Proposed Refrigerant piping sizes for VRF V PLUS - IDUs

Field Connection
Cooling Capacity in Cooling Capacity
Type Model Suction Liquid
TR in KW

Hi Wall VHW10 0.8 2.8 9.5(3/8") 6.35 (1/4") When liquid line length is >10m, use 9.5mm (3/8") instead of 6.35mm (1/4")
Hi Wall VHW12 1.0 3.5 9.5(3/8") 6.35 (1/4") When liquid line length is >10m, use 9.5mm (3/8") instead of 6.35mm (1/4")
Hi Wall VHW16 1.3 4.6 12.7 (1/2") 6.35 (1/4") When liquid line length is >10m, use 9.5mm (3/8") instead of 6.35mm (1/4")
Hi Wall VHW18 1.5 5.3 12.7 (1/2") 6.35 (1/4") When liquid line length is >10m, use 9.5mm (3/8") instead of 6.35mm (1/4")
Hi Wall VHW20 1.7 6.0 15.9 (5/8") 9.5 (3/8")

Hi Wall VHW24 2.0 7.0 15.9 (5/8") 9.5 (3/8")

Compact Cassette VCC08 0.6 2.1 12.7 (1/2") 6.35 (1/4")

Compact Cassette VCC10 0.8 2.8 12.7 (1/2") 6.35 (1/4")

Compact Cassette VCC12 1.0 3.5 12.7 (1/2") 6.35 (1/4") When liquid line length is >10m, use 9.5mm (3/8") instead of 6.35mm (1/4")
Compact Cassette VCC16 1.3 4.6 12.7 (1/2") 6.35 (1/4")

Compact Cassette VCC18 1.5 5.3 12.7 (1/2") 6.35 (1/4")

Large Cassette VLC12 1.0 3.5 12.7 (1/2") 6.35 (1/4")

Large Cassette VLC16 1.3 4.6 12.7 (1/2") 6.35 (1/4")

Large Cassette VLC18 1.5 5.3 12.7 (1/2") 6.35 (1/4")

Large Cassette VLC20 1.7 6.0 12.7 (1/2") 9.5(3/8")

Large Cassette VLC24 2.0 7.0 15.9 (5/8") 9.5 (3/8") 1. When liquid line length is >10m, use 9.5mm (3/8") instead of 6.35mm (1/4")
Large Cassette VLC27 2.3 8.1 15.9 (5/8") 9.5 (3/8") 2. When liquid line length is >10m, use 12.7mm (1/2") instead of 9.5mm (3/8") for DLC 48 and DLC 60 only
Large Cassette VLC34 2.8 9.8 15.9 (5/8") 9.5 (3/8")

Large Cassette VLC38 3.2 11.3 15.9 (5/8") 9.5 (3/8")

Large Cassette VLC48 4.0 14.1 15.9 (5/8") 9.5 (3/8")

Large Cassette VLC60A 5.0 17.6 19.1 (3/4") 9.5 (3/8")

One-Way Cassettes VOC08 0.6 2.1 12.7 (1/2") 6.35 (1/4")

One-Way Cassettes VOC10 0.8 2.8 12.7 (1/2") 6.35 (1/4")

One-Way Cassettes VOC12 1.0 3.5 12.7 (1/2") 6.35 (1/4")

One-Way Cassettes VOC16 1.3 4.6 15.9(5/8") 9.5(3/8")

One-Way Cassettes VOC19 1.6 5.6 15.9 (5/8") 9.5(3/8")

One-Way Cassettes VOC24 2.0 7.0 15.9 (5/8") 9.5(3/8")

Two-Way Cassettes VTC08 0.6 2.1 12.7 (1/2") 6.35 (1/4")

Two-Way Cassettes VTC10 0.8 2.8 12.7 (1/2") 6.35 (1/4")

Two-Way Cassettes VTC12 1.0 3.5 12.7 (1/2") 6.35 (1/4")

Two-Way Cassettes VTC16 1.3 4.6 15.9(5/8") 9.5 (3/8")

Two-Way Cassettes VTC18 1.5 5.3 15.9(5/8") 9.5 (3/8")

Two-Way Cassettes VTC20 1.7 6.0 15.9(5/8") 9.5 (3/8")

Two-Way Cassettes VTC24 2.0 7.0 15.9 (5/8") 9.5 (3/8")

Floor Cum Ceiling Mounted Unit VFC18 1.5 5.3 12.7 (1/2") 6.35 (1/4")

Floor Cum Ceiling Mounted Unit VFC24 2.0 7.0 15.9 (5/8") 9.5 (3/8")

Floor Cum Ceiling Mounted Unit VFC36 3.0 10.6 19.1 (3/4") 9.5 (3/8")

Floor Cum Ceiling Mounted Unit VFC48 4.0 14.1 19.1 (3/4") 9.5 (3/8")

Floor Cum Ceiling Mounted Unit VFC60 5.0 17.6 19.1 (3/4") 9.5 (3/8")

Verticools VVC24 2.0 7.0 15.9 (5/8") 9.5 (3/8")

Verticools VVC27 2.3 8.1 15.9 (5/8") 9.5 (3/8")

Verticools VVC34 2.8 9.8 15.9 (5/8") 9.5 (3/8")

Page 1
Verticools VVC38 3.2 11.3 19.1 (3/4") 12.7 (1/2")

Verticools VVC48 4.0 14.1 19.1 (3/4") 12.7 (1/2")

Concealed Split DCS 10 0.8 2.8 12.7 (1/2") 6.35 (1/4")

Concealed Split DCS12 1.0 3.5 12.7 (1/2") 6.35 (1/4")

Concealed Split DCS16 1.3 4.6 12.7 (1/2") 6.35 (1/4") When liquid line length is >10m, use 9.5mm (3/8") instead of 6.35mm (1/4")
Concealed Split DCS18 1.5 5.3 12.7 (1/2") 6.35 (1/4")

Concealed Split DCS24 2.0 7.0 15.9 (5/8") 9. 5(3/8")

Ducted Splits DSD18 1.5 5.3 12.7 (1/2") 6.35 (1/4")

Ducted Splits DSD24 2.0 7.0 15.9 (5/8") 9.5 (3/8")

Ducted Splits DSD30 2.5 8.8 15.9 (5/8") 9.5 (3/8")

Ducted Splits DSD36 3.0 10.6 15.9 (5/8") 9.5 (3/8") 1. When liquid line length is >10m, use 9.5mm (3/8") instead of 6.35mm (1/4")
Ducted Splits DSD48 4.0 14.1 15.9 (5/8") 9.5 (3/8") 2. When liquid line length is >10m, use 12.7mm (1/2") instead of 9.5mm (3/8") for DSD 48 and above.
Ducted Splits DSD60 5.0 17.6 19.1 (3/4") 9.5 (3/8")

Ducted Splits DSD72 6.0 21.1 19.1 (3/4") 9.5 (3/8")

Ducted Splits DSD96 8.0 28.1 22.2 (7/8") 9.5 (3/8")

Floor Mounted DFM-60 5.0 17.6 19.1 (3/4") 9.5 (3/8")

Floor Mounted DFM-96 8.0 28.1 28.6 (1 1/8") 12.7 (1/2") When liquid line length is >10m, use 12.7mm (1/2") instead of 9.5mm (3/8")

Floor Mounted DFM-120 10.0 35.2 28.6(1 1/8") 12.7 (1/2")

Treated Fresh Air DTFA42 3.5 12.3 15.9 (5/8") 9.5 (3/8")
Treated Fresh Air DTFA66 5.5 19.3 19.1 (3/4") 9.5 (3/8") When liquid line length is >10m, use 12.7mm (1/2") instead of 9.5mm (3/8"), for DTFA 66 & DTFA 82 only
Treated Fresh Air DTFA82 6.8 23.9 22.2 (7/8") 9.5 (3/8")

Heat Recovery Units DHRV03 0.8 2.6 12.7 (1/2") 6.35 (1/4")

Heat Recovery Units DHRV05 1.3 4.6 12.7 (1/2") 6.35 (1/4") When liquid line length is >10m, use9.5mm (3/8") instead of 6.35mm (1/4")
Heat Recovery Units DHRV09 2.2 7.7 15.9 (5/8") 9.5 (3/8")

Ducted Splits - AHU Type VSD132A 11.0 38.7 28.6(1 1/8") 12.7 (1/2") DAEKIT-100
Ducted Splits - AHU Type VSD216A 18.0 63.3 28.6(1 1/8") 15.9 (5/8") DAEKIT-200
Ducted Splits - AHU Type VSD240A 20.0 70.3 28.6(1 1/8") 15.9 (5/8") DAEKIT-200
Floor Mounted - AHU Type VFM216A 18.0 63.3 28.6(1 1/8") 15.9 (5/8") DAEKIT-200
Floor Mounted - AHU Type VFM264A 22.0 77.4 34.9 (1 3/8") 19.05 (3/4") DAEKIT-250

AHU PIPE SIZES:

Capacity AHU Kit Model Field Connection


TR kW Suction Liquid
mm (In) mm (In)
5 17.6 DAEKIT-050 19.1 9.5
6.5 22.9 DAEKIT-065 22.2 9.5
8 28.1 DAEKIT-080 22.2 9.5
10 35.2 DAEKIT-100 28.6 12.7
12.5 44 DAEKIT-125 28.6 12.7
15 52.7 DAEKIT-150 28.6 15.9
20 70.3 DAEKIT-200 28.6 15.9
25 87.9 DAEKIT-250 34.9 19.1
32 112.5 DAEKIT-300 41.3 19.1

Page 2
VRF V PLUS
Top Discharge Type ODU Field Connection Sizes
7HP 8HP 10HP 12HP 14HP 16HP 18HP 20HP 22HP 24HP 26HP 28HP
inch Ǿ mm Ǿ inch Ǿ mm Ǿ inch Ǿ mm Ǿ inch Ǿ mm Ǿ inch Ǿ mm Ǿ inch Ǿ mm Ǿ inch Ǿ mm Ǿ inch Ǿ mm Ǿ inch Ǿ mm Ǿ inch Ǿ mm Ǿ inch Ǿ mm Ǿ inch Ǿ mm Ǿ
Suction 3/4 19.1 3/4 19.1 7/8 22.2 1 1/8 28.6 1 1/8 28.6 1 1/8 28.6 1 1/8 28.6 1 1/8 28.6 1 1/8 28.6 1 1/8 28.6 1 3/8 34.9 1 3/8 34.9

Liquid 3/8 9.5 3/8 9.5 3/8 9.5 1/2 12.7 1/2 12.7 1/2 12.7 5/8 15.9 5/8 15.9 5/8 15.9 5/8 15.9 3/4 19.1 3/4 19.1

oil 1/4 6.4 1/4 6.4 1/4 6.4 1/4 6.4 1/4 6.4 1/4 6.4 1/4 6.4 1/4 6.4 1/4 6.4 1/4 6.4 1/4 6.4 1/4 6.4
ODU Branch Piping ("OL", "ML")
(Base on Sum of ODU capacity)
VRF V PLUS
HP KW HP KW HP KW HP KW HP KW HP KW HP KW HP KW HP KW HP KW HP KW

14 39.2 18 50.4 26 72.8 38 106.4 56 156.8 64 179.2 74 207.2 94 263.2


16 44.8 20 56.0 28 78.4 40 112.0 58 162.4 66 184.8 76 212.8 96 268.8
22 61.6 30 84.0 42 117.6 60 168.0 68 190.4 78 218.4 98 274.4
24 67.2 32 89.6 44 123.2 62 173.6 70 196.0 80 224.0 100 280.0
34 95.2 46 128.8 72 201.6 82 229.6 102 285.6
8 22.4 10 28 12 33.6
36 100.8 48 134.4 84 235.2 104 291.2
50 140.0 86 240.8 106 296.8
52 145.6 88 246.4 108 302.4
54 151.2 90 252.0 110 308.0
92 257.6 112 313.6
Pipe Ǿ mm In mm In mm In mm In mm In mm In mm In mm In mm In mm In mm In
Suction 19.1 3/4" 22.2 7/8" 28.6 1 1/8" 28.6 1 1/8" 28.6 1 1/8" 34.9 1 3/8" 41.3 1 5/8" 41.3 1 5/8" 41.3 1 5/8" 44.5 1 3/4" 54 2 1/8"
Liquid 9.5 3/8" 9.5 3/8" 12.7 1/2" 12.7 1/2" 15.9 5/8" 19.1 3/4" 19.1 3/4" 22.2 7/8" 22.2 7/8" 28.6 1 1/8" 28.6 1 1/8"

If liquid pipe >40m use one size bigger pipe ; except for 1 1/8"

Oil Piping
Oil Piping between ODU's : Use 1/4" (6.35mm ) copper tubes

Page 4
Pipe sizing First branch to IDUs ("BL")
(Base on Sum of IDU capacity)
VRF V PLUS
Revised Recommended Pipe Size (05.12.2017)
Capacity Range
Suction Liquid Suction Liquid

KW KW TR TR mm Ǿ mm Ǿ In Ǿ mm Ǿ

- < 7.0 - < 2.0 12.7 9.5 1/2" 3/8"

≥ 7.0 < 14.1 ≥ 2.0 < 4.0 15.9 9.5 5/8" 3/8"

≥ 14.1 ≤ 22.4 ≥ 4.0 ≤ 6.4 19.1 9.5 3/4" 3/8"

> 22.4 ≤ 28.0 > 6.4 ≤ 8.0 22.2 9.5 7/8" 3/8"

> 28.0 ≤ 44.8 > 8.0 ≤ 12.7 28.6 12.7 1 1/8" 1/2"

> 44.8 ≤ 67.2 > 12.7 ≤ 19.1 28.6 15.9 1 1/8" 5/8"

> 67.2 ≤ 100.8 > 19.1 ≤ 28.7 34.9 19.1 1 3/8" 3/4"

> 100.8 ≤ 151.2 > 28.7 ≤ 43.0 41.3 19.1 1 5/8"

> 151.2 ≤ 173.6 > 43.0 ≤ 49.4 41.3 22.2 1 5/8" 7/8"

> 173.6 ≤ 201.6 > 49.4 ≤ 57.3 41.3 22.2 1 5/8" 7/8"

> 201.6 ≤ 257.6 > 57.3 ≤ 73.3 44.5 28.6 1 3/4" 1 1/8"

> 257.6 - > 73.3 - 54 28.6 2 1/8" 1 1/8"

IMPORTANT NOTE :

Pipe sizes from first branch onwards to IDUs "BL" are given in the above table.

While sizing "BL" remember to cross - check with the sizes of "ML" (ODU to first branch) as well,
The below rule may be applied:

When ODU capacity < IDU capacity, Size the pipe as per ODU capacity.
i.e. = Size of "ML"
When ODU capacity = IDU capacity, Size the pipe as per ODU capacity.
i.e. = Size of "ML"
When ODU capacity > IDU capacity, Size the pipe as per IDU capacity.
i.e. = Size of "ML"

Page 5
VRF V PLUS ODU Cable Size Cable Size
Sr. No MCB Rating
Model (Copper) (Aluminium)
1 7 HP 4 6 32
2 8 HP 4 6 32
3 10 HP 6 10 40
4 12HP 6 10 40
5 14HP 6 10 40
6 16 HP 10 16 50
7 18 HP 16 25 63
8 20 HP 16 25 63
9 22 HP 16 25 63
10 24 HP 16 25 63
11 26 HP 25 35 80
12 28 HP 25 35 80