Professional Documents
Culture Documents
MULTI-DWELLING UNITS
SUBTOPIC 1
Standards and Design of a Residential Multi
Dwellings
Subtopic 1
INTENDED LEARNING
OUTCOMES
At the end of this discussion the student are expected to:
Outdoor Outlets. For a one-family dwelling and each unit of a two-family dwelling that is at grade
level, at least one receptacle outlet accessible at grade level and not more than 2 000 mm above
grade shall be installed at the front and back of the dwelling. For each dwelling unit of a multifamily
dwelling where the dwelling unit is located at grade level and provided with individual exterior
entrance/egress, at least one receptacle outlet accessible from grade level and not more than 2
000 mm above grade shall be installed. See 2.10.1.8(a)(3).
f) Laundry Areas. In dwelling units, at least one receptacle outlet shall be
installed for the laundry.
(b) House Loads. House loads shall be calculated in accordance with Part
III of this article and shall be in addition to the dwelling unit loads calculated
in accordance with Table 2.20.4.5.
(c) Connected Loads. The calculated load to which the demand factors of Table
2.20.4.5 apply shall include the following:
(1) 24 volt-amperes/m2 for general lighting and general-use receptacles.
(2) 1 500 volt-amperes for each 2-wire, 20-ampere smallappliance branch circuit
and each laundry branch circuit specified in 2.20.3.13.
(3) The nameplate rating of all appliances that are fastened in place, permanently
connected or located to be on a specific circuit, ranges, wall-mounted ovens,
counter-mounted cooking units, clothes dryers, water heaters, and space
heaters. If water heater elements are interlocked so that all elements cannot
be used at the same time, the maximum possible load shall be considered the
nameplate load.
(4) The nameplate ampere or kilovolt-ampere rating of all motors and of all low-
power-factor loads.
(5) The larger of the air-conditioning load or the space-heating load.
2.20.4.6 Two Dwelling Units. Where two dwelling units are
supplied by a single feeder and the calculated load under
Part 2.20.3 exceeds that for three identical units calculated
under 2.20.4.5, the lesser of the two loads shall be permitted
to be used.
A 2 storey residential building consist of 6 dwellings
having a typical load of 4700VA. Compute for the total
loads, the main service entrance conductor and main
service equipment.
A multifamily dwelling unit having 12 dwelling with
individual feeder to each dwelling unit. Each dwelling
unit has a floor area of 90 sq. meters and with typical
household appliances including one 8KW electric range
and one 1Hp ACU. Compute for all Total Computed Load,
Main Service Entrance Conductor and Main Service
Equipment.
• IIEE (2017), Philippine Electrical Code 2017
• Branch-Circuit, Feeder and Service Calculations, Part LXII. (n.d.). Electrical Contractor
Magazine. Retrieved July 28, 2020, from https://www.ecmag.com/section/codes-
standards/branch-circuit-feeder-and-service-calculations-part-lxii
• Branch-Circuit, Feeder and Service Calculations, Part LIX. (n.d.). Electrical Contractor
Magazine. Retrieved July 28, 2020, from https://www.ecmag.com/section/codes-
standards/branch-circuit-feeder-and-service-calculations-part-lix