Field Connection
Cooling Capacity in Cooling Capacity
Type Model Suction Liquid
TR in KW
Hi Wall VHW10 0.8 2.8 9.5(3/8") 6.35 (1/4") When liquid line length is >10m, use 9.5mm (3/8") instead of 6.35mm (1/4")
Hi Wall VHW12 1.0 3.5 9.5(3/8") 6.35 (1/4") When liquid line length is >10m, use 9.5mm (3/8") instead of 6.35mm (1/4")
Hi Wall VHW16 1.3 4.6 12.7 (1/2") 6.35 (1/4") When liquid line length is >10m, use 9.5mm (3/8") instead of 6.35mm (1/4")
Hi Wall VHW18 1.5 5.3 12.7 (1/2") 6.35 (1/4") When liquid line length is >10m, use 9.5mm (3/8") instead of 6.35mm (1/4")
Hi Wall VHW20 1.7 6.0 15.9 (5/8") 9.5 (3/8")
Compact Cassette VCC12 1.0 3.5 12.7 (1/2") 6.35 (1/4") When liquid line length is >10m, use 9.5mm (3/8") instead of 6.35mm (1/4")
Compact Cassette VCC16 1.3 4.6 12.7 (1/2") 6.35 (1/4")
Large Cassette VLC24 2.0 7.0 15.9 (5/8") 9.5 (3/8") 1. When liquid line length is >10m, use 9.5mm (3/8") instead of 6.35mm (1/4")
Large Cassette VLC27 2.3 8.1 15.9 (5/8") 9.5 (3/8") 2. When liquid line length is >10m, use 12.7mm (1/2") instead of 9.5mm (3/8") for DLC 48 and DLC 60 only
Large Cassette VLC34 2.8 9.8 15.9 (5/8") 9.5 (3/8")
Floor Cum Ceiling Mounted Unit VFC18 1.5 5.3 12.7 (1/2") 6.35 (1/4")
Floor Cum Ceiling Mounted Unit VFC24 2.0 7.0 15.9 (5/8") 9.5 (3/8")
Floor Cum Ceiling Mounted Unit VFC36 3.0 10.6 19.1 (3/4") 9.5 (3/8")
Floor Cum Ceiling Mounted Unit VFC48 4.0 14.1 19.1 (3/4") 9.5 (3/8")
Floor Cum Ceiling Mounted Unit VFC60 5.0 17.6 19.1 (3/4") 9.5 (3/8")
Page 1
Verticools VVC38 3.2 11.3 19.1 (3/4") 12.7 (1/2")
Concealed Split DCS16 1.3 4.6 12.7 (1/2") 6.35 (1/4") When liquid line length is >10m, use 9.5mm (3/8") instead of 6.35mm (1/4")
Concealed Split DCS18 1.5 5.3 12.7 (1/2") 6.35 (1/4")
Ducted Splits DSD36 3.0 10.6 15.9 (5/8") 9.5 (3/8") 1. When liquid line length is >10m, use 9.5mm (3/8") instead of 6.35mm (1/4")
Ducted Splits DSD48 4.0 14.1 15.9 (5/8") 9.5 (3/8") 2. When liquid line length is >10m, use 12.7mm (1/2") instead of 9.5mm (3/8") for DSD 48 and above.
Ducted Splits DSD60 5.0 17.6 19.1 (3/4") 9.5 (3/8")
Floor Mounted DFM-96 8.0 28.1 28.6 (1 1/8") 12.7 (1/2") When liquid line length is >10m, use 12.7mm (1/2") instead of 9.5mm (3/8")
Treated Fresh Air DTFA42 3.5 12.3 15.9 (5/8") 9.5 (3/8")
Treated Fresh Air DTFA66 5.5 19.3 19.1 (3/4") 9.5 (3/8") When liquid line length is >10m, use 12.7mm (1/2") instead of 9.5mm (3/8"), for DTFA 66 & DTFA 82 only
Treated Fresh Air DTFA82 6.8 23.9 22.2 (7/8") 9.5 (3/8")
Heat Recovery Units DHRV03 0.8 2.6 12.7 (1/2") 6.35 (1/4")
Heat Recovery Units DHRV05 1.3 4.6 12.7 (1/2") 6.35 (1/4") When liquid line length is >10m, use9.5mm (3/8") instead of 6.35mm (1/4")
Heat Recovery Units DHRV09 2.2 7.7 15.9 (5/8") 9.5 (3/8")
Ducted Splits - AHU Type VSD132A 11.0 38.7 28.6(1 1/8") 12.7 (1/2") DAEKIT-100
Ducted Splits - AHU Type VSD216A 18.0 63.3 28.6(1 1/8") 15.9 (5/8") DAEKIT-200
Ducted Splits - AHU Type VSD240A 20.0 70.3 28.6(1 1/8") 15.9 (5/8") DAEKIT-200
Floor Mounted - AHU Type VFM216A 18.0 63.3 28.6(1 1/8") 15.9 (5/8") DAEKIT-200
Floor Mounted - AHU Type VFM264A 22.0 77.4 34.9 (1 3/8") 19.05 (3/4") DAEKIT-250
Page 2
VRF V PLUS
Top Discharge Type ODU Field Connection Sizes
7HP 8HP 10HP 12HP 14HP 16HP 18HP 20HP 22HP 24HP 26HP 28HP
inch Ǿ mm Ǿ inch Ǿ mm Ǿ inch Ǿ mm Ǿ inch Ǿ mm Ǿ inch Ǿ mm Ǿ inch Ǿ mm Ǿ inch Ǿ mm Ǿ inch Ǿ mm Ǿ inch Ǿ mm Ǿ inch Ǿ mm Ǿ inch Ǿ mm Ǿ inch Ǿ mm Ǿ
Suction 3/4 19.1 3/4 19.1 7/8 22.2 1 1/8 28.6 1 1/8 28.6 1 1/8 28.6 1 1/8 28.6 1 1/8 28.6 1 1/8 28.6 1 1/8 28.6 1 3/8 34.9 1 3/8 34.9
Liquid 3/8 9.5 3/8 9.5 3/8 9.5 1/2 12.7 1/2 12.7 1/2 12.7 5/8 15.9 5/8 15.9 5/8 15.9 5/8 15.9 3/4 19.1 3/4 19.1
oil 1/4 6.4 1/4 6.4 1/4 6.4 1/4 6.4 1/4 6.4 1/4 6.4 1/4 6.4 1/4 6.4 1/4 6.4 1/4 6.4 1/4 6.4 1/4 6.4
ODU Branch Piping ("OL", "ML")
(Base on Sum of ODU capacity)
VRF V PLUS
HP KW HP KW HP KW HP KW HP KW HP KW HP KW HP KW HP KW HP KW HP KW
If liquid pipe >40m use one size bigger pipe ; except for 1 1/8"
Oil Piping
Oil Piping between ODU's : Use 1/4" (6.35mm ) copper tubes
Page 4
Pipe sizing First branch to IDUs ("BL")
(Base on Sum of IDU capacity)
VRF V PLUS
Revised Recommended Pipe Size (05.12.2017)
Capacity Range
Suction Liquid Suction Liquid
KW KW TR TR mm Ǿ mm Ǿ In Ǿ mm Ǿ
≥ 7.0 < 14.1 ≥ 2.0 < 4.0 15.9 9.5 5/8" 3/8"
> 22.4 ≤ 28.0 > 6.4 ≤ 8.0 22.2 9.5 7/8" 3/8"
> 28.0 ≤ 44.8 > 8.0 ≤ 12.7 28.6 12.7 1 1/8" 1/2"
> 44.8 ≤ 67.2 > 12.7 ≤ 19.1 28.6 15.9 1 1/8" 5/8"
> 67.2 ≤ 100.8 > 19.1 ≤ 28.7 34.9 19.1 1 3/8" 3/4"
> 151.2 ≤ 173.6 > 43.0 ≤ 49.4 41.3 22.2 1 5/8" 7/8"
> 173.6 ≤ 201.6 > 49.4 ≤ 57.3 41.3 22.2 1 5/8" 7/8"
> 201.6 ≤ 257.6 > 57.3 ≤ 73.3 44.5 28.6 1 3/4" 1 1/8"
IMPORTANT NOTE :
Pipe sizes from first branch onwards to IDUs "BL" are given in the above table.
While sizing "BL" remember to cross - check with the sizes of "ML" (ODU to first branch) as well,
The below rule may be applied:
When ODU capacity < IDU capacity, Size the pipe as per ODU capacity.
i.e. = Size of "ML"
When ODU capacity = IDU capacity, Size the pipe as per ODU capacity.
i.e. = Size of "ML"
When ODU capacity > IDU capacity, Size the pipe as per IDU capacity.
i.e. = Size of "ML"
Page 5
VRF V PLUS ODU Cable Size Cable Size
Sr. No MCB Rating
Model (Copper) (Aluminium)
1 7 HP 4 6 32
2 8 HP 4 6 32
3 10 HP 6 10 40
4 12HP 6 10 40
5 14HP 6 10 40
6 16 HP 10 16 50
7 18 HP 16 25 63
8 20 HP 16 25 63
9 22 HP 16 25 63
10 24 HP 16 25 63
11 26 HP 25 35 80
12 28 HP 25 35 80