You are on page 1of 12

Mat Foundation Design Page 1 of 12

Print Calculation Sheet

DESIGN OF MAT FOUNDATION

Mat Foundation Design(IS 456-2000) - Metric


Job Details

Job Name : Elevated Water Tank AP


Included
X (m) Y (m) Z (m)
Support
2 3.00 0.00 0.00
3 2.12 0.00 -2.12
4 0.00 0.00 -3.00
5 -2.12 0.00 -2.12
6 -3.00 0.00 0.00
7 -2.12 0.00 2.12
8 0.00 0.00 3.00
9 2.12 0.00 2.12

Load Details

Included Loads

Load Case No 5: DEAD LOAD

Load Type : Primary

Serviceability Factor : 1.00

Design Factor : 1.00

Self Weight Factor : 1.00

Column Reactions Applied as Loads on the Mat


For the loads shown in this table, the sign convention is the same as that for JOINT LOADS in STAAD.Pro when global Y is the vertical
axis.

Fy
(kN)
Fx Fz Mx Mz
NODE NO. Downwards is
(kN) (kN) (kNm) (kNm)
negative Upwards is
positive

2 0.32 -540.09 -0.00 -0.00 -0.41


3 0.22 -540.09 -0.22 -0.29 -0.29
4 0.00 -540.09 -0.32 -0.41 -0.00
5 -0.22 -540.10 -0.22 -0.29 0.29
6 -0.32 -540.10 0.00 0.00 0.41
7 -0.23 -540.06 0.22 0.29 0.29
8 -0.00 -540.11 0.32 0.41 0.00
9 0.22 -540.09 0.22 0.29 -0.29

Load Case No 6: LIVE LOAD

Load Type : Primary

Serviceability Factor : 1.00

Design Factor : 1.00

Self Weight Factor : 1.00

Column Reactions Applied as Loads on the Mat


For the loads shown in this table, the sign convention is the same as that for JOINT LOADS in STAAD.Pro when global Y is the vertical
axis.

file:///D:/Shreejay%20Projects/Staad%20Projects/Elevated%20Circular%20Water%20Tan... 4/21/2021
Mat Foundation Design Page 2 of 12

Fy
(kN)
Fx Fz Mx Mz
NODE NO. Downwards is
(kN) (kN) (kNm) (kNm)
negative Upwards is
positive

2 0.00 -14.54 -0.00 -0.00 -0.00


3 0.00 -14.54 -0.00 -0.00 -0.00
4 0.00 -14.54 -0.00 -0.00 -0.00
5 -0.00 -14.54 -0.00 -0.00 0.00
6 -0.00 -14.54 0.00 0.00 0.00
7 -0.00 -14.54 0.00 0.00 0.00
8 -0.00 -14.55 0.00 0.00 0.00
9 0.00 -14.54 0.00 0.00 -0.00

Load Case No 7: WATER PRESSURE

Load Type : Primary

Serviceability Factor : 1.00

Design Factor : 1.00

Self Weight Factor : 1.00

Column Reactions Applied as Loads on the Mat


For the loads shown in this table, the sign convention is the same as that for JOINT LOADS in STAAD.Pro when global Y is the vertical
axis.

Fy
(kN)
Fx Fz Mx Mz
NODE NO. Downwards is
(kN) (kN) (kNm) (kNm)
negative Upwards is
positive

2 -0.00 -647.92 0.00 -0.00 0.00


3 -0.00 -647.94 0.00 0.00 0.00
4 0.00 -647.96 0.00 0.00 -0.00
5 0.00 -647.93 0.00 0.00 -0.00
6 0.00 -647.93 0.00 0.00 -0.00
7 0.00 -647.91 -0.00 -0.00 -0.00
8 -0.00 -647.98 -0.00 -0.00 0.00
9 -0.00 -647.92 -0.00 -0.00 0.00

Load Case No 8: WIND LOAD

Load Type : Primary

Serviceability Factor : 1.00

Design Factor : 1.00

Self Weight Factor : 1.00

Column Reactions Applied as Loads on the Mat


For the loads shown in this table, the sign convention is the same as that for JOINT LOADS in STAAD.Pro when global Y is the vertical
axis.

Fy
(kN)
Fx Fz Mx Mz
NODE NO. Downwards is
(kN) (kN) (kNm) (kNm)
negative Upwards is
positive

2 0.01 -49.06 -0.04 0.87 0.92


3 0.02 -4.32 -0.02 0.90 0.90
4 0.04 -49.06 -0.01 0.92 0.87
5 0.04 -161.13 0.03 0.99 0.87
6 -0.00 -263.16 0.05 1.01 0.94
7 -0.03 -303.97 0.03 0.99 0.99
8 -0.05 -263.16 0.00 0.94 1.01
9 -0.03 -161.13 -0.04 0.87 0.99

Load Combinations

file:///D:/Shreejay%20Projects/Staad%20Projects/Elevated%20Circular%20Water%20Tan... 4/21/2021
Mat Foundation Design Page 3 of 12

Load Case No 1001: SL:1.000 x DL


Load Type : Service
Serviceability Factor : 1.00
Design Factor : 0.00
Code :

Included Primary Load Case Factor


DEAD LOAD 1.00

1002: SL:1.000 x DL+1.000


Load Case No
x LL
Load Type : Service
Serviceability Factor : 1.00
Design Factor : 0.00
Code :

Included Primary Load Case Factor


DEAD LOAD 1.00
LIVE LOAD 1.00

1003: SL:1.000 x DL+1.000


Load Case No
x WLX
Load Type : Service
Serviceability Factor : 1.00
Design Factor : 0.00
Code :

Included Primary Load Case Factor


DEAD LOAD 1.00
WIND LOAD 1.00

Load Case No 1004: SL:1.000 x DL


Load Type : Service
Serviceability Factor : 1.00
Design Factor : 0.00
Code :

Included Primary Load Case Factor


DEAD LOAD 1.00

1005: SL:1.000 x DL+-1.000


Load Case No
x WLX
Load Type : Service
Serviceability Factor : 1.00
Design Factor : 0.00
Code :

Included Primary Load Case Factor


DEAD LOAD 1.00
WIND LOAD -1.00

Load Case No 1006: SL:1.000 x DL


Load Type : Service
Serviceability Factor : 1.00
Design Factor : 0.00
Code :

Included Primary Load Case Factor


DEAD LOAD 1.00

Load Case No 1008: SL:1.000 x DL


Load Type : Service
Serviceability Factor : 1.00
Design Factor : 0.00
Code :

Included Primary Load Case Factor


DEAD LOAD 1.00

Load Case No 1010: SL:1.000 x DL


Load Type : Service
Serviceability Factor : 1.00
Design Factor : 0.00
Code :

Included Primary Load Case Factor


DEAD LOAD 1.00

1011: SL:1.000 x DL+0.800


Load Case No
x LL+0.800 x WLX
Load Type : Service

file:///D:/Shreejay%20Projects/Staad%20Projects/Elevated%20Circular%20Water%20Tan... 4/21/2021
Mat Foundation Design Page 4 of 12

Serviceability Factor : 1.00


Design Factor : 0.00
Code :

Included Primary Load Case Factor


DEAD LOAD 1.00
LIVE LOAD 0.80
WIND LOAD 0.80

1012: SL:1.000 x DL+0.800


Load Case No
x LL
Load Type : Service
Serviceability Factor : 1.00
Design Factor : 0.00
Code :

Included Primary Load Case Factor


DEAD LOAD 1.00
LIVE LOAD 0.80

1013: SL:1.000 x DL+0.800


Load Case No
x LL+-0.800 x WLX
Load Type : Service
Serviceability Factor : 1.00
Design Factor : 0.00
Code :

Included Primary Load Case Factor


DEAD LOAD 1.00
LIVE LOAD 0.80
WIND LOAD -0.80

1014: SL:1.000 x DL+0.800


Load Case No
x LL
Load Type : Service
Serviceability Factor : 1.00
Design Factor : 0.00
Code :

Included Primary Load Case Factor


DEAD LOAD 1.00
LIVE LOAD 0.80

1016: SL:1.000 x DL+0.800


Load Case No
x LL
Load Type : Service
Serviceability Factor : 1.00
Design Factor : 0.00
Code :

Included Primary Load Case Factor


DEAD LOAD 1.00
LIVE LOAD 0.80

1018: SL:1.000 x DL+0.800


Load Case No
x LL
Load Type : Service
Serviceability Factor : 1.00
Design Factor : 0.00
Code :

Included Primary Load Case Factor


DEAD LOAD 1.00
LIVE LOAD 0.80

1019: SL:0.900 x DL+1.000


Load Case No
x WLX
Load Type : Service
Serviceability Factor : 1.00
Design Factor : 0.00
Code :

Included Primary Load Case Factor


DEAD LOAD 0.90
WIND LOAD 1.00

Load Case No 1020: SL:0.900 x DL


Load Type : Service
Serviceability Factor : 1.00
Design Factor : 0.00
Code :

file:///D:/Shreejay%20Projects/Staad%20Projects/Elevated%20Circular%20Water%20Tan... 4/21/2021
Mat Foundation Design Page 5 of 12

Included Primary Load Case Factor


DEAD LOAD 0.90

1021: SL:0.900 x DL+-1.000


Load Case No
x WLX
Load Type : Service
Serviceability Factor : 1.00
Design Factor : 0.00
Code :

Included Primary Load Case Factor


DEAD LOAD 0.90
WIND LOAD -1.00

Load Case No 1022: SL:0.900 x DL


Load Type : Service
Serviceability Factor : 1.00
Design Factor : 0.00
Code :

Included Primary Load Case Factor


DEAD LOAD 0.90

Load Case No 1024: SL:0.900 x DL


Load Type : Service
Serviceability Factor : 1.00
Design Factor : 0.00
Code :

Included Primary Load Case Factor


DEAD LOAD 0.90

Load Case No 1026: SL:0.900 x DL


Load Type : Service
Serviceability Factor : 1.00
Design Factor : 0.00
Code :

Included Primary Load Case Factor


DEAD LOAD 0.90

Load Case No 2001: UL:1.500 x DL


Load Type : Ultimate
Serviceability Factor : 0.00
Design Factor : 1.00
Code :

Included Primary Load Case Factor


DEAD LOAD 1.50

2002: UL:1.500 x DL+1.500


Load Case No
x LL
Load Type : Ultimate
Serviceability Factor : 0.00
Design Factor : 1.00
Code :

Included Primary Load Case Factor


DEAD LOAD 1.50
LIVE LOAD 1.50

2011: UL:1.200 x DL+1.200


Load Case No
x LL+1.200 x WLX
Load Type : Ultimate
Serviceability Factor : 0.00
Design Factor : 1.00
Code :

Included Primary Load Case Factor


DEAD LOAD 1.20
LIVE LOAD 1.20
WIND LOAD 1.20

2012: UL:1.200 x DL+1.200


Load Case No
x LL
Load Type : Ultimate
Serviceability Factor : 0.00
Design Factor : 1.00
Code :

Included Primary Load Case Factor

file:///D:/Shreejay%20Projects/Staad%20Projects/Elevated%20Circular%20Water%20Tan... 4/21/2021
Mat Foundation Design Page 6 of 12

DEAD LOAD 1.20


LIVE LOAD 1.20

2014: UL:1.200 x DL+1.200


Load Case No
x LL
Load Type : Ultimate
Serviceability Factor : 0.00
Design Factor : 1.00
Code :

Included Primary Load Case Factor


DEAD LOAD 1.20
LIVE LOAD 1.20

2019: UL:0.900 x DL+1.500


Load Case No
x WLX
Load Type : Ultimate
Serviceability Factor : 0.00
Design Factor : 1.00
Code :

Included Primary Load Case Factor


DEAD LOAD 0.90
WIND LOAD 1.50

Load Case No 2020: UL:0.900 x DL


Load Type : Ultimate
Serviceability Factor : 0.00
Design Factor : 1.00
Code :

Included Primary Load Case Factor


DEAD LOAD 0.90

Slab and Soil Properties

Thickness
Region Material Unit Weight
(m)
Outer 0.50 Concrete 24.00 kN/m3

Soil Details

Boundary Subgrade Modulus Soil Height Above Mat Soil Density


Outer 30000.00kN/m2/m 0.00m 18.00kN/m3

Mat Geometry

Boundary Name : Inner


Node No X Coor(m) Y Coor(m) Z Coor(m)
1 1.50 0.00 0.00
2 1.47 0.00 0.29
3 1.39 0.00 0.56
4 1.26 0.00 0.82
5 1.08 0.00 1.04
6 0.86 0.00 1.23
7 0.61 0.00 1.37
8 0.34 0.00 1.46
9 0.05 0.00 1.50
10 -0.23 0.00 1.48
11 -0.51 0.00 1.41
12 -0.77 0.00 1.29
13 -1.00 0.00 1.11
14 -1.20 0.00 0.90
15 -1.35 0.00 0.66
16 -1.45 0.00 0.39
17 -1.50 0.00 0.10
18 -1.49 0.00 -0.18
19 -1.43 0.00 -0.46
20 -1.31 0.00 -0.73
21 -1.15 0.00 -0.96
22 -0.94 0.00 -1.17
23 -0.70 0.00 -1.32
24 -0.44 0.00 -1.43

file:///D:/Shreejay%20Projects/Staad%20Projects/Elevated%20Circular%20Water%20Tan... 4/21/2021
Mat Foundation Design Page 7 of 12

Node No X Coor(m) Y Coor(m) Z Coor(m)


25 -0.16 0.00 -1.49
26 0.13 0.00 -1.49
27 0.41 0.00 -1.44
28 0.68 0.00 -1.34
29 0.92 0.00 -1.18
30 1.13 0.00 -0.98
31 1.30 0.00 -0.75
32 1.42 0.00 -0.49
Boundary Name : Outer
Node No X Coor(m) Y Coor(m) Z Coor(m)
33 4.50 0.00 0.00
34 4.42 0.00 0.86
35 4.17 0.00 1.69
36 3.77 0.00 2.45
37 3.24 0.00 3.13
38 2.58 0.00 3.69
39 1.83 0.00 4.11
40 1.01 0.00 4.38
41 0.16 0.00 4.50
42 -0.70 0.00 4.44
43 -1.54 0.00 4.23
44 -2.32 0.00 3.86
45 -3.01 0.00 3.34
46 -3.59 0.00 2.71
47 -4.04 0.00 1.97
48 -4.35 0.00 1.17
49 -4.49 0.00 0.31
50 -4.47 0.00 -0.55
51 -4.28 0.00 -1.39
52 -3.94 0.00 -2.18
53 -3.45 0.00 -2.89
54 -2.83 0.00 -3.50
55 -2.11 0.00 -3.97
56 -1.32 0.00 -4.30
57 -0.47 0.00 -4.48
58 0.39 0.00 -4.48
59 1.24 0.00 -4.33
60 2.04 0.00 -4.01
61 2.77 0.00 -3.55
62 3.40 0.00 -2.95
63 3.90 0.00 -2.25
64 4.25 0.00 -1.47

Analysis Results

Node Displacement Summary

Rx Ry Rz
- Node Number Load Case Dx(mm) Dy(mm) Dz(mm)
(Rad) (Rad) (Rad)

Max Dx 1 5 0.00 -3.43 0.00 0.00 0.00 -0.00


Max Dy 396 8 0.00 -0.33 0.00 0.00 0.00 0.00
Max Dz 1 5 0.00 -3.43 0.00 0.00 0.00 -0.00
Max Rx 135 2011 0.00 -3.66 0.00 0.00 0.00 0.00
Max Ry 1 5 0.00 -3.43 0.00 0.00 0.00 -0.00
Max Rz 226 2011 0.00 -3.64 0.00 0.00 0.00 0.00
Min Dx 1 5 0.00 -3.43 0.00 0.00 0.00 -0.00
Min Dy 79 2011 0.00 -5.79 0.00 -0.00 0.00 0.00
Min Dz 1 5 0.00 -3.43 0.00 0.00 0.00 -0.00
Min Rx 244 2002 0.00 -4.28 0.00 -0.00 0.00 0.00
Min Ry 1 5 0.00 -3.43 0.00 0.00 0.00 -0.00
Min Rz 440 2002 0.00 -4.29 0.00 -0.00 0.00 -0.00

Plate Stress Summary

file:///D:/Shreejay%20Projects/Staad%20Projects/Elevated%20Circular%20Water%20Tan... 4/21/2021
Mat Foundation Design Page 8 of 12

SQx SQy Sx Sy Sxy Mx My Mxy


- Plate Load Case
(kN/m2 ) (kN/m2) (kN/m2) (kN/m2) (kN/m2) (kN-m/m) (kN-m/m) (kN-m/m)

Max SQX 145 2011 442.71 58.86 0.00 0.00 0.00 65.09 88.11 2.06
Max SQY 565 2011 86.19 459.79 0.00 0.00 0.00 91.77 66.96 0.44
Max SX 1 5 19.03 -87.80 0.00 0.00 0.00 14.59 21.74 -0.20
Max SY 1 5 19.03 -87.80 0.00 0.00 0.00 14.59 21.74 -0.20
Max SXY 1 5 19.03 -87.80 0.00 0.00 0.00 14.59 21.74 -0.20
Max MX 203 2011 -764.78 -619.79 0.00 0.00 0.00 186.31 107.87 14.65
Max MY 197 2011 -272.85 -969.76 0.00 0.00 0.00 110.16 189.60 -6.08
Max MXY 350 2011 -291.65 4.30 0.00 0.00 0.00 84.95 62.48 32.71
Min SQX 564 2011 -914.30 -690.94 0.00 0.00 0.00 152.87 133.71 28.52
Min SQY 197 2011 -272.85 -969.76 0.00 0.00 0.00 110.16 189.60 -6.08
Min SX 1 5 19.03 -87.80 0.00 0.00 0.00 14.59 21.74 -0.20
Min SY 1 5 19.03 -87.80 0.00 0.00 0.00 14.59 21.74 -0.20
Min SXY 1 5 19.03 -87.80 0.00 0.00 0.00 14.59 21.74 -0.20
Min MX 141 8 7.80 -19.97 0.00 0.00 0.00 -1.46 4.35 0.08
Min MY 190 8 -13.14 -4.19 0.00 0.00 0.00 3.96 -1.28 1.01
Min MXY 116 2011 -801.62 -126.44 0.00 0.00 0.00 149.39 114.25 -33.13

Soil Pressure Summary for Service Loads

Base Pressure
- Node X-Coor(m) Y-Coor(m) Z-Coor(m) Load Case
(kN/m2)
Maximum Base
79 -1.54 0.00 1.69 1003 142.54
Pressure
Minimum Base
396 3.40 0.00 -2.95 8 9.85
Pressure

Contact Area Summary

Load Case Area in Contact(m2) % of Total Area Area out of Contact(m2) % of Total Area
5 56.17 100.00 0.00 0.00
6 56.17 100.00 0.00 0.00
7 56.17 100.00 0.00 0.00
8 56.17 100.00 0.00 0.00
1001 56.17 100.00 0.00 0.00
1002 56.17 100.00 0.00 0.00
1003 56.17 100.00 0.00 0.00
1004 56.17 100.00 0.00 0.00
1005 56.17 100.00 0.00 0.00
1006 56.17 100.00 0.00 0.00
1008 56.17 100.00 0.00 0.00
1010 56.17 100.00 0.00 0.00
1011 56.17 100.00 0.00 0.00
1012 56.17 100.00 0.00 0.00
1013 56.17 100.00 0.00 0.00
1014 56.17 100.00 0.00 0.00
1016 56.17 100.00 0.00 0.00
1018 56.17 100.00 0.00 0.00
1019 56.17 100.00 0.00 0.00
1020 56.17 100.00 0.00 0.00
1021 56.17 100.00 0.00 0.00
1022 56.17 100.00 0.00 0.00
1024 56.17 100.00 0.00 0.00
1026 56.17 100.00 0.00 0.00
2001 56.17 100.00 0.00 0.00
2002 56.17 100.00 0.00 0.00
2011 56.17 100.00 0.00 0.00
2012 56.17 100.00 0.00 0.00
2014 56.17 100.00 0.00 0.00
2019 56.17 100.00 0.00 0.00
2020 56.17 100.00 0.00 0.00

file:///D:/Shreejay%20Projects/Staad%20Projects/Elevated%20Circular%20Water%20Tan... 4/21/2021
Mat Foundation Design Page 9 of 12

Sliding Check

Sliding Force, Fx Sliding Force, Fz Resisting Force FOS(x) FOS(z)


Load Case No
(kN) (kN) (kN) (Along X Direction) (Along Z Direction)
5 -0.00 0.00 2090.45 N/A N/A
6 0.00 -0.00 408.70 N/A N/A
7 -0.00 0.00 2435.56 N/A N/A
8 -0.00 0.00 864.16 N/A N/A
1001 -0.00 0.00 2090.45 N/A N/A
1002 0.00 0.00 2136.99 N/A N/A
1003 -0.00 0.00 2592.45 N/A N/A
1004 -0.00 0.00 2090.45 N/A N/A
1005 0.00 0.00 1588.45 N/A N/A
1006 -0.00 0.00 2090.45 N/A N/A
1008 -0.00 0.00 2090.45 N/A N/A
1010 -0.00 0.00 2090.45 N/A N/A
1011 -0.00 0.00 2529.29 N/A N/A
1012 0.00 0.00 2127.69 N/A N/A
1013 0.00 -0.00 1726.09 N/A N/A
1014 0.00 0.00 2127.69 N/A N/A
1016 0.00 0.00 2127.69 N/A N/A
1018 0.00 0.00 2127.69 N/A N/A
1019 -0.00 0.00 2383.41 N/A N/A
1020 -0.00 0.00 1881.41 N/A N/A
1021 0.00 -0.00 1379.41 N/A N/A
1022 -0.00 0.00 1881.41 N/A N/A
1024 -0.00 0.00 1881.41 N/A N/A
1026 -0.00 0.00 1881.41 N/A N/A

Overturning Check

Distance to Distance to
Critical Critical Overturning Overturning Resisting Resisting FOS(x) FOS(z)
Load Case
Location Location Moment, Mx Moment, Mz Moment, Rx Moment, Rz (About X (About Z
No
Along X Along Z (kNm) (kNm) (kNm) (kNm) Direction) Direction)
(m) (m)
5 4.50 4.50 0.00 -0.00 22461.73 22477.86 N/A 736978875.19
6 4.50 -4.48 -0.00 -0.00 3543.16 3558.51 N/A N/A
7 -4.49 4.50 0.00 0.00 -26341.71 -26291.57 578938734.73 273870579.74
8 -4.49 4.50 7.50 7.50 -7396.69 -7378.93 986.38 984.01
1001 4.50 4.50 0.00 -0.00 22461.73 22477.86 N/A 736978875.19
1002 4.50 4.50 0.00 -0.00 22985.00 23001.45 N/A 676513167.10
1003 -4.49 4.50 7.50 7.50 -26827.75 -26774.38 3577.59 3570.50
1004 4.50 4.50 0.00 -0.00 22461.73 22477.86 N/A 736978875.19
1005 4.50 -4.48 -7.50 -7.50 15486.84 15552.54 2065.24 2073.99
1006 4.50 4.50 0.00 -0.00 22461.73 22477.86 N/A 736978875.19
1008 4.50 4.50 0.00 -0.00 22461.73 22477.86 N/A 736978875.19
1010 4.50 4.50 0.00 -0.00 22461.73 22477.86 N/A 736978875.19
1011 -4.49 4.50 6.00 6.00 -26373.16 -26321.09 4396.21 4387.56
1012 4.50 4.50 0.00 -0.00 22880.35 22896.73 N/A 687589470.70
1013 4.50 -4.48 -6.00 -6.00 17284.91 17356.47 2881.27 2893.18
1014 4.50 4.50 0.00 -0.00 22880.35 22896.73 N/A 687589470.70
1016 4.50 4.50 0.00 -0.00 22880.35 22896.73 N/A 687589470.70
1018 4.50 4.50 0.00 -0.00 22880.35 22896.73 N/A 687589470.70
1019 -4.49 4.50 7.50 7.50 -24581.58 -24532.51 3278.05 3271.53
1020 4.50 4.50 0.00 -0.00 20215.56 20230.08 N/A 736978875.19
1021 4.50 -4.48 -7.50 -7.50 13247.77 13304.75 1766.65 1774.24
1022 4.50 4.50 0.00 -0.00 20215.56 20230.08 N/A 736978875.19
1024 4.50 4.50 0.00 -0.00 20215.56 20230.08 N/A 736978875.19
1026 4.50 4.50 0.00 -0.00 20215.56 20230.08 N/A 736978875.19

Mat Self Weight (Excluding Pedestal Wt.) = 673.97 kN

Centre of Gravity of Mat (From Origin) = {-0.00, 0.00, 0.00} m

Static Equilibrium Mismatch Report

No result of this type is applicable for this model.

Punching Shear Check

file:///D:/Shreejay%20Projects/Staad%20Projects/Elevated%20Circular%20Water%20Tan... 4/21/2021
Mat Foundation Design Page 10 of 12

Column No. Load Case Service Stress (kN/m) Corner 1 (kN/m) Corner 2 (kN/m) Corner 3 (kN/m) Corner 4 (kN/m) Design Status
2 2002 1118.03 -341.26 -340.18 -340.18 -341.26 Pass
3 2002 1118.03 -341.49 -340.72 -339.96 -340.72 Pass
4 2002 1118.03 -341.27 -341.27 -340.18 -340.19 Pass
5 2011 1118.03 -349.84 -352.26 -353.71 -351.29 Pass
6 2011 1118.03 -399.45 -402.27 -404.37 -401.56 Pass
7 2011 1118.03 -419.29 -421.96 -424.63 -421.96 Pass
8 2011 1118.03 -399.47 -401.57 -404.38 -402.28 Pass
9 2011 1118.03 -349.83 -351.29 -353.70 -352.25 Pass

Design Parameters

Min Max
Top Bottom Pedestal Pedestal Min Max Wood and
Panel f 'c Pedestal Bar Bar
fy (kN/m2) Cover Cover Min Bar Max Bar Spacing Spacing Armer
Name (kN/m2) Cover(m) Size Size
(m) (m) Size (mm) Size (mm) (mm) (mm) Moment
(mm) (mm)
Outer 415000.00 25000.00 0.07 0.07 0.00 10 25 10 57 75.00 500.00 Not Used

Design Output

Top of Mat Longitudinal Direction

Zone = 1

Governing Moment (MGOV) = 0.98 (kN-m/m)

Factor
= 0.85

Effective Depth =
= 0.43 (m)

Limit Moment of Resistance


= 635.09 (kNm)
(Mumax) =

MGOV<= Mumax hence, OK

Steel Required

Calculated Area of Steel = 600.00 (mm2)

Minimum Area of Steel = 600.00 (mm2)

Provided Area of Steel = 603.19 (mm2)

Reinforcement Details

Bar No = 16

Maximum Spacing(Smax)(User
= 500.00 (mm)
Specified)

Minimum Spacing(Smin)(User
= 75.00 (mm)
Specified)

Actual Spacing (S) = 330 (mm)

Smin<= S <= Smax

---------------------------------------

Top of Mat Transverse Direction

Zone = 1

Governing Moment (MGOV) = 1.10 (kN-m/m)

For f 'C <4.0

Effective Depth = = 0.43 (m)

file:///D:/Shreejay%20Projects/Staad%20Projects/Elevated%20Circular%20Water%20Tan... 4/21/2021
Mat Foundation Design Page 11 of 12

Limit Moment of Resistance (Mumax) = 635.09 (kNm)

MGOV<= Mumax hence, OK

Steel Required

Calculated Area of Steel = 600.00 (mm2)

Minimum Area of Steel = 600.00 (mm2)

Provided Area of Steel = 603.19 (mm2)

Reinforcement Details

Bar No = 16

Maximum Spacing(Smax)(User Specified) = 500.00 (mm)

Minimum Spacing(Smin)(User Specified) = 75.00 (mm)

Actual Spacing (S) = 330 (mm)

Smin<= S <= Smax

---------------------------------------

Bottom of Mat Longitudinal Direction

Zone = 1

Governing Moment (MGOV) = -237.01 (kN-m/m)

For f 'C <4.0

Effective Depth = = 0.43 (m)

Limit Moment of Resistance (Mumax) = = 635.09 (kNm)

MGOV<= Mumax hence, OK

Steel Required

Calculated Area of Steel = 1662.22 (mm2)

Minimum Area of Steel = 600.00 (mm2)

Provided Area of Steel = 1809.58 (mm2)

Reinforcement Details

Bar No = 16

Maximum Spacing(Smax)(User Specified) = 500.00 (mm)

Minimum Spacing(Smin)(User Specified) = 75.00 (mm)

Actual Spacing (S) = 110 (mm)

Smin<= S <= Smax

---------------------------------------

Bottom of Mat Transverse Direction

Zone = 1

Governing Moment (MGOV) = -244.09 (kN-m/m)

For f 'C <4.0

Effective Depth = = 0.43 (m)

Limit Moment of Resistance (Mumax) = = 635.09 (kNm)

MGOV<= Mumax hence, OK

Steel Required

file:///D:/Shreejay%20Projects/Staad%20Projects/Elevated%20Circular%20Water%20Tan... 4/21/2021
Mat Foundation Design Page 12 of 12

Calculated Area of Steel = 1716.83 (mm2)

Minimum Area of Steel = 600.00 (mm2)

Provided Area of Steel = 1809.58 (mm2)

Reinforcement Details

Bar No = 16

Maximum Spacing(Smax)(User Specified) = 500.00 (mm)

Minimum Spacing(Smin)(User Specified) = 75.00 (mm)

Actual Spacing (S) = 110 (mm)

Smin<= S <= Smax

---------------------------------------

file:///D:/Shreejay%20Projects/Staad%20Projects/Elevated%20Circular%20Water%20Tan... 4/21/2021