You are on page 1of 46

Introduction 1

Description 2

Installation 3

Connection 4

Commissioning 5

Service and maintenance 6


Equipment Manual

Technical specifications 7

Appendix A

05/2020
L1V30408520AG-03
Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are
graded according to the degree of danger.

DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.

WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.

CAUTION
indicates that minor personal injury can result if proper precautions are not taken.

NOTICE
indicates that property damage can result if proper precautions are not taken.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will
be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to
property damage.
Qualified Personnel
The product/system described in this documentation may be operated only by personnel qualified for the specific
task in accordance with the relevant documentation, in particular its warning notices and safety instructions.
Qualified personnel are those who, based on their training and experience, are capable of identifying risks and
avoiding potential hazards when working with these products/systems.
Proper use of Siemens products
Note the following:

WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
documentation. If products and components from other manufacturers are used, these must be recommended
or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and
maintenance are required to ensure that the products operate safely and without any problems. The permissible
ambient conditions must be complied with. The information in the relevant documentation must be observed.

Trademarks
All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication
may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software
described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the
information in this publication is reviewed regularly and any necessary corrections are included in subsequent
editions.

Siemens AG Copyright © Siemens AG 2017.


Smart Infrastructure Ⓟ 02/2021 Subject to change All rights reserved
Electrical Products
Postfach 10 09 53
93009 Regensburg
GERMANY
Table of contents

1 Introduction ........................................................................................................................................... 5
1.1 Scope of delivery ................................................................................................................. 5
1.2 Latest information ............................................................................................................... 5
1.3 Security information ............................................................................................................ 6
1.4 Open Source Software ......................................................................................................... 7
2 Description............................................................................................................................................. 9
2.1 Area of application............................................................................................................... 9
2.2 Performance features of the I(N), I(Diff), analog module ...................................................... 9
2.3 Design ............................................................................................................................... 11
3 Installation ........................................................................................................................................... 13
3.1 Installation location ........................................................................................................... 13
3.2 Installation steps................................................................................................................ 14
4 Connection .......................................................................................................................................... 15
4.1 Safety information ............................................................................................................. 15
4.2 Connections ...................................................................................................................... 16
5 Commissioning .................................................................................................................................... 25
5.1 Overview ........................................................................................................................... 25
5.2 Setting the expansion module parameters ......................................................................... 26
5.3 Parameterizing with powerconfig....................................................................................... 29
5.4 Reading out measured values............................................................................................. 30
6 Service and maintenance .................................................................................................................... 31
6.1 Calibration ......................................................................................................................... 31
6.2 Firmware update ............................................................................................................... 31
6.3 Troubleshooting guide ....................................................................................................... 31
6.4 Warranty ........................................................................................................................... 32
7 Technical specifications....................................................................................................................... 33
A Appendix ............................................................................................................................................. 37
A.1 Modbus measured quantities with function codes 0x03 and 0x04 ...................................... 37
A.2 Average value quantities .................................................................................................... 37
Index .................................................................................................................................................... 41

Equipment Manual, 05/2020, L1V30408520AG-03 3


Table of contents

4 Equipment Manual, 05/2020, L1V30408520AG-03


Introduction 1
1.1 Scope of delivery
Included in package:
• 1 x 7KM PAC expansion module I(N), I(Diff), analog
• 1 x operating instructions

1.2 Latest information

Up-to-the-minute information
You can find further support on the Internet:
Website (https://support.industry.siemens.com/my/ww/en/requests)

General safety information

DANGER
Hazardous voltage
Will cause death or serious injury.
Turn off and lock out all power supplying this equipment before working on this device.

Note
Only qualified personnel are allowed to install, commission or service this device.
• Wear the prescribed protective clothing.
• Observe the general equipment regulations and safety regulations for working on high-
voltage installations (e.g. DIN VDE, NFPA 70E) as well as national or international
regulations.
• Check that all connections are correctly made before startup.
• Before power is applied to the device for the first time, it must have been located in the
operating area for at least two hours in order to reach temperature balance and avoid
humidity and condensation.
• The limits given in the technical data must not be exceeded even during commissioning or
testing.
• Condensation on the device is not permissible during operation.

Equipment Manual, 05/2020, L1V30408520AG-03 5


Introduction
1.3 Security information

Note
These operating instructions do not purport to cover all details or variations in equipment, or
to provide for every possible contingency in connection with installation, operation, or
maintenance. Should additional information be desired, or should particular problems arise
that are not handled in detail in the operating instructions, please contact Technical Support
for the information you require.

See also
Technical assistance (https://support.industry.siemens.com/My/ww/en/requests)
Industrial security (http://www.siemens.com/industrialsecurity)
Siemens Industrial Security RSS Feed (http://www.siemens.com/industrialsecurity)
www.opensource.org (https://opensource.org/)

1.3 Security information


Siemens provides products and solutions with industrial security functions that support the
secure operation of plants, systems, machines and networks.
In order to protect plants, systems, machines and networks against cyber threats, it is
necessary to implement – and continuously maintain – a holistic, state-of-the-art industrial
security concept. Siemens’ products and solutions constitute one element of such a concept.
Customers are responsible for preventing unauthorized access to their plants, systems,
machines and networks. Such systems, machines and components should only be connected
to an enterprise network or the Internet if and to the extent such a connection is necessary
and only when appropriate security measures (e.g. firewalls and/or network segmentation)
are in place.
For additional information on industrial security measures that may be implemented, please
visit (https://www.siemens.com/industrialsecurity).
Siemens’ products and solutions undergo continuous development to make them more
secure. Siemens strongly recommends that product updates are applied as soon as they are
available and that the latest product versions are used. Use of product versions that are no
longer supported, and failure to apply the latest updates may increase customer's exposure to
cyber threats.
To keep up to date with all the latest product updates, subscribe to the Siemens Industrial
Security RSS Feed at (https://www.siemens.com/industrialsecurity).

6 Equipment Manual, 05/2020, L1V30408520AG-03


Introduction
1.4 Open Source Software

1.4 Open Source Software


This product, solution or service ("Product") contains third-party software components. These
components are Open Source Software licensed under a license approved by the Open
Source Initiative (https://www.opensource.org) or similar licenses as determined by SIEMENS
("OSS") and/or commercial or freeware software components. With respect to the OSS
components, the applicable OSS license conditions prevail over any other terms and
conditions covering the Product. The OSS portions of this Product are provided royalty-free
and can be used at no charge.
If SIEMENS has combined or linked certain components of the Product with/to OSS
components licensed under the GNU LGPL version 2 or later as per the definition of the
applicable license, and if use of the corresponding object file is not unrestricted ("LGPL
Licensed Module", whereas the LGPL Licensed Module and the components that the LGPL
Licensed Module is combined with or linked to is the "Combined Product"), the following
additional rights apply, if the relevant LGPL license criteria are met: (i) you are entitled to
modify the Combined Product for your own use, including but not limited to the right to
modify the Combined Product to relink modified versions of the LGPL Licensed Module, and
(ii) you may reverse-engineer the Combined Product, but only to debug your modifications.
The modification right does not include the right to distribute such modifications and you
shall maintain in confidence any information resulting from such reverse-engineering of a
Combined Product.
Certain OSS licenses require SIEMENS to make source code available, for example, the GNU
General Public License, the GNU Lesser General Public License and the Mozilla Public License.
If such licenses are applicable and this Product is not shipped with the required source code, a
copy of this source code can be obtained by anyone in receipt of this information during the
period required by the applicable OSS licenses by contacting the following address:
Siemens AG
Smart Infrastructure
Electrical Products
Technical Support
Postfach 10 09 53
93009 Regensburg
Germany
You will find Technical Support under (https://www.siemens.com/support-request).
Keyword: Open Source Request (please specify Product name and version, if applicable)
SIEMENS may charge a handling fee of up to 5 EUR to fulfil the request.
Warranty regarding further use of the Open Source Software
SIEMENS' warranty obligations are set forth in your agreement with SIEMENS. SIEMENS does
not provide any warranty or technical support for this Product or any OSS components
contained in it if they are modified or used in any manner not specified by SIEMENS. The
license conditions may contain disclaimers that apply between you and the respective
licensor. For the avoidance of doubt, SIEMENS does not make any warranty commitment on
behalf of or binding upon any third-party licensor. The Open Source Software used in the
product and the license agreements concerning this software can be found in the
Readme_OSS.

Equipment Manual, 05/2020, L1V30408520AG-03 7


Description 2
2.1 Area of application
The expansion module has been designed for use in combination with the 7KM PAC devices.
The guidelines for the 7KM PAC devices also apply to the expansion module.
When used in conjunction with 7KN POWERCENTER, powermanager and Cloud MindSphere,
expansion module I(N), I(Diff), analog makes it possible to monitor measured quantities, such
as
• Real neutral current
• Residual current and
• Analog measured values, e.g. temperature.
Although these measured quantities are generally not monitored during normal operation,
they can provide important information in the event of deviations or changes in a system if
they are evaluated appropriately.
Temporary changes can be converted into event messages by the limit monitoring system.
Persistent changes can be recorded in the form of a trend based on the aggregated values
and stored.
It is possible to record and forward event messages very easily using 7KN POWERCENTER,
powermanager and MindSphere, e.g. in the form of an email or long-term storage of trend
data.

2.2 Performance features of the I(N), I(Diff), analog module


Overview:
• Plug-in expansion module for SENTRON PAC measuring devices with expansion module
functionality, e.g. 7KM PAC3200 / PAC3220 / PAC4200
• Measurement of N-conductor (neutral) current via external current transformer. Direct
measurement via external current transformers is significantly more accurate than
calculated current values.
• Measurement of two residual and PE currents via external summation current transformer
• Measurement of physical quantities of any kind, such as
– Temperature
– Humidity
– Pressure
– Flow measurement is possible using an external 0/4 ... 20 mA transmitter.
• Display of measured values directly on the display of the PAC measuring device
When used in conjunction with the 7KM PAC3220 or 7KM PAC4200 measuring device,

Equipment Manual, 05/2020, L1V30408520AG-03 9


Description
2.2 Performance features of the I(N), I(Diff), analog module

limit values can be configured on the inputs of the expansion module I(N), I(Diff), analog.
In the event of a limit violation, a digital output of the PAC device can be switched in order
to output a status message.
• Status indication via LED
• When used in conjunction with a SENTRON 7KM PAC3220 or PAC4200 measuring device,
the averaging of all measured values is possible in two stages, which are independent of
each other and freely configurable (aggregation).
The associated Modbus table can be found in the Appendix (Page 37).
The expansion module I(N), I(Diff), analog increases the scope of measuring functions of the
SENTRON 7KM measuring devices.

*) N-conductor current measurement


**) Residual current measurement
- I > 0 mA, fault. ***) Residual current flowing across the grounded housing of the system.
- I = 0 A, no fault. The system is in order; no residual current is flowing.
****) Measurement of physical quantities

Figure 2-1 Examples of possible applications

10 Equipment Manual, 05/2020, L1V30408520AG-03


Description
2.3 Design

2.3 Design

(1) Screw terminals for connection of current transformer or sensor


(2) Screw for mounting the expansion module I(N), I(Diff), analog
(3) Ventilation slot
(4) Diagnostic LED

Figure 2-2 Schematic representation of expansion module I(N), I(Diff), analog

IN connection:
Current transformer connection for N-conductor current measurement 1 A / 5 A input

I5 connection:
• 0 ... 20 mA analog input
• 4 ... 20 mA analog input
• 0 ... 60 mA RCM (Residual Current Monitoring)

I6 connection:
• 0 ... 20 mA analog input
• 4 ... 20 mA analog input
• 0 ... 60 mA PE current RCM (Residual Current Monitoring)

Diagnostic LED:
The LED displays the module status:
• Green: OK
• Red: Not OK

Equipment Manual, 05/2020, L1V30408520AG-03 11


Description
2.3 Design

12 Equipment Manual, 05/2020, L1V30408520AG-03


Installation 3
3.1 Installation location

WARNING
Hazardous voltage
Using devices when they are damaged may result in death, serious injury, or property
damage.

The expansion module is inserted in the appropriate slot labeled "MOD1" or "MOD2" on the
rear panel of the SENTRON 7KM PAC measuring device.

Note
Only one expansion module of the type I(N), I(Diff), analog may be connected to the PAC
measuring device.

NOTICE
Condensation may cause the device to malfunction.
The device must be in the operating environment for at least two hours before use to
prevent condensation due to sudden temperature changes.

Equipment Manual, 05/2020, L1V30408520AG-03 13


Installation
3.2 Installation steps

3.2 Installation steps


Install the expansion module before staring up the SENTRON device.

NOTICE

Damaged components must not be operated.

CAUTION
Electrostatic discharge
The expansion modules contain electronic components that can be irreparably damaged by
electrostatic discharge.
When handling modules, make sure that all objects in the handling environment (persons,
workstation and packaging) are properly grounded. Do not touch the module contacts.

NOTICE
Overheating of the device
The expansion module can overheat if the ventilation slots are covered.
Overheating shortens the service life of the expansion module.
Ensure that the ventilation slots are not covered.

Figure 3-1 Installation of the expansion module I(N), I(Diff), analog

14 Equipment Manual, 05/2020, L1V30408520AG-03


Connection 4
4.1 Safety information

DANGER
Hazardous voltage.
Failure to observe this notice will cause death, serious injury or property damage.
Turn off and lock out all power supplying this equipment before working on this device.

WARNING

Some of the following tasks are carried out when hazardous voltage is present. For this
reason, they must only be carried out by qualified personnel who are familiar with and
follow the safety regulations and precautions.

Wear the prescribed protective clothing. Observe the general equipment regulations and
safety regulations for working on high-voltage installations (e.g. DIN VDE, NFPA 70E as well
as national or international regulations).

The limits given in the technical data must not be exceeded even during commissioning or
testing.

The secondary connections of intermediate current transformers must be short-circuited at


the transformers before the power supply lines to the device are interrupted.

The polarity and phase assignment of the instrument transformers must be tested. Before
connecting the device, you must check whether the system voltage matches the voltage
specified on the type plate.

Check that all connections are correctly made before startup.

Before power is applied to the device for the first time, it must have been located in the
operating area for at least two hours in order to reach temperature balance and avoid
humidity and condensation.

Condensation on the device is not permissible during operation.

Equipment Manual, 05/2020, L1V30408520AG-03 15


Connection
4.2 Connections

4.2 Connections

Terminal labeling

Figure 4-1 Terminal labeling with screw terminals

Number Terminal Function


(1) IN k↑ Current transformer input for N-conductor measurement
(2) IN l↓ Current transformer input for N-conductor measurement
(3) I5 S1↑ Summation current transformer input; analog input I5
(4) I5 S2↓ Summation current transformer input; analog input I5
(5) I6 S1↑ Summation current transformer; analog input I6
(6) I6 S2↓ Current transformer input; analog input I6
(7) Interface to PAC device

Connection examples
Several example connections for the expansion module I(N), I(Diff), analog can be found
below.

16 Equipment Manual, 05/2020, L1V30408520AG-03


Connection
4.2 Connections

The device can be connected for current measurement and/or use of the analog inputs I5 / I6
or a combination of both. The module must be individually configured to meet the
requirements of the application.

Current measurement using current transformers

Figure 4-2 Possible connection type with three current transformers

Use of the external current transformer makes it possible to measure higher residual currents
in the system.

Example:
5SV870 is a 500/1 A current transformer. This results in a minimum measurable residual
current in the system of 0.05 mA *500/1 = 25 mA and a maximum measurable residual
current in the system of 500/1*60 mA = 30 A (type AC sine with peak factor 1.41 alpha = 0°)
or 3 A (type A sine with peak factor 4.69 alpha = 135°) as per the definition in IEC / TR 60755.

Equipment Manual, 05/2020, L1V30408520AG-03 17


Connection
4.2 Connections

Figure 4-3 Possible connection type with three current transformers

Use of the external current transformer makes it possible to measure higher system currents.

Example:
Using a 50/5 A current transformer results in a maximum measurable I(N) current in the
system of 50/5*5 A = 50 A (sine with peak factor 1.41).

18 Equipment Manual, 05/2020, L1V30408520AG-03


Connection
4.2 Connections

Figure 4-4 Possible connection type with three current transformers

Use of the external current transformer makes it possible to measure higher residual currents
in the system.

Example:
Type B 5SV870 is a 450/1 current transformer. In this case, the minimum measurable residual
current in the system is limited by the 5S870 current transformer and is 30 mA. The
maximum measurable residual current in the system is determined by the 5S870 current
transformer. It is 1 A.

Note
The current transformer types shown in the drawings are examples. These can be replaced by
other suitable transformers.
If the device is used in the UL market, the use of transformers with UL approval is required.

IN input:
A suitable current transformer must be used to measure the N-conductor current. The
appropriate current transformer ratio must be set on the SENTRON 7KM PAC measuring
device or powerconfig.

Equipment Manual, 05/2020, L1V30408520AG-03 19


Connection
4.2 Connections

I5 input:
A suitable summation current transformer (type A or type B) must be used to measure the
current. The input must be configured accordingly on the SENTRON 7KM PAC measuring
device or powerconfig.

I6 input:
A suitable summation current transformer (type A or type B) must be used to measure the
current. The input must be configured accordingly on the SENTRON 7KM PAC measuring
device or powerconfig.

Note
If two type B transformers are used on I5 and I6 analog inputs, it must be ensured that the
transformers have separate power supplies. Two type B transformers must not be powered by
the same power supply unit. Each type B transformer must have its own power source.

Note
When the expansion module is used as residual current monitor, the device is only designed
to display the residual current. It cannot control the switching elements in the circuit.

20 Equipment Manual, 05/2020, L1V30408520AG-03


Connection
4.2 Connections

Measurement of physical quantities via analog inputs I5 and I6

Figure 4-5 Possible connection type for measuring physical quantities

The I5 and I6 analog inputs can also be used to measure analog signals (0 / 4 ... 20 mA). The
inputs must be configured accordingly on the SENTRON 7KM PAC measuring device or
powerconfig.
A suitable sensor (0 / 4 ... 20 mA) must be used for this application. The inputs I5 and I6 are
passive. A voltage source of ≤ 50 VDC must be connected as shown in the diagram.

Measurement of physical quantities of any kind, such as


• Temperature [°C; °F]
• Humidity [%]
• Pressure [haPa]
can be measured.

Note
If two sensors are used on I5 and I6 analog inputs, it must be ensured that the sensors have
separate power supplies. Two sensors must not be powered by the same power supply unit.
Each sensor must have its own power source.

Equipment Manual, 05/2020, L1V30408520AG-03 21


Connection
4.2 Connections

Note
Refresh time
The refresh time of the measured values can be up to 5 s.

22 Equipment Manual, 05/2020, L1V30408520AG-03


Connection
4.2 Connections

Equipment Manual, 05/2020, L1V30408520AG-03 23


Commissioning 5
5.1 Overview

Requirements
1. The expansion module has already been installed.
2. The expansion module and the PAC device have been connected up correctly.

Note
Check the connections.
Failure to connect up the device correctly can result in malfunctions and failure of the device.
Before you start commissioning the device, check that all connections are correct.

Note
When performing an insulation test of the entire installation with AC or DC, the device should
be disconnected before starting the test.

DANGER
Open transformer circuits will result in electric shock and arc flashover.
Failure to observe this notice will cause death, serious injury or considerable damage
to property.
Current can only be measured by external current transformers. Do not use fuses for circuit
protection. Do not open the secondary circuit of the current transformers under load. Short
circuit the secondary current terminals of the current transformer before removing this
device. The safety information for the current transformers used must be followed.

Equipment Manual, 05/2020, L1V30408520AG-03 25


Commissioning
5.2 Setting the expansion module parameters

5.2 Setting the expansion module parameters


The parameters for the expansion module can be set either directly on the PAC display or via
the communication interface of the PAC device using the SENTRON "powerconfig"
configuration software.
The SENTRON powerconfig configuration software can be downloaded from the Industry
Online Support website (https://support.industry.siemens.com/cs/at/en/view/63452759).

Setting parameters on the PAC device


In the menu "EXPANSION MODULES", call the "I(N) I(DIFF) ANALOG" that you want to
configure and then select menu item "SETTINGS".

26 Equipment Manual, 05/2020, L1V30408520AG-03


Commissioning
5.2 Setting the expansion module parameters

The IN, I5 and I6 inputs of the module can be configured in the "SETTINGS" menu.

Selection Function / value range


IN ► Set the IN input parameters
I5 ► Set the I5 input parameters
I6 ► Set the I6 input parameters
◄ BACK Back to previous level

Setting the IN input parameters


In this screen you can enter the ratio of the current transformer used.

Selection Function / value range Factory setting


IN PRIMARY 1 ... 9999 0
IN SECONDARY 1 ... 5 0
◄ BACK Return to "SETTINGS" menu

Setting the I5 / I6 input parameters


You can select one of three connection options.

Selection Function / value range


CT Use a summation current transformer
ADC 0 - 20 mA Use a 0 ... 20 mA transmitter
ADC 4 - 20 mA Use a 4 ... 20 mA transmitter
◄ BACK Return to "SETTINGS" menu
► I5 / I6 PARAMETERS Advance to parameterization level

You can parameterize the input after you have selected the connection variant.

Setting the CT parameters

Selection Function / value range Factory setting


CT RATIO X / 1 1 - 9999 0
◄ BACK Back to previous level
► SETTINGS Return to "SETTINGS" menu

Example:
A summation current transformer a with transformer ratio of 500/1 should be connected to
input I5 or I6 and parameterized.
The following parameters must be set at input I5 or I6:
CT RATIO: 500

Equipment Manual, 05/2020, L1V30408520AG-03 27


Commissioning
5.2 Setting the expansion module parameters

Current example:

Selection Function / value range Factory setting


Residual current 100 mA / 500 = 0.2 mA (at module input)
100 mA:
Residual current 3 3 A / 500 = 6 mA (at module input)
A:

Maximum measurable residual current with a 500/1 current transformer: 60 mA x 500 = 30 A

Setting the ADC 0/4 - 20 mA parameters

Selection Function / value range Factory setting


LOWER LIMIT Specify the lower limit 0
1 ... 9999
NEGATIVE On: In this position, a negative sign is assigned to the Off
number for the lower limit
UPPER LIMIT Specify the upper limit 0
1 … 9999
NEGATIVE On: In this position, a negative sign is assigned to the Off
number for the lower limit.
UNIT Set the appropriate measuring unit for the measured GrdC (degrees Celsius)
physical quantity.
The selected measuring unit is displayed next to the
measured value in the measured value menu.
• GrdC (temperature in °C)
• GrdF (temperature in °F)
• hPa (pressure in hectopascal)
• % (percent)
• " " (no unit)
◄ BACK Back to previous level
► SETTINGS Return to "SETTINGS" menu

Example:
A temperature measurement transmitter is to be connected and parameterized at input I5.
Transmitter data:

Selection Function / value range Factory setting


Temperature - 50 ... + 250 °C
range:
Output: 4 to 20 mA

28 Equipment Manual, 05/2020, L1V30408520AG-03


Commissioning
5.3 Parameterizing with powerconfig

The following parameters must be set at input I5:


1. Select ADC 4 - 20 mA
2. Enter I5 parameters

Selection Function / value range Factory setting


a. LOWER LIMIT 50
b. NEGATIVE ON
c. UPPER LIMIT 250
d. NEGATIVE OFF
e. UNIT GrdC (°C)

5.3 Parameterizing with powerconfig


The powerconfig software is the combined commissioning and service tool for
communication-capable measuring devices and circuit breakers from the SENTRON family.
The PC-based tool facilitates parameterization of the devices, resulting in substantial time
savings, particularly when several devices have to be set up.
Power monitoring devices from the 7KM PAC series can be parameterized and operated via
various communication interfaces using powerconfig and measured values can be
documented and monitored.
powerconfig provides the following functions:
• Parameterization, documentation, operation and monitoring in one software package
• User-friendly documentation of settings and measured values
• Clear presentation of the available parameters including validity testing of the input values
• Display of the available device statuses and measured values in standardized views
• Project-oriented storage of device data
• Consistent operation and usability
• Support of the various communication interfaces (Modbus RTU, Modbus TCP, PROFIBUS,
PROFINET) (device-dependent)
• Updating of device firmware and loading of language packs (device-dependent)
You can download the powerconfig configuration software from the Industry Online Support
Website (https://support.industry.siemens.com/cs/ww/en/view/63452759).
Information and notes on how to use powerconfig can be found in the Online Help of the
configuration software or by contacting Technical Support.
You launch the Online Help in powerconfig by pressing the "F1" key.

Equipment Manual, 05/2020, L1V30408520AG-03 29


Commissioning
5.4 Reading out measured values

5.4 Reading out measured values


The expansion module measured values can be read out either directly on the PAC display, or
via the communication interface of the PAC device using the SENTRON powerconfig
configuration software, or by means of a Modbus command.

The SENTRON powerconfig configuration software can be downloaded from the Industry
Online Support website (https://support.industry.siemens.com/cs/ww/en/view/63452759).

Reading out from PAC device


In the menu "EXPANSION MODULES", call the "I(N) I(DIFF) ANALOG" from which you want to
read measured values and then select menu item "MEASUREMENT".
See the flowchart in chapter Setting the expansion module parameters (Page 26)

The following module information can be found in menu item "I(N) I(DIFF) ANALOG":
• MLFB number
• Serial number
• Firmware version
• Diagnostics

Measured values of the module are displayed in menu item "Measurement".


The parameters of the expansion module inputs can be set in menu item "Settings". For more
information refer to chapter Setting the expansion module parameters (Page 26).

30 Equipment Manual, 05/2020, L1V30408520AG-03


Service and maintenance 6
6.1 Calibration
The device has been calibrated by the manufacturer before shipping. Recalibration is not
required provided the environmental conditions are maintained.

6.2 Firmware update


The expansion module I(N), I(Diff) analog supports firmware updates.
The latest firmware versions
(https://support.industry.siemens.com/cs/ww/en/view/109756312) can be downloaded from
the Service and Support Portal.

Use the latest version of the SENTRON powerconfig configuration software to install updates.
For update instructions, please see the related documentation and online help.
The last device settings made remain unchanged.

6.3 Troubleshooting guide

Fault Remedy
Device is not working • Check the connection to the PAC device and tighten fastening
screws if required
• Check the power supply to the PAC device
Current values are not correctly displayed • Check the type and settings of the current transformer used and
adjust if necessary
Physical measured quantities are not correctly • Check the connections and wiring
displayed
• Check the transmitter type (0 / 4 ... 20 mA) and configuration type
• Check the external power supply to the transmitter
LED is illuminated red • Check the connection to the PAC device
• Check the contact pins for damage

Equipment Manual, 05/2020, L1V30408520AG-03 31


Service and maintenance
6.4 Warranty

Fault Remedy
The module cannot be successfully configured • Check the PAC communications settings (IP address, protocol, sub-
using the SENTRON powerconfig configuration
net, gateway)
software
• The firewall may be preventing access to the PAC device
Implausible values at I5 or I6 • Check the power supply of type B transformers or external sensors
• Transformers or sensors connected to I5 or I6 must be powered by
separate sources.

6.4 Warranty

Procedure

Note
Loss of warranty
Opening the device invalidates the Siemens warranty. Return nonconforming or damaged
devices to Siemens.

If the device is nonconforming or damaged, proceed as follows (only during the warranty
period):
1. Uninstall the device.
2. Pack the device in a suitable manner to prevent it from being damaged during transport.
3. Return the device to Siemens. You can obtain the address from:
• Your Siemens sales partner
• Technical assistance (https://support.industry.siemens.com/My/ww/en/requests)

Note
The contents of this instruction manual shall not become part of or modify any prior or
existing agreement, commitment, or relationship. The sales contract contains the entire
obligation of Siemens. The warranty contained in the contract between the parties is the sole
warranty of Siemens. Any statements contained herein do not create new warranties or
modify the existing warranty.

Disposal of waste electronic equipment


Waste electronic equipment must not be disposed of as unsorted municipal waste, e.g.
household waste. When disposing of waste electronic equipment, the current local
national/international regulations must be observed.

32 Equipment Manual, 05/2020, L1V30408520AG-03


Technical specifications 7
Device configuration
• IN - measuring input
• I5 - analog input
• I6 - analog input

Supply voltage
No external supply voltage is required. The expansion module is supplied via the PAC device.

Measuring inputs
Connection to AC power systems is only possible via external current transformers.

IN input
Input current IE 10 mA ... 1 A / 50 mA ... 5 A
Max. permissible continuous 1.2 A / 6 A
current
Current impulse overload capa- 100 A for 1 s
bility
Zero point suppression level 1 mA
Electrical isolation Yes
Measuring accuracy *) Class 1 acc. to EN 61557-12
Apparent power consumption 1 A → 4 mVA
during current measurement 5 A → 0.115 VA

*) The overall accuracy depends on the quality of the external current transformer.

I5 / I6 input
Measuring range 0.05 mA ... 20 mA ... 60 mA (sine peak factor 1.41)
Max. permissible continuous 72 mA
current
Zero point suppression level 0.005 mA
Refresh time ≤5s
Connection of external sensors 0 / 4 ... 20 mA (≤ 50 V DC)
Electrical isolation No
Connection of external summa- Acc. to IEC 62020 and IEC / TR 60755 type A* / B*
tion current transformer

*) The accuracy of the measurement and the characteristics depend on the transformer used.

Equipment Manual, 05/2020, L1V30408520AG-03 33


Technical specifications

Connection elements

Table 7- 1 Conductor cross-section

mm2 AWG
Rigid 0.5 ... 4 22 ... 12
Flexible 0.5 ... 4 22 ... 12
Flexible with end sleeve, without plastic 0.5 ... 1.5 22 ... 16
sleeve
Flexible with end sleeve and plastic sleeve 0.5 ... 1.5 22 ... 16
Tightening torque 0.45 ... 0.5 Nm [3.98 ... 4.43 lb-in]

Table 7- 2 Two conductors of same cross-section

mm2 AWG
Rigid 0.5 ... 1.5 22 ... 16
Flexible 0.5 ... 1.5 22 ... 16
Flexible with end sleeve, without plastic 0.5 ... 0.75 22 ... 20
sleeve
Flexible with TWIN end sleeve and plastic 0.5 ... 1.5 22 ... 16
sleeve
Tightening torque 0.45 ... 0.5 Nm [3.98 ... 4.43 lb-in]

Dimensions and weight

Enclosure dimensions (inserted in PAC device) W x H x D 43 mm x 63 mm x 34 mm


Enclosure dimensions (not inserted in PAC device) W x H x D 43 mm x 63 mm x 42 mm
Weight
Device without packaging 58 g
Device with packaging 80 g

34 Equipment Manual, 05/2020, L1V30408520AG-03


Technical specifications

Degree of protection and protection class

Protection class II
Degree of protection according to IEC 60529 IP 20
Pollution degree 2

Note
Further technical specifications, mechanical specifications and electrical specifications as well
as ambient and environmental conditions are identical to those of the SENTRON PAC
measuring device. You can find more information in the operating instructions and in the
equipment manual for the SENTRON PAC3200
(https://support.industry.siemens.com/cs/ww/en/view/26504150), PAC3220
(https://support.industry.siemens.com/cs/ww/en/view/109767307) or PAC4200
(https://support.industry.siemens.com/cs/ww/en/view/34261595) Power Monitoring Device.

Ambient conditions
The device may only be operated within enclosed dry rooms.

Temperature range
Ambient temperature during operating phase -25 ... +55 °C
Ambient temperature during transport and -25 ... +70 °C
storage
Relative humidity < 75%
Environmental conditions as defined by IEC 60068

Equipment Manual, 05/2020, L1V30408520AG-03 35


Technical specifications

Relative humidity in relation to ambient temperature


The maximum relative humidity is 80% at temperatures up to 31 °C, decreasing linearly down
to 50% relative humidity at 40 °C.

Approvals

CE conformity
Applied directives and standards can be found in the EU Declaration of Conformity.

Approvals for Australia and New Zealand


Regulatory Compliance Mark

Approval for Eurasian Economic Union

Approvals for USA and Canada


Products bearing this mark meet both Canadian (CSA) and American (UL) requirements.

Product approval in the United Kingdom (United Kingdom Conformity Assessed)

You can download the relevant certificates


(https://support.industry.siemens.com/cs/ww/en/ps/7KM9200-0AD00-0AA0/cert) from the
Siemens Support website.

36 Equipment Manual, 05/2020, L1V30408520AG-03


Appendix A
A.1 Modbus measured quantities with function codes 0x03 and 0x04
Depending on the device slot (MOD 1 or MOD 2), measured values can be read out of the
following register addresses.

Abbr. in the "Access" column Abbreviation


R Read; read access
W Write; write access
RW Read Write; read and write access

Offset (MOD1) Number of registers Name Format


58001 6 Module MOD_1 struct

Offset (MOD2) Number of registers Name Format


58123 6 Module MOD_2 struct

Design and structure for MOD1 and MOD2


Byte Name Format Unit
0 ... 3 IN Float A
4 ... 7 I5 Float A
8 ... 11 I6 Float A

A.2 Average value quantities


The measured quantities listed below can be read out in two stages via Modbus function
code 0x14 "Read File Record".
• Stage 1 (File Number 1), preset to 10 s
• Stage 2 (File Number 2), preset to 15 min

Application with 7KM PAC3220 measuring device

File Offset address Address Length Name Format Access


(FC 0x14) FC 0x03
FC 0x04
1 89 30089 2 I4_MOD1 float R
1 91 30091 2 I5_MOD1 float R
1 93 30093 2 I6_MOD1 float R

Equipment Manual, 05/2020, L1V30408520AG-03 37


Appendix
A.2 Average value quantities

File Offset address Address Length Name Format Access


(FC 0x14) FC 0x03
FC 0x04
1 95 30095 2 I4_MOD2 float R
1 97 30097 2 I5_MOD2 float R
1 99 30099 2 I6_MOD2 float R
1 345 30345 2 max_I4_MOD1 float R
1 347 30347 2 max_I5_MOD1 float R
1 349 30349 2 max_I6_MOD1 float R
1 351 30351 2 max_I4_MOD2 float R
1 353 30353 2 max_I5_MOD2 float R
1 355 30355 2 max_I6_MOD2 float R
1 601 30601 2 min_I4_MOD1 float R
1 603 30603 2 min_I5_MOD1 float R
1 605 30605 2 min_I6_MOD1 float R
1 607 30607 2 min_I4_MOD2 float R
1 609 30609 2 min_I5_MOD2 float R
1 611 30611 2 min_I6_MOD2 float R
2 89 31089 2 I4_MOD1 float R
2 91 31091 2 I5_MOD1 float R
2 93 31093 2 I6_MOD1 float R
2 95 31095 2 I4_MOD2 float R
2 97 31097 2 I5_MOD2 float R
2 99 31099 2 I6_MOD2 float R
2 345 31345 3 max_I4_MOD1 float R
2 347 31347 4 max_I5_MOD1 float R
2 349 31349 5 max_I6_MOD1 float R
2 351 31351 6 max_I4_MOD2 float R
2 353 31353 7 max_I5_MOD2 float R
2 355 31355 8 max_I6_MOD2 float R
2 601 31601 9 min_I4_MOD1 float R
2 603 31603 10 min_I5_MOD1 float R
2 605 31605 11 min_I6_MOD1 float R
2 607 31607 12 min_I4_MOD2 float R
2 609 31609 13 min_I5_MOD2 float R
2 611 31611 14 min_I6_MOD2 float R

Application with 7KM PAC4200 measuring device

File Offset address Address Length Name Format Access


(FC 0x14) FC 0x03
FC 0x04
1 131 30131 2 I4_MOD1 float R
1 133 30133 2 I5_MOD1 float R
1 135 30135 2 I6_MOD1 float R
1 137 30137 2 I4_MOD2 float R
1 139 30139 2 I5_MOD2 float R

38 Equipment Manual, 05/2020, L1V30408520AG-03


Appendix
A.2 Average value quantities

File Offset address Address Length Name Format Access


(FC 0x14) FC 0x03
FC 0x04
1 141 30141 2 I6_MOD2 float R
1 331 30331 2 max_I4_MOD1 float R
1 333 30333 2 max_I5_MOD1 float R
1 335 30335 2 max_I6_MOD1 float R
1 337 30337 2 max_I4_MOD2 float R
1 339 30339 2 max_I5_MOD2 float R
1 341 30341 2 max_I6_MOD2 float R
1 531 30531 2 min_I4_MOD1 float R
1 533 30533 2 min_I5_MOD1 float R
1 535 30535 2 min_I6_MOD1 float R
1 537 30537 2 min_I4_MOD2 float R
1 539 30539 2 min_I5_MOD2 float R
1 541 30541 2 min_I6_MOD2 float R
2 131 30131 2 I4_MOD1 float R
2 133 30133 2 I5_MOD1 float R
2 135 30135 2 I6_MOD1 float R
2 137 30137 2 I4_MOD2 float R
2 139 30139 2 I5_MOD2 float R
2 141 30141 2 I6_MOD2 float R
2 131 31131 2 I4_MOD1 float R
2 133 31133 2 I5_MOD1 float R
2 135 31135 2 I6_MOD1 float R
2 137 31137 2 I4_MOD2 float R
2 139 31139 2 I5_MOD2 float R
2 141 31141 2 I6_MOD2 float R
2 331 31331 2 max_I4_MOD1 float R
2 333 31333 2 max_I5_MOD1 float R
2 335 31335 2 max_I6_MOD1 float R
2 337 31337 2 max_I4_MOD2 float R
2 339 31339 2 max_I5_MOD2 float R
2 341 31341 2 max_I6_MOD2 float R
2 531 31531 2 min_I4_MOD1 float R
2 533 31533 2 min_I5_MOD1 float R
2 535 31535 2 min_I6_MOD1 float R
2 537 31537 2 min_I4_MOD2 float R
2 539 31539 2 min_I5_MOD2 float R
2 541 31541 2 min_I6_MOD2 float R

Equipment Manual, 05/2020, L1V30408520AG-03 39


Index

A L
Ambient conditions Latest information, 5
Technical specifications, 35
Approvals
Technical specifications, 36 M
Measuring inputs
Technical specifications, 33
C
Calibration
Service and maintenance, 31 O
Connection elements
Open Source Software, 7
Technical specifications, 34
Use, 7
Connection examples, 16

P
D
Performance features
Degree of protection and protection class
Description, 10
Technical specifications, 35
Device configuration
Technical specifications, 33
R
Diagnostic LED
Design, 11 Reading out from PAC device
Dimensions and weight Reading out measured values, 30
Technical specifications, 34 Requirements
Commissioning, 25

F
S
Firmware update
Service and maintenance, 31 Scope of delivery
Introduction, 5
Security functions, 6
I Setting parameters on the PAC device
Setting the expansion module parameters, 26
I5 connection
Setting the ADC parameters
Design, 11
Setting the expansion module parameters, 28
I6 connection
Setting the CT parameters
Design, 11
Setting the expansion module parameters, 27
IN connection
Setting the I5 input parameters
Design, 11
Setting the expansion module parameters, 27
Installation location
Setting the IN input parameters
Installation, 13
Setting the expansion module parameters, 27
Installation steps
Supply voltage
Installation, 14
Technical specifications, 33

Equipment Manual, 05/2020, L1V30408520AG-03 41


Index

T
Terminal labeling, 16
Troubleshooting guide
Service and maintenance, 32

W
Warranty
Service and maintenance, 32

42 Equipment Manual, 05/2020, L1V30408520AG-03

You might also like