SIEMENS [RRABIA ELECTRIC LTO, Equipment Distance Relay Type 7SA522 Installation, Testing and Commissioning Site Report ‘Site Test Report Ne Manufacwer Rated Current Type ‘Auxiliary Voltage MLEB No. CT Ratio = PT Ratio ‘General Functions Selected Distance Protection Power Swing Detection ot Protection for Distance - Protection ‘SOTF ‘Back Up O/C Protection Fault Locator ‘Mechanical Check and Visual Inspection te Destton Fenark “| Check the name plate data according tothe drawings and specications: 2_| Check for transportation damage and correct positioning x] “3 | Veni tightness of extemal wiring Electical Checks te Desiton Fema | Alleonnidions checked according to he wing dagram = “Auxllary power supoly checked for rating and polariy — CT shoring checked indleatons checked [Casing eating checked - = act earthing checked CGontact resistance of tipping and alarm checked Raaeged Functional Test 1- Measurement Injected quantities re i ww anv TA cy SIEMENS Relay Type 75A522 Weasurement a functions. |" primary [secondary | primary | secondary [Cament03 O Current 112 Current 1L3 sia it- positive 12 Negative Voltage ULIE Voltage UL2E Voltage UL3E Voltage UL12 Voltage UL2t 7 Voltage UL3t U0 Ut- positive U2 — Negative ‘Apparent > [power(s) ‘Active power(P) Reactive power(@) Frequency [ Current 114 (Current 112 ‘Current 113 ‘Voltage ULTE Voltage UL2E | Yevalues | Voltage UL3E [Voltage UL12, Pee zs SIEMENS [RRABIA ELECTRIC LTD. Equipment Distance Relay Type 7SA522 Installation, Testing and Commissioning Si Sit Test Report No. Voltage UL Voltage ULSt 300 [Ut positive U2= Nogative z ‘Apparent power(S) Active -power(P) Reactive power(Q) a Frequency, l Power factor Impedance secondary measurement Injected impedance = 6.0 Vr ratio = 1100.1 kv 200 /1 one =a | ealeulated [measured | ~ealoulated | measured | Ror t 5 Xr Re Xe Rls Xia Rls Xt SIEMENS [BRABIA ELECTRIC LT, Equipment Distance Relay Type 7SA522 Installation, Testing and Commissioning Site Report ‘Sita Teot Report Ne. ‘Note injection of2 is from omiron distance but without RIO Wie ofthe relay eating in the retay setting for all zones and Zero sequence compensation factor = 0 inthe tester setting that is rom {ost object parameters then system setings. {you must adust Zero sequence compensation factor 2. Starting of Distance Protection test Setting Value Phase Current threshold for distance measurement=0.1A = 3lo threshold for neutral current pick up=0.1 Vo threshold for zero sequence voltage pick u 2.1-Earth fault detection 2.4.4. By zero sequence current 3l, Thresholds add (1203 ) sv Before test make sure thet {fuse failure monitor add ( 2910 )} and { voltage failure supervision add (2918 )} are turned off ‘Also before testing raise the setting of 310 Threshold for neutral curent pick up add ( 1203 ) ‘more than phase current threshold for distance measuring add ( 1202 ) Phase Calculated PIR UD, Drop Of Measured Caleulated Teasured RN SN TN [Note the drop off current wil be less than phase current tweshold for distance measuring add (1202). Pick up and drop off values can be done using Ramplng from the Or ron test sot If the current setting = 1A and you want to get the pick up and drop off values you wil simulate the following: First choose the phase that willbe tested from signal 4 Le. Lt ‘The current wil increased from 0 to 1.2A by the step Al within time AT il itreaches a value of pick up at this moment the binary output ofthe relay closes and activate the binary input ofthe fester to be ( high 1 ) and the tester wil save this current value, The current stl Increasing til reaches 1.24 and ater that twill decrease by step Al within ime AT of stato 2 til it reaches a SIEMENS [BRABIA ELECTRIC LTD. Equipment Relay Type 7SA522 ‘curent value at which the relay rope off at tie moment the binary output of the relay opane and the binary input ofthe tester will change its status so the tester save this current drop of valu, ‘Theo current sil decreasing til reaches O and the injection wil stop. For achieving that, flows the instructions as inthe folowing figures. ‘Aor finishing lick stat to run the test ‘When the tests finished You can see the actual values of pickup and drop of from measurements Ramp state 1 and 2 Make the test report Long form from parameters menu then Report Export report from fle menu and choose (ff for saving ito be saved as word fle (Open the test report So Peon setas SIEMENS [BRAGIA ELECTRIC LTD, Equipment Distance Relay Type 7SA522 Installation, Testing and Commissioning Site Report ‘Sit Test Report No, Paes SIEMENS FRAGIA ELECTRIC LTD. Eauipment Distance Relay Type 7SA522 Installation, Testing and Commissioning Site Report Pa ees SIEMENS [BRABIA ELECTRICLTD. Eauipment Distance Relay Type 7SA522 Installation, Testing and Commissionin, Site Test Report No. ite Report SIEMENS TRABIA ELECTRIC LTD. Equipment Distance Relay Type 7SA522 Installation, Testing and Comm ‘Sito Tost Report _ No, (BL ies cde Mos Tat Pena Ween Heb Offa fief els) ciel el >| ix Aue seteo: [Geneall Messner Rp Sale 2 fe ion rate Tae Aa Dow ae SIEMENS [BRABIA ELECTRICLTD. Equipment Distance Relay Type 7SA522 Installation, Testing and Commissioning Site Report Silo Test Report No, SIEMENS Distance Relay Type 7SA522 Installation, Testing and Commissioning Site Report Site Test Report No. HII ang et Yap Stepan sise Fi setos, SIEMENS [RRAGIA ELECTIUC LTD. Equipment Distance Relay Type 7SA522 Installation, Testing and Commissioning Site Report ‘Site Test Report No. Tama} oniaval 0400s] 07000 ae] “Taicn a| oaoo0 || -oateo A| —0x003-0,000 Az] essuenents Ra Site 2=-——— Now te Tole Toe ht paws porwa Too sot 502 SIEMENS Distance Relay Type 7SA522 Installation, Testing and Commissioning Site Report __ ‘Ste Test Repot No. 2.4.2: By zoro sequence current 3l, Thresholds and 3Vo Threshold ad (1204 ) Before test make sure that {fuse fallure monitor adé (2810) } and {voltage falure supervision add (2915) } are tuned of. Inject single phase current more than the seting of 310 Threshold for neutral curent pick up add (1208 ) and single phase voltage less than 3U, threshold zero sequence voltage pick up add (1208) then raise the voltage not gradualy but shot til the relay picks up. Then decrease the (Stage by shot not gradually til the relay drops off. Pickup 30 Caleulated Measured 2.2. Phase fault detection add ( 1202 ) [—phoe Pickup Drop OF Calculated Measured Caleulaied Measured RS | ST TR i Inject single phase current you you must raise the seting OF{ phase current thrSshold Tor fstance measuring add ( 1202 )} more than the setting of (310 Thrashold for neutral current pick up add (1203 J} Note you can get the pickup and drop off values by RAMPING as in the case of zero sequence current threshold. But you must choose signal line to line. (IL L2) 3-Zones reach & Time Testing [Fone Feat ypes ime seting |g RN] YN [BN RY | YS] BR | Re i SIEMENS [BRABIA ELECTRIC LTO. Equipment Distance Relay Type 7SA522 Installation, Testing and Commissioning Site Report Report No. 5 — 7 71 i]o T Bs wb 25. |X 3 TSR T 2 fos —| a 35 |x Flos R wk 5 |x _ ~ {1S IR] at ox = |R rc — E las [ : ae 0 |x 7 |® - — } |x q [2s - g 7 IR nil [efx Note: you may find the trip time of relay arcund axigin not accurate. if you face that you must raise the test current to 2 A that is the real simulation for these faults near V.T You can check the reach and the times ofthe distance relay automatically by using the OMICRON tester by open distance then choose advanced distance % Gpen test object parameter 5: Import the RIO flo of your ela eeting ‘Now the zones characteristic wal ba shown 5: Open settings and adjust (test = 1A) then click on ( extended zone active ) to activate 6- Open check for testing zones time 7- Adjust (Zand Phi of the origin to 0) ‘and ( Length to value more than the max. reach of the outer zone. 20 on) and select {all zones ) thats you wart to check all zone f nat choose the required zone. {If you want to achiowe the tet at One ange ony Le. line angle 85" dst (Angle = 85°) “Thon dick add to and choose the faut ype you want odo the tet fr or you may choose ALL to soect all ype faults. Thon dick OK 9- Open Search for tasting zones reach, 410-Repeat steps 7 and 8 8 Gick start button Page tas SIEMENS [RABIA ELECTRICLTD. Equipment Distance Relay Type 7SA522 Installation, Testing and Commissioning Site Report ‘Ste Test Report No. '& The testis being begin and after tis finished open parameters then Report then select Long form to have ail data inthe test report. 10- Open the test report then expor fle to save it ar SIEMENS [BRABIA ELECTRICLTD. Equipment Distance Relay Type 7SA522 Installation, Testing and Commissioning Steep Site Report ‘Sie Test Report [ER Anes TERESA | o SIEMENS ELECTRIC LTD. Equipment Distance Relay Type 7SA522 Installation, Testing and Commissioning Site Report ‘Sli Test Report No. Papert SIEME! [ARABIA ELECTRIC LTD. Equipment ‘Type 7SAS: SIEMENS [BRABIA ELECTRIC LTD. Equipment Distance Relay Type 7SA522 Installation, Testing and Commissioning Site Report ‘Site Test Repor er SIEMENS IRRABIA ELECTRIC LTD. Equipmert tance Relay Type 7SA522 Installation, Testing and Commissioning Site Report ‘Ste Test Report No, — S/O/Sirv/ Gel clas lelw ix) epe]) 14- If you want to achieve the test within angle band 42 Open cheek or testing zones time. 18. Adjust (Z and Phi ofthe origin to 0) and adjust ( Angl. ‘and ( Length to value more than the max. reach ofthe outer zone ie. 20 chm ) and selec (all zones ) that is if you want to check all one i not choose the required zone. (Or you may not to do that and begin with sequence SIEMENS [BRABIA ELECTRIC LTD. Equipment Distance Relay Type 7SA522 Installation ing and Commissioning Site Report ‘Sit Test Report Ne. "Then open sequence: ‘Adjust (Z and Phi ofthe origin to 0) ‘Adjust start angle to 0 and end angle to 360 and angle stop to 90 adjust ( Length to value more than the max. reach ofthe outer zone i.e. 20 ohm ) ad select (all zones ) thats f you want to check all zone if not choose the required zone. 18- Glick OK 416- Open Search for testing zones reach. ‘17- Repeat stops 13 to 15 18: Click start button 419:naw the zones reach and time willbe tested at the 0 ,90 , 180 , 270 angles. Thats bacause we put start angle © and end ang 360 andthe angle stop is 90. You can choose the angle band you want to do the test within also by changing ‘Start angle and end angle and the angle step 20- After the tacts finished open parameters then Report then select Long form to have all data in the test report. 24--Open the test repor then export file to save it this Is from file, Choose (rtf) when you saving to obtain the test report as word fle SIEMENS ELECTRIC LTO. Equipment ‘olay Type 7SAS: Installation, Testing and Commissioning Site Report ‘Ste Test Report No Paz SIEMENS [RRABIA ELECTRIC LTD. Equipment Distance Relay Type 7SA522 Installation, Testing and Commissioning Site Report ‘Sil Test Repot - No, SIEMENS [RRABIA ELECTRICLTD. Equipment Distance Relay Type 7SA522 Installation, Testing and Commissioning Site Report ‘Site Test Report SIEMENS [BRABIA ELECTRIC LTD. Equipment Distance Relay Type 7SA522 Installation, Tasting anel Commissioning Site Report ‘Sito Test Report _ Peon mtes SIEMENS [BRABIA ELECTRICLTO, Equipment Distance Relay Type 7SA522 Installation, Testing and Commissioning Site Report ‘Ste Test Report No 4% Distance directionality check note: If any zone is adjusted to nondirectional you must reverse It to be able to determine the Lndefined area, Also you must specty LEDS for distance pick up forward add (3718) and distance pick up reverse add (3720). Also you may speciy binary outputs for them, All of that can be done from the Masking from distance general. Using RIO file you can do the test. Fonvard drecion | Undefined area | Reverse dvecion | Undstned area Carin faut [From 120t0-22 | From 121 to 150 | From 151 to -60 | From-61 1-23 Phase to ]Fom to [From to | From to Suit {so yu can chek that by cuck CMC by iecng 6 anded es 28 ange 19° Ursrra amo-0 i On Us 6773 angio 240 = OA Note you must change setting of zoro sequence compensation to zero, so the injected Impedance wil be U,/ |; - When you start Injection tho rota wil pick up in forward then increase the angle to be 20° also the relay wll pick up in forward repest that til the relay does not pick up, at this angle ©, the Undefined zone started record this angle. Go on in increasing the angle til the relay picks up in reverse direction, record this angle = Repeat the test but with angle( - 119° ) ‘When you start injection the relay wil pick up in forward then increase the angle to be - 120° also the relay wil pick up in forward repeat that til the relay does not pick up, at this angle the Undefined zone started record this angle. Go on in increasing the angle tl the relay picks up in reverse direction, revod this angle Distance Teleprotection scheme 5.4- Setting at POT "Note: you have to speciy a binary input for {Distance Tele. Carrier reception channel 1 add (4008}},LEDS for (Distance Tele. Carir signal received add (4054)} and (Distance Tele. Caro signal add (4056) end injection status Relay acon shouldbe — [Ralay acual action Zea without GR |Teip with Zp and CS { Zeavith CR__—|rip with Zig and carior Sond Zit Z,0f 2,072, [No carer send 5.2. Setting at PUTT when you inject Zin Z, you wil find that the relay tips with time T; and sends a carrer signal ‘send . when you injec Z in Zig and there isa cartier recelve you wl find thatthe relay trips with time Ty SIEMENS [BRABIA ELECTRIC LTD. Equipment Distance Relay Type 7SA522 Sito Test Report ___ Ne, Tnjecton status [Relay acion shouldbe Relay actual agion ZinZ: Trip with ime delayT; and carer send. Zw OR [Trip with me dolayTis ZatzZ; or Z30rZ0rZ [No carier send —_ — 5.3. Setting at Blocking When you inject Z in reverse direction, you wil iid that the relay trip with its zone time and sends a carer signal send tothe remote end to black its Zsa zane. when you inject Z in Zio and there is a carrier receive you willfind that ysis blocked ard the relay trips with the Dearest zone ~f_Injecion status | Relay adion should ba Rélay adlual adion Zinreverse | Trip withits ime delay and carrer Za wih OR {54+ Setting at Unblocking You must spect binary input for both ds, Tele. Unblocking : unblock channel 1 add (4030)) ‘And (is. Tele. Unblocking; block channel 1 add (4031). When you inject Zin Ze, you will find that the relay behavior wil be asin the table Unblocking | Unblocking Relay action result __block BI” _| unblock Bt 1 0 Relay blocks Z;g and tps withthe nearest zone 5 1 Relay trips instanlaneously with Zye and sends @ carrier signal send tothe remote end, }- Weak infeed with echo -Echo only CFstatus. [Relay acon shoud be Ralayadion 8 off & carrier receive __| Echo signal send immediatly (G.B on & carrier receive | Echo signal send after ime delay add (2502A) — 2- Echo and trip Status Relay aiion should be [Rela C.B off & carior receive | Echo signal eend immediately without local tip ‘CB on & carrerreceive — | Local trip and echo signal send after time olay add (25028) weak infeed with echo and trip injection status Relay action should be. Relay acual acion_] ‘Weak infeed & CB on & carer [Send echo and local trip by weak infeed receive - Alter time setting add (25028) Page 38 SIEMENS [BRABIA ELECTRIC LTD. Equipment Distance Relay Type 7SA522 Installation, Testing and Commissioning Site Report ‘Site Test Report No. 6.3.1 ~ under voltage pick up for local trip if we apaly one phase voltage less than setting 2505 and we apply the other two phases voltage by rormal value and inject one phase current more than add.1130 and the other two phases by nermal ‘current value AlLthis with carrier receive then the relay will send an echo and weak in feed local trip after the time ‘of add, 2502 but ifthe one phase voltage is more than the add. 2605 the relay will send echo only afior time of ade, 2502 Measured ‘Salting add (Z505A) ‘Setting of open pole treshold add (1 730A) — If the injected phase voltage ofthe faulted phase is more than the setting add (250A) or the injacted ‘current of the fauitod phaso with relay stats echo signal only be sent without local tp. 6.3.2-trip time delay for local trip Be sure of specifying binary oulput of weak infeed tip command L125 add (4245) ‘Seting add (2502A) Measured ime (S) You can measure the time as fllow 4- Active binary input for C.B closed 2+ by using state sequencer by adjusting (the omicron tester) as shown, 23: Use the binary output 1 as cartier receive ‘So when you start the tester the binary output 4 will close atthe same time and the relay wil ve carrer receive so the relay will ond echo and give local tp after the ime delay and the ‘ster wil stop when the relay trips. SIEMENS [BRABIA ELECTRIC LD. Equipment Distance Relay Type 7SA522 Installation, Testing and Commissioning Site Report ‘Sito Test Repo No, Pao SIEMENS [BRABIA ELECTRICLTD, Equipment Distance Relay Type 7SA522 Installation, Testing and Commissioning Site Report ‘Site Test Report No. Sts Sees Ti Sean fee nennn £ Cel 8) a] 80a) Slay) alls) |e sae “Tee onthe ST Sp Tie tr ail 7- Power Swing Raise the time setting of trip delay after power swing blocking add (2007 ) to more than the est time ofthe distance zones, Powor swing operating mode add (2002 ) Relay action — [Azone blocked — Zi, Zi Z2HOckoS Now wih — - _ Trp Ze bodied [No tip with [e? - _ Fp with Zito Z Bedked Tap with Ce 7 ‘Tp wih There are two methods for verifying power swing + using Ramping ‘Open omicron program then choose Ramping ‘Adjust the state 1 and state 2 as inthe picture. SIEMENS [BRABIA ELECTRIC LTD. Equipment Distance Relay Type 7SA522 Installation, Testing and Commissioning Site Report ‘Sie Tost Repod Ne, = 00 rap Rn tae ae pst + Speaify led for {power swing detection ade (4164)} that from masking then power swing + According to (Power swing operating mode add ( 2002 )} = all zones blocked + Start injection you wil find that the Led wil light that means power swing is detected and the all zones of distance are blocked To obtain the rate of impedance change at which the relay does not detect the power swing Papers SIEMENS [RRABIA ELECTRIC LTO, Equipment Distance Relay Type 7SA522 increase the At ite bit and start injection and repeat tat til the relay does not recognize the ‘power swing. You may change AV. So dz/dt= AVI(1At) For dz / dt> 6.5 the relay detect power swing For dz / dt < 6.5 the relay doesn't detect power swing That means, when the locus of the impedance stays and does not move for time inthe zone, the relay recognize This case as fault, but if locus ofthe impedance does not stay for time in the zone: And moves quickly to another locus the relay recognize This case as a power swing. = To very the other selections of (Power swing operating mode add ( 2002 )}i wil be dificult because you wil find that the trip time wil nt be accurate that is because of the traveling of tho impedance locus through zones til it reaches the appropriate zone for tripping. Because of this reason we have to use state sequencer for verifying power swing detection ‘And (Power suing operating mode add ( 2002 }. 2 Using stato sequencer ‘At first you must put the zero sequence compensation factor inthe relay By adjusting the first four states the relay wil detect the power swing Slate 1 is adjusted so thatthe impedance is out ofthe the outer zane seting in R axis “The next states are adjusted so that he Impedance entered the zones and dont stay for more ‘Time then the relay will detect power swing ‘Also you can change the Duration of the impedance locus staying in the zone to obtain the rate of impedance change At Which the relay will nt dotact power swing, oO Note: injected curre ‘AV =0.8 ohm So dz/dt= AV/(1At) For dz/ dt> 6.5 the relay detect power swing For dz/ dt <6.5 the relay doesn't detect power swing A ~ To verily the other selections of (Power swing operating mode add ( 2002 } twill be done by adding the fith state but you must adjust its parameters so thatthe impedance equal value in the required zone. Also you must put the time ofthis state more than tha time of The required zone, SIEMENS [BRABIA ELECTRIC LTD. Equipment Distance Relay Type 7SA522 Installation, Testing and Commissioning Site Report Site Test Report Sav) Sn" ceme| 1300 ‘00 outa 1a va SIEMENS [RRABIA ELECTRIC LTD. Equipment Distance Relay Type 7SA522 Installation, Testing and Commissioning Site Report ‘Site Test Report No. 8- Back Up Over Current Protectio Notes whi stages. (Emergency) testing any stage of over current you have to raise the setting of the othe A-Inverse over current 8.1.1- For IEC curve add (2660) is normal curve Solting: p> pick up add (2640)= A, Tip time dial adet2641)= see = Pek Up Bap or} ee Seng asad Cait Measured RY - — | Ye BR Time RY_[_YS_[ BA] Catelated ime (see, inj Curent= 2], = 1A | 1A tA | 1A 20 se for Measured time "sec | 02 inj, Curent= 452A [3A [2 AT 2A To see for ‘Measured ine "see — T=04 inj. Curent=6_b= 3 A~| 3A | 3 A~]3A Tee for ‘Measured tine see ~ 720.08 T=0A4Te/(Wie)-1} (SEC), WHERE 2 TTRITIME ~ Tp: SETTING VALUE TIME MULTPLIER ip. SETTING VALUE CURRENT 1! FAULT CURRENT Setting: Sap pick up add (2650) = A, TS lp ptime dia add(2652) = eae ra Pek Up Drop OF Sota Measured Caioaated Measured RN Ya (oan Page ates SIEMENS [BRABIA ELECTRIC LTD. Equipment Distance Relay Type 7SA522 Installation, Testing and Commissioning Site Report Ste Test Repot = Tine = RY Ye BR] Gaiaiaioa time (see) inj. Cure 7A TR FA [20 sector Measured tine 202 ZA[ 3A 2A [05 cector | — T=04 W.Curen'=6 = 3A | 3A oA ZA |02 sector Measured tine i T2005 TH0A6T/4( ue %2—1} (SEC), - WHERE: TE TRIP TIME ‘Tp SETTING VALUE TIME MULTPLIER Ip: SETTING VALUE CURRENT FAULT CURRENT 8.4.2For IEC curve add (2860) Is vory inverse curve Setting: > pick up add (2640) A, Thtine dal addi264t)= see xe Pick Drop OF : Phas Sang Wieasured ‘Caialated Tioasured RY 7 ve - BR time 7 RY YS BR] Caleuiated ime Tq Curent= 71, = 1A Tk nN a Measured tine" se0 - inj. Curent = 41g= 2A PA za ea Measured time" — 860 in. Curent = 6 = 3 A 3a ZA | SA [0.738 seater Measured tine" s80 20.05 T=13.5Tp/ {(Wip)—1) (SEC), WHERE: T:TRIP TIME Tp: SETTING VALUE TIME MULTPLIER Ip. SETTING VALUE CURRENT NPAULT CURRENT SIEMENS [RRABIA ELECTRIC LTD. Equipment Distance Relay Type 7SA522 Installation, Testing and Commissioning Site Report__ Sie Test Repo No. ‘Setting: kp pick up add (2650) = 3 lo ptimo dial add(26s2) = sec = PickUp Diop Of 7 °_|[—Seting [Measured Calculated Measured Ra. a YN. BN. = — a Time _ RY ve ER | Calculated time inj. Curent= 2], = 1A TARR 27 ss for Measured me" sec — T=02 ‘nj, Curent= 4,5 2A | 2 A 2A 2A | 043 sector Measured ime "sec | I 201 [inj Cunent=6 = 3 A SA oA TA [0.135 see for Measured time —s00 T=0.05 T#13.5 Tp/{(Mp)—1} (SEC), WHERE: T:TRIP TIME ‘Tp: SETTING VALUE TIME MULTPLIER Ip, SETTING VALUE CURRENT SPAULT CURRENT ) 18.1.3: For IEC curve add (2660) is extremely curve Setting: ly> pickup add (2640)= A, T ytime dial adei2641)= sec Phase Ta PER Up Drop OF “Sartng Measured Calaated Heasured RY = YB. BR Time 7 RY YE BR] Calculated tne LL _ se SIEMENS BRABIAELECTHIC LTD. Equipment Distance Relay Type 7SA522 Installation, Testing and Commissioning Site Report. Sie Test Repod No. i Curent= 21, = 10 TA TA TA__] Sa secTor Measured time 60 2 Inj. Curent= 4q= 2A [2 A Ze (059 sec for ‘Measured timo "soe Te04 inj. Curent=6 = 3 A__[ 3A EES 0.114 sector ‘Measured time see T2005 80 Te/{(We 81} (SEC), WHERE: T:TRIPTIME: Tp: SETTING VALUE TIME MULTPLIER ) Ip: SETTING VALUE CURRENT USFAULT CURRENT Selting: Slop pick up ad (2650) A, T3loptime dial ade(2652) = see = Pick Up Drop Of Seting Measited Calculated Measured RN YN = | BN Time RY YS BR | Calculated time ij. Curent= 21, = 1A TAK TA |53 sector] >) [Measured fme 2 Inj. Curent = 47 2% 2A ZA |053 sector ‘Measured time 4 [Isl Curent = 6 1 3A oA BA [0.114 sector ‘Measured time: T=80 To! (Mle }¥=1} (SEC), WHERE: T:TRIPTIME ‘Tp: SETTING VALUE TIME MULTPLIER Ib, SETTING VALUE CURRENT T: FAULT CURRENT Pao 45 SIEMENS [RRABIA ELECTRIC LTD. Equipment Distance Relay Type 7SA522 Installation, Testing and Commissioning Site Report ‘Sie Test Repot Ne. 8.1.4 For EC curve add (2660) is long inverse Setting: > pick up add (2640) A, Tlptime dal add264t)= se = Pick Up —— “Deep OF ‘Seling |“ Measwed__|~Gatouated | Measured RY | Ye Der . J Tine _ RY Ye BR] Caauaied ne in Gurent= 21, = 7A 5 SW Measured tme_" sc qe02 2A | 2 Ko A | 2 Ra sec or 00 201 inj. Curent=6 = 3 A_| 3A 3A SA __|12 sector Measured time" — soo “Koos T=120Tp! {(Wp)=1} (SEC), WHERE: T:TRIPTIME “To: SETTING VALUE TIME MULTPLIER Ip. SETTING VALUE CURRENT 2 PrauurcunRent Soting: Sup pick up add (2850) = _A, TS lop time dial ad2652) = sec Sel Raku Drop OFF —Seting eased Cala assured RN vn 7 BN Time Time Pag ts SIEMENS [BRABIA ELECTRICLYD. Equipment Distance Relay Type 7SA522 Installation, Testing and Commissioning Site Report ‘Site Test Report No. _ = ZI 7A 7a TA] 24sec tor | Measured time T=02 Inj, Curent = 47 ZA ZA 2A |asector [Measured timo soe T=0.4 Inj, Curent= 6 G= 3 A ZA_[ 3A TA__| 142 sector Measurod time s00 T= 0.05 T=120Te/{(Mle)=1} (SEC), WHERE: T:TRIPTIME ‘Tp: SETTING VALUE TIME MULTPLIER Ip, SETTING VALUE CURRENT VSFAULT CURRENT 8.2- low set stage 1> Setting” bn > PEK UP 96d (2620)= A, Tla> time delay add(2621)= see a Operating Ti (5) = Pick Up Diop OF for A Seling | Measured | Calefated | Measured | Saling [Measured RY. | Ys - BR rr Setting: 8lp> pick up add (2622) A, T3lp> ime delay add(2629) = 920 ) Tae Operating Tne) Pick Up Diop OF for A Phase Disp Sailing | Measured | Caleulated | Measured_| —Saling Measured 8.3 high sot stage 1>> Setting: I> pick up add (2610)= A, Tha2> time delay ade(2611)= seo = ass ‘paraiing Tine ey = Fick Up Drop OF for 2lset Sating__|_Messured_| Calculated | measured | Seting | Measured RY SIEMENS [BRAGIA ELECTRICLTD. Equipment Distance Relay Type 7SA522 Installation, Testing and Commissioning Site Report ‘Ste Test Report YS BR ‘Setting: lp >> pick up add (2612) = \ T 3h >> time delay add(2613) sec a ‘Operating Time fe) Pek Up Drop Off for A ‘Seting [Measured | Calculated | Measured | Setting | Measured Phase RN, YeN O [5n 24 STUB Note: you must specify a binary input active low for { Enable I STUB bus function add (7131)) and binary output and led for (OIC - STUB TRIP add (7236). Setting: lyn ® STUB pick up add (2630) A, Thatime delay ade (2631 sec a> STUS ‘Operating Time fe) = Pick Up Diop OF for A, ‘Sefling _|- Measured | Calculated | Measured | Satin | Measured RY, - | YB BR | I — 7 Selting > STUB pick up add (2632) = A, T 3lp STUB time delay add(2633) = sec a> STUB ‘Operating Time (8) — PiekUp Drop OF for A Seting _| Measured | Calculated | Measured | Selig | Measured RY. YN L BN I 9- Switch On to Fault For CB closure recognition add (1134) by binary input manual close only Raise setting of seal in time after manual closure add (1150A ) to 30 see ‘Activate the binary inputs of C.B off and manual close SIEMENS [RRABIA ELECTRIC LTO. Equipment Distance Relay Type 7SA522 Installation, Testing and Commi ‘Site Test Report 19 Site Report 9.4- SOTF associated with distance protection Disable the back up over current protection add (2601 ) Disable the instantancous high speed SOTF OIC add (2404 ) ‘czordng tthe speci zone that wih Isaranoai pater SOTE is sv od (1252) Inject Zin this zone twice one with the activation of the binary inputs of C.B off and manual ose ‘and the other without thera ‘Applied aultin | reassured zone limo (s)_ ithe acivaion ofthe binary inputs of CB affand | 2p manual clos _ _ without the adivation ofthe Binary inputs OF CB off and Za manual lose [with the activation of the binary Inputs of GB off and| "Ze - manual close 2 | Zi cted Note : 4- According to the {recognition of the line closure with add (1134), I itis s ‘to current or voltage or manual close Binary input, For checking SOTF function ‘you must activate binary input of C.8 off and no need to that of manual close. 2 According to the {recognition of the line closure with add (1134), if Itls selected to current flow or manual close Binary input you can check SOTF function without binary Input of manual close but binary input of C.B off must be exist. Wa. SOTF associated with back up overcurrent Disable the distance protection add ( 1201 ) Disabie the instantaneous high speed SOTF O/C ad ( 2404) Inject curent more than the setting {Iph >> pick up add (2610 } twice one withthe activation of the binary inputs of .8 off and marual close and the other without them. Repeat that with {lph> pick up ada (2620) and (lah > pick up add ( 2840) aaaross Setting Pickup | Injected | measure __ ita current (A) | current (A) | ¢ time(s) p> ‘withthe activation of the bit pickup inguts of C.8 off and manual dose ‘add (2610) [without the activation ofthe binary Inguts of C.B off and manual dose SIEMENS [RRABIA ELECTRIC LTD. Equipment Distance Relay Type 7SA522 Installation, Testing and Commissioning Site Report si port No Tph> pick up | withthe activation ofthe binary add ( 2820), | inputs of C.B off nd manual close without the activation ofthe binary [ inputs of C.8 off and manual cose p> plck up withthe activation ofthe binary ‘add (2840) | inputs of C8 off and manual close without the activation of the binary inputs of C.B off and manual close fle when you test any one of current stages you should raise the pick up setting of the others stages ote : 1- According to the {recognition of the line closure with add (1134) if is selected to current or voltage or manual close Binary input, For checking SOTF function ‘you must activate binary input of C.B off and no need to that of man 2- According tothe {recognition ofthe line closure with a Current flow or manual close Binary input you can che Input of manual close but binary input of C.B off must be 9,3- Instantaneous speed SOTF O/C Disable the distance protection add (1201 ) Disable back up over current protection add (2601 ) Inject current more than the seting{ iph >>> pick up add (2404 ) twice one withthe activation of the binary inputs of C.B off and manual close and the other without them “gos ntntncous Nigh spend SOTF OIChas a pve p SOT- Op command L123 tc (428) a0 youu epocty Say cup and at ED fort Me canbe sone fom he ites tom SOT ver caret Ao cat ape nay aul or SOT OF ped up 8 aby ato deny lx op va but et potent Secaoe ie pram Sort indatanoos Sating | Pickup | Tnjected | rneasured (A) | eurent(A) | curent | time(s) ay ‘wih the activation ofthe binary inputs of C.B off and | ‘manual dose without the activation of te binary inputs of C.B off and manual dose SIEMENS [BRABIA ELECTRIC LT, Eauipmont Distance Relay Type 7SA522 Installation, Testing and Commissioning Site Report. Si Tost Repo Ne. Note : 1- According to the (recognition ofthe line closure with add (1424), iit to-current or voltage or manual close Binary input, For checking SOTF function you must activate binary input of C.B off and no need to that of manual close. 2+ According to the {recognition of the line closure with add (1134), if itis selected to ‘current flow or manual close Binary input you can check SOTF function without binary input of manual close but binary input of C.B off must be exist. selected 410- Fuse failure monitoring For voltage fal supervision add (2916) is with current supervision ‘Note: before starting the test you must specify Leds to failure voltage absent add (168) ‘And V.T fuse fallure alarm instantaneous add (170) and V.T fuse failure alarm> 10sec add (169) and distance is blocked add (3652) also you may specify a binary output for V.T fuse fallure alarm> 10sec add (169) and distance is blocked add (3852) to be able measuring the time, all ofthat can be done from the Masking in distance general and measurement supervision. 410-4- For balanced load Ifthe currents balanced in the 3 ~ phase and its amplitude is more than the setting {maximum current threshold I< add (2912A)) and the voltage diference in between any two phases Is more than the setting (minimum voltage threshold U> add (291 1A}, the fuse falure manitor FFM will ‘appear instantaneously with distance blocking 410.1.1- Fuse failure measurement add (2911A) Injected current in 3 phase = 0.2.A [i vtags —g — Picunatage (ITF = threshold U> eda (20114) 3 dlstance biock sating - appear inst oy a 7S WE 8773 S713 EAS 10.1.2. FFM maximum current threshold I< add (29124) Difference vltage fs more than 30 Maximum ourant Biscay sare a) Trad) threshold te add (29128) | T | distance block sotting I Appear inst. SIEMENS [RRABIA ELECTRIC LTD. Equipment Distance Relay Type 7SA522 Installation, Testing and Commissioning Site Report ‘Site Test Report “OTA T 10.1.3. For current less than the sotting of Maximum current threshold I< add (29128) and Difference voltage is more than 30v, FFM will appear after 10 sec with distance: blocking. oO 410.2- For unbalanced load 10.2.1- if the currents unbelanced in the 3- phase and the amplitude ofthe zero sequence Current is more than the setting {maximum current threshold I< add (2912A)} and the voltage c-ifference in between any two phases is moro than the setting (minimum voltage threshold U> ‘tld (2911), the fuse falure monitor FFM and distance blocking will not appear. 10.2.2. Ifthe current is unbalanced in the 3~ phase and the amplitude ofthe zero sequence courtent is less than the setting (maximum current threshold t< add (2042) and the voltage difference in between any two phases Is more than the setting (minimum voltage threshold U> add (2941), the fuse faiure monitor FFM and distance blocking will appear after 10sec. [7] You can verify 10.2.1 and 10.2.2 by injecting single phase current. 10.3- maximum voltage threshold U< (3 phase ) add (29134) 4-You can check that with applying the rormal voltage 3- phase and S-phase curent above the seting of fopen pole threholé add (11208 )} andthe vliage is reicad in the S-phase to lees than the seting{ maximum voltage threshold Us (3 phase) add (2913A} a voltage =psent wil appear fer aime delay seting (ely voltage fale supervision add (29164). [] Injected current = 0.2. ‘Maximum voliage tirechala Pak upvatane FFM and (Ue edd (201A) setting R T distance block | | appearing av ~ —} 2-You can check that with aptying the normal vltag 8 ~ phase and 3- phase curontless than ihe seing of phase sotng threshold fr cstanco maasurement add ( 1202)} andthe votlage is reduced in the 3- phase to equal the value ofthe sting { maximum voltage threshold Us( 3 paso ) ade (2943A)) a FFM wil appear instantaneously o SIEMENS [RRABIA ELECTRICLTO, Equipment Distance Relay Type 7SA522 installation, Testing and Commissioning Site Report __ ‘Se Test Report : Ne, 3. Asin 2 but the current is more than tho setting of {phase setting threshold for distance ‘measurement add ( 1202) }a voltage absent wil appear instantanoously. 14- Fault locator Line length = 6 km Z= 0.152801 km o=a1 RAT YN | BN RY | YS] _BR Injected impedance 1 Rolay reading (Km) [Je injected impedance with angle: 12. Memory test 12.4 Memory time measurement test ‘equance ] Seauencez ‘Sequances Tie wa change Tie oe Va [Weve Jia ie fe [Wa We [ve Te Te eve [ve [ve Te ee aris [aris farsa pez fox [oz fo -]o-[o-o- fe fale je jet 7 aa 00 we [BO = === == = = > Memory time measurement = 12.2 Memory voltage measurement test f Sequence? | Sequence] Sequences Memory voltage measurement = Panes

You might also like