Partes Allen Bradley de Contactores
Partes Allen Bradley de Contactores
Description Bulletin 509 starters are designed for full voltage voltage starting of
polyphase squirrel cage motors. These starters meet NEMA standards, are
easy to wire and service, simple to select, and offer Class 10, 15, 20, and 30
overload protection in the complete range of NEMA sizes 00 to 9.
All Bulletin 509 starters are available with Bulletin 592 eutectic alloy
overload relays as well as Smart Motor Protectors (SMPs) -- Solid-state
Overloads for additional flexibility in motor protection.
Contacts 3B 3C 16
12
9
6 3E
11
3D
1 3A
10
8
15 3F 3
7
4
13C
Sizes 3
2
and 4 only.
14
13 13D
14A
5
Size 5 only.
17
13B 17A
J Heater Element 13A 13E
Type J or W (Specify)
2
Renewal Parts
Bulletin 509, Sizes 0 through 4 (all series)
Size 5 (series L)
Renewal Parts
Size 0 Size 1 Size 2 Size 3 Size 4 Size 5 (Series L)Ê
Item Description of Renewal Parts
Part No. Part No. Part No. Part No. Part No. Part No.
1 Contact Block Cover 40410-499-01 40410-499-02 40420-499-01 40430-457-51 40440-456-51 42450-800-01
Movable Contact Support and Armature 40410-498-01 Series A
2Ë 40420-498-01 40430-452-51 40440-453-51 42450-801-01
Assembly 40410-498-03 Series B
3Ë Stationary Contact Block and Base Assembly 40410-494-03 40410-494-04 40420-495-02 40430-462-52 40440-462-52 42450-307-62
3A Saddle Clamp Assembly (for size 0 and 1) X-225492 — — — —
3B Lug — — X-316012 40430-461-51 40440-461-51 42450-804-01
3C Bolt — — M-6289 M-6532 M-6834 —
3D Front Terminal without Contact 40430-022-02 40440-030-02 42450-302-52
3E Rear Terminal without Contact Ì Ì Ì 40430-024-02 40440-314-51 40440-314-51
3F Front/Rear Terminal Screw 28168-107-26 28168-502-26 Í
4 Coil Cover 40410-496-01 40420-497-01 40430-454-51 40440-454-51 42450-803-01
5 Tie Point Terminal 599-TP02 599-TP34
6 Auxiliary Contact Block (refer to page 14) J 595-A (used as hold-in contact)
7 Operating Coil See Table on page 4
8 Yoke (50-- 60 Hz) J 40410-497-01 J 40410-497-02 J 40430-455-51 J 40440-458-51
9 Movable Contact
10 Contact Spring
Order Single Pole Contact Set
11 Front Stationary Contact
12 Rear Stationary Contact
Single Pole Contact Set (includes (1) each
9-- 12 J 40410-331-51 J 40410-331-52 J 40420-322-51 J 40430-300-51 J 40440-300-51 J 42450-805-01
item 9-- 12)
Eutectic Alloy Overload Relay (includes item
13 42185-800-01 40185-800-01 40185-801-01 40185-802-01 J 592-B0V16Î
13B test module)
13A Eutectic Alloy Heater Element Screw M-1552 —
Test Module (included with item 13 overload
13B 40185-499-01 40430-459-51 42450-807-01
relay)
Overload Relay Auxiliary Contact
13C — J 595-A34 Ï —
(included with item 13)
13D Overload Mounting Plate — — — 40430-045-02 40440-028-02 42450-028-02
13E Jumper — — — — — 42195-800-01
Smart Motor Protection (SMP) Solid-state
14 See Table on page 5
Overload Relay
14A SMP Reset Bar Only (SMP-1, SMP-2) 40794-011-01
15 Mtg. Screw w/Washer (3 req’d) 28169-100-26 28169-101-26 40430-460-51 40440-459-51Î
Mounting Plate for Eutectic Alloy, SMP-1ä,
40410-124-02 40420-083-02
16 SMP-2ä Ð 40430-044-02 40440-027-02
Mounting Plate for SMP-3ä Ð 40794-031-02 40794-032-02
17 Current Transformer — — — — — X-241563Î
17A Transformer Spring — — — — — 42450-806-01Î
3
Renewal Parts
Bulletin 509, Sizes 0 through 4 (all series)
Size 5 (series L)
J Operating Coils
Coil No.
AC Volts Hz Size 5
Size 0- 1 Size 2 Size 3 Size 4
Series LÊ
24 60 CB013 CC013 CD013 — —
115-- 120 60 AF236
CB236 CC236 CD236 CE236
110 50 AF236
110-- 115 50 CB322 CC322 CD322 CE322 AF322
200-- 208 60 CB249 CC249 CD249 CE249 AF249
220-- 230 50 CB339 CC339 CD339 CE339 AF339
60 CB254 CC254 CD254 CE254 AF254
230-- 240
50 CB342 CC342 CD342 CE342 AF342
277 60 CB260 CC260 CD260 CE260 AF260
380 50 CB354 CC354 CD354 CE354 AF354
415 50 CB357 CC357 CD357 CE357 AF357
440-- 460 50 CB360 CC360 CD360 CE360 AF360
460-- 480 60 CB273 CC273 CD273 CE273 AF273
500 50 CB364 CC364 CD364 CE364 AF364
575-- 600 60 CB278 CC278 CD278 CE278 AF278
Coil Data
Contactor
or
No. Voltamperes Burden for 60 Hz CoilsË
Starter
Size of
Poles
Motor 24 Volts 115- 120 Volts 200- 208 Volts 230- 240 Volts 460- 480 Volts 575- 600 Volts
Load Inrush Sealed Inrush Sealed Inrush Sealed Inrush Sealed Inrush Sealed Inrush Sealed
0 2-- 5 192 29 192 29 192 29 192 29 192 29 192 29
1 2-- 5 192 29 192 29 192 29 192 29 192 29 192 29
2 2-- 3 240 29 240 29 240 29 240 29 240 29 240 29
2 4-- 5 315 38 315 38 315 38 315 38 315 38 315 38
3 2-- 3 660 45 660 45 660 45 660 45 660 45 660 45
3 4-- 5 840 58 840 58 840 58 840 58 840 58 840 88
4 2-- 3 — — 1225 69 1225 69 1225 69 1225 69 1225 69
4 4-- 5 — — 1490 96 1490 96 1490 96 1490 96 1490 96
5
2-- 3 — — 1490 96 1490 96 1490 96 1490 96 1490 96
(Series L)
Ë For 50 Hz coils, consult your nearest Allen-Bradley Sales Office.
4
Renewal Parts
Bulletin 509, Sizes 0 through 4 (all series)
Size 5 (series L)
5
Renewal Parts
Bulletin 509, Sizes 0 through 4 (all series)
Size 5 (series L)
Ê For NEMA starters sizes 0-- 2, a new mounting plate is required for retrofit to existing Bulletin 509 starters. For sizes 0-- 1 starters, order Part No. 40410-124-02 and for size 2
starters, order Part No. 40420-083-02.
Ë Allen-Bradley recommends using 120 or 240 V AC coils on all SMP-3 NEMA starters. When using coil voltages other than 120 or 240 V AC, consult your nearest Allen-Bradley
Sales Office.
Ì The ratings of the triacs and the hard output contact (relay) internal to the SMP-3 must not be exceeded. See the SMP-3 User’s Manual for actual ratings.
Í This SMP-3 overload relay has an interposing relay with a 120 V AC coil.
6
Renewal Parts
Bulletin 509, Sizes 0 through 4 (all series)
Size 5 (series L)
Disassembly
ATTENTION: To prevent electrical shock, disconnect from
Replacing Contacts When severe contact wear is evidenced, it is recommended that all contacts
be replaced, which will guard against uneven contact closings. Be sure to
check contact spring flexibility and replace if necessary. Order the required
number of single pole contact sets from the part listings on Page 3. Follow
steps 1--5 under Disassembly.
Note: Torque for coil cover sizes 0 to 2 are approximately 14--17 lbs.-in.
Sizes 3 to 5 are approximately 25--30 lbs.-in.
7
Renewal Parts
Bulletin 509, Sizes 0 through 4 (all series)
Size 5 (series L)
“Seating
Projection”
The mounting screws or bolts that secure the front stationary contacts (item
11) are accessible from the front and are located directly below and to the
back of the front terminal assemblies. A socket wrench should be used to
loosen and tighten contact securing bolts.
Note: Front and rear contacts should be removed and replaced in pairs, one
at a time.
1. Loosen and remove the screw or bolt and lift out the contact.
2. Install the replacement contact (front and rear stationary contacts are
identical) and tighten the contact mounting screw or bolt securely.
8
Renewal Parts
Bulletin 509, Sizes 0 through 4 (all series)
Size 5 (series L)
9
Renewal Parts
Bulletin 509, Sizes 0 through 4 (all series)
Size 5 (series L)
1. Secure the overload relay to the mounting plate with the two previously
removed screws with washers. Tighten securely.
Note: Place the flat washers next to the molded plastic part. Overload
relay embossments are provided for proper alignment.
2. Secure the stationary contact block and base assembly with the three
screws with washers and tighten securely.
3. Retighten securely the three terminal screws to overload bus.
4. Insert the yoke into the operating coil. It is designed to fit only one way.
5. Insert the yoke and operating coil into the movable contact support
assembly.
6. Insert all three parts as a unit into the stationary contact block and base
assembly.
7. Replace the coil cover. Check the tie point terminal for proper position.
Tighten the coil cover screws securely.
8. Replace contact block cover and tighten screws securely.
9. Install the auxiliary contact block(s). Refer to detailed instructions under
Installing or Replacing an Auxiliary Contact Block on page 15.
10. Properly reconnect all wiring and tighten the screws.
Eutectic Alloy Overload The eutectic alloy overload relay is equipped with a test module (item 13b)
Relay Test Module on the right hand side, that allows opening the normally closed overload
contact for test purposes,without tripping the relay.
1. To remove, use an appropriate size screwdriver. Hold the blade vertically
and insert the screwdriver tip into the slot provided on the test module, to
the point where it “bottoms”.
2. Slide the test module out to the right.
3. Slide the replacement test module into place and press firmly until it locks
in place.
10
Renewal Parts
Bulletin 509, Sizes 0 through 4 (all series)
Size 5 (series L)
Replacing the Eutectic Alloy Refer to exploded view, Figure 1 for item number.
Overload Relay
The overload relay (item 13) is connected to the block and base assembly
(item 3), mounting plate, and load lines.
1. Remove the control wire(s) from the overload relay and label wires if
necessary.
2. Remove the load wiring from the overload relay terminals. Label all the
wires to prevent installing the wires incorrectly.
3. Loosen but do not remove the three terminal screws that connect the
overload relay bus to the block and base assembly, approximately three
turns.
Note: Terminal screws on sizes 3, 4, and 5 must be removed.
11
Renewal Parts
Bulletin 509, Sizes 0 through 4 (all series)
Size 5 (series L)
Nylon
Nylon Standoff
Spacer
Insulator
Current
Transformer
Module
Overload
Relay
Current
Transformer
Lug
Refer to Figure 4 and exploded view, Figure 1 for item numbers. The current
transformers (Item 17) are attached to the current transformer module and
connected to the overload relay (Item 13).
1. Label and remove all wires from the overload relay. Remove the
grounding screw from the current transformer module mounting plate.
2. Loosen and remove the two 10-32 ¢ 1 in. screws and washers which
secure the overload relay mounting plate to the 3/4 in. ¢ 1-9/16² nylon
standoffs. The overload relay is now free of the starter.
3. Label and remove the terminal wiring from the current transformer to be
replaced. Label to indicate which wire was connected to the terminal near
the polarity mark.
4. Loosen and remove the three 5/16 in.-24 ¢ 3/4 in. hexagon head load
terminal screws connecting the load terminals to the contactor.
5. Loosen and remove the four 1/4 in.-28 ¢ 3/4 in. hexagon head screws
connecting the current transformer module to the mounting plate. The
current transformer module is now free of the mounting plate.
6. To replace the center current transformer: Remove the rectangular nylon
spacer insulator from the load terminal. The transformer can now be
removed and replaced.
7. To replace either of the outer current transformers: Loosen and remove
the 3/4 in. ¢ 1-9/16 in. nylon standoff attached to the load terminals.
Turn the current transformer module over and remove the 5/16 in.-24 ¢
1-1/4 in. hexagonal head screw and the 10-32 ¢ 3/4 in. screw from the
load terminals.
12
Renewal Parts
Bulletin 509, Sizes 0 through 4 (all series)
Size 5 (series L)
Turn the module back over and slide the load terminals out of the
transformer. The current transformer spring (Item 17A) and current
transformer can now be removed from the module. Note the position of
the spring before removing.
The replacement current transformer and spring are placed into the
module so that the rectangular holes in the center of the spring and
transformer are aligned and the spring is below the transformer, concave
side facing up. Slide the load terminal through the transformer so that the
load terminal lug is on the same side and in the same direction as the
other load terminal lugs.
Turn the module over and refasten the 5/16 in.-24 ¢ 1-1/4 in. screw
(torque to 50 lbs.-in) and the 10-32 ¢ 3/4 in. screw (torque to 30 lbs.-in.)
to the load terminal. Turn the module over (right side up) and refasten the
3/4 in. ¢ 1-9/6 in. nylon standoff to the load terminal torque to
16 lbs.-in.)
13
Renewal Parts
Bulletin 509, Sizes 0 through 4 (all series)
Size 5 (series L)
Auxiliary Contacts
Figure 5
Bulletin 509 Starters are designed to accept one to four Bulletin 595
Auxiliary Contact Blocks which can provide up to six auxiliary contacts of
the user’s choice. Auxiliary contact blocks mount beneath the coil cover at
positions marked P1, P2, P3, or P4 on the coil cover. They can be mounted
without the use of tools or additional hardware.
Loosen coil cover screws and lift out the auxiliary contact block by pivoting
its back end away from starter.
14
Renewal Parts
Bulletin 509, Sizes 0 through 4 (all series)
Size 5 (series L)
Figure 6
Align Arrows
Molded Tabs
Exert
Pivotal
Force
4. Exert a pivotal force at the lower end of the block until it snaps into place.
Refer to Figure 7.
15
Renewal Parts
Bulletin 509, Sizes 0 through 4 (all series)
Size 5 (series L)
This contact can easily be added to the block type eutectic alloy overload
relay used on Bulletin 509 sizes 0, 1, 2, and 5 starters. It mounts in place of
the standard eutectic alloy overload relay test module. A typical application
would be for an alarm circuit indicating when the overload relay has tripped.
Figure 9
Test
Module
Auxiliary
Mounting Contact
Screw Block
16
Renewal Parts
Bulletin 509, Sizes 0 through 4 (all series)
Size 5 (series L)
4. Slide the N.O. or N.C. auxiliary contact block into the overload relay in
place of the test module.
5. Secure the block, using the mounting screw provided, through the hole in
the overload relay housing. See Figure 9.
1. Insert proper size screwdriver in slot at the top of Circuit Test Module;
press towards mounting plate and pull module from relay. Refer to
Figure 10.
Figure 10
Overload
Relay
Housing
Circuit
Test
Module
Screwdriver
Stationary Movable
Contacts Contacts
17
Renewal Parts
Bulletin 509, Sizes 0 through 4 (all series)
Size 5 (series L)
Modifications (cont.) 3. Place the section containing the stationary contacts above the retaining
ribs on the overload relay and the section containing the movable contacts
below the same retaining ribs. Refer to Figure 12.
Figure 12
Retaining Ribs
4. Securely tighten two screws to fasten the two sections of the auxiliary
contact together and to the overload relay housing retaining ribs. Refer to
Figure 13.
Figure 13
Tighten
Screws
Securely
Retaining
Rib
18
Renewal Parts
Bulletin 509, Sizes 0 through 4 (all series)
Size 5 (series L)
Replacing an N.O. or N.C. The function of the auxiliary is N.O. when mounted on the end of the relay
Auxiliary Contact on an furthest from the reset button and N.C. when mounted on the end nearest the
reset button.
Overload Relay (for Sizes 3
and 4 Starters) Note: N.O. and N.C. are stamped on the relay housing to indicate function.
Slide Apart
and Remove
Loosen
Two
Screws
19
Renewal Parts
Bulletin 509, Sizes 0 through 4 (all series)
Size 5 (series L)
20 Publication 509-6.0 May 1996 Copyright 1996 Allen-Bradley Company, Inc., a Rockwell International company Printed in USA