38.12 THE NALCO WATER HANDBOOK
| J Semone
—%& i
os Heat
Cooling tower loads
Moat Cy
Oc - gpm
Bosin 3)
Voucs
FIG. 38.6 Evaporative cooling system using a cooling tower. Water
and solids balances are shown,
+ Limit ~ once-through flow
aod Upper limit ~ once-through flo
Exomple - 10,000 gpm at 20°F temperature cise
1000 = Makeup 4)
_-— Blowdown: M-E
Makeup. gpm
_- Evaporation (E)
Lower limit - evaporation rate
200
100 1 L L L L L
1 2 3 4 5 6 7 8
Concentration ratio (CR)
FIG. 38.7 Reduction of makeup flow by concentration ii
system,
an evaporative cooling
system and to permit the plant operator to calculate performance. Figure 38.6
helps to clarify these definitions.
1, Recirculation rate (QJ: This is the flow of cooling water being pumped
through the entire plant cooling loop, usually cooling a number of exchangers.
Q. can usually be estimated from the recirculating pump nameplate data:
however, actual measurements are more accurate. The actual recirculation is
seldom more than the nameplate data and frequently may be 10 to 20% less.
A pump curve, usually available from the manufacturer, plots recirculating
flow against head; a pressure gauge on the pump discharge should provide a
reasonably accurate estimate of flow.
2. Temperature differential or range (AT): This term refers to the difference
between the average water temperature returning to the tower from the plantCOOLING WATER TREATMENT 38.13
exchangers (7;) and the average water temperature following evaporation (7)
(tower basin).
. Evaporation (E): E is the water lost to the atmosphere in the cooling process
[gallons per minute (m’/min)]. The evaporation rate is dependent on the
amount of water being cooled (Q.) and the temperature differential, AT, As a
rule of thumb, for each 10°F (5.6°C) temperature drop across the evaporation
process, 1% of the recirculation rate (Q,) is evaporated. Therefore, a 20°F
(11.2°C) AT across a cooling tower produces an evaporation loss of 2% of the
recirculation rate (0.02 Q. = E).
= ¢ 0
<< @1000
a (i-T)
oa 560
(metric)
The amount of evaporation that can take place over a given tower is limited
primarily by the relative humidity of the air. Relative humidity is determined
by measuring the wet and dry bulb temperatures of the air. E can be as low
as 0.75% per 10°F of AT in high humidity areas like the Gulf Coast in the
United States. Conversely, E may be as high as 1.2% per 10°F AT in regions
of very low humidity, such as the arid regions of the southwestern United
States. E depends to a lesser degree on the liquid-to-gas flow ratio, and con-
ductive heat losses in other areas of cooling systems.
|. Makeup (M): The input of water required to replace the water lost by evap-
oration plus that being lost through blowdown, tower drift, and other mis-
cellaneous losses. It is usually measured by a flow meter; if not it may be
calculated as shown below:
M= Ex (ag)
eee
. Concentration ratio (CR): Makeup to a recirculating cooling water system
contains dissolved impurities. The evaporating water produces pure H,O
vapor, leaving behind these impurities. The ratio of the concentrations of
salts in the circulating water (C,) to those of the makeup (Cy) is the concen-
tration ratio.
CR = Ci Cy
Since the input solids must equal the output solids,
MX Cy = BX Ca
where M is the makeup flow and B represents loss of concentrated water.
Therefore, the concentration ratio is also
CR = M/B
The CR should be calculated for several individual components of the
water to determine if the system is “in balance.” In the ideal case, the system
is in balance when the CRs of all ions in the water (Ca, Mg, alkalinity, etc.)
are equal. If the concentration ratios are not equal, it can indicate that some38.14 THE NALCO WATER HANDBOOK
mineral (CaCO,, SiO,, etc.) is precipitating from the recirculating water. For
example, if the CR for calcium or alkalinity is more than 0.5 below the CR
for magnesium, then CaCO; is probably precipitating in the cooling system.
By knowing what may precipitate, the CR can be a valuable indicator that a
problem is occurring.
The concentration ratios of some ions will be affected by chemicals added
to the cooling system. The CR for SO,?- would be increased when sulfuric
acid is added or where the plant atmosphere contains SO. In these cases, the
CR for alkalinity would be decreased because alkalinity is destroyed by acid
added to the tower. Chlorination of the cooling water will increase the CR for
CI-. A CR based on conductivity will also be increased by some of the treat-
ment chemicals added.
‘As shown in Figure 38.7, even a small degree of concentration enormously
reduces water demand, and the greater the CR, the lower the demand as the
evaporation rate is approached as a limit.
Blowdown (B): Since pure water vapor is discharged by evaporation, the dis-
solved and suspended solids left behind concentrate. If there were no water
loss other than evaporation, these solids would concentrate to brine, causing
massive scale and corrosion. To balance this, regulated flow is bled from the
circulating system. This blowdown (B,) is calculated and controlled to
remove solids at the same rate at which they are introduced by the makeup.
There are other uncontrolled losses from the system. One is drift (B,); the
other is leakage (B,), sometimes deliberate, but usually accidental. These are
included in the total blowdown calculation,
oe
B= Be+ Bo+ By
Blowdown is related to other factors thus:
B=M-E
and B=M/CR
Pa
Drift (Bp): Even though evaporating water is pure, some water droplets
escape as mist through the evaporation equipment. In modern cooling tow-
ers, very intricate mist and drift eliminators may be added to reduce this
droplet loss to about 0.0005% of the recirculation rate. A more usual drift loss
in conventional cooling towers is in the range of 0.05 to 0.2% loss based on
the recirculation rate. Since drift contains dissolved solids it is really a por-
tion of the blowdown. In the absence of a controlled blowdown, as when the
blowdown valve is deliberately closed, drift establishes the maximum con-
centration ratio in the absence of other system losses.
}. System losses (B,): Circulating water may be lost in the plant through pump
or valve leaks; by tap-off for once-through cooling of pump glands, compres-
sor jackets, or bearings; or draw-off for such uses as equipment or floor area
washup when the cooling water line happens to be close to where water is
needed, In many plants, miscellaneous draw-off of recirculating cooling water
is so great that it is impossible to build up the concentration ratio over 1.2 to
1.5. This severely limits the selection of an economical chemical treatment
program and prevents effective conservation of water.
Holding capacity of system (V): Usually most of the water in a system is
contained in the cooling tower basin or spray pond. An approximation of the
holding capacity can be obtained by calculating the volume of water in the
2
=COOLING WATER TREATMENT 38.15
basin and adding an extra 20 to 30% for the water contained in the lines and
equipment. Additional increases may be required if the system has an
unusually large number of open box condensers, jacketed vessels, or furnaces
with substantial water holding capacity.
10. Time/cycle (): One cycle is defined as the time required for water to make
one trip around the circulating loop. This time is a function of the holding
capacity and the recirculation rate.
t= V/Q
Holding time index (HTI): The holding time index is an expression of the
half-life of a treatment chemical added to an evaporative cooling system.
Mathematically, this index represents the time required to dilute an added
chemical to 50% of its original concentration after the chemical addition is
discontinued. It is also the time required to concentrate the makeup solids by
a factor of 2. This is an important factor in setting control limits where chem-
ical feed may be interrupted. It is also important for establishing an effective
dosage for biological control agents, which are slug fed into the system. A
dilution curve for a chemical slug fed into a cooling tower system is illustrated
by Figure 38.8.
1
Calculation of Holding Time Index
The half-life of a system depends on the capacity and the rate at which the com-
ponents are leaving the system. For a cooling tower, the half-life depends primar-
ily on the system capacity and the blowdown rate. In its simplest form, the equa-
tion to calculate holding time index is
capacity (gal)
B (gal/min)
where 0.693 = In 2.0, a number derived from standard half-life equations.
To illustrate how the holding time index depends on other elements of a cool-
ing system, the factors used to calculate blowdown (B) can be substituted:
HTI = 0.693 X
capacity x (CR — 1)
HTI = 0.693 X =
or
capacity X (CR — 1)
Q. X aT X 0.001
This illustrates that a change in several factors (Q,, AT, CR, or capacity) will all
affect the HTT.
Another method of calculating holding time index is illustrated in the follow-
ing example.
HTI = 0.693 X
1, Calculate the time per cycle, t.
2. From Table 38.1 determine the number of cycles required to reach the pre-
vailing concentration ratio, based on the temperature drop through the tower
or spray pond.38.16 ‘THE NALCO WATER HANDBOOK
3. Multiply this by the time per cycle to get the holding time index expressed in
minutes, then divide by 60 or 1440 to convert to hours or days, respectively.
The following example illustrates this calculation:
1, Recirculation rate: Pump data show a recirculation rate of 5500 gal/min (21
m°/min). Use 5000 gal/min (19 m/min) as a good estimate of actual
recirculation.
1000
Example: A slug of biocide at 50 mg/t
would be diluted to 25 mg/l in 34 passes
(1 2% evaporation (20°F)
100
Passes cross tower ot 20°F
10
0 20 40 60 80 100
Percent of original concentration remaining
FIG. 38.8 The effect of time and makeup dilution on slug appli-
cation of a chemical to an evaporative cooling water system.COOLING WATER TREATMENT 38.17
TABLE 38.1 Cycles Required to Concentrate in the
Absence of Blowdown
a ‘Temperature drop through tower
ratio 10° 20" 30"
Lt 6S cycles —3.2cycles 2.1 cycles
13 20.2 10.2 70
13 34.5 172 117
18 35 28 19
20 69 34 23
25 105 52 35
3.0 138 70 47
35 174 87 58
40 208 104 70
45 241 120 81
5.0 324 162 93
2. Temperature drop:
105°F — 85°F = 20°F
(VC — 30°C = 11°C)
3. Evaporation loss: 20°F (11°C) is equivalent to 2% evaporation loss:
0.02 >< $000 = 100 gal/min evaporation loss
4. Concentration ratio (see analyses on Figure 38.9): Tests on the makeup and
recirculating water show concentration ratios of 2.8 to 8.3.
The approximate concentration ratio is 3.0 based on magnesium and silica,
since magnesium and silica remain soluble at the prevailing pH and concen-
tration conditions, Chlorine and sulfuric acid are both being added to the sys-
tem and thereby eliminate the use of Cl” and SO,~ as valid CR indicators.
$. Makeup:
CR
Mn Ex(G5)
M= 100 x 3 = 150 gal/min
(M = 0.38 x 3 = 0.57 m/min)
6. Holding capacity of the system: Basin contains 72,000 gal (284 m’). The total
holding capacity of the system is estimated to be 100,000 gal (379 m’).38.18 THE NALCO WATER HANDBOOK,
igentfieation of Analyses Tabslated Betow |
a Raw water 6.
|
_Recirculated cooling water ¢ }
|_c_Concentration ratios F |
Consttueat ae
Caleum GC)
[CMagnenamn
Sodium (by difference)
Total Electeoivte x0
Bicarbonate ‘x00.
Carbonate =
Hvaroxvi
Suutore
rend t
Cee Saace ——
war Teco) 190
P alk TR_|
Carbon Drange TR
no
Sia
Toba
TDS
Goler
T
Not valid, since |CIl, and 4,50] are being fed.
T
FIG. 38.9 Concentration ratios in an evaporative cooling system.
7. Time/cycle:
100,000
[0008 «ce
379 m*
379m’,
(« Cre ge mi)
8. Holding time index: If CR = 3, and AT
average cycles at 70; at 70 cycles,
HTI = 70 X 20 = 1400 min, or 23h
20°F (11°C), Table 38.1 showsCOOLING WATER TREATMENT 38.19
COOLING TOWERS
Cooling towers are designed to evaporate water by intimate contact of water with
air. Cooling towers are classified by the method used to induce air flow (natural
or mechanical draft) and by the direction of air flow (either counterflow or cross-
flow relative to the downward flow of water).
In natural draft towers, air flow depends on the surrounding atmosphere,
which establishes the difference in densities between the warmer air inside the
tower and the external atmosphere; wind velocity also affects performance. Most
natural draft towers in modern utility service are of hyperbolic design (Figure
38.10), which has been used for many years in European installations. These tall
towers provide cooling without fan power, and they also minimize plume prob-
lems and drift.
FIG. 38.10 Hyperbolic towers cooling condenser water ina utility station. (Courtesy
of The Marley Company.)
Mechanical draft cooling towers use fans to move air instead of depending on
natural draft or wind. This speeds the cooling process and increases the efficiency
of the tower by increasing the air velocity over droplets of water falling through
the tower. Mechanical towers can, therefore, evaporate much more water than
natural draft towers of the same size.
There are two designs of mechanical draft towers, forced and induced draft. In
forced draft towers (Figure 38.11) fans mounted on the side of the tower force
through the tower packing, producing intimate mixing of air with the falling
water.
Induced draft cooling towers (Figure 38.12) are either counterflow or crossflow
with fans on top pulling cooling air up through or horizontally across the falling
water. The choice between forced draft and induced draft is based on engineering
considerations that take prevailing weather patterns into account. A major con-
sideration is to avoid recirculation of the warm air discharge, which would greatlyWorm moist
Drift eliminator air discharge
section
Spray pipe
distributors Hot water
return
Enclosed
sides
oo
Basin with level controls ———_
for makeup regulation
FIG. 38.11 Forced-draft tower design. This design was widely used prior to
development of the induced-draft design. Fans and motors are conveniently
located for maintenance.
circulating pump
FIG. 38.12 Induced-draft tower. Air enters the tower louvers and is well distributed before
exiting at top.
38.20