Professional Documents
Culture Documents
Three-Phase Fault Detection During Power Swing by Transient Monitor
Three-Phase Fault Detection During Power Swing by Transient Monitor
5, SEPTEMBER 2015
Abstract—Distance relays are immune to inadvertent operation power swing, the PSB should differentiate it from power swing
during power swings by a block known as “power swing blocking to unblock relay. Due to the presence of the negative and zero
(PSB)”. Its main function is discriminating faults from power sequences, the detection procedure of unsymmetrical faults is
swings. However, if a fault occurs during a power swing, PSB
easier than that of symmetrical ones.
should be de-blocked and let the distance relay to operate normally
and clear the fault accordingly. Meanwhile, discrimination of a Different methods are proposed to solve this problem. Power
three-phase fault from a power swing is the most difficult task due swing center voltage (SCV) is a method which is proposed in
to their likelihood. This paper proposes a new method to overcome [6], but has the difficulty in choosing an appropriate threshold;
this issue by monitoring the transient period established in the meanwhile, it has a relatively long detection time (two cycles).
process of current dynamic phasor estimation. In this regard, Wavelet transform utilization is introduced in [7]; however,
transient monitor (TM) index, which is the difference between the it needs relatively high sampling rate (40.96 KHz). In [8], a
estimated current samples regenerated from the calculated dy-
method based on extracting the high frequency component en-
namic phasors and the actual sample values, is used to distinguish
the fault from the power swing. Fourier-Taylor transformation ergy of the forward and backward traveling waves is proposed.
is applied to estimate the dynamic phasor of the current signal. Differential power based fault detection technique is also pro-
Simulation results verify the inherent potential of the proposed posed, which makes use of auto regression technique to predict
method to overcome the issue. the future samples [9]; however, it needs a lot of simulations
Index Terms—Distance relay, dynamic phasor, power swing to select the appropriate parameters of the regression method.
blocking, three-phase fault, transient monitor. Approximate entropy of the signal to detect the fault during the
power swing is proposed in [10]. In [11], superposition the-
orem is used for detection of direction, selection of the faulted
I. INTRODUCTION phase, and detection of power swing. While the method does
not require complicated mathematical operations, setting the
P OWER systems are prone to faults, which should be iden- threshold value is a difficult task. Another method is proposed
tified and cleared in due time to protect the equipments in [12] that uses the decaying dc component of the fault current,
and allow normal operation of the system, thereafter. Distance extracted by the Prony analysis as an index of presence of a
relay is used to protect the transmission line by measuring the fault. In [13], a technique based on negative sequence compo-
apparent impedance in order to estimate the distance to fault. nent of the current signal is used for detecting all types of faults;
Power swing is a phenomenon that creates large fluctuations of however, it is applicable only to compensated lines. In [14],
active and reactive powers between two areas of an electrical a method based on the maximum change rate of three-phase
system following severe disturbances such as line faults, loss of active and reactive powers is proposed, which is zero during
generating units, and switching heavy loads. It could affect the fault and higher than 0.7 during power swing; nevertheless,
distance relay's behavior, which may result in the relay malfunc- the method ignores the resistive component of the impedance.
tion. Recent blackouts indicate the involvement of Zone 3 of Another method is proposed in [15] based on detection of the
distance relays during system stressed conditions such as power fundamental frequency component created on the instantaneous
swings [1]–[5]. three-phase active power after inception of a symmetrical fault;
The main task of power swing blocking (PSB) unit is to pre- however, it assumes that the fault resistance is negligible. In
vent unintended operation of the relay during stable or unstable [16], an adaptive neuro-fuzzy inference system is proposed that
power swing. The most common technique in order to detect a in spite of its fast response, re-training is required whenever the
power swing is based on different rates of impedance changes. power system experiences major changes.
In other words, when a fault occurs, the impedance change rate In this paper, an index named transient monitor (TM) is used
from a normal-load point to fault-point is significantly faster as an indicator of a fault during a power swing. The proposed
than power swing condition [5]. When a fault occurs during a method is based on comparing the calculated TM and the speci-
fied threshold. It will detect the fault whenever the TM exceeds
the predetermined threshold during a power swing. As phasor
Manuscript received March 16, 2014; revised July 01, 2014 and September
estimation is the major part of this index calculation, dynamic
14, 2014; accepted October 13, 2014. Date of publication November 06, 2014;
date of current version July 17, 2015. Paper no. TPWRS-00372-2014. phasors are used to enhance the performance of the method. The
The authors are with the Faculty of Electrical and Computer Engineering, threshold value is determined by phasor estimation accuracy. As
Shahid Beheshti University, Tehran 1658953571, Iran (e-mail: J_Khoda- dynamic phasors are used to extract the signals, so the threshold
parast@sbu.ac.ir; khederzadeh@pwut.ac.ir).
Color versions of one or more of the figures in this paper are available online
value is reduced.
at http://ieeexplore.ieee.org. Traditionally, the phasor is defined for steady state sinusoidal
Digital Object Identifier 10.1109/TPWRS.2014.2365511 signals with constant amplitude and phase. However, the power
0885-8950 © 2014 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
KHODAPARAST AND KHEDERZADEH: THREE-PHASE FAULT DETECTION DURING POWER SWING BY TRANSIENT MONITOR 2559
II. POWER SWING AND FAULT DURING POWER SWING III. TRANSIENT MONITOR
The effect of power swing on the performance of distance TM is introduced to examine the quality of phasor estimation.
relay is well described by a simple two-machine model as shown It is actually the difference of real input samples and the recom-
in Fig. 1. and are the voltages behind transient reac- puted samples obtained by phasor estimation [25]. A sinusoidal
tances with constant magnitude and variable phase during a signal is described as
power swing. leads by the angle . Bus B is supposed
as an infinite bus and as the total impedance (including trans- (2)
mission line and transient reactances of the machines); thereby, where is the amplitude of signal , is the sample number,
the apparent impedance seen by the distance relay is is the phase angle in radians, and ( is the sample
per cycle). Conventional (static) phasor is expressed as
(1) (3)
Equation (4) is a discrete time signal because the last inserted sample is noticeably different from the
in terms of static phasor's Taylor-Fourier coefficients others:
and represents the conjugate operator. These coef-
ficients are estimated from the least square method: (13)
(11)
(19)
However, when a fault occurs during the power swing, the input
signal of phasor estimation process is considered as
where is the starting sample of a fault, is the amplitude, where are constant parameters. The accuracy
and . When the first sample of the fault is of phasor estimation obtained by dynamic phasor is higher than
observed in the data window, is not equal to zero anymore, static one due to consideration of first and second derivatives of
KHODAPARAST AND KHEDERZADEH: THREE-PHASE FAULT DETECTION DURING POWER SWING BY TRANSIENT MONITOR 2561
V. SIMULATION RESULTS
Fig. 3. Flowchart of the proposed method. Simulations are performed for different operating conditions
with dynamic phasor estimation during power swing and three-
phase fault.
the phasor. The result of (20) is approximately zero like (10), but
its value is relatively lower than (10), which represents lower A. Evaluation of Dynamic Phasor Estimation
TM for dynamic phasor during power swing compared to the
Test signal (25) is used to validate the proposed method in
static one.
estimating the dynamic phasor in power swing condition:
In this paper, dynamic phasor of currents is calculated based
on second-order Taylor-Fourier method and TM index is used (25)
to detect three-phase fault during power swing. Current signal is
considered as input signal because its TM is higher than voltage. where
A flowchart of proposed method is shown in Fig. 3.
Fig. 5. Effect of variance and frequency sampling on standard deviation of D. Fault Detection During Power Swing
dynamic phasor estimation error.
To demonstrate the proposed fault detection method, a series
of simulations are carried out on a two-machine system, shown
in Fig. 1. To excite the power swing with different slip frequen-
cies, displacement angle of source , i.e., , is considered as
follows:
(26)
TABLE I
DIFFERENT CASES FOR COMPARISON BETWEEN PROPOSED
AND SUPERIMPOSED METHOD
Fig. 10. TMs of different cases A, B, C, and D based on Table II for WSCC.
Fig. 11. TMs of different cases E and F based on Table II for WSCC.
Fig. 9. WSCC simulation. (a) Single-line. (b) Phase A bus voltage measured
by relay R for inception of fault at 1.5 s during power swing started at 0.65 s.
TABLE II
DIFFERENT STUDY CASES DURING POWER SWING FOR WSCC
According to Fig. 10, the threshold value is determined around to Fig. 11, where Case E is for a two-phase fault and Case F is
0.7 A based on different switching simulations to improve the for a single-phase fault during a power swing.
security of the proposed method during a noisy condition (Case
B) and a load increasing (Case D) event. The proposed method F. Comparison With Other Methods
operates successfully in harmonic condition (Case A) because Three common methods in discriminating fault from power
Fourier-Taylor method of phasor estimation removes harmonic swing are considered for comparison. These are proposed in
from the output. In the compensated line condition (Case C), [15] (method 1), in [14] (method 2), and in [11] (method 3).
the threshold value of 0.7 A is also appropriate. Detecting The methods 1, 2, and 3 and the proposed method are applied
unsymmetrical faults during power swing is best employed to WSCC and the results are presented in Fig. 12. According to
by using negative sequence component. The proposed method Fig. 12, the proposed method provides the least threshold value,
also behaves satisfactorily for unsymmetrical faults according so it is the most reliable method.
KHODAPARAST AND KHEDERZADEH: THREE-PHASE FAULT DETECTION DURING POWER SWING BY TRANSIENT MONITOR 2565
VI. CONCLUSION [14] X. Lin, Y. Gao, and P. Liu, “A novel scheme to identify symmetrical
fault occurring during power swings,” IEEE Trans. Power Del., vol.
During a power swing, the trajectory of the apparent 21, no. 1, pp. 73–78, Jan. 2008.
impedance seen by a distance relay may enter into its operating [15] B. Mahamedi and J. Zhu, “A novel approach to detect symmetrical
zones, thereby appearing as a fault and causing inadvertent faults occurring during power swings by using frequency components
of instantaneous three phase active power,” IEEE Trans. Power Del.,
relay operation, which may lead to unwanted consequences and
vol. 27, no. 3, pp. 1368–1376, Jul. 2012.
affect the system's security. [16] H. Zade and Z. Li, “A novel power swing blocking scheme using adap-
Power swing blocking unit is designed to prevent this mal- tive neuro-fuzzy inference system,” Electr. Power Syst. Res., vol. 78,
function in the distance relay. However, if a fault occurs during no. 7, pp. 1138–1146, 2008.
[17] J. A. de la o serna, “Dynamic phasor estimates for power system oscil-
stable or unstable power swing, it should be detected and it is lations,” IEEE Trans. Instrum. Meas., vol. 56, no. 5, pp. 1648–1657,
necessary to unblock the relay. In this paper, a new method is Oct. 2007.
presented to detect a symmetrical fault during a power swing. [18] IEEE Standard for Synchrophasors for power system, IEEE Std. C37.
The proposed approach is based on the transient variations at 118—2005, sponsored by the power system relaying committee.
[19] M. Platas and J. Serna, “Dynamic phasor and frequency estimates
the beginning of the fault inception time that could be well cap- through maximally flat differentiators,” IEEE Trans. Instrum. Meas.,
tured by transient monitor extracted by dynamic phasor estima- vol. 59, no. 7, pp. 1803–1811, Jul. 2010.
tion method. The transient monitor index is introduced to dif- [20] R. Mai, Z. He, L. Fu, B. Kirby, and Z. Bo, “A dynamic synchrophasor
estimation algorithm for online application,” IEEE Trans. Power Del.,
ferentiate between the fault and power swing. For validation of vol. 25, no. 2, pp. 570–578, Apr. 2010.
the proposed method, different fault locations, swing frequen- [21] J. Serna, “Phasor estimation from phasorlets,” IEEE Trans. Instrum.
cies, and fault inception times (different ) are examined during Meas., vol. 54, no. 1, pp. 134–143, Feb. 2005.
the power swing period. According to the results, the proposed [22] J. serna and J. Rodriguez-Maldonado, “Instantaneous oscillating
phasor estimates with Taylor-Kalman filters,” IEEE Trans. Power
method demonstrates its ability to unblock distance relay in dif- Syst., vol. 26, no. 4, pp. 2336–2344, Nov. 2011.
ferent relevant conditions. [23] J. serna and J. Rodriguez-Maldonado, “Taylor-Kalman-Fourier filters
for instantaneous oscillating phasor and harmonic estimates,” IEEE
REFERENCES Trans. Instrum. Meas., vol. 61, no. 4, pp. 941–951, Apr. 2012.
[24] A. Munoz and J. Serna, “Shank method for dynamic phasor estima-
[1] P. Kundu and K. Pradhan, “Synchrophasor-assisted zone 3 operation,”
tion,” IEEE Trans. Instrum. Meas., vol. 57, no. 4, pp. 813–819, Apr.
IEEE Trans. Power Del., vol. 29, no. 2, pp. 660–667, Apr. 2014.
2008.
[2] J. Blumschein, Y. Yelgin, and M. Kereit, “Blackout prevention by
[25] A. G. Phadke and J. S. Thorp, Synchronized Phasor Measurements and
power swing detection and out-of-step protection,” J. Power Energy
Their Applications. New York, NY, USA: Springer, 2008, ch. 2, pp.
Eng., vol. 2, pp. 694–703, Apr. 2014.
39–45.
[3] Power grid, “Report on the Grid Disturbance on 30th and 31th July
2012,” CERC Order in Petition, no. 167, Aug. 1, 2012.
[4] S. Lim, C. Liu, J. Lee, M. Choi, and S. Rim, “Blocking of zone 3 relays
to prevent cascaded events,” IEEE Trans. Power Syst., vol. 23, no. 2,
pp. 747–753, May 2008. Jalal Khodaparast was born in Iran in 1987. He re-
[5] IEEE PSRC WG D6, “Power swing and out of step considerations on ceived the B.Sc. and M.Sc. degrees in electrical en-
transmission lines,” A Report to Power System Relaying Committee of gineering from Shahrood University of Technology,
The IEEE Power Engineering Society, 2005. Shahrood, Iran, in 2008 and 2010, respectively, and is
[6] B. Su et al., “Fast detector of symmetrical fault during power swing currently pursuing the Ph.D. degree in the Electrical
for distance relay,” in Proc. IEEE Power Eng. Soc. General Meeting, and Computer Engineering Department, Abbaspour
2005, pp. 1836–1841. Collage of Technology, Shahid Beheshti University,
[7] S. Brahma, “Distance relay with out of step blocking function using Tehran, Iran.
wavelet transform,” IEEE Trans. Power Del., vol. 22, no. 3, pp. His research interests are wide area protection,
1360–1366, Jul. 2007. flexible AC transmission systems (FACTS), power
[8] C. Pang and M. Kezunovic, “Fast distance relay scheme for detecting system dynamics, digital signal processing, power
symmetrical fault during power swing,” IEEE Trans. Power Del., vol. electronics, and power quality.
25, no. 4, pp. 2205–2212, Oct. 2010.
[9] J. Ganeswara and A. Pradhan, “Differential power based symmetrical
fault detection during power swing,” IEEE Trans. Power Del., vol. 27,
no. 3, pp. 1557–11564, Jul. 2012. M. Khederzadeh (SM'06) received the B.Sc. degree
[10] L. Fu, Z. He, R. Mai, and Z. Bo, “Approximate entropy and its appli- in electrical engineering from Sharif University of
cation to fault detection and identification in power swing,” in Proc. Technology, Tehran, Iran, in 1980, the M.Sc. degree
IEEE Power Eng. Soc. General Meeting, 2006, pp. 1–8. in electrical engineering from Tehran University,
[11] A. Apostolov, D. Tholomier, and S. Richard, “Superimposed compo- Tehran, Iran, in 1990, and the Ph.D. degree in
nents based sub-cycle protection of transmission lines,” in Proc. IEEE electrical engineering from Sharif University of
Power Eng. Soc. General Meeting Power Syst. Conf. Expo., 2004, pp. Technology in 1996.
592–597. He was a Postdoctoral Fellow with the University
[12] S. Lofifard, J. Faiz, and M. Kezunovic, “Detection of symmetrical of Western Ontario, London, ON, Canada, from 2004
faults by distance relays during power swings,” IEEE Trans. Power to 2005. Currently, he is an Associate Professor and
Del., vol. 25, no. 1, pp. 81–87, Jan. 2010. Director of the Power System Protection and Control
[13] P. Nayak and P. Bajpai, “A fault detection technique for the series- Research Center, Electrical and Computer Engineering Department, Shahid Be-
compensated line during power swing,” IEEE Trans. Power Del., vol. heshti University, Tehran, Iran. His research interests include power system pro-
28, no. 2, pp. 714–722, Apr. 2013. tection, control and monitoring, and power system dynamics.