FOOTING DESIGN

Axial Loads
Service 374 kN Bearing Capacity 150 kN/m2
Ultimate 546 kN
Column Dimensions
h 225 mm
fcu 25 Nmm2 b 225 mm
fy 460 Nmm2
fyv 460 Nmm2 Footing Depth 250 mm
Cover 40 mm
Main bar size 12 mm
Distri bar size 0 mm
d effective 204 mm
d' DNN mm
0

Footing Width 1600 mm


Footing Length 1600 mm

Suggest width 1579 mm

Surcharge has not been taken in to account in this calculations


As Provided shall be added manually
NG DESIGN
Calculations Area per meter width
K' = 0.176 Spacing T10 T12 T16
k = 0.048 100 785 1131 2011
125 628 905 1609
z = 192.354 mm 150 523 754 1314
175 449 646 1149
M/bd2 = 1.211 N/mm2 200 392 565 1005
250 314 452 804
Moment 50 kNm

As 600 mm2

As Provided 754 mm2

100As/bd = 0.370

Vc = 0.537 N/mm2

Vertical Line Shear Stress


v = 0.505 N/mm2 SHEAR OK

Punching Shear Stress


At Face of the Column
v = 2.974 SHEAR OK Vc = 4 0.8fcu

At 1.5d from face of the Column


v = 0.581 SHEAR FAIL
4 Nmm2 Provide 2T20
(main steel)

5 Nmm2
THIS IS WRONG SHEAR DESIGN
Input
V1
fcu 35 N/mm2
fyv 250 N/mm2 d eff
stirup Dia 10 mm
Cover 25 mm
x
L 5400 mm
h 750 mm
bv 300 mm L V2
V1 100 kN
V2 115 kN
log. Bar Dia.(at V1) 20 mm
log. Bar Dia.(at V2) 20 mm

Provide NOMINAL for V1 Provide NOMINAL for V2


Additional shear r/f to be provided 0.0 mm Additional shear r/f to be provided
(from the V1) (from the V2)

Smin 0.0 mm Smin 0.0 mm


IGN
d eff (at V1) 705 mm
d eff (at V2) 705 mm

h (beam height) V1d(Consider enhancement)/kN


71.93056 kN
V2d(Consider enhancement)/ 86.93056 kN

v1 0.340 N/mm2
v2 0.411 N/mm2

bv (100As/bd)1 0.297
(100As/bd)2 0.297

vc1 0.366 N/mm2


vc2 0.366 N/mm2

S min1 284.7 mm
S min2 284.7 mm

vc1+0.4 0.766 N/mm2


v +0.4
c
2
0.766 N/mm2
NAL for V2
0.0 mm Nominal shear r/f Smin 125 mm