Forged parts for capital materials are required, if possible . Capital materials refer to below listed parts: 1
31 a) Pump shaft
32 b) Pump casing
33 c) Volute
34 d) Impeller
35
36 11. Coupling guards shall be of a non-sparking material such as aluminum or brass.
37
38 12. Preliminary seal plan is Plan 53B Vendor to confirm suitability for the application based on past experiences. 1
39 Plan 53B seal shall include, as minimum, temperature transmitter on N2 charging line, accumulator, pressure transmitter 1
40 air cooled heat exchanger , drain and vent valve, and interconnecting piping. 1
41 Vertical pumps with mechanical seals shall be provided with a valved vent connection on the box or flush piping, located to
42 ensure fluid at the seal face before start-up.
43 Shaft sleeves (SS316 hardened) shall be provided under the mechanical seal.
44
45 13. Pumps are provided with automatic start-up. Driver shall be sized for end of curve operation considering maximum density.
46
47 14. Pump length to be advised by vendor considering requirement for NPSH margin.
48
49 15. Hydraulic power has been determined based on maximum density of liquid. 1
50
51 16. Suction pressure region shall be rated to maximum discharge pressure. 1
52
53
54
55
56
57
58

D R A
N
I 25-JUL 8
- 2 0 1
D
RINTE
HEN P
T ROLL
ED W 9 / 14
NCON
Job Code 0-7723
Owner's
17546Z-UN2-FM-MR-43PA401
Doc. No.
SONATRACH Contractor's
S-43-1358-101
Hassi Messaoud Upside North Project Doc. No.
MECHANICAL DATA SHEET FOR COMMON FLARE
Sheet 10 of 14 Rev. 2
KO DRUM PUMPS UN21-PA-43-401A/B
MECHANICAL SEAL DATASHEET Corporate Name and Site: SONATRACH
FOR CENTRIFUGAL & ROTARY PUMPS Job or Project Reference: HASSI MESSAOUD UPSIDE NORTH PROJECT
SI UNITS / PAGE 1 OF 2 (1 bar = 0.1 MPa) Item No. / Service Name: UN21-PA-43-401A/B / COMMON FLARE KO DRUM PUMPS
Data to be completed by: Project Phase: INQUIRY PROPOSAL CONTRACT
Purchaser Identification Number:
Seal Vendor Other Identification:
Purchaser or Seal Vendor Date / Revision Number: / / /
Optional Features By:
1 SEAL SPECIFICATION (Note 12) SEAL MATERIALS FLUID DATA (Pumped Stream, Flush Fluid)
2 Seal Code (Annex D) Secondary Seals (6.1.6.5) Pumped Stream
3 By Vendor FKM inner / outer seal type or name
4 Vendor's Seal Code sprial-wound gasket & concentration (%)
5 FFKM dissolved contaminent
6 Vendor's Seal Drawing No. NBR H2S ml/m3
7 specify: wet
8 Vendor other @ inner seal Cl2 ml/m3
9 Category 1 (4.1.2) other @ outer seal other, specify
10 Category 2 Seal Faces (6.1.6.2) ml/m3
11 Category 3 Carbon / SiC inner / outer seal solid contaminent
12 Arrangement 1 (4.1.4) piping plans: SiC / SiC concentration (mass fraction)
13 1CW-FX (Cat. 1) 01, 02, 03, 11, 13, SSiC pumping temperature
14 1CW-FL (Cat. 2&3) 14, 21, 22, 23, 31, RBSiC normal °C
15 1CW-FL (Cat. 1) 32, 41, 51, 62, 65A specify: max. °C
16 segm. carb. bush. 65B, 66A, 66B, 99 other @ inner seal min. °C
17 (Cat. 2&3) (7.1.2.1) other @ outer seal specific gravity at indicated temperature
18 Arrangement 2 (4.1.4) piping plans: Metal Bellows (6.1.6.6) @ normal temp. kg/m3
19 2CW-CW (liquid) 01, 02, 03, 11, 13, UNS N10276 (Type B) inner / outer seal @ max. temp. kg/m3
20 2CW-CS (gas) 14, 21, 22, 23, 31, UNS N07718 (Type C) absolute vapor pressure at ref. temperature
21 2NC-CS (gas) 32, 41, 52, 55, 61, UNS N07718 (Type B) normal temp. bar
22 fix carbon throttle 62, 66A, 66B, 71, UNS N08020 max. temp. bar
23 bushing (7.2.2.1) 72, 75, 76, 99 specify: atmosph. boiling point °C
24 Arrangement 3 (4.1.4) 53B piping plans: other @ inner seal viscosity @ norm. temp. Pa.s (s. line 14)
25 3CW-FB (liquid) 01, 02, 03, 11, 13, other @ outer seal hazardous
26 3CW-BB (liquid) 14, 21, 22, 23, 31, Springs (6.1.6.4) flammable
27 3CW-FF (liquid) 32, 53A, 53B, 53C UNS N10276 or N06455 (multiple springs) other, specify
28 flush connection 54, 61, 62, 66A, UNS S31600 or S31635 (single spring) fluid solid @ ambient
29 fix carbon throttle 66B, 74, 99 Metal Parts (6.1.6.3 & 6.1.6.7) solidifies @ temp. °C
30 bushing (7.3.2.2 / 7.3.2.1) UNS S31600 or S31635 pour point temp. °C
31 3NC-BB (gas) UNS N10276 solidifies under shear
32 3NC-FB (gas) UNS N08020 polymerizing agents
33 3NC-FB (gas) other, specify: name or type
34 Type A (4.1.3) inner / outer seal SEAL CHAMBER DATA polymerize @ temp. °C
35 stationary spring (6.1.1.2) ASME B73.1&2 (Category 1) plates out/decomposes
36 single spring (6.1.5.1) cylindrical @ conditions
37 Type B (4.1.3) tapered regulated for fugative
38 stationary bellows (6.1.1.2) API 610 (Category 2 & 3) or other emissions ml/m3
39 Type C (4.1.3) other, specify special pump cleaning
40 rotating bellows (6.1.1.3) bolt on seal chamber (6.1.6.8) procedures, specify
41 Piping Plans prod. - between seals - atm. fixed throat bush alternate process fluids
42 (Annex G) floating throat bush & concentration, spec.
43 Sleeve Shaft Drive seal chamber vent Flush Fluid (not required if same as pumped stream)
44 set screws heating/cooling jacket type or name
45 approval for (6.1.3.14) PUMP DATA & concentration (%)
46 ≥ 9 set screws Manufacturer seal vendor review
47 other, specify model fluid temperature:
48 SEAL PERFORMANCE DATA frame/size normal °C
49 Sealing Pressure Rating Case Material max. °C
50 dynamic bar(ga) (3.1.27) Suction Press. (rated) bar (ga) min. °C
51 static bar(ga) (3.1.84) Discharge Pressure bar (ga) specific gravity at indicated temperature
52 Arr. 3: continous operation @ abnormal barrier Seal Chamber Pressure @ normal temp. kg/m3
53 pressure conditions [7.3.1.2 d)] normal bar (ga) @ max. temp. kg/m3
54 Temperature minimum bar (ga) absolute vapor pressure at ref. temperature
55 max. allowable °C (3.1.51) maximum bar (ga) normal temp. bar
56 min. metal design °C (6.1.6.11.1) static bar (ga) max. temp. bar
57 Additional Data for Category 3 Shaft Details atmosph. boiling point °C
58 generated heat, normal kW diameter mm viscosity @ norm. temp. Pa.s (s. line 48)
59 heat soak, normal kW speed r/min flow rate req'd max. l/min
60 axial thrust on shaft N horizontal min. l/min
61 Test of Seal by Pump Manufacturer (10.3.6) vertical pressure req'd max. bar (ga)

D R A 62 modified seal faces specify faces or seal CW rotation


respective to driver
min. bar (ga)

N
I 5-JUL 8
2
- 2 0 1 63 alternative seal

D
on page 2 line 54, 55 CCW rotation

RINTE
HEN P
T ROLL
ED W 10 / 14
NCON
Job Code 0-7723
Owner's
17546Z-UN2-FM-MR-43PA401
Doc. No.
SONATRACH Contractor's
S-43-1358-101
Hassi Messaoud Upside North Project Doc. No.
MECHANICAL DATA SHEET FOR COMMON FLARE KO
DRUM PUMPS UN21-PA-43-401A/B
Sheet 11 of 14 Rev. 2
MECHANICAL SEAL DATASHEET Corporate Name and Site: SONATRACH
FOR CENTRIFUGAL & ROTARY PUMPS Job or Project Reference: HASSI MESSAOUD UPSIDE NORTH PROJECT
SI UNITS / PAGE 2 OF 2 (1 bar = 0.1 MPa) Item No. / Service Name: UN21-PA-43-401A/B / COMMON FLARE KO DRUM PUMPS
Data to be completed by: Project Phase: INQUIRY PROPOSAL CONTRACT
Purchaser Identification Number:
Seal Vendor Other Identification:
Purchaser or Seal Vendor Date / Revision Number: / / /
Optional Features By:
1 FLUID DATA (Quench, Buffer, Barrier) SEAL AUXILIARY SYSTEM (Connection Lines, Components, Instrumentation )
2 Quench Fluid (plan 51, 62) General Barrier & Buffer Reservoirs (plan 52, 53A)
3 type or name joint user/vendor layout (8.1.3) supplier/ref. code
4 supply temp. max. °C supplier connect. lines dimensions standard
5 min. °C support/stand By Vendor (8.3.6.2.7) alternative
6 flow rate req'd max. l/min design limits of attached pressure casing (pump) other
7 min. l/min MAWP bar (ga) capacity 12 l d(shaft) ≤ 60 mm
8 Buffer & Barrier Fluid (liquid/gas) max. allow. temp. °C (8.1.4) [8.3.6.2.5 a)] 20 l d(shaft) > 60 mm
9 type or name design limits of seal aux. system (Category 1/2/3) other l
10 selection: purchaser MAWP if >20/40 bar bar (ga) height - seal gland/NLL m (8.3.6.2.2)
11 selection: seal vendor max. allow. temp. °C ASME B31.3 (8.3.6.2.8)
12 review: purchaser comment ASME code stamp
13 review: seal vendor optional components Bladder Accumulator (plan 53B)
14 flow rate req'd max. l/min press. relief valve MAWP pump casing > supplier/ref. code
15 min. l/min in suct. piping of pump MAWP aux. system nomin. size 20 l d(shaft) ≤ 60 mm
16 cooling/heating (+/-) kW therm. relief valves (9.8.3) 35 l d(shaft) > 60 mm
17 supply pressure (< seal ch. press. for plan 52,55,72) ext. circul. pump (8.3.7) plan 23,52,53 designed l (Table 9)
18 max. bar (ga) utility manifold conn. (8.2.24) Piston Accumulator (plan 53C)
19 min. bar (ga) restr. orifice nipple (8.3.5.4) in flush line supplier/ref. code
20 fluid operating normal °C (only liquid) other, specify pressure ratio
21 temperature max. °C special requirements barrier liquid volume (8.3.6.4.2)
22 min. °C special alloys min/max 0.2 / 2.8 l d(shaft) ≤ 60 mm
23 specific gravity at indicated temperature hazardous service min/max 0.35/5.1 l d(shaft) > 60 mm
24 @ normal temp. kg/m3 other, specify External Seal Flush Systems (plan 54 and 55)
25 @ max. temp. kg/m3 system hold up period days plan 52,53 supplier/ref. code
26 absolute vapor pressure at ref. temperature filling system (8.1.9.5) Collect. Reservoir for liquid leakage (plan 65, 75)
27 @ normal temp. bar hot surfaces insulation supplier/ref. code
28 @ max. temp. bar protection Barrier/Buffer Gas Supply System (plan 72, 74)
29 atmosph. boiling point °C pipe taper threads (8.2.13) supplier/ref. code
30 viscosity @ norm. temp. Pa.s ASME B1.20.1 press. control valves (9.9)
31 specific heat capacity @ constant pressure for ISO 7 press. amplifier (9.10)
32 liquid @ normal temp. J/kg.K Connection Lines INSTRUMENTATION As per S-00-1370-001 / 003
33 SITE & UTILITIES As per S-00-1220-001 tubing (8.2.8, Table 6) design temp. > 100 °C °C (9.1.7)
34 control voltage V piping (8.2.9, Table 5) IEC 604529,dsgn. IP65
(9.1.2)
35 frequency Hertz schedule NEMA 250,encl. Type 4
36 phase size 12 mm d(shaft) ≤ 60 mm Units (press.,temp.,level,flow)
37 electrical area CL 20 mm d(shaft) > 60 mm Temp. Indicator f. p. plan
38 GR other mm bi-metalic option for piping
(9.2.1)
39 DIV heat tracing (8.2.23) liquid filled plan 32, 53B, 53C

40 ambient temp. max. °C Cooler (plan 21, 22, 23, 41, 53B, 53C) Pressure-Instruments
(Design)
41 min. °C supplier/ref. code gauges for piping plan
42 cooling water Not Available ASME B31.3 (8.3.2.1.2) oil filled gauges (9.4.3)
43 other cooling liquid water cooler (8.3.2.2) transmitter for p. plan
44 supply temperature °C pipe, galvanized CS (8.2.21) switches for p. plan
45 flow rate l/min air cooler if required set press. min. bar (ga)
46 Cl2 content ml/m3 natural air draft (8.3.2.3.1) max. bar (ga)
47 pressure normal bar (ga) forced air draft (8.3.2.3.2) Level-Instruments (plan 52, 53A, 75)
48 design bar (ga) w. high temp. alarm rfl. indicator weld pad (9.6.1)
49 ATEX group Cyclone Separator removable (9.6.2)
EC Directive
50 cat. 94/9/EC
supplier/ref. code transmitter hydrostatic (9.5.3)
51 T class capacit.
52 INSPECTION & TESTING ultrasonic
53 Test at Pump Manufacturer - Seal Specific. Welded Designs switches (9.5.1.8)
54 modified seal faces purchaser approval for (6.1.6.10.5) set points high
55 alternative seal welded connections low
56 Miscelaneous 100% inspection of (6.1.6.10.5) Flow-Instruments
57 opt. seal qual. testing (10.3.2.1.2) all welds, method: flow indicator f. p. plan
58 hardness test, for magnetic particle e.g. in cooling water outlet line (8.2.22) or plan 32
59 purchaser participation liquid penetrant flow meter for p. plan
60 inspector's checklist (Annex H) radiographic transmitter for p. plan
61 ultrasonic switches for p. plan

DR01A NOTES purchaser


62

IN
25-JU
L-2
8 63

RINTE
D
seal vendor

HEN P
T ROLL
ED W 11 / 14
NCON
Job Code 0-7723
Owner's
Doc. No.
17546Z-UN2-FM-MR-43PA401

SONATRACH Contractor's
Hassi Messaoud Upside North Project Doc. No.
S-43-1358-101

MECHANICAL DATA SHEET FOR COMMON FLARE


Sheet 12 of 14 Rev. 2
KO DRUM PUMPS UN21-PA-43-401A/B
UN21-PZ-43-401A/B: COMMON FLARE KO DRUM PUMPS
Rev. GENERAL
1 Motor Tag No : UN21-PM-43-401A/B Quantity: 2 Material Requisition: R-2158-101
2 Service COMMON FLARE KO DRUM PUMPS MOTOR Referenced standard: IEC 60034 Project Specification: S-00-1381-019 / S-00-1382-100
3 Supplier TBD Manufacturer B
SITE DATA
4 Installation (Indoor/Outdoor) / Ambient Type Outdoor Corrosive/Chemical/Dust/Sandstorm
5 Air Design Temperature Max: +55ºC Min: -5ºC
6 Max. Design Temperature Exposed: 90ºC Shaded: 55ºC
8 Altitude a.s.l.: Ranging from 130 to 170 m
9 Relative Humidity at 40ºC Max: 50 % Min: 20 %
10 Special conditions Tropicalization
11 Area Classification (Acc. To IEC Standards) Zone 2
12 ATEX Marking Required
13 Certifying authority / certificate Nr B B
14 Design Life 30 years
DRIVEN MACHINE DATA
14 Manufacturer / Machine Type B B
15 Item / Model B B
16 ABS Power RTD / MAX (kW) / Speed (rpm) B B B
17 Coupling type Dry Flexible coupling (Diaphram or Disk pack)
18 Drive System / Ratio B B
19 Req. Torque RTD / MAX / Breakaway (N*m) B B B
20 Inertia (MR2)(Kg*m2) / Thrust Load (N) B B
21 Moment of inertia of driven machine (Jdm) (kgm2) B
22 Moment of Inertia of driven machine at motor shaft (Jdm) (Kg*m2) B
23 Inertia constant of complete system (H) (second) B
24 Gear Ratio of gear box (output / input) (p.u.) B
MOUNTING DETAILS
Required by Company Vendor Data
25 Mounting (Vertical / Horizontal / Foot /Flange / Skirt / other) B
26 Slide rails (Y / N) B
27 Overall dimensions, to end of shaft L x W x H complete (mm) B
28 Shaft Type (Single end / Double end / Extended) B
29 Shaft end-float (+/- mm) B
30 Shaft end play (mm) B
31 Rotor air gap (mm) B
32 Rotor polar moment of inertia GD2 (kgm2) B
33 Rotor only weight (kg) B
34 Motor complete weight (kg) B
35 Heat exchanger weight (kg) B
BEARING DETAILS
Required by Company Vendor Data
36 Bearing type non-drive end (Ball / Roller / Sleeve) B
37 Bearing type drive end (Ball / Roller / Sleeve) B
38 Bearing manufacturer non-drive end B
39 Bearing manufacturer drive end B
40 Bearing reference Nº non-drive end B
41 Bearing reference Nº drive end B
42 Bearing PT 100-4W resistance temp. detectors required (Y / N) Y B
43 Vibration detectors required, 2 per bearing (Y / N) B
44 Insulated bearing required (Y / N) B
45 Lubrication oil (Forced / Ring / Grease / other) B
46 Lubrication interval min 2000 hrs B
47 Forced lubrication oil pressure (bar) B
48 Forced lubrication oil flow rate (m3 hour) B
49 Bearing oil inlet temperature (ºC) B
50 Bearing oil outlet temperature (ºC) B

D R A
N
I 25-JUL 8
- 2 0 1
D
RINTE
HEN P
T ROLL
ED W 12 / 14
NCON
Job Code 0-7723
Owner's
Doc. No.
17546Z-UN2-FM-MR-43PA401

SONATRACH Contractor's
Hassi Messaoud Upside North Project Doc. No.
S-43-1358-101

MECHANICAL DATA SHEET FOR COMMON FLARE


Sheet 13 of 14 Rev. 2
KO DRUM PUMPS UN21-PA-43-401A/B
UN21-PZ-43-401A/B: COMMON FLARE KO DRUM PUMPS
MOTOR DESIGN PARAMETERS
Rev. Required by Company Vendor Data
51 Rated Output B
52 Number of Poles B
53 Voltage 5500 V ± 5 % B
54 Frequency 50 ± 2 % B
55 Phases 3 B
56 Rated short time withstand in main terminal box (kA/second) B
57 System Neutral Through high resistance in transformer B
58 Direction of Rotation looking at non-drive-end (CW / CCW) B
59 Winding connection (Star / Delta) Star B
60 Enclosure protection degree IP 55 B
61 Shock protection IK08 B
63 Protection Ex(n), Ex(d), Ex(e), Ex(p): Motor frame Eex-d B
64 Painting (Applicable standards/color) S-00-13A0-001 B
65 Efficiency 96 % min. B
66 Explosion hazardous area (Non-hazardous / Zone 2 / Zone 1) Zone 2 B
67 Gas group (IIA, IIB, IIC,…) IIA B
68 Temperature class (T2 / T3 / T4 / T5 / T6 / Other) T3 B
69 Stator cooling (TEFC / CACA / other) TBD B
79 Lowest motor voltage at starting 80 % B
80 Nb of consecutive starts within 1 hour Cold: 3 Hot: 2 Cold: B Hot: B
81 Vibration Limit Class A B
82 Noise Level at 1m 82 dB(A) max. B
83 Maximum starting Current ( % Full load Current) 500 max. B
ELECTRICAL CIRCUIT PARAMETERS
84 Base impedance Zbase (ohms) B
85 Magnetising reactace Xm (p.u.) B
86 Core loss resistance Rc (p.u.) B
87 Stator leakage reactance at standstill X11 (p.u.) B
88 Stator leakage reactance at full-load X10 (p.u.) B
89 Stator resistance at 20 ºC R1 (ohms) B
90 Stator resistance at 20 ºC R1 (p.u.) B
91 Rotor leakage resistance at standstill X21 (p.u.) B
92 Rotor leakage reactance at full-load X20 (p.u.) B
93 Rotor resistance at 20 ºC R20 (ohms) B
94 Rotor resistance at 20 ºC R20 (p.u.) B
95 Negative sequence reactance X2 (p.u.) B
96 Zero sequence reactance X0 (p.u.) B
97 Zero sequence resistance R0 (p.u.) B
98 Full Load Speed B
99 Full Load Current/Locked Rotor Current B
100 No load current B
101 Starting Time (100% of Voltage) at full load B
102 Starting Time (80% of Voltage) at full load B
103 Allowable Locked Rotor Withstand Time B
104 Thermal Time Constant B
105 Efficiency ( at 100%, 75% & 50% load) 100%: B 75%: B 50%: B
106 Power Factor ( at 100%, 75% & 50% load) 100%: B 75%: B 50%: B
107 Locked Rotor Power Factor B
108 Full load Torque B
109 Locked/Pull Up/Breakdown Torque B B B
110 Open circuit time constant B
111 Material of frame / rotor / internal or external Fan B B B
THERMAL PARAMETERS AND RELATED DATA
Required by Company Vendor Data
112 Duty to IEC 60034 Part 1 S1 B
113 Starting duty B
114 Method of starting (DOL / VSDS / other) DOL B
115 Run-up or starting time (sec.) B
116 Thermal rating time te (sec.) B
117 Safe stallling time hot (sec.) B
118 Safe stalling time cold (sec.) B
119 Thermal time constandt (τ) (sec.) B
120 Insulation Class to IEC 60085 F B
121 Temperature rise to IEC 60085 80 B B
122 Temperature rise to IEC 60085 (ºK) 80 ºK B
123 Motor withstand overload for 1 hour 110% B

D R A
N
I 25-JUL 8
- 2 0 1
D
RINTE
HEN P
T ROLL
ED W 13 / 14
NCON
Job Code 0-7723
Owner's
Doc. No.
17546Z-UN2-FM-MR-43PA401

SONATRACH Contractor's
Hassi Messaoud Upside North Project Doc. No.
S-43-1358-101

MECHANICAL DATA SHEET FOR COMMON FLARE


Sheet 14 of 14 Rev. 2
KO DRUM PUMPS UN21-PA-43-401A/B
UN21-PZ-43-401A/B: COMMON FLARE KO DRUM PUMPS
MAIN TERMINAL BOX/POWER JUNCTION BOX
Rev. Required by Company Vendor Data
124 Main terminal boxes, quantity (1/2) B
125 Main terminal boxes, segregated (Y/N) B
126 Protection degree IP 65 B
127 Protection Ex(n), Ex(d), Ex(e), Ex(p) EEx-e B
128 Location of Main terminal box B
129 Main terminal box MULTI-DIRECTIONAL B
130 Cable Entry BOTTOM B
131 Cable Type and Size on main terminal box B
132 DIA. EXT. B
133 Cable Gland TBD B
AUXILIARY TERMINAL BOX/AUXILIARY JUNCTION BOX
Required by Company Vendor Data
Winding Bearing Vibrat. Winding Bearing Vibrat.
Heater Differ CT´s Heater Differ CT´s
Temp Temp Detec. Temp Temp Detec.
134 Protection degree IP65 IP65 IP65 IP65 IP65 B B B B B
135 Protection Ex(n), Ex(d), Ex(e) EEx-e EEx-e EEx-e EEx-e EEx-e B B B B B
136 Location of Aux. terminal box B B B B B
137 Aux. terminal box MUL-DIREC. MUL-DIREC. MUL-DIREC. MUL-DIREC. MUL-DIREC. B B B B B
138 Cable Entry BOTTOM BOTTOM BOTTOM BOTTOM BOTTOM B B B B B
139 Cable Type and Size on aux. terminal box B B B B B
140 DIA. EXT. B B B B B
141 Cable Gland Type TBD TBD TBD TBD TBD B B B B B
EARTHING/GROUNDING
142 Grounding terminal inside terminal boxes Required B
143 Grounding tap on frame Required B
ACCESSORIES
Required by Company Vendor Data
144 Winding temperature detectors Required
145 Type / Quantity PT 100 / 6 (two per winding) B
146 Set for alarm / shut down B
147 Bearing temperature detectors Required
148 Type / Quantity PT 100 / 2 (per bearing) B
149 Set for alarm / shut down B
150 Vibration detector Not required
151 Type / Quantity
152 Set for alarm / shut down
153 CT for differential protection Not required
154 Type / Ratio / Qty
155 Supplied by
156 Anticond. heaters (Nb / power / voltage) Required B
157 Maximum sheath temperature 200ºC B
158 Drain plug Provided B
NOTES
159 1) Fields with letter "B" are to be filled by Manufacturer.
160 2) Accesories (bearings, vibration devices, other) shall comply with requirements of MV Motors Technical Specification S-00-1382-100
161 3) TBD: To be Defined on detailed engineering project

D R A
N
I 25-JUL 8
- 2 0 1
D
RINTE
HEN P
T ROLL
ED W 14 / 14
NCON