S7-300 Module data

Digital output module SM 322; DO 8 x DC 48-125 V/1.5 A; (6ES7322-1CF00-0AA0)

Digital output module SM 322; DO 8 x DC 48-125 V/1.5 A; (6ES7322-1CF00-0AA0)

Order number: "Standard module"


6ES7322-1CF00-0AA0

Order number: "SIPLUS S7-300 module"


6AG1322-1CF00-2AA0

Properties
Properties of SM 322; DO 8 x DC 48-125 V/1.5 A:
• 8 outputs, with reverse polarity protection, and electrically isolated in groups of 4

• Output current 1.5 A

• Rated load voltage 48 VDC to 125 VDC

• Suitable for solenoid valves, DC contactors and signal lamps

• Group error display (SF)

Use of the module with high-speed counters


Please note when using the module in combination with high-speed counters:

Note
When using a mechanical contact to switch on the power supply, the outputs of SM 322; DO
8 x DC 48-125 V/1.5 A will carry a "1" signal for the duration of ca. 50 µs due to the circuit structure.

This document constitutes a free excerpt compiled by the user himself/herself from the documentation provided by Siemens for this product. Siemens disclaims all liability for the
completeness of this document. It shall only be used for the user's own internal purposes. It shall not be passed on to third parties.
3/17/2021
S7-300 Module data
Digital output module SM 322; DO 8 x DC 48-125 V/1.5 A; (6ES7322-1CF00-0AA0)

Wiring and block diagrams of SM 322; DO 8 x DC 48-125 V/1.5 A

① Channel number
② Status display - green
Error LED - red
③ Backplane bus interface

Technical specifications of M 322; DO 8 x DC 48-125 V/1.5 A

Technical specifications

Dimensions and weight

Dimensions W x H x D (mm) 40 x 125 x 117

Weight ca. 250 g

Module-specific data

Supports isochronous mode no

Number of outputs 8

Cable length max. 600 m


• unshielded max. 1000 m
• shielded

This document constitutes a free excerpt compiled by the user himself/herself from the documentation provided by Siemens for this product. Siemens disclaims all liability for the
completeness of this document. It shall only be used for the user's own internal purposes. It shall not be passed on to third parties.
3/17/2021
S7-300 Module data
Digital output module SM 322; DO 8 x DC 48-125 V/1.5 A; (6ES7322-1CF00-0AA0)

Technical specifications

Voltages, currents, electrical potentials

Rated load voltage L+ 48 VDC to 125 VDC

• Reverse polarity protection yes, by fusing1)

Total current of outputs (per group)

• horizontal mounting position max. 6 A


to 40 °C max. 4 A
to 50 °C max. 3 A
to 60 °C

• vertical mounting position max. 4 A


to 40 °C

Electrical isolation yes


• between channels and the backplane bus

• between channels yes


in groups of 4

Maximum potential difference 146 VDC / 132 VAC


• between different circuits

Isolation test voltage 1500 VAC

Current consumption max. 100 mA


• from the backplane bus max. 2 mA
• from load voltage L+ (no-load)

Power loss of the module typ. 7.2 W

Status, interrupts, diagnostics

Status display green LED per channel

Interrupts none

Diagnostic functions red LED (SF) 2)


• Group error display

Actuator selection data

Output voltage min. L+ (-1.2 V)


• "1" signal

Output current
1.5 A
• "1" signal
10 mA to 1.5 A
Rated value
Permitted range

• Permitted surge current max. 3 A for a duration of 10 ms

• with "0" signal (residual current) max. 0.5 mA

Output delay (resistive load)

This document constitutes a free excerpt compiled by the user himself/herself from the documentation provided by Siemens for this product. Siemens disclaims all liability for the
completeness of this document. It shall only be used for the user's own internal purposes. It shall not be passed on to third parties.
3/17/2021
S7-300 Module data
Digital output module SM 322; DO 8 x DC 48-125 V/1.5 A; (6ES7322-1CF00-0AA0)

Technical specifications

• "0" to "1" transition max. 2 ms


• "1" to "0" transition max. 15 ms

Lamp load max. 15 W at 48 V


max. 40 W at 125 V

Wiring two outputs in parallel

• for redundant load control supported (only outputs of the same group)

• for performance increase not supported

Control of a digital input supported

Switching frequency max. 25 Hz


• with resistive load max. 0.5 Hz
• with inductive load max. 10 Hz
• with lamp load

Internal limiting of the inductive shutdown voltage to typ. M (-1V)

Short-circuit protection of the output yes, electronic3)


• Threshold typ. 4.4 A

Replacement fuses Fuse 6.3 A/250 V, fast-blow, 5 x 20 mm

• Schurter SP0001.1012
• Wickman 194-1630-0

Fuse holder 653 0000 040


• Wickman

Wiring of the actuators using a 20-pin front connector

1) Fuses on this module are only supplementary. External surge current protection (suitable for tap
circuits conforming to local regulations for electrical engineering) is required in the supply lines of the
load circuit.
2) Possible errors:
- no load voltage
- defective fuse
- output overload
3) If an overload condition is detected, the output is disabled for the duration of ca. 2.4 s.

This document constitutes a free excerpt compiled by the user himself/herself from the documentation provided by Siemens for this product. Siemens disclaims all liability for the
completeness of this document. It shall only be used for the user's own internal purposes. It shall not be passed on to third parties.
3/17/2021