You are on page 1of 8

2558 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 30, NO.

5, SEPTEMBER 2015

Three-Phase Fault Detection During


Power Swing by Transient Monitor
Jalal Khodaparast and Mojtaba Khederzadeh, Senior Member, IEEE

Abstract—Distance relays are immune to inadvertent operation power swing, the PSB should differentiate it from power swing
during power swings by a block known as “power swing blocking to unblock relay. Due to the presence of the negative and zero
(PSB)”. Its main function is discriminating faults from power sequences, the detection procedure of unsymmetrical faults is
swings. However, if a fault occurs during a power swing, PSB
easier than that of symmetrical ones.
should be de-blocked and let the distance relay to operate normally
and clear the fault accordingly. Meanwhile, discrimination of a Different methods are proposed to solve this problem. Power
three-phase fault from a power swing is the most difficult task due swing center voltage (SCV) is a method which is proposed in
to their likelihood. This paper proposes a new method to overcome [6], but has the difficulty in choosing an appropriate threshold;
this issue by monitoring the transient period established in the meanwhile, it has a relatively long detection time (two cycles).
process of current dynamic phasor estimation. In this regard, Wavelet transform utilization is introduced in [7]; however,
transient monitor (TM) index, which is the difference between the it needs relatively high sampling rate (40.96 KHz). In [8], a
estimated current samples regenerated from the calculated dy-
method based on extracting the high frequency component en-
namic phasors and the actual sample values, is used to distinguish
the fault from the power swing. Fourier-Taylor transformation ergy of the forward and backward traveling waves is proposed.
is applied to estimate the dynamic phasor of the current signal. Differential power based fault detection technique is also pro-
Simulation results verify the inherent potential of the proposed posed, which makes use of auto regression technique to predict
method to overcome the issue. the future samples [9]; however, it needs a lot of simulations
Index Terms—Distance relay, dynamic phasor, power swing to select the appropriate parameters of the regression method.
blocking, three-phase fault, transient monitor. Approximate entropy of the signal to detect the fault during the
power swing is proposed in [10]. In [11], superposition the-
orem is used for detection of direction, selection of the faulted
I. INTRODUCTION phase, and detection of power swing. While the method does
not require complicated mathematical operations, setting the

P OWER systems are prone to faults, which should be iden- threshold value is a difficult task. Another method is proposed
tified and cleared in due time to protect the equipments in [12] that uses the decaying dc component of the fault current,
and allow normal operation of the system, thereafter. Distance extracted by the Prony analysis as an index of presence of a
relay is used to protect the transmission line by measuring the fault. In [13], a technique based on negative sequence compo-
apparent impedance in order to estimate the distance to fault. nent of the current signal is used for detecting all types of faults;
Power swing is a phenomenon that creates large fluctuations of however, it is applicable only to compensated lines. In [14],
active and reactive powers between two areas of an electrical a method based on the maximum change rate of three-phase
system following severe disturbances such as line faults, loss of active and reactive powers is proposed, which is zero during
generating units, and switching heavy loads. It could affect the fault and higher than 0.7 during power swing; nevertheless,
distance relay's behavior, which may result in the relay malfunc- the method ignores the resistive component of the impedance.
tion. Recent blackouts indicate the involvement of Zone 3 of Another method is proposed in [15] based on detection of the
distance relays during system stressed conditions such as power fundamental frequency component created on the instantaneous
swings [1]–[5]. three-phase active power after inception of a symmetrical fault;
The main task of power swing blocking (PSB) unit is to pre- however, it assumes that the fault resistance is negligible. In
vent unintended operation of the relay during stable or unstable [16], an adaptive neuro-fuzzy inference system is proposed that
power swing. The most common technique in order to detect a in spite of its fast response, re-training is required whenever the
power swing is based on different rates of impedance changes. power system experiences major changes.
In other words, when a fault occurs, the impedance change rate In this paper, an index named transient monitor (TM) is used
from a normal-load point to fault-point is significantly faster as an indicator of a fault during a power swing. The proposed
than power swing condition [5]. When a fault occurs during a method is based on comparing the calculated TM and the speci-
fied threshold. It will detect the fault whenever the TM exceeds
the predetermined threshold during a power swing. As phasor
Manuscript received March 16, 2014; revised July 01, 2014 and September
estimation is the major part of this index calculation, dynamic
14, 2014; accepted October 13, 2014. Date of publication November 06, 2014;
date of current version July 17, 2015. Paper no. TPWRS-00372-2014. phasors are used to enhance the performance of the method. The
The authors are with the Faculty of Electrical and Computer Engineering, threshold value is determined by phasor estimation accuracy. As
Shahid Beheshti University, Tehran 1658953571, Iran (e-mail: J_Khoda- dynamic phasors are used to extract the signals, so the threshold
parast@sbu.ac.ir; khederzadeh@pwut.ac.ir).
Color versions of one or more of the figures in this paper are available online
value is reduced.
at http://ieeexplore.ieee.org. Traditionally, the phasor is defined for steady state sinusoidal
Digital Object Identifier 10.1109/TPWRS.2014.2365511 signals with constant amplitude and phase. However, the power

0885-8950 © 2014 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
KHODAPARAST AND KHEDERZADEH: THREE-PHASE FAULT DETECTION DURING POWER SWING BY TRANSIENT MONITOR 2559

Fig. 1. Two-machine system with distance relay.

system is actually in dynamic condition. In the dynamic con-


dition, the amplitude and phase varies with time, which intro-
duces the concept of dynamic phasor [17]. Due to lack of rec-
ommended specific algorithm to estimate phasor in IEEE Std.
C37.118, phasor estimation has attracted a lot of attention [18].
Different algorithms are proposed to estimate the dynamic pha-
sors [19]–[24]. In this paper, the amplitude and phase of the
power system variables are considered as time dependent and
are represented by second-order Taylor polynomials, estimated
by the least square method.
The contributions of the paper are summarized as follows:
• Dynamic phasors are used to calculate apparent impedance
seen by distance relay to enhance the performance of the
relay during stressed conditions like power swing.
• A relevant index is introduced to discriminate a power
swing from a three-phase fault, especially when the relay is
blocked during a power swing and a three-phase fault oc-
curs. It is worth noting that monitoring the transient period
using dynamic phasors is a new contribution well suited Fig. 2. Z locus for a) pure power swing and b) fault during power swing.
for this application.
The paper is organized as follows: Section II briefly describes
the concept of power swing and inception of a fault during a this scenario continues until it reaches to an equilibrium point.
power swing. TM using dynamic phasors as a tool for discrimi- Once a fault occurs, the impedance leaves the power swing locus
nation of a fault from a power swing is presented in Section III. immediately and reaches to the line . At this time, the relay
Section IV deals with the error analysis originated by noise. must detect the fault and trip quickly. This scenario is shown
Section V presents simulation results to verify the proposed in Fig. 2(b). This paper proposes a technique (using TM) for
approach. detecting this situation (faults) during the power swing.

II. POWER SWING AND FAULT DURING POWER SWING III. TRANSIENT MONITOR
The effect of power swing on the performance of distance TM is introduced to examine the quality of phasor estimation.
relay is well described by a simple two-machine model as shown It is actually the difference of real input samples and the recom-
in Fig. 1. and are the voltages behind transient reac- puted samples obtained by phasor estimation [25]. A sinusoidal
tances with constant magnitude and variable phase during a signal is described as
power swing. leads by the angle . Bus B is supposed
as an infinite bus and as the total impedance (including trans- (2)
mission line and transient reactances of the machines); thereby, where is the amplitude of signal , is the sample number,
the apparent impedance seen by the distance relay is is the phase angle in radians, and ( is the sample
per cycle). Conventional (static) phasor is expressed as
(1) (3)

Based on (2) and with samples per cycle, we have


For a constant and different ratio, the locus of
as shown in Fig. 2 is a circular arc or a straight line. According
to Fig. 2, for , the swing-impedance locus is a
straight line perpendicular to line at its midpoint, where
the voltage becomes zero (similar to a fault), i.e., and
are in phase opposition . The main application of
these arcs is to determine values of by intersecting swing-
impedance loci and arcs. Fig. 2(a) shows an example of stable
power swing. For instance, impedance starts from in (4)
its first swing, reaches to , and then returns back;
2560 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 30, NO. 5, SEPTEMBER 2015

Equation (4) is a discrete time signal because the last inserted sample is noticeably different from the
in terms of static phasor's Taylor-Fourier coefficients others:
and represents the conjugate operator. These coef-
ficients are estimated from the least square method: (13)

(5) The difference between TM values during a pure power


swing and during a fault condition is an indication of fault
where is the Hermitian transpose operator. Re-computing the inception. By increasing the value of this difference, the reli-
samples from the estimated phasor is as follows: ability of the fault detection method based on TM enhances.
Therefore, phasor should be estimated more accurately during
(6) power swing. As the amplitude and phase of the voltage/current
signal have variable values during a power swing, dynamic
The difference between the input and recomputed sample phasor concept is the best tool for this condition. A sinusoidal
data, calculated from the phasor estimates, is considered as the quantity with variable amplitude and phase is defined as
error of estimation process [25]:
(14)

where and are the variable amplitude and phase of


the signal, respectively; is the dynamic phasor expressed
as
(15)
(7)
In order to approximate dynamic phasor, second-order Taylor
series of around is given by

Therefore, TM is calculated by (16)

According to the equations presented in [17] and for


(8)
N samples of the signal in (14), the discrete time signal
in terms of its Taylor-Fourier
Pure sinusoidal input results in zero value for TM because the coefficients is extracted as
estimated phasor is exactly equal to the input. However, during
(17)
a pure power swing, the signal could be defined as
where matrix is in the basic form of in (4) with the dif-
(9)
ference that it contains first and second derivative of dynamic
where is sample per swing frequency, and is the amplitude phasor.
of the envelope of the signal. Therefore, during power swing, These coefficients are calculated by least square method as
the first column of is obtained as (18)

The difference between input and recomputed sample data,


calculated from the dynamic phasor estimates, is considered as
(10) the error of estimation process:

Regarding (10), the result is approximately zero because the


variation of amplitude is negligible during low frequency oscil-
lation:

(11)
(19)
However, when a fault occurs during the power swing, the input
signal of phasor estimation process is considered as

Therefore, the first array of is obtained as


(12)
(20)

where is the starting sample of a fault, is the amplitude, where are constant parameters. The accuracy
and . When the first sample of the fault is of phasor estimation obtained by dynamic phasor is higher than
observed in the data window, is not equal to zero anymore, static one due to consideration of first and second derivatives of
KHODAPARAST AND KHEDERZADEH: THREE-PHASE FAULT DETECTION DURING POWER SWING BY TRANSIENT MONITOR 2561

Fig. 4. Amplitude estimation during power swing using dynamic phasor.

where is the exact value of the phasor and is the estimated


one. (sample per cycle) and (variance of input error) are
two parameters which affect the output of (24). has inverse
relationship with the phasor estimation error, while has di-
rect relationship, which will be demonstrated in the simulation
results.

V. SIMULATION RESULTS
Fig. 3. Flowchart of the proposed method. Simulations are performed for different operating conditions
with dynamic phasor estimation during power swing and three-
phase fault.
the phasor. The result of (20) is approximately zero like (10), but
its value is relatively lower than (10), which represents lower A. Evaluation of Dynamic Phasor Estimation
TM for dynamic phasor during power swing compared to the
Test signal (25) is used to validate the proposed method in
static one.
estimating the dynamic phasor in power swing condition:
In this paper, dynamic phasor of currents is calculated based
on second-order Taylor-Fourier method and TM index is used (25)
to detect three-phase fault during power swing. Current signal is
considered as input signal because its TM is higher than voltage. where
A flowchart of proposed method is shown in Fig. 3.

IV. ERROR ANALYSIS


Noise is an unwanted part of every signal in real condition
and affects the accuracy of phasor estimation part of the pro-
posed method. Noise is considered zero-mean Gaussian noise
in the input signal. By adding a sinusoidal quantity with vari-
able amplitude and phase to Gaussian noise, (21) is resulted as The result of phasor estimation is shown in Fig. 4. Power
swing is composed of amplitude and phase modulation.
(21) Fig. 4 shows only the amplitude estimation. Errors on the
order of are provided by this method (second-order
where is a zero-mean Gaussian noise with a variance of . Fourier-Taylor transform) which indicates that a low threshold
In this condition, (22) is the matrix form of (21) based on N value for the diagnosis process is required.
samples of the noisy signal, as
B. Effect of Sampling Frequency and Noise Variance on the
(22) Accuracy of Phasor Estimation
where and , , and are Standard deviation of dynamic phasor estimation depends
matrices defined in (17). By assuming the covariance matrix of on error variance of additive noise and sampling frequency
noise as . (where is a unit matrix), the solution of of the input signal. Higher sampling rates produce lower
(22) based on least square method is [25] estimation errors, while lower variances of the input noise
produce lower error values. In order to show the effect of noise
(23) variance and sampling frequency on the standard deviation
simultaneously, the test signal (25) is utilized; this is sampled
Covariance matrix of the phasor estimation error is
at six different sampling rates (8, 16, 32, 64, 128, and 256
obtained as
times per cycle) and additive noise with nine different vari-
ances .
(24)
Fig. 5 shows the standard deviation of 1000 phasor estimation
2562 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 30, NO. 5, SEPTEMBER 2015

interval around the fundamental frequency leads to lower distor-


tions in the phasor estimation. The more persistent flat gain of
the method validates the strength of the dynamic phasor concept
in oscillating conditions. This figure also helps to explain the
behavior of the dynamic phasor method when other frequency
components are present in the input signal. This method pro-
vides zero-gain in non-fundamental components, which demon-
strates its ability to remove the harmonic impacts in the output.
So, this method does not have difficulties in harmonic condi-
tions, and as a consequence, presence of harmonics has no ef-
fect on the fault detection approach.

Fig. 5. Effect of variance and frequency sampling on standard deviation of D. Fault Detection During Power Swing
dynamic phasor estimation error.
To demonstrate the proposed fault detection method, a series
of simulations are carried out on a two-machine system, shown
in Fig. 1. To excite the power swing with different slip frequen-
cies, displacement angle of source , i.e., , is considered as
follows:

(26)

where is a constant scaling coefficient, is the damping


time constant, and is the slip frequency. Power system
frequency is 50 Hz and it is sampled at 2 kHz. The data of the
power system, shown in Fig. 1, are: , ,
, , . The
power system condition during power swing is: Fault posi-
tion=100% of the line length, Load angle= , Fault inception
Fig. 6. Frequency responses of second-order Taylor-Fourier (dynamic phasor).
time=1 s, Fault duration=0.2 s, Swing frequency=5 Hz.
The impedance locus for this condition is determined and
shown in Fig. 7(a). According to this figure, the impedance starts
errors. This figure clearly indicates the direct relationship of to move at =0.4 s and enters into the protective relay's charac-
the error standard deviation and noise variance, meanwhile its teristics of distance relay due to the power swing. In this condi-
inverse relationship with the sampling frequency. tion, the distance relay is blocked to avoid inadvertent tripping
during power swing; meanwhile, a fault occurs at =1 s. So
C. Harmonic and Frequency Analysis
the impedance leaves the power swing locus immediately and
Frequency analysis illustrates the relationship between the reaches to the fault impedance point at =1.06 s. Distance relay
input signal and output signal in the frequency domain. It is done should detect this condition and be unblocked.
by exciting the estimator with a complex exponential sequence TM calculated by dynamic phasor which is proposed in this
signal , where is fundamental angular frequency and paper is used to detect this condition. TM calculation procedure
is the harmonic order). for current dynamic phasor is shown step by step in Fig. 7(b).
The frequency response of dynamic phasor estimation The value of TM during power swing is negligible due to the
method is shown in Fig. 6. As shown in this figure, the mag- high accuracy of dynamic phasor estimation as demonstrated
nitude response is unsymmetrical. This is well explained by before. When three-phase fault is initiated , TM shows
the fact that the asymmetries belong to complex filters. It an upward trend due to a series of windows in phasor estima-
is apparent when the input signal corresponds to a constant tion process which contain both pre-fault and fault data [shaded
amplitude and constant phase signal that this method works boxes in Fig. 7(b)]. According to this figure, by determining a
properly with a gain equal to 1 p.u. in the magnitude response. low threshold value, the proposed method can detect the fault
This frequency domain analysis simply shows the advantage of during a power swing, accurately.
dynamic phasor method in comparison to the static phasor in In order to examine the accuracy of the proposed method
oscillating condition. in detecting a fault during power swing, superimposed current
The main feature of an appropriate method is to provide a gain method is used and their corresponding results for three dif-
with value of 1 p.u. around the positive fundamental frequency ferent cases (based on Table I) are shown in Fig. 8. Super-
and a zero-gain in the negative fundamental frequency. This is imposed method is based on extracting superimposed compo-
mainly because the signal model corresponds to two rotary com- nent, created at fault time. The changes created during transi-
ponents; the first one rotates at positive and the second one ro- tion from a normal state to a fault state in a power system com-
tates at negative fundamental frequency. Therefore, complete monly known as superimposed component could be considered
elimination of negative and complete passing of positive signal as an index to distinguish the fault. This component is calcu-
is the main duty of the method. This feature could be accessible lated based on subtracting the expected no-fault current sample
by the dynamic phasor concept as shown in Fig. 6. The flatter from the latest measured sample [8].
KHODAPARAST AND KHEDERZADEH: THREE-PHASE FAULT DETECTION DURING POWER SWING BY TRANSIENT MONITOR 2563

TABLE I
DIFFERENT CASES FOR COMPARISON BETWEEN PROPOSED
AND SUPERIMPOSED METHOD

Fig. 8. Comparison of the proposed and superimposed methods in different


cases based on Table I. (a) Case 1. (b) Case 2. (c) Case 3.

. Therefore, the reliability of the superimposed


method in this condition is very low.
Case 3) Regarding Fig. 8(c), a three-phase fault is initiated
with during a power swing with frequency
of 2 Hz. Superimposed method actually loses its
ability to detect the fault during power swing, while
the proposed method operates successfully in this
condition like the previous cases.

E. Results for the WSCC


For evaluation of the proposed method's performance in a
large system, three-machine WSCC is considered and simulated
Fig. 7. Step by step evaluation of the proposed fault detection method. (a) Z in MATLAB [Fig. 9(a)] [13]. Distributed models are used for
locus of power swing, (b) Current transient monitor. transmission lines, and saturation effect is considered for trans-
formers. A distance relay is considered at bus-8 on line 8–9. A
three-phase fault is simulated on line 6–9 at 0.6 s and is cleared
Case 1) Regarding Fig. 8(a), both methods show appropriate after 0.05 s by opening the breakers of both ends (CB1, CB2).
behavior in this condition. By allocating threshold This event causes a power swing on line 8–9 and is observed by
about 0.3 for superimposed method, three-phase relay R. Needless to say, any fault on line 8–9 during a power
fault can be detected correctly. This value is about swing should also be detected immediately. During this power
0.01 for the proposed method. swing, a three-phase fault occurs on this line at 1.5 s, 400 km
Case 2) Regarding Fig. 8(b), the proposed method can de- far away from relay R. The voltage waveform of phase-A seen
tect the fault accurately as the previous case but by R is shown in Fig. 9(b).
superimposed method needs a high value for the For verification of the proposed method in different condi-
threshold (about 0.8) which is due to the high angle tions, six different cases are considered (as listed in Table II)
difference between the two machine voltages and the corresponding results are shown in Figs. 10 and 11.
2564 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 30, NO. 5, SEPTEMBER 2015

Fig. 10. TMs of different cases A, B, C, and D based on Table II for WSCC.

Fig. 11. TMs of different cases E and F based on Table II for WSCC.

Fig. 9. WSCC simulation. (a) Single-line. (b) Phase A bus voltage measured
by relay R for inception of fault at 1.5 s during power swing started at 0.65 s.

TABLE II
DIFFERENT STUDY CASES DURING POWER SWING FOR WSCC

Fig. 12. Threshold values of different presented methods.

According to Fig. 10, the threshold value is determined around to Fig. 11, where Case E is for a two-phase fault and Case F is
0.7 A based on different switching simulations to improve the for a single-phase fault during a power swing.
security of the proposed method during a noisy condition (Case
B) and a load increasing (Case D) event. The proposed method F. Comparison With Other Methods
operates successfully in harmonic condition (Case A) because Three common methods in discriminating fault from power
Fourier-Taylor method of phasor estimation removes harmonic swing are considered for comparison. These are proposed in
from the output. In the compensated line condition (Case C), [15] (method 1), in [14] (method 2), and in [11] (method 3).
the threshold value of 0.7 A is also appropriate. Detecting The methods 1, 2, and 3 and the proposed method are applied
unsymmetrical faults during power swing is best employed to WSCC and the results are presented in Fig. 12. According to
by using negative sequence component. The proposed method Fig. 12, the proposed method provides the least threshold value,
also behaves satisfactorily for unsymmetrical faults according so it is the most reliable method.
KHODAPARAST AND KHEDERZADEH: THREE-PHASE FAULT DETECTION DURING POWER SWING BY TRANSIENT MONITOR 2565

VI. CONCLUSION [14] X. Lin, Y. Gao, and P. Liu, “A novel scheme to identify symmetrical
fault occurring during power swings,” IEEE Trans. Power Del., vol.
During a power swing, the trajectory of the apparent 21, no. 1, pp. 73–78, Jan. 2008.
impedance seen by a distance relay may enter into its operating [15] B. Mahamedi and J. Zhu, “A novel approach to detect symmetrical
zones, thereby appearing as a fault and causing inadvertent faults occurring during power swings by using frequency components
of instantaneous three phase active power,” IEEE Trans. Power Del.,
relay operation, which may lead to unwanted consequences and
vol. 27, no. 3, pp. 1368–1376, Jul. 2012.
affect the system's security. [16] H. Zade and Z. Li, “A novel power swing blocking scheme using adap-
Power swing blocking unit is designed to prevent this mal- tive neuro-fuzzy inference system,” Electr. Power Syst. Res., vol. 78,
function in the distance relay. However, if a fault occurs during no. 7, pp. 1138–1146, 2008.
[17] J. A. de la o serna, “Dynamic phasor estimates for power system oscil-
stable or unstable power swing, it should be detected and it is lations,” IEEE Trans. Instrum. Meas., vol. 56, no. 5, pp. 1648–1657,
necessary to unblock the relay. In this paper, a new method is Oct. 2007.
presented to detect a symmetrical fault during a power swing. [18] IEEE Standard for Synchrophasors for power system, IEEE Std. C37.
The proposed approach is based on the transient variations at 118—2005, sponsored by the power system relaying committee.
[19] M. Platas and J. Serna, “Dynamic phasor and frequency estimates
the beginning of the fault inception time that could be well cap- through maximally flat differentiators,” IEEE Trans. Instrum. Meas.,
tured by transient monitor extracted by dynamic phasor estima- vol. 59, no. 7, pp. 1803–1811, Jul. 2010.
tion method. The transient monitor index is introduced to dif- [20] R. Mai, Z. He, L. Fu, B. Kirby, and Z. Bo, “A dynamic synchrophasor
estimation algorithm for online application,” IEEE Trans. Power Del.,
ferentiate between the fault and power swing. For validation of vol. 25, no. 2, pp. 570–578, Apr. 2010.
the proposed method, different fault locations, swing frequen- [21] J. Serna, “Phasor estimation from phasorlets,” IEEE Trans. Instrum.
cies, and fault inception times (different ) are examined during Meas., vol. 54, no. 1, pp. 134–143, Feb. 2005.
the power swing period. According to the results, the proposed [22] J. serna and J. Rodriguez-Maldonado, “Instantaneous oscillating
phasor estimates with Taylor-Kalman filters,” IEEE Trans. Power
method demonstrates its ability to unblock distance relay in dif- Syst., vol. 26, no. 4, pp. 2336–2344, Nov. 2011.
ferent relevant conditions. [23] J. serna and J. Rodriguez-Maldonado, “Taylor-Kalman-Fourier filters
for instantaneous oscillating phasor and harmonic estimates,” IEEE
REFERENCES Trans. Instrum. Meas., vol. 61, no. 4, pp. 941–951, Apr. 2012.
[24] A. Munoz and J. Serna, “Shank method for dynamic phasor estima-
[1] P. Kundu and K. Pradhan, “Synchrophasor-assisted zone 3 operation,”
tion,” IEEE Trans. Instrum. Meas., vol. 57, no. 4, pp. 813–819, Apr.
IEEE Trans. Power Del., vol. 29, no. 2, pp. 660–667, Apr. 2014.
2008.
[2] J. Blumschein, Y. Yelgin, and M. Kereit, “Blackout prevention by
[25] A. G. Phadke and J. S. Thorp, Synchronized Phasor Measurements and
power swing detection and out-of-step protection,” J. Power Energy
Their Applications. New York, NY, USA: Springer, 2008, ch. 2, pp.
Eng., vol. 2, pp. 694–703, Apr. 2014.
39–45.
[3] Power grid, “Report on the Grid Disturbance on 30th and 31th July
2012,” CERC Order in Petition, no. 167, Aug. 1, 2012.
[4] S. Lim, C. Liu, J. Lee, M. Choi, and S. Rim, “Blocking of zone 3 relays
to prevent cascaded events,” IEEE Trans. Power Syst., vol. 23, no. 2,
pp. 747–753, May 2008. Jalal Khodaparast was born in Iran in 1987. He re-
[5] IEEE PSRC WG D6, “Power swing and out of step considerations on ceived the B.Sc. and M.Sc. degrees in electrical en-
transmission lines,” A Report to Power System Relaying Committee of gineering from Shahrood University of Technology,
The IEEE Power Engineering Society, 2005. Shahrood, Iran, in 2008 and 2010, respectively, and is
[6] B. Su et al., “Fast detector of symmetrical fault during power swing currently pursuing the Ph.D. degree in the Electrical
for distance relay,” in Proc. IEEE Power Eng. Soc. General Meeting, and Computer Engineering Department, Abbaspour
2005, pp. 1836–1841. Collage of Technology, Shahid Beheshti University,
[7] S. Brahma, “Distance relay with out of step blocking function using Tehran, Iran.
wavelet transform,” IEEE Trans. Power Del., vol. 22, no. 3, pp. His research interests are wide area protection,
1360–1366, Jul. 2007. flexible AC transmission systems (FACTS), power
[8] C. Pang and M. Kezunovic, “Fast distance relay scheme for detecting system dynamics, digital signal processing, power
symmetrical fault during power swing,” IEEE Trans. Power Del., vol. electronics, and power quality.
25, no. 4, pp. 2205–2212, Oct. 2010.
[9] J. Ganeswara and A. Pradhan, “Differential power based symmetrical
fault detection during power swing,” IEEE Trans. Power Del., vol. 27,
no. 3, pp. 1557–11564, Jul. 2012. M. Khederzadeh (SM'06) received the B.Sc. degree
[10] L. Fu, Z. He, R. Mai, and Z. Bo, “Approximate entropy and its appli- in electrical engineering from Sharif University of
cation to fault detection and identification in power swing,” in Proc. Technology, Tehran, Iran, in 1980, the M.Sc. degree
IEEE Power Eng. Soc. General Meeting, 2006, pp. 1–8. in electrical engineering from Tehran University,
[11] A. Apostolov, D. Tholomier, and S. Richard, “Superimposed compo- Tehran, Iran, in 1990, and the Ph.D. degree in
nents based sub-cycle protection of transmission lines,” in Proc. IEEE electrical engineering from Sharif University of
Power Eng. Soc. General Meeting Power Syst. Conf. Expo., 2004, pp. Technology in 1996.
592–597. He was a Postdoctoral Fellow with the University
[12] S. Lofifard, J. Faiz, and M. Kezunovic, “Detection of symmetrical of Western Ontario, London, ON, Canada, from 2004
faults by distance relays during power swings,” IEEE Trans. Power to 2005. Currently, he is an Associate Professor and
Del., vol. 25, no. 1, pp. 81–87, Jan. 2010. Director of the Power System Protection and Control
[13] P. Nayak and P. Bajpai, “A fault detection technique for the series- Research Center, Electrical and Computer Engineering Department, Shahid Be-
compensated line during power swing,” IEEE Trans. Power Del., vol. heshti University, Tehran, Iran. His research interests include power system pro-
28, no. 2, pp. 714–722, Apr. 2013. tection, control and monitoring, and power system dynamics.

You might also like