BRITISH STANDARD BS EN
1838:1999
BS 5266-7:1999
Lighting applications -
Emergency lighting
ICs 91.160.10
COPYRIGHT 2003; British Standards Institution on ERC Specs and Standards Document provided by IHS Licensee=Dumez GTM/5919881100, User=, 12/09/2003
00:57:28 MST Questions or comments about this message: please call the Document
Policy Group at 1-800-451-1584.
STD.BSI BS EN 1 8 3 8 - E N G L 1777 M 1b24bb9 07993L4 T Z U D
BS EN 18381999
National foreword
This British Standard is the English language version of EN 1838:1999. Together with
BS 52681:1999, it supersedes BS 52661:1983 which is withdrawn.
This standard gives details of the UK A deviations in annex B and should be read in
co~unction with BS 5261:1999.
The UK participation in its preparation was entrusted to Technical Committee
C P W 9 , Emergency lighting, which has the responsibility to:
Summary of pages
This document comprises a front cover, an inside front cover, the EN title page,
pages 2 to 9 and a back cover.
The BSI copyright notice displayed in this document indicates when the document
was last issued.
O BSI 10-1999
COPYRIGHT 2003; British Standards Institution on ERC Specs and Standards Document provided by IHS Licensee=Dumez GTM/5919881100, User=, 12/09/2003
00:57:28 MST Questions or comments about this message: please call the Document
Policy Group at 1-800-451-1584.
S T D - B S I BS E N L838-ENGL L777 W 1b24bb7 0797315 9b7 II
EUROPEAN flmm EN 1838
NORME EUR0PEE”E
EUROPMSCHE NORM April 1999
ICs 91.160.10
English version
CEN members are the national standards bodies of Austria, Belgium, Czech
Republic, Denmark Finiand, France, Germax Greece, Iceland, Ireland, Italy,
Luxembourg, Netherlands, Norway, Portugal, Spain, Sweden, Switzerland and
United Kingdom.
O 1999 CEN AU rights of exploitation in any form and by any means reserved worldwide for CEN national
Members.
Ref. No. EN 1838:1999 E
COPYRIGHT 2003; British Standards Institution on ERC Specs and Standards Document provided by IHS Licensee=Dumez GTM/5919881100, User=, 12/09/2003
00:57:28 MST Questions or comments about this message: please call the Document
Policy Group at 1-800-451-1584.
Page 2
EN 18381999
Foreword Contents
This European Standard has been prepared by Page
Technical Committee CENíïC 169, Light and lighting,
Foreword 2
the Secretariat of which is held by DIN.
This European Standard shall be given the status of a Introduction 3
national standard, either by publication of an identical 1 Scope 3
text or by endorsement, at the latest by October 1999, 2 Normative references 3
and conflicting national standards shall be withdrawn
at the latest by October 1999. 3 Definitions 4
According to the CENKENELEC Internal Regulations, 4 Emergency escape lighting 4
the national standards organizations of the following 4.1 General 4
counlxies are bound to implement this European
Standard: Austria, Belgium, Czech Republic, Denmark,
4.2 Escape route lighting 4
Finland, Fí-ance, Germany,Greece, Iceland, Ireland, 4.3 Open area (anti-panic) lighting 5
Im,Luxembourg, Netherlands, Norway, Portugal, 4.4 High risk task area lighting 6
Spain, Sweden, Switzerland and the United Kingdom.
4.5 Standby lighting 6
It is intended to replace in part national standards
relating to emergency lighting luminous requirements. 5 Safety signs 6
It should be read in conjunction with the standards Annex A (nonnative) Luminance and
being produced by CENmC 169 WG7, Measurement illuminance measurements 7
and presentation of photometric data, and in Annex B (informative) Countries requiring
conjunction with prEN 50172 Emergency escupe different light levels 8
lighting systems.
Usem of this EN, prepared in the field of application of Annex C (informative) Bibliography 9
Article 118 A of the EC WaQ,should be aware that
standards have no formal legal relationship with
--`,`````,,,,,`,```,,,```,``,`,-`-`,,`,,`,`,,`---
Directives which may have been made under Article
118A of the lkeaty In addition, national legislation in
the Member states may contain more Stsingent
requirements than the minimum requirements of a
Directive based on Article 118 A. Information on the
relationship between the national legislation
implementing Directives based on Article 118 A and
this EN may be given in a national foreword of the
national standard implementing this EN.
COPYRIGHT 2003; British Standards Institution on ERC Specs and Standards Document provided by IHS Licensee=Dumez GTM/5919881100, User=, 12/09/2003O BSI 10-1999
00:57:28 MST Questions or comments about this message: please call the Document
Policy Group at 1-800-451-1584.
S T D * B S I BS EN Lö38-ENGL 3 9 9 9 W Lb2LibbS 0779337 737'
Page 3
EN 18381999
The objective of high risk task area lighting is to EN 605982-22, Luminaires - Part 2-22:PartzcUh.r
contribute to the safety of people involved in a requirements - Luminaires for emergency lighting.
potentially dangerous process or situation and to (IEC 605982-22:1997, modified)
enable proper shut down procedures to be carried out prEN 50172, Emergency escape lighting syslslems.
for the safety of other occupants of the location.
IS0 3864:1984, Safety colours a,nd safety signs.
There are emerging techniques that when applied to
escape routes in addition to conventional emergency IEC 50 - Chapter 845, Intemational Electrotechnical
lighting luminaires can enhance their effectiveness in V O C & U- ~ chap&
~~ 845: Lightiw.
an emergency. These techniques are not included in
this standard.
3 Definitions 3.10
For the purposes of this standard the following externally illuminated safety sign
definitions apply a sign that is illuminated, when it is required, by an
3.1 external source
emergency lighting 3.11
lighting provided for use when the supply to the internally illuminated safety sign
normal lighting fails a sign that is illuminated, when it is required, by an
[IEC 50 - Chapter 8451 internal source
3.2
escape route
4 Emergency escape lighting
a route designated for escape in the event of an 4.1 General
emergency To provide visibility for evacuation purposes lighting is
required in the volume of the space. In this standard
3.3 the recommendation is W e d by the mounting of
emergency escape lighting luminaires at least 2 m above the floor. Signs which
that part of emergency lighting that provides are provided at aìì exits intended to be used in an
ilìumination for the safety of people leaving a location emergency and along escape routes shall be
or attempting to terminate a pokntiaüy dangerous illuminated to indicate unambiguously the route of
process before doing so escape to a point of safety.
3.4 Where direct sight of an emergency exit is not
escape route lighting possible, an dìuminated directional sign (or series of
that part of emergency escape lighting provided to signs) shall be provided to assist progression towards
ensure that the means of escape can be effectively the emergency exit.
identified and safely used when the location is An escape lighting luminaire complying with EN
occupied 605982-22 shall be sited to provide appropriate
illuminance near each exit door and at positions where
3.6 it is necessary to emphasize potential danger or safety
open area lighting equipment. The positions to be emphasized shall
(in some countries known as anti-panic lighting) include the following:
that part of emergency escape lighting provided to a) at each exit door intended to be used in an
avoid panic and provide illumination allowing people emergency;
to reach a place where an escape route can be b) near (see note) s t a k so that each fight of staiis
identified receives direct light;
3.6 c) near (see note) any other change in level;
high risk task area lighting d) mandatory emergency exits and safety signs;
that part of emergency escape lighting that provides e) at each change of àirection;
illumination for the safety of people involved in a f ) at each intersection of corridors;
potentially dangerous process or situation and to g) outside and near to each f i a l exit;
enable proper shut down procedures for the safety of h) near (see note) each first aid post;
the operator and other occupants of the premises i) near (see note) each piece of fire fighting
3.7 equipment and call point.
standby lighting Positions denoted as h) or i) if not on the escape route
that part of emergency lighting provided to enable nor in an open area shall be illuminated to 5 lx
normal activities to continue substantially unchanged minimum on the floor.
[IEC 50 - Chapter 8451 N0TE.T BO>For the purposes of this clause, "near" is normally
considered to be within 2 m measured horizontally.
3.8 4.2 Escape route lighting
emergency exit 4.2.1 For escape routes up to 2 m in width, the
a way out that is intended to be used during an horizontal illuminances on the floor along the centre
emergency line of an escape route shall be not less than 1 Ix and
3.9 the central band consisting of not less than half of the
safety sign width of the route shall be illuminated to a minimum
a sign which gives a general safety message, obtained of 50 % of that value.
N0TE.T 18>1 Wider escape routes can be treated as a number of
by a combination of colour and g e o m e ~ cshape and 2 m wide strips or be provided with open area (anti-panic)
which, by the addition of a graphic symbol or text, lighting.
gives a particular safety message N0TE.T 18>2 Countries requiring different lighting levels are
[IS0 3864:1984] given in annex B.
--`,`````,,,,,`,```,,,```,``,`,-`-`,,`,,`,`,,`---
O BSI 10-1999
COPYRIGHT 2003; British Standards Institution on ERC Specs and Standards Document provided by IHS Licensee=Dumez GTM/5919881100, User=, 12/09/2003
00:57:28 MST Questions or comments about this message: please call the Document
Policy Group at 1-800-451-1584.
S T D - B S I B S EN 3838-ENGL 1 9 9 9 m lb2Libb9 0799339 502 m
Page 5
EN 18381999
O BSI 10-1999
COPYRIGHT 2003; British Standards Institution on ERC Specs and Standards Document provided by IHS Licensee=Dumez GTM/5919881100, User=, 12/09/2003
00:57:28 MST Questions or comments about this message: please call the Document
Policy Group at 1-800-451-1584.
S T D = B S I BS EN 1838-ENGL 1777 I1 b 2 4 b b 9 0799320 22Li D
Page 6
EN 18381999
4.4.1 In areas of high risk the maintained illuminance 6.1 Safety signs shall be illuminated to at least 50 % of
on the reference plane shall be not less than 10 % of the required luminance w i t h 5 s and full required
the required maintained illuminance for that task, luminance withii 60 s.
however it shall be not less than 15 lx. It shall be free 6.2 The colours shall conform to the requirements of
of harmful stroboscopic effects. IS0 3864.
4.4.2 The uniformity of the high risk task area lighting
6.3 The luminance of any area of safety colour of the
illuminance shall be not less than 0,l.
sign shall be at least 2 cam2 in all relevant viewing
4.4.3 Disability glare shall be kept low by limiting the directions (see annex A).
luminous intensity of the luminaires within the field of
view. These shall not exceed the values in Table 1 6.4 The ratio of the maximum to the minimum
within the zone 60" to 90" from the downward vertical luminance within either white or the safety colour shall
at all angles of azimuth. be not greater than 101.
N0TE.T 2O>High variation of a x e n t points should be avoided.
4.4.4 In order to identa safety colours, the minimum
value for the colour rendering index Ra of a lamp shall 6.6 The ratio of the luminance LWhite to the luminance
be 40. The luminaire shall not substantially subtract Lcolourshall be not less than 5 1 and not greater than
from this. 151 (see annex A).
4.4.6 The minimum duration shall be the period for 6.6 A s an internally i l l w e d sign is discernible at a
which the risk exists to people. greater distance than an externally illuminated sign of
4.4.6 High risk task area lighting shall provide the full the same size the maximum viewing distance (see
required illuminance permanently or within 0,5 s Figure 4) shall be determined by use of the following
depending upon application. equation:
Compliance with 4.4.1 to 4.4.4 and 4.4.6 can be
checked by measurement or by comparison with d=sXp (1)
authenticated data from a supplier. where
4.6 Standby lighting d is the viewing chstance;
When standby lighting is used for emergency escape p is the height of the pictogram;
lighting purposes it shall comply with the relevant s is a constant: 100 for externally illuminated
requirements of this standard. signs; 200 for internally illuminated signs.
Where a standby lighting level lower than the minimum
normal lighting is employed, the lighting is to be used
oniy to shut down or terminate processes.
--`,`````,,,,,`,```,,,```,``,`,-`-`,,`,,`,`,,`---
O BSI 10-1999
COPYRIGHT 2003; British Standards Institution on ERC Specs and Standards Document provided by IHS Licensee=Dumez GTM/5919881100, User=, 12/09/2003
00:57:28 MST Questions or comments about this message: please call the Document
Policy Group at 1-800-451-1584.
Page 7
EN 18381999
Annex A (normative)
Luminance and iUuminance
measurements
A.l Luminance measurements of signs
Luminances are measured normal to the surface over a
10 mm diameter patch for each coloured surface of the
sign. The minimum and maximum luminance is
measured over the areas of each colour. For the
coloured background a 10 mm wide outer border is
excluded from the measurements. In order to
determine the luminance ratio between two acljacent
colours the luminance measurement should be taken at
a &stance of 15 mm on either side of the junction of
the two colours. A search shall be made for the
maximum and minimum ratios. If the area of colour is
less than 30 mm the patch size shall be reduced.
For safety signs with a shortest side less than 100 mm
the diameter of the patch size and the width of the
excluded border shall be reduced to not less than 10 %
of that shortest side.
A.2 Instrumentation for site measurement
All illuminance measurements shall be made with a
cosine photopic V(A) - corrected meter and all
luminance measurements shall be made with a
photopic V(A)- corrected meter.
The meter shall have an error tolerance not exceeding
10 %.
The measurement may be taken up to 20 mm height
above the floor.
--`,`````,,,,,`,```,,,```,``,`,-`-`,,`,,`,`,,`---
O BSI 10-1999
COPYRIGHT 2003; British Standards Institution on ERC Specs and Standards Document provided by IHS Licensee=Dumez GTM/5919881100, User=, 12/09/2003
00:57:28 MST Questions or comments about this message: please call the Document
Policy Group at 1-800-451-1584.
STD-BSI BS EN 1838-ENGL 1979 El lb2Libb7 0799322 OT7
Page 8
EN 18381999
Countries requiring different light levels United Kingdom (SI No. 1065, SI No.
2179, SI No. 1709)
Adeviation: National deviation due to regulations, the
BS 52661:1988 “Emergency Lighting“.
alteration of which is for the time being outside the
Clause 4.2.1 Defined escape routes:The
competence of the CENKENELEC member.
horizontal illuminance at floor level on the
This European Standard does not fall under any centre line of a defined escape route
Directive of the EC. should be not less than 0,2 lx. In addition
In the relevant CENICENELEC countries these for escape routes up to 2 m wide 50 % of
Adeviaíions are valid instead of the provisions of the the route width should be lit to a
European Standard untii they have been removed. minimum of 0,l Ur. Wider escape routes
can be treated as a number of 2 m wide
Ciause Deviation bands.
1 France’) 4.2.614.3.6 Germany (0 7 Abs. 4 der
Certified products are mandatory with Arbeitsstätknverordnung und der
defined performances. Illuminance and Arbeitsstätten-Richtlinie ASR 714)
luminance design principles are not used. The period between the failure of the
4 Italy21 normal lighting when the electric supply
fails and the reaching of the required
For cinemas, theatres and similar locations illuminance shall last not longer than 15 s.
the minimum dlwninance level measured
at l m above the floor shall be 5 ix in 4.2.6 Ireland (S.I. No. 497 of 1997)
proximity to the stairs and Exit doors. A I.S. 32171989 “Code of Practice for
minimum iliuminance of 2 Ur is required Emergency Lighting”.Ciause 4.2.6
along escape routes. Where defined Response t i m The emergency lighting
illuminance levels are required by law, specified in this code should be provided
they shall not be considered as design within 5 s of the failure of the normal
values but actual measured values lighting supply.
including reflectance and available when United Kingdom (SI No. 1065, SI No.
emergency lighting is required 2179, SI No. 1709)
4.1 France’) BS 52661:1988 “EmergencyLighting”.
g), h) and i) are not included in the Clause 4.2.6 Response time: The
French requirements. emergency lighting detailed in this code
should be provided within 5 s of the
--`,`````,,,,,`,```,,,```,``,`,-`-`,,`,,`,`,,`---
4.2 France’)
failure of the normal lighting supply, but at
On escape routes, certiñed emergency the discretion of the enforcing authority
luminaires must be installed with a this period can be extended to a
spacing of not more than 15 m (30 m in maximum of 15 s in premises likely to be
schools). occupied for the most part by persons
4.2.1 Ireland (S.I. No. 497 of 1997) who are familiar with them and the escape
routes.
IS. 32171989 “Code of Practice for
Emergency Lighting”. Clause 4.2.1 Defined
escape routes:The horizontal illuminance
at floor level on the centre line of a clearly
defined escape route shall be not less than
0,5 ix.
i) The deviations for Rance are based on the following national regulations:
Règlement de sécurité contre l’incendie dans les ERP, arrêté du 25 juin 1980 modifié, livre II, chapitre VIII, section III.
Arrêté du 10 novembre 1976 relatif aux circuits et installations de sécurité dans les établissements soumis au code du travail.
2, The deviation for Italy is based on the following national regulations:
O BSI 10-1999
COPYRIGHT 2003; British Standards Institution on ERC Specs and Standards Document provided by IHS Licensee=Dumez GTM/5919881100, User=, 12/09/2003
00:57:28 MST Questions or comments about this message: please call the Document
Policy Group at 1-800-451-1584.
S T D * B S I BS EN 1B38-ENGL 1 9 9 9 R Lb2‘4bb9 0779323 T33 I
I
Page 9
EN 18381999
--`,`````,,,,,`,```,,,```,``,`,-`-`,,`,,`,`,,`---
BSI is the independent national body responsible for preparing British Standash. It
presents the UK view on standards in Europe and at the international level. It is
incorporated by Royal Charter.
Revisions
British Standards are updated by amendment or revision. Users of British Standards
should make sure that they possess the latest amendments or editions.
It is the constant aim of BSI to improve the quality of our products and services. We
would be grateful if anyone finding an inaccuracy or ambiguity while using this
British Standard would inform the Secretary of the technical committee responsible,
the identity of which can be found on the inside front cover. Tel 020 8996 9000.
Fax: O20 8996 7400.
BSI offers members an individual updating service caiied PLUS which ensures that
subscribers automatically receive the latest editions of standards.
Buying standards
Orders for a l l BSI, international and foreign standardspublications should be
addressed to Customer Services. Tel 020 8996 9001. Fax:020 8996 7001.
In response to orders for international standards, it is BSI policy to supply the BSI
implementation of those that have been published as British Standards, unless
otherwise requested.
Information on standards
BSI provides a wide range of information on national, European and international
standards through its Library and its Technical Help to Exporters Service. Various
BSI electronic information services are also available which give details on all its
products and services. Contact the Information Centre. Tel 020 8996 7111.
Fax: 020 8996 7048.
Subscribing members of BSI are kept up to date with standards developments and
receive substantial discounts on the purchase price of standards. For details of
these and other benefits contact Membership Administration. Tel 020 8996 7002.
Fax: O20 8996 7001.
Copyright
Copyright subsists in ail BSI publications. BSI also holds the copyright, in the UK, of
the publications of the international standardization bodies. Except as permitted
under the Copyright, Designs and Patents Act 1988no extract may be reproduced,
stored in a refxieval system or transmitted in any form or by any means - electronic,
photocopying, recording or otherwise - without prior written permission from BSI.
This does not preclude the free use, in the course of implementing the standard, of
necessary details such as symbols, and size, type or grade designations. If these
details are to be used for any other purpose than implementation then the prior
written permission of BSI must be obtained.
If permission is granted, the terms may include royalty payments or a licensing
agreement. Details and advice can be obtained from the Copyright Manager.
Tel 020 8996 7070.
BSI
389 Chiswick High Road
London
w4 4AL
--`,`````,,,,,`,```,,,```,``,`,-`-`,,`,,`,`,,`---
COPYRIGHT 2003; British Standards Institution on ERC Specs and Standards Document provided by IHS Licensee=Dumez GTM/5919881100, User=, 12/09/2003
00:57:28 MST Questions or comments about this message: please call the Document
Policy Group at 1-800-451-1584.