You are on page 1of 16

ENGINEER’S STAMP: CONTRACTOR’S STAMP:

c For Approval UK UK LS 14.Oct.2021

B For Approval 8. 8. /6 13-Sep-2021

A For Approval 8. 8. /6-Aug-2021

‫ﺗﻧﻘﻳﺢ‬ ‫ﺳﺑﺏ ﺍﻹﺻﺩﺍﺭ‬ ‫ﺑﻭﺍﺳﻁﺔ‬ ‫ﺭﺍﺟﻌﻬﺎ‬ ‫ﻭﺍﻓﻖ ﻋﻠﻳﻬﺎ‬ ‫ﺍﻟﺗﺎﺭﻳﺦ‬


REV. ISSUED FOR PREPARED CHECKED APPROVED DATE

‫ﺍﻟﻣﻣﻠﻛﺔ ﺍﻟﻌﺭﺑﻳـــﺔ ﺍﻟﺳـــــﻌﻭﺩﻳــــﺔ‬


KINGDOM OF SAUDI ARABIA
‫ﺍﻟﻣﺅﺳﺳﺔ ﺍﻟـﻌـﺎﻣـــﺔ ﻟﺗﺣﻠﻳــﺔ ﺍﻟﻣﻳـــﺎﻩ ﺍﻟﻣﺎﻟﺣـــــﺔ‬
SALINE WATER CONVERS ION CORPORATION (SWCC)

Project No.‫ﺭﻗﻢ ﺍﻟﻤﺸﺮﻭﻉ‬ ‫ﻧﻈﺎﻡ ﻧﻘﻞ ﻣﻴﺎﻩ ﻣﺪﻳﻨﺔ ﺍﻟﻘﻨﻔﺪﺓ ﺍﻟﺠﺪﻳﺪ‬


200201034819 AL QUNFUDHAH NEW CITY FEEDER WATER TRANSMISSION
SYSTEM

‫ﻳﺳﺎ ﻟﻠﻬﻧﺩﺳﺔ ﻭﺍﻟﺗﻛﻧﻭﻟﻭﺟﻳﺎ ﻭﺍﻻﺳﺗﺷﺎﺭﺍﺕ‬


‫ﺍﻟﻣﻬﻧﺩﺱ‬
AYESA ENGINEERING, TECHNOLOGY, CONSULTING
ENGINEER

(‫ﺍﻟﺷﺭﻛﺔ ﺍﻟﺳﻌﻭﺩﻳﺔ ﻟﺧﺩﻣﺎﺕ ﺍﻷﻋﻣﺎﻝ ﺍﻟﻛﻬﺭﺑﺎﺋﻳﺔ ﻭﺍﻟﻣﻳﻛﺎﻧﻳﻛﻳﺔ )ﺷﺭﻛﺔ ﻣﺳﺎﻫﻣﺔ ﻣﻘﻔﻠﺔ‬


SAUDI SERVICES FOR ELECTRO MECHANIC WORKS CO. (CJSC)
‫ﺍﻟﻣﻘـــﺎﻭﻝ‬
CONTRACTOR

Dd,K^ddDEd&KZ,s

DOCUMENT NO.: SHEET REV.:


1 0 - Q D 6 0 - F - 2 6 1 1 OF 29 C
SUB-
KSB PUMPS
CONTRACTOR
METHOD STATEMENT FOR
INSTALLATION OF HVAC
SYSTEM
TABLE OF CONTENT

1. SCOPE OF WORK

2. STANDARDS AND REGULATION

3. RESPONSIBILITIES

4. WITNESS INSTALLED ITEMS

5. EQUIPMENT, MATERIALS & TOOLS

6. METHOD STATEMENT
1. SCOPE OF WORK
This method statement describes the procedure for installation of HVAC
system duct & duct accessories at below buildings.
To ensure that the installation of HVAC duct & duct accessories and
related activities are executed safely and in accordance with the
contract requirements and that all quality assurance control activities
required for the same are conducted in a systematic manner, Works are
inspected and conformance is verified and documented.

2. STANDARDS AND REGULATIONS


• The work under the all sections shall comply with June, 2016 Edition of
the applicable standards and codes of the following:

• ASHRAE - American society of Heating, Refrigeration and Air-conditioning


Engineers
• SWCC Specification reference number QA10-G-008 Rev.3
• ASTM - American society of Testing and Materials
• NFPA- National Fire Protection Association
• UL - Underwriters Laboratories
• SMACNA - Sheet Metal and Air Conditioning Contractors
National
Association.
• SAES-K-001 Saudi Aramco Design and Installation of Heating,
Ventilation and Air Conditioning.
• SAES-K-100 Saudi Aramco Mechanical (HVAC) Code.
• SAES-K-002 Air conditioning system for Essential Operating Facilities
(Batteries room)
• SAES-K-003 Air conditioning system for Communication Building
• SATIP-K-001 01 to 12 Saudi Aramco Typical Inspection Plan (HVAC)

3. RESPONSIBILITIES
Project Manager
• PM will be responsible for the over-all work involved in the project works.
QA/QC Manager
• Responsible for the overall distribution and implementation of this
procedure
Construction Manager
• Responsible for the works execution and implementation of this procedure
at Fabrication Shop and Field.
Safety Supervisor/Safety Officer
• Prepares Risk Assessments and Daily Task Risk Assessments,
recognizes the hazards and all the control measures to arrest the hazards
are done prior to start of work.
• Line Supervisor and safety officer to conduct Daily Task Risk
Assessment and Risk Assessment with the employees and make sure
that they understand the hazards and risk involved and the necessary
measures which needs to be taken to mitigate the risk before work
starts.
• Responsible for ensuring that all safety requirements necessary to start
these activities is provided by the construction group as per project HSE
manual / requirements and specifications.
• Conducts inspection to ensure that all safety requirements are being
maintained up to the completion of this activity.
• Carry daily tool box talks and prepares necessary documents and reports.
• To report any safety violation to HSE Supervisor and HSE Manager in
order to take corrective action.
• HSE supervisor to visit the site and attend meeting as and when
required.

4.WITNESS INSTALLED ITEMS

1. HVAC system installation shall be subject to test and inspection


under witness by the QC. Inspector and/ or Owner's representative
(PID) at any reasonable time and place before, during and after
installation.
2. Installation of duct work shall be in accordance with this procedure.

5. EQUIPMENT, MATERIALS & TOOLS


The materials, types, performance requirement, finishes, etc., shall be
as approved in relevant documents.
The following equipment shall be installed as per this method statement.

• G.I rectangular duct


• Duct Accessories (Dampers, Grills & Diffusers)
• G.I supports
• Package air conditioning units(PACU )
• Air handling units(AHU )
• Ventilation fans.
• Sand trap louvers
• Fan coil units_(FCU) and sp lit units.
• Insulation materials
• Duct electric heaters

The following materials/tools will be used to carry out task for HVAC
system.
• Hand Tools as below
a. Rotary Hammer
b. Drill Machine
c. Mini Grinder
d. Speed cutter
e. Blower
f. Jigsaw
g. Plier
h. Monkey plier
1. Vise Grip
j. Ratchet
k. Adjustable wrench
1. Hammer
m. Rubber Hammer
n. Right Angle
o. Hacksaw frame
p. Sealant Gun
q. Sp anner
r. Rivet gun

Machineries using for height works

• Ladders and step ladders


• Scaffolding.
• Mobile elevating platforms
• Cranes for lifting/ installing the equipment and ducts.

6. METHOD STATEMENTS (QA10-G-008 Rev.3)

6.1 HANDLING AND STORAGE:

• All Duct pieces (i.e. duct sections of rectangular, square, circular) C-


cleats shall be fabricated in FACTORY as per approved material
equipped with special purpose computer numerical
controlled (CNC) machinery and special purpose tools.
• All duct section shall be fabricated I joined as per SMACNA standard
I design drawing details.
• On receipt of ducts and accessories at site, necessary precautions
shall be taken for unloading, shifting and storage as follows:

o Materials received at site will be inspected and ensure that the


materials are as per approved material submittals.
o Any ductworks (rectangular I square I circular) delivered at site
will be carefully offloaded by deploying necessary I
adequate dedicated manpower for loading and unloading
materials in
such a way that no damage is caused to ductwork.
• Any part of the galvanised ductwork, where the galvanising has been cut
or damaged during manufacture or erection, shall be cleaned down to
bright metal and painted two coats of aluminium, zinc or other
corrosion-resisting paint
o Ducts and accessories will be stored in a place free of water,
dust and adequately covered.
o It will be ensured that the fabricated duct pieces are numbered
or tagged as per latest approved drawing to avoid wrong
connections during assembly or installation and to expedite
assembly works.
o All insulation material will be stored in a dry place and adequate
cover will be provided.

• Any discrepancies, damage etc., found will be notified and will be


reported for further action.
• Materials found not suitable for site will be removed from site
immediately.
• Duct Sealant, adhesive, gasket, ducts & etc. shall be stored in
enclosed areas as per Manufacturer's recommendations. Also attach
or include the Manufacturer's recommendations & Product data sheet
limitations where applicable to the material.

6.2 DUCT HANGERS AND SUPPORT INSTALLATION:

• Secure all necessary permit-to-works prior to start of HVAC works.


• Work Supervisor will conduct safety briefing on all workers.
• Clear floor in respective building where G.I duct to be installed.
• Supports for rectangular ducts when suspended from above shall be
installed on two opposite side of each duct.
• Supports for rectangular ducts shall be riveted, bolted, or metal
screwed to each side of the duct at not more than the intervals
specified.
• Concrete fasteners shall be installed after the concrete has been
poured and the form works have been removed.
• The Support system shall not penetrate enclosures containing fluid
or electrical wiring in such a manner to create a hazard.
• Horizontal duct shall have a Support within 1.2 m of each branch
intersection.
• Rectangular duct risers from floor shall be supported by angles or
channels secured to the sides of duct with welds, bolts, sheet metal
screws, or blind rivets. Fasteners shall be located within 0.05 m of
the duct edges, locate others at evenly spaced interval.
• Angles shall be at 3.6 m intervals for rectangular and round duct
risers.
• All duct hanger & supports details shall be according to the
drawing.

6.3 INSTALLATION OF HVAC DUCT:

• Prior to installation of ducts, coordinate with other trades/ discip line will
be done.
• Secure all necessary permit-to-works prior to start of HVAC works.
• Work Supervisor will conduct safety briefing on all workers.
• Clear floor in respective building where G.I duct to be installed.
• Transport the duct pieces and fittings to final location.
• Duct pieces will be installed and joined together as declared on approved
drawing.
• Assembled ducts will be fitted manually and will be installed on
supports. Similarly the next length of duct will be installed and two are
joined together by means of suitable C-cleats, S-cleats or flanges with
gasket and tied GI nut bolts and washers.
• The ducts will be properly aligned and leveled to maintain bottom of duct
(B.O.D) and distances as per approved drawing.
• Wherever branch take off collars are to be taken, suitable cutout will be
made in the ducts.
• Approved duct sealant shall be applied on the joints. Any excess sealant
shall be removed so that the joint is left in clean and tidy condition.
• Ensure that the ductwork is clean and no tools/construction debris
exists within ductwork before proceeding to next length.
• All open ends of the ductwork shall be temporarily sealed with polyth en e
sheets before leavin g the job site to prevent ingress of moisture and dirt.
• Installation of duct work shall be checked, inspected and tested before
applying thermal insulation at ductwork joints.
• All building exhausts shall be direct ly to the outside with a point of
discharge of at least 1.5 m away from any open able window or door, and
a minimum of 1m above and 3m horizont ally away from any air intake.
• Metal ducting shall be groun ded, provide jumpers at flexible connection
in HVAC room.
• Joints, seams and fittings of duct systems shall be made substantially
airtight by means of tapes, mastic, gasket or other approved methods.
• If air leakages in ducts located outside of buildings are exposed to
weather, they shall receive exterior duct sealant.
• Seal class C shall be provide d for 0.05 m w.g pressure class duct
Construction. Class C: Transverse joints only.
• Installation of duct shall be done with proper alignment.
• All duct work shall comply with SMACNA standards suitable for 0.05 m
w.g pressure class.
• All ducts shall be thoroughly cleaned before assembling. All open ends shall be
sealed with polythene covers at all times during construction. All joints shall be
sealed with an approved mastic and taped externally to make an air -tight joint. All
flanges shall be fitted with gaskets.
• All connections to equipment shall be made with angle-flange joints.
• Where ducts penetrate any structural wall or slab, they shall be sleeved and 25 mm
thick rock wool inserted between the sleeve and the duct. Any gaps between the
sleeve and the structure shall be sealed with heavy grout and finished with a dense
mastic. All ductwork shall be airtight according to DIN EN 1507 Class B or
equivalent

Material Specifications: Material Confirms to: ASTM A653


Material: Galvanized Iron sheets LF Quality.
Zinc Coating: G-90.
Thickness: As per General Construction Drawings.

6.4 DUCT TESTING PROCEDURE (LIGHT TEST/SMOKE TEST):

• Below procedure explains light test for low pressure ducts.


• Select a section of duct to be tested.
• Light test shall be perform ed in sections prior to insulation.
• The light test shall be perform e d with heavy duty halogen lamps (500 or
1000 Watts lamps).
• Test light shall be fixed at the ends of the stick with enough length to
reach the farthest joint to be tested.
• Position the light inside the duct in the area of joints to be tested.
• Check the outer side of the duct area or joint being tested for any
visibility/leak of light from inside.
• If any leak found, seal the area and repeat the test.
Smoke Test: -
• Ensure to close all the duct joints with proper duct sealant to avoid the
chance of leakage, avoid splattering of the sealant in the joints.
• Dampers can be used to isolate the area which need to be tested,
• Run the Smoke Fane for 15 Minutes to pressurize the Smoke (time
Depen d on the Duct length and size).
• Scaffoldin g will be provided to access the ducts
• The end of line shall be opening to confirm. the smoke reach to all the
branches.
• Check at every joint- the Smoke from outside shall not be visible.
• If any defects found, the point shall be marked and then rectified sealed
after finishing the test
• After rectification, the test to be repeated;
• Test to be done for each section of the duct

6.5 PACKAGED AIR CONDITIONING UNITS (PACU) AND AIR HANDLING


UNITS(AHU):

• Install the unit's level on structural curbs. Coordinate wall penetrations


and flashing with wall construction. Secure PACU's & AHU to structural
supports with anchor bolts.
• Provide spring vibration isolators under the PACU & AHU for vibration
control.
• Install condensate drain, minimum connection size, with trap siphon tee
fitting and indirect connection to nearest roof drain or area drain.
• Connect the supply and return ducts to PACU & AHU with
flexible duct connectors.

6.6 SPLIT-SYSTEM AIR CONDITIONERS

• Install the unit's level and plumb.

• Install evaporator fan components using manufacturer's standard


mounting devices securely fastened to building structure.
• Install ground mounted, compressor c-condenser components on the pre
cast concrete equipment bases. Rubber pad vibration isolators can be
used to avoid vibration.
6.7 INSULATION OF DUCTWORK:

• Installation of duct work (com plet e with accessories) shall be checked,


inspected and light tested before applying insulation.
• Clean the surface of the duct to remove dust and grease.
• Spread adhesive at the surface of the duct.
• For large ducts of width more than 0.5 m, flx stuck up pins at regular intervals.
Apply adhesive to the surface of the duct and fix insulation firmly
in position. Insert stoppers over the pins to hold insulation firmly to the
duct. Bend the pin to lock stopper in position and seal with 3mm thick
aluminum tape.
• When insulating dampers, ensure that the handle is not covered by the
insulation to permit opening and closing of dampers. Ensu re Access doors
are not covered fully and are easy to open/close.
• Indoor duct and outdoor duct will be insulated as per Project specification.
• Material Specifications:

a) Material confirm s to:_ASTM C518


b) Material: Fiberglass Insulation - Board Insulation (Vapor retardant
aluminum foil reinforce d Kraft paper laminate-FRK).
c) Densit y minimu m 48 kgfm3
d) Thickness: 25mm (Indoor) & SOmm (Outdoo r), Outdoor duct
insulation -shall be cladded with 0.8mm thick aluminum jackets.
e) Make: AFICO

6.8 FLEXIBLE DUCTS:

• Flexible ducts shall be installed in accordance with SMACNA standard.


• The bends of the flexible ducts shall not exceed 45 Degrees.
• The length of the flexible duct shall not exceed 1.5 meters.
• The flexible ducts shall be supported every 1.5 meters (max.) to avoid it
from sagging and touching the false ceiling.

6.9 GRILLS AND DIFFUSERS:

• Grills and registers shall be installed with self-tapping screws to the wall
or to the ducts as per shop drawings.
• Supply grills or registers shall be installed with collar from branch.
• Return grills or registers shall be installed without volume dampers.
• Supply ceiling diffusers shall be installed with plenum box and volum e
damper on the branch, the type of the diffusers shall be in accord an c e wit h
the false ceilin g.
• Return ceiling diffusers shall be the same model with the supply diffusers.

• Air Terminal Devices shall be mounted at locations shown on approved


Drawings.
• Air terminal devices shall not be installed directly on the main ducts.
• Air terminal devices shall be connected to main ducts with Branch
ducts having a minimum length of two duct sizes.

6. 10 FIRE & SMOKE DAMPERS:

• The fire dampers shall be installed in accordance with


manufacturer's recommendation.
• Access doors shall be minimum of 300 x 300_mm opening shall
be provided on each fire damper to reach the blade for maintenance
purpose.
• The location of the fire dampers shall be as specified in the approved
shop drawings.
• Type of duct connection to Fire Damper sleeve shall be
breakaway connection.
• Adequate space f opening is provided for restoring the damper
(when done manually) in its normal operating condition. (SMACNA
Appendix E).
• Retaining angle shall be secured to sleeve on 8" centers. Retaining
angles shall not be fixed to the walls.
• Clearance of the damper sleeves within a wall shall be 0.03 mjft
of width (or Height).
• Before installation visual inspection of damper and fusible link will
be done.
• Lift or handle damper using sleeve or frame.
• Damper must be installed into duct or opening square and free of
twist or other misalignment.
• Fire/smoke damper should be installed in fire rated Wall, floors
and partitions.
• Duct Access doors will be provided for internal Access to all frre/
smoke damper for sizes bigger than 300 mm width of the duct.

6. 11 VOLUME DAMPERS & BACK DRAFT DAMPERS INSTALLATION:

6. 11.1 Volume Dampers:


• All volume dampers shall be installed in accordance with SMACNA Standard
and HVAC drawings.
GRAPHIC SCALE IN METERS:
0 1 5

RECOMMENDED CONSTRUCTION FOR


RECTANGULAR LOW PRESSURE DUCTS
n
mi
RECOMMENDED DUCT RISER 10
0 mm
LONGEST SIZE U.S. GAUGE LONGITUDINAL INTERMEDIATE
SUPPORT W
=
OF DUCT (MM) (THICKNESS) CONNECTIONS REINFORCEMENT TRANSVERSE CONNECTIONS
HANGER STRAPS ANGLES HANGER RODS
1/ 4
A=
A
UP TO 300 26 (0.55MM) PITTSBURGH - S-SLIP GA24 D-SLIP GA24

DUCT SIZE UP TO ANGLE SIZE 301 TO 550 24 (0.70MM) PITTSBURGH - S-SLIP GA24 D-SLIP GA24
NOTES:
25MM "STANDING" SLIPS DUCT DUCT
551 TO 750 24 (0.70MM) PITTSBURGH -
750x400 25x25x3 mm 45
° GA-22 AND D-DRIVE 24 1. FOR DRAWING LEGEND AND FURTHER HVAC NOTES, REFER TO DWG NO. 10-UV00-B-601
900x450 25x25x3 mm 751 TO 1350 22 (0.80MM) PITTSBURGH - DMT FLANGE
DUCT
W 2. DUCT INSULATION SHALL BE AS PER SPECIFICATION M15.
1050x600 30x30x3 mm 1351 TO 1500 20 (1.00MM) PITTSBURGH - DMT FLANGE
1200x750 30x30x3 mm DMT FLANGE WITH ONE TIE
OW 1501 TO 2150 20 (1.00MM) PITTSBURGH -
FL ROD 10MM DIA
DMT FLANGE WITH TWO TIE
10mm BOLT
18 (1.20MM) -
2151 TO 2300 PITTSBURGH ROD 10MM DIA (MINIMUM)
NEOPRENE GASKET NEOPRENE GASKET
2301 & ABOVE 18 (1.20MM) PITTSBURGH
40x40x4MM GI ANGLE
+10MM DIA TIE ROD
DMT FLANGE WITH TWO TIE 25mm 25mm ANGLE ANGLE
ROD 10MM DIA

(ALT - 1) (ALT - 2) (ALT - 3)


2 BRANCH CONNECTION
- DETAIL RECOMMENDED GAUGES FOR
4
- GALVANIZED STEEL DUCTS
DUCT
RECOMMENDED HANGER SIZES FOR
INSULATION RECTANGULAR DUCT
RETURN AND EXHAUST DUCT (DIVERGING)
BOLT or No.8 SCREW ANGLE HANGERS
DUCT LONGEST STRAP HANGERS MAXIMUM
SCREWED OR (ALT-1)
AHNGERS/TRAOEZE ROD/TRAPEZE
SPACING
DIMENSION
BOLTED TO WALL (ALT-2) (ALT-3)

20°
m ax
AIR FLOW UP THRU 450mm 25mm X 16 Ga. 25mm X 25mm X 3mm 8 mm Ø 3000 mm
NON-COMBUSTABLE
GI DUCT SLEEVE SLEEVE ON BOTH SIDES 460 THRU 670mm 25mm X 16 Ga. 25mm X 25mm X 3mm 8 mm Ø 3000 mm
DUCT GAUGE 24 680 THRU 1070mm 25mm X 16 Ga. 40mm X 40mm X 3mm 8 mm Ø 3000 mm

25
1080THRU 1520mm 25mm X 16 Ga. 40mm X 40mm X 3mm 10 mm Ø 3000 mm
1530 TO 2130mm 40mm X 16 Ga. 50mm X 50mm X 3mm 10 mm Ø 2400 mm
ANGULAR BAR
UN INSULATED/INSULATED DUCT
(GALVANIZED STEEL)
ANGULAR BAR SUPPLY DUCT (CONTRACTING)

25

30°
max
FILLED WITH INSULATION AIR FLOW 6 RECTANGULAR DUCT HANGER SUPPORT
(ROCKWOOL) OR ANY
NON-COMBUSTABLE MATERIAL -
ISOMETRIC FRONT VIEW WALL PARTITION
LEGEND:

1 RECTANGULAR DUCT SUPPORT FROM WALL 3 DUCT RUNNING THROUGH 5 TYPICAL DUCT TRANSITION
- - HOLLOW BLOCK WALL -

1-1/2" STANDING
SEAM RIVETED ON
12" CENTER
INSULATED FLEXIBLE
FLASHING WITH DUCT (1.80m MAX.
WELDED CORNER
SEAMS LENGTH)
DUCT
ROOF
32 x 32 x 3MM THICK CURB
STEEL BRACING
(GALVANIZED OR VOLUME
PAINTED WITH OXIDE) ANCHOR
#24 GAUGE ALUMINUM DAMPER
INSULATION APPLIED TO DUCTWORK SHEET METAL CLADDING BOLT
ON ALL FOUR SIDES WITH FOR EXPOSED TO VIEW SS CLAMP
APPROVED ADHESIVES METAL CLADDING SUPPLY
DUCT ONLY SS DUCT
(AS SPECIFIED) DUCT HANGER 8 mm DIA
DUCTWORK THREADED ROD CLAMP
(TYP.)
ALUMINIUM FOIL BACKED/PANEL TYPE DETAIL "A"
OR ROLL TYPE.
OPPOSED PLENUM
INSULATION AS
SPECIFIED BLADE DAMPER BOX
SELF ADHESIVE ALUMINIUM TAPE
FLANGED CONNECTION T-RUNNERS COLLAR

6MMØ BOLT DUCT WORK END TABS OR FLAPS FOR JOINTS


FORMED BY STRIPPING FROM THE SUPPLY CEILING
VAPOR BARRIER SEAL OVER LAPS SUSPENDED CEILING
DIFFUSER
WITH A QUICK TACKING ADHESIVE
PITTBURG LOCK SEAM
AIR DUCT AS SPECIFIED ANGLE UNDERCUT WITH
NEOPRENE GASKET
INSULATION AS SPECIFIED FLASHING WITH
40mm (MIN)
WELDED CORNER FLAME RESISTANT 51 x 51 x 102MM U.S.G #20 11 FLEXIBLE DUCT & SUPPLY CEILING DIFFUSER DETAIL
PAVIOR GALVANIZED SHEET METAL
150mm (MIN) SEAMS QUICKTACKING ADHESIVE TO
CORNER BEADING
-
BE COATED 100% OF DUCT
NEOPRENE GASKET SEE DETAIL "A" SURFACE AREA
CUT BACK STICK FIXING
BONDING
600

STICK PINS APPLIED TO PINS AFTER APPLICATION


OF THERMAL INSULATION ADHESIVE
ALL DUCT SURFACES #18 GAUGE TIE WIRE
THERMAL INSULATION SOLAR HEAT
SHIELD H.C. SPACE AT 305MM OR
PROTECTION APPROVED EQUAL
ROOF BUILT UP
(BITU-THENE)

ROOF SLAB
DUCT
ROOF CURB REFERENCE DRAWING:
DRAWING No. TITLE
7 EXTERNAL INSULATION 8 SUPPLY AND RETURN 10 INDOOR / OUTDOOR DUCT INSULATION AND HANGER QA10-G-008 Rev.3 PROJECT SPECIFICATION G02
- TO RECTANGULAR DUCT - DUCT DETAIL AT ROOF DECK GRAVEL
- QC10-H-055 Rev.0 HVAC SPECIFICATION M15
MORTAR CANT. FALSE 10-QB20-R-601 HVAC DESIGN BASIS REPORT
RETURN AIR CEILING
DIFFUSER 10-UV00-B-601 HVAC General Notes & Legends

9 SUPPLY/RETURN DUCT 12 RETURN CEILING DIFFUSER DETAIL


- PENETRATION THRU ROOF DETAIL -
ENGINEER'S STAMP: CONTRACTOR'S STAMP:

SSEM DOCUMENT COMMENT SHEET


No. 10-UV00-G-601 No. EH-SSEMR-D-2142
Rev. 0 Date 22.01.2021
FOR ALL DUCT RISERS, A CURB IS PROVIDED STATUS A: Approved for construction (AFC)
AROUND THE FLOOR OPENING WHERE DUCT 100mm LONG B: Approved as noted (AAN)
PASSES THROUGH. METAL SCREW
T1 T14 1" FLANGE & HEM D: For Information only (INF)
25 INSULATION
80 mm

METAL FLANGED
RUBBER IMPREGNATED FITTING
BOLT ON 100 mm FABRIC DUCT
ALTERNATE POSITION CENTERS
T10 OF BOLT 11/2" POCKET
T13 T13 SLIP
DUCT VIEW-B
T15 DUCT
T1

SCREW CAP
WELDED ALL
1"x1/8" BAND IRON AROUND SUPPORT BRACKETS
20 U.S. GAGE FOR ADJUSTABLE
STEEL VIEW-B SCREWED DROP RODS REV. ISSUED FOR DRAWN CHECKED APPROVED DATE
80 mm

PLENUM BOX INSULATED


14 SEAM APPLICATION - TYPICAL 15 RECTANGULAR-FLEXIBLE CONNECTION OUTSIDE WITH 50mm
THICK, 32KG/M3 DENSITY KINGDOM OF SAUDI ARABIA
PLAN - - 17 DUCT TEST HOLE DETAIL GLASS FIBER
INSULATION
-
DUCT JOINT SALINE WATER CONVERSION CORPORATION (SWCC)

L 50x50x3 mm
25 mm
FLOOR DOOR THICK
Project No. AL QUNFUDHAH NEW CITY FEEDER
DUCT 200201034819
DISCHARGE SPIGOT WATER TRANSMISSION SYSTEM
DOOR TO SUIT DIFFUSER
NECK SIZE DUCTWORK INLET
CONCRETE SLAB SS STEEL SCREW SPIGOT
3 mm
DRIVE SLIP STANDING DRIVE SLIP DRIVE SLIP-REINFORCED STANDING S
ELEVATION INDOOR FACE
T-1 T-2 T-3 T-10
ENGINEER AYESA ENGINEERING, TECHNOLOGY, CONSULTING
GRILLE HEIGHT + DEPTH

RECOMMENDED DUCT RISER


SUPPORT RIVET GASKET 18 DOOR GRILLE
-
DUCT SIZE UP TO ANGLE SIZE SAUDI SERVICES FOR ELECTRO MECHANIC WORKS CO. (CJSC)
OUTDOOR FACE CONTRACTOR
900x450 25mm X 16 Ga. COMPANION ANGLE STANDING S (BAR STANDING S (ANGLE
(CAULK OR GASKET) REINFORCED) REINFORCED)
1200x600 25mm X 16 Ga.
1500x750 25mm X 16 Ga. T-22 T-13 T-14 HVAC TYPICAL INSTALLATION DETAILS
SCALE

ALUMINUM FRAME NTS


13 DUCT RISER SUPPORT 16 TRANSVERSE SEAMS 19 SQUARE DIFFUSER PLENUM BOX DRAWING NO. SHEET REV.
COORDINATE SIZE AND DIMENSION WITH
- - ARCHITECT AND OTHER TRADES -
1 0 - U V 0 0 - G - 6 0 1 1/4 1
FINAL
ENGINEERING
IBG Ltd.
GRAPHIC SCALE IN METERS:
0 1 5

DUCT THERMAL INSULATION


(SEE SPECIFICATION) NOTES:
METAL CLADDING
(SEE SPECIFICATION
DU DUCT SUPPORT 1. FOR DRAWING LEGEND AND FURTHER HVAC NOTES, REFER TO DWG NO. 10-UV00-B-601
CT
WI 2. DUCT INSULATION SHALL BE AS PER SPECIFICATION M15.
D TH SEAL SLEEVE THROUGH TURNING VANE
FIRE WALLS IN A
SMOKE-TIGHT MANNER
ACCESS PANEL

DUCT HEIGHT
300x300mm
AIR DUCT
TERMINATE SLEEVE AP
FLUSH W/ FINISHED MASTIC SEALANT
WALL SURFACE
STAINLESS SHEET STEEL FLASHING
STANDARD WEIGHT STEEL PIPE SECURED BY STAINLESS STEEL
SLEEVE OF SIZE TO PASS PIPE CLAMPING SUPPORT
AND INSULATION LOAD BEARING THERMAL
INSULATION INSERT EXTENDED
PIPE AND INSULATION TO BE 50MM BEYOND ANGLE SUPPORT
GALV. FRAME CENTERED IN SLEEVE-DO COUNTER FLASHING
NOT SUPPORT FROM SLEEVE
GALV. SHEAR BLADE
FINISHED ROOF LEVEL
EXTENDED SHAFT FINISHED ESCUTCHEON PLATE 50MM THICK PRECAST PAVER
FLUSH AGAINST WALL OF SIZE TO 100 mm FOR ANCHOR SUPPORT
COMPLETELY COVER OPENING
AIR DUCT
DUCTWORK PIPING EXPOSED TO VIEW

50
ROOF STRUCTURE
LEAN CONCRETE

SEALANT WITH
BACK ROD (TYP)

NOTES:
1. FOR ROOF CONSTRUCTION AND FLASHING DETAILS SEE ARCHITECTURAL DRAWING
2. FOR CURB CONSTRUCTION, SEE STRUCTURAL DRAWINGS. LEGEND:

20 MAIN DUCT VOLUME DAMPER 21 PIPE SLEEVE THRU INTERIOR WALLS 22 DUCT PENETRATION THRU ROOF
- INSTALLATION DETAIL - -

PRESSURE PRESSURE PRESSURE


DUCT SIZE DUCT GAGE DUCT SIZE DUCT GAGE DUCT SIZE DUCT GAGE
CLASS CLASS CLASS
525 - 1200 mm 24 250 Pa 1225 - 1800 mm 22 250 Pa 2425 & ABOVE mm 18 250 Pa
525 - 900 mm 24 500 Pa 1825 - 2100 mm 20 250 Pa
925 - 1200 mm 22 500 Pa 2125 - 2400 mm 18 250 Pa 2125 & ABOVE mm 18 500 Pa
1225 - 1350 mm 20 500 Pa 1375 - 1500 mm 20 500 Pa
1525 - 2100 mm 18 500 Pa

) 28mm )
GTH GTH
L EN L EN
T D. T D. H) TH
)
0(
S (S GT N G
0 S. CLEAT (SLIP JOINT) 00 L EN LE 10 MMØ TIE ROD WITH INTERNAL
12 12 . D. AND EXTERNAL NUTS
(2 GAGE LESS THAN DUCT) (STD 10 mm Ø TIE ROD WITH INTERNAL (ST
SPOT WELD
2 00 AND EXTERNAL NUTS 00
1 00 SPOT WELD 12 00
6 6

25mm

S. CLEAT
PITTSBURGH
DUCT MATE
PITTSBURGH
DRIVE SLIP
DRIVE SLIP LONGITUDE
JOINT
6 MM

160 160
(2 GAGE LESS THAN DUCT) PITTSBURGH
LONGITUDE
160 160 JOINT INTERMEDIATE REINFORCEMENT
6 MM

40 X 40 X 4 mm ANGLE
160 160

6 MM
160 160

6 MM
STANDARD STRAIGHT DUCT 1200 mm SPOT WELD
STANDARD STRAIGHT DUCT 1200 mm LONG WITH WAVER BEADING 160 mm
LONG WITH WAVER BEADING 160 mm CENTER TO CENTER DUCT MATE DUCT MATE
CENTER TO CENTER
134 mm LONG DUCTMATE CLEAT STANDARD STRAIGHT DUCT 1200 mm
PRESSURE JOINTS SNAPPED 450 mm CENTER TO LONG WITH WAVER BEADING 160 mm STANDARD STRAIGHT DUCT 1200 mm
DUCT SIZE DUCT GAGE
CLASS CENTER CENTER TO CENTER LONG WITH WAVER BEADING 160 mm
CENTER TO CENTER
0 - 250 mm 26 250 Pa
10 MM NUT/BOLT & WASHER
275 - 500 mm 24 250 Pa
525-750 mm 22 250 Pa
775-1050 mm 20 250 REFERENCE DRAWING:
0 - 250 mm 26 500 Pa DRAWING No. TITLE
275 - 500 mm 24 500 Pa QA10-G-008 Rev.3 PROJECT SPECIFICATION G02
525-750 mm 22 500 Pa
QC10-H-055 Rev.0 HVAC SPECIFICATION M15
775-1050 mm 20 500 Pa
10-QB20-R-601 HVAC DESIGN BASIS REPORT

23 DUCT CONSTRUCTION-01 24 DUCT CONSTRUCTION-02 25 DUCT CONSTRUCTION-03 26 DUCT CONSTRUCTION-04 10-UV00-B-601 HVAC General Notes & Legends

- - - -

R1
ENGINEER'S STAMP: CONTRACTOR'S STAMP:
USED WHERE ALL THREE DUCT
HEIGHTS H, H1 & H2 DIFFER SSEM DOCUMENT COMMENT SHEET
No. 10-UV00-G-601 No. EH-SSEMR-D-2142
Rev. 0 Date 22.01.2021
STATUS A: Approved for construction (AFC)
H2 B: Approved as noted (AAN)

H1 D: For Information only (INF)

WxH
150
B
R1

INTERNAL VANES
W1B x H1

NOTE:
REFER TO FIG. 2.5 PAGE 2.6 OF SMACNA-DUCT CONSTRUCTION FLANGE
R1A = 3/4 W1B STANDARDS FOR DIMENSIONS H1 & H2
R2

W2B x H2

R1B = R1A + W1A


B

REV. ISSUED FOR DRAWN CHECKED APPROVED DATE


R2A = 3/4 W2B SPOT WELDING
A R2B = R2A + W2A KINGDOM OF SAUDI ARABIA
R1 R2
R = 1 1/2 W A W 6.5mm TIE RODS ON INLET & OUTLET
W1A = x (W1B x H1) WELDED TO VANES & INSIDE FACE OF
WxH

(W1B x H1)+(W2B x H2)


ELBOW SALINE WATER CONVERSION CORPORATION (SWCC)
W DUCT WALL GASKET
W1A W2A W2A = x (W2B x H2)
(W1B x H1)+(W2B x H2)
WxH ELBOW DEPTH H NUMBER OF TIE
RODS REQUIRED Project No.
W

AL QUNFUDHAH NEW CITY FEEDER


0 - 300 mm NONE 200201034819
WATER TRANSMISSION SYSTEM
325 - 500 mm 1
525 - 1200 mm 2
H 1225 - 1600 mm 3
1625 - 2000 mm 4 AYESA ENGINEERING, TECHNOLOGY, CONSULTING
ENGINEER
0
15

27 RADIUS ELBOW - R = 1 1/2 W 28 END BRANCH - 2 29 SHORT RADIUS BENDS 30 SLIDE IN FLANGE JOINT CONNECTION DETAIL SAUDI SERVICES FOR ELECTRO MECHANIC WORKS CO. (CJSC)
CONTRACTOR
- - - -

HVAC TYPICAL INSTALLATION DETAILS


SCALE

NTS
DRAWING NO. SHEET REV.

1 0 - U V 0 0 - G - 6 0 1 2/4 1
FINAL
ENGINEERING
IBG Ltd.
GRAPHIC SCALE IN METERS:
0 1 5
115mm
90°
INSULATION
50mm R.

39mm
R.
DUCT 25mm R.
NOTES:

mm
PROVIDE RIGID INSULATION 57mm
GALV. STEELB DOOR WITH ALUMINUM FILE

115
SEE DETAIL-A 90°
(GAUGE 24) REINFORCED COATING
1. FOR DRAWING LEGEND AND FURTHER HVAC NOTES, REFER TO DWG NO. 10-UV00-B-601

50 mm
25 MM NEOPRENE
NOTCHED LOCK-OVER COATED FIBER-GLASS FIG. A 2. DUCT INSULATION SHALL BE AS PER SPECIFICATION M15.
EDGE FOR QUICK INSULATION SINGLE VANE ELBOW DETAIL 1
INSTALLATION SINGLE VANE
DETAIL 2
EXPANSION BOLT 25mm R. RUNNER
6 mm THICK STEEL MIN. 24 Ga.
PLATE WELD TO 90°
FLOOR ANGLE. 50mm R.

82
100 x 100

TRAPEZE SUPPORT 57 57 28mm

R.
SEAL WITH WALL 50mm R.
FOAM GASKET

mm
90°

1 00
CAM LOCK
DUCT INSULATION
R=57 MM FIG. B DETAIL 3
PROVIDE RIGID INSULATION SMALL DOUBLE VANE SMALL DOUBLE VANE
WITH ALUMINIUM FILE SUPPORT FROM ROOF STEEL
REINFORCED COATING. SQUARE ELBOW ALTERNATE DETAIL 4
LARGE DOUBLE VANE
GALVANIZED
THREADED ROD

S)
MM
4-1/2P. 206mm

DIU
GALV. STEEL FRAME INSULATION

115
(GAUGE 24) WITH SEAL

(RA
ANGLE IRON WELD AT DUCT RUNNER
ALL POINTS OF CONTACT 57mm
TYPE-2
LOCKING NUT 45° 45°
LOCK OVER EDGE AND WASHER
FRAME TYPICAL MASONRY
EXPANSION BOLT SUPPORT NUT
AND WASHER ANGLE IRON
FOAM
INSULATION PROVIDE RIGID INSULATION
WALL SUPPORT WITH ALUMINUM FILE FLOOR SUPPORT
NOTE : HINGE REINFORCED COATING
DOOR
PROVIDE ACCESS DOOR TO WITHIN REACHABLE DISTANCE NOTE: ALTERNATE FIG. C ALTERNATE DETAIL 5
FOR ALL FIRE DAMPERS. LARGE DOUBLE VANE
DETAIL-A ALL WELDED ANGLE IRON SUPPORT SHALL HAVE ANTI CORROSION LARGE DOUBLE VANE RUNNER
EPOXY COATING SQUARE ELBOW
LEGEND:

31 ACCESS DOOR DETAIL 32 DUCTWORK SUPPORT DETAIL 33 VANES & VANE RUNNERS 34 VANED ELBOW DETAIL
- - - -

FIRE DAMPER SLEEVE STRAP

FIRE DAMPER
25mm MIN. OVERLAP TO
ALL SIDE OF DAMPER WASHER
ROCKWOOL OR WEAK NUT
CONCRETE FILLER
6mm MIN. CONCRETE SLAB FOR DUCTS UP FOR DUCTS UP TO
TO 450mm. 910mm.
BOLTS AND NUTS, SCREWS
TACK WELDS OR STEEL POP PITTSBURGH LOCK DRIVE SLIP
RIVETS 300mm MAX. C/C DRIVE PIN THREADED STUD
LONGITUDINAL SEAMS
FIRE
DAMPER
POWDER ACTUATED FASTENERS
75 300 MAX.

DUCT DUCT

W
MAX.

BAR WHERE INDICATED

H
6mm CLEARANCE IN SCHEDULE

H
150 50*50*3mm THICK
MAX. ACCESS DOOR AS STEEL ANGLE
PER SMACNA
DUCT INSULATION STRAP ROD FOR DUCTS
6mm CLEARANCE ACCESS DOOR UP TO 450mm.
AS PER SMACNA
MAXIMUM
40x40x4mm THICK M.S STANDING S1 STANDING S2 EXPANSION SHIELDS EXPANSION NAIL
GALVANISED ANGLE DIMENSION.

CONCRETE ANCHORS

REFERENCE DRAWING:
DRAWING No. TITLE

35 FIRE DAMPER INSTALLATION DETAIL 36 FIRE DAMPER INSTALLATION DETAIL 37 DUCT JOINTS 38 UPPER ATTACHMENT FOR DUCT HANGERS QA10-G-008 Rev.3 PROJECT SPECIFICATION G02
QC10-H-055 Rev.0 HVAC SPECIFICATION M15
- VERTICAL - HORIZONTAL - -
10-QB20-R-601 HVAC DESIGN BASIS REPORT
10-UV00-B-601 HVAC General Notes & Legends

ENGINEER'S STAMP: CONTRACTOR'S STAMP:

SSEM DOCUMENT COMMENT SHEET


FACTORY WIRED FROM No. 10-UV00-G-601 No. EH-SSEMR-D-2142
MOTOR TO DISCONNECT Rev. 0 Date 22.01.2021
FRAMING FRAMING STATUS A: Approved for construction (AFC)
B: Approved as noted (AAN)
D: For Information only (INF)

200 OR 300 mm
DAMPER BLADE

ROOF CURB
CONNECTING BAR
CONNECTING DAMPER BLADE BLADES
BAR
20 mm
H-10
H

H+100

1950 < B < 3900 WIRING


150 < B < 1950
SHAFT EXTENSION B
WIRE GUARD REV. ISSUED FOR DRAWN CHECKED APPROVED DATE
B-10 MOTOR MOUNT
FAN FRAME
STOPPER KINGDOM OF SAUDI ARABIA
30 mm

SAND CHUTE SALINE WATER CONVERSION CORPORATION (SWCC)

25 100 SAND DRAIN HOLES


RECOMMENDED DUCT AND SECCURE FAN FRAME
FRONT SECTION B+100
RECOMMENDED
DAMPER SIZE MOTOR MOUNT TO BLOCKING
ROOF OPENING Project No. AL QUNFUDHAH NEW CITY FEEDER
200201034819
PLAN ELEVATION
WATER TRANSMISSION SYSTEM

ENGINEER AYESA ENGINEERING, TECHNOLOGY, CONSULTING

SAUDI SERVICES FOR ELECTRO MECHANIC WORKS CO. (CJSC)


CONTRACTOR
39 MULTIBLADE VOLUME DAMPER 40 FLUSH MOUNTED SAND TRAP LOUVER 41 ROOF MOUNTED CENTRIFUGAL EXHAUST FAN 42 WALL MOUNTED EXHAUST AXIAL FAN
- - - -
HVAC TYPICAL INSTALLATION DETAILS
SCALE

NTS
DRAWING NO. SHEET REV.

1 0 - U V 0 0 - G - 6 0 1 3/4 1
FINAL
ENGINEERING
IBG Ltd.
GRAPHIC SCALE IN METERS:
0 1 5

WALL
AIR GRILL
WITH DAMPER NOTES:

1. FOR DRAWING LEGEND AND FURTHER HVAC NOTES, REFER TO DWG NO. 10-UV00-B-601

WALL OPENING
2. DUCT INSULATION SHALL BE AS PER SPECIFICATION M15.
INSIDE OF BLDG OUTSIDE OF
BLDG.

CONCRETE
WALL

LOUVER
ELECTRICAL
CONDUIT
BY OTHERS

40X40X4MM
STEEL 'L' TYPE ANGLE BAR
FOR MOUNTING FRAME

BACKDRAFT
DAMPER
INSECT/ BIRD
SCREEN
SILICON
GASKET

SELF TAPPING S/M EXPANSION TYPE


SCREWS OR LAG BOLTS

LEGEND:

43 WALL MOUNTED EXHAUST FAN DETAIL 44 TYPICAL DETAIL OF EXHAUST AIR LOUVER
- -

AIR OUTLET
AIR INTAKE

3 OUTDOOR
CONDENSING UNIT
WALL CHASING WEATHERPROOF SLEEVES
4
FOR REFRIGERANT PIPING
CONDENSING UNIT
1
CONDENSING UNIT
SUCTION PIPE AIR INTAKE
REFRIGERANT PIPE INTERCONNECTING PIPING
2 CONCRETE SUPPORT (TYP.) AND WIRING CONCEALED IN
WALL
BASE INDOOR FAN
LIQUID PIPE COIL UNIT

CONCRETE
BASE AIR FILTER
AIR OUTLET

1. CLOSED CELL TUBE 1NSULATION 18mm. THICKNESS NEOPRENE REFRIGERANT PIPE REMOTE CONTROL
2. ADHESIVE FOSTER 85-20 OR EQUIVALENT FINSHED GRADE LEVEL
PADS SUCTION & LIQUID TO FCU REFER TO CIVIL DWGS.
3. 4 OZ. CORA CLOTH BONDED ON THE INSULATION WITH 2 LAYERS OF
ATLAS FOSTER 30-36 OR EQUIVALENT
4. 2 COATS OF VINYL BASED VAPOR BARRIER FOSTER 30-35 OR
EQUIVALENT
REFERENCE DRAWING:
CONDENSATE DRAIN
PIPE TO NEAREST DRAWING No. TITLE
NOTE: VIBRATION ISOLATOR
REFRIGERANT PIPE INSULATION IS SUBJECTED TO MANUFACTURER FLOOR DRAIN QA10-G-008 Rev.3 PROJECT SPECIFICATION G02
RECOMMENDATION AND PROJECT SPECIFICATION QC10-H-055 Rev.0 HVAC SPECIFICATION M15
10-QB20-R-601 HVAC DESIGN BASIS REPORT
10-UV00-B-601 HVAC General Notes & Legends

45 INSTALLATION OF REFRIGERANT 46 INSTALLATION OF SPLIT A/C UNIT AT ROOF LEVEL 47 INSTALLATION OF SPLIT A/C UNIT AT GROUND LEVEL 48 INSTALLATION DETAIL FOR DX SPLIT UNIT
- EXPOSED PIPES - (CONDENSING UNIT) - (CONDENSING UNIT) - ENGINEER'S STAMP: CONTRACTOR'S STAMP:

SSEM DOCUMENT COMMENT SHEET


No. 10-UV00-G-601 No. EH-SSEMR-D-2142
Rev. 0 Date 22.01.2021
STATUS A: Approved for construction (AFC)
B: Approved as noted (AAN)
D: For Information only (INF)

MAX. SAG 1/2" PER FOOT


OF SUPPORT SPACING GAGE 26 ALUMINIUM
NIPPLE CLADDING (FOR OUTDOOR
DRAIN CONNECTION
(40MMØ MIN.) LOCATION)
WATER LEVEL WHEN FAN IS
RUNNING

25mm BAND CLAMP WITH CELLULAR GLASS PIPE


CLEANOUT PLUG WIRE IS OPTIONAL INSULATION WITH FACTORY REV. ISSUED FOR DRAWN CHECKED APPROVED DATE

TEE AHU APPLIED VAPOR BARRIER


DRAIN PAN PITCH 1.0% (DOWN) KINGDOM OF SAUDI ARABIA

RUBBER VIBRATION ISOLATOR 300


X

mm SALINE WATER CONVERSION CORPORATION (SWCC)


300mm MINIMUM MA
XIM
TO NEAREST FLOOR DRAIN UM
OPEN DRIP FIG. A
FFL
X=TOTAL STATIC JOINT SEALER
Y

PRESSURE OF UNIT + 15 Project No. AL QUNFUDHAH NEW CITY FEEDER


(MM. WG.) Y=1/2(X) OR
LARGER OR 75MM MIN. 200201034819
WATER TRANSMISSION SYSTEM

PIPE NON-FERROUS BAND


U-BEND MAX. SAG 1/2" PER
FOOT OF SUPPORT 25mm MINIMUM
SPACING
1. NORMAL REINFORCED CONCRETE PAD WILL BE USED. OVERLAP ENGINEER AYESA ENGINEERING, TECHNOLOGY, CONSULTING
2. RUBBER VIBRATION ISOLATOR WILL BE USED BELOW FAN, AHU AND SMALL ACCU.
3. INTERNAL VIBRATION SPRING ISOLATOR WILL BE USED FOR AHU VENTILATOR BY
MANUFACTURER.
NOTES: 4. EXTERNAL VIBRATION SPRING ISOLATOR WILL BE USED FOR PACKAGE AND ACCU
1. ALLOW SUFFICIENT SPACE BELOW DRAIN PAN FOR TRAP. (CONDENSER)
2. PITCH DOWN DRAIN FOR PROPER RUN OFF. SAUDI SERVICES FOR ELECTRO MECHANIC WORKS CO. (CJSC)
BONDING ADHESIVE CONTRACTOR
3. MANUALLY PRIME FILL TRAP BEFORE START UP TO FORM INITIAL DRAIN SEAL. BETWEEN PIPE AND
FIG. B INSULATION
NOTE: HVAC TYPICAL INSTALLATION DETAILS
REFRIGERANT PIPE INSULATION IS SUBJECTED TO MANUFACTURER SCALE
RECOMMENDATION AND PROJECT SPECIFICATION
NTS
DRAWING NO. SHEET REV.
49 AHU/PAC DRAIN PIPE CONNECTION 50 TYPICAL AHU FOUNDATION DETAIL 51 FLEXIBLE DUCT SUPPORT DETAILS 52 REFRIGERANT PIPING INSULATION DETAIL
- - - -
1 0 - U V 0 0 - G - 6 0 1 4/4 1
FINAL
ENGINEERING
IBG Ltd.