Professional Documents
Culture Documents
Symmetrical Fault Detection Technique During Power Swing Based On S-Transform
Symmetrical Fault Detection Technique During Power Swing Based On S-Transform
Abstract—Disturbances in a power system such as line switching time delay and this might cause the power swing blocking
and sudden removal of faults may cause instability which lead to scheme function fail to reset the relay.
the power swing phenomenon. During a power swing, the mal-
operation of distance relay is among the problem which needs to Mecharoui and Thomas in [5] developed a technique to
be solved. In the case of a power swing, a distance relay is detect fault during power swing based on monitoring the
designed to block detection to avoid wrong interpretation of relay voltage phase angle. However the technique proved to be
current signals. However, this blocking scheme proves to be problematical for high resistance fault. Further work was
unreliable as it could block the trip signals when a genuine fault carried out in [6] to concentrate particularly in detecting high
occurs in the system during a power swing. Hence, it is vital to resistance fault during power swing, but the symmetrical fault
develop a proper fault detection technique during a power swing is not being considered in this paper.
to avoid such circumstances. This paper presents a detection
technique to detect symmetrical faults during a power swing A simple approach based on Fast Fourier Transform (FFT)
based on the time frequency transform known as S-Transform. analysis on DC component of current is used in [7] to detect
To ascertain validity of the proposed scheme, it was verified with fault during a power swing and it works for both symmetrical
the IEEE 14-bus system and simulation results showed that the and asymmetrical fault. Another approach based on FFT
proposed technique was able to detect symmetrical faults analysis is developed by Mahamedi [8]. Unfortunately both
occurring in the power system. techniques require a proper selection of Fourier coefficient,
especially for detecting high resistance fault.
Keywords-distance protection; power swing; symmetrical fault;
S-Transform Time-frequency analysis using wavelet transform (WT) has
been introduced in [9] and [10] for identification of the power
I. INTRODUCTION swing and detection of symmetrical faults during a power
Power swing is a consequence result from system swings. However for the sake of implementation of the wavelet
disturbance such as such as sudden removal of faults, line based scheme, the proper selection of the wavelet coefficient is
switching, or generator disconnection. When one of these an essential, and inaccuracy in the selection might caused some
system disturbances happens to any power system, it may of the cases cannot be detected.
break the balance between generators and loads, and causes Abidin et al. [2] introduced time-frequency analysis using
oscillations in generator rotor angles [1]-[2]. During a power S-Transform as a feature extraction tool for characterizing the
swing, the voltage and current fluctuate simultaneously, respective features of fault, stable swing, and unstable swing
causing fluctuating in the measured apparent impedance at the for distance relay operation. This technique was found to be
distance relay point, hence it will enter the relay tripping zones problematical for the detection of faults with resistance of more
leading to undesired relay operation. than 50 Ω.
Power swing blocking (PSB) scheme function is employed All of the techniques which have been reported are not able
in modern distance relay to prevent any unwanted relay to operate properly during high resistance faults and/or
operation during power swing. The main philosophy of this symmetrical faults. This paper presents a detection technique to
scheme is to block the relay operation during a power swing detect symmetrical fault during a power swing based on S-
and reset the relay when a genuine fault occurs during a power Transform analysis on the distance relay inputs based on
swing. Literature surveys up to recent years show PSB ideas voltage and current signals. In order to ascertain validity of the
has lead to new security issue for distance relay operation. proposed scheme, evaluation and simulation are conducted
Benmouyal et al. [3] and Su et al. [4] tracked the power under IEEE 14-bus system with various study cases which will
swing voltage center (PSCV) to detect a symmetrical fault be discussed in detail in the following sections.
during a power swing. However, these methods require longer
2
, . . (2)
where H(f) denotes the Fourier Transform of h(t).
From equation (2), the discrete time series of S-Transform
corresponding to h(t) is shown in following equation by letting
τ -› k/T, f -› n/NT , and α -› m/NT ,
, ∑ . . (3)
, ∑ . (4)
Figure 1. Single line diagram of IEEE 14-bus system
where 2 and 2 .
Initially, a three-phase fault is initiated at line 3-4 at t=1.5s
and cleared after 500ms. This sends the power system into IV. PROPOSED SCHEME
power swing. At this condition, fault is created at line 4-5 at The scheme proposed in this paper used S-Transform as
t=2.5s to get the situation of fault during a power swing. Figure signal processing tool to extract the features between power
2 shows the typical voltage and current signals measured by the swing and symmetrical fault occurring during a power swing.
distance relay located near bus-5 at line 2-5 during a power Under power swing condition and symmetrical fault after
swing and after a three-phase fault occurring during a power power swing condition, inputs of distance relay based on
swing. voltage and current are calculated and processed using S-
20 Transform tools to generate the S-matrix.
10
Further, the magnitude of the S-matrix is calculated using
voltage
0
following equation,
-10
-20
0 500 1000 1500 2000 2500 3000 3500 4000 ∑ . (5)
samples
10
5
∑ . (6)
current
0
where δ denotes the magnitude of S-Transform of signal Vbus(t)
-5
and Iline(t) respectively.
-10
0 500 1000 1500 2000
samples
2500 3000 3500 4000
From each of equation (5) and (6), the smallest value of
each of column in the matrix of δ is further defined by using
Figure 2. Voltage and current signals of three-phases for a power swing and following equation,
after three-phase fault occurring during a power swing
8
S1-1 2012 IEEE Student Conference on Research and Development
2000
∑ . (7) 1500
voltage
1000
∑ . (8) 500
Based on each of equation (7) and (8), a row vector of 500 1000 1500 2000 2500 3000 3500 4000
samples
length n, filled with smallest value of each of column in matrix 2000
of δ is obtained. Further, the corresponding output from each of 1500
equation (7) and (8) is computed to register the faults during a
current
power swing. The proposed technique is very straightforward 1000
and the process of identifying the fault during a power swing is 500
2000
1500
voltage
1000
500
1500
current
1000
500
6
The magnitude of the S-matrix is calculated using equation
voltage
4
(5) and (6). Since the obtained outputs from the above
calculation are in m-by-n matrix, contour plot is used to 2
0.01
0.005
0
0 500 1000 1500 2000 2500 3000 3500 4000
samples
Figure 6. Minimum value of of the S-matrix on voltage and current signals
for the event of normal power swing
9
S1-1 2012 IEEE Student Conference on Research and Development
x 10
-3
Van Cutsem, T.; Vittal, V., “Definition and Classification of Power
6
System Stability”, IEEE Transaction on Power System, Vol. 19, No. 2,
May 2004.
voltage
4
[2] Farid bin Abidin, Ahmad, Adaptive Distance Protection to Prevent False
2 Relay Tripping during Voltage Collapse and Power Swing, PHD Thesis,
2010.
0
0 500 1000 1500 2000 2500 3000 3500 4000 [3] Benmouyal , D. Hou and D. Tziouvaras, Zero-Setting Power-Swing
samples Blocking Protection, [online]
0.02
Available:
0.015
http://www.selinc.com/techpprs/6172_ZeroSetting_20050302.pdf
current
0.01 [4] Su, B., Dong, X.Z., Bo, Z.Q., Sun, Y.Z., Caunce, B.R.J., Tholomier, D.,
0.005 and Apostolov, A., “Fast Detector of Symmetrcial Fault during Power
Swing for Distance Relay”, IEEE Power Engineering Society General
0
0 500 1000 1500 2000 2500 3000 3500 4000
Meeting, 2005.
samples [5] Mechraoui, A. and Thomas, D.W.P., “A New Blocking Principle with
Figure 7. Minimum value of of the S-matrix on voltage and current signals Phase and Earth Fault Detection during Fast Power Swings for Distance
for the event three-phase fault occurring during a power swing Protection”, IEEE Transactions on Power Delivery, Vol. 10, No.3, July
1995.
Based on the result shown in Figure 6 and Figure 7, it is [6] Mechraoui, A. and Thomas, D.W.P., “A New Principle for High
Resistance Earth Fault Detection during Fast Power Swings for Distance
clearly observed there is significant feature when a fault Protection”, IEEE Transactions on Power Delivery, Vol. 12, No. 4,
occurred in the power system and cleared from the power 1997.
system. Whenever a fault occurred in the normal condition or [7] Karegar, H. K., and Mohamedi, B., “A New Method for Fault Detection
during a power swing, the fault can be easily detected by using during Power Swing in Distance Protection”, 6th International
the proposed technique. Conference on Electrical Engineering/Electronics, Computer,
Telecommunications and Information Technology, 2009.
VI. CONCLUSION [8] Mahamedi, B., “A Very Fast Unblocking Scheme for Distance
Protection to Detect Symmetrical Faults during Power Swing”,
A symmetrical fault detection technique during a power Conference Proceedings IPEC, 2010.
swing for the distance relay had been presented in this paper. It [9] Brahma, S.M., “Distance Relay with Out-of-Step Blocking Function
make use of the utilization of S-Transform processing tool to using Wavelet Transform”, IEEE Transactions on Power Delivery, Vol.
process the distance relay input signals based on voltage and 22, No. 3, 2007.
current signals to detect symmetrical fault occurs in the power [10] Chengzong Pang, and Kezunovic, M., “Fast Distance Relay Scheme for
system. Despite whether the fault is occurred during a normal Detecting Symmetrical Fault during Power Swing”, IEEE Transactions
condition or a power swing condition, this technique is proven on Power Delivery, Vol. 25, No. 4, 2010.
able to detect the fault. [11] N. Mithulananthan, C. A. Ca˜nizares, and J. Reeve. “Indices to Detect
Hopf Bifurcation in Power Systems”, NAPS-2000, Oct 2000.
ACKNOWLEDGMENT [12] Sameh K. M. Kodsi, Accounting for the Effects of Power System
Controllers and Stability on Power Dispatch and Electricity Market
The authors would like to extend their gratitude to Prices, PhD Thesis, 2005.
Universiti Teknologi MARA (UiTM) for supports on the [13] Yu-Hsiang Wang, The Tutorial: S-Transform, [online]
project in term of scholarship and financial support. Available:
http://djj.ee.ntu.edu.tw/S%20transform.pdf
REFERENCES
[1] Kundur, P.; Paserba, J.; Ajjarapu, V.; Andersson, G.; Bose, A.;
Canizares, C.; Hatziargyriou, N.; Hill, D.; Stankovic, A.; Taylor, C.;
10