PCSVN2010

Warning Ask a qualified installer or contractor to install this product. Do not try to install the product by yourself.
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
contractor to install those parts and accessories. Use of unauthorised parts and accessories or
improper installation of parts and accessories can result in water or refrigerant leakage, electrical
shock, fire or explosion.
Read the user's manual carefully before using this product. The user's manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any enquiries, please contact your local importer, distributor and/or retailer.

AIR CONDITIONING SYSTEM


Cautions on product corrosion COOLING ONLY [50Hz] ・HEAT PUMP [50Hz]
1. Air conditioners should not be installed in areas where corrosive gases, such as an acidic or alkaline gas, are produced.
2. When installing outdoor units in coastal areas, be sure to contact your local distributor and avoid direct exposure of the units to
sea breezes.

Specifications, designs and other content appearing in this brochure are current as of June 2020 but subject to change without notice.

c All rights reserved 06/20 SS


Designed for use in cafe and restaurants,
retail shops and small offices.

Daikin’s SkyAir series delivers superior comfort and energy performance


for both occupants and building owners.

1 2
Daikin provides your on-demand
inverters with a variety of indoor units

Contents
Lineup P.5-8
RZF, RZA series P.5-6
RZFC series P.7-8

DAIKIN SkyAir Series P.9-16


Energy Saving P.9
Benefits of an Inverter P.10
Smart Airflow Control P.11
Ceiling mounted cassette type Ceiling mounted cassette type Duct connection low static Quick Cooling P.12
(Standard panel with Sensing) (Standard panel) pressure height compact type Durability P.13
Convenient Functions P.14
Design Flexibility P.15
Reuse of Existing Piping P.16

Indoor Unit P.17-44


Ceiling Mounted Cassette type P.17-30
<Round Flow>
Compact Multi Flow P.31-32
Ceiling Mounted Cassette Type
Duct Connection Middle Static P.33-34
Pressure Type
Ceiling Mounted Slim Duct Type P.35-36
Duct Connection Low Static P.37-38
Pressure Width Compact Type
Duct Connection Low Static P.39-40
Pressure Height Compact Type
Compact multi flow Duct connection middle static
Floor standing type Floor Standing Type P.41-42
ceiling mounted cassette type pressure type
Ceiling Suspended Type P.43-44

Outdoor Unit P.45-46

Remote Controller P.47-50

Functions P.51-58
RZF series P.51-52
RZA series P.53-54
RZFC series P.55-56

Specifications P.59-71
RZF series P.59-63
RZA series P.64-67
RZFC series P.68-71
Duct connection low static
Ceiling mounted slim duct type Ceiling suspended type
pressure width compact type Options P.72-76
RZF, RZA series P.72-74
RZFC series P.75-76
3 4
Product Lineup RZF series RZA series

Cooling only
50 60 71 100 125 140
CEILING MOUNTED
CASSETTE TYPE Page
Round Flow 17
Indoor unit FCF50CVM FCF60CVM FCF71CVM FCF100CVM FCF125CVM FCF140CVM
Outdoor unit RZF50CV2V RZF60CV2V RZF71CV2V RZF71CYM RZF100CVM RZF100CYM RZF125CVM RZF125CYM RZF140CVM RZF140CYM
COMPACT MULTI FLOW
CEILING MOUNTED Page
CASSETTE TYPE
Indoor unit FFF50BV1 FFF60BV1 31
Outdoor unit RZF50CV2V RZF60CV2V
DUCT CONNECTION
MIDDLE STATIC Page
PRESSURE TYPE
Indoor unit FBA50BVMA(9) FBA60BVMA (9) FBA71BVMA(9) FBA100BVMA(9) FBA125BVMA(9) FBA140BVMA(9) 33
Outdoor unit RZF50CV2V RZF60CV2V RZF71CV2V RZF71CYM RZF100CVM RZF100CYM RZF125CVM RZF125CYM RZF140CVM RZF140CYM
CEILING MOUNTED
SLIM DUCT TYPE Page
Indoor unit FDF50BV1 FDF60BV1 35
Outdoor unit RZF50CV2V RZF60CV2V
FLOOR STANDING TYPE
Page
Indoor unit FVA50AMVM FVA60AMVM FVA71AMVM FVA100AMVM FVA125AMVM FVA140AMVM 41
Outdoor unit RZF50CV2V RZF60CV2V RZF71CV2V RZF71CYM RZF100CVM RZF100CYM RZF125CVM RZF125CYM RZF140CVM RZF140CYM
CEILING SUSPENDED TYPE
Page
Indoor unit FHA50BVMV FHA60BVMV FHA71BVMV FHA100BVMV FHA125BVMA FHA140BVMA 43
Outdoor unit RZF50CV2V RZF60CV2V RZF71CV2V RZF71CYM RZF100CVM RZF100CYM RZF125CVM RZF125CYM RZF140CVM RZF140CYM

OUTDOOR UNIT

Page
Outdoor unit RZF50CV2V RZF60CV2V RZF71CV2V RZF71CYM RZF100CVM RZF100CYM RZF125CVM RZF125CYM RZF140CVM RZF140CYM
45
1 phase, 3 phase, 1 phase, 3 phase, 1 phase, 3 phase, 1 phase, 3 phase,
Power supply 1 phase, 220V, 50Hz 1 phase, 220V, 50Hz 380-415 / 380V, 220-240 / 220-230V, 380-415 / 380V, 220-240 / 220-230V, 380-415 / 380V, 220-240 / 220-230V, 380-415 / 380V,
220V, 50Hz 50 / 60Hz 50 / 60Hz 50 / 60Hz 50 / 60Hz 50 / 60Hz 50 / 60Hz 50 / 60Hz

Heat Pump
50 60 71 100 125 140
CEILING MOUNTED
CASSETTE TYPE Page
Round Flow 17
Indoor unit FCF50CVM FCF60CVM FCF71CVM FCF100CVM FCF125CVM FCF140CVM
Outdoor unit RZA50DV2V RZA60DV2V RZA71DV1 RZA100DV1 RZA100DY1 RZA125DV1 RZA125DY1 RZA140DV1 RZA140DY1
DUCT CONNECTION
MIDDLE STATIC Page
PRESSURE TYPE
Indoor unit FBA50BVMA(9) FBA60BVMA(9) FBA71BVMA(9) FBA100BVMA(9) FBA125BVMA(9) FBA140BVMA(9) 33
Outdoor unit RZA50DV2V RZA60DV2V RZA71DV1 RZA100DV1 RZA100DY1 RZA125DV1 RZA125DY1 RZA140DV1 RZA140DY1
FLOOR STANDING TYPE
Page
Indoor unit FVA50AMVM FVA60AMVM FVA71AMVM FVA100AMVM FVA125AMVM FVA140AMVM 41
Outdoor unit RZA50DV2V RZA60DV2V RZA71DV1 RZA100DV1 RZA100DY1 RZA125DV1 RZA125DY1 RZA140DV1 RZA140DY1
CEILING SUSPENDED TYPE
Page
Indoor unit FHA50BVMV FHA60BVMV FHA71BVMV FHA100BVMV FHA125BVMA FHA140BVMA 43
Outdoor unit RZA50DV2V RZA60DV2V RZA71DV1 RZA100DV1 RZA100DY1 RZA125DV1 RZA125DY1 RZA140DV1 RZA140DY1

OUTDOOR UNIT
NEW Page
Outdoor unit RZA50DV2V RZA60DV2V RZA71DV1 RZA100DV1 RZA100DY1 RZA125DV1 RZA125DY1 RZA140DV1 RZA140DY1 45
Power supply 1 phase, 220V, 50Hz 1 phase, 220V, 50Hz 1 phase, 220-240V, 50Hz 1 phase, 220-240V, 50Hz 3 phase, 380-415V, 50Hz 1 phase, 220-240V, 50Hz 3 phase, 380-415V, 50Hz 1 phase, 220-240V, 50Hz 3 phase, 380-415V, 50Hz

5 6
Product Lineup RZFC series

Cooling only
40 50 60 71 85 100 125 140
CEILING MOUNTED
CASSETTE TYPE
Round Flow
Page
17

Indoor unit FCFC40DVM FCFC50DVM FCFC60DVM FCFC71DVM FCFC85DVM FCFC100DVM FCFC125DVM FCFC140DVM
Outdoor unit RZFC40DVM RZFC50DVM RZFC60DVM RZFC71DVM RZFC71DY1 RZFC85DVM RZFC85DY1 RZFC100DVM RZFC100DY1 RZFC125DY1 RZFC140DY1

DUCT CONNECTION
MIDDLE STATIC
PRESSURE TYPE
Page
33

Indoor unit FBFC40DVM(9) FBFC50DVM(9) FBFC60DVM(9) FBFC71DVM(9) FBFC85DVM(9) FBFC100DVM(9) FBFC125DVM(9) FBFC140DVM(9)
Outdoor unit RZFC40DVM RZFC50DVM RZFC60DVM RZFC71DVM RZFC71DY1 RZFC85DVM RZFC85DY1 RZFC100DVM RZFC100DY1 RZFC125DY1 RZFC140DY1

DUCT CONNECTION
LOW STATIC PRESSURE
WIDTH COMPACT TYPE
Page
37

Indoor unit FDBF40DV1 FDBF50DV1 FDBF60DV1 FDBF71DV1 FDBF85DV1


Outdoor unit RZFC40DVM RZFC50DVM RZFC60DVM RZFC71DVM RZFC71DY1 RZFC85DVM RZFC85DY1

DUCT CONNECTION
LOW STATIC PRESSURE
HEIGHT COMPACT TYPE
Page
39

Indoor unit FDLF40DV1 FDLF50DV1 FDLF60DV1 FDLF71DV1 FDLF85DV1


Outdoor unit RZFC40DVM RZFC50DVM RZFC60DVM RZFC71DVM RZFC71DY1 RZFC85DVM RZFC85DY1

OUTDOOR UNIT

Page
45
Outdoor unit RZFC40DVM RZFC50DVM RZFC60DVM RZFC71DVM RZFC71DY1 RZFC85DVM RZFC85DY1 RZFC100DVM RZFC100DY1 RZFC125DY1 RZFC140DY1

1 phase, 1 phase, 1 phase, 1 phase, 3 phase, 1 phase, 3 phase, 1 phase, 3 phase,


220-240 / 3 phase, 3 phase,
Power supply 220-240 / 220-230V, 220-240 / 220-230V, 220-240 / 220-230V, 220-240 / 380-415V, 220-240 / 380-415V, 380-415V,
50 / 60Hz 50 / 60Hz 50 / 60Hz 220-230V, 220-230V, 220-230V, 380-415V, 50Hz 380-415V, 50Hz
50 / 60Hz 50Hz 50 / 60Hz 50Hz 50 / 60Hz 50Hz

7 8
New Inverters launched Benefits of an Inverter

Cooling only Why is inverter technology economical?

Heat Pump Inverter system consumes less

unit price + cost of electricity


electricity, and soon recovers Non inverter Inverter
the difference in initial cost.

Total cost =
This results in lower total cost. Inverters save more

Energy Saving energy over time

Recovery point Time

Throughout the cooling season, Daikin’s new Inverter air conditioner can adjust Rated condition
inverter models reduce energy consumption its cooling capacity according to
the cooling load. This results in Non inverter cooling capacity
CSPF values by capacity for cassette models
less power consumption.

Capacity
Load
Inverter RZF-C series R32 <cassette type> On/Off operation
In response to fluctuating cooling load, Non inverter air Lower efficiency Inverter cooling capacity
Inverter RZFC-D series R32 <cassette type>
conditioners repeatedly perform ON (full-power)/OFF
Previous non-inverter series R22 <cassette type> (zero-power) operation. Inverter air conditioners, however,
*CSPF (cooling seasonal performance factor) is a new international operate at optimal cooling capacity according to the Cooling load Partial load area
energy-efficiency criterion calculated by methods stipulated in ISO 16358-1. cooling load. Since inverter air conditioners provide required
minimum cooling capacity with minimum electrical power, 0
total power consumption can be reduced during cooling period. 35
CSPF 7 Outdoor ambient temperature (°C)
Value

6 6.60
6.31
Inverters operate without repeated ON/OFF operation.
6.17
Inverter Highway driving Non inverter City driving
5 5.50 Continuous driving Constantly stopping
5.13 5.15 5.00 without stopping
Stop, go, stop ...
and starting
4.90 4.90 and starting is consumes energy and
4 4.67 4.67 4.67
4.29 more fuel efficient. is less fuel efficient.
4.10
3
3.10
2.77 2.71 2.79 2.79 2.73
2 2.69 2.63 Why is inverter technology more comfortable?

1 When temperature does not Non inverter Inverter


fluctuate much, the set
0 temperature is maintained.
Inverter ------- RZF50 RZF60 RZF71 ------- RZF100 RZF125 RZF140
CV2V CV2V CV2V / YM CVM / YM CVM / YM CVM / YM Inverter control responds to load changes
and causes minor temperature adjustments.
Non-inverter control frequently turns ON and Room
RZFC40 RZFC50 RZFC60 RZFC71 RZFC85 RZFC100 RZFC125 RZFC140 OFF in response to load fluctuations or load temperature Too hot
Inverter
DVM DVM DVM DVM / Y1 DVM / Y1 DVM / Y1 DY1 DY1
mismatch and causes large temperature Large
temperature
swings. fluctuation
R18 R21 R26 R30 R36 R42 R48
Non Inverter R35GV1
NUV1 NUV1 NUV1 / Y1 NUV1 / Y1 NUV1 / Y1 NUY1 NUY1 Set
temperature
Non inverter
Comfortable
Small
temperature
fluctuation
Inverter
What is CSPF? Non inverter
CSPF is the value for the annual total cooling load divided by the annual total power consumption at outdoor Too cold Too cold

air conditions specified by ISO standard. Time

9 10
Smart Airflow Control Quick Cooling
Indoor units can provide 5-step and 3-step fine control of air volume Faster cooling and RZF series Quick start function RZF series
5-step: FCF, and FHA series dehumidification Quickly make space comfortable RZA series
3-step: FCFC, FBA, FBFC, FDBF, FDLF, and FVA series before the arrival of office workers
New inverter control technology brings quick comfort. or shop customers.
Inverter (RZF-C series) The airflow rate of indoor unit is automatically
Comfort ensured by ‘Auto’ Conventional inverter (RZR-L series) controlled, increasing the capacity of the outdoor unit
airflow rate that matches Non inverter and quickly bringing the room to a comfortable
temperature.
load level Capacity This function will operate for a maximum of 30
*Except for FFF, FDF, FDBF, and FDLF series minutes until the air conditioner automatically returns
Convenient energy-efficiency for stores to normal operation.
INV Max
with peak and quiet periods.
Non Max

Better performance
than non-inverter models!
Level 1 (Low) Level 2 Level 3 (Medium) Level 4 Level 5 (High) Auto Reaches maximum capacity faster
than usual inverter models.

Start Time

Indoor
temp. Reaches the
set temperature faster.
BRC1E63 wired remote controller
is used for ‘Quick start’.
Start

Also convenient for high ceilings and spaces with long blow distances
Cassette type <Round Flow>: Ceiling suspended type: *Field setting with remote controller

maximum 4.2 m* maximum 4.3 m Setting


temp.
Start Time

4.2 4.3 Indoor


m m humidity Removeshumidity faster.

Start

See page 27 See page 44


*Maximum 4.2 m for FCF100-140 / FCFC100-140
Maximum 3.5 m for FCF50-71 / FCFC40-85

Start Time

11 12
Durability Convenient Functions
Microchannel heat RZF series Overvoltage PCB RZF series Navigation remote controller BRC1E63 includes various RZF series RZA series

exchanger RZFC series (Outdoor unit option) See page 74


convenient functions
Microchannel technology utilises superior heat transfer Unstable power supply is a common problem in many Automatic return to temperature preset by owner. Owner can preset upper and lower temperatures.
regions. It can cause overvoltage which can significantly
benefits of aluminium to create a more efficient air Setpoint auto reset Setpoint range set
conditioner. damage electronic devices.
To prevent voltage fluctuations, it is usually necessary to - Even if the set temperature is - Saves energy by limiting the min.
With a new resistance corrosion aluminium alloy, the changed, the new set and max. set temperature.
Daikin microchannel heat exchanger becomes highly attach a stabiliser when installing an air conditioner.
temperature returns to the - Avoids excessive heating or
durable. The RZF-C series is equipped with a highly-durable previous preset value after a cooling.
A salt spray test has been conducted to demonstrate the electronic circuit. preset duration of time. - This function is convenient if the
corrosion-resistant capability of our products in This circuit eliminates the need for a stabiliser and offer - Period selectable from 30, 60, remote controller is installed
corrosive environments for a certain period of time. additional protection for devices in the outdoor unit, 90, or 120 minutes. where anyone can change the
such as its fan motor and compressor. settings.
Test of durability
- Testing organization MTEC Thailand
- Testing standard ASTM B117 Coated printed circuit boards Restaurant example
- Result (outdoor unit)
Coated circuit boards prevent Restaurant opened Full tables at lunchtime After 30 minutes*
Before testing After testing problems caused by humidity
and airborne dust.
27 °C 24 °C Returns to
It also protects against salt
contained in sea breezes.
27 °C
automatically
Both sides of the PCB in
Normal Under outdoor units are coated.
observation telescope
No evidence of corrosion was observed
Automatic protection against Temperature is set to 27ºC Then is lowered to 24ºC Automatically returns to
After undergoing an intensive test, the Daikin microchannel low voltage for crowded room preset temperature (27ºC)
heat exchanger is able to maintain its shape without In AM and PM peak electricity consumption periods, *Preset-return time can be set at 30, 60, 90, or 120 min
corrosion, which strongly confirms its durability in a highly supply may fluctuate. Built-in low-voltage protection will
corrosive environment. automatically cut operations. When normal voltage is
restored, operation will resume as before.
Demand control function RZF100-140CVM, 71-140CYM RZA series
Please see a video of the
QR Outdoor unit installation is By setting limits that restrict power consumption, you can cut electricity bills.
* Field setting with remote controller
Micro Channel Heat
Exchanger test in Pattaya.
space possible even with limited space - Power consumption is given first priority, and limits maximum power
consumption of unit.
* Required for Demand adaptor (Option)
Limitation

consumption
Maximum power consumption can be set at 40, 60, 70, 80, or 100%.

Power
8:00 12:00 16:00 20:00 Time
100
m or
mo m or
re
100 0 mmre
10 mo
Night quiet operation mode RZF series RZA series
m or
mo m or mm Consideration is given for people living nearby.
re 0 r e
50 mo Outdoor unit operating sound can be reduced.
Peak outdoor temperature *Field setting with remote controller

Self-diagnosis functions enable

Capacity (%)
prompt maintenance response The operating
noise bothers
100

8 hours
An error message appears on the LCD of the remote me at night! 50 10 hours
controller and an LED lights up on the unit.

Load (%)
When the BRC1E63 is installed, the error code appears
0
showing contact information and model name. Contact your 48

Sound (dB(A))
Rated
Daikin dealer and provide the error code and model name.

Operating
Quiet mode
44 Quiet mode

8:00 12:00 16:00 20:00 0:00 4:00 8:00

Note: Daikin data for RZF71C


Operating sound about 4 dB quieter

13 14
Design Flexibility Reuse of Existing Piping RZF series RZA series

Possible to forced OFF and ON/OFF operation using external command Benefit 1
*Field setting with remote controller
*Except for FFF, FDF, FDBF, and FDLF series Simplified installation reduces replacement time and cost
Round flow cassette type Duct connection middle static pressure type
Lighting
When considering air conditioner replacement, do the following
Interlock things concern you?
The length of time the business will be closed
Effect on sales during replacement work
Interlock High costs and long work period due to scaffolding needed for pipe replacement

These problems are solved by Daikin!


Where feasible, we reduce work costs and time by reusing existing pipes*.
External Equipment Interlock (FCF-C series only) RZF series RZA series

Power conservation is possible though interlock* of external equipment, *Optional adaptor for wiring: BRP11B62 is necessary.
*Strict conditions apply, please check the table on page 46 for acceptable pipe sizing (if pipes are to be reused).
such as lighting, with the infrared presence sensor.
Human presence is detected by the built-in infrared presence Sensor The presence detection signal of the infrared presence
sensor in the sensing panel, and the presence detection interlock sensor can turn only external equipment ON/OFF without
Benefit 2
mode interlocking with air conditioner operation/stop (ON/OFF).
signal can be output and interlocked with external equipment
such as ventilation and lighting equipment. You can increase cooling capacity and achieve higher energy efficiency
Upgrade to an air conditioner with the latest technology for greater comfort and energy efficiency.
External equipment also
Presence Sensor Sensor automatically turns ON/OFF.
detection Undetected Detected
signal Contact OFF Contact ON
Lighting Ventilation
Further energy savings
and power conservation
R22 R32
equipment equipment Non inverter inverter
Infrared presence 7.6 kW 14.0 kW
Note: class class
sensor information Adaptor for wiring: When the presence detection signal is output to external equipment using the
BRP11B62 (Option) adaptor for wiring, other functions, such as interlock with the duct booster fan
and the output of other signals, become disabled.
φ9.5 φ15.9 φ9.5 φ15.9
Pipes used
as they are!
Indoor units (FCF, FCFC, FBA, FBFC, FHA, and FVA series) comply with D -Net standards
*FFF series requires optional adaptor to connect DIII-Net.
As a result, the greater capacity units
FDF, FDBF, and FDLF series cannot connect DIII-Net because they cannot use optional adaptor. FHC26NUV1 FCF140CVM ensure better performance to cope
R26NUV1 RZF140CVM
with the increasing amount of heat
generated by office equipment and
Previous indoor unit New indoor unit CSPF: 2.63 CSPF: 5.00
occupants.

Adaptor not Technology


required
Advanced technology, including the use of corrosion resistant electronic expansion valves, acid neutralisers and improved
Optional
FHQ-BV interface adaptor compressor reliability, enables the re-use of existing piping* without the need of pipe flushing for a simplified replacement process.
is required FHA-B

Stronger refrigerating Highly corrosion resistant Highly reliable


VRV machine oil electronic expansion valve compressor
VRV
An acid neutraliser agent is added to disable Compressor durability is improved
acids (chlorine ions), which cause corrosion. by installing a filter or accumulator
to collect solid foreign substances.

Acid neutraliser
Filter or
accumulator
Acid (chlorine ion)
Compressor

Refrigerant pipe

Easy connection to DIII-NET and long piping length makes this solution suitable for projects including and SkyAir.
15 16
Specification Option Specification Option
CEILING MOUNTED CASSETTE TYPE Round Flow FCF
P.59, 64 P.72
FCFC
P.68 P.75

Cassette air conditioner with 360° P.19-22 FCF only


FCF series movie
at Daikin official

uniform airflow sets the standard Circulation Airflow 1. Blows horizontally


YouTube site.

2. Strikes the wall


Cools the entire room to deliver
comfort that never feels cold.
The illustration shows typical airflow.
Effectiveness may differ according to room 3. Reaches every
conditions, room size, and distance to walls. corner of the room

P.23 FCF only P.24-26 FCF only

Individual Airflow Sensing Technology


FCF50/60/71/100/125/140CVM
FCFC40/50/60/71/85/100/
125/140DVM Direction Control Dual sensors and individual airflow direction
control automatically provide optimal control
*Shown above is FCF50-71. Airflow direction can be individually adjusted of airflow.
for each air discharge outlet to deliver
optimal air distribution.

Infrared
presence
C sensor
Option Accessory required for indoor unit.
FCF series FCFC series B D
A Infrared
Navigation Remote Controller Wireless Remote Controller *2 Simplified Remote Controller Wireless Remote Controller *2 floor
(Wired) *1 (Wired) *1 sensor
Cooling only
BRC7M635F (Fresh white) Cooling only
BRC7M635K (Black)
BRC1E63 BRC2E61 BRC7F635F
Heat pump
BRC7M634F (Fresh white)
BRC7M634K(Black)
Selectable Airflow Pattern
Signal receiver unit (Installed type)
Wireless remote controller is supplied in a set with a signal receiver. Because air flows out from corner outlets, comfort spreads more widely.
Note: Remote controller cable is not included and must be obtained locally.
1
Note: A signal receiver must be added to the indoor unit.
2

Typical flow patterns There are a total of 18 flow patterns.

Panel Variations All-round flow 3-way flow L-shaped 2-way flow Opposite 2-way flow

FCF only FCF only


Standard panel with Sensing Standard panel Designer panel
(Fresh white) (Fresh white) (Fresh white) (E.g., installed in middle of ceiling) (E.g., installed near a wall) (E.g., installed in a corner) (E.g., installed in a long room)
4-way flow also possible.

*
Note:
Minimum distance - Whatever the discharge direction, the same type of panel is used. If
Required distance to of 500mm installing for other than all-round flow, an air discharge outlet sealing
wall surface for closing
FCF only FCF only FCF only
air discharge outlet * 200mm
closing
for corner material (option) must be used to close each unused outlet.
- Operation sound increases when using 2-way or 3-way flow.
Standard panel with Sensing Standard panel Auto grille panel
*
(Black) (Black) (Fresh white) Wall surface - Designer panel cannot operate 2-way and 3-way flow.

17 18
CEILING MOUNTED CASSETTE TYPE Round Flow FCF series movie
at Daikin official
FCF only YouTube site.

Circulation Airflow Evenly Distributes Cool and Warm Air *1 *1. Applicable when wired remote controller BRC1E63 is used.

Cooling Heating

Airflow until now had areas that were either too cool or not cool enough. Airflow until now did not warm areas at floor level or near windows and walls.
(only downward flow)
Problem 1 Problem 1
Hot outdoor air entering through Outdoor air entering through
windows and walls causes these windows and walls causes areas
areas to become hot. 4-Way Flow near windows and walls to be cold. 4-Way Flow
Problem Problem 2 Problem Problem 2 Cold
Cool air accumulating directly Hot Warm air does not reach floor outdoor
outdoor air
underneath causes cold air air level, and areas at floor level
pockets at floor level. remain cold.

Problem 3 1 Problem 3 1
Airflow blowing directly on people Warm air blowing directly on
causes discomfort for people in 3 people causes discomfort from 3
the room. air conditioner.

Problem 4 Problem 4
Quick descent of cool air causes 4 2 Room is slow to get warm because 4 2
insufficient cooling for corners of warm air does not reach to all
the room. corners.

Circulation airflow cools the entire room to deliver comfort that never feels cold. Circulation airflow warms the entire room starting from your feet.
During 2-way During 2-way
horizontal flow horizontal flow
Hot Cold
outdoor air outdoor air

Airflow effectively avoids Airflow effectively avoids


blowing air directly on people. blowing air directly on people.

Cool air moves down along Comfort without cold air Cools by airflow blocking out Airflow quickly makes the Warmth reliably Warms by airflow blocking out
the walls and to every corner pockets at floor level. hot air near windows and walls. entire room warm and reaches feet. cool air near windows and walls.
of the room. comfortable.

Configurations of Circulation Airflow (Cooling) Configurations of Circulation Airflow (Heating)

Operation Performs repeatedly Operation Performs repeatedly


(at start) Airflow (at start) Airflow
direction When the set direction When the set
changes temperature is reached, changes temperature is reached,
normal operation normal operation
(all-round flow) begins. (all-round flow) begins.

Note:
Cools areas around Cools entire room Cools areas around Cools entire room Results may vary depending on Warms areas around Warms the middle Warms areas around Warms the middle
walls using using 4-way walls using using 4-way equipment conditions, room size, walls using of the room using walls using of the room using
2-way horizontal flow swing flow 2-way horizontal flow swing flow and distance from indoor unit to walls. 2-way horizontal flow 4-way down flow 2-way horizontal flow 4-way down flow

19 20
CEILING MOUNTED CASSETTE TYPE Round Flow FCF series movie
at Daikin official
FCF only YouTube site.

Circulation Airflow Evenly Distributes Cool and Warm Air *1 *1. Applicable when wired remote controller BRC1E63 is used.

Comfort to the Entire Room with Even Temperatures and No Cold Air Pockets at Floor Level Comfort to the Entire Room with Even Temperatures and Warmth Reaches Feet

Cooling 4-way cassette (Swing) Heating 4-way cassette (Down blow)

30.0 30.0
29.0 28.0
28.0 26.0
27.0 24.0
26.0 22.0
25.0 20.0
24.0 18.0
23.0 16.0
22.0 14.0
21.0 12.0
20.0 10.0
Comparison Conditions Comparison Conditions
Areas at floor level are cold while areas Room size: Width 7.5m x depth 7.5m x height 2.6m Room size: Width 7.5m x depth 7.5m x height 2.6m
around walls are hot. Indoor unit capacity: 71 class Areas around walls and feet are cold. Outdoor air temperature: 5°C
Outdoor air temperature: 35°C Indoor unit capacity: 71 class
Airflow rate and air direction: high / swing Airflow rate and air direction: high / Down blow

Circulation Airflow (2-way horizontal + 4-way swing) Circulation Airflow (2-way horizontal + 4-way swing)

30.0 30.0
29.0 28.0
28.0 26.0
27.0 24.0
26.0 22.0
25.0 20.0
24.0 18.0
23.0 16.0
22.0 14.0
21.0 12.0
20.0 10.0

Approx. 5% energy savings *2 Approx. 15% energy savings *3


Full comfort is provided with no cold feet. by reducing uneven temperatures Areas around walls and feet are warm. by reducing uneven temperatures

*2.Calculated under the following comparison conditions: When the average temperature at a height of 0.6m above the floor reaches set temperature. (26°C) *3.Calculated under the following comparison conditions: When the average temperature at a height of 0.6m above the floor reaches set temperature. (22°C)

Velocity
Three Technologies That Achieved Circulation Airflow 10%
3 Increased velocity in ※ increase!
1 Use of new wide flaps (Straight) 2-way flow (Strongly) All-round Two-way
Airflow velocity is increased by up to flow flow
With new, larger flaps, a straighter trajectory for airflow was achieved.
10% during 2-way flow.

※.Other 2 outlets are controlled by changing the flap
Conventional flap New wide flap New wide flap direction (angle) to suppress airflow volume.
construction inhibits
ceiling dirt and grime.
By tapering both flap ends,
Things to remember when using circulation airflow
the airflow that causes dirty [Table 1]
ceilings is directed downward. Main points for use Installation conditions Distance to wall from indoor unit
Round flow Indoor unit
Effectiveness may differ according to room conditions, capacity FCF50-71 FCF100-140
room size, and distance to walls. Distance
range 1.5-5m 1.5-7m

Wall surface
Airflow operation differs when using the designer panel. Distance Minimum distance between
to wall indoor units [Table 2]
(Operation repeatedly switches from 3-way horizontal [Table 2]
Optimizing airflow angle (Horizontally)
[Table 1]
2 flow to 4-way downward flow [swing] to Minimum distance between indoor units
Conventional flap New wide flap 2-way horizontal flow to 4-way downward flow [swing].)
1.8m or more above floor surface
Indoor unit
FCF50-71 FCF100-140
The airflow angle was made more horizontal. Floor surface capacity

Circulation airflow functions during connection with wired Distance


range 5m or more 7m or more
remote controller. (BRC1E63). However, use is not
possible for the following conditions:
- When a sealing material of air discharge outlet (for 2, 3, 4-way flow) and branch ducts are used;
- When individual airflow setting is selected;
- When using group control other than round flow.

21 22
CEILING MOUNTED CASSETTE TYPE Round Flow FCF series movie
at Daikin official

Individual Airflow Direction Control *1


Daikin Sensing Technology *1,2 FCF only YouTube site.
FCF only
*1. Applicable when wired remote controller BRC1E63 is used. *1. Applicable when wired remote controller BRC1E63 is used.  *2. Applicable when sensing panel (BYCQ125EEF/EEK) is installed.

Comfortable air conditioning for all room layouts and conditions Dual Sensors*2
Dual sensors and individual airflow direction control automatically provide
Airflow direction can be individually
adjusted for each air discharge outlet to
Easy setting is possible with a wired remote controller. optimal control of airflow.
BRC1E63
deliver optimal air distribution.
Infrared presence sensor
The sensor detects the presence of people in each of the
Position 0 There are
identification
4 areas.
(Fixed airflow to marks near
the air outlets. Ceiling height 2.7m 3.5m 4.0m
highest position)
Remote controller
screen
Detection range approx. approx. approx.
(diameter)*3 8.5m 11.5m 13.5m
Detecting the
presence of people *3. The infrared presence sensor detects 80cm above the floor.
in each of the 4 areas

C
Infrared floor sensor
Individual airflow settings B D The sensor detects the floor temperature and
No individual A automatically adjusts operation of the indoor unit to
setting ・No individual setting (Auto airflow) Detecting the reduce the temperature difference between the ceiling
(Auto airflow) ・Position 0 (Highest point) average temperature and the floor.
・Position 1 of the floor
・Position 2 Ceiling height 2.7m 3.5m 4.0m
・Position 3 Detection range
Position 4 approx. approx. approx.
Swing ・Position 4 (Lowest point)
(Fixed airflow to the (diameter)*4 11m 14m 16m
(Up/down) ・Swing
lowest position) *4. The infrared floor sensor detects at the floor surface.
Individual settings are possible as stated above.

When individual airflow is selected, airflow direction can be adjusted to room layout.
Auto Airflow Functions*5 *5.Airflow direction should be set to “Auto”.

For shops and restaurant


Direct Airflow (default: OFF) Cooling Dry
When human presence is detected
When human presence is not detected

Swing
Swing is
selected for
areas near
the windows. No individual (Auto)
Auto is set for people
sitting farthest from
The seats here the entrance. Optimal air direction by “Auto” Optimal air direction by “Auto” Swing (narrow)
Sitting here is hot are comfortable
because of the hot air though…
With “Auto” airflow direction mode, flaps are controlled When presence is detected, air direction is set
from outside.
to deliver optimal airflow when the room is unoccupied. to “Swing (narrow)” to deliver cool air to users.
Position 0
For offices The airflow is at the Draft prevention (default: OFF) Heating When human presence is detected
highest setting (Position 0)
for people who When human presence is not detected
Swing dislike air blowing
Discussions near Swing is set for directly on them.
a hot window meetings near
quickly heat up.
the windows.

Optimal air direction by “Auto” Optimal air direction by “Auto” Blown horizontally
It’s quite pleasant
It is very cold here, when cold air isn’t
isn’t it?… Discussions also blowing on us. With “Auto” airflow direction mode, flaps are controlled When presence is detected, drafts are
go smoothly.
to deliver optimal airflow when the room is unoccupied. prevented by making the flap horizontal.
When human is not detected for 5 minutes, the unit automatically returns to controlling the flaps for an unoccupied room.
23 24
CEILING MOUNTED CASSETTE TYPE Round Flow

Daikin Sensing Technology *1,2 *1. Applicable when sensing panel (BYCQ125EEF/EEK) is installed.
*2. Applicable when wired remote controller BRC1E63 is used.
FCF only FCF only

Comfort and Energy Saving Preventing Overcooling / Overheating*3 Sensing Sensor Functions*5,6 *5. These functions are not available when using the group control system.
*6. User can set these functions with remote controller.
*3.Airflow direction and airflow rate should be set to “Auto”.
Floor temperature is detected and overcooling prevented. Cooling Sensing sensor low mode (default: OFF)
When there are no people in a room,
the set temperature is shifted automatically.
Without sensing function With sensing function
- The system automatically saves energy by detecting
whether or not the room is occupied. The set temperature is
Operation is
reduced in places
shifted automatically if the room is unoccupied.
where there are
no people.
30°C near ceiling 30°C near ceiling

Room 2 Room temperature is • Cooling set temperature: 26°C • Shift temperature: 1.0°C
temperature is calculated as 27°C in the area which Example
detected as • Shift time: 30 min. • Limit cooling set temperature: 30°C
is in the vicinity of the person.
30°C.

Set temperature (°C)


*7
24°C near floor 28 28°C
20°C near floor 1 27°C
*7
27
26 26°C
26℃ 26℃
26°C If people do not return,
Automatically reverts the air conditioner will
Occupied when people return. raise the set
Unoccupied temperature 1°C every
Area around feet gets too cold because the air The floor temperature, Automatic control using 30 minutes and then
conditioner continues until the temperature near the which is lower than the temperature near the operate at 30°C.
Time
near the ceiling, is person as the room After 30 min After another 30 min
ceiling reaches the set temperature.
detected. temperature.

Energy The temperature near the person is automatically calculated by detecting the temperature of
savings the floor. Energy is saved because the area around the feet does not get too cold. Example
• Heating set temperature: 20°C • Shift temperature: 1.0°C
• Shift time: 30 min. • Limit heating set temperature: 16°C

Set temperature (°C)


20°C 20°C
Feet are kept warm and comfortable while reducing uncomfortable drafts. Heating
20
19 19°C
*7

18 18°C
*7 If people do not return,
the air conditioner will
Without sensing function With sensing function Occupied
Automatically reverts lower the set temperature
Unoccupied when people return. 1°C every 30 minutes
When air is blown horizontally... and then operate at
16°C.
Time
After 30 min After another 30 min
Drafts are
minimal, but feet
get cold.

Shift temperature and time can be selected from 0.5 to 4°C in 0.5°C increments and 15, 30, 45, 60, 90 or 120 minutes respectively
17°C near floor with remote controller.
20°C near floor
*7. On basic screen of remote controller, set temperature does not change.
Feet get cold, because warm air collects near the ceiling.
Area near floor doesn’t reach set temperature and feet feel cold.
The floor temperature, In order to
For this reason, we end up raising the temperature setting. which is lower, is detected reduce drafts, Sensing sensor stop mode (default: OFF)
and warm air is blown air is blown When there are no people in a room, the system stops automatically.*8,9
downward where there is horizontally
When air is blown downward... - The system automatically saves energy by
no human presence. where a
person is detecting whether or not the room is occupied.
Comfortable because Absent stop time can be selected from
located.*4 - Based on preset user conditions, the system 1 to 24 hrs in 1 hr increments with
draft is reduced and area remote controller.
Feet are automatically stops operation if the room is
warm, but draft around feet is warm.
is strong.
unoccupied.
*8.Please note that upon re-entering the room,
*4. Draft prevention function is set OFF in the initial setting. the air conditioner will not switch on automatically.
20°C near floor *9.To protect the machine, the standby system may
The tendency of people to raise operate temporarily.

Uncomfortable draft occurs, because air is blown downward. Energy the temperature too much is
savings prevented, because you are
To avoid draft, air direction is changed to horizontal and feet get cold.
warmed up from the feet.

To increase comfort, Auto airflow rate mode controls the airflow in accordance with the difference between
floor and ceiling temperatures.
When there is a large difference between the ceiling and floor temperatures, the airflow rate is automatically increased.
When the difference becomes small, the airflow rate is automatically reduced.
25 26
CEILING MOUNTED CASSETTE TYPE Round Flow

Comfort Quick and Easy Installation Washer fixing plate

mm 95 Washer
950 0m
Unified square panels m Same for Lightweight Easy hanging
all models
Panel size is the same for all models. All models can be installed without using a lifter. Washer fixing plates secure washers
It is easy to maintain a neat appearance when multiple units are in place and prevent washers from
installed in the same room. falling for easy installation.

Optimal comfort and convenience assured by 3 air discharge modes Installable in tight ceiling spaces
Standard panel
Air direction Standard setting1 Draft prevention setting Ceiling soiling prevention
setting2 (field setting) 256mm ( FCF50-71C, 261mm ( FCF50-71C,
FCFC40-85D )
Easy removal of corner cover
(field setting) FCFC40-85D )
298mm ( FCF100-140C, 303mm ( FCF100-140C,
FCFC100-140D ) It is possible to easily
For shops with FCFC100-140D )
Desired situation For gentle drafts. When drafts are unwanted. light coloured ceilings that remove without use
must be kept spotless. of screws or tools.

Auto-swing Designer panel FCF only

256mm 261mm +42mm*1


5-level 298mm 303mm
air direction setting Note: 42mm*1
1
Air direction is set to the
standard position when the
Draft prevention At heating startup and thermo OFF, air discharge is automatically set to *1.Body height (ceiling required space) is 42 mm higher than standard panel.
unit is shipped from the
(In heating mode) a near horizontal to prevent direct exposure to cool air drafts. factory. The position can be
changed from the remote
controller. Auto grille panel FCF only
Auto air direction The air direction is set automatically to the memorised 2
Closing of the corner
control position of the previous air direction.
discharge outlets is
256mm 261mm +55mm*2
recommended. 298mm 303mm
55mm*2
Switchable fan speed: Suitable for high ceilings
*2.Body height (ceiling required space) is 55 mm higher than standard panel.
FCF 5 steps and Auto Even in spaces with high ceilings, a comfortable airflow is carried *When the ceiling space is limited, an optional panel spacer is available.
down to the floor level. (see P.30)
FCFC 3 steps and Auto
Standard Setting Setting

When all round flow is Easy height adjustment Ease in temporary hanging
selected, ceilings up
Each corner of the unit has an
of decoration panel
4.2
Quiet operation dB(A)
3.2
m
3.6
m m to 4.2 m in height can
be accommodated. adjuster pocket that lets you
Sound pressure level (FCF100-140C, easily adjust the unit's In addition to the temporary
Indoor unit
H HM M ML L FCFC100-140D) suspended height. hanging fixtures in 2 places
FCF50-71C 37.0 34.5 32.0 29.5 27.5 normally used, corner part
FCF100C 45.0 41.5 38.0 35.0 32.5 Criteria for ceiling height and number of air discharge outlets Note: mounting fixtures in 4 places
If the wireless remote controller is
(Ceiling height is reference value) installed, a signal receiver unit is are provided.
FCF125/140C 46.0 43.0 40.0 36.0 32.5
housed in one of the adjuster pockets. Corner part mounting
Number of air discharge outlets used fixtures (in 4 places) Temporary hanging
FCFC40-60D 37.0 ------- 32.0 ------- 28.0
FCF50-71C, FCFC40-85D FCF100-140C, FCFC100-140D fixtures (in 2 places)
FCFC71D 37.0 ------- 34.0 ------- 28.0 All round 4-way 3-way 2-way All round 4-way 3-way 2-way
FCFC85D 38.0 ------- 34.0 ------- 29.0
Standard
flow flow flow flow flow flow flow
2.7 m 3.1 m 3.0 m 3.5 m 3.2 m 3.4 m 3.6 m 4.2 m
flow
Temporary placement of control Drain pump
------- ------- Ceiling Equipped as standard
box lid
FCFC100D 45.0 38.0 33.0
height
High ceiling 3.0 m 3.4 m 3.3 m 3.8 m 3.6 m 3.9 m 4.0 m 4.2 m
FCFC125/140D 46.0 ------- 40.0 ------- 33.0 High ceiling 3.5 m 4.0 m 3.5 m - 4.2 m 4.5 m 4.2 m - accessory with 850 mm
Because the control box lid can be temporarily hung 850 mm lift.
Note:
The aforementioned is for standard panels. See the installation manual for designer panels. on the unit, there is no need to climb down the
Factory settings are for standard ceiling height and all-round flow. stepladder to retrieve it. 175 mm
High ceiling settings (1) and (2) are set with the remote controller by field setting.
High-efficiency filters are not available for high ceiling applications.

Transparent drain socket


Cleanliness

Silver ion anti-bacterial drain pan Non-flocking flaps The detached lid can
A built-in antibacterial Flaps can be detached without use of tools. be hung on a hook. Hanging height adjustment
treatment that uses silver Condensation does not easily
Because the configuration of the hanger bracket changed, the
ion in the drain pan prevents form and dirt does not cling to
the growth of slime, non-flocking flaps. Installed in any direction dimensions from the ceiling to the hanger bracket also change
during height adjustment for indoor unit.
bacteria, and mould that They are easy to clean. Since the orientation of the Hanger A Dimensions
cause odours and clogging. suction grille can be bracket Standard panel 125-130mm
(The lifespan of a silver ion
cartridge depends on the
Filter has anti-mould and adjusted after installing,
the direction of the suction A
Designer panel
Auto grille panel
167-172mm
180-185mm

usage environment, but antibacterial treatment grille lines can be unified Ceiling
Chamber option*+ standard panel 175-180mm

should be changed once Prevents mould and microorganisms growing out of the when multiple units are surface *High-efficiency filter, ultra long-life filter, and
fresh air intake
every two to three years.) dust and moisture that adheres to the filters. installed.
27 28
CEILING MOUNTED CASSETTE TYPE Round Flow

Easy Maintenance Options

Condition of the drain pan and Auto grille panel (option) FCF only
Options required for specific operating environments
drain water Grille and air filter cleaning can be performed
Ultra long-life filter unit Fresh air intake kit
the Note 1.2
Can be checked by removing
s t o pen lle! without need for a stepladder by lowering the grille.
the suction grille and drain plug. Ju ion gri Even in dusty environments where the air conditioning Using this kit, a duct can be connected to take in outdoor
suct A dedicated remote controller for the auto grille panel is constantly operating, the ultra long-life filter only has air. There are two chamber types that have intake in two
Note: For inquiries concerning auto (BRC16A2) is included. places: with T-duct joint and without T-duct joint.
grille panel installations, please
to be cleaned once a year.
Operation is not possible using BRC1E63.
contact your local dealer or Daikin Filter chamber Outside
representative. (Can be used with high-efficiency filter)
The drop length corresponds to
Drain outlet ceiling height and can be set for
(with rubber plug) 8 different levels.
Ultra long-life filter
Ceiling Height
Drop Length Dusty area: annual filter change
Standard (m) *For dust concentration of 0.3 mg/m3 (Requires separately sold Air purifier.) The units can be installed in the following
2.4 1.2 1 year (Approx. 5,000 hr) 15 hr/day x 28 day/month x 12 month/year
different ways
24 mm diameter drain outlet 2.7 1.6 Ordinary store or office: filter change every 4 years
*For dust concentration of 0.15 mg/m3
The drain outlet allows 3.0 2.0 4 years (Approx. 10,000 hr) 8 hr/day x 25 day/month x 12 month/years Chamber type (without T-duct joint) Note 3.4.5
x 4 years
insertion of a finger or 3.5 2.4 KDDP55B160
dental mirror for 3.8 2.8
inspection of the Flexible duct
4.2 3.1
High-efficiency filter unit
(obtained locally)
internal cleanliness of
the drain pan. 4.5 3.5 T-duct joint
(obtained locally)
5.0* 3.9 Available in two types: 65% and 90% colorimetry.
Removal of the suction Suction
Intake duct
chamber
panel enables access. *Airflow range is up to 4.5m. Filter chamber (obtained locally)
Please refer to “criteria for ceiling Connection (duct length: 4 m max.)
(Can be used with ultra long-life filter)
height and number of air discharge chamber
outlets” on page 27.
Ultra long-life filter (option) High-efficiency filter
Chamber type (with T-duct joint) Note 3.4.5
See page 30
KDDP55B160K
Maintenance is not required in normal shops or
offices for up to four years.
Insulation kit for high humidity Flexible duct

Please use if you think the temperature and humidity


Low gas pressure detection inside the ceiling exceeds 30°C and RH 80%,
T-duct joint
Suction
respectively. chamber Intake duct
(obtained locally)
Connection (duct length: 4 m max.)
Top panel insulation(1) chamber
Top panel insulation(2)
Top panel insulation(3)
Direct installation type Note 6
Insulation for decoration panel
Side panel insulation KDDP55X160A
Suspension bracket insulation

Panel spacer
Duct flange
Use when only minimal space is available between (with insulation material)
Intake duct
drop ceilings and ceiling slabs. (obtained locally)

Note: Some ceiling constructions


may hinder installation. Contact
your Daikin Dealer before Note: 1. Use of options will increase operating sound.
installing your unit.
40mm 2. Connecting ducts, fan, insect nets, fire dampers, air filters, and
Panel spacer other parts should, as required, be obtained locally.
3. When a local-obtained fan is used, an interlock with air conditioner
is necessary.Optional PCB (BRP11B62) is required for
interlocking.

Sealing material of air discharge outlet


4. When installing a fresh air intake kit (chamber type), two air outlet
corners are closed.
5. It is recommended that the volume of outdoor air introduced
By using this option, 2-way, 3-way, or 4-way flow can through the kit is limited to 10% of the maximum airflow rate of the
be selected. indoor unit. Introducing higher quantities will increase the operating
sound and may also influence temperature sensing.
6. The volume of fresh air for direct installation type is approximately
1% of the indoor unit airflow.

Branch duct chamber


The chamber type is recommended when more fresh air is
necessary.

This chamber lets you connect a round flexible duct to


the air discharge opening at any time after the original
installation.

29 30
Specification Option
COMPACT MULTI FLOW CEILING MOUNTED CASSETTE TYPE
P.60 P.73

Quiet and decorative style that easily Compact Comfort

installs in new or old buildings Sized to fit inside 600mm wide Designed for low draft
ceiling grids performance 0 Horizontal flow 0

575 mm
Less draft
575 mm can be felt

286 tion
mm Decolrais also
e
pan act.
comp Consistent comfort throughout
Auto-swing operation Airfow direction can be
700 mm distributes conditioned air adjusted in accordance with
more evenly. room conditions.
Auto-swing 5-levels air direction setting
700 mm
Standard 0 0
FFF50/60BV1 setting Auto-swing Settable to 5 different levels
between 0 and 60 60
between 0 and 60
60
Fits without the need to Draft
cut T-bar grid prevention
setting 0
Auto-swing
0
Settable to 5 different levels
35 35
The control box is built in to the unit, (Field setting) between 0 and 35 between 0 and 35

so maintenance is possible Setting to


by simply removing the grille. prevent soiling
25 Auto-swing 25 Settable to 5 different levels
An inspection opening is not required of ceiling
(Field setting) 60
between 25 and 60 between 25 and 60
even for modules other than 60

600 mm x 600 mm. Note: This angle above is provided as a guide.

Ceiling panel

T bar Multi-Flow System Air direction can


4-way flow be selected
according to installation.
600 mm 1 pattern
600 mm
3-way flow

4 patterns

Quiet Operation
2-way flow
Quiet, but small-diameter fan
1 pattern
Quiet operation is achieved even with a compact
body and developed spiral hub cover that reduces " " denotes piping direction. Note: Operation sound increases
the static pressure inside the indoor unit. Drain piping " " denotes sealing when using 2-way or 3-way flow.
material for air discharge outlet (option) .
Note:
For 3-way or 2-way flow installation, the sealing
material for air discharge outlet (option) must
be used to close off the unused outlet(s).

Accessory required for indoor unit.


Two selectable temperature-sensors
Option

Both indoor unit and wired remote controllers contain temperature-sensors.


Wired Remote Controller Wireless Remote Controller Spiral hub cover
Temperature sensing can be set at the unit or, to further improve comfort
level, closer to the target area at the wired remote control.
Navigation Remote Controller dB(A)
This feature require initial setting by the installer.
Sound pressure level *Temperature-sensor on indoor unit must be used when the air conditioner is controlled
Indoor unit
High Low from another room.
Cooling only
**Wireless remote controller does not have a temperature-sensor.
BRC7E531W 50/60B 41 32
BRC1E63
Switchable fan speed: High/Low
Signal receiver unit
(Installed type)
Wireless remote controller
is supplied in a set with a High setting provides maximum reach while low setting minimizes drafts.
signal receiver.

Drain pump
750 mm
Note: Remote controller cable is not included and must be obtained locally. Note: A signal receiver must be added to the indoor unit.
Equipped as standard accessory with
750 mm lift.

31 32
Specification Option Specification Option
DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE FBA
P.60, 61, 65 P.73
FBFC
P.69 P.76

Middle static type allows Design and Installation


Flexibility Adjustable E.S.P.
greater flexibility External static pressure can be controlled to within a
Only 245 mm high range of 50 Pa to 150 Pa (FBA series and
FBFC100-140 )* by using a DC fan motor.
1,000 mm 800 mm
Installation is
possible even in
buildings with narrow 50 Pa 150 Pa
ceiling spaces.
245
mm
Set to low static Set to high static pressure for
pressure when ducts advanced needs such as when
are short. using dampers and long ducts.

One of the industry’s most compact bodies in the mid-static Comfort airflow is achieved in accordance with conditions
pressure range. such as duct length.
*30-130 Pa for FBFC40-60, 40-140 Pa for FBFC71/85.
FBA50/60/71/100/125/140BVMA(9) Indoor unit FBFC40/50/60D
FBA50/60/71B FBA100/125/140B
FBFC71/85D FBFC100/125/140D
FBFC40/50/60/71/85/100/ Height 245 mm Airflow rate auto adjustment function
125/140DVM(9) Width 700 mm 1,000 mm 1,400 mm
Depth 800 mm Controls the airflow rate using a remote controller
during test run.
It is automatically adjusted to approximately ±10% of
the rated H tap airflow.
Bottom suction is available
Wiring and servicing can be
done from the underside of unit
Interlock control
joist
the unit (an option part As an energy saving feature, * Field setting with remote controller
required). the room air conditioning unit
Air suction
can be interlocked with the
ceiling hotel key card system.
Using a 3rd-party building Interlock
Rear suction Bottom suction management system, air
conditioning and lighting can
Air suction flange Shield plate for side plate (option)
be interlocked.

DIII-NET communication standard


Connection to a centralised control system is available
without need for an optional adaptor.
Switch bottom plate with
Control box air suction flange.
cover Bottom Air suction
plate Make the control box flange
face inward. Bottom plate
Option Accessory required for indoor unit.
Easy Maintenance
FBA series FBFC series

Navigation Remote Controller Wireless Remote Controller *2 Simplified Remote Controller Wireless Remote Controller *2 Position of drain pan inspection
opening
(Wired) *1 (Wired) *1
Control box cover
Control box faces outward. Control box faces inward. Modified for easier inspection work.
Cooling only
Cooling only
BRC1E63
BRC4C66
Heat pump
BRC2E61 BRC4C66 Higher lift is realized Drain pan maintenance check window
BRC4C65 DC drain pump: This makes it possible to
FBA Standardly equipped inspect for drain pan dirt Inspection
opening for

FBFC Optional accessory 850 mm and to confirm drainage


during installation
drain pan

Drain pan
maintenance
without the use of tools. check window
Signal receiver unit (Installed type)
Wireless remote controller is supplied in a set with a signal receiver.

Note: 1Remote controller cable is not included and must be obtained locally. Note: 2A signal receiver must be added to the indoor unit. Clean
Comfort
Simultaneous air conditioning of two rooms and ventilation grille (ventilation opening) Silver ion anti-bacterial drain pan
When air conditioning two rooms
simultaneously, the air discharged
Door-installed
ventilation grille
Wall-installed
ventilation grille Under-door cutout Switchable fan speed: 3 steps and Auto A built-in antibacterial treatment that
into each room must be circulated “Auto” is applicable when wired remote controller is used. uses silver ion in the drain pan
back to the air conditioner. prevents the growth of slime,
To achieve this, a ventilation duct Ventilates air through bacteria, and mould that cause
High Efficiency
Partitioning wall
should be installed for each room or the partitioning wall. odours and clogging.
one of the indicated ventilation (See right)
(The lifespan of a silver ion cartridge
grilles should be installed on the Ventilation grille Ventilation grille Under-door cutout depends on the usage environment,
partitioning wall or under the door
between the rooms.
Note:
The under-door cutout method should be used only when there is a small volume of airflow.
DC fan motor and DC drain pump but should be changed once every
These are utilised to improve energy efficiency. two to three years.)
33 34
Specification Option
CEILING MOUNTED SLIM DUCT TYPE P.61 P.73

Compact and Slim Design


Suitable for tight ceiling spaces Only 200 mm high
Easily installed in even shallow ceiling cavity with a
height of just 240 mm.
Indoor unit FDF50B FDF60B
200mm Height
Width
200 mm
1,100 mm
Depth 620 mm
620mm Weight 30 kg
1,100 mm

FDF50/60BV1
Bulkhead Installation
The slim duct type can be hidden inside the ceiling to provide a clean exterior. It is suitable for living rooms with shallow
tray ceilings or areas requiring a discreet appearance. FDF-B series are 1,100 mm wide, making them ideal for narrow
spaces.
All models are 200 mm high and require a space of only 240 mm between the drop ceiling and ceiling slab. With these
compact measurements, any unit can easily be installed in even shallow tray ceilings.

240 mm

Air inlet and suction grille


(parts obtained locally)
Air outlet

Smooth Finish Air discharge


Suspension bolt*
duct*
The only visible sign of these unobtrusive units is their Air filter
Air discharge
discharge grilles. grille*
They fit completely inside the ceiling to maintain the
original decor of a room.
AIR

Quiet Operation Chamber


dB(A) Signal receiver wire Air suction
Option Accessory required for indoor unit. Length = 1,900 mm grille*
Indoor unit
Sound pressure level
H L AIR
Wired Remote Controller Wireless Remote Controller 50/60B 38 34 *Locally obtained parts
Navigation Remote Controller
Note:
1. To prevent an increase in operation sound, avoid installing the air suction
grille directly below the suction chamber.
Cooling only
2. Grilles, piping connections, ducts, and installation parts should be obtained
BRC1E63 BRC4C64 locally.
Signal receiver unit Duct-connected types do not have drain pumps.
(Installed type)
Wireless remote controller
is supplied in a set with a
signal receiver.

Note: Remote controller cable is not included and must be obtained locally. Note: A signal receiver must be added to the indoor unit.

35 36
Specification Option
DUCT CONNECTION LOW STATIC PRESSURE WIDTH COMPACT TYPE P.70 P.76

Design and Installation Comfort


Perfect for narrow entranceways Flexibility
Switchable fan speed: 3 steps
Only 700 mm width 700
Installation is possible mm
even in narrow entrance 800 mm Quiet Operation
ways at hotels and
condminiums. 245 25dB(A) in L tap for 40-60 class.
mm Operation sound is as quiet as a whisper.

Indoor unit FDBF40/50/60D FDBF71/85D


Height 245 mm
Width 700 mm 1,000 mm
FDBF40/50/60/71/85DV1 Depth 800 mm
Weight 26 kg 36 kg

Option Accessory required for indoor unit. Width compact type 700 mm
Wired Remote Controller
Mirror Pipe *New features for both FDBF and FDLF series.

Simplified Remote Controller


Enables selection of right or left piping at installation site
BRC2E61
Note: Remote controller cable is not included
and must be obtained locally.

Wireless Remote Controller

Can
Signal receiver unit select!
Cooling only (Installed type)
BRC4C66 For left side For right side
Wireless remote connection connection
controller is supplied
Note: A signal receiver in a set with a signal
must be added to receiver.
the indoor unit.

37 38
Specification Option
DUCT CONNECTION LOW STATIC PRESSURE HEIGHT COMPACT TYPE P.71 P.76

Compact and Slim Design Bulkhead Installation


Enables high-ceiling design Only 200 mm high The slim duct type can be hidden inside the ceiling to
provide a clean exterior. It is suitable for living rooms
Easily installed in even shallow ceiling space. with shallow tray ceilings or areas requiring a
discreet appearance.
1,100 mm 620 mm FDLF series are 900 and 1,100 mm wide, making
them ideal for narrow spaces.
200 All models are 200 mm high and require a space of
mm
only 240 mm between the drop ceiling and ceiling
slab. With these compact measurements, any unit
can easily be installed in even shallow tray ceilings.

Indoor unit FDLF40/50/60D FDLF71/85D


Height 200 mm
FDLF40/50/60/71/85/DV1 Width 900 mm 1,100 mm
Depth 620 mm
Weight 28 kg 31 kg

Comfort Air outlet Air inlet and suction grille


(parts obtained locally)

Switchable fan speed: 3 steps


Only
240 mm
required

Easy Maintenance *New features for both FDBF and FDLF series.

1 stop service space Easier and faster cleaning


Owners save spaces for services Current New
Need to be removed by orderly The integrated fan motor can
Ceiling be removed and reinstalled in
one time
Height compact type 200 mm Require installation
AIR space only 20 mm on
Option Accessory required for indoor unit. top and bottom

Wired Remote Controller


Simplified Remote Controller

BRC2E61
space Easy access to Control box from bottom side
to
ceiling Current New
Note: Remote controller cable is not included
and must be obtained locally. Need space area inside for All wiring and maintenance
maintenance Control box can be done from bottom side

Wireless Remote Controller

Signal receiver unit


Thin design
Cooling only (Installed type) Easier and
Require limited space
BRC4C66 faster
Wireless remote for installation maintenance.
controller is supplied and service
Note: A signal receiver in a set with a signal
must be added to receiver.
the indoor unit.

39 40
Specification Option
FLOOR STANDING TYPE P.62, 66 P.74

New airflow control for Comfortable Airflow Control

more comfort Left and right directions (by remote controller) (Applicable when BRC1E63 is used.)

Auto swing direction is selectable from 3 patterns to suit the layout of the room.

Pattern 1 Swing wide across the front Pattern 2 Swing across left side Pattern 3 Swing across right side
BRC1E63
can be incorporated
New comfortable airflow control
into the indoor unit.

When installed in the center of a wall. When installed in the corner of a room.

Up and down directions (by hand)


Independent up-and-down airflow directions facilitate even room temperature and help save energy.
FVA50/60/71/100/
125/140AMVM Freely select both Example applications
New unit
up and down Upper louver (1)
When cooling
airflow direction Upper interlocking louvers (4)
Turning louvers
with 8-louver Lower interlocking louvers (2)
and upward
(horizontal blade) Lower louver (1) and leaving
setting. and horizontal
Each set of louvers to will reduce
can be independently uneven room
adjusted. (Manual adjustment) temperature.

Comfort Easy Maintenance

Switchable fan speed: 3 steps and Auto Long-life filter (standard) requires
“Auto” is applicable when BRC1E63 is used. no maintenance for about 1 year*
High fan speed mode (applicable for FVA50-100) The filter is washable and reused after 1 year.
* For dust concentration of 0.15 mg/m3
To carry airflow to the far side of the room, airflow rate can -Two time settings (2500 hrs and 1250 hrs) are available to match the
be increased 5% or 10% depending on the installation installation environment. Maintenance time warning is displayed on the
condition or customer's request. (Field setting by remote remote controller (filter sign).
-The periodical cleaning time for the filter can be shortened depending on
controller.) the usage environment.

Option Accessory required for indoor unit.


Programme "Dry" Employs a safety lock function of
Dehumidification is microprocessor controlled to prevent
abrupt and uncomfortable changes in air temperature.
suction grille
Wired Remote Controller Wireless Remote Controller The grille will not open even upon impact.

Convenience
Navigation Remote Controller
High Efficiency
Cooling only
BRC4C66 DC fan motor improves efficiency Wireless remote controller
BRC1E63 Heat pump Signal receiver unit ( separate type ) is supplied
Easy Installation
(Installed type)
BRC4C65 Wireless remote controller
is supplied in a set with a
in a set with a signal receiver.
(BRC4C66, BRC4C65)
Lightweight indoor unit
signal receiver.

Note: Remote controller cable is not included and must be obtained locally. Note: A signal receiver must be added to the indoor unit. Enables smooth transport and installation of the indoor unit.
(kg)

Indoor unit 50/60/71A 100/125/140A


Weight 42 50
■ This product is equipped with a gas sensor.
The gas sensor reacts to nearby smoke, chemical agents, and paint as well as equipment containing flammable gas (including propane,
butane, or methane), and sprays using flammable gases (such as LPG), including insecticides and hair spray. When this occurs, a
malfunction is displayed and operation is not possible. DIII-NET communication standard
■ A gas sensor that has once reacted must be replaced with a new gas sensor. Connection to a centralised control system is available
without option.
41 42
Specification Option
CEILING SUSPENDED TYPE P.63, 67 P.74

Comfortable airflow travels Stylish Model Installation Flexibility for


Freedom of Design
throughout the room Sophisticated design
Flap neatly closes when not in use.
Flexible
White colour installation 30 mm 30 mm
The unit fits more or more or more

*Water used in the test-run can be drained from


snugly into tight the air discharge opening rather than from the
spaces.
Comfort side as was formerly the case.

The technology of the DC fan motor, Drain pump kit (option)


wide sirocco fan, and large heat can be easily
600
exchanger combine for greater airflow incorporated mm
FHA50/60/71/100BVMV
FHA125/140BVMA and quiet operation Drain pipe connection can
be done inside the unit.
Refrigerant and drain pipe Drain pump kit
Auto swing (up and down) and louvers outlets are at the same
opening.
(built inside
the unit)
( left and right by hand ) bring comfort
to the room DIII-NET communication standard
Connection to a centralised control system is available
Louver manually adjusts for straight without need for an optional adaptor.
or wide angle airflow
All wiring and internal servicing can
be done from under the unit

The rear side removable


frame allows ease of
access for piping work
Suitable for high ceilings
Easy Maintenance
4.3
3.5
m
m
Drain pump kit (option) includes a
silver ion antibacterial agent
50-71BVMA 100-140BVMA That assists in preventing the growth of slime, bacteria,
and mould that cause odours and clogging.
50-71B 100B 125/140B
Standard 2.7m or less 3.8m or less 4.3m or less Non-flocking flap
High ceiling 2.7m-3.5m 3.8m-4.3m - Condensation does not easily
Note: Factory settings is “standard”.
form and dirt does not cling to
“High ceiling” are set with remote controller by field setting. non-flocking flap.
It is easy to clean. Non-flocking flap

Option Accessory required for indoor unit. Switchable fan speed: 5 steps and Auto
Control of airflow rate has been improved from 3-step to 5-step. Easy-clean, flat surfaces
Wired Remote Controller Wireless Remote Controller
It is easy to wipe dirt off the flat side and lower surfaces
of the unit.
Navigation Remote Controller
Cooling only
Quiet Operation
BRC7M56
dB(A)
Oil Resistant Grille
Sound pressure level
BRC1E63 Indoor unit
Heat pump
BRC7M53
Signal receiver unit
(Installed type) H HM M ML L Oil-resistant plastic is used for the
Wireless remote controller
is supplied in a set with a
50/60B 37.0 36.0 35.0 33.5 32.0 air suction grille.
signal receiver. 71B 38.0 37.0 36.0 35.0 34.0 This satisfies durability in restaurants and other similar
100B 42.0 40.0 38.0 36.0 34.0 environments.
125B 44.0 42.5 41.0 39.0 37.0 Note:
Note: Remote controller cable is not included and must be obtained locally. Note: A signal receiver must be added to the indoor unit.
Intended for use in salons, dining rooms, and ordinary sales floors, this
140B 46.0 44.0 42.0 40.0 38.0 specification is not suitable for kitchens or other harsh environments.

43 44
OUTDOOR UNIT

Compact Outdoor Unit


Reuse of Existing Piping: Refrigerant Pipe Size Table RZF series
RZA series
Existing pipe size (Liquid / Gas) 6.4 / 6.4 / 9.5 / 9.5 / 9.5 / 12.7 / 12.7 / Level Design pressure
19.1 15.9 19.1 difference (High pressure)
RZF Outdoor Unit 12.7 15.9 12.7 15.9

series RZF50CV2V RZF


Condition
9.5 / 15.9 Max. piping length 10m 10m 50m 50m ------- 25m -------
RZF60CV2V RZF71CYM RZF125CVM / YM 50-71CV2V
Cooling Chargeless pipng length 10m 10m 30m 30m ------- 15m ------- Max.
only RZF71CV2V RZF100CVM / YM RZF140CVM / YM 4.15MPa
Condition 30m
RZF
71CYM 9.5 / 15.9 Max. piping length 10m 10m 50m 50m 50m 25m 25m
100-140C Chargeless pipng length 10m 10m 30m 30m 30m 15m 15m The allowable minimum piping length
is 5 m.
Existing pipe size (Liquid / Gas) 6.4 / 6.4 / 9.5 / 9.5 / 9.5 / 12.7 / 12.7 / Level Design pressure ・Refer to the installation manual for
Outdoor Unit 12.7 15.9 12.7 15.9 19.1 15.9 19.1 difference (High pressure) details other than those mentioned in
Condition the left table such as additional
RZA refrigerant charge amount.
9.5 / 15.9 Max. piping length 10m 10m 50m 50m ------- ------- -------
50/60D ・Clean the existing piping if its length
RZA Chargeless pipng length 10m 10m 30m 30m ------- ------- ------- Max. exceeds 30m.
4.15MPa
series Condition 30m
・Clean the existing piping if existing
RZA 9.5 / 15.9 10m 10m 75m 75m 75m 35m 35m piping length exceeds limit of
Max. piping length
71-140D chargeless piping length to perform
Chargeless pipng length 10m 10m 30m 30m 30m 15m 15m pump-down refrigerant recovery.
RZA100DY1
RZA50DV2V RZA71DV1 RZA125DV1 / Y1 Standard pipe size Same condition with standard pipe Piping length and chargeless piping length are shortened
Heat
Pump RZA60DV2V RZA100DV1 RZA140DV1 / Y1 Piping length and chargeless piping length are much shortened Cooilng capacity is lowered (pay attention to piping length)
Reuse of existing piping is not allowed

Technology for energy efficiency


RZFC85DVM 4
RZFC
RZFC100DVM
series RZFC40DVM
The high efficiency compressor to achieve a high COP 2
RZFC50DVM RZFC71DY1
Cooling
RZFC60DVM RZFC85DY1 RZFC125DY1 1 Compressor equiped with reluctance DC motor
only RZFC71DVM RZFC100DY1 RZFC140DY1 3
Daikin DC Inverter models are equipped with the reluctance DC motor for compressor.
The reluctance DC motor uses 2 different types of torque, neodymium magnet*1 and 1
reluctance torque*2.
Easy Installation and Maintenance This motor can save energy because it generates more power with a smaller electric
power than an AC or previous DC motor.
Swing compressor
4-direction piping offers greater layout Facilitates pump down (Refrigerant recovery function) Reluctance DC Motor Reluctance
DC motor High efficiency during partial
freedom (RZF125/140, RZA71-140, RZFC125/140)

Motor efficiency
A pump-down switch is provided to make it easier to collect load operation.
refrigerant if the unit is to be moved or layout modified. DC motor *1. A neodymium magnet
The outer panel for the piping connection part of the front, More than 20%
is approximately 10
Energy savings is Swing bushing
*Pump-down function is available for pre-charged refrigerant amount. Note: times stronger than a
right side and backside can be removed and is easier for Data are based standard ferrite realised,
Refrigerant gas
*Although pumping-down operation allows most of the refrigerant to AC motor
post-installation piping work. be recovered in a short period of time, some refrigerant will remain
on studies magnet. eliminating the
conducted under *2. The torque created by friction and the
inside the indoor unit and refrigerant piping. Rotational speed controlled the change in power leakage of
Using a refrigerant recovery machine, recover remaining refrigerant
Removable part of bottom
Small load Large load conditions at a between the iron and
from the stop valve service port until the pressure falls to 0.09 MPa.
Low capacity High capacity
Daikin laboratory. magnet parts. refrigerant gas. Piston by incorporated
blade and roller.
(gauge pressure:-0.011MPa) or less.
frame makes the piping 2 Refrigerant cooling Fan
3
work easier Separation Low gas pressure detection function (RZF100-140CVM, RZF71-140CYM, RZA71-140D, RZFC71-140DY1) V-cut Propeller Fan (RZF50-100, RZA50/60, RZFC40-100)
(RZF125/140, RZA71-140, RZFC125/140) available
Effective gas monitoring reduces the labor required Daikin’s unique refrigerant Through use of a V-cut propeller fan that imitates the
for operation, maintenance, and repairs. cooling system exhibits efficiency of the swan, a migratory bird, airflow becomes
high cooling capacity smooth and loss is reduced.
even during high outdoor
temperatures.
Night Quiet Operation Mode RZF series RZA series Refrigerant cooling helps protect Imitating the
V-cut performance
the printed circuit board and propeller fan of the swan
The automatic night quiet mode will initiate 8 hours after maintains high cooling capacity
Sound pressure level1 (dB(A)) even during high outdoor
the peak temperature is reached in the daytime, and temperatures.
Rated
normal operation will resume 10 hours after that. Night Quiet
Mode
Peak outdoor temperature
Cooling Heating 4 High condensing capacity by micro channel heat exchanger RZF series RZFC series
50-71C 48 ------ 44
Reduced wind resistance
Capacity (%)

100C 49 ------ 45 The flattening of the heat exchanger tubes improves the flow of air and increases heat exchange efficiency.
100 RZF Reducing noise will
125C 52 ------ 45 reduce capacity slightly. Conventional tube and fin coil Micro channel coil
Conventional heat Micro channel
exchanger heat exchanger
8 hours 140C 54 ------ 45
50 10 hours Note : The diameter of the refrigerant
50-60D 47 49 43 1
Anechoic chamber The diameter of the Flat, multi-hole channel(holes where refrigerant
Load (%)

conversion value, refrigerant channel aluminium heat flows) is approx.1mm.


71D 48 50 44 (holes where
0 measured according to JIS exchanger tubes
100DV1 49 53 45 refrigerant flows) Approx.
48 parameters and criteria. is approx. 7mm
RZA 7mm
Sound (dB(A))

Rated Approx.
Note : 100DY1 48 50 44 During operation these
1mm
Operation

Quiet mode Utilizing flat, multi-hole heat exchanger tubes


44 Quiet mode Daikin date for RZF71C 125D 49 51 45 values are somewhat
increases the heat exchange area and realizes
Operating sound about higher owing to ambient Flow of refrigerant Flow of refrigerant energy savings.
8:00 12:00 16:00 20:00 0:00 4:00 8:00 4 dB quieter
140D 53 56 49 conditions.

45 46
REMOTE CONTROLLER - Optional accessory -

Easy-to-read remote controller allows various system control configurations and can control multiple indoor units.
Remote controller options are shown on the page introducing each indoor unit model.

Navigation Remote Controller NEW Simplified Remote Controller


(Wired Remote Controller) (Wired Remote Controller)

RZF series RZA series RZFC series


BRC1E63 BRC2E61 ON/OFF button
Operation mode
This simple, modern designed remote controller with
selection
fresh white colour matches your interior design. Temperature
Operation is much easier and smoother, just follow setting (+/-)
Airflow rate
the indications on the navigation remote controller.
(Fan speed)

Airflow direction

Energy saving Simple operation Compact


Using only six buttons, users have direct access Measuring only 85 x 85 mm, the new remote controller is
Setpoint auto reset Setpoint range set
to basic functions. extremely compact and complements any interior design.
- Even if the set temperature is changed, the new set temperature returns to - Saves energy by limiting the This enables them to easily set comfort to their
the previous preset value after a preset duration of time. min. and max. set preference.
- Period selectable from 30, 60, 90, or 120 min. temperature.
35
Restaurant example - Avoids excessive heating or Reduced size mm
cooling.
Restaurant opened Full tables at lunchtime After 30 minutes* Intuitive design
- This function is convenient if

120 mm

120 mm
Temperature is set to 27ºC Then is lowered to 24ºC for Automatically returns to preset
crowded room temperature (27ºC) the remote controller is By using pictograms, the user-friendly interface

85 mm
Returns to 35
installed where anyone can enables:
27°C 24°C 27 °C change the settings.
mm
automatically Overseas guests at hotels to understand
functions without having to know a foreign
language. 120 mm 85 mm 70 mm

*Preset-return time can be set Children and elderly users at home to operate Conventional Conventional
BRC2E61 simplified
OFF timer (programmed)
at 30, 60, 90, or 120 min
without having to read difficult and hard-to-see remote controller remote controller
commands.
- Sets and saves setting for an increment of time that automatically turns OFF
air conditioner after a preset period of time for each time operation starts.
- Period can be preset from 30 to 180 minutes in 10-minute increments.

Convenience
5-step airflow control Setback (default: OFF)
- The number of airflow steps depends on the type of - Maintains the room temperature in a specific range
indoor unit. during unoccupied periods by temporarily starting an
5-step control applies to FCF and FHA series. air conditioner that had been turned OFF.

Energy consumption monitoring *1,2,3,4 Weekly schedule


- Past power consumption for the current and - 5 actions per day can be scheduled
previous days (2-hour intervals), week (1-day for each day of the week.
intervals), and year (1-month intervals) can be - The holiday function will disable
checked. schedule timer for the days that
Note:
have been set as holiday.
*1
Availability of this function may vary according to model (limited to - 3 independent schedules can be set.
partial (e.g. summer, winter, mid-season)
functionality)
*2
Time setting is necessary. 
*3
This function cannot be used during group control.  Auto display off
*4
This is a reference value for comparison and is not intended as a - While operation is stopping, LCD display can be turned OFF.
value for investigation purposes in the calculation of electricity bills
or contract for electricity. Because it is a simple calculation of
It will be displayed again if any button is pressed.
power consumption, there are cases when the calculated value - Period can be preset from 10, 30, 60 minutes, and OFF.
differs with the measurement results of a wattmeter. Initial setting is 30 minutes.

47 48
REMOTE CONTROLLER - Optional accessory -

System variation to control multiple indoor units


Wireless Remote Controller Control pattern Wired remote controller Wireless remote controller

Control by 1 (Basic system)


The wireless remote controller is supplied in a set with a signal receiver. remote controller Non-polar, double-core Signal receiver unit installed
(max. wiring length 500 m) on indoor unit
Signal receiver unit of installed type is contained inside decoration panel or
indoor unit.
Shape of signal receiver unit differs according to the indoor unit. For control from 2 Control by 1 wireless remote
Control by 2 locations such as in controller and 1 wired remote
Note: The signal receiver unit shown in the photograph is for mounting inside the decoration panel of
controller (See note 2 and 3)
the ceiling mounted cassette type. remote controllers room and control room,
Connects 2 wired remote Signal receiver unit installed
exits, etc.
controllers (See note 1) on indoor unit
BRC7M6345F Backlight LCD of new wireless remote controller
Signal receiver unit
(For ceiling mounted
cassette type) For simultaneous
Group control control of up to 16
indoor units.
Automatic address setting function Automatic address setting function
Signal receiver unit installed on 1 indoor unit
Pressing the backlight button helps
operating in dark rooms.
Operation and monitoring
Control by is carried out using the (Command from outside)
Wireless remote controller for each indoor unit type contact signal from the
(Command from outside)
external command operation control box in
Cooling only Heat pump Optional wiring adaptor for Optional wiring adaptor for
the monitoring room.
CEILING MOUNTED BRC7M635F(K) (FCF series) BRC7M634F(K) (FCF series) electrical appendices is necessary electrical appendices is necessary
CASSETTE TYPE BRC7F635F (FCFC series)
Central remote controller (option) Central remote controller (option)
COMPACT MULTI FLOW BRC7E531W ----------------
DUCT CONNECTION MIDDLE BRC4C66 BRC4C65 (FBA series only) Centralised control of
STATIC PRESSURE TYPE up to 64 indoor groups
Centralised remote
CEILING MOUNTED BRC4C64 ---------------- control from remote location
SLIM DUCT TYPE up to 1 km away.
DUCT CONNECTION LOW STATIC BRC4C66 ----------------
PRESSURE WIDTH COMPACT TYPE Interface adaptor for SkyAir series (option) is Interface adaptor for SkyAir series (option) is
required (See note 4) required (See note 4)
DUCT CONNECTION LOW STATIC BRC4C66 ----------------
PRESSURE HEIGHT COMPACT TYPE
Heat Reclaim Heat Reclaim
FLOOR STANDING TYPE BRC4C66 BRC4C65 Ventilator Ventilator
Link by remote
CEILING SUSPENDED TYPE BRC7M56 BRC7M53 controller group control.
Can be operated simultaneously or Can be operated simultaneously by
independently by remote controller remote controller
(set by ventilation mode)

Wired remote controller has built-in temperature-sensor Interlock control Central remote controller (option) Central remote controller (option)
Enables temperature sensing closer to target area for improved comfort. (When using a remote control from another room, with Heat Reclaim
temperature-sensor of the indoor unit air inlet must be selected.) Ventilator

Facilitates maintenance and repair Zone link control by Heat Reclaim Heat Reclaim
centralised control. Ventilator Ventilator
All initial settings can be set from the remote controller. After interior construction is complete, ceiling mounted cassette type can be
remotely set without having to use a stepladder to access for manual setting. Heat Reclaim Ventilator for indoor units Heat Reclaim Ventilator
Setting contents: High ceiling use, air direction, filter type, address for centralised control (group control address is set automatically). within a zone is operated by interlocking. for indoor units within a
Can also be operated independently by zone is operated by interlocking.
remote controller.
Remote controller is equipped with error code display functions. This facilitates service in the unlikely event of a malfunction.
*Model name display function applies to BRC1E63 only. (Some models show their model code.) Note: 1Available combinations: 1) BRC1E63 (main) and BRC1E63 (sub) 2) BRC2E61 (main) and BRC2E61 (sub)
2
When a wireless remote controller is used, it is not possible to use 2 wireless remote controllers.
SkyAir shares common control with Heat Reclaim Ventilator and the other Daikin air-conditioning 3
Available combinations: 1) BRC1E63 (main) and BRC7M (sub) 2) BRC2E61 (main) and wireless remote controller (sub)
units, thus simplifying interlocking operations. 4
FFF requires interface adaptor for SkyAir series. FDF, FDBF, and FDLF series cannot connect to contralised control.

Easily adaptable to large-scale, high-function, centralised remote control systems.


Installing and connecting control wiring between SkyAir and other Daikin air-conditioning equipment is easy.
Easily adaptable to large-scale, high-function, centralised remote control system.
Central remote controller Unified on/off controller Schedule timer
LCD panel shows operating status in letters, numbers, and motion. DCS302CA61 (Option) DCS301BA61 (Option) DST301BA61 (Option) DCS601C51 (Option)

Airflow / swing display Displays auto-swing operating status and setting position of air discharge angle.

Preset temperature / Displays preset room temperature and operating status (fan, dry, cool).
operation mode display
Operation start and stop time can be set for individual timers up to 72 hours. The LCD also Centralised control, with setting as Centralised control of on/off by Unified control of weekly schedule With its high functionality, the full
simple as it is with a standard group or all at once for up to 256 for up to 1,024 indoor units. colour “all-in-one” graphic controller
Programming time display shows when it is time to clean the filter, when changeover is under centralised control, remote controller, of up to 64 groups indoor units. Schedule timer sets on/off time in 1 minute units facilitates management of SkyAir
and ventilation/cleaning. (1,024 indoor units) is possible. to be executed twice a day for a week at a time. System in a variety of ways.
Monitors operating status within the system covering 40 items, and displays a message to
Self-diagnosis function Enables centralised control via connection to a high-speed, DIII-NET The interface adaptor for SkyAir
indicate as soon as a malfunction occurs. Interface adaptor for SkyAir series
communication system, adopted for the Daikin   system. series is required for Compact
DTA112BA51 (Option) Necessary for interface adaptor for SkyAir series with the central remote control units shown at above. multi flow cassette type (FFF) .

49 50
FUNCTIONS
CEILING MOUNTED COMPACT MULTI FLOW CEILING DUCT CONNECTION MIDDLE CEILING MOUNTED

Functions
FLOOR STANDING TYPE CEILING SUSPENDED TYPE
CASSETTE TYPE Round Flow MOUNTED CASSETTE TYPE STATIC PRESSURE TYPE SLIM DUCT TYPE

overview Indoor unit FCF50-140CVM FFF50/60BV1 FBA50-140BVMA(9) FDF50/60BV1 FVA50-140AMVM


FHA50-100BVMV
FHA125/140BVMA

RZF series Outdoor unit RZF50-71CV2V, 100-140CVM


RZF71-140CYM
RZF50/60CV2V
RZF50-71CV2V, 100-140CVM
RZF71-140CYM
RZF50/60CV2V
RZF50-71CV2V, 100-140CVM
RZF71-140CYM
RZF50-71CV2V, 100-140CVM
RZF71-140CYM
Cooling only Remote Wired BRC1E63 ------- BRC1E63 ------- BRC1E63 ------- BRC1E63 ------- BRC1E63 ------- BRC1E63 -------
controller Wireless ------- BRC7M635F (K) ------- BRC7E531W ------- BRC4C66 ------- BRC4C64 ------- BRC4C66 ------- BRC7M56
1 Energy consumption monitoring *1 1
2 Sensing sensor stop mode *1 Sensing panel 2
3 Sensing sensor low mode *1, 2 Sensing panel 3
4 Auto display OFF *1 4
Energy 5 Setpoint auto reset *1 5
Saving 6 Setpoint range set *1 6
7 OFF timer (programmed) *1 7
8 Weekly schedule timer *1 8
9 ON/OFF timer 9
10 Circulation airflow *1 10
11 Setback *1 11
12 Quick start *1 12
13 Individual airflow control *1 13
14 Infrared presence sensor Sensing panel 14
15 Infrared floor sensor Sensing panel 15
16 Auto airflow function *1 Sensing panel 16
17 Auto swing 17
18 Swing pattern selection 18
Comfort 19 Draft prevention function (heating) 19
20 DC fan motor (Indoor unit) 20
21 Switchable fan speed 5 step 5 step 2 step 2 step 21 3 step 3 step 2 step 2 step 3 step 3 step 5 step 5 step
22 Auto airflow rate 22
23 High fan speed mode 23 *6

24 Two selectable temperature-sensors 24


25 High ceiling application 3.5m / 4.2m 3.5m / 4.2m 25 3.5m / 4.3m 3.5m / 4.3m
26 Hot start 26
27 Year-round cooling applicable 27
28 Night quiet operation *3 28
29 Anti-bacterial air filter 29 *7

30 Mould-proof air filter 30


Cleanliness 31 Silver ion anti-bacterial drain pan 31
32 Mould-proof drain pan 32
33 Auto grille panel 33
34 Drain pump mechanism 34 *7

35 Pre-charged for up to 30 m *3 35
36 Long-life filter 36 *7
Work & 37 Filter sign 37
Servicing 38 Low gas pressure detection *3 38
39 Emergency operation 39
40 Self-diagnosis function 40
41 Service contact display *1 41
42 Auto-restart 42
43 Auto-cooling / heating change-over 43
44 Control by 2 remote controllers *8 44 *8

45 Group control by 1 remote controller 45


46 External equipment interlock *4 Sensing panel 46
Control 47 External signal forced OFF and ON/OFF operation 47
48 External command control *5 48
49 Central remote control *7 49
50 Interlock control with Heat Reclaim Ventilator 50
51 DIII-NET communication standard *7 51
52 High-efficiency filter 52
53 Ultra long-life filter 53
Options 54 Fresh air intake kit 54
55 Overvoltage PCB *3 55

Note: *1: Applicable when BRC1E63 is used. *2: Not applicable when group control. *3: For outdoor units. *4: Adaptor for Wiring (and installation box) is necessary. *5: Wiring adaptor for electrical appendices (and installation box) is necessary.
*6: Applicable for FVA50-100. *7: Option is requied. *8: It is not possible to use 2 wireless remote controllers. Combination of BRC1E63 (main) and BRC7M (sub) is available.

51 52
FUNCTIONS
CEILING MOUNTED DUCT CONNECTION MIDDLE

Functions
CASSETTE TYPE Round Flow STATIC PRESSURE TYPE FLOOR STANDING TYPE CEILING SUSPENDED TYPE

overview Indoor unit FCF50-140CVM FBA50-140BVMA(9) FVA50-140AMVM


FHA50-100BVMV,
FHA125/140BVMA

RZA series Outdoor unit RZA50/60DV2V, 71-140DV1


RZA100-140DY1
RZA50/60DV2V, 71-140DV1
RZA100-140DY1
RZA50/60DV2V, 71-140DV1
RZA100-140DY1
RZA50/60DV2V, 71-140DV1
RZA100-140DY1
Heat pump Remote Wired BRC1E63 ------- BRC1E63 ------- BRC1E63 ------- BRC1E63 -------
controller Wireless ------- BRC7M634F (K) ------- BRC4C65 ------- BRC4C65 ------- BRC7M53
1 Energy consumption monitoring *1 1
2 Sensing sensor stop mode *1 Sensing panel 2
3 Sensing sensor low mode *1, 2 Sensing panel 3
4 Auto display OFF *1 4
Energy 5 Setpoint auto reset *1 5
Saving 6 Setpoint range set *1 6
7 OFF timer (programmed) *1 7
8 Weekly schedule timer *1 8
9 ON/OFF timer 9
10 Circulation airflow *1 10
11 Setback *1 11
12 Quick start *1 12
13 Individual airflow control *1 13
14 Infrared presence sensor Sensing panel 14
15 Infrared floor sensor Sensing panel 15
16 Auto airflow function *1 Sensing panel 16
17 Auto swing 17
18 Swing pattern selection 18
Comfort 19 Draft prevention function (heating) 19
20 DC fan motor (Indoor unit) 20
21 Switchable fan speed 5 step 5 step 3 step 3 step 21 3 step 3 step 5 step 5 step
22 Auto airflow rate 22
23 High fan speed mode 23 *6

24 Two selectable temperature-sensors 24


25 High ceiling application 3.5m / 4.2m 3.5m / 4.2m 25 3.5m / 4.3m 3.5m / 4.3m
26 Hot start 26
27 Year-round cooling applicable 27
28 Night quiet operation *3 28
29 Anti-bacterial air filter *7 29
30 Mould-proof air filter 30
Cleanliness 31 Silver ion anti-bacterial drain pan 31
32 Mould-proof drain pan 32
33 Auto grille panel 33
34 Drain pump mechanism 34 *7

35 Pre-charged for up to 30 m *3 35
36 Long-life filter *7 36
Work & 37 Filter sign 37
Servicing 38 Low gas pressure detection *3 38
39 Emergency operation 39
40 Self-diagnosis function 40
41 Service contact display *1 41
42 Auto-restart 42
43 Auto-cooling / heating change-over 43
44 Control by 2 remote controllers *8 44 *8

45 Group control by 1 remote controller 45


46 External equipment interlock *4 Sensing panel 46 Note:
Control 47 External signal forced OFF and ON/OFF operation 47 *1: Applicable when BRC1E63 is used.
48 External command control *5 48 *2: Not applicable when group control.
49 Central remote control 49 *3: For outdoor units.
50 Interlock control with Heat Reclaim Ventilator 50 *4: Adaptor for Wiring (and installation box) is necessary.
51 DIII-NET communication standard 51 *5: Wiring adaptor for electrical appendices (and installation box)
is necessary.
52 High-efficiency filter 52 *6: Applicable for FVA50-100.
53 Ultra long-life filter 53 *7: Option is requied.
Options 54 Fresh air intake kit 54 *8: It is not possible to use 2 wireless remote controllers.
55 Overvoltage PCB *3 55 Combination of BRC1E63 (main) and BRC7M (sub) is available.

53 54
FUNCTIONS
CEILING MOUNTED DUCT CONNECTION MIDDLE STATIC DUCT CONNECTION LOW STATIC DUCT CONNECTION LOW STATIC

Functions
CASSETTE TYPE Round Flow PRESSURE TYPE PRESSURE WIDTH COMPACT TYPE PRESSURE HEIGHT COMPACT TYPE

overview Indoor unit FCFC50-140DVM FBFC40-140DVM(9) FDBF40-85DV1 FDLF40-85DV1

RZFC series Outdoor unit RZFC40-100DVM


RZFC71-140DY1
RZFC40-100DVM
RZFC71-140DY1
RZFC40-85DVM
RZFC71/85DY1
RZFC40-85DVM
RZFC71/85DY1
Cooling only Remote Wired BRC2E61 ------- BRC2E61 ------- BRC2E61 ------- BRC2E61 -------
controller Wireless ------- BRC7F635F ------- BRC4C66 ------- BRC4C66 ------- BRC4C66
1 Energy consumption monitoring 1
2 Sensing sensor stop mode 2
3 Sensing sensor low mode 3
4 Auto display OFF 4
Energy 5 Setpoint auto reset 5
Saving 6 Setpoint range set 6
7 OFF timer (programmed) 7
8 Weekly schedule timer 8
9 ON/OFF timer 9
10 Circulation airflow 10
11 Setback 11
12 Quick start 12
13 Individual airflow control 13
14 Infrared presence sensor 14
15 Infrared floor sensor 15
16 Auto airflow function 16
17 Auto swing 17
18 Swing pattern selection 18
Comfort 19 Draft prevention function (heating) 19
20 DC fan motor (Indoor unit) 20
21 Switchable fan speed 3 step 3 step 3 step 3 step 21 3 step 3 step 3 step 3 step
22 Auto airflow rate 22
23 High fan speed mode 23
24 Two selectable temperature-sensors 24
25 High ceiling application 3.5m / 4.2m 25
26 Hot start 26
27 Year-round cooling applicable 27
28 Night quiet operation 28
29 Anti-bacterial air filter *3 29
30 Mould-proof air filter 30
Cleanliness 31 Silver ion anti-bacterial drain pan 31
32 Mould-proof drain pan 32
33 Auto grille panel 33
34 Drain pump mechanism *3 34
35 Pre-charged for up to 10 / 15m *1 35
36 Long-life filter *3 36
Work & 37 Filter sign 37
Servicing 38 Low gas pressure detection *1 38
39 Emergency operation *4 *4 39 *4 *4

40 Self-diagnosis function 40
41 Service contact display 41
42 Auto-restart 42
43 Auto-cooling / heating change-over 43
44 Control by 2 remote controllers *5 *5 44 *5 *5

45 Group control by 1 remote controller 45


46 External equipment interlock 46
Control 47 External signal forced OFF and ON/OFF operation 47
48 External command control *2 48 Note:
49 Central remote control 49 *1: For outdoor units.
50 Interlock control with Heat Reclaim Ventilator 50 *2: Wiring adaptor for electrical appendices (and installation box)
51 DIII-NET communication standard 51 is necessary.
*3: Option is requied.
52 High-efficiency filter 52 *4: For outdoor unit RZFC-DY1 only.
53 Ultra long-life filter 53 *5: It is not possible to use 2 wireless remote controllers.
Options 54 Fresh air intake kit 54 Combination of BRC2E61 (main) and wireless remote controller
55 Overvoltage PCB 55 (sub) is available.

55 56
FUNCTIONS
Cleanliness
Abundance of functions that provide comfortable 29. Anti-bacterial air filter 31. Silver ion anti-bacterial drain pan
air-conditioning in stores and offices The air filter has an anti-bacterial treatment to help prevent the
growth of bacteria and mould on it.
A built-in antibacterial treatment that uses silver ion in the drain pan
prevents the growth of slime, bacteria, and mould that cause odours
Note: Some features are only available on selected models. See overview pages for full list of features applicable to each unit. and clogging.
30. Mould-proof air filter
Sanitary filter has mould-resistant treatment. 32. Mould-proof drain pan
Energy Saving Mould-proof drain pan prevents growth of mould in highly humid conditions.

1. Energy consumption monitoring 6. Setpoint range set


Past power consumption is displayed for the current and previous
days as well as in weekly and yearly intervals.
Saves energy by limiting the minimum and maximum set temperatures.
Avoids excessive heating and cooling.
Work & Servicing
2. Sensing sensor stop mode 7. OFF timer (programmed) 33. Auto grille panel 38. Low gas pressure detection
When the room is unoccupied, the system stops automatically. Sets and saves setting for an increment of time that automatically Grille and air filter cleaning can be performed without need for Insufficient gas charging is normally hard to detect. During test run
turns off air conditioner after a preset period of time for each time a stepladder by lowering the grille. after installation and regular inspection, the refrigerant level is
3. Sensing sensor low mode operation starts. monitored by a microprocessor to maintain proper gas pressure.
When the room is unoccupied, the set temperature is shifted 34. Drain pump mechanism Reliability is assured and maintenance and inspection can be carried
automatically. 8. Weekly schedule timer Steeper gradient realises more efficient out more quickly.
Up to five operation ON/OFF settings can be programmed per day for condensate drainage. High-lift is especially
4. Auto display OFF each day of the week. Not only can the time be set for the operation useful for long lengths of drain piping. 39. Emergency operation
While operation is stopping, the LCD display can be turned off.  ON setting, but also the temperature. Even if there is a malfunction elsewhere in the system, the fan or
It can be displayed again when any button is pressed. 35. Pre-charged for up to 30 m, 10 / 15 m compressor can still be operated. (depending on the malfunction)
9. ON/OFF timer If refrigerant piping length does not exceed 30 m, 10 m,
5. Setpoint auto reset Operation starts when the preset time of the ON timer elapses and or 15 m, there is no need for on-site gas charging. 40. Self-diagnosis function
Even if the set temperature is changed, the new set temperature stops when the preset time of the OFF timer elapses. ・30 m: RZF/RZA series ・10 m: RZFC40-71DVM The operating parameters of indoor and outdoor units, and sensor
returns to the previous preset value after a preset duration of time. ・15 m: RZFC85-100DVM, 71-140DY1 data at critical locations throughout the system, are constantly
monitored using a microcomputer. To facilitate quick response in the
36. Long-life filter event of a malfunction, a message appears on the LCD of the remote
Maintenance is not required for one year*. controller and an LED on the unit illuminates.
Comfort The filter is washable and can be reused.
*For dust concentration of 0.15 mg/m3 41. Service contact display
When installing the unit, registration of the service contact is available
10. Circulation airflow 20. DC fan motor (Indoor unit) 37. Filter sign to the wired remote controller.
The filter sign warns you when it is time to clean the filter.
At the start of operation, airflow changes repeatedly between DC fan motor improves efficiency.
*When using a wired remote controller the sign is displayed in the LCD.
horizontal flow and downward flow (swing during cool operation),
and air is sent throughout the room to eliminate uneven 21. Switchable fan speed When using a wireless remote controller the filter sign lamp illuminates
on the signal receiver unit.
temperatures. High setting provides maximum reach while low setting minimises drafts.

11. Setback 22. Auto airflow rate


Maintains the room temperature in a specific range during
unoccupied periods by temporarily starting an air conditioner that
Airflow rate is automatically controlled in accordance with the
difference between room temperature and set temperature. Control
had been turned OFF.
23. High fan speed mode 42. Auto-restart 48. External command control
12. Quick start You can increase fan speed approximately 10% higher than the
If there is a power outage while the equipment is operating, Operation and monitoring is carried out using the contact signal from
At operation start, capacity priority operation is possible. "high" setting. the operation control box in the building monitoring room.
operations will restart in the same mode as before the power
13. Individual airflow control 24. Two selectable temperature-sensors cut when electricity is restored. *Wiring adaptor for electrical appendices (and installation box) is necessary.

Airflow direction can be individually adjusted for each air Temperature-sensors are included in 43. Auto-cooling / heating change-over 49. Central remote control
discharge outlet to deliver optimal air distribution. the indoor unit and optional wired
Detects difference in preset temperature and actual room Optional central remote controller enables centralised control of up to
remote controller. Temperature sensing
14. Infrared presence sensor closer to target area is possible to
temperature and automatically switches to cooling or heating 1024 indoor units (64 groups) from up to 1 km away.
accordingly.
The sensor detects the presence of people in each of the 4 areas. further increase the comfort level. 50. Interlock control with Heat Reclaim Ventilator
15. Infrared floor sensor
Use the temperature-sensor in the indoor unit when
controlling air conditioning from another room.
44. Control by 2 remote controllers Enables interlocking control with external equipment such as Heat
Using 2 remote controllers you can operate the equipment Reclaim Ventilator.
The sensor detects the floor temperature and automatically Note: Wireless remote controllers have no temperature-sensor.
locally or from a remote location.
adjusts operation of the indoor unit to reduce the temperature
25. High ceiling application *When a wireless remote controller is used, it is not possible to use 2 51. DIII-NET communication standard
difference between the ceiling and the floor.
wireless remote controllers. Connection to a centralised control system is available
Delivers air-conditioning comfort
16. Auto airflow function all the way down to the floor in
without need for an optional adaptor.
When this function is set, airflow direction can be directed toward air-conditioning zones with high
45. Group control by 1 remote controller
or away from people when human presence is detected. ceilings. You can turn up to 16 indoor units ON/OFF with a single
remote controller. (When using connected indoor units, the
Note: When units are installed on high ceilings, depending on the model,
17. Auto swing settings must all be the same and on/off will be simultaneous.)
Delivers comfortable air-conditioning to all areas, near to and far
various restrictions concerning maximum height, air discharge direction,
Options
from the air-conditioner.
and choice of options may apply.
46. External equipment interlock
The air flow direction can be fixed at your desired angle by the
26. Hot start Human presence is detected by the built-in infrared presence
52. High-efficiency filter
Cold air flow is avoided when heating operation starts or when sensor in the sensing panel, and the presence detection
remote controller. signal can be output and interlocked with external equipment. Two types are available: 65% and 90% colorimetry.
switching to heat after defrosting.
18. Swing pattern selection Power conservation is possible though the interlock of
53. Ultra long-life filter
You can freely set air discharge settings by remote controller.
27. Year-round cooling applicable external equipment, such as lighting, with the infrared
presence sensor. Requires no maintenance for about 4 years* (10,000h) in
Efficient cooling even in winter when the indoor temperatures are
(1) Standard (2) Draft prevention (3) Ceiling soiling *Adaptor for Wiring (and installation box) is necessary. stores and offices.
higher than those outside, such as in underground public spaces or
setting setting prevention setting *For dust concentration of 0.15 mg/m3
offices with many computers.
47. External signal forced OFF and ON/OFF
28. Night quiet operation 54. Fresh air intake kit
operation You can provide air-conditioning with fresh air from outside.
The Automatic night quiet mode will initiate 8 hours after the peak
temperature is reached in the daytime, and normal operation will The air conditioner can be interlocked with the keycard Convenient for places where a ventilation fan cannot be installed.
resume 10 hours after that. system and turned ON/OFF by locking and unlocking the
19. Draft prevention function (heating) room. 55. Overvoltage PCB
The air conditioner can be also be turned OFF by the interlock Optional circuit eliminates the need for a stabiliser and offer
To prevent cold air drafts, automatically adjusts airflow to near
with the ventilation and lighting OFF signal. additional protection for devices in the outdoor unit, such as
horizontal position when heating initially starts or when the thermo off.
*Field setting with remote controller. its fan motor and compressor.

57 58
SPECIFICATIONS RZF series

CEILING MOUNTED CASSETTE TYPE <Round Flow> (1 Phase) Cooling only COMPACT MULTI FLOW CEILING MOUNTED CASSETTE TYPE (1 Phase) Cooling only
50 60 71 100 125 140 50 60
Indoor unit FCF50CVM FCF60CVM FCF71CVM FCF100CVM FCF125CVM FCF140CVM Indoor unit FFF50BV1 FFF60BV1
Model Model
Name Outdoor unit Name Outdoor unit
RZF50CV2V RZF60CV2V RZF71CV2V RZF100CVM RZF125CVM RZF140CVM RZF50CV2V RZF60CV2V
Power supply Outdoor unit 1 Phase, 220V, 50Hz 1 Phase, 220-240 / 220-230V, 50 / 60Hz Power supply Outdoor unit 1 Phase, 220V, 50Hz
Cooling Capacity 1,2 5.0 6.0 7.1 10.0 12.5 14.0 Cooling Capacity 1,2 5.0 6.0
Rated (Min. - Max.) kW (2.3-5.6) (2.6-6.3) (3.2-8.0) (5.0-11.2) (5.7-14.0) (6.2-15.5) Rated (Min. - Max.) kW (2.3-5.6) (2.6-6.3)
17,100 20,500 24,200 34,100 42,700 47,800 17,100 20,500
Btu/h (7,800-19,100) (8,900-21,500) (10,900-27,300) (17,100-38,200) (19,500-47,800) (21,200-52,900) Btu/h (7,800-19,100) (8,900-21,500)
Power consumption Cooling 1 kW 1.14 1.53 1.93 2.97 4.18 5.47 Power consumption Cooling 1 kW 1.51 2.00
COP kW/kW 4.39 3.92 3.68 3.37 2.99 2.56 COP kW/kW 3.31 3.00
CSPF kWh/kWh 6.60 6.31 6.17 5.50 5.15 5.00 CSPF kWh/kWh 4.96 4.73
Indoor unit Colour Unit ---------- Indoor unit Colour Unit ----------
Decoration panel Fresh white Decoration panel White
Airflow rate 3
m /min 23.0 / 21.0 / 18.5 / 16.0 / 13.5 34.5 / 31.0 / 27.5 / 24.0 / 20.0 36.5 / 33.0 / 29.0 / 25.0 / 21.0 Airflow rate (H/L) m /min
3
15.0 / 10.0
(H / HM / M / ML / L) cfm 812 / 741 / 653 / 565 / 477 1,218 / 1,094 / 971 / 847 / 706 1,288 / 1,165 / 1,024 / 883 / 741 cfm 530 / 353
Sound pressure level 3 (H / HM / M / ML / L) dB(A) 37.0 / 34.5 / 32.0 / 29.5 / 27.5 45.0 / 41.5 / 38.0 / 35.0 / 32.5 46.0 / 43.0 / 40.0 / 36.0 / 32.5 Sound pressure level 3 (H/L) dB(A) 41 / 32
Dimensions Unit mm 256X840X840 298X840X840 Dimensions Unit mm 260(286*)X575X575 (*Include control box)
(HXWXD) Decoration panel mm 50X950X950 (HXWXD) Decoration panel mm 55X700X700
Machine Unit kg 22 24 Machine Unit kg 17.5
weight Decoration panel kg 5.5 weight Decoration panel kg 2.7
Certified Operation range °CWB 14 to 25 Certified Operation range °CWB 14 to 25
Outdoor Colour Ivory white Outdoor Colour Ivory white
unit Coil Type Micro channel unit Coil Type Micro channel
Compressor Type Hermetically sealed swing type Compressor Type Hermetically sealed swing type
Motor output kW 1.3 1.6 2.4 Motor output kW 1.3
Refrigerant charge (R32) kg 1.2 (Charged for 30 m) 1.3 (Charged for 30 m) 1.9 (Charged for 30 m) Refrigerant charge (R32) kg 1.2 (Charged for 30 m)
Sound Cooling dB(A) 48 49 52 54 Sound Cooling dB(A) 48
pressure level 3 Night quiet mode pressure level 3
dB(A) 44 45 Night quiet mode dB(A) 44
Dimensions (HXWXD) mm 595X845X300 695X930X350 990X940X320 Dimensions (HXWXD) mm 595X845X300
Machine weight kg 41 48 64 Machine weight kg 41
Certified Operation range °CDB 21 to 46 Certified Operation range °CDB 21 to 46
Piping Liquid (Flare) mm 9.5 Piping Liquid (Flare) mm 9.5
connections Gas (Flare) mm 15.9 connections Gas (Flare) mm 15.9
Drain Indoor unit mm VP25 (I.D. 25XO.D. 32) Drain Indoor unit mm VP20 (I.D. 20XO.D. 26)
Outdoor unit mm 26.0 (Hole) 18.0 (Hole) 26.0 (Hole) Outdoor unit mm 26.0 (Hole)
Max. interunit piping length m 50 (Equivalent length 70) Max. interunit piping length m 50 (Equivalent length 70)
Max. installation level difference m 30 Max. installation level difference m 30
Heat insulation Both liquid and gas piping Heat insulation Both liquid and gas piping
Note :
1
Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal).
2
Capacities are net, including a deduction for cooling for indoor fan motor heat.
3
The operation sound is measured in anechoic chamber. If it is measured under the actual installation conditions, it is normally over the set value due to environmental noise and sound reflection.

CEILING MOUNTED CASSETTE TYPE <Round Flow> (3 Phase) Cooling only DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE (1 Phase) Cooling only
71 100 125 140 50 60 71 100 125 140
Indoor unit FCF71CVM FCF100CVM FCF125CVM FCF140CVM Indoor unit FBA50BVMA(9) FBA60BVMA(9) FBA71BVMA(9) FBA100BVMA(9) FBA125BVMA(9) FBA140BVMA(9)
Model Model
Name Outdoor unit Name Outdoor unit
RZF71CYM RZF100CYM RZF125CYM RZF140CYM RZF50CV2V RZF60CV2V RZF71CV2V RZF100CVM RZF125CVM RZF140CVM
Power supply Outdoor unit 3 Phase, 380-415 / 380V, 50 / 60Hz Power supply Indoor unit 1 Phase, 220-240V / 220-230V, 50 / 60Hz
Cooling Capacity 1,2 7.1 10.0 12.5 14.0 Outdoor unit 1 Phase, 220V, 50Hz 1 Phase, 220-240 / 220-230V, 50 / 60Hz
Rated (Min. - Max.) kW (3.2-8.0) (5.0-11.2) (5.7-14.0) (6.2-15.5)
Cooling Capacity 1,2 5.0 6.0 7.1 10.0 12.5 14.0
Rated (Min. - Max.) kW (2.3-5.6) (2.6-6.3) (3.2-8.0) (5.0-11.2) (5.7-14.0) (6.2-15.5)
24,200 34,100 42,700 47,800
Btu/h (10,900-27,300) (17,100-38,200) (19,500-47,800) (21,200-52,900) 17,100 20,500 24,200 34,100 42,700 47,800
Btu/h (7,800-19,100) (8,900-21,500) (10,900-27,300) (17,100-38,200) (19,500-47,800) (21,200-52,900)
Power consumption Cooling 1 kW 1.93 2.97 4.18 5.47
COP kW/kW 3.68 3.37 2.99 2.56 Power consumption Cooling 1 kW 1.35 1.64 2.15 3.01 4.44 5.69
CSPF kWh/kWh 6.17 5.50 5.15 5.00 COP kW/kW 3.70 3.66 3.30 3.32 2.82 2.46
Indoor unit Colour Unit ---------- CSPF kWh/kWh 5.51 5.30 5.19 4.88 4.70 4.47
Decoration panel Fresh white Indoor unit Colour ----------
Airflow rate m3/min 23.0 / 21.0 / 18.5 / 16.0 / 13.5 34.5 / 31.0 / 27.5 / 24.0 / 20.0 36.5 / 33.0 / 29.0 / 25.0 / 21.0 Fan Airflow rate (H/M/L) m3/min 18.0 / 15.0 / 12.5 23.0 / 19.5 / 16.0 32.0 / 27.0 / 22.5 36.0 / 30.5 / 25.0
(H / HM / M / ML / L) cfm 812 / 741 / 653 / 565 / 477 1,218 / 1,094 / 971 / 847 / 706 1,288 / 1,165 / 1,024 / 883 / 741 cfm 635 / 530 / 441 812 / 688 / 565 1,130 / 953 / 794 1,271 / 1,077 / 883
Sound pressure level 3 (H / HM / M / ML / L) dB(A) 37.0 / 34.5 / 32.0 / 29.5 / 27.5 45.0 / 41.5 / 38.0 / 35.0 / 32.5 46.0 / 43.0 / 40.0 / 36.0 / 32.5 External static pressure 3
Pa Rated 50 (50-150)
Dimensions Unit mm 256X840X840 298X840X840 Sound pressure level 4 (H/M/L) dB(A) 35.0 / 33.0 / 31.0 38.0 / 35.0 / 33.0 38.0 / 35.5 / 33.0 40.0 / 37.5 / 35.0
(HXWXD) Decoration panel mm 50X950X950 Air filter 5 ----------
Machine Unit kg 22 24 Dimensions (HXWXD) mm 245X1000X800 245X1400X800
weight Decoration panel kg 5.5 Machine weight kg 37 47
Certified Operation range °CWB 14 to 25 Certified Operation range °CWB 14 to 25
Outdoor Colour Ivory white Outdoor Colour Ivory white
unit Coil Type Micro channel unit Coil Type Micro channel
Compressor Type Hermetically sealed swing type Compressor Type Hermetically sealed swing type
Motor output kW 1.6 2.4 Motor output kW 1.3 1.6 2.4
Refrigerant charge (R32) kg 1.3 (Charged for 30 m) 1.9 (Charged for 30 m) Refrigerant charge (R32) kg 1.2 (Charged for 30 m) 1.3 (Charged for 30 m) 1.9 (Charged for 30 m)
Sound Cooling dB(A) 48 49 52 54 Sound Cooling dB(A) 48 49 52 54
pressure level 3 pressure level 4
Night quiet mode dB(A) 44 45 Night quiet mode dB(A) 44 45
Dimensions (HXWXD) mm 695X930X350 990X940X320 Dimensions (HXWXD) mm 595X845X300 695X930X350 990X940X320
Machine weight kg 48 64 Machine weight kg 41 48 64
Certified Operation range °CDB 21 to 46 Certified Operation range °CDB 21 to 46
Piping Liquid (Flare) mm 9.5 Piping Liquid (Flare) mm 9.5
connections Gas (Flare) mm 15.9 connections Gas (Flare) mm 15.9
Drain Indoor unit mm VP25 (I.D. 25XO.D. 32) Drain Indoor unit mm VP25 (I.D. 25XO.D. 32)
Outdoor unit mm 18.0 (Hole) 26.0 (Hole) Outdoor unit mm 26.0 (Hole) 18.0 (Hole) 26.0 (Hole)
Max. interunit piping length m 50 (Equivalent length 70) Max. interunit piping length m 50 (Equivalent length 70)
Max. installation level difference m 30 Max. installation level difference m 30
Heat insulation Both liquid and gas piping Heat insulation Both liquid and gas piping
Note : Note :
1
Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal). 1
Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal)
2
Capacities are net, including a deduction for cooling for indoor fan motor heat. 2
Capacities are net, including a deduction for cooling for indoor fan motor heat.
3
The operation sound is measured in anechoic chamber. If it is measured under the actual installation conditions, it is normally over the set value due to environmental noise and sound reflection. 3
External static pressure is changeable in 11 stages by remote controller.
4
The operation sound is measured in anechoic chamber. If it is measured under the actual installation conditions, it is normally over the set value due to environmental noise and sound reflection.
5
Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its dust collection efficiency (gravity method) 50% or more.

59 60
SPECIFICATIONS RZF series

DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE (3 Phase) Cooling only FLOOR STANDING TYPE (1 Phase) Cooling only
71 100 125 140 50 60 71 100 125 140
Indoor unit FBA71BVMA(9) FBA100BVMA(9) FBA125BVMA(9) FBA140BVMA(9) Indoor unit FVA50AMVM FVA60AMVM FVA71AMVM FVA100AMVM FVA125AMVM FVA140AMVM
Model Model
Name Outdoor unit Name Outdoor unit
RZF71CYM RZF100CYM RZF125CYM RZF140CYM RZF50CV2V RZF60CV2V RZF71CV2V RZF100CVM RZF125CVM RZF140CVM
Power supply Indoor unit 1 Phase, 220-240V / 220-230V, 50 / 60Hz Power supply Outdoor unit 1 Phase, 220V, 50Hz 1 Phase, 220-240 / 220-230V, 50 / 60Hz
Outdoor unit 3 Phase, 380-415 / 380V, 50 / 60Hz Cooling Capacity 1,2 5.0 6.0 7.1 10.0 12.5 14.0
Rated (Min. - Max.) kW (2.3-5.6) (2.6-6.3) (3.2-8.0) (5.0-11.2) (5.7-14.0) (6.2-15.5)
Cooling Capacity 1,2 7.1 10.0 12.5 14.0
Rated (Min. - Max.) kW (3.2-8.0) (5.0-11.2) (5.7-14.0) (6.2-15.5) 17,100 20,500 24,200 34,100 42,700 47,800
Btu/h (7,800-19,100) (8,900-21,500) (10,900-27,300) (17,100-38,200) (19,500-47,800) (21,200-52,900)
24,200 34,100 42,700 47,800
Btu/h (10,900-27,300) (17,100-38,200) (19,500-47,800) (21,200-52,900) Power consumption Cooling 1 kW 1.23 1.79 2.51 3.48 4.48 5.71
Power consumption Cooling 1 kW 2.15 3.01 4.44 5.69 COP kW/kW 4.07 3.35 2.83 2.87 2.79 2.45
COP kW/kW 3.30 3.32 2.82 2.46 CSPF kWh/kWh 6.03 4.86 4.46 4.19 4.67 4.18
CSPF kWh/kWh 5.19 4.88 4.70 4.47 Indoor unit Colour Fresh white
Indoor unit Colour ---------- Airflow rate m3/min 18 / 16 / 14 28 / 25 / 22 28 / 26 / 24 30 / 28 / 26
Fan Airflow rate (H/M/L) m /min
3
23.0 / 19.5 / 16.0 32.0 / 27.0 / 22.5 36.0 / 30.5 / 25.0 (H / M / L) cfm 635 / 565 / 494 988 / 883 / 777 988 / 918 / 847 1,059 / 988 / 918
cfm 812 / 688 / 565 1,130 / 953 / 794 1,271 / 1,077 / 883 Sound pressure level (H / M / L)
3
dB(A) 43 / 41 / 38 50 / 47 / 44 51 / 48 / 46 53 / 51 / 48
External static pressure 3 Pa Rated 50 (50-150) Dimensions (HXWXD) mm 1,850X600X270 1,850X600X350
Sound pressure level 4 (H/M/L) dB(A) 38.0 / 35.0 / 33.0 38.0 / 35.5 / 33.0 40.0 / 37.5 / 35.0 Machine weight kg 42 50
Air filter 5 ---------- Certified Operation range °CWB 14 to 25
Dimensions (HXWXD) mm 245X1000X800 245X1400X800 Outdoor Colour Ivory white
Machine weight kg 37 47 unit Coil Type Micro channel
Certified Operation range °CWB 14 to 25 Compressor Type Hermetically sealed swing type
Outdoor Colour Ivory white Motor output kW 1.30 1.60 2.40
unit Coil Type Micro channel Refrigerant charge (R32) kg 1.2 (Charged for 30 m) 1.3 (Charged for 30 m) 1.9 (Charged for 30 m)
Compressor Type Hermetically sealed swing type Sound Cooling dB(A) 48 49 52 54
pressure level 3
Motor output kW 1.6 2.4 Night quiet mode dB(A) 44 45
Refrigerant charge (R32) kg 1.3 (Charged for 30 m) 1.9 (Charged for 30 m) Dimensions (HXWXD) mm 595X845X300 695X930X350 990X940X320
Sound Cooling dB(A) 48 49 52 54 Machine weight kg 41 48 64
pressure level 4
Night quiet mode dB(A) 44 45 Certified Operation range °CDB 21 to 46
Dimensions (HXWXD) mm 695X930X350 990X940X320 Piping Liquid (Flare) mm 9.5
Machine weight kg 48 64 connections Gas (Flare) mm 15.9
Certified Operation range °CDB 21 to 46 Drain Indoor unit mm VP20 (I.D. 20XO.D. 26)
Piping Liquid (Flare) mm 9.5 Outdoor unit mm 26.0 (Hole) 18.0 (Hole) 26.0 (Hole)
connections Gas (Flare) mm 15.9 Max. interunit piping length m 50 (Equivalent length 70)
Drain Indoor unit mm VP25 (I.D. 25XO.D. 32) Max. installation level difference m 30
Outdoor unit mm 18.0 (Hole) 26.0 (Hole) Heat insulation Both liquid and gas piping
Max. interunit piping length m 50 (Equivalent length 70)
Max. installation level difference m 30
Heat insulation Both liquid and gas piping
Note :
1
Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal)
2
Capacities are net, including a deduction for cooling for indoor fan motor heat.
3
External static pressure is changeable in 11 stages by remote controller.
4
The operation sound is measured in anechoic chamber. If it is measured under the actual installation conditions, it is normally over the set value due to environmental noise and sound reflection.
5
Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its dust collection efficiency (gravity method) 50% or more.

CEILING MOUNTED SLIM DUCT TYPE (1 Phase) Cooling only FLOOR STANDING TYPE (3 Phase) Cooling only
50 60 71 100 125 140
Indoor unit FDF50BV1 FDF60BV1 Indoor unit FVA71AMVM FVA100AMVM FVA125AMVM FVA140AMVM
Model Model
Name Outdoor unit Name Outdoor unit
RZF50CV2V RZF60CV2V RZF71CYM RZF100CYM RZF125CYM RZF140CYM
Power supply Outdoor unit 1 Phase, 220V, 50Hz Power supply Outdoor unit 3 Phase, 380-415 / 380V, 50 / 60Hz
Cooling Capacity 1,2 5.0 6.0 Cooling Capacity 1,2 7.1 10.0 12.5 14.0
Rated (Min. - Max.) kW (2.3-5.6) (2.6-6.3) Rated (Min. - Max.) kW (3.2-8.0) (5.0-11.2) (5.7-14.0) (6.2-15.5)
17,100 20,500 24,200 34,100 42,700 47,800
Btu/h (7,800-19,100) (8,900-21,500) Btu/h (10,900-27,300) (17,100-38,200) (19,500-47,800) (21,200-52,900)
Power consumption Cooling 1
kW 1.51 1.98 Power consumption Cooling 1
kW 2.51 3.48 4.48 5.71
COP kW/kW 3.31 3.03 COP kW/kW 2.83 2.87 2.79 2.45
CSPF kWh/kWh 4.98 4.78 CSPF kWh/kWh 4.46 4.19 4.67 4.18
Indoor unit Colour Unit ---------- Indoor unit Colour Fresh white
Fan Airflow rate (H/L) m3/min 16.0 / 13.5 Airflow rate m3/min 18 / 16 / 14 28 / 25 / 22 28 / 26 / 24 30 / 28 / 26
cfm 565 / 477 (H / M / L) cfm 635 / 565 / 494 988 / 883 / 777 988 / 918 / 847 1,059 / 988 / 918
External static pressure Pa 40 Sound pressure level 3 (H / M / L) dB(A) 43 / 41 / 38 50 / 47 / 44 51 / 48 / 46 53 / 51 / 48
Sound pressure level 3 (H/L) dB(A) 38 / 34 Dimensions (HXWXD) mm 1,850X600X270 1,850X600X350
Air filter Mould-proof air filter (Removable / Washable / Mould proof) Machine weight kg 42 50
Dimensions (HXWXD) mm 200X1100X620 Certified Operation range °CWB 14 to 25
Machine weight kg 30 Outdoor Colour Ivory white
Certified Operation range °CWB 14 to 25 unit Coil Type Micro channel
Outdoor Colour Ivory white Compressor Type Hermetically sealed swing type
unit Coil Type Micro channel Motor output kW 1.60 2.40
Compressor Type Hermetically sealed swing type Refrigerant charge (R32) kg 1.3 (Charged for 30 m) 1.9 (Charged for 30 m)
Motor output kW 1.3 Sound Cooling dB(A) 48 49 52 54
pressure level 3
Refrigerant charge (R32) kg 1.2 (Charged for 30 m) Night quiet mode dB(A) 44 45
Sound Cooling dB(A) 48 Dimensions (HXWXD) mm 695X930X350 990X940X320
pressure level 3
Night quiet mode dB(A) 44 Machine weight kg 48 64
Dimensions (HXWXD) mm 595X845X300 Certified Operation range °CDB 21 to 46
Machine weight kg 41 Piping Liquid (Flare) mm 9.5
Certified Operation range °CDB 21 to 46 connections Gas (Flare) mm 15.9
Piping Liquid (Flare) mm 9.5 Drain Indoor unit mm VP20 (I.D. 20XO.D. 26)
connections Gas (Flare) mm 15.9 Outdoor unit mm 18.0 (Hole) 26.0 (Hole)
Drain Indoor unit mm VP20 (I.D. 20XO.D. 26) Max. interunit piping length m 50 (Equivalent length 70)
Outdoor unit mm 26.0 (Hole) Max. installation level difference m 30
Max. interunit piping length m 50 (Equivalent length 70) Heat insulation Both liquid and gas piping
Max. installation level difference m 30 Note :
Heat insulation Both liquid and gas piping
1
Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal).
2
Capacities are net, including a deduction for cooling for indoor fan motor heat.
Note : 3
The operation sound is measured in anechoic chamber. If it is measured under the actual installation conditions, it is normally over the set value due to environmental noise and sound reflection.
1
Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal).
2
Capacities are net, including a deduction for cooling for indoor fan motor heat.
3
The operation sound is measured in anechoic chamber. If it is measured under the actual installation conditions, it is normally over the set value due to environmental noise and sound reflection.

61 62
SPECIFICATIONS RZF series SPECIFICATIONS RZA series

CEILING MOUNTED CASSETTE TYPE <Round Flow> (1 Phase) Heat Pump


CEILING SUSPENDED TYPE (1 Phase) Cooling only
50 60 71 100 125 140
50 60 71 100 125 140 Model Indoor unit FCF50CVM FCF60CVM FCF71CVM FCF100CVM FCF125CVM FCF140CVM
Indoor unit FHA50BVMV FHA60BVMV FHA71BVMV FHA100BVMV FHA125BVMA FHA140BVMA Name Outdoor unit RZA50DV2V RZA60DV2V RZA71DV1 RZA100DV1 RZA125DV1 RZA140DV1
Model
Name Power supply Outdoor unit 1 Phase, 220V, 50Hz 1 Phase, 220-240V, 50Hz
Outdoor unit RZF50CV2V RZF60CV2V RZF71CV2V RZF100CVM RZF125CVM RZF140CVM
Cooling capacity 1,3 kW 5.0 (1.4-6.0) 6.0 (1.4-7.1) 7.1 (3.2-8.0) 10.0 (3.2-11.2) 12.5 (5.0-14.0) 14.0 (5.0-16.0)
Power supply Outdoor unit 1 Phase, 220V, 50Hz 1 Phase, 220-240 / 220-230V, 50 / 60Hz Rated (Min. - Max.) Btu/h 17,100 (4,800-20,500) 20,500 (4,800-24,200) 24,200 (10,900-27,300) 34,100 (10,900-38,200) 42,700 (17,100-47,800) 47,800 (17,100-54,600)
Cooling Capacity 1,2 5.0 6.0 7.1 10.0 12.5 14.0 Heating capacity 2,3 kW 6.0 (1.4-7.1) 7.1 (1.4-8.0) 8.0 (3.5-9.0) 11.2 (3.5-12.5) 14.0 (5.1-16.0) 16.0 (5.1-18.0)
Rated (Min. - Max.) kW (2.3-5.6) (2.6-6.3) (3.2-8.0) (5.0-11.2) (5.7-14.0) (6.2-15.5) Rated (Min. - Max.) Btu/h 20,500 (4,800-24,200) 23,200 (4,800-27,300) 27,300 (12,000-30,700) 38,200 (11,900-42,700) 47,800 (17,400-54,600) 54,600 (17,400-61,400)
17,100 20,500 24,200 34,100 42,700 47,800 Power consumption Cooling 1 1.11 1.49 1.90 3.06 3.52 4.21
Btu/h (7,800-19,100) (8,900-21,500) (10,900-27,300) (17,100-38,200) (19,500-47,800) (21,200-52,900) kW
Heating 2 1.27 1.54 2.05 2.90 3.81 4.75
Power consumption Cooling 1 kW 1.20 1.53 2.30 3.24 4.29 5.40 COP Cooling 4.50 4.03 3.73 3.27 3.55 3.32
COP kW/kW 4.17 3.92 3.09 3.09 2.91 2.59 kW/kW
Heating 4.73 4.61 3.90 3.86 3.68 3.37
CSPF kWh/kWh 6.30 6.11 5.91 5.17 5.09 4.78 CSPF Cooling kWh/kWh 7.22 6.85 6.13 5.54 5.76 5.20
Indoor unit Colour White Indoor unit Colour Unit ----------
Airflow rate m3/min 15.0 / 13.5 / 12.0 / 11.0 / 10.0 20.5 / 18.8 / 17.0 / 15.5 / 14.0 28.0 / 26.0 / 24.0 / 22.0 / 20.0 31.0 / 29.0 / 27.0 / 25.0 / 23.0 34.0 / 31.5 / 29.0 / 26.5 / 24.0 Decoration panel Fresh white
(H / HM / M / ML / L) cfm 530 / 477 / 424 / 388 / 353 724 / 664 / 600 / 547 / 494 988 / 918 / 847 / 777 / 706 1,094 / 1,024 / 953 / 883 / 812 1,200 / 1,112 / 1,024 / 935 / 847 Airflow rate m3/min 23.0 / 21.0 / 18.5 / 16.0 / 13.5 34.5 / 31.0 / 27.5 / 24.0 / 20.0 36.5 / 33.0 / 29.0 / 25.0 / 21.0
Sound pressure level 3 (H / HM / M / ML / L) dB(A) 37.0 / 36.0 / 35.0 / 33.5 / 32.0 38.0 / 37.0 / 36.0 / 35.0 / 34.0 42.0 / 40.0 / 38.0 / 36.0 / 34.0 44.0 / 42.5 / 41.0 / 39.0 / 37.0 46.0 / 44.0 / 42.0 / 40.0 / 38.0 (H / HM / M / ML / L) cfm 812 / 741 / 653 / 565 / 477 1,218 / 1,094 / 971 / 847 / 706 1,288 / 1,165 / 1,024 / 883 / 741
Dimensions (HXWXD) mm 235X960X690 235X1270X690 235X1590X690 Sound pressure level 4 (H / HM / M / ML / L) dB(A) 37.0 / 34.5 / 32.0 / 29.5 / 27.5 45.0 / 41.5 / 38.0 / 35.0 / 32.5 46.0 / 43.0 / 40.0 / 36.0 / 32.5
Machine weight kg 25 32 38 Dimensions Unit mm 256X840X840 298X840X840
Certified Operation range °CWB 14 to 25 (HXWXD) Decoration panel mm 50X950X950
Outdoor Colour Ivory white Machine Unit kg 22 24
unit Coil Type Micro channel weight Decoration panel kg 5.5
Compressor Type Hermetically sealed swing type Certified Cooling °CWB 14 to 25
Motor output kW 1.3 1.6 2.4 Operation range Heating °CDB 15 to 27
Refrigerant charge (R32) kg 1.2 (Charged for 30 m) 1.3 (Charged for 30 m) 1.9 (Charged for 30 m) Outdoor Colour Ivory white
Sound Cooling dB(A) 48 49 52 54 unit Coil Type Cross fin coil
pressure level 3
Night quiet mode dB(A) 44 45 Compressor Type Hermetically sealed swing type
Dimensions (HXWXD) mm 595X845X300 695X930X350 990X940X320 Motor output kW 1.3 2.4 3.3
Machine weight kg 41 48 64 Refrigerant charge (R32) kg 1.7 (Charged for 30 m) 2.6 (Charged for 30 m) 3.75 (Charged for 30 m)
Certified Operation range °CDB 21 to 46 Sound Cooling / Heating dB(A) 47 / 49 48 / 50 49 / 53 49 / 51 53 / 56
Piping Liquid (Flare) mm 9.5 pressure level 4 Night quiet mode dB(A) 43 44 45 49
connections Gas (Flare) mm 15.9 Dimensions (HXWXD) mm 595X845X300 990X940X320 1,430X940X320
Drain Indoor unit mm VP20 (I.D. 20XO.D. 26) Machine weight kg 45 69 93
Outdoor unit mm 26.0 (Hole) 18.0 (Hole) 26.0 (Hole) Certified Cooling °CDB -5 to 46
Max. interunit piping length m 50 (Equivalent length 70) Operation range Heating °CWB -15 to 15.5
Max. installation level difference m 30 Piping Liquid (Flare) mm 9.5
Heat insulation Both liquid and gas piping connections Gas (Flare) mm 15.9
Drain Indoor unit mm VP25 (I.D. 25XO.D. 32)
Outdoor unit mm 26.0 (Hole)
Max. interunit piping length m 50 (Equivalent length 70) 75 (Equivalent length 90)
Max. installation level difference m 30
Heat insulation Both liquid and gas piping

CEILING SUSPENDED TYPE (3 Phase) Cooling only CEILING MOUNTED CASSETTE TYPE <Round Flow> (3 Phase) Heat Pump
71 100 125 140 100 125 140
Indoor unit FHA71BVMV FHA100BVMV FHA125BVMA FHA140BVMA Model Indoor unit FCF100CVM FCF125CVM FCF140CVM
Model Name Outdoor unit RZA100DY1 RZA125DY1 RZA140DY1
Name Outdoor unit RZF71CYM RZF100CYM RZF125CYM RZF140CYM Power supply Outdoor unit 3 Phase, 380-4150V, 50Hz
Power supply Outdoor unit 3 Phase, 380-415 / 380V, 50 / 60Hz Cooling capacity 1,3 kW 10.0 (5.0-11.2) 12.5 (5.0-14.0) 14.0 (5.0-16.0)
7.1 10.0 12.5 14.0 Rated (Min. - Max.) Btu/h 34,100 (17,100-38,200) 42,700 (17,100-47,800) 47,800 (17,100-54,600)
Cooling Capacity 1,2
Rated (Min. - Max.) kW (3.2-8.0) (5.0-11.2) (5.7-14.0) (6.2-15.5) Heating capacity 2,3 kW 11.2 (5.1-12.5) 14.0 (5.1-16.0) 16.0 (5.1-18.0)
Rated (Min. - Max.) Btu/h 38,200 (17,400-42,700) 47,800 (17,400-54,600) 54,600 (17,400-61,400)
24,200 34,100 42,700 47,800
Btu/h (10,900-27,300) (17,100-38,200) (19,500-47,800) (21,200-52,900) Power consumption Cooling 1 2.78 3.52 4.21
kW
Heating 2 2.71 3.81 4.75
Power consumption Cooling 1
kW 2.30 3.24 4.29 5.40
COP Cooling 3.60 3.55 3.32
COP kW/kW 3.09 3.09 2.91 2.59 kW/kW
Heating 4.14 3.68 3.37
CSPF kWh/kWh 5.91 5.17 5.09 4.78 CSPF Cooling kWh/kWh 5.91 5.76 5.20
Indoor unit Colour White Colour Unit ----------
Indoor unit
Airflow rate m3/min 20.5 / 18.8 / 17.0 / 15.5 / 14.0 28.0 / 26.0 / 24.0 / 22.0 / 20.0 31.0 / 29.0 / 27.0 / 25.0 / 23.0 34.0 / 31.5 / 29.0 / 26.5 / 24.0 Decoration panel Fresh white
(H / HM / M / ML / L) cfm 724 / 664 / 600 / 547 / 494 988 / 918 / 847 / 777 / 706 1,094 / 1,024 / 953 / 883 / 812 1,200 / 1,112 / 1,024 / 935 / 847 Airflow rate m3/min 34.5 / 31.0 / 27.5 / 24.0 / 20.0 36.5 / 33.0 / 29.0 / 25.0 / 21.0
Sound pressure level 3 (H / HM / M / ML / L) dB(A) 38.0 / 37.0 / 36.0 / 35.0 / 34.0 42.0 / 40.0 / 38.0 / 36.0 / 34.0 44.0 / 42.5 / 41.0 / 39.0 / 37.0 46.0 / 44.0 / 42.0 / 40.0 / 38.0 (H / HM / M / ML / L) cfm 1,218 / 1,094 / 971 / 847 / 706 1,288 / 1,165 / 1,024 / 883 / 741
Dimensions (HXWXD) mm 235X1270X690 235X1590X690 Sound pressure level 4 (H / HM / M / ML / L) dB(A) 45.0 / 41.5 / 38.0 / 35.0 / 32.5 46.0 / 43.0 / 40.0 / 36.0 / 32.5
Machine weight kg 32 38 Dimensions Unit mm 298X840X840
Certified Operation range °CWB 14 to 25 (HXWXD) Decoration panel mm 50 950 950
X X

Ivory white Machine Unit kg 24


Outdoor Colour weight
unit Coil Type Micro channel Decoration panel kg 5.5
Certified Cooling °CWB 14 to 25
Compressor Type Hermetically sealed swing type
Operation range Heating °CDB 15 to 27
Motor output kW 1.6 2.4
Outdoor Colour Ivory white
Refrigerant charge (R32) kg 1.3 (Charged for 30 m) 1.9 (Charged for 30 m)
unit Coil Type Cross fin coil
Sound Cooling dB(A) 48 49 52 54
pressure level 3 Compressor Type Hermetically sealed swing type
Night quiet mode dB(A) 44 45 3.3
Motor output kW
Dimensions (HXWXD) mm 695X930X350 990X940X320 Refrigerant charge (R32) kg 3.75 (Charged for 30 m)
Machine weight kg 48 64 Sound Cooling / Heating dB(A) 48 / 50 49 / 51 53 / 56
Certified Operation range °CDB 21 to 46 pressure level 4 Night quiet mode dB(A) 44 45 49
Piping Liquid (Flare) mm 9.5 Dimensions (HXWXD) mm 1,430X940X320
connections Gas (Flare) mm 15.9 Machine weight kg 93
Drain Indoor unit mm VP20 (I.D. 20XO.D. 26) Certified Cooling °CDB -5 to 46
Outdoor unit mm 18.0 (Hole) 26.0 (Hole) Operation range Heating °CWB -15 to 15.5
Max. interunit piping length m 50 (Equivalent length 70) Piping Liquid (Flare) mm 9.5
Max. installation level difference m 30 connections Gas (Flare) mm 15.9
Both liquid and gas piping Drain Indoor unit mm VP25 (I.D. 25XO.D. 32)
Heat insulation
Outdoor unit mm 26.0 (Hole)
Note :
1
Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal). Max. interunit piping length m 75 (Equivalent length 90)
2
Capacities are net, including a deduction for cooling for indoor fan motor heat. Max. installation level difference m 30
3
The operation sound is measured in anechoic chamber. If it is measured under the actual installation conditions, it is normally over the set value due to environmental noise and sound reflection. Heat insulation Both liquid and gas piping
Note :
1
Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal).
2
Rated heating capacities are based on the following conditions: Indoor temp., 20°CDB, 15°CWB; outdoor temp., 7°CDB, 6°CWB. Equiv. refrigeration piping, 7.5 m (horizontal).
3
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
4
The operation sound is measured in anechoic chamber. If it is measured under the actual installation conditions, it is normally over the set value due to environmental noise and sound reflection.

63 64
SPECIFICATIONS RZA series

DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE (1 Phase) Heat Pump FLOOR STANDING TYPE (1 Phase) Heat Pump
50 60 71 100 125 140 50 60 71 100 125 140
Model Indoor unit FBA50BVMA(9) FBA60BVMA(9) FBA71BVMA(9) FBA100BVMA(9) FBA125BVMA(9) FBA140BVMA(9) Model Indoor unit FVA50AMVM FVA60AMVM FVA71AMVM FVA100AMVM FVA125AMVM FVA140AMVM
Name Outdoor unit RZA50DV2V RZA60DV2V RZA71DV1 RZA100DV1 RZA125DV1 RZA140DV1 Name Outdoor unit RZA50DV2V RZA60DV2V RZA71DV1 RZA100DV1 RZA125DV1 RZA140DV1
Power supply Indoor unit 1 Phase, 220-240V / 220-230V, 50 / 60Hz Power supply Outdoor unit 1 Phase, 220V, 50Hz 1 Phase, 220-240V, 50Hz
Outdoor unit 1 Phase, 220V, 50Hz 1 Phase, 220-240V, 50Hz Cooling Capacity 1,3 kW 5.0 (1.4-6.0) 6.0 (1.4-7.1) 7.1 (3.2-8.0) 10.0 (3.2-11.2) 12.5 (5.0-14.0) 14.0 (5.0-16.0)
Cooling Capacity 1,3 kW 5.0 (1.4-6.0) 6.0 (1.4-7.1) 7.1 (3.2-8.0) 10.0 (3.2-11.2) 12.5 (5.0-14.0) 14.0 (5.0-16.0) Rated (Min. - Max.) Btu/h 17,100 (4,800-20,500) 20,500 (4,800-24,200) 24,200 (10,900-27,300) 34,100 (10,900-38,200) 42,700 (17,100-47,800) 47,800 (17,100-54,600)
Rated (Min. - Max.) Btu/h 17,100 (4,800-20,500) 20,500 (4,800-24,200) 24,200 (10,900-27,300) 34,100 (10,900-38,200) 42,700 (17,100-47,800) 47,800 (17,100-54,600) Heating capacity 2,3 kW 6.0 (1.4-7.1) 7.1 (1.4-8.0) 8.0 (3.5-9.0) 11.2 (3.5-12.5) 14.0 (5.1-16.0) 16.0 (5.1-18.0)
Heating capacity 2,3 kW 6.0 (1.4-7.1) 7.1 (1.4-8.0) 8.0 (3.5-9.0) 11.2 (3.5-12.5) 14.0 (5.1-16.0) 16.0 (5.1-18.0) Rated (Min. - Max.) Btu/h 20,500 (4,800-24,200) 23,200 (4,800-27,300) 27,300 (12,000-30,700) 38,200 (11,900-42,700) 47,800 (17,400-54,600) 54,600 (17,400-61,400)
Rated (Min. - Max.) Btu/h 20,500 (4,800-24,200) 23,200 (4,800-27,300) 27,300 (12,000-30,700) 38,200 (11,900-42,700) 47,800 (17,400-54,600) 54,600 (17,400-61,400) Power consumption Cooling 1 1.24 1.65 2.18 3.29 3.85 4.50
kW
Power consumption Cooling 1 1.23 1.64 2.00 3.17 3.74 4.27 Heating 2 1.50 1.96 2.49 3.36 4.22 5.26
kW
Heating 2 1.31 1.81 2.09 2.90 3.73 4.56 COP Cooling 4.04 3.63 3.25 3.04 3.25 3.11
kW/kW
COP Cooling 4.06 3.66 3.56 3.15 3.34 3.28 Heating 3.99 3.62 3.21 3.33 3.31 3.04
kW/kW
Heating 4.58 3.92 3.82 3.86 3.75 3.51 CSPF Cooling kWh/kWh 6.04 5.41 5.32 5.27 5.43 5.02
CSPF Cooling kWh/kWh 6.28 5.92 5.71 5.33 5.30 4.93 Indoor unit Colour Fresh white
Indoor unit Colour ---------- Airflow rate (H / M / L) m3/min 18 / 16 / 14 28 / 25 / 22 28 / 26 / 24 30 / 28 / 26
Fan Airflow rate (H / M / L) m3/min 18.0 / 15.0 / 12.5 23.0 / 19.5 / 16.0 32.0 / 27.0 / 22.5 36.0 / 30.5 / 25.0 cfm 635 / 565 / 494 988 / 883 / 777 988 / 918 / 847 1,059 / 988 / 918
cfm 635 / 530 / 441 812 / 688 / 565 1,130 / 953 / 794 1,271 / 1,077 / 883 Sound pressure level 4 (H / M / L) dB(A) 43 / 41 / 38 50 / 47 / 44 51 / 48 / 46 53 / 51 / 48
External static pressure 4 Pa Rated 50 (50-150) Dimensions (HXWXD) mm 1,850X600X270 1,850X600X350
Sound pressure level 5 (H/M/L) dB(A) 35.0 / 33.0 / 31.0 38.0 / 35.0 / 33.0 38.0 / 35.5 / 33.0 40.0 / 37.5 / 35.0 Machine weight kg 42 50
Air filter 6 ---------- Certified Cooling °CWB 14 to 25
Dimensions (HXWXD) mm 245X1000X800 245X1400X800 Operation range Heating °CDB 15 to 27
Machine weight kg 37 47 Outdoor Colour Ivory white
Certified Cooling °CWB 14 to 25 unit Coil Type Cross fin coil
Operation range Heating °CDB 15 to 27 Compressor Type Hermetically sealed swing type
Outdoor Colour Ivory white Motor output kW 1.3 2.4 3.3
unit Coil Type Cross fin coil Refrigerant charge (R32) kg 1.7 (Charged for 30 m) 2.6 (Charged for 30 m) 3.75 (Charged for 30 m)
Compressor Type Hermetically sealed swing type Sound Cooling / Heating dB(A) 47 / 49 48 / 50 49 / 53 49 / 51 53 / 56
pressure level 4
Motor output kW 1.3 2.4 3.3 Night quiet mode dB(A) 43 44 45 49
Refrigerant charge (R32) kg 1.7 (Charged for 30 m) 2.6 (Charged for 30 m) 3.75 (Charged for 30 m) Dimensions (HXWXD) mm 595X845X300 990X940X320 1,430X940X320
Sound Cooling / Heating dB(A) 47 / 49 48 / 50 49 / 53 49 / 51 53 / 56 Machine weight kg 45 69 93
pressure level 5
Night quiet mode dB(A) 43 44 45 49 Certified Cooling °CDB -5 to 46
Dimensions (HXWXD) mm 595X845X300 990X940X320 1,430X940X320 Operation range Heating °CWB -15 to 15.5
Machine weight kg 45 69 93 Piping Liquid (Flare) mm 9.5
Cooling °CDB -5 to 46 connections Gas (Flare) mm 15.9
Certified
Operation range Heating °CWB -15 to 15.5 Drain Indoor unit mm VP20 (I.D. 20XO.D. 26)
Piping Liquid (Flare) mm 9.5 Outdoor unit mm 26.0 (Hole)
connections Gas (Flare) mm 15.9 Max. interunit piping length m 50 (Equivalent length 70) 75 (Equivalent length 90)
Drain Indoor unit mm VP25 (I.D. 25XO.D. 32) Max. installation level difference m 30
Outdoor unit mm 26.0 (Hole) Heat insulation Both liquid and gas piping
Max. interunit piping length m 50 (Equivalent length 70) 75 (Equivalent length 90)
Max. installation level difference m 30
Heat insulation Both liquid and gas piping

DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE (3 Phase) Heat Pump FLOOR STANDING TYPE (3 Phase) Heat Pump
100 125 140 100 125 140
Model Indoor unit FBA100BVMA(9) FBA125BVMA(9) FBA140BVMA(9) Model Indoor unit FVA100AMVM FVA125AMVM FVA140AMVM
Name Outdoor unit RZA100DY1 RZA125DY1 RZA140DY1 Name Outdoor unit RZA100DY1 RZA125DY1 RZA140DY1
Power supply Indoor unit 1 Phase, 220-240V / 220-230V, 50 / 60Hz Power supply Outdoor unit 3 Phase, 380-415V, 50Hz
Outdoor unit 3 Phase, 380-415V, 50Hz
Cooling Capacity 1,3 kW 10.0 (5.0-11.2) 12.5 (5.0-14.0) 14.0 (5.0-16.0)
Cooling Capacity 1,3 kW 10.0 (5.0-11.2) 12.5 (5.0-14.0) 14.0 (5.0-16.0)
Rated (Min. - Max.) Btu/h 34,100 (17,100-38,200) 42,700 (17,100-47,800) 47,800 (17,100-54,600)
Rated (Min. - Max.) Btu/h 34,100 (17,100-38,200) 42,700 (17,100-47,800) 47,800 (17,100-54,600)
Heating capacity 2,3 kW 11.2 (5.1-12.5) 14.0 (5.1-16.0) 16.0 (5.1-18.0) Heating capacity 2,3 kW 11.2 (5.1-12.5) 14.0 (5.1-16.0) 16.0 (5.1-18.0)
Rated (Min. - Max.) Rated (Min. - Max.) Btu/h 38,200 (17,400-42,700) 47,800 (17,400-54,600) 54,600 (17,400-61,400)
Btu/h 38,200 (17,400-42,700) 47,800 (17,400-54,600) 54,600 (17,400-61,400)
Power consumption Cooling 1 2.78 3.74 4.27 Power consumption Cooling 1
3.00 3.85 4.50
kW kW
Heating 2 2.69 3.73 4.56 Heating 2 3.16 4.22 5.26
COP Cooling 3.60 3.34 3.28 COP Cooling 3.33 3.25 3.11
kW/kW kW/kW
Heating 4.16 3.75 3.51 Heating 3.55 3.31 3.04
CSPF Cooling kWh/kWh 5.75 5.30 4.93 CSPF Cooling kWh/kWh 5.60 5.43 5.02
Indoor unit Colour ---------- Colour
Indoor unit Fresh white
Fan Airflow rate (H / M / L) m3/min 32.0 / 27.0 / 22.5 36.0 / 30.5 / 25.0
Airflow rate (H / M / L) m3/min 28 / 25 / 22 28 / 26 / 24 30 / 28 / 26
cfm 1,130 / 953 / 794 1,271 / 1,077 / 883
External static pressure 4 Pa Rated 50 (50-150) cfm 988 / 883 / 777 988 / 918 / 847 1,059 / 988 / 918
Sound pressure level 5 (H/M/L) dB(A) 38.0 / 35.5 / 33.0 40.0 / 37.5 / 35.0 Sound pressure level 4 (H / M / L) dB(A) 50 / 47 / 44 51 / 48 / 46 53 / 51 / 48
Air filter 6 ---------- Dimensions (HXWXD) mm 1,850X600X350
Dimensions (HXWXD) mm 245X1400X800 Machine weight kg 50
Machine weight kg 47 Certified Cooling °CWB 14 to 25
Certified Cooling °CWB 14 to 25 Operation range Heating °CDB 15 to 27
Operation range Heating °CDB 15 to 27 Outdoor Colour Ivory white
Outdoor Colour Ivory white unit Coil Type Cross fin coil
unit Coil Type Cross fin coil
Compressor Type Hermetically sealed swing type
Compressor Type Hermetically sealed swing type
Motor output kW Motor output kW 3.3
3.3
Refrigerant charge (R32) kg 3.75 (Charged for 30 m) Refrigerant charge (R32) kg 3.75 (Charged for 30 m)
Sound Cooling / Heating dB(A) 48 / 50 49 / 51 53 / 56 Sound Cooling / Heating dB(A) 48 / 50 49 / 51 53 / 56
pressure level Night quiet mode
5 pressure level 4
dB(A) 44 45 49 Night quiet mode dB(A) 44 45 49
Dimensions (HXWXD) mm 1,430X940X320 Dimensions (HXWXD) mm 1,430X940X320
Machine weight kg 93 Machine weight kg 93
Certified Cooling °CDB -5 to 46 Cooling °CDB -5 to 46
Certified
Operation range Heating °CWB -15 to 15.5 Operation range Heating °CWB -15 to 15.5
Piping Liquid (Flare) mm 9.5
connections Gas (Flare) Piping Liquid (Flare) mm 9.5
mm 15.9 connections Gas (Flare) mm 15.9
Drain Indoor unit mm VP25 (I.D. 25XO.D. 32)
Outdoor unit mm 26.0 (Hole) Drain Indoor unit mm VP20 (I.D. 20XO.D. 26)
Max. interunit piping length m 75 (Equivalent length 90) Outdoor unit mm 26.0 (Hole)
Max. installation level difference m 30 Max. interunit piping length m 75 (Equivalent length 90)
Heat insulation Both liquid and gas piping Max. installation level difference m 30
Note : Heat insulation Both liquid and gas piping
1
Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal).
2
Rated heating capacities are based on the following conditions: Indoor temp., 20°CDB, 15°CWB; outdoor temp., 7°CDB, 6°CWB. Equiv. refrigeration piping, 7.5 m (horizontal). Note :
3
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. 1
Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal).
4
External static pressure is changeable in 11 stages by remote controller. 2
Rated heating capacities are based on the following conditions: Indoor temp., 20°CDB, 15°CWB; outdoor temp., 7°CDB, 6°CWB. Equiv. refrigeration piping, 7.5 m (horizontal).
5
The operation sound is measured in anechoic chamber. If it is measured under the actual installation conditions, it is normally over the set value due to environmental noise and sound reflection. 3
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
6
Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its dust collection efficiency (gravity method) 50% or more. 4
The operation sound is measured in anechoic chamber. If it is measured under the actual installation conditions, it is normally over the set value due to environmental noise and sound reflection.

65 66
SPECIFICATIONS RZA series SPECIFICATIONS RZFC series

CEILING SUSPENDED TYPE (1 Phase) Heat Pump CEILING MOUNTED CASSETTE TYPE <Round Flow> (1 Phase) Cooling only
50 60 71 100 125 140 40 50 60 71 85 100
Model Indoor unit FHA50BVMV FHA60BVMV FHA71BVMV FHA100BVMV FHA125BVMA FHA140BVMA Indoor unit FCFC40DVM FCFC50DVM FCFC60DVM FCFC71DVM FCFC85DVM FCFC100DVM
Name Outdoor unit RZA50DV2V RZA60DV2V RZA71DV1 RZA100DV1 RZA125DV1 RZA140DV1 Model
Name Outdoor unit
Power supply Outdoor unit 1 Phase, 220V, 50Hz 1 Phase, 220-240V, 50Hz RZFC40DVM RZFC50DVM RZFC60DVM RZFC71DVM RZFC85DVM RZFC100DVM
Cooling Capacity 1,3 kW 5.0 (1.4-6.0) 6.0 (1.4-7.1) 7.1 (3.2-8.0) 10.0 (3.2-11.2) 12.5 (5.0-14.0) 14.0 (5.0-16.0) Power supply Outdoor unit 1 Phase, 220–240 / 220-230V, 50 / 60Hz
Rated (Min. - Max.) Btu/h 17,100 (4,800-20,500) 20,500 (4,800-24,200) 24,200 (10,900-27,300) 34,100 (10,900-38,200) 42,700 (17,100-47,800) 47,800 (17,100-54,600) Cooling Capacity 1,2 4.0 5.0 6.0 7.1 8.5 10.0
Rated (Min. - Max.) kW (1.8-4.5) (2.3-5.6) (2.6-6.3) (3.2-8.0) (4.2-10.0) (5.0-11.2)
Heating capacity 2,3 kW 6.0 (1.4-7.1) 7.1 (1.4-8.0) 8.0 (3.5-9.0) 11.2 (3.5-12.5) 14.0 (5.1-16.0) 16.0 (5.1-18.0)
Rated (Min. - Max.) Btu/h 20,500 (4,800-24,200) 23,200 (4,800-27,300) 27,300 (12,000-30,700) 38,200 (11,900-42,700) 47,800 (17,400-54,600) 54,600 (17,400-61,400) 13,600 17,100 20,500 24,200 29,000 34,100
Btu/h (6,100-15,400) (7,800-19,100) (8,900-21,500) (10,900-27,300) (14,300-34,100) (17,100-38,200)
Power consumption Cooling 1 1.30 1.66 2.09 3.22 3.62 4.48
kW
Heating 2 1.52 2.07 2.42 3.00 4.05 4.75 Power consumption Cooling 1 kW 1.26 1.57 1.89 2.38 2.85 3.35
COP Cooling 3.85 3.61 3.40 3.11 3.45 3.13 COP kW/kW 3.18 2.98
kW/kW
Heating 3.95 3.43 3.30 3.73 3.46 3.37 CSPF kWh/kWh 5.13 4.90 4.67
CSPF Cooling kWh/kWh 6.12 5.65 5.61 5.37 5.62 5.02 Indoor unit Colour Unit White
Indoor unit Colour White Decoration panel Fresh white
Airflow rate 3
m /min 15.0 / 13.5 / 12.0 / 11.0 / 10.0 20.5 / 18.8 / 17.0 / 15.5 / 14.0 28.0 / 26.0 / 24.0 / 22.0 / 20.0 31.0 / 29.0 / 27.0 / 25.0 / 23.0 34.0 / 31.5 / 29.0 / 26.5 / 24.0 Airflow rate m /min3
19 / 14 / 11 23 / 18 / 13 34 / 27 / 20
(H / HM / M / ML / L) cfm 530 / 477 / 424 / 388 / 353 724 / 664 / 600 / 547 / 494 988 / 918 / 847 / 777 / 706 1,094 / 1,024 / 953 / 883 / 812 1,200 / 1,112 / 1,024 / 935 / 847 (H / M / L) cfm 671 / 494 / 388 812 / 635 / 459 1,200 / 953 / 706
Sound pressure level 4 (H / HM / M / ML / L) dB(A) 37.0 / 36.0 / 35.0 / 33.5 / 32.0 38.0 / 37.0 / 36.0 / 35.0 / 34.0 42.0 / 40.0 / 38.0 / 36.0 / 34.0 44.0 / 42.5 / 41.0 / 39.0 / 37.0 46.0 / 44.0 / 42.0 / 40.0 / 38.0 Sound pressure level 3 (H / M / L) dB(A) 37 / 32 / 28 37 / 34 / 28 38 / 34 / 29 45 / 38 / 33
Dimensions (HXWXD) mm 235X960X690 235X1270X690 235X1590X690 Dimensions Unit mm 256X840X840 298X840X840
Machine weight kg 25 32 38 (HXWXD) Decoration panel mm 50X950X950
Certified Cooling °CWB 14 to 25 Machine Unit kg 19 22 24
Operation range Heating °CDB 15 to 27 weight Decoration panel kg 5.5
Outdoor Colour Ivory white Certified Operation range °CWB 14 to 25
unit Coil Type Cross fin coil Outdoor Colour Ivory white
Compressor Type Hermetically sealed swing type unit Coil Type Micro channel
Motor output kW 1.3 2.4 3.3 Compressor Type Hermetically sealed swing type
Refrigerant charge (R32) kg 1.7 (Charged for 30 m) 2.6 (Charged for 30 m) 3.75 (Charged for 30 m) Motor output kW 1.20 1.30 1.60
Sound Cooling / Heating dB(A) 47 / 49 48 / 50 49 / 53 49 / 51 53 / 56 Refrigerant charge (R32) kg 0.7 (Charged for 10 m) 0.8 (Charged for 10 m) 1.0 (Charged for 15 m)
pressure level 4
Night quiet mode dB(A) 43 44 45 49 Sound pressure level 3 Cooling dB(A) 48 49 50 51 52
Dimensions (HXWXD) mm 595X845X300 990X940X320 1,430X940X320 Dimensions (HXWXD) mm 595X845X300 695X930X350
Machine weight kg 45 69 93 Machine weight kg 34 37 44
Certified Cooling °CDB -5 to 46 Certified Operation range °CDB 21 to 46
Operation range Heating °CWB -15 to 15.5 Piping Liquid (Flare) mm 6.4 9.5
Piping Liquid (Flare) mm 9.5 connections Gas (Flare) mm 12.7 15.9
connections Gas (Flare) mm 15.9 Drain Indoor unit mm VP20 (I.D. 20XO.D. 26)
Drain Indoor unit mm VP20 (I.D. 20XO.D. 26) Outdoor unit mm 18.0 (Hole)
Outdoor unit mm 26.0 (Hole) Max. interunit piping length m 30 (Equivalent length 40) 50 (Equivalent length 70)
Max. interunit piping length m 50 (Equivalent length 70) 75 (Equivalent length 90) Max. installation level difference m 15 30
Max. installation level difference m 30 Heat insulation Both liquid and gas piping
Heat insulation Both liquid and gas piping

CEILING SUSPENDED TYPE (3 Phase) Heat Pump CEILING MOUNTED CASSETTE TYPE <Round Flow> (3 Phase) Cooling only
100 125 140 71 85 100 125 140
Model Indoor unit FHA100BVMV FHA125BVMA FHA140BVMA Indoor unit FCFC71DVM FCFC85DVM FCFC100DVM FCFC125DVM FCFC140DVM
Name Outdoor unit RZA100DY1 RZA125DY1 RZA140DY1 Model
Name Outdoor unit
Power supply Outdoor unit 3 Phase, 380-415V, 50Hz RZFC71DY1 RZFC85DY1 RZFC100DY1 RZFC125DY1 RZFC140DY1
Cooling Capacity 1,3 kW 10.0 (5.0-11.2) 12.5 (5.0-14.0) 14.0 (5.0-16.0) Power supply Outdoor unit 3 Phase, 380-415V, 50Hz
Rated (Min. - Max.) Btu/h 34,100 (17,100-38,200) 42,700 (17,100-47,800) 47,800 (17,100-54,600) Cooling Capacity 1,2 7.1 8.5 10.0 12.5 14.0
Rated (Min. - Max.) kW (3.2-8.0) (4.2-10.0) (5.0-11.2) (5.7-14.0) (6.2-15.5)
Heating capacity 2,3 kW 11.2 (5.1-12.5) 14.0 (5.1-16.0) 16.0 (5.1-18.0)
Rated (Min. - Max.) Btu/h 38,200 (17,400-42,700) 47,800 (17,400-54,600) 54,600 (17,400-61,400) 24,200 29,000 34,100 42,700 47,800
Btu/h (10,900-27,300) (14,300-34,100) (17,100-38,200) (19,500-47,800) (21,200-52,900 )
Power consumption Cooling 1 2.78 3.62 4.48
kW
Heating 2 2.73 4.05 4.75 Power consumption Cooling 1 kW 2.38 2.85 3.35 4.70 5.88
COP Cooling 3.59 3.45 3.13 COP kW/kW 2.98 2.66 2.38
kW/kW
Heating 4.11 3.46 3.37 CSPF kWh/kWh 4.67 4.29 4.10
CSPF Cooling kWh/kWh 5.86 5.62 5.02 Indoor unit Colour Unit White
Indoor unit Colour White Decoration panel Fresh white
Airflow rate m3/min 28.0 / 26.0 / 24.0 / 22.0 / 20.0 31.0 / 29.0 / 27.0 / 25.0 / 23.0 34.0 / 31.5 / 29.0 / 26.5 / 24.0 Airflow rate m3/min 23 / 18 / 13 34 / 27 / 20 36 / 29 / 21
(H / HM / M / ML / L) cfm 988 / 918 / 847 / 777 / 706 1,094 / 1,024 / 953 / 883 / 812 1,200 / 1,112 / 1,024 / 935 / 847 (H / M / L) cfm 812 / 635 / 459 1,200 / 953 / 706 1,271 / 1,024 / 741
Sound pressure level 4 (H / HM / M / ML / L) dB(A) 42.0 / 40.0 / 38.0 / 36.0 / 34.0 44.0 / 42.5 / 41.0 / 39.0 / 37.0 46.0 / 44.0 / 42.0 / 40.0 / 38.0 Sound pressure level 3 (H / M/ L) dB(A) 37 / 34 / 28 38 / 34 / 29 45 / 38 / 33 46 / 40 / 33
Dimensions (HXWXD) mm 235X1590X690 Dimensions Unit mm 256X840X840 298X840X840
Machine weight kg 38 (HXWXD) Decoration panel mm 50X950X950
Certified Cooling °CWB 14 to 25 Machine Unit kg 22 24
Operation range Heating °CDB 15 to 27 weight Decoration panel kg 5.5
Outdoor Colour Ivory white Certified Operation range °CWB 14 to 25
unit Coil Type Cross fin coil Outdoor Colour Ivory white
Compressor Type Hermetically sealed swing type unit Coil Type Micro channel
Motor output kW 3.3 Compressor Type Hermetically sealed swing type
Refrigerant charge (R32) kg 3.75 (Charged for 30 m) Motor output kW 1.60 2.40
Sound Cooling / Heating dB(A) 48 / 50 49 / 51 53 / 56 Refrigerant charge (R32) kg 1.0 (Charged for 15 m) 1.35 (Charged for 15 m)
pressure level 4
Night quiet mode dB(A) 44 45 49 Sound pressure level 3 Cooling dB(A) 50 51 52 54 56
Dimensions (HXWXD) mm 1,430X940X320 Dimensions (HXWXD) mm 695X930X350 990X940X320
Machine weight kg 93 Machine weight kg 46 62
Certified Cooling °CDB -5 to 46 Certified Operation range °CDB 21 to 46
Operation range Heating °CWB -15 to 15.5 Piping Liquid (Flare) mm 9.5
Piping Liquid (Flare) mm 9.5 connections Gas (Flare) mm 15.9
connections Gas (Flare) mm 15.9 Drain Indoor unit mm VP20 (I.D. 20XO.D. 26)
Drain Indoor unit mm VP20 (I.D. 20XO.D. 26) Outdoor unit mm 18.0 (Hole) 26.0 (Hole)
Outdoor unit mm 26.0 (Hole) Max. interunit piping length m 50 (Equivalent length 70)
Max. interunit piping length m 75 (Equivalent length 90) Max. installation level difference m 30
Max. installation level difference m 30 Heat insulation Both liquid and gas piping
Heat insulation Both liquid and gas piping Note :
Note :
1
Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal).
1
Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal).
2
Capacities are net, including a deduction for cooling for indoor fan motor heat.
2
Rated heating capacities are based on the following conditions: Indoor temp., 20°CDB, 15°CWB; outdoor temp., 7°CDB, 6°CWB. Equiv. refrigeration piping, 7.5 m (horizontal).
3
The operation sound is measured in anechoic chamber. If it is measured under the actual installation conditions, it is normally over the set value due to environmental noise and sound reflection.
3
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
4
The operation sound is measured in anechoic chamber. If it is measured under the actual installation conditions, it is normally over the set value due to environmental noise and sound reflection.

67 68
SPECIFICATIONS RZFC series

DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE (1 Phase) Cooling only DUCT CONNECTION LOW STATIC PRESSURE WIDTH COMPACT TYPE (1 Phase) Cooling only
40 50 60 71 85 100 40 50 60 71 85
Indoor unit FBFC40DVM(9) FBFC50DVM(9) FBFC60DVM(9) FBFC71DVM(9) FBFC85DVM(9) FBFC100DVM(9) Indoor unit FDBF40DV1 FDBF50DV1 FDBF60DV1 FDBF71DV1 FDBF85DV1
Model Model
Name Outdoor unit Name Outdoor unit
RZFC40DVM RZFC50DVM RZFC60DVM RZFC71DVM RZFC85DVM RZFC100DVM RZFC40DVM RZFC50DVM RZFC60DVM RZFC71DVM RZFC85DVM
Power supply Indoor unit ---------- Power supply Indoor unit ----------
Outdoor unit 1 Phase, 220–240 / 220-230V, 50 / 60Hz Outdoor unit 1 Phase, 220-240V, 50Hz
Cooling Capacity 1,2 4.0 5.0 6.0 7.1 8.5 10.0 Cooling Capacity 1,2 4.0 5.0 6.0 7.1 8.5
Rated (Min. - Max.) kW (1.8-4.5) (2.3-5.6) (2.6-6.3) (3.2-8.0) (4.2-10.0) (5.0-11.2) Rated (Min. - Max.) kW (1.8-4.5) (2.3-5.6) (2.6-6.3) (3.2-8.0) (4.2-10.0)
13,600 17,000 20,500 24,200 29,000 34,100 13,600 17,100 20,500 24,200 29,000
Btu/h (6,100-15,400) (7,800-19,100) (8,900-21,500) (10,900-27,300) (14,300-34,100) (17,100-38,200) Btu/h (6,100-15,400) (7,800-19,100) (8,900-21,500) (10,900-27,300) (14,300-34,100)
Power consumption Cooling 1 kW 1.19 1.56 2.07 2.37 2.74 3.17 Power consumption Cooling 1 kW 1.19 1.56 2.07 2.37 2.98
COP kW/kW 3.35 3.20 2.90 3.00 3.10 3.15 COP kW/kW 3.35 3.20 2.90 3.00 2.85
CSPF kWh/kWh 4.38 4.18 3.98 CSPF kWh/kWh 4.38 4.13 3.93
Indoor unit Colour ---------- Indoor unit Colour ----------
Fan Airflow rate (H/M/L) m /min
3
15.5 / 12 / 9 25 / 20 / 16.5 36 / 30.5 / 25 Fan Airflow rate (H/M/L) m /min
3
15 / 12 / 9.5 22.5 / 20 / 17.5
cfm 547 / 424 / 318 883 / 706 / 582 1,271 / 1,077 / 883 cfm 530 / 424 / 335 794 / 706 / 618
External static pressure 3 Pa Rated 30 (30-130) Rated 40 (40-140) Rated 50 (50-150) External static pressure Pa Rated 15 (15-38)
Sound pressure level 4 (H/M/L) dB(A) 37 / 35 / 30 39 / 37 / 34 40 / 37.5 / 35 Sound pressure level 3 (H/M/L) dB(A) 37 / 33 / 25 39 / 35 / 33
Air filter 5 ---------- Air filter 4 ----------
Dimensions (HXWXD) mm 245X700X800 245X1,000X800 245X1,400X800 Dimensions (HXWXD) mm 245X700X800 245X1,000X800
Machine weight kg 26 36 46 Machine weight kg 26 36
Certified Operation range °CWB 14 to 25 Certified Operation range °CWB 14 to 25
Outdoor Colour Ivory white Outdoor Colour Ivory white
unit Coil Type Micro channel unit Coil Type Micro channel
Compressor Type Hermetically sealed swing type Compressor Type Hermetically sealed swing type
Motor output kW 1.20 1.30 1.60 Motor output kW 1.20 1.30 1.60
Refrigerant charge (R32) kg 0.7 (Charged for 10 m) 0.8 (Charged for 10 m) 1.0 (Charged for 15 m) Refrigerant charge (R32) kg 0.7 (Charged for 10 m) 0.8 (Charged for 10 m) 1.0 (Charged for 15 m)
Sound pressure level 4 Cooling dB(A) 48 49 50 51 52 Sound pressure level 3 Cooling dB(A) 48 49 50 51
Dimensions (HXWXD) mm 595X845X300 695X930X350 Dimensions (HXWXD) mm 595X845X300 695X930X350
Machine weight kg 34 37 44 Machine weight kg 34 37 44
Certified Operation range °CDB 21 to 46 Certified Operation range °CDB 21 to 46
Piping Liquid (Flare) mm 6.4 9.5 Piping Liquid (Flare) mm 6.4 9.5
connections Gas (Flare) mm 12.7 15.9 connections Gas (Flare) mm 12.7 15.9
Drain Indoor unit mm VP25 (I.D. 25XO.D. 32) Drain Indoor unit mm VP25 (I.D. 25XO.D. 32)
Outdoor unit mm 18.0 (Hole) Outdoor unit mm 18.0 (Hole)
Max. interunit piping length m 30 (Equivalent length 40) 50 (Equivalent length 70) Max. interunit piping length m 30 (Equivalent length 40) 50 (Equivalent length 70)
Max. installation level difference m 15 30 Max. installation level difference m 15 30
Heat insulation Both liquid and gas piping Heat insulation Both liquid and gas piping

DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE (3 Phase) Cooling only DUCT CONNECTION LOW STATIC PRESSURE WIDTH COMPACT TYPE (3 Phase) Cooling only
71 85 100 125 140 71 85
Indoor unit FBFC71DVM(9) FBFC85DVM(9) FBFC100DVM(9) FBFC125DVM(9) FBFC140DVM(9) Indoor unit FDBF71DV1 FDBF85DV1
Model Model
Name Name Outdoor unit
Outdoor unit RZFC71DY1 RZFC85DY1 RZFC100DY1 RZFC125DY1 RZFC140DY1 RZFC71DY1 RZFC85DY1
Power supply Indoor unit ---------- Power supply Indoor unit ----------
Outdoor unit 3 Phase, 380-415V, 50Hz Outdoor unit 3 Phase, 380-415V, 50Hz
Cooling Capacity 1,2 7.1 8.5 10.0 12.5 14.0 Cooling Capacity 1,2 7.1 8.5
kW (3.2-8.0) (4.2-10.0) (5.0-11.2) (5.7-14.0) (6.2-15.5) Rated (Min. - Max.) kW (3.2-8.0) (4.2-10.0)
Rated (Min. - Max.)
24,200 29,000 34,100 42,700 47,800 24,200 29,000
Btu/h (10,900-27,300) (14,300-34,100) (17,100-38,200) (19,500-47,800) (21,200-52,900) Btu/h (10,900-27,300) (14,300-34,100)
Power consumption Cooling 1
kW 2.37 2.74 3.17 5.21 6.22 Power consumption Cooling 1
kW 2.37 2.98
COP kW/kW 3.00 3.10 3.15 2.40 2.25 COP kW/kW 3.00 2.85
CSPF kWh/kWh 3.98 3.71 3.60 CSPF kWh/kWh 3.93
Indoor unit Colour ---------- Indoor unit Colour ----------
Fan Airflow rate (H/M/L) m3/min 25 / 20 / 16.5 36 / 30.5 / 25 Fan Airflow rate (H/M/L) m3/min 22.5 / 20 / 17.5
cfm 883 / 706 / 582 1,271 / 1,077 / 883 cfm 794 / 706 / 618
External static pressure 3 Pa Rated 40 (40-140) Rated 50 (50-150) External static pressure Pa Rated 15 (15-38)
Sound pressure level 4 (H/M/L) dB(A) 39 / 37 / 34 40 / 37.5 / 35 Sound pressure level 3 (H/M/L) dB(A) 39 / 35 / 33
Air filter 5 ---------- Air filter 4 ----------
Dimensions (HXWXD) mm 245X1,000X800 245X1,400X800 Dimensions (HXWXD) mm 245X1,000X800
Machine weight kg 36 46 Machine weight kg 36
Certified Operation range °CWB 14 to 25 Certified Operation range °CWB 14 to 25
Outdoor Colour Ivory white Outdoor Colour Ivory white
unit Coil Type Micro channel unit Coil Type Micro channel
Compressor Type Hermetically sealed swing type Compressor Type Hermetically sealed swing type
Motor output kW 1.60 2.40 Motor output kW 1.60 1.60 2.40
Refrigerant charge (R32) kg 1.0 (Charged for 15 m) 1.35 (Charged for 15 m) Refrigerant charge (R32) kg 1.0 (Charged for 15 m)
Sound pressure level 4 Cooling dB(A) 50 51 52 54 56 Sound pressure level 3 Cooling dB(A) 50 51
Dimensions (HXWXD) mm 695X930X350 990X940X320 Dimensions (HXWXD) mm 695X930X350
Machine weight kg 46 62 Machine weight kg 46
Certified Operation range °CDB 21 to 46 Certified Operation range °CDB 21 to 46
Piping Liquid (Flare) mm 9.5 Piping Liquid (Flare) mm 9.5
connections Gas (Flare) mm 15.9 connections Gas (Flare) mm 15.9
Drain Indoor unit mm VP25 (I.D. 25XO.D. 32) Drain Indoor unit mm VP25 (I.D. 25XO.D. 32)
Outdoor unit mm 18.0 (Hole) 26.0 (Hole) Outdoor unit mm 18.0 (Hole)
Max. interunit piping length m 50 (Equivalent length 70) Max. interunit piping length m 50 (Equivalent length 70)
Max. installation level difference m 30 Max. installation level difference m 30
Heat insulation Both liquid and gas piping Heat insulation Both liquid and gas piping

Note : Note :
1
Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal)
1
Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal)
2
Capacities are net, including a deduction for cooling for indoor fan motor heat.
2
Capacities are net, including a deduction for cooling for indoor fan motor heat.
3
External static pressure is changeable in 11 stages by remote controller.
3
The operation sound is measured in anechoic chamber. If it is measured under the actual installation conditions, it is normally over the set value due to environmental noise and sound reflection.
4
The operation sound is measured in anechoic chamber. If it is measured under the actual installation conditions, it is normally over the set value due to environmental noise and sound reflection.
4
Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its dust collection efficiency (gravity method) 50% or more.
5
Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its dust collection efficiency (gravity method) 50% or more.

69 70
SPECIFICATIONS RZFC series OPTIONS RZF series RZA series

DUCT CONNECTION LOW STATIC PRESSURE HEIGHT COMPACT TYPE (1 Phase) Cooling only Indoor unit
Indoor unit
40
FDLF40DV1
50
FDLF50DV1
60
FDLF60DV1
71
FDLF71DV1
85
FDLF85DV1
CEILING MOUNTED CASSETTE TYPE < Round Flow >
Model Kit name
Name Outdoor unit Name of option Remark
RZFC40DVM RZFC50DVM RZFC60DVM RZFC71DVM RZFC85DVM FCF50CVM FCF60CVM FCF71CVM FCF100CVM FCF125CVM FCF140CVM
Power supply Indoor unit ---------- Standard panel with Fresh white BYCQ125EEF
Outdoor unit 1 Phase, 220-240V, 50Hz Sensing Black BYCQ125EEK
Cooling Capacity 1,2 4.0 5.0 6.0 7.1 8.5 Decoration Fresh white BYCQ125EAF
kW (1.8-4.5) (2.3-5.6) (2.6-6.3) (3.2-8.0) (4.2-10.0) 1 panel Standard panel
Rated (Min. - Max.) Black BYCQ125EAK
13,600 17,100 20,500 24,200 29,000 Designer panel 1 Fresh white BYCQ125EAPF
Btu/h (6,100-15,400) (7,800-19,100) (8,900-21,500) (10,900-27,300) (14,300-34,100) Auto grille panel 2,3 Fresh white BYCQ125EASF
Power consumption Cooling 1 kW 1.19 1.56 2.07 2.37 2.98 Sealing material of air discharge outlet 4 For usage of 3-, 4-way flow KDBH551C160
2
COP kW/kW 3.35 3.20 2.90 3.00 2.85 For usage of 2-way flow KDBH552C160
CSPF kWh/kWh 4.33 4.13 3.93 3 Panel spacer KDB55J160F
Indoor unit Colour ---------- Fresh air intake kit Chamber Without T-duct joint KDDP55B160 (Components: KDDP55C160-1, KDDP55B160-2) 8
Fan Airflow rate (H/M/L) m /min
3
16 / 14 / 12 20 / 18 / 16.5 4 type 5,6 With T-duct joint KDDP55B160K (Components: KDDP55C160-1, KDDP55B160K2) 8
cfm 565 / 494 / 424 706 / 635 / 582 Direct installation type 7 KDDP55X160A
External static pressure Pa Rated 15 (15-38) High-efficiency filter unit 9 (Colorimetric method 65%) KAF556D80 KAF556D160
5 (Including filter chamber)
Sound pressure level 3 (H/M/L) dB(A) 37 / 33 / 30 40 / 37 / 34 (Colorimetric method 90%) KAF557D80 KAF557D160
Air filter Mould-proof air filter (Removable / Washable / Mould proof) Replacement high-efficiency filter 9,10 (Colorimetric method 65%) KAF552D80 KAF552D160
6
Dimensions (HXWXD) mm 200X900X620 200X1,100X620 (Colorimetric method 90%) KAF553D80 KAF553D160
Machine weight kg 28 31 7 Filter chamber KDDFP55C160
Certified Operation range °CWB 14 to 25 8 Replacement long-life filter KAF5511D160
Outdoor Colour Ivory white 9 Replacement long-life filter (Auto grille panel) KAF5512D160
unit Coil Type Micro channel 10 Ultra long-life filter unit (Including filter chamber) 9 KAF555D160
Compressor Type Hermetically sealed swing type 11 Replacement ultra long-life filter 9,10 KAF550D160
Motor output kW 1.20 1.30 1.60 12 Branch duct chamber 4 KDJP55C80 KDJP55C160
Refrigerant charge (R32) kg 0.7 (Charged for 10 m) 0.8 (Charged for 10 m) 1.0 (Charged for 15 m) 13 Insulation kit for high humidity 9,11 KDTP55K80A KDTP55K160A
Sound pressure level 3 Cooling dB(A) 48 49 50 51 Cooling only BRC7M635F (Fresh white) / BRC7M635K (Black)
14 Remote controller Wireless type
Dimensions (HXWXD) mm 595X845X300 695X930X350 Heat pump BRC7M634F (Fresh white) / BRC7M634K (Black)
Machine weight kg 34 37 44 15 Navigation remote controller Wired type 12 BRC1E63
Certified Operation range °CDB 21 to 46 16 Central remote controller 13 DCS302CA61
Piping Liquid (Flare) mm 6.4 9.5 17 Unified ON/OFF controller 13 DCS301BA61
connections Gas (Flare) mm 12.7 15.9 18 Schedule timer 13 DST301BA61
Drain Indoor unit mm VP25 (I.D. 25XO.D. 32) 19 intelligent Touch Controller 13 DCS601C51
Outdoor unit mm 18.0 (Hole) 20 Adaptor for wiring 14 BRP11B62
Max. interunit piping length m 30 (Equivalent length 40) 50 (Equivalent length 70) 21 Wiring adaptor for electrical appendices 14 KRP4AA53
Max. installation level difference m 15 30 22 Installation box for adaptor PCB KRP1H98A
Heat insulation Both liquid and gas piping 23 Remote sensor (for indoor temperature) BRCS01A-5
24 Wireless LAN connecting adaptor BRP072C42-1
Note:
1
When installing designer panel, body height (ceiling required dimension) is 42 mm higher than 7
The volume of fresh air for direct installation type is approximately 1% of the indoor unit airflow.
standard panel. Designer panel cannot operate 2 and 3 way flow. The chamber type is recommended when more fresh air is necessary.
2
A dedicated remote controller (BRC16A2) for the auto grille panel is included for lowering and 8
Please order using the names of both components instead of set name.
raising the suction grille. 9
This option cannot be installed to designer panel and auto grille panel.
3
When installing auto grille panel, body height (ceiling required dimension) is 55 mm higher than 10
Filter chamber is required.
DUCT CONNECTION LOW STATIC PRESSURE HEIGHT COMPACT TYPE (3 Phase) Cooling only
4
standard panel.
Circulation airflow is not available with this option.
11
12
Please use in case temperature/humidity inside ceiling may get over 30˚C, 80% RH.
Wiring for wired remote controller should be obtained locally.
71 85 5
When installing a fresh air intake kit (chamber type), two air outlet corners are closed. 13
The indoor unit is equipped standardly with the interface adaptor for SkyAir series. An option is unnecessary.
6
It is recommended that the volume of outdoor air introduced through the kit is limited to 10% of 14
Installation box for adaptor PCB(KRP1H98A) is necessary.
Indoor unit FDLF71DV1 FDLF85DV1 the maximum airflow rate of the indoor unit. Introducing higher quantities will increase the
Model
operating sound and may also influence temperature sensing.
Name Outdoor unit RZFC71DY1 RZFC85DY1
Power supply Indoor unit ----------
Round flow type: List of optional parts required to achieve different flow patterns
Outdoor unit 3 Phase, 380-415V, 50Hz For each flow pattern – all round, 4-way, 3-way, 2-way, branch duct connection – the compatibility of each independently installed option
Cooling Capacity 1,2 7.1 8.5 (shown in the column on the left) to accessory options (listed across the top of each table) is shown in the cells where the relevant row and column intersect.
Rated (Min. - Max.) kW (3.2-8.0) (4.2-10.0) A circle (o) indicates compatibility, and a cross (x) indicates incompatibility. Any options not shown below are not suitable for independent or accessory installation.
24,200 29,000
Btu/h (10,900-27,300) (14,300-34,100) All round flow 4-way flow
Power consumption Cooling 1
kW 2.37 2.98
Optional accessory parts Fresh air intake kit Fresh air intake kit Insulation kit High-efficiency Ultra long-life
COP kW/kW 3.00 2.85 Designer panel Auto grille panel Panel spacer1
Independently installable optional parts (Chamber type) 1 , 2 (Direct installation type) for high humidity filter unit2 filter unit2
CSPF kWh/kWh 3.93 Panel/grille related Designer panel x o o o x x x
Indoor unit Colour ---------- Auto grille panel x o o o x x x
Fan Airflow rate (H/M/L) m3/min 20 / 18 / 16.5 Panel spacer1 o o o o x o o
cfm 706 / 635 / 582 Auxillary function related Fresh air intake kit (Chamber type)1,2 o o o x x o o
External static pressure Pa Rated 15 (15-38) Fresh air intake kit (Direct installation type) o o o x o o o
Sound pressure level 3 (H/M/L) dB(A) 40 / 37 / 34 Insulation kit for high humidity x x x x o x x
Air filter Mould-proof air filter (Removable / Washable / Mould proof) Filter related High-efficiency filter unit2 x x o o o x x
Dimensions (HXWXD) mm 200X1,100X620 Ultra long-life filter unit2 x x o o o x x
Machine weight kg 31
Certified Operation range °CWB 14 to 25 3-way flow 2-way flow 5
Outdoor Colour Ivory white Optional accessory parts Fresh air intake kit Fresh air intake kit Insulation kit High-efficiency Ultra long-life
Designer panel Auto grille panel Panel spacer1,3
unit Coil Type Micro channel Independently installable optional parts (Chamber type)1,2 (Direct installation type) for high humidity filter unit2 filter unit2

Compressor Type Hermetically sealed swing type Panel/grille related Auto grille panel x o o x x x
Motor output kW 1.60 1.60 2.40 Panel spacer1,3 x x x
Refrigerant charge (R32) kg 1.0 (Charged for 15 m) Auxillary function related Fresh air intake kit (Chamber type)1,2 x o x x x o
Sound pressure level 3 Cooling dB(A) 50 51 Fresh air intake kit (Direct installation type) x o x o x o
Dimensions (HXWXD) mm 695X930X350 Insulation kit for high humidity x x x x o x x
Machine weight kg 46 Filter related Ultra long-life filter unit2 x x o o x x

Piping
Certified Operation range
Liquid (Flare)
°CDB 21 to 46
Branch duct connection
mm 9.5
connections Gas (Flare) mm 15.9 Optional accessory parts Fresh air intake kit Fresh air intake kit Insulation kit High-efficiency Ultra long-life
Designer panel Auto grille panel Panel spacer1
Independently installable optional parts (Chamber type)1,2 (Direct installation type) for high humidity filter unit2 filter unit2
Drain Indoor unit mm VP25 (I.D. 25XO.D. 32)
Branch duct chamber 1 1-way branch / unit 3-way flow o o o o o 4
x x o
Outdoor unit mm 18.0 (Hole)
Max. interunit piping length m 50 (Equivalent length 70)
2-way branch / unit 2-way flow x o x o o 4
x x o
1-way branch / unit 2-way flow x o x o o 4
x x o
Max. installation level difference m 30
Heat insulation Both liquid and gas piping 1. In some cases, depending on how the unit is embedded in the ceiling, use of branch ducts and fresh air intake kits may not be possible. Before starting installation work make sure to check whether or not
joint installation is possible. In particular, ensure that the lower fixing position caused by the addition of panel spacers is acceptable.
Note : 1Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal) When branch ducts are used, circulation airflow is not available.
2
Capacities are net, including a deduction for cooling for indoor fan motor heat. 2. When two different types of optional chambers are used together, a fresh air intake kit must be installed in the upper position.
3
The operation sound is measured in anechoic chamber. If it is measured under the actual installation conditions, it is normally over the set value due to environmental noise and sound reflection. 3. It is not possible to use panel spacers in a 2-way flow installation. (△)
4. It is not possible to install a branch duct on the same side to which a fresh air intake kit (direct mount) is installed.
5. When 3-way or 2-way flow is selected, circulation airflow is not available.

71 72
OPTIONS RZF series RZA series

Indoor unit
COMPACT MULTI FLOW CEILING MOUNTED CASSETTE TYPE FLOOR STANDING TYPE
Kit name Kit name
No. Name of option Remark
FFF50BV1 FFF60BV1 No. FVA50AMVM FVA100AMVM
Name of option Remark
1 Decoration panel BYFQ60B3W1 FVA60AMVM FVA125AMVM
FVA71AMVM FVA140AMVM
2 Sealing material of air discharge outlet KDBH44BA60
1 Replacement long-life filter KAF95M160
3 Panel spacer KDBQ44BA60A
Cooling only BRC4C66
4 Fresh air intake kit Direct installation type KDDQ44XA60 2 Remote controller Wireless type
Heat pump BRC4C65
5 Replacement long-life filter KAF441C60
3 Navigation Remote Controller Wired type 1 BRC1E63
6 Remote controller Wireless type Cooling only BRC7E531W
4 Central remote controller 2 DCS302CA61
7 Navigation remote controller Wired type 1 BRC1E63
5 Unified ON/OFF controller 2 DCS301BA61
8 Central remote controller 2 DCS302CA61
6 Schedule timer 2 DST301BA61
9 Unified ON/OFF controller 2 DCS301BA61
7 intelligent Touch Controller 2 DCS601C51
10 Schedule timer 2
DST301BA61
8 Adaptor for wiring 3 BRP11B61
11 intelligent Touch Controller 2 DCS601C51
9 Wiring adaptor for electrical appendices(2) 3 KRP4AA52
12 Adaptor for wiring 3 BRP11B61
10 Installation box for adaptor PCB KRP4AA95
13 Wiring adaptor for electrical appendices(2) 3 KRP4AA53
Note :
14 Installation box for adaptor PCB KRP1BB101 1
Wiring for wired remote controller should be obtained locally.
15 Remote sensor (for indoor temperature) BRCS01A-1
2
The indoor unit is equipped standardly with the interface adaptor for SkyAir series. An option is unnecessary.
3
Installation box for adaptor PCB (KRP4AA95) is necessary.
16 Interface adaptor for SkyAir series DTA112BA51
Note :
1
Wiring for wired remote controller should be obtained locally.

CEILING SUSPENDED TYPE


2
This optional accessory requires DTA112BA51.
3
Installation box for adaptor PCB (KRP1BB101) is necessaary.
Kit name

No. FHA100BVMV
Name of option Remark FHA50BVMV
FHA71BVMV FHA125BVMA
FHA60BVMV
FHA140BVMA
DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE 1 Replacement long-life filter Resin net KAF501B56 KAF501B80 KAF501B160
Kit name 2 Fresh air intake kit KDDQ50A140
No. Name of option Remark FBA50BVMA(9) FBA100BVMA(9) 3 Drain pump kit KDU50R160
FBA60BVMA(9) FBA125BVMA(9)
FBA71BVMA(9) FBA140BVMA(9) 4 L-type piping kit (for upward direction) KHFP5N160

1 Long-life filter1 KAF631C80 KAF631C160 Cooling only BRC7M56


5 Remote controller Wireless type
65% KAF632C80 KAF632C160 Heat pump BRC7M53
2 High-efficiency filter1
90% KAF633C80 KAF633C160 6 Navigation Remote Controller Wired type 1 BRC1E63
3 Filter chamber (for rear suction)1 KDDFP63B80 KDDFP63B160 7 Central remote controller 2 DCS302CA61
4 Service panel Fresh white KTBJ25K80F KTBJ25K160F 8 Unified ON/OFF controller 2 DCS301BA61
5 Air discharge adaptor KDAP25A71A KDAP25A140A 9 Schedule timer 2 DST301BA61
6 Shield plate for side plate KDBD63A160 10 intelligent Touch Controller 2 DCS601C51
Cooling only BRC4C66 11 Adaptor for wiring BRP11B61
7 Remote controller Wireless type
Heat pump BRC4C65 12 Wiring adaptor for electrical appendices 3 KRP4AA52
8 Navigation Remote Controller Wired type2 BRC1E63 13 Installation box for adaptor PCB KRP1D93A
9 Remote sensor (for indoor temperature) BRCS01A-4 14 Adaptor box mounting plate KKSAP50A56 ----------
10 Adaptor for wiring BRP11B62 15 Remote sensor (for indoor temperature) BRCS01A-4
11 Wiring adaptor for electrical appendices(2) KRP4AA51 Electrical box with earth terminal (3 blocks)
16 KJB311AA
12 Mounting plate for adaptor PCB.3,4,5 KRP4A98
17 Electrical box with earth terminal (2 blocks) KJB212AA
13 Central remote controller6 DCS302CA61
18 Wireless LAN connecting adaptor BRP072C42-1
14 Unified ON/OFF controller6 DCS301BA61
Note :
15 Schedule timer6 DST301BA61 1
Wiring for wired remote controller should be obtained locally.
16 intelligent Touch Controller6 DCS601C51
2
The indoor unit is equipped standardly with the interface adaptor for SkyAir series. An option is unnecessary.
3
Installation box for adaptor PCB (KRP1D93A) is necessary.
17 Wireless LAN connecting adaptor BRP072C42-1
Note :
1
If installing high efficiency filter and long-life filter to the unit, filter chamber is required.
2
Wiring for wired remote controller should be obtained locally. Kit name
3
Mounting plate is necessary for each adaptor marked .
4
Up to 2 adaptors can be fixed for each mounting plate.
5
Only one mounting plate can be installed for each indoor unit.
6
The indoor unit is equipped standardly with the interface adaptor for SkyAir series. An option is unnecessary.

Outdoor unit
CEILING MOUNTED SLIM DUCT TYPE 1 Phase RZF50/60/71CV2V RZA50/60DV2V RZA71/100/125/140DV1
RZF100CVM RZF125/140CVM
Kit name No. Name of option
No. Name of option Remark 3 Phase ---------- ---------- RZF71/100CYM RZF125/140CYM RZA100/125/140DY1
FDF50BV1 FDF60BV1
Remote controller Wireless type Cooling only 1 Central drain plug KKP014A4 KKP937A4 KKPJ5G280
1 BRC4C64
2 Fixture for preventing overturning ---------- KKTP5B112
2 Navigation remote controller Wired type 1 BRC1E63
3 Wire fixture for preventing overturning ---------- K-KYZP15C
3 Remote sensor (for indoor temperature) BRCS01A-1
4 Demand adaptor ---------- KRP58M6 KRP58M51 KRP58M51+EKMKSA1 KRP58M51+EKMKSA2
4 Insulation kit for high humidity KDT25N63
1 Phase BRV2BPSF ---------- BRV2BPSS BRV2BPL ----------
Note : 5 Overvoltage PCB
1
Wiring for wired remote controller should be obtained locally. 3 Phase ---------- BRV2BPSS+BRV2BPSS ----------

73 74
OPTIONS RZFC series

Indoor unit
CEILING MOUNTED CASSETTE TYPE < Round Flow > DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE
Kit name Kit name
FCFC40DVM FCFC100DVM No. Name of option Remark FBFC40DVM(9) FBFC71DVM(9) FBFC100DVM(9)
No. Name of option Remark FCFC71DVM FBFC50DVM(9) FBFC125DVM(9)
FCFC50DVM FCFC125DVM FBFC85DVM(9)
FCFC85DVM FBFC60DVM(9) FBFC140DVM(9)
FCFC60DVM FCFC140DVM
1 Long-life filter 1 KAF631C56 KAF631C80 KAF631C160
1 Decoration panel Standard panel Fresh white BYCQ125EAF
65% KAF632C56 KAF632C80 KAF632C160
For usage of 3-, 4-way flow KDBH551C160 2 High-efficiency filter 1
2 Sealing material of air discharge outlet 90% KAF633C56 KAF633C80 KAF633C160
For usage of 2-way flow KDBH552C160
3 Filter chamber(for rear suction)1 KDDFP63B56 KDDFP63B80 KDDFP63B160
3 Panel spacer KDB55J160F
4 Service panel Fresh white KTBJ25K56F KTBJ25K80F KTBJ25K160F
Chamber Without T-duct joint KDDP55B160 (KDDP55C160-1, KDDP55B160-2) 4

type 1,2 5 Air discharge adaptor KDAP25A56A KDAP25A71A KDAP25A140A


4 Fresh air intake kit With T-duct joint KDDP55B160K (KDDP55C160-1, KDDP55B160K2) 4

6 Shield plate for side plate KDBD63A160


Direct installation type 3 KDDP55X160A
7 Remote controller Wireless type Cooling BRC4C66
(Colorimetric method 65%) KAF556D80 KAF556D160
5 High-efficiency filter unit 8 Simplified Remote Controller Wired type 2 BRC2E61
(Including filter chamber) (Colorimetric method 90%) KAF557D80 KAF557D160
9 Remote sensor (for indoor temperature) BRCS01A-4
(Colorimetric method 65%) KAF552D80 KAF552D160
6 Replacement high-efficiency filter 5 10 Adaptor for wiring 3 BRP11B62
(Colorimetric method 90%) KAF553D80 KAF553D160
11 Wiring adaptor for electrical appendices(2) 3 KRP4AA51
7 Filter chamber KDDFP55C160
12 Mounting plate for adaptor PCB.3,4,5 KRP4A98
8 Replacement long-life filter KAF5511D160
13 Central remote controller 6 DCS302CA61
9 Ultra long-life filter unit (Including filter chamber) KAF555D160
14 Unified ON/OFF controller 6 DCS301BA61
10 Replacement ultra long-life filter 5 KAF550D160
15 Schedule timer 6 DST301BA61
11 Branch duct chamber KDJP55C80 KDJP55C160
16 intelligent Touch Controller 6 DCS601C51
12 Insulation kit for high humidity 6 KDTP55K80A KDTP55K160A
17 Drain pump kit BDU24AMD2
13 Remote controller Wireless type Cooling only BRC7F635F
Note:
14 Simplified remote controller Wired type 7 BRC2E61 1
If installing high efficiency filter and long-life filter to the unit, filter chamber is required. 4
Up to 2 adaptors can be fixed for each mounting plate.
2
Wiring for wired remote controller should be obtained locally. 5
Only one mounting plate can be installed for each indoor unit.
15 Central remote controller 8
DCS302CA61 3
Mounting plate is necessary for each adaptor marked . 6
The indoor unit is equipped standardly with the interface adaptor for SkyAir series. An option is unnecessary.
16 Unified ON/OFF controller 8 DCS301BA61
17 Schedule timer 8 DST301BA61
18 intelligent Touch Controller 8 DCS601C51
19 Adaptor for wiring 9 BRP11B62
20 Wiring adaptor for electrical appendices 9 KRP4AA53 DUCT CONNECTION LOW STATIC PRESSURE WIDTH COMPACT TYPE
Kit name
21 Installation box for adaptor PCB KRP1H98A
No. Name of option Remark FDBF40DV1 FDBF71DV1
22 Remote sensor (for indoor temperature) BRCS01A-5 FDBF50DV1 FDBF85DV1
Note: FDBF60DV1
1
When installing a fresh air intake kit (chamber type), two air outlet corners are closed. 4
Please order using the names of both components instead of set name. 1 Remote controller Wireless type Cooling BRC4C66
2
It is recommended that the volume of outdoor air introduced through the kit is limited to 10% of 5
Filter chamber is required.
the maximum airflow rate of the indoor unit. Introducing higher quantities will increase the 6
Please use in case temperature/humidity inside ceiling may get over 30˚C, 80% RH. 2 Simplified Remote Controller Wired type 1 BRC2E61
operating sound and may also influence temperature sensing. 7
Wiring for wired remote controller should be obtained locally.
3
The volume of fresh air for direct installation type is approximately 1% of the indoor unit airflow. 8
The indoor unit is equipped standardly with the interface adaptor for SkyAir series. An option is unnecessary. 3 Remote sensor (for indoor temperature) BRCS01A-1
The chamber type is recommended when more fresh air is necessary. 9
Installation box for adaptor PCB(KRP1H98A) is necessary.
Note:
1
Wiring for wired remote controller should be obtained locally.

Round flow type: List of optional parts required to achieve different flow patterns
For each flow pattern – all round, 4-way, 3-way, 2-way, branch duct connection – the compatibility of each independently installed option
(shown in the column on the left) to accessory options (listed across the top of each table) is shown in the cells where the relevant row and column intersect. DUCT CONNECTION LOW STATIC PRESSURE HEIGHT COMPACT TYPE
A circle (o) indicates compatibility, and a cross (x) indicates incompatibility. Any options not shown below are not suitable for independent or accessory installation. Kit name
No. Name of option Remark FDLF40DV1 FDLF71DV1
FDLF50DV1 FDLF85DV1
Optional accessory parts
Panel spacer1 Fresh air intake kit Fresh air intake kit Insulation kit High-efficiency Ultra long-life FDLF60DV1
Independently installable optional parts (Chamber type) 1 , 2 (Direct installation type) for high humidity filter unit2 filter unit2
Panel/grille related Panel spacer1 o o x o o 1 Remote controller Wireless type Cooling BRC4C66

All-round flow Auxillary function related Fresh air intake kit (Chamber type)1,2 o x x o o 2 Simplified Remote Controller Wired type 1 BRC2E61
4-way flow Fresh air intake kit (Direct installation type) o x o o o 3 Remote sensor (for indoor temperature) BRCS01A-1
Insulation kit for high humidity x x o x x
Filter related High-efficiency filter unit2 o o o x x Note:
Wiring for wired remote controller should be obtained locally.
o o o
1
Ultra long-life filter unit2 x x

Optional accessory parts


Panel spacer1 Fresh air intake kit Fresh air intake kit Insulation kit High-efficiency Ultra long-life
Independently installable optional parts (Chamber type) 1 , 2 (Direct installation type) for high humidity filter unit2 filter unit2
Panel/grille related Panel spacer 1,3
x x
3-way flow
2-way flow 5
Auxillary function related Fresh air intake kit (Chamber type)1,2 x x x o
Fresh air intake kit (Direct installation type) x o x o
x x o x x
Outdoor unit
Insulation kit for high humidity
Filter related Ultra long-life filter unit2 o o x x
Kit name
Optional accessory parts Fresh air intake kit Fresh air intake kit Insulation kit High-efficiency Ultra long-life 1 Phase RZFC40/50/60/71DVM RZFC85/100DVM ----------
Independently installable optional parts Panel spacer1 (Chamber type) 1 , 2 (Direct installation type) for high humidity filter unit2 filter unit2 No. Name of option
Branch duct Branch duct chamber 1 1-way branch / unit 3-way flow o o o 4
x x o 3 Phase ---------- RZFC71/85/100DY1 RZFC125/140DY1
connection 2-way branch / unit 2-way flow x o o 4
x x o 1 Central drain plug KKP014A4 KKP937A4 KKPJ5G280
1-way branch / unit 2-way flow x o o 4
x x o 2 Fixture for preventing overturning ---------- ---------- KKTP5B112
1. In some cases, depending on how the unit is embedded in the ceiling, use of branch ducts and fresh air intake kits may not be possible. Before starting installation work make sure to check whether or not 3 Wire fixture for preventing overturning ---------- ---------- K-KYZP15C
joint installation is possible. In particular, ensure that the lower fixing position caused by the addition of panel spacers is acceptable. When branch ducts are used, circulation airflow is not available.
2. When two different types of optional chambers are used together, a fresh air intake kit must be installed in the upper position.
3. It is not possible to use panel spacers in a 2-way flow installation. (△)
4. It is not possible to install a branch duct on the same side to which a fresh air intake kit (direct mount) is installed.
5. When 3-way or 2-way flow is selected, circulation airflow is not available.

75 76