Ahu Performance Test
Ahu Performance Test
• PURPOSE:
• SCOPE:
• RESPONSIBILITY:
Engg. Dept.
• PROCEDURE:
1.1 AHU performance must be studied for all clean rooms by outside party
using calibrated laser based particle counter.
1.3 This test should be carried out for Non-unidirectional airflow systems
because the recovery performance is a function of air re-circulation ratio,
inlet-outlet airflow geometry, thermal conditions and the air distribution
characteristics within the controlled zone.
1.4.2 Calculate the no. Of locations as per ISO guidelines using formula
NL=√ Area
1.4.4 Put OFF the AHU starts taking reading after 5 minutes. Note down
the time taken to cross the ISO class limits.
1.4.5 Switch ON the AHU, start taking reading note down the time taken
to regain the initial condition.
1.4.7.3 The slope value of the tangent line represents the recovery
performance.