COMMERCIAL ESTABLISHMENT
Commercial establishment means non-lodging
related public and private facilities which serve the
general public or selected members of the general
public, including government and professional
offices and non-lodging related retail businesses
such as store
Below are the common types of Commercial
Establishments
• Restaurants
• Banks
• Malls / Store Building
• Commercial Offices
INTENDED LEARNING
OUTCOMES
At the end of this discussion the student are expected to:
Exception No. 1: Where the assembly, including the overcurrent devices protecting the feeder(s), is
listed for operation at 100 percent of its rating, the ampere rating of the overcurrent device shall be
permitted to be not less than the sum of the continuous load plus the noncontinuous load.
Exception No. 2: Overcurrent protection for feeders over 600 volts, nominal, shall comply with Part
2.40.11.
2.30.7 Service Equipment — Overcurrent Protection
Exception No. 1: For motor-starting currents, ratings that conform with 4.30.4.2, 4.30.5.2,
and 4.30.5.3 shall be permitted.
Exception No. 2: Fuses and circuit breakers with a rating or setting that conforms with
2.40.1.4(b) or (c) and 2.40.1.6 shall be permitted.
Exception No. 3: Two to six circuit breakers or sets of fuses shall be permitted as the
overcurrent device to provide the overload protection. The sum of the ratings of the circuit
breakers or fuses shall be permitted to exceed the ampacity of the service conductors,
provided the calculated load does not exceed the ampacity of the service
conductors.
Exception No. 4: Overload protection for fire pump supply conductors shall conform with
6.95.1.4(b)(1).
Exception No. 5: Overload protection for 120/240-volt, 3-wire, single-phase dwelling
services shall be permitted in accordance with the requirements of 3.10.1.15(b)(6).
2.15.1.2 Minimum Rating and Size.
(1) General. Feeder conductors shall have an ampacity not less than required to supply the
load as calculated in Parts 2.20.3, 2.20.4, and 2.20.5. The minimum feeder-circuit conductor
size, before the application of any adjustment or correction factors, shall have an allowable
ampacity not less than the noncontinuous load plus 125 percent of the continuous load.
Exception: Where the assembly, including the overcurrent devices protecting the feeder(s), is listed for operation at 100
percent of its rating, the allowable ampacity of the feeder conductors shall be permitted to be not less than the sum of
the continuous load plus the noncontinuous load.
The size of the feeder circuit grounded conductor shall not be smaller than that required by
2.50.6.13, except that 2.50.6.13(f) shall not apply where grounded conductors are run in
parallel. Additional minimum sizes shall be as specified in 2.15.1.2(a)(2) and (a)(3) under the
conditions stipulated.
(2) Ampacity Relative to Service Conductors. The feeder conductor
ampacity shall not be less than that of the service conductors where
the feeder conductors carry the total load supplied by service
conductors with an ampacity of 55 amperes or less.
(1) The sum of the noncontinuous loads plus 125 percent of continuous loads
(2) The sum of the noncontinuous load plus the continuous load if the service-entrance conductors
terminate in an overcurrent device where both the overcurrent device and its assembly are listed
for operation at 100 percent of their rating
2.20.3.4 Show-Window and Track Lighting
(a) Show Windows.
For show-window lighting, a load of not less than 660 volt-amperes/linear
meter shall be included for a show window, measured horizontally along its
base.
(b) Track Lighting.
For track lighting in other than dwelling units or guest rooms or guest suites
of hotels or motels, an additional load of 150 volt-amperes shall be included
for every 600 mm of lighting track or fraction thereof. Where multicircuit track
is installed, the load shall be considered to be divided equally between the
track circuits.
(c) Motor Loads.
Outlets for motor loads shall be calculated in accordance with
the requirements in 4.30.2.2, 4.30.2.4, and 4.40.1.6.
a. 100m2 restaurant
b. 150m2 bank
c. 9m show window
A store 15m by 18m has 9m of show window. There are a
total of 80 duplex receptacles. The service is 240V single
phase. The actual connected lighting load is 8,500VA.
• IIEE (2017), Philippine Electrical Code 2017