Professional Documents
Culture Documents
COMMUNICATIONS
CABLING STANDARDS
INTRODUCTION .......................................................................................................................................................4
I. ABOUT THIS MANUAL .....................................................................................................................................4
II. COMMUNICATIONS RESOURCES’ RESPONSIBILITIES FOR PROJECTS .................................................................4
III. THE TELECOMMUNICATIONS DISTRIBUTION SYSTEM DESIGN PROCESS FOR UC DAVIS .............................6
IV. OVERVIEW OF THIS MANUAL ......................................................................................................................7
THE HORIZONTAL SEGMENT .............................................................................................................................8
I. THE DESIGN PROCESS ......................................................................................................................................8
II. THE TYPE AND NUMBER OF OUTLETS ..............................................................................................................8
III. CABLE TYPES AND LENGTHS.......................................................................................................................9
IV. TERMINATION HARDWARE REQUIREMENTS AT THE OUTLET ....................................................................11
V. ASSIGNING THE NAM NUMBERS TO THE APPROPRIATE LOCATIONS, AND NAM MATRICES. .........................11
VI. CROSS CONNECTING VOICE NAMS. .........................................................................................................12
VII. STRUCTURES TO SUPPORT THE HORIZONTAL CABLING .............................................................................12
VIII. CABLE TESTING PROCEDURES...................................................................................................................16
THE INTERMEDIATE DISTRIBUTION FRAME ..............................................................................................20
I. THE DESIGN PROCESS ....................................................................................................................................20
II. THE SIZE OF THE IDF .....................................................................................................................................20
III. THE LOCATION OF THE IDF.......................................................................................................................21
IV. DESIGN REQUIREMENTS ............................................................................................................................21
V. TERMINATION HARDWARE REQUIREMENTS IN THE IDF............................................................................23
VI. STRUCTURES TO SUPPORT THE CABLING IN THE IDF ................................................................................25
VII. DRAWINGS FOR CONSTRUCTION/PROJECT MANAGERS .............................................................................27
THE RISER SEGMENT...........................................................................................................................................30
I. THE DESIGN PROCESS ....................................................................................................................................30
II. THE SIZE OF THE COPPER RISER CABLE .........................................................................................................31
IV. STRUCTURES TO SUPPORT VERTICALLY ALIGNED IDFS ...........................................................................32
V. STRUCTURES TO SUPPORT HORIZONTALLY OFFSET IDFS ..............................................................................34
THE BUILDING DISTRIBUTION FRAME..........................................................................................................36
I. THE DESIGN PROCESS ....................................................................................................................................36
II. THE SIZE OF THE BDF....................................................................................................................................36
III. THE LOCATION OF THE BDF .....................................................................................................................37
IV. DESIGN REQUIREMENTS ............................................................................................................................38
V. TERMINATION HARDWARE REQUIREMENTS IN THE BDF ..........................................................................39
VI. STRUCTURES TO SUPPORT THE CABLING IN THE BDF ...............................................................................42
VII. CABLE PATHWAYS ENTERING THE BDF ...................................................................................................43
VIII. DRAWINGS FOR CONSTRUCTION/PROJECT MANAGERS .............................................................................45
THE CAMPUS SEGMENT......................................................................................................................................47
I. THE DESIGN PROCESS ....................................................................................................................................47
II. CABLE ROUTES ..............................................................................................................................................47
III. CABLE DISTRIBUTION METHODS...............................................................................................................48
IV. UNDERGROUND (IN CONDUIT) AND DIRECT BURIED CABLE REQUIREMENTS ...........................................48
V. CABLE TYPES ............................................................................................................................................51
VI. SPLICE BOXES, MANHOLES, AND PULL BOXES .........................................................................................56
VII. AERIAL CABLE REQUIREMENTS ................................................................................................................60
VIII. ELECTRICAL PROTECTION AND BONDING/GROUNDING REQUIREMENTS ...................................................61
APPENDIX A.............................................................................................................................................................62
SPECIFICATIONS.......................................................................................................................................................62
SPECIFICATION 01 ................................................................................................................................................63
NETWORK ACCESS MODULE (NAM).......................................................................................................................63
SPECIFICATION 02 ................................................................................................................................................65
FACEPLATES ............................................................................................................................................................65
SPECIFICATION 03 ................................................................................................................................................66
CONDUIT .................................................................................................................................................................66
SPECIFICATION 04 ................................................................................................................................................67
HORIZONTAL CONDUIT CAPACITY ..........................................................................................................................67
SPECIFICATION 05 ................................................................................................................................................68
CABLE TRAYS..........................................................................................................................................................68
SPECIFICATION 06 ................................................................................................................................................69
COLOR CODES FOR CROSS CONNECT FIELDS...........................................................................................................69
SPECIFICATION 07 ................................................................................................................................................70
DISTRIBUTION CABINETS.........................................................................................................................................70
SPECIFICATION 08 ................................................................................................................................................81
CONDUIT FILL FOR RISER CABLES ...........................................................................................................................81
SPECIFICATION 09 ................................................................................................................................................82
PULL BOXES ............................................................................................................................................................82
SPECIFICATION 10 ................................................................................................................................................84
CONDUIT FOR UNDERGROUND CABLING .................................................................................................................84
SPECIFICATION 11 ................................................................................................................................................86
ELECTRICAL PROTECTION, BONDING/EARTHING ....................................................................................................86
APPENDIX B.............................................................................................................................................................89
REFERENCE MATERIALS ..........................................................................................................................................89
APPENDIX C.............................................................................................................................................................92
GLOSSARY ...............................................................................................................................................................92
APPENDIX D...........................................................................................................................................................103
UC DAVIS POLICY AND PROCEDURE MANUAL, SECTION 310-10..........................................................................103
APPENDIX E...........................................................................................................................................................104
NAM MATRICES:..................................................................................................................................................104
VOICE NAM MATRIX .......................................................................................................................................104
DATA NAM MATRIX: .......................................................................................................................................105
MATV NAM MATRIX: ......................................................................................................................................106
APPENDIX F ...........................................................................................................................................................107
INTRODUCTION
A. This manual contains the policies and procedures for architects, contractors, and
telecommunications design professionals who are involved in telecommunications
projects on the UC Davis campus. The manual should be used as a guide for
projects providing telecommunications cabling. Work may include new or
renovated buildings and may consist of upgrading or adding cabling
infrastructures, cable and network electronics equipment.
1. Schematic – These are the initial planning documents and design drawings
which assist departments in the early stage of the project. The Schematic
Design documents shall consist of System Narrative, including BDF/IDF
information, campus connection points, drawings should include title
Sheet, single line diagrams, site plan (may be part of electrical site plan).
8. Electrical service requirements and service points for ADFs, BDFs, and
IDFs, as well as any necessary ancillary electrical work as part of the
project.
1. The Horizontal Segment consists of the NAMs,cabling to the IDF and the
associated pathways
3. The Riser Segment refers to the riser cable, and the sleeves, slots, and
conduits that enable the cable to pass from floor to floor, BDF to IDF, IDF
to IDF.
4. The Building Distribution Frame is the room that houses system common
equipment and hardware for terminating the campus and riser cables.
A. This manual is divided into five Segments with each Segment divided into six or
more sections. Section 1 of each Segment is the Introduction to that segment.
1. The horizontal cable and connecting hardware that provide the means for
transporting the telecommunications signals between the network access
module (NAM) in the work area and the horizontal cross-connect in the
intermediate distribution frame (IDF).
2. The horizontal cabling pathways and spaces that distribute and support the
horizontal cable and connecting hardware between the NAM and the IDF.
Note: Cables that interconnect IDFs on the same floor, while physically
horizontal in orientation, are considered part of the riser segment.
B. This section describes the policies and procedures for the following design
activities:
2. Identifying the types and lengths of cable used in the horizontal segment.
A. Work area outlets at UC Davis fall into three general configurations: basic,
enhanced, and integrated.
B. The features of these three designs may be combined in the most cost-effective
manner with Communications Resources’ approval.
C. At least two enhanced outlets must be provided in each office and conference
room.
E. A 4 × 4 × 2½ inch back box with a single gang plaster ring must be used at each
work area for NAM installations. From each backbox a minimum of ¾” conduit
for basic and enhanced NAM, minimum 1” for integrated NAMs, will be run to
the cable pathway support system. Conduit is to be sized appropriately for the fill
of cable it is to accommodate.
A. UC Davis recognizes two types of cables for use in the horizontal segment: UTP
(unshielded twisted pair) cable and fiber optic cable.
1. UTP cable will be 4-pair, 24 AWG, solid conductor cabling that meets all
the latest ANSI/TIA/EIA 568-A and TIA/EIA 568-A-1 Propagation and
Delay Skew specifications for Category 5e cable, with all current
Amendments and Bulletins, and must meet Anixter Level 6 (ALC-6)
performance requirements.
B. All conductive cabling and associated components must comply with Article 800
of the NEC (1996). Furthermore, all fiber optic cabling must comply with Article
770 of the NEC (1996).
E. Horizontal UTP cable and fiber optic cable will not be spliced.
F. The maximum lengths of horizontal distribution cables are shown in Table 2-1
(see Note).
Table 2-1
Note: These limits apply to all types of horizontal cables. In establishing these
limits, a 33-foot allowance was made for the combined length of patch cables and
cables used to connect equipment in the work area and IDF.
G. Equipment cables attach directly to active equipment and must meet the same
performance requirements as the patch cords. Patch cables and cross-connect
jumpers must not attach directly to active equipment.
H. Cable slack must be provided at both ends of cable runs to accommodate future
cabling system changes.
1. The minimum amount of slack must be 1 foot for UTP cables and 3 feet
for fiber optic cables at the outlet. At the IDF, UTP horizontal cables
are to meet manufactures procedures for slack, for patch panels, and
110 frames.
3. The fiber optic cable must have a 10-foot service loop at the IDF.
4. The slack must be included in all length calculations to ensure that the
horizontal cable does not exceed 295 feet.
A. Each UTP cable will be terminated at the outlet with an Ortronics GigaMo
Solution: OR-60950011, OR-60950012 SERIES II, or OR-63750001
TRACJACK Module Information Outlet. (Face plates for the designated outlets
must be from the same vendor.)
B. Each fiber optic cable will be terminated at the outlet using a SC-style duplex
connector mounted in a modular-coupling mounting module.
Refer to Appendix A Specification 01 for details about NAMs.
V. Assigning the NAM numbers to the appropriate locations, and NAM Matrices.
B. NAM numbers shall be obtained by the Consultant from the UC Davis Line Assigner
at 530-752-4598.
Note: All additional NAM numbers shall be obtained only from the UC Davis Line
Assigner at 530-752-4598. NAM numbers shall not be duplicated.
C. After NAM numbers have been pre-assigned to the floor plans, the Consultant will
complete the NAM matrices. Refer to Appendix A Specification 01 for information
on NAM matrices. Nam matrices are to be completed at the beginning of
Construction Document preparation. A hardcopy of NAM matrices shall be provided
to UCD Project Manager, and excel 2000 spreadsheet file to be provided to
Communications Resources.
D. The Consultant will ensure that specifications are placed in the contract documents
that inform the Cabling Contractor regarding use of and maintenance of the NAM
matrices for the project.
A. The Project Consultant shall ensure that the Contractor provides a Voice NAM
Matrix, identifying all cross connections from the NAM to the BDF.
C. The Voice NAM Matrix shall be provided prior to final inspection of the cabling
work
A. Special attention must be given when selecting and designing the type and layout
of structures to support the horizontal cabling. The design must accommodate
cabling changes with a minimum of disruptions to occupants.
Note: UC Davis requires that the space above the ceiling grid be used, whenever
possible, to route the horizontal cabling.
B. Listed below are the steps needed to complete this phase of the design process:
3. Annotate, on the floor plan, the locations of the IDFs. If these locations
have not been identified, please complete Section 3, The Intermediate
Distribution Frame, before proceeding with this section.
4. Verify that the distance from each outlet to the horizontal cross-connect in
the IDF does not exceed 295 feet. This distance must include the planned
cable path as well as any vertical transitions.
Note: If there are horizontal cable lengths that exceed 295 feet, the IDF
must be relocated to a more centralized location or another IDF
must be added. Section 3, The Intermediate Distribution Frame,
addresses how to locate and size the IDF.
5. Sketch the route of the conduit and the cable tray on the floor plan.
6. Identify firewalls or fire rated barriers that will be breached during cable
installation.
Note: All horizontal pathways that penetrate fire rated barriers must be
firestopped in accordance with applicable fire codes. See Figure 2-1.
Metallic
d it Approved fire stop
bl
Fire rated
b i
Figure 2-1. Conduit must extend through the fire rated barrier when a fire rated barrier
exists between the outlet and the cable tray.
b) Conduits will be of a size that will ensure that a 40% fill ratio is
not exceeded.
c) The ends of the conduit will be bonded and earthed. Conduit will
be earthed to MTGB. Refer to Figure 2-2.
d) Surface molding will be used to route cable from the work area
outlet to the interstitial space in areas with limited ceiling access.
8. Identify outlets that will be located on walls that are not made of sheet
rock construction such as plaster walls, concrete block walls, exterior
walls, and insulated walls. Written approval must be obtained from the
Manager, Systems Engineering & Development, Communications
Resources to use surface mounted outlets if these walls cannot be fished.
Note: Exterior walls, while furred and covered with sheet rock, may not
provide the necessary clearance between the sheet rock and the backing
material (commonly concrete block) for standard outlets.
10. Minimum cable bend radii and conduit capacity must be considered when
using a modular furniture system.
11. Annotate on the floor plan the cable paths that will be supported with J-
hooks.
Note: J-hooks will be placed at least every 4 feet to support the cable, and
will be annotated on the construction drawings.
A. General
1. The Contractor shall perform tests on the Voice Telephone Plant cable.
The tests shall be performed end-to-end from each termination block on
each pair. Provide machine-generated documentation of all test results on
Contractor-provided, and University’s Representative-approved forms.
This end-to-end test shall include the following:
a) DC Continuity
b) Reversals
c) Shorts
d) Opens
e) Overall loop resistance/cable length
f) Attenuation
g) Splits
1. UC Davis requires that all UTP cable pairs be tested with a Level II or
Level III tester for full compliance with Category 5e specifications
regardless of intended use.
2. Test results must be provided for all conductor pairs of each cable.
Parameter Category 5e
Specified Frequency 1-100 MHz
Range
Attenuation 24.0 dB
NEXT 30.1 dB
ACR 6.1 dB
ELFEXT 17.4 dB
D. Fiber Testing
1. The horizontal fiber optic cable must be tested using a double-ended loss
test. See Table 2-4 for proper fiber testing measures.
b) The dB loss for a horizontal segment must not exceed 2.0 dB.
(1) Select two test jumpers. Ensure that the jumpers have a
fiber core size of 62.5 µm and are connected with SC- style
connectors (see Figure 2-3).
(2) Ensure that the optical source meter is stabilized and has a
center wavelength within ± 20 nm of the multi-mode
nominal wavelength.
(3) Ensure that the power meter and the light source are set to
850 nm if testing multi-mode fiber or 1310 if testing single
mode fiber.
(6) Verify the second test jumper by adding this second jumper
between the power meter and the original jumper.
Note: If the loss is greater than 0.5 dB, clean all connectors
(except the connector inserted at the source) and test again.
If the loss is still unacceptable, replace the second test
jumper.
(7) Test the horizontal segment from each end of the fiber -
from the NAM at the outlet and from the distribution
cabinet in the communications room.
(8) The total signal loss for a fiber link will not be greater than
2.0 dB - this includes connector loss and fiber loss.
Basic Guideline for Loss Measurements for Installed Fiber Optic Cables
Connector loss: 0.75 dB per mated pair
Fiber loss: Multi-mode: 2.5 dB/km @ 850 nm, 2.5 dB/km @ 1300 nm
Fiber loss: Single mode: 1.0 dB/km @ 1310 nm
Table 2-4
A. The intermediate distribution frame (IDF) is the space where the horizontal cable
is terminated on patch panels, 110-blocks, or connector panels, and cross-
connected to the riser cable.
B. The IDF supports the voice, data, and video needs of one floor of a building as
opposed to an entire building or campus. It may also support other building
information systems such CATV, alarms, security, audio,800mhz radio, other
wireless systems and other telecommunications systems.
A. The size of the IDF depends on its function and the size of the usable floor space
it serves. Usable floor space refers to the building areas used by the occupants in
their normal daily work functions. The minimum IDF sizes shown are based on
providing telecommunications service to one individual work area of 100 sq. ft.
C. Multiple IDFs are required if the usable floor space to be served exceeds 10,000
square feet or the cable length between the work area outlet and the horizontal
cross-connect in the IDF exceeds 295 feet. Minimum IDF sizes are shown in
Table 3-1.
D. Additional floor space must be allocated if fire alarm panels and/or building
monitoring equipment are located in the IDF.
E. Additional floor space must be allocated for additional applications, such as,
Video Distribution cabling and equipment, etc.
Table 3-1
Note: These wall lengths are the minimum acceptable. Shorter wall lengths will not allow space
for equipment.
A. Since the IDF is the focal point for many communications services, it must be
designed as an integral part of the overall building.
B. The IDF must be located as close as possible to the center of, and on the same
floor as, the work area it serves in order to minimize the horizontal cable lengths.
.
C. Access to the IDF must be directly from hallways, not through classrooms,
offices, or mechanical spaces.
D. The IDF must be located above any threat of flooding. All water pipes transiting
the room(as well as the associated plumbing fixture) must be removed or
contained.
E. The IDF must not be located near power supply transformers, elevator or pump
motors, generators, x-ray equipment, radio transmitters, or other potential sources
of electromagnetic interference.
F. The IDF must not share space with electrical, janitorial, or storage facilities.
I. The locations of the IDFs must be submitted to the project manager for inclusion
in the construction drawings, and they must be annotated on the floor plan.
A. The major factors that must be considered when designing the IDF are as follows:
2. The doors must be a minimum of 3 feet wide and 6 feet, 8 inches tall. The
doors must open outward and be lockable.
3. The floor must be sealed concrete or tile to minimize dust and static
electricity.
5. The IDF must not be equipped with a drop tile or other false ceiling.
7. All walls must be lined with Trade Size ¾-inch AC-grade plywood, 8 feet
high, as measured from finished floor.
b) The patch panels must be labeled above the RJ45 module as shown
in Figure 3-1.
60125 60126 60127 60128 60129 60130 60131 60132 60133 60134 60135 60136 60137 60138 60139 60140 60141 60142 60143 60144 60145 60146 60147 60148
Insert Fiber details: What type connector panels (high density etc.)?
B. Space for terminations of each type of cable must be located on one continuous
wall or rack.
2. There must be additional backboard space for routing cables, patch cords,
and/or cross-connect jumpers.
C. Cross-connect fields, patch panels, and active equipment in the IDF must be
placed to allow cross-connections and interconnections via jumpers, patch cords,
and equipment cables whose lengths per channel do not exceed:
2. 33 feet total for patch cords or jumpers and line cords used to connect to
the outlet.
equipment organized, and to allow the cable plant to be installed to UC Davis and
EIA/TIA 569 specifications.
b) All ladder racking must be bonded and earthed to the busbar in the
IDF.
Fiber distribution
cabinet is located
at the top of the
relay rack or cabinet
with network electronics
below
In smaller IDFs,
Network fiber, UTP, and
network electronics
Electronics can be located in
the same rack or
cabinet
A. The following steps must be taken once the size, location, design requirements,
termination hardware, and support structures for the cabling have been
determined for the IDF:
g) Location and height of lighting (insure that ladder racking will not
block or otherwise interfere with the lighting)
2
Reference: UC Davis Campus Standards & Design Guide for drawing content pages, 29, 30 & 31 dated June
2000.
A. The riser segment consists of the riser cable and the supporting infrastructure
within a building or cluster of buildings that connect the intermediate distribution
frames (IDFs) and the building distribution frame (BDF).
B. The riser segment must be designed one segment at a time as illustrated in Figure
4-1, even though the riser cables may follow the same path.
IDF 3.1
Segment B
IDF 2.1
Segment A
BDF 1.1
C. This section describes the policies and procedures for the following design
activities:
A. The size of the riser cable is a function of the number of basic, enhanced, and
integrated outlets supported by the IDF.
1. The minimum number of copper cable pairs required for each type of
outlet is as follows: basic outlets = 1.5 pairs; enhanced outlets = 2 pairs,
integrated outlets = 2.5 pairs
2. Commonly available cable sizes are 50, 100, 200, 300, 600, 900 and 1200
pairs.
In this case, the riser cable would be 200 pairs, the next larger, commonly
available copper cable, above 100 pair.
Note: The minimum number of fiber strands for each type of IDF is shown in
Table 4-1. Each IDF fiber cable shall be comprised of 50% multimode
and 50% single mode fiber strands (example: 12 fiber cable with 6
multimode and 6 singlemode fiber strands)
A. IDFs that are vertically aligned must be connected with sleeves or slots. A sleeve
is a circular opening through the ceiling or floor of an IDF that allows the passage
of cables and wires. A slot is similar to a sleeve except that it is a rectangular
opening.
B. Sleeves and slots must be positioned near a wall on which the riser cables can be
supported.
C. They must be located where pulling and termination will be easy, preferably on
the left side of the IDF.
D. Sleeves and slots must not be placed directly above or below the wall space that is
used for termination fields.
E. Sleeves and slots must conform to the National Electrical Code (NEC) and local
fire codes.
F. Sleeves and slots must not be left open after cable installation and they must be
properly firestopped at all times in accordance with applicable building codes.
G. Sleeves must extend a maximum of 4 inches above the floor level. Slots must
have a 1-inch high curb. See Figure 4-1 for typical sleeve and slot dimensions.
H. Rigid steel conduit (RSC) sleeves must be 4 inches in diameter unless a structural
engineer requires a smaller size or obstructions are present. They must be fitted
with plastic bushings on both ends and equipped with pull strings.
Table 4-1 lists the minimum number of 4-inch sleeves that must be used based on the total feet
that the sleeves support.
Total Square Feet Quantity of Sleeves
Up to 50,000 3
50,000 to 100,000 4
100,000 to 300,000 5-8
300,000 to 500,000 9-12
Table 4-1
Table 4-2 lists the sizes of slots that are required based on the total square feet
served by the slot.
A. IDFs that are not vertically aligned must be connected with cable trays or
conduits.
B. Cable trays that are used to support horizontal cabling may be used to support
riser cables provided the following conditions are met:
1. The cable trays’ carrying capacity can accommodate the riser cables.
2. The route of the cable trays can be used or modified to accommodate the
lateral run between the IDFs.
3. The riser cables conform to NEC Article 800-3(b)(1), NEC Article 800-
3(b)(3), and comply with the State of California fire codes as interpreted
by the State Fire Marshal’s department.
4. The riser cables are UL Listed Type CMP or OFNP if they are placed in
air-handling plenums without conduit.
C. Conduit will be used to route the riser cables between the IDFs if cable trays are
not used to support the horizontal cabling. Conduit paths are tightly controlled
pathways that must be coordinated with other trades during construction or
remodeling.
See Appendix A Specification 08 for details on conduit fill for riser cables.
3. The conduit will be installed with a pull string and the ends will be bushed
to protect the cable.
4. Conduits that enter the IDF must be placed near the corner and as close as
possible to the wall where the backboard is mounted to allow for proper
cable racking and to minimize the cable route inside the IDF.
5. Conduit located in the ceiling must protrude into the IDF 1 to 2 inches and
above 7½ feet above the finished floor. Conduit will not turn down.
D. Listed below are the steps needed to plan conduit runs in the riser segment:
1. Identify on the floor plans the IDFs that will be supported using conduit.
4. Determine if any pull boxes are needed along the conduit run.
a) Pull boxes are required in sections of conduit that are 100 feet or
more in length or that contain more than two 90° bends. Pull boxes
must not be used in lieu of a bend.
b) Cables must feed straight through a pull box.
See Appendix A Specification 09 for details on installing and selecting the proper size of
pull boxes.
5. Notify the project manager of the locations and sizes of the pull boxes for
inclusion in the mechanical or electrical designs.
6. Annotate on the floor plan the locations and sizes of the pull boxes.
B. The building distribution frame (BDF) is the room that houses the
telecommunications equipment that meets the voice, data, and video needs of an
entire building. This equipment may include Private Branch Exchange (PBX),
switching nodes, local area network hubs, and video distribution equipment,
and/or network routers.
C. The BDF contains cross-connect facilities for terminating cables and for
connecting the horizontal and riser segments to each other and to
telecommunications equipment. The BDF may also support other building
information systems such CATV, alarms, security, audio, and other
telecommunications systems.
D. Whether this space is separated or combined with the building service entrance, it
is, by almost every definition, a specialized area. This room will house sensitive
electronic components that will generate heat 24 hours a day, 365 days a year and
must be cooled to maintain operating performance.
E. The air handling system for equipment rooms must be designed to provide
positive air flow and cooling even during times when the main building systems
are shut down. This may require separate air handlers and/or small stand-alone
cooling systems that are thermostatically controlled in this space. If this room is
to be used as a Area Distribution Facility (ADF), the air handling system should
be connected to the building’s backup power generation system.
A. The size of the BDF depends upon the size and variety of the equipment to be
installed and the size of the area that the room will serve.
1 The BDF must provide enough space for all planned equipment and
cables, including any environmental control equipment, power
distribution/conditioners, and uninterrupted power supply systems that
will be installed there.
2. The BDF must also provide space for access to the equipment for
maintenance and administration, and for equipment changes with minimal
disruptions.
2. A minimum of 2 feet shall be left at the end of the row of equipment bays.
A minimum of 5 feet between walls and equipment bays will allow space
for wall mounted copper cable terminations and the required 36” distance
from equipment for work space.
4. For one row of equipment bays hold the “x” dimension to 10 feet, for two
rows of equipment bays hold the “x” dimension to 16 feet, and for three
rows of equipment bays hold the “x” dimension to 22 feet.
A. The BDF must be located as close as possible to the building entrance so that it is
accessible for the delivery of large equipment.
B. The BDF must not be located in any place that may be subject to water or steam
infiltration, humidity from nearby water or steam, heat, and any other corrosive
atmospheric or environmental conditions.
C. The BDF must not be located near electrical power supply transformers, elevator
or pump motors, generators, x-ray equipment, radio transmitters, radar
transmitters, induction heating devices, and other potential sources of
electromagnetic interference.
F. The BDF must not share space in or be located near electrical closets, boiler
rooms, washrooms, janitorial closets, and storage rooms.
G. The location of the BDF must be submitted to the project manager for inclusion in
the construction drawings, and it must be annotated on the floor plan.
A. The major factors that must be considered when designing the BDF are as
follows:
3. The doors must be double doors that are 6 feet wide by 7 feet, 6 inches
tall. The doors shall be keyed to campus standards for access by
Communications Resources only. They must open outward and be
lockable. Access shall allow for future equipment changes.
4. The floor must be sealed concrete or tile to minimize dust and static
electricity.
b) The light switches must be located near the entrance of the BDF.
c) Power for the lighting must not come from the same circuits as
power for the telecommunications equipment.
7. All walls must be lined with Trade Size ¾-inch AC-grade plywood, 8 feet
high.
A. The BDF serves as the main cross-connect for riser cables and common
equipment circuits coming from the PBX, and riser cables extending to the IDFs.
Campus cables and service provider cables are also cross-connected in the BDF.
c) Electrical Specification:
(1) Be ANSI/TIA/EIA-568-A AND ISO/IEC 11801 category
5e Anixter Level 6 compliant.
(2) The following requirements shall also be met.
The distribution cabinets must be configured with jumper troughs to aid in jumper
management. The fiber distribution cabinets must be wall mounted or rack
mounted in either equipment racks or enclosed data cabinets. Reference
Specification 7 in Appendix A.
C. To facilitate changes and to minimize the lengths of patch cords, jumpers, and
equipment cables, cables of the same type must be terminated adjacent to each
other.
D. Space for terminations of each type of cable must be located on one continuous
wall or rack.
1. There must be a clear space of 5 to 6 inches above and below the top and
bottom of the connecting hardware for cabling handling.
2. There must be additional backboard space for routing cables, patch cords,
and/or cross-connects jumpers.
E. Cross-connect fields, patch panels, and active equipment in the BDF must be
placed to allow cross-connections and interconnections via jumpers, patch cords,
and equipment cables whose lengths per channel do not exceed:
2. 33 feet total for patch cords or jumpers and line cords used to connect to
the outlet.
b) Provide proper clearance from top of cable tray and HVAC ducting
or other obstacles.
c) All ladder racking must be bonded and earthed to the busbar in the
BDF.
Cabinets are equipped with 10-32 threads see associated Specs for
requirements.
A. Sleeves, slots, and conduit are used to route the cables entering and exiting the
BDF. The cross-connect points must be located near the end of the riser pathways
to minimize the need for cable routing in the BDF.
B. A sleeve is a circular opening through the ceiling or floor of a BDF that allows the
passage of cables. A slot is similar to a sleeve except that it is a rectangular
opening.
1. Sleeves and slots must be positioned near a wall on which the cables can
be supported.
3. Sleeves and slots must not be placed directly above or below the wall
space that is used for termination fields.
5. They must not be left open after cable installation and they must be
properly firestopped in accordance with applicable building codes.
6. Sleeves must extend a maximum of 4 inches above the floor level. Slots
must have a 1-inch high curb.
Table 5-1 lists the minimum number of 4-inch sleeves that must be used based on
the total square feet that the sleeves support.
Total Square Feet Quantity of Sleeves
Up to 50,000 3
50,000 to 100,000 4
100,000 to 300,000 5-8
300,000 to 500,00 9-12
Table 5-1
Table 5-2 lists the sizes of slots that are required based on the total usable area served by
the slot.
Note: The number of sleeves and/or sizes of slots must be specified prior to
construction because coring holes through concrete is expensive, it creates dust, and it
may cause water damage or create structural hazards.
An engineer registered in the State of California must approve all structural changes
and floor penetrations.
A. The following steps must be taken once the size, location, design requirements,
cross-connect and termination hardware, and support structures have been
determined for the BDF:
3
Reference: UC Davis Campus Standards & Design Guide for drawing content pages, 29, 30 & 31 dated June
2000.
The campus segment consists of the cables and structures needed to inter-connect BDFs
and area distribution frames (ADFs). It includes underground (in conduit) cables, direct
buried cables, splice boxes, manholes, pull boxes, aerial cables, pole lines, outside
terminals, and support structures. The campus segment must be designed and installed to
ANSI/EIA/TIA-758 Specifications for Outside Plant Construction.
A. This section describes the policies and procedures for the following design
activities:
A. The following steps must be taken to identify the cable routes between new
buildings and major building renovations.
3. Sketch the cable route from the starting point to the terminating point in
the buildings to be served on the campus layout map.
B. Underground (in conduit) and direct buried cable projects must be worked from
engineering drawings approved by the Manager Systems Engineering &
Development, Communications Resources. These drawings4 must include the
following information:
1. Details of typical trench cross sections showing cable and duct locations in
the trench, clearances from final grade, backfill materials and depths,
pavement cutting information, and compacting requirements for both
paved and unpaved areas.
4
Reference: UC Davis Campus Standards & Design Guide for drawing content pages, 29, 30, & 31 dated June
2000.
C. All cables entering a building must conform to the bonding and grounding
requirements listed in NEC Articles 250 and 800.
E. The minimum depth of a trench must allow 24 inches of cover from the top of the
cable to final grade. Local underground utilities must be contacted, a
Underground Service Alert (USA) call number receipt (ticket) must be present
and on site during any construction and utilities located before digging to locate
all subsurface facilities such as power, gas, water, and outdoor lighting.
Table 6-1 shows the vertical or horizontal separations that must be maintained
between telecommunications facilities and other facilities sharing a common
trench.
or
4 inches of masonry
or
Table 6-1.
Figure 6-1. Trench cross-section for underground and direct buried placement in paved
areas.
Figure 6-2: Trench cross-section for underground and direct buried placement in paved areas.
V. Cable Types
A. UC Davis recognizes two types of cable for outside use in the campus segment:
copper cable and fiber optic cable.
b) PIC cables must be marked with cable length, cable code, date and
location of manufacture, and manufacturer.
(1) PE-39 refers to filled cable with solid insulation for direct-
buried applications.
(2) PE-89 refers to filled cable with an expanded insulation for
direct-buried applications.
1. Optical fibers shall be placed inside a loose buffer tube. The nominal outer
diameter of the buffer tube shall be 3.0 mm.
3. The fibers shall not adhere to the inside of the buffer tube.
6. Buffer tubes containing fibers shall be color-coded with distinct and recognizable
colors in accordance with TIA/EIA-598-A, "Optical Fiber Cable Color Coding."
6.1. Buffer tube colored stripes shall be inlaid in the tube by means of
co-extrusion when required. The nominal stripe width shall be 1 mm.
7. For dual layer buffer tube construction cables, standard colors are used for tubes
1 through 12 and stripes are used to denote tubes 13 through 24. The color
sequence applies to tubes containing fibers only, and shall begin with the first
tube. If fillers are required, they shall be placed in the inner layer of the cable.
The tube color sequence shall start from the inside layer and progress outward.
8. In buffer tubes containing multiple fibers, the colors shall be stable across the
specified storage and operating temperature range and not subject to fading or
smearing onto each other or into the gel filling material. Colors shall not cause
fibers to stick together.
9. The buffer tubes shall be resistant to external forces and shall meet the buffer
tube cold bend and shrink back requirements of 7 CFR 1755.900.
10. Fillers may be included in the cable core to lend symmetry to the cable
cross-section where needed. Fillers shall be placed so that they do not interrupt
the consecutive positioning of the buffer tubes. In dual layer cables, any fillers
shall be placed in the inner layer. Fillers shall be nominally 3.0 mm in outer
diameter.
11. The central anti-buckling member shall consist of a dielectric, glass reinforced
plastic (GRP) rod. The purpose of the central member is to prevent buckling of
the cable. The GRP rod shall be overcoated with a black colored thermoplastic
when required to achieve dimensional sizing to accommodate buffer tubes/fillers.
12. Each buffer tube shall be filled with a non-hygroscopic, non-nutritive to fungus,
electrically non-conductive, homogenous gel. The gel shall be free from dirt and
foreign matter. The gel shall be readily removable with conventional nontoxic
solvents.
13. Buffer tubes shall be stranded around the dielectric central member using the
reverse oscillation, or "S-Z", stranding process. Water blocking yarn(s) shall be
applied longitudinally along the central member during stranding.
14. Two polyester yarn binders shall be applied contra helically with sufficient
tension to secure each buffer tube layer to the dielectric central member without
crushing the buffer tubes. The binders shall be non-hygroscopic, non-wicking
and dielectric with low shrinkage.
15. For single layer cables, a water blocking tape shall be applied longitudinally
around the outside of the stranded tubes/fillers. The tape shall be held in place by
a single polyester binder yarn. The water blocking tape shall be non-nutritive to
fungus, electrically non-conductive and homogenous. It shall also be free from
dirt and foreign matter.
16. For dual layer cables, a second (outer) layer of buffer tubes shall be stranded over
the original core to form a two-layer core. A water blocking tape shall be applied
longitudinally over both the inner and outer layer with each being held in place
with a single polyester binder yarn. The water blocking tape shall be non-
nutritive to fungus, electrically non-conductive and homogenous. It shall also be
free from dirt and foreign matter.
17. The cable shall contain at least one ripcord under the sheath for easy sheath
removal of all-dielectric cable. The cable shall contain at least one ripcord under
the inner sheath and under the steel armor for armored cable. The ripcord color
shall be orange for non-armored sheaths and yellow for armored sheaths.
19. The high tensile strength dielectric yarns shall be helically stranded evenly
around the cable core.
Figure 1
21. Armored cables shall have an inner sheath of MDPE. The minimum nominal
jacket thickness of the inner sheath shall be 1.0 mm. The inner jacket shall be
applied directly over the tensile strength members and water blocking tape. A
water blocking tape shall be applied longitudinally around the outside of the
inner jacket. The armor shall be a corrugated steel tape, plastic-coated on both
sides for corrosion resistance, and shall be applied around the outside of the
water blocking tape with an overlapping seam with the corrugations in register.
The outer jacket shall be applied over the corrugated steel tape armor. The outer
jacket shall be a MDPE with a minimum nominal jacket thickness of 1.4 mm.
The polyethylene shall contain carbon black to provide ultraviolet light
protection and shall not promote the growth of fungus. See Figure 2.
Figure 2
22. The MDPE jacket material shall be as defined by ASTM D1248, Type II, Class C
and Grades J4, E7 and E8.
23. The jacket or sheath shall be free of holes, splits, and blisters.
24. The cable jacket shall contain no metal elements and shall be of a consistent
thickness.
25. Cable jackets shall be marked with manufacturer’s name, sequential meter or foot
markings, month and year, or quarter and year of manufacture, and a
telecommunication handset symbol, as required by Section 350G of the National
Electrical Safety Code (NESC). The actual length of the cable shall be within -
0/+1% of the length markings. The print color shall be white, with the exception
that cable jackets containing one or more co-extruded white stripes shall be
printed in light blue. The height of the marking shall be approximately 2.5 mm.
25.1. The cable jacket of a cable containing two different fiber types (hybrid
construction) shall be marked to indicate quantity of each fiber type,
identity of each fiber type and the fiber sequence.
26. If the initial marking fails to meet the specified requirements (i.e., improper text
statement, color, legibility, or print interval), the cable may be remarked using a
contrasting alternate color. The numbering sequence will differ from the
previous numbering sequence, and a tag will be attached to both the outside end
of the cable and to the reel to indicate the sequence of remarking. The preferred
remarking color will be yellow, with the secondary choice being blue.
27. The maximum pulling tension shall be 2700 N (608 lbf) during installation (short
term) and 890 N (200 lbf) long term installed.
28. The shipping, storage, and operating temperature range of the cable shall be
-40°C to +70°C. The installation temperature range of the cable shall be -30°C
to +70°C.
29. Performance Single Mode:
A. Splice boxes and manholes are needed where maximum cable reel lengths are
exceeded, at the intersection of main and branch conduit runs, and at other
locations where splices are needed in a conduit system.
1. UC Davis has accepted the general sizing guidelines for splice boxes and
manholes used by Pacific Bell Telephone. These guidelines are based on
ultimate requirements.
7. The strength of concrete used for manholes must be at least 3,500 psi.
d) An entry ladder.
9. Manholes that are between 12 feet and 20 feet long must use two covers.
Manholes over 20 feet long must use three covers. All manhole covers
must be marked for easy identification (T for telephone, S for signal, and
TV for CCTV/CATV).
12. Cores into existing manholes can only be done via shop drawings
Clearly identify the methods and procedures to be used in coring. Shop
drawings for coring into manholes are to be submitted to Communications
Resources for review and comment prior to commencement of work.
2. All pull box covers must be marked for easy identification (UC Davis
Communications).
C. Aerial entrances must be limited to small buildings requiring 100 cable pairs or
less for service provider connections.
5
Reference: UC Davis Campus Standards & Design Guide for drawing content pages, 29, 30 & 31 dated June
2000.
2. Obtain necessary permits and easements for building and maintaining pole
lines.
3. Coordinate with other utilities with respect to possible joint use and to
minimize inductive interference.
4. Design the pole line for ultimate needs, taking into consideration pole line
classification, storm loading, and clearance requirements.
5. Poles must be of proper strength and length to meet the weights of cables,
wires, and strands supported by them. See Table 6 in CPUC’s Go 95 for
the proper setting depths for various pole lengths.
a) The span from the last pole to the building must not exceed 100
feet.
8. The suspension strand and cable must be placed on the road side of the
pole line.
E. For minimum clearances of wires and cables over streets, walkups, agricultural
areas, railroads, etc., see Rule 37 and Table 1 of CPUC’s GO 95.
F. Aerial cables must enter a building through a conduit with an approved service
head.
Any system installed on the UC Davis campus must conform to the NEC for electrical,
and bonding/grounding requirements. Also, buildings shall meet ANSI/TIA/EIA-607 (1994)
Commercial Building Grounding and Bonding Requirements for Telecommunications
APPENDIX A
Specifications
Specification 02 Faceplates
Specification 03 Conduit
Specification 01
Network Access Module (NAM)
Telecommunications System
Design Segment
♦ Horizontal
♦ IDF
♦ Riser
♦ BDF
♦ Campus
These specifications provide a minimum configuration that must be used when planning new construction
or major remodeling of an existing facility. Communications Resources must be consulted during the
early utilities planning phase of the project since each site may have technical requirements requiring a
modification of these specifications.
The network access module (NAM) is the connector on which the UTP cable or fiber optic cable
terminates.
1. Contact the UC Davis Line Assignor at 530-752-4598 to obtain blocks of NAM numbers for
project assignment.
2. The UC Davis Line Assignor will need to know how many Voice, Data and MATV NAM
numbers are required by the Project Consultant.
3. Pre-Assign the NAM numbers to the floor plans.
4. Prepare the NAM Matrices: see spreadsheets in appendix E.
5. Ensure that the Contractor provides a cross connect sheet (NAM Voice Matrix) which
identifies all cross connects from the NAM to the Building Distribution Frame (BDF). The
Contractor will cross connect from the BDF to the NAM one pair for each voice NAM.
6. Prepare Contract specifications that instruct the Cabling Contractor on use of and
maintenance of the NAM Matrices during the project construction.
When a surface mounted outlet is used the top of the outlet will be labeled as shown in Figure
01-2. The cable supporting a voice NAM number must be located in the top left position of the
faceplate.
Specification 02
Faceplates
Telecommunications System
Design Segment
♦ Horizontal
♦IDF
♦Riser
♦ BDF
♦Campus
These specifications provide a minimum configuration that must be used when planning new construction
or major remodeling of an existing facility. Communications Resources must be consulted during the
early utilities planning phase of the project since each site may have technical requirements requiring a
modification of these specifications.
Specification 03
Conduit
Telecommunications System
Design Segment
♦ Horizontal
♦ IDF
♦ Riser
♦ BDF
♦ Campus
These specifications provide a minimum configuration that must be used when planning new construction
or major remodeling of an existing facility. Communications Resources must be consulted during the
early utilities planning phase of the project since each site may have technical requirements requiring a
modification of these specifications.
______________________________________________________________________________
Conduit Runs
• Follow the most direct route possible with no more than two 90° bends between pull boxes.
• Contain no continuous sections longer than 100 feet. Pull boxes must be used for runs that
exceed 100 feet in length.
Conduit must not be run through areas in which flammable materials may be stored or over or
adjacent to boilers, incinerators, hot water lines, or steam lines.
Bend Radii
The radius of a conduit bend must be at least 6 to 10 times the diameter of the conduit,
depending on its size. Choose the bend radii for conduits according to the following table.
For additional information on conduit bend radius requirements and recommendations, see
specifications in ANSI/NFPA 70 and ANSI/EIA/TIA 569.
Specification 04
Horizontal Conduit Capacity
Telecommunications System
Design Segment
♦ Horizontal
♦ IDF
♦ Riser
♦ BDF
♦ Campus
These specifications provide a minimum configuration that must be used when planning new construction
or major remodeling of an existing facility. Communications Resources must be consulted during the
early utilities planning phase of the project since each site may have technical requirements requiring a
modification of these specifications.
The following chart provides guidelines used by ANSI/EIA/TIA-569 on cable capacity for
horizontal conduits that have no more than two 90° bends. The diameter of the conduit increases
incrementally as the run approaches the IDF from the furthest outlet. This chart is based on 40%
fill.
Number of Cables
Trade
Size Cable Outside Diameter
(inches) .22 .24 .29 .31 .37 .53 .62 .70
1 7 6 3 3 2 1 0 0
1¼ 12 10 6 4 3 1 1 1
1½ 16 15 7 6 4 2 1 1
2 22 20 14 12 7 4 3 2
2½ 36 30 17 14 12 6 3 3
3 50 40 20 20 17 7 6 6
3½ - - - - 22 12 7 6
4 - - - - 30 14 12 7
Specification 05
Cable Trays
Telecommunications System
Design Segment
♦ Horizontal
♦ IDF
♦ Riser
♦ BDF
♦Campus
These specifications provide a minimum configuration that must be used when planning new construction
or major remodeling of an existing facility. Communications Resources must be consulted during the
early utilities planning phase of the project since each site may have technical requirements requiring a
modification of these specifications.
• Cable trays must be solid bottom, aluminum trays or corrugated ventilated trays. They must
be 18 inches wide and at least 6 inches deep. Smaller buildings and secondary tray sections
serving fewer than 25 work areas may utilize a 12-inch wide tray.
• Cable trays must be secured on 10-foot centers using a single center-mounted steel
supporting rod and bottom "T" connector, angled wall supports, or a standard trapeze type
support system.
• Cable trays must meet Zone 3 seismic bracing standards.
• Cable trays will be used only over areas with ceiling access and must transition to a
minimum of three 4-inch conduits when routed over fixed ceiling spaces that are longer than
15 feet.
• Cable trays must be bonded end-to-end.
• Cable trays must extend 6 inches into the IDF then utilize a drop out to protect station cables
from potential damage from the end of the tray.
• All cable tray penetrations through firewalls must allow cable installers to fire-seal around
the cables after they are installed. Tray-based mechanical firestop systems will be used when
a cable tray must penetrate a fire barrier.
• Cable trays will not be placed within 5 inches of any overhead light fixture and within 12
inches of any electrical ballast. A minimum clearance of 12 inches above the cable tray must
be maintained at all times. All bends and T-joints in the cable trays must be fully accessible
from above (within one foot).
• Cable trays must be mounted no higher than 12 feet above the finished floor, and must not
extend more than 8 feet over a fixed ceiling area.
Specification 06
Color Codes for Cross Connect Fields
Telecommunications System
Design Segment
♦ Horizontal
♦ IDF
♦ Riser
♦ BDF
♦Campus
These specifications provide a minimum configuration that must be used when planning new construction
or major remodeling of an existing facility. Communications Resources must be consulted during the
early utilities planning phase of the project since each site may have technical requirements requiring a
modification of these specifications.
The following color codes for cross connect fields must be used to identify horizontal and riser
cables.
Specification 07
Distribution Cabinets
Telecommunications System
Design Segment
♦ Horizontal
♦ IDF
♦Riser
♦ BDF
♦Campus
These specifications provide a minimum configuration that must be used when planning new construction
or major remodeling of an existing facility. Communications Resources must be consulted during the
early utilities planning phase of the project since each site may have technical requirements requiring a
modification of these specifications.
UC Davis recognizes five types of distribution cabinets for use in the IDFs:
Type 1, Type 2, Type 3, Type 3A, 3L, 3B and Type 3R. The type of cabinet used depends on the
network electronics and termination hardware housed in them, and the number of work areas
they serve. The following chart lists the types of distribution cabinets and when each must be
used.
• for indoor use, except the Type 3R, as an equipment safeguard against
dust, filling dirt, non-corrosive liquids, and pedestrian traffic in congested
locations,
• for UL/NEMA 2 specifications in the IDFs and BDF with locked doors,
• so the sides of the frame will be open in cases where they must be joined
with additional enclosures,
• with solid sides to close the end panels of single or joined enclosures,
• with solid top panels, or top panels equipped with fans. In some cases,
side-mount or top-mount air conditioning units may be required,
• with a top mounted fan, approximately 535 CFM, 115 VAC. The fan must
include finger guards and power cord,
• with a solid bottom panel, 16 gauge, zinc plate to enclose the bottom of the
cabinet and secure it,
• with the doors to be solid, hinged on the left, and easily changed to hinge
on the right. Two door configurations must be hinged on their respective
sides,
• with handles which can be locked with a key. Keys will be common for all
cabinet types, See CR for Key Code.
• and come equipped with ANSI/EIA RS-310-D drillings. Holes for internal
mountings must be 10-32 tapped. Extra screws and miscellaneous
hardware for future maintenance requirements must be included. Each
rack angle assembly must be adjustable in depth, so that there is a
minimum of 6 inches of clearance between the closed door and the face of
any installed panel,
• cables can enter the cabinets either from the top or the bottom. Provision
for cable entry knockouts are required in all designs. 2-inch trade size,
T&B XTRAFLEX liquidtite nonmetallic conduit, equipped with
XTRAFLEX must be used. All plastic connectors, both 90° and/or 45°
angles for bringing cables into the cabinets must be used, plastic bushing
must be installed on end of conduit to protect cable,
All cabinets are designed to accommodate standard 19-inch rack mountable equipment.
A dedicated 20 AMP circuit with a four-plex outlet must be located near each cabinet.
The cabinets must have the following dimensions:
Note: Overall height of all standing cabinets must not exceed 84 inches.
ADF Cabinet: ADF cabinets are used only in Area Distribution Frame locations. Planning for
a new ADF must be coordinated with Communications Resources Department Systems
Engineering & Development Unit.
The IDF Type 3 wall unit must be designed to house electronic and electrical components with
appropriately placed knockouts for cable entries. A design providing for 90° pivoting must be
provided. This feature must allow access to the rear of the enclosure for future maintenance
requirements. The hinged component of the wall-mounted cabinet must support equipment
weights up to 100 pounds.
The Type 3A is not a cabinet. It defines wall mounted components on a 4’X8’ of wall space.
Type 3B:
The Type 3B must be designed for wall mounting. It is typically used in lieu of a type 3 when
there is not 24 inches of depth available. It must include its own mounting apparatus and does
not require a mounting platform. The IDF Type 3B must be designed to house electrical
components with appropriately placed knockouts for cable entries. Construction of the IDF Type
3B must include the following features:
Type 3L
The "Type 3L" IDF closet, also referred to the "labcab," has the same architectural
limitation imposed on all "Type 3" cabinets. The maximum number of NAMs that a
"Type 3L" cabinet will support is 48. In addition, this configuration is applied where
local wiring may only extend to within the same room as the cabinet. Typical
All "Type 3L" cabinets will house the networking components in a cabinet structure for
security and management purposes. The UC Davis policy dictates that the networking
electronics shall be housed in a secure cabinet when co-located with any other equipment
not related to communications. The closet shall have a ¾ inch plywood wall that is at
least 3 feet by 4 feet. A ground from the TMBG shall be used on all Type 3L cabinets.
Type 3R:
The Type 3R Outside Plant external enclosure is used to house telephone, data and video
system patch panels, and equipment. The enclosure shall be water and gas tight (when
sealed) and shall be provided with a built-in heating and cooling unit to maintain
consistent temperatures within the enclosure at all times.
The entire enclosure shall meet NEMA type 3R, 4X and Bellcore TA-NWT-000487,
Newton 7101, part number 2143990079, and shall be constructed of steel or aluminum
panels a minimum of 1/8” thick, powder coat painted for exposed conditions. It shall be
fitted with lifting eyebolts.
All exterior seams shall be made weather tight with a silicone sealant.
The doors shall have a three point latching mechanism, external vandal resistant door
handle, provision to mount padlocks, and each door shall have grounding straps. All
doors shall be fitted with a documentation pocket, all external doors shall have Bellcore
quarter turn style door locks.
Overall dimension are not to exceed 63” (H) x 56” (W) x 46” (D).
Provide all mounting components and accessories and securely fix enclosure to concrete
pad. Connect built-in heating and cooling systems, and power strip, to electrical system.
Provide strain relief and cable management inside the enclosure to ensure tidy routing of
all cables.
The enclosure shall consist of three chambers, communications cable entry chamber,
electrical chamber, (including a built in heat exchanger) and communications chamber
(central chamber). Each chamber to have it’s own chamber ground bus.
Specification 08
Conduit Fill for Riser Cables
Telecommunications System
Design Segment
♦Horizontal
♦ IDF
♦ Riser
♦ BDF
♦Campus
These specifications provide a minimum configuration that must be used when planning new construction
or major remodeling of an existing facility. Communications Resources must be consulted during the
early utilities planning phase of the project since each site may have technical requirements requiring a
modification of these specifications.
This table shows the conduit fill ratio requirements for riser cables. The number of cables, which
can be installed, is actually limited by the allowed maximum pulling tension of the cables. This
fill ratio requirement does not apply to sleeves and conduit runs without bends and under 50 feet.
Internal diameters are taken from the manufacturing standard for electric metallic tubing and
rigid metal conduit.
Specification 09
Pull Boxes
Telecommunications System
Design Segment
♦ Horizontal
♦ IDF
♦ Riser
♦ BDF
♦Campus
These specifications provide a minimum configuration that must be used when planning new construction
or major remodeling of an existing facility. Communications Resources must be consulted during the
early utilities planning phase of the project since each site may have technical requirements requiring a
modification of these specifications.
Pull boxes must be installed in easily accessible locations. A pull box may be
placed in an interstitial ceiling space only if it is listed for that purpose and it is
placed above a suitable marked, removable ceiling panel.
For horizontal cable, the width and depth of the pull box must be adequate for fishing,
pulling, and looping the cable. The length must be 12 times the diameter of the largest
conduit.
Use the table below to select the proper size of pull box.
Specification 10
Conduit for Underground Cabling
Telecommunications System
Design Segment
♦ Horizontal
♦ IDF
♦ Riser
♦ BDF
♦Campus
These specifications provide a minimum configuration that must be used when planning new construction
or major remodeling of an existing facility. Communications Resources must be consulted during the
early utilities planning phase of the project since each site may have technical requirements requiring a
modification of these specifications.
• Conduit stubs entering the building must extend beyond the foundation
landscaping. All conduit ends adjacent to the building must be flagged for
easy identification.
• Conduit entering from a below grade point must extend 4 inches above the
finished floor in the BDF. Conduit entering from ceiling height must
terminate 4 inches below the finished ceiling.
• All metallic conduit and sleeves must be reamed, bushed, and capped
when placed.
• The top of the conduit must be buried at least 24 inches below the ground
surface. Warning tape equipped with a metallic tracer shall be placed 18-
inches above top of conduit bank.
• The area around the conduit entrance must be free of any construction,
storage, or mechanical apparatus.
• There must be no more than two 90° bends between pulling points on all
entrance cables.
• All bends must be long, sweeping bends with a radius not less than 6 times
the internal diameter of conduits 2 inches or smaller, or 10 times the
internal diameter of conduits larger than 2 inches.
• Conduit must be positioned on the field side of the poles (the side that is
protected from the normal flow of traffic).
Note: Two spare 4-inch conduits must be brought into every building in addition to the quantities
specified above.
Specification 11
Electrical Protection, Bonding/Earthing
Telecommunications System
Design Segment
♦ Horizontal
♦ IDF
♦ Riser
♦ BDF
♦ Campus
These specifications provide a minimum configuration that must be used when planning new construction
or major remodeling of an existing facility. Communications Resources must be consulted during the
early utilities planning phase of the project since each site may have technical requirements requiring a
modification of these specifications.
Electrical protection must be provided for cables that are subject to lightning, power contact,
ground potential rise, or induction. The minimum protection is a tri-element gas module device.
Cables exposed to power sources must be provided with sneak current protectors which will
protect cables against voltage and power surges by interrupting the current or by grounding the
conductors.
Ground systems must conform to the NEC specifications. Approved ground systems are:
• ground ring (20 feet or more of bare copper wire in direct contact with the
earth-it encircles the building)
Equipment single point grounds must be grounded to the building grounding systems as
defined in ANSI/TIA/EIA-607 (1994) Commercial Building Grounding and Bonding Requirements
for Telecommunications
Riser cables must be grounded at the point of origination and at any floor in which pairs leave
the cable sheath. Riser cable sheaths must be bonded to approved grounds in the IDFs and the
BDF.
Cable sheaths of cables entering a building must be bonded to an approved ground at the
building entrance location.
Protector panels will be wired to an approved ground by the straightest and shortest means.
Bonding conductors are not intended to carry electrical load currents under normal conditions,
but must carry fault currents so that electrical protection (circuit breakers) will properly operate.
A #6 AWG copper conductor will be used to bond the communications components to the
ground. A larger conductor will be used if the ground source exceeds 5 ohms.
The electrical contractor must provide access to a bonding connection at the electrical service
ground during new construction (NEC 250-71(b)). A telecommunications main grounding
busbar (TMGB) must be specified in the BDF with an approved ground connector back to the
electrical service ground point.
A telecommunications grounding busbar (TGB) must be specified for each IDF in the building.
Each TGB will have a #6 AWG conductor back to the TMGB.
In a renovation or remodeling project where a suitable ground to the electrical service ground is
not available, a grounding electrode will be installed in accordance with the NEC Section 250-
83. Note: a metallic water pipe connected to a utility water distribution system is no longer the
first choice for a grounding electrode. The NEC recommends the that a ½ inch diameter, 5 foot
ground rod be used.
Communications bonding relies on short direct paths that have minimum resistive and inductive
impedance:
APPENDIX B
Reference Materials
Customer-owned OSP cabling extends between separated structures including the terminating
connecting hardware at or within the structures. The OSP pathway includes the pathway through
the point of entry into the building space. Customer-owned OSP pathways may include aerial,
direct-buried, underground (e.g., duct), and tunnel distribution techniques. Customer-owned OSP
pathways and spaces specified by this Standard are intended to have a useful life in excess of
forty (40) years.
The OSP cabling specified by this Standard is intended to support a wide range of applications
(e.g., voice, data, video, alarms, environmental control, security, audio, etc.) on commercial,
industrial, institutional and residential sites. The customer-owned OSP cabling specified by this
Standard is intended to have a useful life in excess of thirty (30) years.
Underwriters Laboratories (UL), LAN Cable Certification Program. Test products to verify
that performance meets or exceeds industry standards. The UL tests the electrical shock, flame
spread, and smoke production characteristics of cables. The UL also tests cables for
transmission properties.
National Electrical Code (NEC) Sections 250 and 800, provide a set of codes governing items
such as voltage limits, transmission media conductor size, overvoltage protection requirements,
fire resistance of cables, and cabling methods. It is important to check with local governing
bodies to determine if their codes supersede the NEC articles.
Copies of the ANSI/EIA/TIA industry standards may be purchased from Global Professional
Publications, 15 Inverness Way East, Englewood, Colorado 80112- 5776, (800) 854-7179 or
(714) 261-1455.
BICSI TDM and CO-OSP Manuals can be purchased from BICSI, 10500 University Center
Drive, Suite 100, Tampa, Florida, 33612-6415, (800) 242-7405.
NEC book can be obtained through the National Fire Protection Association (NFPA),
Batterymarch Park, Quincy, MA 02269, (617) 770-3000
UL LAN Cable Certification Program publication is available from UL, Literature Stock, 333
Pfingsten Road, Northbrook, IL 60062-2096, (708) 272-8800 ext. 43731.
California Public Utilities Commission, 505 Van Ness Avenue, San Francisco, CA, (415) 703-
1170.
APPENDIX C
Glossary
American Wire The standard gauge for measuring the diameter of copper,
Gauge (AWG) aluminum, and other conductors.
Approved Ground Grounds that meet National Electric Code (NEC) requirements
such as building steel, ground rings, and other devices.
Bend Radius The radius a fiber can bend before the risk of breakage or
increase in attenuation.
Buffer Tubes Loose fitting covers over optical fibers used for protection and
isolation.
Cable Assembly An optical fiber cable that has connectors installed on one or
both ends. General use of these cable assemblies includes the
optoelectronic equipment and interconnection of multi-mode
and single mode optical fiber cable systems. If connectors are
attached to only one end of the cable, the cable assembly is a
pigtail. If connectors are attached to both ends, it is a jumper.
Cable Bend Radius Cable bend radius during installation implies that the cable is
experiencing a tensile load. Free bend implies a lower
allowable bend radius since it is at a condition of no load.
Cable Tray The portion of the pathway system that permits the placing of
main or high volume cables between the entrance location and
all cross-connect points within a building and between
buildings.
A ladder, trough, solid-bottom or channel raceway system
intended for, but not limited to, the support of
telecommunications media.
Ceiling Distribution A distribution system that uses the space between a suspended
System or false ceiling and the structural surface above the ceiling.
Core Area The area within a building that contains usable space for
elevators, power cables, and telecommunications cables.
Demarcation Point A point at which two services may interface and identify the
(DEMARC) division of responsibility.
Direct Buried Cable A cable installed under the surface of the ground (not in
conduit) in such a manner that it cannot be removed without
disturbing the soil.
Distribution Panel A wiring board that provides a patch panel function and
mounts either in a rack or on a wall.
Drop Ceiling A ceiling that creates an area or space between the ceiling
material and the structure above the material.
Entrance Facility An entrance to a building for both public and private network
service cables (including antennae) including the entrance
point at the building wall and continuing to the entrance room
or space.
Fire Rating System The time in hours (or fractions of hours) that:
Fire Wall A wall that helps to prevent fire spreading from one container
or area to another and that runs from structural floor to
structural ceiling.
Floor Slab The upper part of a reinforced concrete floor carried on beams
below the slab.
A concrete mat poured on sub-grade serving as a floor rather
than as a structural member.
Furniture System Furniture walls combined with furniture units such as desks,
work surfaces, file cabinets, etc.
Main Cross-Connect The cross-connect in the main equipment room for connecting
entrance cables, riser cables, and equipment cables.
Patch Cord A short length of wire or fiber cable with connectors on each
end used to join communications circuits at a crosscurrent.
Plenum An air duct inside buildings through which cable can be pulled
or housed.
Power Pole A raceway placed between the ceiling and floor in conjunction
with ceiling distribution systems. It is used for the
concealment of telecommunications and electrical wiring from
the ceiling space to the work area.
Protector (Ground A wire runs from the ground lug on the protector to an
Conductor) approved ground via the shortest and straightest route. Limit
this wire to 3.28 feet in length and do not pass it within 5.9
Protector (Open An outside plant protector that limits the voltage between
Wire) telecommunications conductors and the ground. Open wire
protectors are equipped with either 10- or 20-mil carbon
electrodes. Typical open wire protectors limit voltage up to
1,250V DC.
Pull Cord Cord placed within a raceway and used to pull cable through
the raceway.
Pull Strength The maximum pulling force that can be safely applied to a
cable or raceway without damage.
Riser Cabling The cabling that distributes from the entrance facility to the
equipment room, intermediate distribution frames, and
between buildings.
Sheath (Cable) Loop A type of loop diversity that assigns circuits among different
Diversity sheaths or cables.
Single-mode Fiber An optical wave guide (or fiber) in which the signal travels in
one “mode”. The fiber has a small core diameter.
Sneak Current The use of devices to protect against sneak currents either by
Protection interrupting the current (sneak current fuses) or grounding the
conductor (heat coils).
Tight Buffer A cable construction where each glass fiber is tightly buffered
by a protective thermoplastic coating to a diameter of 900
microns. High tensile strength rating is achieved providing
durability, ease of handling, and ease of connectivity.
Trench A narrow furrow dug into the earth for the direct installation of
buried cable or for the installation of troughs or ducts. The
trench is refilled with soil or covers the direct buried cable,
trough, or duct.
APPENDIX D
UC Davis Policy and Procedure Manual, Section 310-10
Note: At the time of this update to the Communications Resources Cabling Standards, the
campus telecommunications Policy and Procedure is scheduled for revision. Check the
http://www.mrak.ucdavis.edu/web-mans/ppm/310/310-10.htm web page for the up to date
version.
APPENDIX E
NAM MATRICES:
VOICE NAM MATRIX
Bldg:
CAAN:
Zone:
Bldg:
CAAN:
Zone:
Bldg:
CAAN:
Zone:
APPENDIX F
SUPPORTING STANDARDS FOR IN-BUILDING RADIO COMMUNICATION
SYSTEM AMPLIFICATION
1.0 Purpose.
This purpose of this document is to establish the policies and procedures regarding the needs assessment,
specifications, type, cost evaluation, testing and acceptance of an in-building radio system required in new campus
buildings.
All buildings require the capability to support radio communications of the local public safety entities (Fire, Police
etc.) Since each building is unique in its location, construction, and interior design, this document provides
guidance in support of the formal Radio System Coverage Evaluation / In-Building Radio Communication Systems
which requires consideration of funding appropriations for specific radio system coverage of each newly constructed
facility and/or consideration for existing facilities that may be impacted by the new construction. In many cases, a
placeholder is to be used for in-building amplification costs; based on historical data, a recommendation of $35,000
should be used for capital projects exceeding 5000 square feet or multi-level structures. (Refine estimate during cost
evaluation)
2.1 Definitions.
6
The California Governor’s Office of Emergency Services (OES) Auxiliary
Communications Service (ACS) uses a "circuit merit" rating as a reporting
system for transmission quality.
CM5 = Completely clear, each word fully understood.
CM4 = Clear with slight amount of static and or interference.
Each word is understood.
CM3 = Static and or interference present, but the bulk of the
transmission is understood without having to be repeated. Deemed
to be the margin of acceptable, professional communication.
CM2 = Static and interference are prevalent and words are missing.
Fiber Optic – Optical transport of radio signals over fiber optic cable.
Off – Air Repeater – A repeater that receives frequencies from and antenna and amplifies and
retransmits these frequencies.
NPSPAC – National Public Safety planning and Advisory Committee
FCC – Federal Communications Commission
Except as otherwise provided, no person shall, erect, construct, change the use of or provide an addition of more
than 20% to, any building or structure or any part thereof, or cause the same to be done which fails to support
adequate radio coverage for the clients of the University of California, Davis 800 MHz Trunked Communications
System, (including but not limited to Firefighters, Police Officers, or Emergency Response Personnel). For purposed
of this section, adequate radio coverage shall include all of the following:
• A minimum signal strength of -95 dBm available in 95% of the area of each floor of the building or
structure when transmitted from the campus Central Transceiver of the University of California, Davis 800
MHz Trunked Communications System; 7
• A minimum signal strength of -95 dBm received at the campus Central Transceiver of the University of
California, Davis 800 MHz Trunked Communications System when transmitted from 95% of the area of
each floor of the building;
• The frequency range which must be supported shall be 821-823 MHz and 866-868 MHz; and
Buildings and structures which cannot support the required level of radio coverage shall be equipped with either (A)
an internal multiple antenna system with or without FCC type accepted bi-directional 800 MHz amplifiers as needed
or (B) radiating cable system (leaky coax). If any part of the installed system or systems contains an electrically
powered component, the system shall be capable of operating on an independent battery and/or generator system for
a period of at least twelve (12) hours without external power input. The battery system shall automatically charge in
the presence of an external power input. If used, bi-directional amplifiers shall include filters to reduce adjacent
frequency interference at least 35 dB below the NPSPAC band. The filters shall be tuned to 825 MHz and to 870
MHz so that they will be 35 dB below the NPSPAC frequencies of 824 MHz and 869 MHz respectively. Other
settings may be used provided that they don't attenuate the NPSPAC frequencies and further provided that they are
not more than one MHz from the NPSPAC frequencies.
5.0 Evaluation Process.
CM1 = Signal is barely evident and the words are not understandable.
CM0 = Nothing heard
7
When measuring the performance of a bi-directional amplifier, signal strength measurements are based on one
input signal adequate to obtain a maximum continuous operating output level.
The evaluation process for determining the need for in-building amplification is conducted in a minimum
of three phases: Pre-construction, construction, and acceptance/implementation.
Before the construction of the new building, basic information can be gathered to begin the process of
determining the need, type and actual implementation of augmentation to the radio system. In most
cases, the following information must be known to properly design and cost estimate an in-building
radio system.
With the information above, the following steps can establish determining the potential need for an in-
building radio system.
• If the signal strength of the donor is –95 dBm or less on the outside of the building, the
probability of additional in-building coverage is high.
• If the signal strength of the donor is greater than –95 dBm, determine the expected signal
strength of the donor by subtracting the sum of the interior losses due to walls, doors and
windows from the ambient signal outside the building. (See Table 1)
• If a signal strength of -95 dBm or greater is calculated at the inner most point of the
building, an in building system may not be required.
• If the signal strength is calculated at –95 dBm or less, an in-building system is warranted.
• To determine signal strengths for specific areas on campus and evaluate the impact of the
facility on existing structures, consult the latest UC Davis Outdoor RF Survey report.
• If determined that In-building amplification is required for either the proposed site or
existing structures impacted by the proposed construction, provide placeholder in budget
for cost of communication system based on results of the above.
As the construction progresses, refinements to the placeholder budget should be made to ensure adequate funds
are available to cover the cost of providing in-building amplification to the new facility and to re-
evaluate the impact on existing structures. Re-visiting the specifications from the initial evaluation will
fine-tune the proposed cost line item.
Using criteria from Section 7, the Project Manager will accept the In-Building amplification
measurements, ensuring they are within design specification. The budget line item may be closed out
upon final acceptance.
Once a determination has been made that in-building amplification is required for the proposed facility or as an
augmentation to existing facilities impacted by the new facility, cost estimating an in building coverage system is
mostly an academic process. The first step in this process is to determine if the system should be fiber based or an
Off- air system. Each system has it own unique advantages and disadvantages. (Table 2 identifies several cost
considerations that may be quantified in the planning stage)
Request for Survey and Proposal (RFSP) should be created to provide to multiple wireless system
vendors. The format of the RFP can be mandated or left open to each vendor. However, the RFSP
should at the minimum include the following sections:
3
NOTE: Radiating cable is typically used in narrow spaces such as tunnels and hallways. This is due the high
coupling loss between the radiating cable and subscriber unit. As well, radiating cable has limited propagation and
poor wall penetration characteristics.
The RFSP should clearly state the areas where coverage is needed, the grade of service expected
(GOS), and construction schedule of the building in process. Additionally, the RFP should include the
information gathered in the pre-construction assessment phase of this policy.
Once implemented, the RF coverage system should be tested via the pre-determined Acceptance Test Plan
(ATP). The ATP should include personnel from Information and Educational Technology, Police,
Fire, Safety and Vendor. A walk through test should be completed and any discrepancies noted and
resolved by the vendor.
When an in-building radio system is required, and upon completion of project installation, it will be the Project
Manager’s responsibility to have the radio system tested to ensure that two-way coverage on each floor of the
building are within General policy requirements as prescribed below:
• Each floor of the building shall be divided into a grid of approximately twenty (20) equal areas.
• The test shall be conducted using a Motorola MTS 2000, or equivalent, portable radio, talking
through the campus Central Transceiver of the University of California, Davis 800 MHz Trunked
Communications System.
o A spot located approximately in the center of a grid area will be selected for the test.
o The radio will be keyed to verify two-way communications to and from the outside of the
building through the campus Central Transceiver.
o Once the spot has been selected, prospecting for a better spot within the grid area will not
be permitted.
• Each grid area will be tested for transmission/reception; minimum signal strength of –95 dBm. If
signal strength fails to meet the requirement, the grid area shall be marked as a fail.
• A maximum of two (2) nonadjacent areas will be allowed to fail the test. In the event that three (3)
of the areas fail the test, in order to be more statistically accurate, the floor may be divided into
forty (40) equal areas.
o In such event, a maximum of four (4) nonadjacent areas will be allowed to fail the test.
o After the forty (40)-area test, if the system continues to fail, the project Manager shall
have the system altered to meet the 95% coverage requirement.
The gain values of all amplifiers shall be measured and the test measurement results shall be kept on file
with Communications Resources, a Division of Information and Educational Technology, so that
the measurements can be verified each year during the annual tests. In the event that the
measurement results became lost, the building owner will be required to rerun the acceptance test
to reestablish, the gain values.
Communications Resources will periodically test in-building amplification systems. Results of the testing will be
compared to designed specifications and corrective action taken if required maintaining the system within the
desired design specification.
4
Overall project management of the implementation of an in building coverage system should be offered and
included in the turnkey proposal submitted.
Communications Resources shall be responsible for conducting or contracting system testing. All tests
shall be conducted, documented and signed by a person in possession of a current FCC license, or a
current technician certification issued by the Associated Public-Safety Communications Officials
International (APCO) or the Personal Communications Industry Association (PCIA). All test records
shall be retained on the inspected premises and a copy submitted to Communications Resources and to
the Police/Fire Department officials.
At the discretion of Communications Resources, but no less than semi-annually, the campus shall
conduct an Outdoor RF Survey mapping the campus footprint for RF energy. The report should
specify specific frequencies, coverage with relative signal strength highlight those areas of signal
strength below standards.
8.3 Annual Tests.
When an in-building radio system are installed, Communications Resources shall test all active
components of the system, including but not limited to amplifiers, power supplies and backup
batteries, a minimum of once every twelve (12) months. Amplifiers shall be tested to ensure that the
gain is the same as it was upon initial installation and acceptance. Backup batteries and power supplies
shall be tested under load for a period of one (1) hour to verify that, they will properly operate during
an actual power outage. If within the one (1) hour test period, in the opinion of the testing technician,
the battery exhibits symptoms of failure, the test shall be extended for additional one (1) hour periods
until the /testing technician confirms the integrity of the battery. All other active components shall be
checked to determine that they are operating within the manufacturer's specifications for the intended
purpose.
8.4 Five-Year Tests.
In addition to the annual test, Communications Resources shall perform a radio coverage test a
minimum of once every five (5) years to ensure that the radio system continues to meet the
requirements of the original acceptance test. The procedure set forth above shall apply to such tests.
Police and fire personnel, after providing reasonable notice to Communications Resources, shall have
the right to enter property to conduct field-testing to be certain that the required level of radio
coverage is present. Discrepancies from field-testing and recorded tests shall immediately be brought
to the attention of Communications Resources. Communications Resources will provide corrective
action in response to reported discrepancies.
Machinery 1-4
3-6
Light machinery 5-10
Metallic Hoppers 10-15
General Machinery (10-20 sq ft)
Heavy Machinery (>20 sq ft)
Inventory 3-5
3-6
Light Textile 4-7
Empty Cardboard 8 -11
Metal Inventory
Heavy Textile
COST
ITEM