You are on page 1of 20

A1700 Programmable

Polyphase Meter
Chapter 5 - Input/Output

M120 001 5S
5.2007

A1700 Chapters

Chapter 1 Introduction M120 001 1


Chapter 2 Over view M120 001 2
Chapter 3 Hardware M120 001 3
Chapter 4 Communications M120 001 4
Chapter 5 Input/Output M120 001 5
Chapter 6 Installation M 120 0016
Chapter 7 Software Support M120 001 7
Chapter 8 IEC 870 Meter (Special) M120 001 8
Chapter 9 T. L. Compensation (Special) M120 001 9
A1700 Users Manual - Chapter 5 1
________________________________________________________________________

CONTENTS

1 SCOPE ........................................................................................................................... 3

2 WARNINGS, CE MARKING AND EMC......................................................................... 3


2.1 Handling.......................................................................................................................... 4
2.2 CE Mark.......................................................................................................................... 4
2.3 Electromagnetic Compatibility (EMC)............................................................................. 5

3 OUTPUT RELAY MODULE ........................................................................................... 6


3.1 Relay Functions .............................................................................................................. 6
3.2 Mechanical...................................................................................................................... 6
3.3 Module Terminal Connections........................................................................................ 7
3.4 Technical Information ..................................................................................................... 7
3.5 Output Module Installation and Removal ....................................................................... 8
3.5.1 Output Module Installation.............................................................................................. 8
3.5.2 Removing an Output Module.......................................................................................... 8

4 INPUT MODULE ............................................................................................................ 9


4.1 Features.......................................................................................................................... 9
4.2 Normal Operation ........................................................................................................... 9
4.3 Power Failure................................................................................................................ 10
4.4 Cumulative Register ..................................................................................................... 10
4.5 Load Profile Recording ................................................................................................. 10
4.6 Load Profile Recording (Power Failure) ....................................................................... 11
4.7 Customer Defined Registers ........................................................................................ 11
4.8 Customer Defined Registers (Power Failure)............................................................... 12
4.9 Input Module Displays .................................................................................................. 12
4.10 Battery Back-up ............................................................................................................ 13
4.11 External End of Integration Input Overview.................................................................. 13
4.12 Terminal Connections................................................................................................... 14
4.13 Technical Data.............................................................................................................. 14
Battery Warning ............................................................................................................ 15
4.14 Installing and Removing Modules................................................................................. 15
4.14.1 Installing and Configuring an Input Module .................................................................. 15
4.14.2 Removing an Input Module........................................................................................... 17
4.14.3 Checking Input Module Operation ................................................................................ 18
4.14.4 Wiring External Meters to the A1700 Meter Inputs....................................................... 18

© Elster Metering Limited - M120 001 5S - 5/2007


2 A1700 Users Manual - Chapter 5
____________________________________________________________________

FORWARD

HEALTH AND SAFETY WARNING

Compliance with Instructions in this Manual


The instructions and information in this manual are provided in compliance with Section 6 of
the UK Health and Safety at Work Act, as amended by Schedule 3 of the Consumer
Protection Act 1987.

The purchaser is responsible for making sure that everyone, whether in his employment or
not, who will be associated with the products supplied by Elster Metering Systems, and to
which these instructions and information apply, are made
familiar with the contents of this manual.

This applies to all persons who may be involved in activities such as unpacking, inspecting,
testing, setting, cleaning, installing, commissioning, operating, maintaining, decommissioning
or disposing of the products.

Safety of Persons using Electrical Products


Employers are reminded that they have a duty to ensure, as far as is reasonably practicable,
the Health, Safety and Welfare at work of all their Employees. Employers must therefore
ensure that employees are informed, trained and supervised and use proper working
procedures to ensure the safety of themselves and others. The information provided in this
manual is intended to ensure that products are properly installed and otherwise handled in
order to maintain them in a safe condition.

In the UK, employers have duties under the Health and Safety at Work Act 1974 and the
various regulations stemming therefrom.

In countries outside the UK, employers should ensure proper compliance with the Health and
Safety Legislation which is applicable to them.

Putting into Service


Products supplied by Elster Metering Systems have been designed and manufactured, in
accordance with appropriate standards, to operate under specified conditions, when properly
installed.

The purchaser or delegated contractor is responsible for the "Putting into Service" of any
Elster Metering Systems products which have been supplied as "Non-connected". All
related activities must therefore be carried out with due regard to any applicable legislation,
standards and good practice.

© Elster Metering Limited - M120 001 5S - 5/2007


Input/Output Modules 3
___________________________________________________________________

Input/Output Modules
1 SCOPE
This Chapter covers the operation and installation of the following modules:
Input Modules MODVAL-K (two summations) and MODVAL-L (five summations)
Output module type MODVAB (three solid state relays plus one 5A relay) and output module
type MODVAC (four solid state relays).
Before installing a module, read the Safety Warnings, Warnings, Precautions for handling
electrostatic discharge sensitive devices and EMC Guidelines below.

2 WARNINGS, CE MARKING AND EMC

SAFETY WARNINGS

Installation must always be carried out by appropriately trained and qualified personnel, in
accordance with normal metering custom and practice.
Only use the authorised utility procedures to install and service metering equipment.
The A1700 meter has a terminal cover plate to protect live meter terminals.
If the terminal cover plate is not fitted to the A1700 meter, all supplies to the meter must
be isolated before a module is installed or removed.
External circuits connected to the A1700 meter internal relay terminals may be at line
potential. Isolate all external circuits connected to the meter internal relay terminals before
installing a module.
Failure to do so may result in electric shock.
Cables at potential greater than 40Volts should remain segregated from those at lower
voltages.
The installer is responsible for ensuring that all connected cables are adequately rated for
the application and all signal circuits are adequately protected by fuses.

Battery Warning

The Input module (MODVAL-K(L) contains a Nickel-metal-hydride (Ni:MH) battery.


This battery is completely safe under normal conditions. However, it must never be
recharged except in accordance with manufacturer’s instructions, disassembled,
heated above 65° C, incinerated, or have the contents exposed to water. Fire,
explosion or severe burns may result if these instructions are disregarded.
In the interests of safety, environmental protection and possible legislation,
Ni-MH batteries require careful disposal.
Before arranging for the disposal of these cells, users should satisfy themselves that
the proposed means of disposal is both safe and compliant with local legislation
requirements.
4 A1700 Users Manual - Chapter 5
____________________________________________________________________

CAUTION

To ensure correct operation, the relay retransmit threshold must be no less than 2.5
times the (meter pulse value x CT Ratio x VT ratio). This will ensure that the maximum
relay output pulse rate (4Hz) is not exceeded.
Installation of a faulty module may affect the main meter functionality.

2.1 Handling

ELECTROSTATIC WARNING

Observe precautions for handling electrostatic discharge sensitive devices


When handling modules and module peripheral equipment described in this manual,
observe electrostatic discharge precautions at all times.
Avoid touching connector pins and printed circuit boards where the PCB is exposed.
Failure to adhere to this instruction may result in electrostatic damage, contamination
or corrosion.

2.2 CE Mark

A1700 meters and their internal modules delivered to customers for use in European
Economic Area (EU & EFTA) countries are CE marked to indicate compliance with the
requirements of the Electromagnetic Compatibility Directive.
This compliance has been demonstrated by subjecting representative samples of the
product, installed in accordance with the instructions and guidelines given in this
document, to the tests prescribed in the following standards :-

EN 61036:1996, Alternating current static watt-hour meters for active energy


(Class 1 and 2)
EN 50081-1:1992, Electromagnetic compatibility generic emission standard –
Part 1: Residential, Commercial and Light Industry
EN50082-1:1992, Electromagnetic compatibility generic immunity standard – Part
1: Residential, Commercial and Light Industry
EN60687:1993, Alternating current static watt-hour meters for active energy –
(Class 0.2s and 0.5s)
EN 61268:1996, Alternating current static var-hour meters for reactive energy
(Class 2 and 3)
The user can therefore be confident that, provided the guidelines and instructions are
properly followed, all units installed will satisfy the requirements for residential,
commercial and light industrial premises.
Elster Metering Systems holds on record the appropriate Declaration of Conformity,
and supporting documentation, against which the CE mark is affixed.

© Elster Metering Limited - M120 001 5S - 5/2007


Input/Output Modules 5
___________________________________________________________________

2.3 Electromagnetic Compatibility (EMC)


The input modules (MODVAL-K and MODVAL-L) and output modules (MODVAB and
MODVAC) have been designed and tested for compliance with the EMC and other applicable
directives.
It is, however, the responsibility of the installer for ensuring that a system conforms to the
directives.

In order to assist the installer the following guidelines are given:


1. Keep a.c. and d.c. circuits separated by a minimum of 50mm where possible
2. Where a.c. and d.c. circuits must cross, do so at right angles to each other
3. The cables for each circuit must be bunched together to minimise the loop area enclosed
4. The cables for the relay must use a twisted pair
5. Where the environment is electrically hostile, screened twisted pair cable may be
required. The screen must be connected to earth at one point only
6. Ancillary equipment must also be CE marked
7. If interposing relays are used (a.c. or d.c.) then these must be correctly and adequately
suppressed
6 A1700 Users Manual - Chapter 5
____________________________________________________________________

3 OUTPUT RELAY MODULE


There are two types of output modules available for use with the A1700 meter.
MODVAB - Three solid state relays and one 5A relay.
MODVAC - Four solid state relays.
The Output Module can be provided in addition to the A1700 meters four internal relays,
bringing the total number of relays available to eight.
Output modules are protected to isolation Class II.
For information on installing a module or removing a module, see Section 3.5.

3.1 Relay Functions


Each solid state relay is optically coupled and can be programmed to perform one of the
following functions:
1) Retransmit pulses: Wh total import/export, varh lagging/leading import/export,
Customer defined registers, VAh or input pulses. The nominal pulse value is 80msecs
2) Output a demand (integration) reset. The pulse width is 2.5 seconds
3) Output an end of billing reset. The pulse width is 2.5 seconds
4) Close a contact when designated time-of-use register is active
5) Close a contact if the demand alarm level will be exceeded. The alarm remains closed
until the next complete period with a lower demand. The contactor can be programmed
to close for 2 seconds at 90% of the programmed threshold
6) Close or open a contact when any combination of the alarm or monitoring events are set.
The relay can be set to latched or pulsed while the alarm is active. The alarm may be set
for the following conditions:
Option board error Battery fail Battery elapsed warning
Meter fault Reverse run warning Over current
Phase failure Partial demand Comm event
Time and date Voltage imbalance Instrumentation event
change (-U/1/2/3/4/5) (-1/2/3/4/5)
7) Power outage - closed when power present

The 5A relay (Type MODVAB) is intended for controlling an external load or contactor. It will
normally be programmed to operate when a designated time-of-use register is active or for an
alarm or monitoring event.

3.2 Mechanical
1. The meter must be already securely installed using all three fixing positions
2. The module terminals will accept a cable size of 1.5 sq mm maximum. The screws are
2.5mm diameter. In order not to stress the retainer inside the terminal the cable size
must not be less than 0.4 sq mm. Single strand wire is recommended but if multi-strand
wire is used, it must not be folded prior to insertion into the terminal
3. An appropriate fuse must protect output circuits that are connected to an a.c. supply
4. Check that all screws are tight

© Elster Metering Limited - M120 001 5S - 5/2007


Input/Output Modules 7
___________________________________________________________________

3.3 Module Terminal Connections

25 26 27 28 29 30 31 32

Relay 5* Relay 6 Relay 7 Relay 8

Type MODVAB - * Relay 5 rated 5A

3.4 Technical Information

Module Life 15 years (no maintenance is required)


Temperature Range - Operating -20°C to +55°C
- Storage -25°C to +70°C
Output relays - Type Volt free normally open contacts
MOD VAB Relay 5 1 - High Rating Relay
Relays 6 - 8 3 - Standard Relays
MOD VAC Relays 5 - 8 4 - Standard Relays

Standard Relay
Number of Operations (close/open cycle) > 109
Rating 240V a.c.
100mA
Recommended Minimum Load Impedance >6 kohms

Relay 5 (High Rating Relay)


Number of operations
Resistive Load 100,000 (18 operations/day)
240V, 5A, 0.4pf 30,000 (5 operations/day)
Rating 240V a.c. 5A

Relay Isolation Protective Class II


8 A1700 Users Manual - Chapter 5
____________________________________________________________________

3.5 Output Module Installation and Removal

3.5.1 Output Module Installation


1. Observe all Safety Warnings, Warnings, Precautions for handling
electrostatic discharge sensitive devices and EMC Guidelines in
Section 2
2. External circuits connected to the A1700 meter internal relay terminals
may be at line potential. Isolate all external circuits connected to the
meter internal relay terminals before removing a module
3. Remove the terminal cover from the meter
4. Make all module connections
5. Slide the module into the left module port as shown opposite, making
sure that the module clicks into place
6. Refit the terminal cover and fit appropriate seals

3.5.2 Removing an Output Module


1. Observe all Safety Warnings, Warnings, Precautions for handling
electrostatic discharge sensitive devices and EMC Guidelines in
Section 2
2. External circuits connected to the A1700 meter internal relay terminals
may be at line potential. Isolate all external circuits connected to the
meter internal relay terminals before removing a module
3. Remove the terminal cover from the meter
4. Disconnect all wires to the module terminals
5. Lift the hinged lid on the meter's main cover. Insert a 3mm electrician’s
screwdriver into the hole by the side of the module identifier and press
the clip. Grip the module as shown and pull downwards
6. Refit the terminal cover and fit appropriate seals

© Elster Metering Limited - M120 001 5S - 5/2007


Input/Output Modules 9
___________________________________________________________________

4 INPUT MODULE
Two versions of the input module are available.
MODVAL-K Data logging input for use with relay output and SO output (two summation
registers)
MODVAL-L (A1700 P******** -2/3/4/5 only) Data logging input for use with relay output and
SO output (five summation registers)
An Input Module can only be used with the multi-utility version of the A1700 meter. The
Module has four opto-isolated inputs that can be utilised for collecting pulses from external
meters, or for the creation of an event from external equipment such as end of billing reset.
The module interfaces to the left module slot of the A1700 meter. For information on
installing or removing a module, see Section 4.14.
Modules are isolated to protective Class II, IEC 61036.

4.1 Features
• Inputs for data collection from external meters
• Inputs for creation of end of billing and/or end of integration period
• Programmable scaling factor per input
• Records input pulses or engineering units
• Two (five) summations for each of three customer defined registers, allowing module
inputs to be combined or a module input to be combined with an A1700 internal register
• Input circuit detection without use of external power
• Pulse collection continues and load profile data is stored when power to meter is removed
• Class II isolation from meter

4.2 Normal Operation


The Input Module has four opto-isolated inputs Input Module
for collecting pulses from external equipment. In Input 1 (kWh)

normal operation these pulses are collected and Input 2 (Export kWh)

stored by the host meter. Input 3 (Gas)

Input 4 (Water)

Inputs can be accepted from any pulsing meter


including electricity, gas or water. Each input can
be independently programmed to be active or
inactive. When the input is active the following
parameters can be set:

Input set as pulse counter


Debounce setting 16ms to 136ms (8ms steps)
Transition setting Triggers on +ve or -ve edge
Scaling factor 0.001 (min) 99999.999 (max)
For pulse count Set scaling factor to 1
Initial offset Between 0 and 9999999999999.999
10 A1700 Users Manual - Chapter 5
____________________________________________________________________

Input set to record event


Each input can also be used to monitor an external event such as an alarm signal. The
event is recorded in the cumulative register by setting it to pulsed input with a scaling factor
of one. Recorded events can be used to retransmit information via the relays or can be
read via the meter communications ports.

4.3 Power Failure Input Module

In the event of a power failure to the host Input 1 Store Input 1

meter, the module stores the input pulses Input 2 Store Input 2

Input 3 Store Input 3


in internal registers. Input 4 Store Input 4
An internal battery supports the module for at Transfer on power-up
of A1700
least 48 hours when fully charged for a
maximum of 96 periods. 48 hour
Battery Back-up

Examples:
Integration period No. of periods Hours of storage
30 96 48
15 96 24
60 96 periods or until battery discharged

The module keeps a full record of demand periods, partial demands and cumulative totals
during the outage.
Once power has been restored, the register data is transferred to the host meter as load
profile data and the cumulative registers are updated. Any input that is configured to action
an End of Billing or End of Integration period is ignored during a power outage.

4.4 Cumulative Register


Each input has a Cumulative Register that can be initially Input Module A1700

offset to ensure the input register matches the reading of the


Input 4
external meter. In addition a scaling factor can be applied to Input 3
Input 2
each input. Cumulative registers can also be used as TOU Input 1
Total kWh Cumulative 1

registers or combined with Customer Defined Registers.


The display registration of these registers can be set TOU
Relay
Customer Defined
independently.
Display
Cumulative Register, TOU Register and Customer Defined
Register readings can be re-transmitted via the A1700
meter's relays.

A1700 Load
Input Module Profile Recording
4.5 Load Profile Recording
Each input and Customer Defined Register has an Input 1 Rising
Demand Registers

associated Rising Demand Register that is scaled by the Input 2

Input 3
30 minutes Reset

appropriate scaling factor. Input 4


Store Load
Profile Data

At the end of the integration period, load profiling is stored


in non-volatile memory. The Rising Demand Register is
then reset to zero.

© Elster Metering Limited - M120 001 5S - 5/2007


Input/Output Modules 11
___________________________________________________________________

Integration Period
The Integration Period of the module is aligned to the A1700 Integration Period in its
configuration data. The period may be configured to 1, 2, 3, 4, 5, 10, 12, 15, 20, 30 or 60
minutes. An overview of the external end of integration period reset is given in section 4.11.
The diagram above shows a record of Input 1 with a 30 minute integration period.

A1700 Load
4.6 Load Profile Recording (Power Failure) Input Module Profile Recording

The Input Module continues to collect the rising demand Transfer


Registers and
Rising Stored Rising
data and store the load profile data for each Input and Input 1
Demand Registers Load Profile
data on
Demand Registers
Input 2
Customer Defined Register during a power failure. Input 3
30 minutes Reset Power-up 30 minutes Reset

When power is restored to the meter, the contents of the Input 4


Store Load Store Load
Rising Demand Registers and stored Load Profile Data Profile Data Profile Data

are transferred to the meter and used to construct load


profile information.

A1700 Customer
Input Module Defined Registers
4.7 Customer Defined Registers
Input 1 Wh) Input 1 + Input 2 + Input 3

The A1700 meter has three Customer Defined Water (1 litre/Pulse)


Wh Register + Input 1 + Input 2
Input 3 (Export Wh)
Registers. Each register is programmable to summate Gas (1ft3/pulse)
pulses from two (Five) of the following source Import Register + Export Register

registers:
1. Wh total import
2. Wh total export
3. Q1 varh import lagging energy
4. Q2 varh import leading energy
5. Q3 varh export lagging energy
6. Q4 varh export leading energy

When an input module MODVAL(K) is introduced to the system the A1700 Customer
Defined Register formats are further enhanced, allowing inputs to be used in the equation.

7. Input 1
8. Input 2 Input Module
9. Input 3
Input 1 Input 1
10 Input 4
Input 2 Input 2

Input 3 Input 3
Example: Summate Wh total import Input 4

with Wh total export Input 1 + Input 3

Customer Defined

Customer Defined
A1700 P******** -2/3/4/5 Customer Defined Registers

When input module MODVAL-L is fitted,


the above versions of the A1700 allow up
to five channels (including the four inputs) to be summated.

Examples: Summate all four inputs (Wh) with Wh total import e.g. (Wh total
import +
Input 1 + Input 2 + Input 3 + Input 4)

Summate all quadrants e.g. (Q1 + Q2 + Q3 + Q4)


12 A1700 Users Manual - Chapter 5
____________________________________________________________________

4.8 Customer Defined Registers (Power Failure)


The internal battery supports the three Customer Defined Registers during a power failure.
The registers continue processing the input summations until the power is restored. The
register content is then transferred to the host meter cumulative registers on power-up.

4.9 Input Module Displays


The following A1700 displays are available for the input module. They must be programmed in
the utility section as part of the display sequence to be displayed. These displays are found in
the security section display list and should be transferred into the utility list.

Module Installation Displays

Input Module: Input Module: Input Module: REMOVE NOW


HOLD TO CONFIG Configuring... Configured Not Configured

Display 1 or Display 2 or Display 3 or Display 4

These displays are available during the input module installation procedure (see Section 4.14).

Module Status Displays

Input M Status Input M Status


Configured Not Configured

Display 1 or Display 2
These displays show the configuration status of the input module.

Module Detection Displays

Input Module Input Module Input Module


Present Not Present ?

Display 1 or Display 2 or Display 3


Display 1 or display 2 will normally be displayed. If the module is in the configuration
process, a question mark, (display 3) may be displayed. This will change to present or not
present at the end of the configuration process.

External End of Integration Input

External Int External Int External Int External Int


Disabled Initial Window Locked Unlocked

Display 1 or Display 2 or Display 3 or Display 4

This display shows the status of an external end of integration period input.
For a detailed description of the windowing system, see Section 4.11.

© Elster Metering Limited - M120 001 5S - 5/2007


Input/Output Modules 13
___________________________________________________________________

4.10 Battery Back-up


The battery is charged from the meter and in its fully charged state will support the module in
the event of a power outage for a minimum of 48 hours. The life of the battery is 6 years. From
a completely discharged state, the battery needs to be connected to the mains for 24 hours to
become fully charged.

4.11 External End of Integration Input Overview


The external end of integration input (EEOII) mode involves a “windowing” system in which a
time synchronisation pulse is expected. Depending upon the circumstances, the meter will
adjust its internal clock source (on board crystal) so as to synchronise to the external signal.
The window sync must not be performed:
1. At a midnight boundary
2. During s deferred tariff changeover
3. During daylight savings adjustments

Initial Window Mode Operation


To facilitate easier configuration of this mode, a window 40% of the duration of the integration
period value is provided. For instance, for a 30-minute integration period, a window of 720
seconds is provided (360 seconds either side of the normal end of integration boundary).
If the expected synchronisation signal is not detected within this window, or the power should
fail, this is deemed to be an abnormal condition and the meter will discontinue EEOII mode
operation. Should the synchronisation signal be detected correctly, the meter will adjust its
internal clock to the nearest integration period boundary and “normal window mode” operation
will commence.
Note: It is also inadvisable to change the demand period length when the module is in "initial
window" mode. The demand period length should be set prior to enabling "end of integration
input synchronisation" mode.
When configuring for EEOII mode the mains clock sync plus time adjust is disabled.

Normal Window Mode Operation


Once the meter has initially locked to the external clock source, normal mode operation
commences. This mode also involves a windowing scheme but the window size is fixed to 20
seconds (10 seconds each side of the integration period boundary).

Locked Operation
Normally, the time synchronisation signal is detected within the window and the meter
remains locked to the external source. Upon detection, the meter adjusts the internal clock to
the integration period boundary, as for the initial window – this is known as locked operation.
14 A1700 Users Manual - Chapter 5
____________________________________________________________________

Unlocked Operation
Should the external time signal not be detected within the window, the meter will perform an
end of integration (and associated events) at the closing edge of the window but the internal
meter clock will not be adjusted. Should a time synchronisation input be seen in the
subsequent window, the meter will again not adjust the internal clock but will resume locked
operation in subsequent periods that have synchronisation signals within the window.
Following the first missed time synchronisation input, if the meter continues to detect no time
synchronisation inputs, the meter will perform an end of integration (and associated events) in
the centre of the window (much as it would do for no EEOII mode in operation).

4.12 Terminal Connections


Input 1 Input 2 Input 3 Input 4
49 50 51 52 53 54 55 56

+ve com +ve com +ve com +ve com

Note: The four 'common' terminals are connected together internally.

4.13 Technical Data

Input Terminals
Voltage 0V to 0.5V = low
2.5V to 27V (max) = high
Current 10mA max
Source Impedance <1kΩ closed, >3kΩ open
Input Pulse Types Relay (normally open) Transistor
Pulse Width 20ms min
Pulse Rate 20 Hz max
Pulse Debounce 16ms to 136ms max (programmable)
Transition Type -ve or +ve edge
Internal Isolation (module installed) 6kV common mode impulse (applied to all three phases
and neutral) with respect to ground.
Input Isolation 4kV for 1 minute
Open Circuit Voltage (across terminals) 2V max
Isolation Protective Class II, IEC 61036
Battery
Type 3.6V Ni:MH
Support Time 48 Hours
Life 6 Years

© Elster Metering Limited - M120 001 5S - 5/2007


Input/Output Modules 15
___________________________________________________________________

Battery Warning

Battery Warning

The module contains a Nickel-Metal-Hydride (Ni:MH) battery. This battery is completely safe
under normal conditions. However, it must never be recharged (except in accordance with
manufacturer’s instructions), disassembled, heated above 65° C, incinerated, or have the
contents exposed to water.
Fire, explosion or severe burns may result if these instructions are disregarded.
In the interests of safety, environmental protection and possible legislation, Ni-MH batteries
require careful disposal.
Before arranging for the disposal of these cells, users should satisfy themselves that the
proposed means of disposal is both safe and compliant with local legislation requirements.

4.14 Installing and Removing Modules


Important Note - Always ensure that the installation procedure is followed when installing an
input module. At the time of installation the A1700 meter internal relays are inhibited and will
not be reactivated until the installation procedure is complete.

4.14.1 Installing and Configuring an Input Module


Once an input module has been installed in an A1700, configuration data has to be transferred
to the module from the A1700. This transfer can be initiated in a number of ways, but a
suitable scheme to support the module must first be present in the A1700.
To program the scheme and displays to the A1700, see Power Master Unit Manual M120 001 6.
Section 4.11 specifies the times it is inadvisable to install an input module. It is also
inadvisable to change the demand period length when the module is in "initial window" mode
or during "daylight savings". The demand period length should be set prior to enabling "end of
integration period mode".

Installing with power off (simplest method)


If an input module scheme has previously been programmed to an A1700, and the input
module is inserted when the meter power is off, restoring the power will configure the input
module.
16 A1700 Users Manual - Chapter 5
____________________________________________________________________

Installing and configuring the module (Meter energised)

Using the pushbuttons

1. Observe all Safety Warnings, Warnings, Precautions for handling electrostatic


discharge sensitive devices and EMC Guidelines in Section 2
2. Remove the terminal cover and raise the hinged clear lid on the meter's main cover
3. Ensure the terminal cover plate is correctly fitted and that any A1700 relay
supplies are isolated
4. Slide the module into the left module port as shown opposite until the module is
loosely held in the module slot (Do not push the module fully home at this stage)
5. Isolate all input supplies then make all module connections
6. Short press the Reset pushbutton to enter the Utility mode, then using the
display pushbutton, step to the Input Module HOLD TO CONFIG display
(Display 1 below)
7. Press and hold the display pushbutton. The message Input Module Configuring
will be displayed (Display 2 below). Release the button. During this period all
relays configured will be inhibited
8. Push the module fully home, making sure the module clicks into place. Energise the input
supplies
9. After detection (approximately 20 seconds) the display will toggle to Input Module
Configured (Display 3 below). The module is now configured. If the module is not detected
the message REMOVE NOW (Display 4 below) is displayed.
Note: the module should be removed immediately if the message is seen
10. Refit the terminal cover and fit appropriate seals
11. Switch on any relay supplies

Input Module: Input Module: Input Module: REMOVE NOW


HOLD TO CONFIG Configuring... Configured Not Configured

Display 1 Display 2 Display 3 Display 4

Using the communications ports


As an alternative to the above method, a scheme containing 'Install and configure module' can
be downloaded via the optical port or via a communications module if the input module is
already fitted.

Incorrect installation of module


If a module is incorrectly fitted, the meter will resume normal operation as soon as the module
is removed from the meter. The meter will remember the most recent relay settings provided it
is removed immediately as stated in step seven above.
Relays will retransmit energy with no loss of information as soon as the module is removed
from the meter.

© Elster Metering Limited - M120 001 5S - 5/2007


Input/Output Modules 17
___________________________________________________________________

4.14.2 Removing an Input Module


Removing with power off (simplest method)
The Input module can be removed from the meter when the power is off. When power to the
meter is restored the meter will recognise the module has been removed.

Removing using the pushbuttons (without de-energising the meter)

1. Observe all Safety Warnings, Warnings, Precautions for handling electrostatic


discharge sensitive devices and EMC Guidelines in Section 2
2. Isolate the input module supplies
3. Remove the terminal cover from the meter and raise the hinged clear lid on the meter's
main cover
4. Ensure the meter terminal plate is correctly fitted and that any meter relay supplies are
isolated
5. Short press the Reset pushbutton to enter the Utility mode, then using the display
pushbutton, step to the Input Module, HOLD TO CONFIG (Display 1 below)
6. Press and hold the display pushbutton until Input Module, Configuring (display 2 below) is
displayed. Release the button. During this period all relays configured will be inhibited
7. Before the configuration process is complete (Approximately 20 seconds), insert a 3mm
electrician’s screwdriver into the hole by the side of the module identifier and press the
clip. Grip the module and pull downwards
8. Refit and seal the terminal cover and fit appropriate seals

Input Module: Input Module:


HOLD TO CONFIG Configuring...
Display 1 Display 2

Removing via communications ports


As an alternative to the above method, a scheme containing 'Install and configure module'
can be downloaded via the optical port or via a communications module. The input module
should be removed while 'Input Module: Configuring' is displayed.
18 A1700 Users Manual - Chapter 5
____________________________________________________________________

4.14.3 Checking Input Module Operation Input Module Terminals

Correct operation of the module inputs can be checked by Input 1 Input 2 Input 3 Input 4
wiring each input to an A1700 Meter internal relay, then setting +ve com +ve com +ve com +ve com
of an event on the input and confirming that the action of the
output relay is detected by the module.
49 50 51 52 53 54 55 56
To wire the inputs to the outputs, follow the connection notes
below.

Connection Notes 17 18 19 20 21 22
1. Any input can be wired to any output.
2. The Input Module Terminal common must be wired to the +ve com +ve +ve com +ve
common of the A1700 Meter relay being used. RL1 RL3 RL 2 RL 4
A1700 Meter Internal Relays

4.14.4 Wiring External Meters to the A1700 Meter Inputs


The A1700 meter inputs will accept pulses from any external source
containing a clean contact or transistor type switch output.
A contact can be one of, but not restricted to, the following:
• A relay in a Utility Meter
• A contactor indicating the state of apparatus i.e. ON or OFF
• An open collector transistor

These types of inputs are used to convey information to the Input Module in the form of pulses
or changes of state.

The length of the pulse accepted is defined by the de-bounce time.


For a setting of 20ms, pulses MUST be at least 20ms long before they will
be recognised by the system.
Changes of state must be present for at least 20ms before they are
registered. This value can be adjusted by altering the de-bounce time of the
selected input. The de-bounce time can be set between 16ms and 136ms in
8ms steps.