Professional Documents
Culture Documents
Screen Bonding
Mitton Consulting Limited
Overview
Introduction
Cable screens, induced voltages and currents in the screen
Three core cable
Single core cable
Different bonding methods for single core cables
Solidly bonded single-core cable system
Specially bonded single-core cable systems
Single-point-bonding system
Split single-point-bonding system
Cross-bonding system
If the cable screen is bonded at both ends, the mmf will cause a
circulating current to flow if there is electrical continuity.
Induced voltages from three phases sum to zero along the entire length of the
cable
Cable screen should be earthed at both ends
Cross-bonding system
R R
Y Y
B B
0V Length
R R
Y Y
B B
0V
Mitton Consulting Limited
Solidly bonded single-core cable
system
Advantages
Minimum material required - most economical if heating is not an issue
Provides path for fault current, minimizing earth return current and
EGVR at cable destination
Does not require screen voltage limiter (SVL)
Less electromagnetic radiation
Disadvantages
Provides path for circulating current
Heating effects in cable screen, greater losses
Cable therefore might need to be de-rated or larger cable required
Transfers voltages between sites when there is an EGVR at one site
Can lay cables in trefoil formation to reduce screen losses
Normally applies to short cable section of tens of metres long
Circulating current is proportional to the length of the cable and the
magnitude of the load current
Mitton Consulting Limited
Single-point-bonded system
Cable screen solidly earthed at one end only
Open circuit in cable screen, no circulating current
Zero volt at the earthed end, standing voltage at the unearthed end
Optional PVC insulated earth continuity conductor required to provide path for fault
current, if returning from earth is undesirable, such as in a coal mine
SVL installed at the unearthed end to protect the cable insulation during fault
conditions
Transposition of earth continuity conductor at the mid point of the section
Reduce circulating current in the continuity conductor
R R
Y Y
SVL installed at
unearthed end
B B
Earth continuity
conductor Mitton Consulting Limited
Single-point-bonded system
Induced voltage proportional to the length of the cable and the current carried in the cable
Zero volt with respect to the earth grid voltage at the earthed end, standing voltage at the unearthed end
No circulating current in the screen
Circulating current in the earth-continuity conductor is not significant, as magnetic field from phases are
partially balanced
The magnitude of the standing voltage is depended on the magnitude of the current flows in the core,
much higher if there is an earth fault
0V Length
R R
Y Y
B B
R R
Y Y
B B
0V Length
R R
Y Y
B B
R R
Earthing
resistance not Y Y
shown in the plot
B B
Major section
Minor section Minor section Minor section
Mitton Consulting Limited
Cross-bonded cable system
what if cable cores not transposed
Other than cross-bonding the screen, why transpose
the cables core?
If core not transposed, not well neutralised resulting in some
circulating currents
Cable should be transposed and the screen needs to be cross
bonded at each sectionalising joint position for optimal
neutralisation
Inner screen,
smaller induced
voltage
R R
Earthing Y Y
resistance not
shown in the plot
B B
R R
Y Y
B B
Joints with
sectionalising
insulation Joints with
Lockable link box sectionalising
insulation
Earthing Cross bonding
resistance is not
connections Screen voltage
shown in the plot
limiter
Length
Major section
R R
Earthing
resistance is not
shown in the plot
Y Y
B B
Section 3 Section 2
Section 1
XLPE cable
Rated Voltage 10-70 kV
Copper Conductor 65o C
25 or 35 mm2 screen
Flat formation, one group only
Laying depth 1.0m
Distance between cable 70mm
Ground temperature 20o C
Ground thermal resistivity 1.0 km/W
1m 1m
0.150m
0.015m
0.017 m
30
GRND_Rscreen: Bus/Line 4.
GRND_Rscreen: Bus/Line 4.
GRND_Yscreen: Bus/Line 5.
GRND_Yscreen: Bus/Line 5.
0.60 GRND_Bscreen: Bus/Line 6.
GRND_Bscreen: Bus/Line 6.
Section Current Magnitude (Amps)
Shunt Potential Magnitude (Volts)
20
0.45
0.30
10
0.15
0
0.00
0 15 30 45 60
0 15 30 45 60 RunID:Flat 2 Point Term.:Source
RunID:Flat 2 Point Term.:Source
0.15 10
0.10
0.05
0.00 0
0 15 30 45 60 0 15 30 45 60
RunID:trefoil 2 Po Term.:Source
RunID:trefoil 2 Po Term.:Source
20 2.0
GRND_Rscreen: Bus/Line 4. GRND_Rscreen: Bus/Line 4.
GRND_Yscreen: Bus/Line 5. GRND_Yscreen: Bus/Line 5.
This voltage GRND_Bscreen: Bus/Line 6.
GRND_Earth : Bus/Line 7.
GRND_Bscreen: Bus/Line 6.
GRND_Earth : Bus/Line 7.
Section Current Magnitude (Amps)
depends on
Shunt Potential Magnitude (Volts)
15 1.5
the capacity
current and
the 10 1.0
resistance of
the earth grid
5 0.5
0 0.0
0 15 30 45 60 0 15 30 45 60
RunID:Flat 1 Point Term.:Source RunID:Flat 1 Point Term.:Source
6000
GRND_Rscreen: Bus/Line 4.
GRND_Yscreen: Bus/Line 5.
GRND_Bscreen: Bus/Line 6.
Shunt Potential Magnitude (Volts)
4500
3000
1500
0
0 15 30 45 60
RunID:Flat 1 Point Term.:Source
Section Number
Mitton Consulting Limited
Single-point-bonding system
fault condition –low EGVR at source
1000 A actual fault current, 0.05Ω earth grid at the source site
Screen only bonded at the source
The voltage at the screen is dominated by the induced voltage
Approximately 700 V/km
800
Rscreen : Bus/Line 4.
Yscreen : Bus/Line 5.
Bscreen : Bus/Line 6.
Shunt Potential Magnitude (Volts)
600
This voltage
400
depends on the
resistance of the
earth grid and the
200 actual fault current
0
0 15 30 45 60
RunID:Flat 1 Point Term.:Source
Section Number
6.0
GRND_Rscreen: Bus/Line 4.
GRND_Yscreen: Bus/Line 5.
GRND_Bscreen: Bus/Line 6.
Shunt Potential Magnitude (Volts)
4.5
3.0
1.5
0.0
0 50 100 150 200
RunID:Flat 2 Point Term.:Source
Section Number
Mitton Consulting Limited
Cross-bonding cable system
cable core not transposed
Asymmetric voltage profile along the screens as expected
0.7 V appears at the termination joints, with respect to remote earth
Approximately 0.5 A circulating current
Cable core should be transposed to eliminate imbalance
Induced voltage on
outer cable screen
GRND_Rscreen: Bus/Line 4.
GRND_Yscreen: Bus/Line 5.
This voltage 6.0 GRND_Bscreen: Bus/Line 6.
depends on
Shunt Potential Magnitude (Volts)
the current
4.5
imbalance and
the resistance
of the earth 3.0
Induced voltage on
grid middle cable screen
1.5
0.0
0 50 100 150 200
RunID:Flat 2 Point Term.:Source
Section Number